Plan Review Details - Project Z21010025
Plan Review Stops For Project Z21010025
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 02-05-2021 Cont ID  
Sent By scwelter Date 02-05-2021 Time 15:51 Rev Time 0.00
Received By rthermid Date 02-05-2021 Time 15:50 Sent To  
Notes
2021-02-05 15:58:101% IN PRIVATE DEVELOPMENT. ALL PRIVATE DEVELOPMENT
 PROJECTS, INCLUDING NEW CONSTRUCTION, OR THE RENOVATION
 OR IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 ALL BUILDINGS WITHIN NEW PLANNED DEVELOPMENTS SHALL BE
 ASSESSED CUMULATIVELY TOWARDS THIS PUBLIC ART
 REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED
 SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF
 THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW
 CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS.
 DEVELOPER MUST SELECT ONE OF THE FOLLOWING OPTIONS:
 (1) OPTION 1: INSTALL AND ARTWORK ON THE DEVELOPMENT
 SITE VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF
 THE TOTAL CONSTRUCTION COSTS; OR
 (2) OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT
 OF ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR
 DEPOSIT TO THE PUBLIC ART ACCOUNT.
 PLEASE CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC
 ART AND CULTURE AT [email protected]
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 02-11-2021 Cont ID  
Sent By rbrown Date 02-10-2021 Time 20:42 Rev Time 0.00
Received By rbrown Date 02-10-2021 Time 20:42 Sent To  
Notes
2021-02-10 20:44:57DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 5. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION
 OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING,
 CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT
 (561) 805 6659, OR BY EMAIL: [email protected]
  
 8. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 9. ACCESSIBLE ROUTE FROM SIDEWALK TO BUILDING ENTRANCE.
 THE ACCISSIBLE ROUTE AND PARKING SPACES SHALL BE
 LOCATED/CONFIGURED SO THAT THE USER IS NOT COMPELLED TO
 WALK OR WHEEL BEHIND PARKED VEHICLES OR IN THE TRAVEL
 LANE. SECTIONS 206.2, 402.2 AND 502.3 OF FLORIDA
 ACCESSIBILITY CODE
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 04-27-2021 Cont ID  
Sent By rrossano Date 04-27-2021 Time   Rev Time 0.00
Received By rrossano Date 04-27-2021 Time   Sent To  
Notes
2021-04-27 10:55:49COMMENTS PER RICK ROSSANO, PROJ. COORD. WPB ENG.
 SERVICES, [email protected], 561-494-1098:
 1. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER
 (CONDITION OF SITE PLAN APPROVAL). STORMWATER APPEARS
 TO BE ONSITE ONLY; IF SO, NO CCTV OF CITY STORMWATER
 INFRASTRUCTURE ALONG PROJECT FRONTAGE IS NEEDED.)
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE SPV.,
 CITY OF WPB PUB. UTILITIES, 561-822-2262,
 [email protected]
 -BACKFLOW ASSEMBLY MAY NOT BE LOCATED IN A UTILITY
 EASEMENT. ONE WAY TO RESOLVE WOULD BE ADJUSTING
 BOUNDARIES/DIMENSIONS OF PROPOSED UTILITY EASEMENT.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 02-04-2021 Cont ID  
Sent By RROSSANO Date 02-04-2021 Time   Rev Time  
Received By rrossano Date 02-04-2021 Time   Sent To  
Notes
2021-02-04 11:43:23COMMENTS PER RICK ROSSANO, PROJ. COORD. WPB ENG.
 SERVICES, [email protected], 561-494-1098:
 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 4. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 STORMWATER PIPES ALONG ENTIRE PROJECT FRONTAGE.
 5. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 6. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 7. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW
 PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER,
 STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND
 OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL
 AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW.
 DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY,
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 8. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP
 UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY
 LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY.
 9. FOR FORMAL ENGINEERING SUBMITTAL , PROVIDE DEDICATED
 UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS.
 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER
 METER AND BACKFLOW PREVENTION.
 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT
 DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW
 PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL
 BACKFLOWS.
 12. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES
 OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 16. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY
 ELEVATIONS AT MANHOLE TIE-IN.
 17. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY LINES
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER LINES
 ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL
 ADDRESSES.
 19. FOR FORMAL ENGINEERING SUBMITTAL, WHEN TRENCHING IN
 IN CITY MAINTAINED ROADWAY AREAS ADD NOTE TO PROVIDE 50
 FT. PAVEMENT RESTORATION TRANSITION ON EACH SIDE OF
 PROPOSED TRENCH PER CITY OF WPB STANDARD DETAIL GC-4.
 20. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
  
 COMMENTS FROM MARK HURLEY, FIELD CUSTOMER SERVICE SPV.,
 CITY OF WPB PUB. UTILITIES, 561-822-2262,
 [email protected]
  
 -SITE PLAN SAYS SOUTHERN WALL IS 2INCHES OFF PROPERTY
 LINE. IS THAT CORRECT, AND WOULD BUILDING FOOTER BE
 SAME DISTANCE FROM PROPERTY LINE?
  
