Plan Review Details - Project Z21030020
Plan Review Stops For Project Z21030020
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 07-26-2021 Cont ID  
Sent By rrossano Date 07-26-2021 Time   Rev Time 0.00
Received By rrossano Date 07-26-2021 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 07-06-2021 Cont ID  
Sent By rrossano Date 07-06-2021 Time   Rev Time 0.00
Received By rrossano Date 07-06-2021 Time   Sent To  
Notes
2021-07-06 18:39:19-UTILITY PLAN SAYS HOTEL HAS A RESTAURANT. IS THERE A
 GREASE TRAP/INTERCEPTOR PROPOSED?
  
 -LOOKS TO BE SEVERAL TREE CONFLICTS WITH PRIVATE
 UTILITIES: FIRE HYDRANT, SOUTHERN FDC, LIFT STATION
 WATER LINE. ALSO POSSIBLE TREE CONFLICT WITH STRUCTURE
 THAT LOOKS LIKE SIGN MONUMENT NEAR THE WATER METER.
  
 -PLEASE ADD ABOVE-GROUND METER WATER SERVICE STANDARD
 DETAIL REV. SEP2019 TO CIVIL PLANS AND UPDATE
 REFERENCED NUMBERS ON THE BLOWUP DETAIL. WS-3 SHOULD BE
 THE METER AND FIRELINE DCDA SHOULD BE WS-5.
  
 -ADD ?PRIVATE? TO LABEL OF THE FIRE HYDRANT.
  
 -DEMO PLAN SAID FIRE HYDRANTS ARE BEING REMOVED. WILL
 THE PIPES FEEDING THE FIRE HYDRANTS ALSO BE REMOVED?
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 04-06-2021 Cont ID  
Sent By rrossano Date 04-06-2021 Time   Rev Time  
Received By rrossano Date 04-06-2021 Time   Sent To  
Notes
2021-04-06 19:39:19PASSED WITH PROVISO:
  
 I DIDN?T SEE ANY CIVIL PLANS AND IT DIDN?T SHOW ANY OF
 THE AREA NEAR THE WATER METERS. IF THEY ARE NOT
 AFFECTING THOSE, THEN I DON?T HAVE ANY REVIEW COMMENTS.
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status P Date 06-07-2021 Cont ID  
Sent By aburnett Date 06-07-2021 Time 15:33 Rev Time 0.00
Received By aburnett Date 06-07-2021 Time 15:33 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-15-2021 Cont ID  
Sent By rcaranci Date 04-15-2021 Time 11:42 Rev Time 0.00
Received By rcaranci Date 04-15-2021 Time 11:42 Sent To  
Notes
2021-04-15 11:43:27FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: PALM BEACH RIVERSTONE MINOR PD AMENDMENT
 Z21030020
 APRIL 15, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. REVISE THE SITE PLAN TO SHOW THE DIMENSIONS FOR ALL
 TERMINAL AND INTERIOR LANDSCAPE ISLANDS AS THEY ARE
 SHOWN ON THE APPROVED PLANS. CLOUD ALL CHANGES TO THE
 SITE PLAN.
  
 2. THE TERMINAL LANDSCAPE ISLAND AT THE EAST END OF THE
 ROW OF 4 PARKING SPACES ADJACENT TO THE PARKING GARAGE
 IS NOT DIMENSIONED AND DOES NOT MEET THE 8 FOOT MINIMUM
 LANDSCAPE AREA WIDTH INSIDE CURB. ONE PARKING SPACE MAY
 HAVE TO BE CONVERTED TO LANDSCAPE AREA TO MEET THE
 REQUIREMENT.
  
 3. THE CHANGES TO THE SITE PLAN WILL AFFECT THE
 LANDSCAPE PLAN. SUBMIT A REVISED LANDSCAPE PLAN
 MATCHING THE SITE PLAN CHANGES. CLOUD ALL CHANGES TO
 THE LANDSCAPE PLAN.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 07-02-2021 Cont ID  
Sent By   Date 07-02-2021 Time   Rev Time 0.00
Received By   Date 07-02-2021 Time   Sent To  
Notes
2021-07-02 15:17:10NO FURTHER COMMENTS FROM PUBLIC WORKS.
  
 MATT HEJAZI
 [email protected]
 822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-09-2018 Cont ID  
Sent By   Date 06-09-2021 Time   Rev Time  
Received By   Date 06-09-2021 Time   Sent To  
Notes
2021-06-09 14:57:34PLEASE PROVIDE THE FOLLOWINGS:
 1- AUTOTURN EXHIBIT (DYNAMIC ENVELOPE AND THE VEHICLE
 WHEEL PATH) FOR THE SANITATION SERVICE,
 2- CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF
 SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER)
 3- DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS FOR THE MULTI-FAMILY BULDING.
  
 *PLEASE NOTE SANITATION SERVICE FOR LARGE SIZE
 CONTAINERS (I.E. FOR 8+ CUB YD COMPACTOR, OR ROLL-OFF
 CONTAINER) SHALL BE PROVIDED FROM CITY OF WEST PALM
 BEACH APPROVED VENDORS. PLEASE CONTACT DEPARTMENT OF
 PUBLIC WORKS FOR THE LIST OF APPROVED VENDORS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 3 Status P Date 08-03-2021 Cont ID  
Sent By tward Date 08-03-2021 Time 15:19 Rev Time 0.00
Received By tward Date 08-03-2021 Time 15:35 Sent To  
Notes
2021-08-03 15:35:15THE CIVIL PLANS FOR THE 6/25/2021 SUBMITTAL ONLY SHOWS
 ONE SHEET WITH A NOTE IN THE REVISION BLOCK: SHEET C-07
 - REV. 'A', DATED 3/17/21, "REVISED FDC LOCATION".
  
 THE CIVIL PLANS FOR THE 7/26/2021 SUBMITTAL ONLY
 INCLUDED THE SHEETS C-03, C-04, C-06, C-07 AND C-10.
 ONLY SHEET C-07 HAD A REVISION NOTE AS LISTED ABOVE.
 THE RESPONSE NARRATIVE INCLUDED IN THIS SUBMITTAL
 INDICATED: THE ARCHITECTURAL BACKGROUND WAS CHANGED FOR
 SHEETS C-03, C-04, C-06 AND C-07; REVISIONS MADE TO
 SHEET C-07 DUE TO PRIOR ENGINEERING COMMENTS; AND A
 CITY STANDARD DETAIL ADDED TO SHEET C-10.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 (O) 561-494-1120
 (M) 561-351-0510

Review Stop STORM STORMWATER
Rev No 2 Status P Date 08-03-2021 Cont ID  
Sent By tward Date 08-03-2021 Time 15:16 Rev Time 0.00
Received By tward Date 08-03-2021 Time 15:18 Sent To  
Notes
2021-08-03 15:18:32THE 5/25/2021 SUBMITTAL DID NOT INCLUDE ANY CIVIL PLANS
 TO REVIEW.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 (O) 561-494-1120
 (M) 561-351-0510

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 06-02-2021 Cont ID  
Sent By vnoel Date 06-02-2021 Time 06:59 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date 06-01-2021 Cont ID  
Sent By   Date 06-01-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-06-01 17:42:25PASSED WITH THE FOLLOWING CONDITIONS (FROM PREVIOUS
 APPROVAL):
  
 1. PROVIDE REVISED COUNTY TPS LETTER REFLECTING THE
 LATEST INTENSITIES.
 2. DEVELOPMENT ON THESE PARCELS TOTALING 11.61 ACRES
 SHALL BE RESTRICTED TO GENERATE NO MORE THAN 10,677
 WEEKDAY DAILY EXTERNAL TRIPS OR 331 WEEKDAY AM PEAK
 HOUR EXTERNAL TRIPS OR 1,003 WEEKDAY PM PEAK HOUR
 EXTERNAL TRIPS, OR AS REVISED, WHEN EVALUATED USING THE
 LATEST PALM BEACH COUNTY TRIP GENERATION RATES PER THE
 FLU AMENDMENT TRAFFIC ANALYSIS.
 3. PROVIDE TRANSPORTATION DEMAND MANAGEMENT (TDM)
 MEASURES INCLUDING THE FOLLOWING AND PROVIDE YEARLY
 USAGE SUMMARY OF THESE TDM MEASURES TO THE CITY:
 3A. SHORT AND LONG TERM BICYCLE STORAGE AREAS
 3B. ELECTRIC VEHICLE CHARGING STATIONS
 3C. BIKE/MOPED/ELECTRIC BIKE/ MICROMOBILITY SHARING
 AREA
 3D. RESERVED CARPOOL AND VANPOOL SPACES
 4. CONTRIBUTE FUNDING TOWARDS A CORRIDOR STUDY ON 45TH
 STREET BETWEEN MILITARY TRAIL AND BROADWAY TO IDENTIFY
 LONG-TERM STRATEGIES TO IMPROVE THE SAFETY AND MOBILITY
 OF ALL MODES OF TRANSPORTATION.
 5. PROVIDE SHUTTLE SERVICE BETWEEN HOTEL AND TRI-RAIL
 MANGONIA STATION FOR BOTH PATRON AND EMPLOYEES.
 CONSIDER POTENTIALLY EXTENDING THE SERVICE TO
 RESIDENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 08-03-2021 Cont ID  
Sent By llouie Date 08-03-2021 Time   Rev Time 0.00
Received By llouie Date 08-03-2021 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 06-09-2021 Cont ID  
Sent By llouie Date 06-09-2021 Time   Rev Time 0.00
Received By llouie Date 06-09-2021 Time   Sent To  
Notes
2021-06-09 14:29:36GENERAL COMMENTS:
  