 -PLEASE VERIFY BUILDING WILL NOT HAVE FIRE SPRINKLERS.
  
 -WILL A SEPARATE METERED IRRIGATION WATER SERVICE BE
 NEEDED?
  
 -PLANS SAID THERE MAY BE A TENANT, BUT ONLY SHOWING ONE
 WATER METER ON WATER PLANS. WILL THE WATER ACCOUNT
 HOLDER LET THE TENANT USE THEIR WATER?
  
 -WATER DEMAND CALCULATIONS ARE MISSING FROM WATER PLAN.
 PLEASE ADD.
  
 -PLEASE VERIFY PAVEMENT RESTORATION AREA BOUNDARIES
 FROM UTILITY WORK ARE CORRECT DIMENSIONS.
  
 -UTILITY EASEMENT NEEDED FOR WATER METER BOX ON PRIVATE
 PROPERTY.
  
 -WATER SERVICE STANDARD DETAILS ARE OLD REVISION.
 PLEASE REPLACE WITH NEWEST REVISION.
  
 -USUALLY 5/8? METER HAS 1? TAP. PLEASE UPDATE OR
 INDICATE WHY 2? TAP IS NEEDED.
  
 -FOR FORMAL ENGINEERING SUBMITTAL, PLEASE ADD WATER
 SERVICE PIPE SIZE AND MATERIAL TYPE.
  
 -WPB GIS IS SHOWING A 4INCH WATER MAIN BRANCH IN CLOSE
 PROXIMITY TO THE WATER SERVICE TAP. PLEASE SHOW THAT ON
 WATER PLAN FOR FORMAL ENGINEERING SUBMITTAL.
  
 -THERE SHOULD BE A FIRE HYDRANT ACROSS FROM THE
 NORTHEAST CORNER OF THE PROPERTY. PLEASE SHOW ON THE
 WATER PLAN.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-05-2021 Cont ID  
Sent By pleduc Date 02-05-2021 Time 12:41 Rev Time 0.00
Received By pleduc Date 02-05-2021 Time 12:36 Sent To  
Notes
2021-02-05 12:36:39THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT. THE FOLLOWING COMMENTS ARE INTENDED
 TO PROVIDE GUIDANCE FOR BUILDING PLAN SUBMITTAL.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 7TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND IF APPLICABLE CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT.
  
 9A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND
 SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL,
 THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND
 THE CITY'S PLANNING AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 05-03-2021 Cont ID  
Sent By rcaranci Date 05-03-2021 Time 16:39 Rev Time 0.00
Received By rcaranci Date 05-03-2021 Time 16:39 Sent To  
Notes
2021-05-03 16:40:25FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 6907 NORTON AVE Z21010025
 MAY 3, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE THE REQUIRED TERMINAL LANDSCAPE
 ISLAND WITH 8 FEET LANDSCAPE WIDTH AT THE WEST END OF
 THE NORTH ROW OF PARKING.
 ALLOWED PER 94-443(C)(3) FOR LESS THAN 12 SPACES.
  
 2. SATISFIED. PROVIDE THE REQUIRED 5 FOOT LANDSCAPE
 BUFFER FOR THE NORTH, WEST AND PORTIONS OF THE SOUTH
 BUFFER THAT ARE NOT COVERED BY THE PROPOSED BUILDING AT
 ZERO SETBACK. THE ZERO SETBACK IS ONLY POSSIBLE WHERE
 THE ADJACENT BUILDING TO THE SOUTH IS AT ZERO SETBACK.
 SHOW THE LENGTH OF ALL FOUR BUFFER SECTIONS AND SHOW
 THE REQUIRED AND PROVIDED TREES FOR EACH 30 FEET OR
 PORTION THEREOF.
  
 3. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS.
 SHADE TREES ARE PROVIDED IN THE BUFFER.
  
 4. SATISFIED. THE PARKING SPACES APPEAR TO BE 18 FEET
 IN LENGTH WITH A WHEEL STOP AT 16 FEET. STAFF SUGGESTS
 REDUCING THE PAVED AREAS FOR PARKING SPACES AND PLACING
 THE CURBS AT 16 FEET TO ALLOW FOR ADDITIONAL PERVIOUS
 LANDSCAPE AREA AT THE OVERHANG.
  