 1.) ALL PROPOSED CHANGES SHALL BE IDENTIFIED IN THE
 JUSTIFICATION STATEMENT. [4/9/2021 REPEAT COMMENT: NO
 REVISED JUSTIFICATION STATEMENT FOUND IN THE
 RESUBMITTAL PACKAGE.]
  
 2.) PLEASE CONFIRM THAT THE PROPOSED CHANGES TO THE
 SITE WILL NOT IMPACT THE APPROVED CIVIL PLANS, AS NO
 CIVIL PLANS HAVE BEEN SUBMITTED, AND REPEATED REQUESTS
 WERE MADE TO THE APPLICANT TO CONFIRM. WILL NEED
 STATEMENT FOR THE FILE.
  
  
 PLANS AND EXHIBIT:
  
 (THE FOLLOWING COMMENTS ARE REPEAT COMMENTS BUT HAVE
 BEEN MODIFIED BASED ON STAFF?S REVIEW OF THE 5/25/2021
 RESUBMITTAL PACKAGE):
  
 1.) THE PLANS AND EXHIBIT ARE NOT CONSISTENT WHICH HAS
 CREATED A LOT OF CONFUSION WITH THE PROPOSED CHANGES
 FOR THE MINOR AMENDMENT. ALL PLANS MUST MATCH. ADDRESS
 FOR CONSISTENCY.
  
 2.) CONFLICTING INFORMATION PROVIDED FOR THE EAST
 (REAR) SETBACK IN THE PLANS AND TABULAR. ADDRESS FOR
 CONSISTENCY.
  
 3.) NORTH (SIDE) SETBACK SEEMS TO HAVE CHANGED TO
 190?-0?; HOWEVER, THE OLD SETBACK OF 193?-5? IS STILL
 NOTED IN THE PLAN SHEETS.
  
 4.) SURFACE PARKING LAYOUT FOR POD 3 IS INCONSISTENT IN
 THE PLAN SHEETS. LAYOUT MUST MATCH IN ALL SHEETS.
 ADDRESS FOR CONSISTENCY.
  
 5.) CHECK PARKING CALCULATIONS FOR POD 3. NUMBERS
 PROVIDED IN THE PLAN SHEETS (INCLUDING EXHIBIT
 HIGHLIGHTING CHANGES) DO NOT MATCH THE NUMBERS PROVIDED
 IN THE PARKING CALCULATIONS TABULAR. ADDRESS FOR
 CONSISTENCY.
  
 6.) PROPOSED CHANGES TO THE LOADING AREA OF POD 3 IS
 NOT REFLECTED IN THE PLAN SHEETS. ADDRESS FOR
 CONSISTENCY. ALSO MAKE SURE THAT THE LOADING AREA HAS
 UNOBSTRUCTED ACCESS TO THE LOADING ZONE.
  
 7.) RELOCATE THE UNIT MIX BREAKDOWN TABULAR SO THAT
 STAFF SEE ENTIRE BUILDING FOOTPRINT AND VERIFY THE
 CLOSEST SETBACK DISTANCE ALONG THE EAST (REAR) PROPERTY
 LINE. THE TABULAR SEEMS TO OBSTRUCT THE LOCATION OF THE
 CLOSEST POINT OF THE BUILDING TO THE EAST (REAR)
 PROPERTY LINE THAT WAS DEPICTED IN THE APPROVED SITE
 PLAN.
  
 8.) TO MAINTAIN THE 8 FT. HIGH CONCRETE WALL ALONG THE
 WEST PROPERTY LINE, THE WALL MUST BE SETBACK GREATER
 THAN 5 FT. (AS IT WAS PROVIDED IN THE APPROVED PLAN).
 THE PLANS ARE INCONSISTENT AND SHOW THE WALL IN VARIOUS
 LOCATIONS ALONG THE WEST PROPERTY LINE. ADDRESS FOR
 CONSISTENCY.
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * ALL REVISION DATES SHALL BE INCLUDED IN THE MODIFIED
 SHEETS FOR TRACKING PURPOSES. FAILURE TO PROVIDE THE
 REVISION DATE WILL RESULT IN A ?FAIL? IN THE SYSTEM.
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDED A MINIMUM OF FOUR
 (4) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($60.00 WHICH WILL BE DUE WITH THE NEXT RESUBMITTAL.)
  

Review Stop Z ZONING
Rev No 1 Status F Date 04-09-2021 Cont ID  
Sent By llouie Date 04-09-2021 Time   Rev Time  
Received By llouie Date 04-09-2021 Time   Sent To  
Notes
2021-04-09 13:47:42GENERAL COMMENTS:
  
 1.) AN INSUFFICIENT NUMBER OF HARDCOPY SETS HAD BEEN
 PROVIDED WITH THE ORIGINAL SUBMITTAL. PLEASE BE SURE TO
 PROVIDE THE MINIMUM NUMBER OF SETS REQUIRED FOR
 RESUBMITTAL (SEE INSTRUCTIONS FOR RESUBMITTAL).
  
 2.) THERE WAS AN ISSUE WITH THE PRINTING OF THE HARD
 COPY SET THAT WAS SUBMITTED. PLEASE CHECK TO MAKE SURE
 THE PLANS ARE LEGIBLE.
  
 3.) THE APPROVED AND THE PROPOSED BUILDING CALCULATIONS
 DO NOT ADD UP. IT WAS THE UNDERSTANDING OF STAFF THAT
 THE BUILDING SQUARE FOOTAGE FOR THE RESIDENTIAL
 BUILDING WOULD NOT BE CHANGING IN THE ZOOM CALL FOR THE
 PROPOSED AMENDMENT BACK IN FEBRUARY. THERE SEEMS TO BE
 ADDITIONAL BUILDING SQUARE FOOTAGE FROM THE APPROVED
 PLAN. PLEASE CLARIFY. ALSO NOTE THAT AS DISCUSSED IN
 THE ZOOM CALL FOR THE PROPOSED AMENDMENT BACK IN
 FEBRUARY, THAT ANY BUILDING ADDITION GREATER THAN 5%
 WOULD REQUIRE A MAJOR AMENDMENT TO THE PD.
  
 4.) AN AMENDMENT TO THE MASTER DEVELOPMENT PLAN (SHEET
 MDP-1) AND THE OVERALL SITE PLAN (SHEET OSP-1) IS
 REQUIRED AS PART OF THIS AMENDMENT SINCE THE DATA
 CALCULATIONS HAVE CHANGED.
  
 5.) ALL PROPOSED CHANGES SHALL BE IDENTIFIED IN THE
 JUSTIFICATION STATEMENT. CHANGES NOT PROVIDED IN THE
 JUSTIFICATION STATEMENT INCLUDE PERVIOUS/IMPERVIOUS
 SURFACE AREA, RELOCATION OF 8 FT. HIGH CONCRETE WALL,
 ADJUSTMENTS MADE TO THE LANDSCAPE ISLANDS, ETC. (JUST
 TO NAME A FEW.).
  
 6.) ALL REVISION DATES SHALL BE INCLUDED IN THE
 MODIFIED SHEETS FROM THE APPROVED PLANS FOR TRACKING
 PURPOSES. FAILURE TO PROVIDE THE REVISION DATE WILL
 RESULT IN A "FAIL" IN THE SYSTEM.
  
  
  
 SITE DATA/AREAS EXHIBITS (SHEET SD-1):
  
 1.) PLEASE ADDRESS THE FOLLOWING IN THE OVERALL
 DEVELOPMENT SITE DATA TABULAR: A) EXISTING FLU IS NO
 LONGER COMMERCIAL (C). PLEASE CORRECT TO COMMERCIAL
 EAST (CE). B) EXISTING ZONING IS NO LONGER GENERAL
 COMMERCIAL (GC). PLEASE CORRECT TO COMMERCIAL PLANNED
 DEVELOPMENT (CPD) WITH UNDERLYING GC. C) THE
 CALCULATIONS PROVIDED FOR POD 3 IN THE CONCURRENCY
 SUMMARY TABLE DOES NOT ADD UP. PLEASE ADDRESS OR
 CLARIFY.
  
 2.) PLEASE ADDRESS THE FOLLOWING IN THE LAND USE AND
 ZONING INFORMATION AND NOTES FOR POD 3 (LOT 2 PER PLAT)
 TABLE: CHECK CALCULATIONS FOR FAR, LOT AREA, BUILDING,
 IMPERVIOUS AND PERVIOUS SURFACE AREA. THE NUMBERS DON?T
 SEEM TO ADD UP AND MUST BE ADDRESSED FOR CONSISTENCY.
  
  
  
 SITE PLAN COMMENTS (SHEET SP-1):
  
 1.) THE DATA CALCULATIONS ARE MISSING FROM THE "CLEAN"
 SITE PLAN ENLARGEMENT FOR THE RESIDENTIAL PARCEL (SHEET
 SP-1). PLEASE PROVIDE.
  
 2.) IN ORDER TO PROVIDE AN 8 FT. HIGH CONCRETE WALL
 ALONG THE WEST PROPERTY LINE (FRONT), THE WALL SHALL BE
 SETBACK MORE THAN 5 FT. FROM THE PROPERTY LINE;
 OTHERWISE, THE HEIGHT OF THE WALL CANNOT EXCEED 4 FT.
 IN HEIGHT (WITHIN THE FRONT SETBACK). ACCORDING TO THE
 PROPOSED MODIFICATIONS TO THE PROJECT, THE WALL HAS
 BEEN MOVED AND NOW DOES NOT MEET THE WALL HEIGHT
 REQUIREMENTS OF THE ZLDRS WITHIN THE FRONT SETBACK.
  
 3.) THE WIDTH OF THE INGRESS/EGRESS TO THE STRUCTURED
 PARKING GARAGE SEEMS TO HAVE BEEN REDUCED FROM 24 FT.
 TO 20 FT. WRITTEN CONFIRMATION FROM THE CITY?S TRAFFIC
 ENGINEERING SHALL BE PROVIDED STATING THAT THERE ARE NO
 ISSUES WITH THE WIDTH OF THE INGRESS/EGRESS.
  
 4.) ADDRESS THE FOLLOWING COMMENTS AS IT RELATES TO THE
 NOTES AND LABELS FOR SHEET SP-1: A) SURFACE PARKING
 CALCULATIONS HAVE CHANGED; 86 PARKING SPACES SEEMS TO
 BE THE INCORRECT NUMBER OF SURFACES PARKING SPACES
 PROVIDED. B) SHOW THE SETBACK DIMENSION OF THE PROPOSED
 MONUMENT SIGN TO THE PROPERTY LINE FOR CONSISTENCY WITH
 THE APPROVED PLANS AND TO VERIFY THAT NO CHANGES HAVE
 BEEN MADE TO THE SETBACK OF THE MONUMENT SIGN. C)
 DIMENSIONS REQUIRED FOR THE LOADING ZONE FOR
 CONSISTENCY WITH THE ZLDRS. D) FLOATING NOTES FOR:
 PRIVATE PATIOS, 12' FPL EASEMENT, 16'-6" VERT.
 CLEARANCE UNDER ENTRY CANOPY. E) REAR (EAST) SETBACK
 SEEMS TO BE MISLABELED AT 23'-10". A DIMENSION HAS BEEN
 PROVIDED THAT SHOWS THE EAST SETBACK AT 23'-9". PLEASE
 ADDRESS FOR CONSISTENCY.
  
  
  
 ARCHITECTURAL DRAWINGS:
  
 1.) FULL ARCHITECTURAL FLOOR PLANS SHALL BE REQUIRED
 FOR EACH LEVEL TO COMPLETE THE ARCHITECTURAL SET AS
 PART OF THE AMENDMENT TO THE APPROVED PLANS.
  
 2.) SIGNAGE HAS BEEN DETECTED ON THE ELEVATIONAL
 DRAWINGS. PLEASE PROVIDE THE FOLLOWING NOTES IN THE
 PLAN: ALL WALL SIGNAGE SHALL COMPLY WITH ARTICLE XIII,
 SIGN REGULATIONS OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. THE COMPLIANCE NOTE HAS REMOVED IN THE
 PROPOSED PLANS.
  
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($60.00).