 5. SATISFIED. PROVIDE THE REQUIRED 50 POINTS FORM THE
 FLORIDA FRIENDLY DESIGN OPTIONS LIST.
  
 6. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT
 BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 02-10-2021 Cont ID  
Sent By rcaranci Date 02-10-2021 Time 17:14 Rev Time 0.00
Received By rcaranci Date 02-10-2021 Time 17:14 Sent To  
Notes
2021-02-10 17:14:34FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 6907 NORTON AVE Z21010025
 FEBRUARY 10, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE THE REQUIRED TERMINAL LANDSCAPE ISLAND WITH
 8 FEET LANDSCAPE WIDTH AT THE WEST END OF THE NORTH ROW
 OF PARKING.
  
 2. PROVIDE THE REQUIRED 5 FOOT LANDSCAPE BUFFER FOR THE
 NORTH, WEST AND PORTIONS OF THE SOUTH BUFFER THAT ARE
 NOT COVERED BY THE PROPOSED BUILDING AT ZERO SETBACK.
 THE ZERO SETBACK IS ONLY POSSIBLE WHERE THE ADJACENT
 BUILDING TO THE SOUTH IS AT ZERO SETBACK. SHOW THE
 LENGTH OF ALL FOUR BUFFER SECTIONS AND SHOW THE
 REQUIRED AND PROVIDED TREES FOR EACH 30 FEET OR PORTION
 THEREOF.
  
 3. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL
 AND INTERIOR ISLANDS.
 4. THE PARKING SPACES APPEAR TO BE 18 FEET IN LENGTH
 WITH A WHEEL STOP AT 16 FEET. STAFF SUGGESTS REDUCING
 THE PAVED AREAS FOR PARKING SPACES AND PLACING THE
 CURBS AT 16 FEET TO ALLOW FOR ADDITIONAL PERVIOUS
 LANDSCAPE AREA AT THE OVERHANG.
  
 5. PROVIDE THE REQUIRED 50 POINTS FORM THE FLORIDA
 FRIENDLY DESIGN OPTIONS LIST.
  
 6. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO
 SEPARATE LANDSCAPING FROM UTILITY LINES.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 06-08-2021 Cont ID  
Sent By   Date 06-08-2021 Time   Rev Time 0.00
Received By   Date 06-08-2021 Time   Sent To  
Notes
2021-06-08 15:32:13CONDITION OF APPROVAL:
 THE DUMPSTER SHALL BE ON WHEEL AND BE ROLLED OUT ON THE
 SERVICE DAYS FOR SERVICE ON NORTON AVE.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 02-08-2021 Cont ID  
Sent By   Date 02-08-2021 Time   Rev Time  
Received By   Date 02-08-2021 Time   Sent To  
Notes
2021-02-08 12:46:18PLEASE PROVIDE THE DUMPSTER ENCLOSURE DETAIL. FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status P Date 06-08-2021 Cont ID  
Sent By tward Date 06-08-2021 Time 23:13 Rev Time 0.00
Received By tward Date 06-08-2021 Time 23:35 Sent To  
Notes
2021-06-08 23:35:35THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE APRIL
 27, 2021 SUBMITTAL, THEY CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL.
  
 1. REVISE EXFILTRATION TRENCH DESIGN AND STORMWATER
 MANAGEMENT CALCULATIONS TO ACCOUNT FOR THE CHANGE IN
 THE INLET GRATE ELEVATION TO 14.08 FT NAVD.
  
 2. PROVIDE VERTICAL DATUM REFERENCE IN THE STORMWATER
 MANAGEMENT CALCULATIONS.
  
 3. PROVIDE ON THE CIVIL ENGINEERING PLANS THE GRATE/RIM
 AND INVERT ELEVATIONS OF THE EXISTING SANITARY SEWER
 AND STORMWATER STRUCTURES.
  
 4.PROVIDE SWALES ALONG THE NORTH AND SOUTH PROPERTY
 LINES THAT DRAIN TOWARD NORTON AVE TO PREVENT RUNOFF
 FROM FLOWNG ONTO ADJACENT PROPERTIES.
  
 5. CROSS SECTIONS WILL BE NEEDED WITH THE ENGINEERING
 PERMIT SUBMITTAL THROUGH THE MIDDLE OF THE DRIVEWAY
 (EAST-WEST) AND THROUGH THE PARKING LOT FROM NORTH PL
 TO SOUTH PL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)

Review Stop STORM STORMWATER
Rev No 1 Status F Date 02-11-2021 Cont ID  
Sent By tward Date 02-11-2021 Time 18:55 Rev Time 0.00
Received By tward Date 02-11-2021 Time 18:57 Sent To  
Notes
2021-02-11 18:57:43THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. CONSIDER REDUCING THE DEPTH OF THE PARKING BY 2 FEET
 AND PROVIDE LANDSCAPE OVERHANG.
  
 2. MOVE S-102 FURTHER FROM THE BACK OF SIDEWALK WITH
 THE GRATE ELEVATION LOWER THAN THE BACK OF SIDEWALK
 ELEVATION TO ENSURE THE STORMWATER RUNOFF IS CAPTURED
 IN THE SYSTEM.
  
 3. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD ERP
 CRITERIA.
  
 4. REPLACE SIDEWALK ADJACENT TO THE DRIVEWAY APRON WITH
 6? THICK SIDEWALK PER CITY DETAILS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 4. DRAINAGE CALCULATIONS WILL BE REVIEWED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 05-06-2021 Cont ID  
Sent By vnoel Date 05-06-2021 Time 07:12 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2021-05-06 07:13:20CONDITION OF APPROVAL:
  
 1. UNITY OF TITLE PRIOR TO BUILDING PERMIT.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 02-08-2021 Cont ID  
Sent By vnoel Date 02-08-2021 Time 09:40 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2021-02-08 09:52:051. SHOW CONVERSION TO NGVD.
 2. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date 06-08-2021 Cont ID  
Sent By   Date 06-08-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-06-08 15:16:36NO FURTHER COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 05-03-2021 Cont ID  
Sent By   Date 05-03-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-05-03 18:28:04TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 02-10-2021 Cont ID  
Sent By   Date 02-10-2021 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2021-02-10 21:10:21TRAFFIC COMMENTS
 1) PROVIDE COUNTY TPS LETTER
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 05-21-2021 Cont ID  
Sent By rthermid Date 05-14-2021 Time   Rev Time 0.00
Received By rthermid Date   Time   Sent To  
Notes
2021-05-21 08:26:07PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 5/14/2021
 PROJECT NO.: Z21010025
 CASE NO.: ISPR 21-02
 ________________________________________
  
 1. SATISFIED: PURSUANT TO SECTION 94-485 (Q) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS),
 ONE BICYCLE PARKING SPACE SHALL BE PROVIDED FOR EVERY
 20 AUTOMOBILE PARKING SPACES OR FRACTION THEREOF,
 REQUIRED FOR THE USE.
 2. SATISFIED: PURSUANT TO SECTION 94-443 OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS), A
 LANDSCAPE BUFFER OF AT LEAST 5 FEET IN WIDTH SHALL BE
 PROVIDED WHEN ADJACENT TO NON RESIDENTIAL ZONING
 DISTRICTS. PLEASE PROVIDE A 5 FOOT SIDE SETBACK ON THE
 SOUTHERN PORTION OF THE PROPERTY, ADJACENT TO THE
 PARKING LOT.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG

Review Stop Z ZONING
Rev No 1 Status F Date 02-11-2021 Cont ID  
Sent By rthermid Date 02-11-2021 Time   Rev Time  
Received By rthermid Date 02-11-2021 Time   Sent To  
Notes
2021-02-11 09:55:25PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ________________________________________
  
 DATE OF REVIEW: 2/11/2021
 PROJECT NO.: Z21010025
 CASE NO.: ISPR 21-02
 ________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-485 (Q) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS (ZLDRS), ONE BICYCLE
 PARKING SPACE SHALL BE PROVIDED FOR EVERY 20 AUTOMOBILE
 PARKING SPACES OR FRACTION THEREOF, REQUIRED FOR THE
 USE.
 2. PURSUANT TO SECTION 94-443 OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), A LANDSCAPE
 BUFFER OF AT LEAST 5 FEET IN WIDTH SHALL BE PROVIDED
 WHEN ADJACENT TO NON RESIDENTIAL ZONING DISTRICTS.
 PLEASE PROVIDE A 5 FOOT SIDE SETBACK ON THE SOUTHERN
 PORTION OF THE PROPERTY, ADJACENT TO THE PARKING LOT.
 ________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 4 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) IN ORDER TO BE CONSIDERED FOR THE APRIL 9, 2021,
 PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE
 SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED
 DOCUMENTS/PLANS NO LATER THAN TUESDAY, MARCH 9, 2021.
  
 G) TO BE PLACED ON THE JUNE 15, 2021, PLANNING BOARD
 AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO LATER
 THAN MARCH 9, 2021. SIGNAGE SHALL CONFORM, AND BE
 INSTALLED ACCORDING TO THE REQUIREMENTS OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS; SUCH
 REQUIREMENTS ARE ALSO PROVIDED IN THE DEVELOPMENT
 APPLICATION. A SIGNED AND NOTARIZED AFFIDAVIT SHALL BE
 PROVIDED BY THE DEADLINE REFERENCED ABOVE.
  
 H) IF AFTER THE CASE HAS BEEN ADVERTISED THE APPLICANT
 DESIRES TO REQUEST A CONTINUANCE, A FEE OF $50 PLUS THE
 COST OF ADVERTISING WILL BE CHARGED.
 ________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 TTY: 800.955.8771
 E: [email protected]
 W: WPB.ORG

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved