Plan Review Details - Project Z20100020
| Plan Review Stops For Project Z20100020 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
12-09-2020 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
12-09-2020 |
Time |
20:30 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
12-09-2020 |
Time |
20:29 |
Sent To |
|
|
| Notes |
| 2020-12-09 20:36:52 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. REMODELING OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 4. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND | | | CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF | | | CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL | | | NEIGHBORING PROPERTIES. | | | | | | 5. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS ASSIGNED BASED ON THE LOCATION | | | OF THE BUILDING ENTRANCE. FOR STREET ADDRESSING, | | | CONTACT CAROLINE PUELL, ADDRESSING COORDINATOR, AT | | | (561) 805 6659, OR BY EMAIL: [email protected] | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
4 |
Status |
P |
Date |
07-14-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-14-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
07-14-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-14 11:56:21 | COMMENTS DATED 7/1/21 MAY BE ADDRESSED DURING FORMAL | | | ENGINEERING SUBMITTAL. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
07-01-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-01-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
07-01-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-01 14:38:26 | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -DEMO PLAN WITH CIVILS SHOWS FPL EASEMENT AND SAYS IT | | | WILL BE ABANDONED AND NEW EASEMENT PROVIDED BUT SURVEY | | | SHOWS NOT EASEMENT. HAS EASEMENT ALREADY BEEN ABANDONED | | | AND WHERE WILL THE NEW EASEMENT BE? | | | | | | -THERE WERE SEVERAL UTILITY POLES THAT HAD CALLOUT | | | NOTES SAYING THEY WERE BEING RELOCATED. DO THE PLANS | | | SHOW THEIR UPDATED LOCATIONS WITH ALL ACCOUNTED FOR? | | | | | | -FUTURE DUMPSTER AREA COULD PRESENT CONFLICT WITH | | | EXISTING SEWER UTILITY. | | | | | | -PRIOR ASKED FOR AREA NEAR EXISTING TAMARIND METER BOX | | | SO IT COULD POSSIBLY BE RELOCATED OUT OF SIDEWALK IN | | | THE FUTURE. PLEASE CALLOUT DIMENSION BETWEEN EXISTING | | | SIDEWALK AND PROPOSED WALL/FENCE ON PLANS. 2 FEET WOULD | | | BE SUFFICIENT. | | | | | | -DID NOT SEE UPDATED LANDSCAPE PLAN SUBMITTED. | | | RECOMMEND APPLICANT CHECK TO MAKE SURE ANY CHANGES IN | | | THIS SUBMITTAL DID NOT CREATE CONFLICT WITH LANDSCAPING | | | PLAN. | | | | | | -IS 5 FOOT SLIDING GATE STILL GOING TO BE NEAR NORTH | | | PROPERTY LINE? IF SO PLEASE PROVIDE MORE INFORMATION | | | AND LABEL IT ON CIVIL PLANS. ALSO WILL IT BE ABLE TO | | | COMPLETELY ENCLOSE THE DRIVEWAY AND PARKING LOT? IF SO, | | | HOW DO VEHICLES GET OUT OF THE ALLEY IF THEY PULL IN | | | WHEN THE GATE IS CLOSED? | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
03-04-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
03-04-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
03-04-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-04 19:26:07 | | | | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -IS 8INCH GV NUMBER 1 ON UTILITY PLAN EXISTING OR | | | PROPOSED? IF PROPOSED, HOW WILL WATER BE SHUT DOWN TO | | | INSTALL THE 8INCH GATE VALVE? | | | | | | -PLEASE LABEL ALL NEW WATER MAIN AND WATER SERVICE | | | PIPING WITH MATERIAL TYPE. | | | | | | -PLEASE LABEL EXISTING 8INCH WATER MAIN WITH PIPE | | | MATERIAL TYPE. | | | | | | -ICON IS MISSING FOR 4INCH GV NUMBER 1. | | | | | | -PRIVATE FIRELINE AND DOMESTIC BACKFLOW ASSEMBLIES MAY | | | NOT BE LOCATED IN THE ROW. MUST BE INSIDE PROPERTY | | | LINE. | | | | | | -PRIVATE FDC MAY NOT BE LOCATED IN THE ROW. | | | | | | -PLEASE LABEL WIRE PULL BOX ON UTILITY PLAN THAT IS | | | LOCATED NEAR THE WATER METER BOX. | | | | | | -PLEASE VERIFY THERE IS EXSAN PIPE RUNNING IN NORTH | | | ALLEY. IF CORRECT, ADD LABEL WITH PIPE SIZE AND IF IT | | | IS PRIVATE OR CITY OWNED. | | | | | | -EXISTING DOMESTIC METER ADJACENT 7TH ST IS 3/4INCH. | | | | | | -FOR FORMAL ENGINEERING SUBMITTAL, PLEASE LABEL NEW | | | WATER SERVICE PIPING FOR DOMESTIC METER WITH PIPE SIZE | | | AND MATERIAL TYPE. | | | | | | COMMENTS FROM SUZANNE BERGLUND, P.E., ENGINEERING | | | MANAGER, CITY OF WEST PALM BEACH, 561-494-1075, | | | [email protected] | | | | | | 1) ENSURE COORDINATION WITH PROPOSED POTABLE WATER AND | | | SANITARY SEWER SERVICES WITH THE TAMARIND AVENUE | | | IMPROVEMENTS PROJECT. (I AM JUST LOOKING FOR | | | ACKNOWLEDGEMENT HERE AND WANT TO PUT THIS ON RECORD) | | | 2) PLEASE COORDINATE WITH LT CLIFFORD HAGAN, | | | [email protected] ON THE EXISTING POLICE INFRASTRUCTURE | | | THAT IS CURRENTLY ON THE PROPERTY. THIS INFRASTRUCTURE | | | MUST REMAIN AND OR APPROVAL TO REMOVE OR RELOCATE | | | EQUIPMENT MUST BE RECEIVED. | | | 3) PLEASE COORDINATE WITH PENNI REDFORD, | | | [email protected], 561-804-4981, ON THE REMOVAL OR | | | RELOCATION OF THE EXISTING SOLAR PANEL EQUIPMENT THAT | | | IS CURRENTLY ON THE PROPERTY. | | | | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
12-03-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
12-03-2020 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
12-03-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-03 08:49:41 | 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. TO VIEW | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AND OTHER | | | ENGINEERING RELATED DOCUMENTS, OPEN A BROWSER IN CHROME | | | AND GO TO: WWW.WPB.ORG/ENGDOCS . TO LOGIN, UNDER | | | ?EMAIL? ENTER [email protected] ; UNDER ?PASSWORD? ENTER | | | SIMPLE321# | | | THERE ARE 4 PAGES OF AVAILABLE ENGINEERING DOCUMENTS | | | FOR YOUR USE. | | | 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH, | | | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED | | | SEPT. 22, 2008. (SUPPLEMENT NO. 18) CHAPTER 90 | | | UTILITIES, ARTICLE I. SEC. 90-7. | | | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE | | | FACILITIES OF THE CITY: | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, OPEN A BROWSER IN CHROME AND GO TO: | | | WWW.WPB.ORG/ENGDOCS .TO LOGIN, UNDER ?EMAIL? ENTER | | | [email protected] ; UNDER ?PASSWORD? ENTER SIMPLE321# | | | CROSS-CONNECTION CONTROL MANUAL IS ON PAGE 4. | | | 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1040 FOR FURTHER | | | ASSISTANCE. | | | 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS | | | OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL | | | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, | | | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL | | | UTILITY CROSSINGS. | | | 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | ROW. | | | 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE | | | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB | | | DEVELOPMENT APPLICATION). | | | 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND | | | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM | | | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE | | | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29). | | | 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND | | | STORMWATER ALONG ENTIRE PROJECT FRONTAGE. | | | 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED | | | AREAS. | | | 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE | | | APPLICABLE. | | | 14. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED | | | LOCATION OF WATER METER AND BACKFLOW PREVENTION. | | | 15. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | 16. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS | | | FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS. | | | 17. COORDINATE WITH TAMARIND AVE. IMPROVEMENT PROJECT; | | | CONTACT SUZANNE BERGLUND PE, CITY OF WPB ENG. MANAGER | | | AT [email protected] OF 561-494-1075. | | | 18. FOR ENGINEERING SUBMITTAL, PROVIDE PROFILE VIEW OF | | | PROPOSED UTILITIES. | | | 19. ALL PROPOSED STRUCTURES AND TREES SHALL MAINTAIN | | | MIN. 5 FT. FROM CITY UTILITIES. | | | | | | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -THE WATER SERVICE STANDARD DETAILS ARE OLD REVISION. | | | PLEASE REPLACE WITH NEWEST REVISION. | | | -PLEASE ADD PAVEMENT RESTORATION STANDARD DETAIL TO | | | CIVIL PLAN SET AND MAKE SURE PAVEMENT RESTORATION AREAS | | | COMPLY WITH THE STANDARDS. | | | -WATER DEMAND CALCULATIONS ARE NOT ON WATER PLAN C5.1. | | | PLEASE ADD TO PLAN. | | | -VERIFY THAT THERE WILL BE NO CONFLICT BETWEEN PROPOSED | | | TREES AND THE WATER SERVICE. IF CONFLICT FOUND, | | | INCREASE DISTANCE AND ADD ROOT BARRIERS. | | | -WILL THE BENCHES AND SOLAR CHARGING STATIONS THAT ARE | | | CURRENTLY LOCATED NEAR THE SE CORNER OF THE PROPERTY BE | | | REMOVED DURING DEMOLITION? | | | -EXISTING IRRIGATION BACKFLOW ASSEMBLY DOES NOT APPEAR | | | TO BE LEAD-FREE COMPLIANT. RECOMMEND REPLACING WITH NEW | | | LEAD-FREE BACKFLOW ASSEMBLY IF WILL BE USING FOR | | | DOMESTIC POTABLE USES. IF REPLACED, BACKFLOW ASSEMBLY | | | WILL NEED TO BE RELOCATED CLOSER TO WATER METER. | | | -EXISTING WATER SERVICE FOR 801 N TAMARIND IS SETUP AS | | | AN IRRIGATION ACCOUNT IN THE UTILITY BILLING SYSTEM. | | | CUSTOMER WOULD NEED TO UPDATE IT WITH UTILITY BILLING. | | | -IF 801 AND 819 TAMARIND WILL REMAIN SEPARATE | | | PROPERTIES WITH THE EXISTING PROPERTY LINES, THEN | | | SUGGEST NOT HAVING FIRELINE WATER SERVICE FOR 801 | | | ENCROACH ONTO 819 PROPERTY LINE. | | | -ON SHEET C5.1, PLEASE RELOCATE 4IN GV #2 AND DCDA | | | EAST, CLOSER TO THE SIDEWALK. GV SHOULD STILL REMAIN | | | OUT OF THE SIDEWALK AND HAVE ?POINT OF SERVICE? ADDED | | | TO LABEL. | | | -DCDA DOES NOT HAVE AN ICON ON THE PLAN AND IS LIKELY | | | BIGGER THAN REPRESENTED. | | | -FOR FORMAL ENGINEERING SUBMITTAL OF WATER PLAN, LABEL | | | THE FIRELINE SERVICE WITH PIPE MATERIAL TYPE AND SIZE. | | | ALSO ADD REFERENCED WS SD # TO DCDA LABEL, AND ADD | | | SIZES TO THE LABELS FOR THE BACKFLOW ASSEMBLY AND WATER | | | METER. | | | -EXISTING WATER METER BOX FOR 819 N TAMARIND NEEDS | | | UTILITY EASEMENT ADDED. EXTEND THIS UE WEST SUCH THAT | | | THE METER BOX CAN BE RELOCATED OUT OF THE SIDEWALK IN | | | THE FUTURE. ALSO ADD UE AROUND INCOMING WATER SERVICE | | | AND 4IN GV#2. | | | -VERIFY THAT DISTANCE BETWEEN FDC AND CLOSEST FIRE | | | HYDRANT IS ACCEPTABLE. DISTANCE MAY NEED TO BE | | | DECREASED. | | | -FUTURE DUMPSTER MAY NOT BE ALLOWED TO RESIDE IN A CITY | | | ALLEY INSTEAD OF ON PRIVATE PROPERTY. RECOMMEND GETTING | | | CONFIRMATION FOR PLANNING PURPOSES. | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
12-02-2020 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
12-02-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
12-02-2020 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2020-12-02 14:36:44 | FIRE HAS NO OBJECTIONS TO THE PROPOSED RELOCATION. | | | | | | SHOULD BUILDING PERMITS BE SUBMITTED, FIRE MAY PROVIDE | | | PLAN REVIEW COMMENTS IF APPLICABLE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
03-23-2021 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
03-23-2021 |
Time |
17:12 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
03-23-2021 |
Time |
17:12 |
Sent To |
|
|
| Notes |
| 2021-03-23 17:12:41 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 801AND 819 N TAMARIND Z20100020 | | | MARCH 23, 2021 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | ? THE RESPONSES TO COMMENTS DROPPED THE NUMBER ON | | | COMMENT#2 ON LANDSCAPE COMMENTS, SO THE REST ARE | | | MIS-NUMBERED. | | | | | | 1. SATISFIED. ON THE TREE DISPOSITION CHART SHOWING THE | | | MANGO TREE TO BE REMOVED, IF THE DIAMETER IS 25 FEET, | | | THE MITIGATION DUE WOULD BE 491 SQ FT. STAFF SUGGESTS | | | SAVING THE TREE AND WORKING IT INTO THE REVISED SITE | | | PLAN WITH THE PARKING AND THE REQUIRED PRIVATE OPEN | | | SPACE. | | | | | | | | | 2. PARTIALLY SATISFIED. PROVIDE THE LOCATION OF THE 12% | | | REQUIRED PRIVATE OPEN SPACE AND IDENTIFY THE TYPE. SHOW | | | THE REQUIREMENTS MET FOR THE TYPE OF OPEN SPACE | | | INCLUDING VEGETATED AREA AND TREE CANOPY COVERAGE | | | REQUIRED. | | | | | | INTERIOR COURTYARD MUST BE SURROUNDED BY WALLS AND | | | CANNOT BE AREAS AROUND THE BUILDING AS SHOWN. OTHER | | | CHOICES FOR NWD -5 ARE ROOFTOP GARDEN TERRACE WHICH ARE | | | NOT POSSIBLE. STAFF SUGGESTS USING THE AREA ON THE | | | NORTH SIDE OF THE BUILDING TO DO EITHER GARDEN OR | | | INTERIOR COURTYARD ENCLOSED BY A WALL AND THE BUILDING. | | | IT MAY NEED SOME OF THE SPACE DESIGNATED FOR FUTURE | | | BUILDING LOCATION. THE AREA CAN BE EXTENDED TOWARD | | | TAMARIND TO THE BUILDING SETBACK LINE. | | | | | | 3. SATISFIED. PROVIDE THE REQUIRED TERMINAL LANDSCAPE | | | ISLAND WITH 8 FEET LANDSCAPE WIDTH AT THE END OF EACH | | | ROW OF PARKING. ALONG THE NORTH BUFFER, THE 5 FEET OF | | | REQUIRED LANDSCAPE BUFFER CAN BE A PART OF THE TERMINAL | | | ISLAND, BUT THE 8 FEET INSIDE CURB MUST BE PROVIDED. | | | THE REQUIRED TREE MUST BE PROVIDED IN ADDITION TO THE | | | BUFFER TREE REQUIREMENT. | | | | | | 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A | | | MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO | | | BE PLANTED WITHIN THE INTERIOR OF AN OFF-STREET PARKING | | | AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE | | | PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE | | | REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION | | | 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS. ONLY | | | THREE TREES ARE SHOWN, BUT THE CHART INDICATES 4. | | | | | | 5. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30 | | | FEET OR PORTION THEREOF ADJACENT TO PARKING AREAS. | | | PROVIDE THE REQUIRED AND PROVIDED BUFFER TREES FOR THE | | | NORTH AND WEST BUFFER. TREE SPECIES AND MATURE HEIGHT | | | MUST MEET FALL ZONE REQUIREMENTS TO BE LESS THAN THE | | | DISTANCE TO THE FIRST TRACKS. | | | | | | 6. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION | | | 94-442(G) TO UTILIZE DROUGHT TOLERANT SPECIES FOR | | | REMAINDER OF REQUIRED TREES AND SHRUBS RATHER THAN THE | | | ADDITIONAL PARKING AREA TREES. | | | | | | 7. SATISFIED. ADD A SECTION IN THE LANDSCAPE DATA CHART | | | TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. PROVIDE | | | THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT TOLERANT | | | PLANTS BASED ON FINAL PLANT LIST. | | | | | | 8. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE | | | LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | INDICATE THAT THE OVERHEAD WIRES AND POLE IN THE ALLEY | | | WILL BE ELIMINATED. | | | | | | 9. PARTIALLY SATISFIED. SHOW LOCATIONS OF ALL PROPOSED | | | WATER, SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | | | | ? LOCATION OF DRAINAGE LINE PREVENTS ANY TREE PLACEMENT | | | ON THE SOUTH SIDE OF BUILDING, LOCATION SHOULD BE | | | CONSIDERED TO ALLOW ROOM FOR TREES. | | | | | | 10. PARTIALLY SATISFIED. PROVIDE A DETAIL AND LOCATIONS | | | OF ROOT BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY | | | LINES. | | | ? LOCATIONS OF ROOT BARRIERS SHOWN DO NOT ALLOW PROPER | | | ROOT SPACE FOR THE SPECIES. ROOT BARRIERS SHOULD BE | | | LOCATED CLOSER TO THE LINES ON PRIVATE UTILITIES. | | | ? THE LOCATION OF WATER LINES AND ROOT BARRIERS | | | ADJACENT TO THE EXISTING MEDJOOL DATE PALM IN THE RIGHT | | | OF WAY ARE NOT ACCEPTABLE. MOVE AWAY FROM ROOT SYSTEM | | | OF PALM. | | | | | | 11. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | | | | 12. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND REDESIGN THE LOCATIONS OF THE | | | LIGHTING ON SHORTER POLES TO RESOLVE ANY CONFLICTS WITH | | | TREES IN THE PARKING AREA LANDSCAPE ISLANDS. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
12-08-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-08-2020 |
Time |
15:46 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-08-2020 |
Time |
15:46 |
Sent To |
|
|
| Notes |
| 2020-12-08 15:46:35 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 801AND 819 N TAMARIND Z20100020 | | | DECEMBER 8, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. ON THE TREE DISPOSITION CHART SHOWING THE MANGO TREE | | | TO BE REMOVED, IF THE DIAMETER IS 25 FEET, THE | | | MITIGATION DUE WOULD BE 491 SQ FT. STAFF SUGGESTS | | | SAVING THE TREE AND WORKING IT INTO THE REVISED SITE | | | PLAN WITH THE PARKING AND THE REQUIRED PRIVATE OPEN | | | SPACE. | | | | | | | | | 2. PROVIDE THE LOCATION OF THE 12% REQUIRED PRIVATE | | | OPEN SPACE AND IDENTIFY THE TYPE. SHOW THE REQUIREMENTS | | | MET FOR THE TYPE OF OPEN SPACE INCLUDING VEGETATED AREA | | | AND TREE CANOPY COVERAGE REQUIRED. | | | | | | 3. PROVIDE THE REQUIRED TERMINAL LANDSCAPE ISLAND WITH | | | 8 FEET LANDSCAPE WIDTH AT THE END OF EACH ROW OF | | | PARKING. ALONG THE NORTH BUFFER, THE 5 FEET OF REQUIRED | | | LANDSCAPE BUFFER CAN BE A PART OF THE TERMINAL ISLAND, | | | BUT THE 8 FEET INSIDE CURB MUST BE PROVIDED. THE | | | REQUIRED TREE MUST BE PROVIDED IN ADDITION TO THE | | | BUFFER TREE REQUIREMENT. | | | | | | 4. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75 | | | PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED | | | WITHIN THE INTERIOR OF AN OFF-STREET PARKING AREA SHALL | | | BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF | | | CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE | | | AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL | | | AND INTERIOR ISLANDS. ONLY THREE TREES ARE SHOWN, BUT | | | THE CHART INDICATES 4. | | | | | | 5. BUFFER LENGTHS REQUIRE ONE TREE PER 30 FEET OR | | | PORTION THEREOF ADJACENT TO PARKING AREAS. PROVIDE THE | | | REQUIRED AND PROVIDED BUFFER TREES FOR THE NORTH AND | | | WEST BUFFER. TREE SPECIES AND MATURE HEIGHT MUST MEET | | | FALL ZONE REQUIREMENTS TO BE LESS THAN THE DISTANCE TO | | | THE FIRST TRACKS. | | | | | | 6. UPDATE THE DESIGN OPTIONS CHART FOR FLORIDA FRIENDLY | | | LANDSCAPE REQUIREMENTS PER SECTION 94-442(G) TO UTILIZE | | | DROUGHT TOLERANT SPECIES FOR REMAINDER OF REQUIRED | | | TREES AND SHRUBS RATHER THAN THE ADDITIONAL PARKING | | | AREA TREES. | | | | | | 7. ADD A SECTION IN THE LANDSCAPE DATA CHART TO COMPLY | | | WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM OF 60 | | | PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE | | | OR DROUGHT TOLERANT SPECIES SELECTED FROM THE CITY LIST | | | OR THE LIST OF SPECIES IN THE MOST RECENT EDITION OF | | | SOUTH FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. PROVIDE THE TOTAL PERCENTAGE OF | | | NATIVE AND DROUGHT TOLERANT PLANTS BASED ON FINAL PLANT | | | LIST. | | | | | | 8. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. INDICATE | | | THAT THE OVERHEAD WIRES AND POLE IN THE ALLEY WILL BE | | | ELIMINATED. | | | | | | 9. SHOW LOCATIONS OF ALL PROPOSED WATER, SEWER AND | | | DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | | | | 10. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO | | | SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 11. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND | | | EQUIPMENT. | | | | | | 12. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE | | | LANDSCAPE PLAN AND REDESIGN THE LOCATIONS OF THE | | | LIGHTING ON SHORTER POLES TO RESOLVE ANY CONFLICTS WITH | | | TREES IN THE PARKING AREA LANDSCAPE ISLANDS. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
3 |
Status |
P |
Date |
07-02-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-02-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-02-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-02 15:06:32 | NO FURTHER COMMENTS FROM DEPT. OF PUBLIC WORKS. | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-20 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
F |
Date |
03-05-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-05-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
03-05-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-05 15:02:50 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF | | | THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE | | | UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION | | | SERVICE. | | | 2- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR | | | THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
11-30-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
11-30-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-11-30 08:45:34 | PLEASE PROVIDE THE FOLLOWINGS: | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF | | | THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE | | | UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION | | | SERVICE. | | | 2- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE | | | DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE | | | LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7. | | | 3- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR | | | THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE | | | FOLLOWING SPECS: | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
07-19-2021 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-19-2021 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-19-2021 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2021-07-19 14:57:22 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 6/16/2021 RESUBMITTAL. THEY CAN BE ADDRESSED FOR | | | THEENGINEERING PERMIT APPLICATION. | | | | | | 1. REVISE WATER AND SANITARY SEWER NOTE NO. 5 ON SHEET | | | C0.2 TO READ MIN. 36" COVER FROM FINISHED GRADE. | | | | | | 2. REMOVE "32.00' ASPHALT" FROM SECTION B-B (DETAIL 12) | | | ON SHEET C4.2. THE PGD PLAN SHOWS PAVERS. | | | | | | 3. PROVIDE ADDITIONAL EXISTING AND PROPOSED SPOT GRADES | | | FOR 7TH STREET (CENTERLINE, EDGE OF PAVEMENT) | | | DEMONSTRATING THE ROADWAY WILL DRAIN TOWARD THE CURB | | | AND GUTTER AND TO THE EXISTINGDRAINAGE STRUCTURE. | | | REVISE SECTION C-C TO SHOW THE EXISTING PAVEMENT WILL | | | DRAIN TOWARD THE VALLY GUTTER. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
12-10-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-10-2020 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-10-2020 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2020-12-10 10:21:28 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | | | | 1. THE CITY'S OFFICIAL VERTICAL DATUM IS NGVD1929. THE | | | SURVEY USES NAVD1988. THE CITY HAS ALLOWED NAVD1988 | | | PROVIDED THE CONVERSION BETWEEN NAVD1988 AND NGVD1929 | | | IS LISTED. PROVIDE THE VERTICAL DATUM AND CONVERSION | | | EQUATION ON EVERY SHEET WITH ELEVATION INFORMATION | | | (C4.2, C4.3), | | | | | | 2. MOVE THE DRAINAGE STRUCTURE AND STORM PIPE OUT OF | | | THE ALLEY RIGHT OF WAY. | | | | | | 3. PROVIDE TYPICAL CROSS SECTION OF THE ALLEY. | | | | | | 4. PROVIDE CROSS SECTIONS FROM EAST AND SOUTH FACES OF | | | THE BUILDING TO THE ROADWAY EDGE OF PAVEMENT SHOWING | | | PROPOSED GRADING, PERIMETER BERM AND/OR SWALE, | | | SIDEWALK, PROPERTY LINE AND CURB AND GUTTER. | | | | | | 5. EXTEND SECTION B-B TO THE WEST FACE OF THE BUILDING, | | | PROVIDING DIMENSIONS AND TYPICAL SURFACE SLOPES. | | | | | | 6. PROVIDE CROSS SECTION FROM NORTH FACE OF BUILDING TO | | | NORTH PROPERTY LINE ACROSS THE FUTURE EXPANSION AREA. | | | | | | 7. CURB RAMP WILL BE NEEDED ON BOTH SIDES OF THE ALLEY | | | AT N. TAMARIND AVE. SIDEWALKS. | | | | | | 8. MATCH EXISTING WEST INVERT ELEVATION AT DRAINAGE | | | STRUCTURE EX CB 570 AT NW CORNER OF N. TAMARIND AVE AND | | | 7TH ST. | | | | | | 9. RCP STROM PIPE TO BE USED WITHIN RIGHT OF WAY OR | | | UNDER ANY SIDEWALKS THAT THE CITY WILL BE MAINTAINING. | | | | | | 10. CONSIDER REDUCING PARKING SPACE LENGTHS AND | | | PROVIDING PERVIOUS OVERHANG AT THE ENDS OF THE PULL-IN | | | PARKING SPACES. | | | | | | 11. SUGGEST SPECIFYING STABILIZED SUB-GRADE FOR THE | | | ONSITE ASPHALT. | | | | | | 12. MODIFY SECTION C-C TO PROVIDE ADA COMPLIANT PATH | | | ACROSS THE DRIVE. | | | | | | 13. SHOW DROP CURB ACROSS DRIVE IN SECTION C-C. | | | | | | 14. REMOVE BLEEDER FROM THE WEIR. THE CITY DOES NOT | | | ALLOW THE USE OF BLEEDERS ON CONTROL STRUCTURES USED | | | WITH EXFILTRATION TRENCHES. | | | | | | 15. THE SIDE VIEW OF THE STRUCTURE DETAILS (S-101) IS | | | SHOWING THE INFLOW PIPE IN THE WRONG LOCATION. | | | | | | 16. PROVIDE PRB'S ON EACH SIDE OF THE EXFILTRATION | | | TRENCH TO EXTEND THE LIFE OF THE EXFILTRATION TRENCH. | | | CONSIDER INCORPORATING LOW IMPACT DEVELOPMENT DRAINAGE | | | FEATURES INTO THE PROJECT. | | | | | | 17. PROVIDE A PRB FOR THE OUTFALL PIPE TO KEEP | | | FLOATABLES ONSITE AND OUT OF THE CITY'S MS4. | | | | | | 18. GRADING OF 7TH ST WILL NEED TO BE DESIGNED TO | | | PREVENT STANDING WATER WITHIN THE RIGHT OF WAY. | | | | | | 19. SHOW THE LIMITS OF MILLING AND RESURFACING FOR THE | | | TRENCH CUTS ON N. TAMARIND AVE. | | | | | | 20. INCLUDE R/W STRIPING ON THE SIGNING, STRIPING AND | | | GEOMETRIC PLAN. | | | | | | 21. SHOW THE UTILITIES ON THE LANDSCAPE PLANS. | | | | | | 22. NO SURVEY WAS PROVIDED. | | | | | | 23. WHAT ARE CRA'S PLANS FOR UNDERGROUNDING THE | | | OVERHEAD UTILITIES? | | | | | | 24. THREE OF THE FOUR PROPOSED EXTERIOR ELEVATIONS | | | MISLABELED ON SHEET A-3. | | | | | | 25. PROVIDE A PLAN SHOWING THE RESTORATION OF THE | | | PROPERTY AT 464 FERN STREET WHEN THE STRUCTURE IS | | | REMOVED. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. A SFWMD ERP MAY BE REQUIRED. PROVIDE A COPY OF THE | | | PERMIT PRIOR TO STARTING CONSTRUCTION. | | | | | | 4. PROVIDE A COPY OF THE DRAINAGE CALCULATIONS WITH THE | | | ENGINEERING PERMIT APPLICATION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | | | | | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
03-15-2021 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
03-15-2021 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-15 13:40:42 | 1. SEE ADDITIONAL RIGHT-OF-WAY TAKING FOR TAMARIND AVE. | | | PER ROAD PLAT BOOK 11, P 94. | | | 2. NEED APPROVAL FROM FPL FOR RELOCATION ALONG WEST | | | PROPERTY LINE PROPOSED FOR LANDSCAPING. | | | 3. SLIDING GATE AT EXIT WILL CONFLICT WITH PROPOSED FPL | | | TRANSFORMER IN SOUTHWEST CORNER. | | | 4. SP-1 STILL SHOWS 2-WAY TRAFFIC OFF 7TH STREET. | | | 5. CITY TO PREPARE A CORRECTIVE UNITY OF TITLE. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
12-07-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
12-07-2020 |
Time |
07:45 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-07 08:06:09 | 1. NEED SIGNED AND SEALED SURVEY BY A REGISTERED LAND | | | SURVEYOR. | | | 2. PLEASE COORDINATE WITH VLADIMIR JEANNOT IN | | | ENGINEERING FOR PROPOSED TAMARIND AVE. | | | 3. THE UTILITY EASEMENT IS ACTUALLY AN FPL EASEMENT PER | | | ORB 27819/1951. THERE IS ANOTHER FPL EASEMENT IN THE NE | | | CORNER PER ORB 29015/1709. BOTH ARE PROPOSED TO HAVE AN | | | 8' X 8' TRANSFORMER. | | | 4. UNITY OF TITLE WILL BE REQUIRED. | | | 5. NEED APPROVED PLAN BY FPL FOR ANY RE-ROUTING PRIOR | | | TO SITE PLAN APPROVAL. | | | 6. IS THE SOUTH EXIT PROPOSED TO BE GATED? |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
5 |
Status |
P |
Date |
07-14-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-14-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-14 19:15:02 | PASSED WITH THE FOLLOWING CONDITION: PROVIDE COUNTY TPS | | | LETTER | | | | | | TRAFFIC COMMENTS: | | | 1. PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER. | | | [REQUEST ACKNOWLEDGED] | | | 2. SATISFIED. THE PARKING STALL LOCATED IN THE | | | SOUTH-WEST CORNER OF THE PROPERTY SHOULD BE EITHER | | | REMOVED OR MOVED FURTHER NORTH. A VEHICLE BACKING-UP | | | INTO IT WOULD BE MANEUVERING ON PUBLIC ROW. PLEASE | | | CLARIFY THE USE OF THE SMALLER STALLS IMPLEMENTED IN | | | LIEU OF THE ORIGINAL CAR STALL. [CLARIFIED] | | | 3. SATISFIED. PROVIDE AUTOTURN ANALYSIS SHOWCASING | | | GARBAGE TRUCK MANEUVERING IN AND OUT OF THE PROPERTY. | | | IF NO GARBAGE TRUCK WILL ENTER THE PROPERTY, HOW IS THE | | | FUTURE DUMPSTER GOING TO BE SERVICED? [ANSWERED] | | | | | | SITE COMMENTS: | | | 4. SATISFIED. COORDINATE WITH SUZANNE BERGLUND AS THE | | | PROPOSED DEVELOPMENT MAY BE IMPACTED BY THE ON-GOING | | | TAMARIND STREETSCAPE PROJECT | | | 5. SATISFIED. INSTALL A RAMP ON THE NORTH SIDE OF 7TH | | | ST NEAR THE RAILROAD TRACKS AND A CROSSWALK ACROSS 7TH | | | ST IN ORDER TO CONNECT TO THE EXISTING RAMP ON THE | | | SOUTH SIDE. INSTALL TACTILE MATS ON EACH RAMP. | | | | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
4 |
Status |
F |
Date |
07-01-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-01-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-07-01 19:17:59 | TRAFFIC COMMENTS: | | | 1. PARTIALLY SATISFIED. PROVIDE COUNTY TPS LETTER. | | | REQUEST ACKNOWLEDGED. | | | 2. NOT SATISFIED. THE PARKING STALL LOCATED IN THE | | | SOUTH-WEST CORNER OF THE PROPERTY SHOULD BE EITHER | | | REMOVED OR MOVED FURTHER NORTH. A VEHICLE BACKING-UP | | | INTO IT WOULD BE MANEUVERING ON PUBLIC ROW. PLEASE | | | CLARIFY THE USE OF THE SMALLER STALLS IMPLEMENTED IN | | | LIEU OF THE ORIGINAL CAR STALL ONE | | | 3. PARTIALLY SATISFIED. PROVIDE AUTOTURN ANALYSIS | | | SHOWCASING GARBAGE TRUCK MANEUVERING IN AND OUT OF THE | | | PROPERTY. IF NO GARBAGE TRUCK WILL ENTER THE PROPERTY, | | | HOW IS THE FUTURE DUMPSTER GOING TO BE SERVICED? | | | | | | SITE COMMENTS: | | | 4. SATISFIED. COORDINATE WITH SUZANNE BERGLUND AS THE | | | PROPOSED DEVELOPMENT MAY BE IMPACTED BY THE ON-GOING | | | TAMARIND STREETSCAPE PROJECT | | | 5. SATISFIED. INSTALL A RAMP ON THE NORTH SIDE OF 7TH | | | ST NEAR THE RAILROAD TRACKS AND A CROSSWALK ACROSS 7TH | | | ST IN ORDER TO CONNECT TO THE EXISTING RAMP ON THE | | | SOUTH SIDE. INSTALL TACTILE MATS ON EACH RAMP. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
F |
Date |
06-10-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-10-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-06-10 01:57:19 | TRAFFIC COMMENTS: | | | 1. PROVIDE COUNTY TPS LETTER | | | 2. THE PARKING STALL LOCATED IN THE SOUTH-WEST CORNER | | | OF THE PROPERTY SHOULD BE EITHER REMOVED OR MOVED | | | FURTHER NORTH. A VEHICLE BACKING-UP INTO IT WOULD BE | | | MANEUVERING ON PUBLIC ROW | | | 3. PROVIDE AUTOTURN ANALYSIS SHOWCASING GARBAGE TRUCK | | | MANEUVERING IN AND OUT OF THE PROPERTY | | | SITE COMMENTS: | | | 4. COORDINATE WITH SUZANNE BERGLUND AS THE PROPOSED | | | DEVELOPMENT MAY BE IMPACTED BY THE ON-GOING TAMARIND | | | STREETSCAPE PROJECT | | | 5. REVISED COMMENT: CLOSE THE RAMP ON THE SOUTH SIDE OF | | | 7TH ST EAST OF THE RAILROAD TRACKS AND INSTALL A CURB | | | | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
03-25-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-25-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-25 09:54:34 | TRAFFIC COMMENTS: | | | 1. PROVIDE COUNTY TPS LETTER | | | 2. THE PARKING STALL LOCATED IN THE SOUTH-WEST CORNER | | | OF THE PROPERTY SHOULD BE EITHER REMOVED OR MOVED | | | FURTHER NORTH. A VEHICLE BACKING-UP INTO IT WOULD BE | | | MANEUVERING ON PUBLIC ROW | | | 3. PROVIDE AUTOTURN ANALYSIS SHOWCASING GARBAGE TRUCK | | | MANEUVERING IN AND OUT OF THE PROPERTY | | | 4. COORDINATE WITH SUZANNE BERGLUND AS THE PROPOSED | | | DEVELOPMENT MAY BE IMPACTED BY THE ON-GOING TAMARIND | | | STREETSCAPE PROJECT | | | 5. INSTALL A RAMP ON THE NORTH SIDE OF 7TH ST NEAR THE | | | RAILROAD TRACKS AND A CROSSWALK ACROSS 7TH ST IN ORDER | | | TO CONNECT TO THE EXISTING RAMP ON THE SOUTH SIDE. | | | INSTALL TACTILE MATS ON EACH RAMP. | | | | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
12-10-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
12-10-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-12-10 12:16:47 | TRAFFIC COMMENTS: | | | 1. PROVIDE TPS LETTER | | | 2. DRIVEWAY ON 7TH ST IS VERY CLOSE TO RR CROSSING. | | | FULL ACCESS OPERATIONS MAY CAUSE SAFETY AND OPERATIONAL | | | ISSUES. ONE-WAY ACCESS/EGRESS IS RECOMMENDED, | | | 3. REVIEW/IMPROVE INTERNAL CIRCULATION. IN CASE OF | | | TWO-WAY CIRCULATION, THERE IS NO TURN-AROUND SPACE FOR | | | VEHICLES HEADING NORTH WITHIN THE PARKING LOT | | | 4. PROVIDE AUTOTURN SHOWCASING GARBAGE TRUCK OPERATIONS | | | | | | SITE COMMENTS: | | | 5. PARKING STALLS | | | 5A. ANGLE PARKING RECOMMENDED, IN CASE OF ONE-WAY | | | INTERNAL CIRCULATION | | | 5B. IF CURRENT DESIGN IS KEPT, PROVIDE AUTOTURN | | | ANALYSIS FOR THE SOUTH-WEST CORNER PARKING STALL, AS IT | | | MAY REQUIRE MANEUVERING ON PUBLIC ROW, WHICH IS NOT | | | ALLOWED. | | | 6. PLEASE COORDINATE WITH SUZANNE BERGLUND AS THE | | | PROPOSED DEVELOPMENT MAY BE IMPACTED BY THE ON-GOING | | | TAMARIND STREETSCAPE PROJECT | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
03-17-2021 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
03-17-2021 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
03-17-2021 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2021-03-17 14:39:29 | SITE PLAN: | | | 1. PARTIALLY SATISFIED. PLEASE UPDATE SITE DATA TABLE | | | TO INCLUDE THE FOLLOWING INFORMATION: | | | A. SATISFIED | | | B. REQUIRED AND PROVIDED BICYCLE PARKING ? REQUIRED | | | BICYCLE PARKING IS AS FOLLOWS: | | | I. NOT SATISFIED. BICYCLE PARKING SHALL BE PROVIDED AT | | | A MINIMUM OF ONE SPACE PER EVERY 100 FEET OF STREET | | | FRONTAGE AND LOCATED WITHIN THE PUBLIC ROW, PARALLEL TO | | | CURB OR AT THE BACK OF THE SIDEWALK (BEST PLACEMENT CAN | | | BE EVALUATED) | | | PLEASE INCLUDE 2 BICYCLE RACKS WITHIN THE ROW FOR | | | PUBLIC USE, KEEPING 5-FOOT SIDEWALK CLEARANCE, AND | | | 2-FOOT CLEARANCE FROM CURB. THE RACKS FOR PALM TRAN ARE | | | SEPARATE AND FOR THEIR RIDERS | | | II. PARTIALLY SATISFIED. COMMERCIAL DEVELOPMENTS, SHALL | | | PROVIDE SECURE BIKE RACKS AND/OR STORAGE AT A RATIO OF | | | ONE BICYCLE PARKING SPACE PER EVERY 15 PARKING SPACES, | | | WITHIN THE PRIVATE PROPERTY (FOR TENANT USE) | | | THE BICYCLE RACKS NEED TO BE ON A HARD SURFACE, LIKE | | | CONCRETE OR PAVERS | | | | | | C. SATISFIED. | | | D. SATISFIED. | | | 2. SATISFIED. | | | 3. SATISFIED. | | | 4. SATISFIED. | | | 5. NOT SATISFIED. THE MAXIMUM PARKING FOR THIS | | | COMMERCIAL PROPERTY WITHIN NWD-5 IS 3/1000 SF WHICH IS | | | 9 PARKING SPACES. ANY SPACES ABOVE THE MAXIMUM PARKING | | | COUNTS TOWARDS FAR. PLEASE UPDATE FAR CALCULATION | | | ACCORDINGLY IF KEEPING OVER THE MAXIMUM | | | THE PARKING DATA STATES 10 SPACES, BUT THERE ARE 12 ON | | | SITE. 2 OF THESE SPACES ARE ABOVE THE MAXIMUM | | | PERMITTED, SO WOULD COUNT TOWARDS FAR. PLEASE INCLUDE | | | THE TWO SPACES WITHIN THE PROPOSED FAR ((8.5X22) X2)) | | | 6. PARTIALLY SATISFIED. WHAT IS PROPOSED WITHIN THE | | | UTILITY AREA ON THE SOUTH SIDE OF THE BUILDING? CAN | | | THIS BE LOCATED INTERNAL TO THE SITE OR ELSEWHERE THAT | | | IS NOT WITHIN VIEW OF A STREET FRONTAGE? | | | THE GATE CANNOT SWING INTO THE DRIVE AISLE, PLEASE | | | REORIENT TO HAVE GATE OPENINGS FACING NORTH INTO | | | SIDEWALK AREA. PLEASE CONFIRM WITH TRACY WARD WHETHER | | | STORMWATER LINES CAN RUN UNDER THIS UTILITY AREA | | | 7. SATISFIED | | | 8. ONGOING. PLEASE RELOCATE THE EXISTING BUS STOP | | | FURTHER NORTH TO ALLOW FOR A BENCH AT THE BACK OF THE | | | SIDEWALK FOR TRANSIT RIDERS. BENCH CAN BE ACCOMMODATED | | | WITHIN THE PRIVATE OPEN SPACE REQUIREMENT. PLEASE | | | CONSIDER THE INCORPORATION OF A BUS SHELTER FOR PALM | | | TRAN RIDERS AS AN AMENITY FOR PUBLIC TRANSIT IN THIS | | | NEIGHBORHOOD | | | RELOCATION OF BUS SHELTER TO OTHER LOCATION WITHIN | | | TAMARIND SUBJECT TO ENGINEERING AND PLANNING REVIEW. | | | 9. SATISFIED | | | 10. PLEASE INCLUDE BICYCLE RACK SPECS WITH BUILDING | | | PERMIT SUBMITTAL. PLANNING CAN GIVE GUIDANCE ON | | | APPROVED BICYCLE RACK TYPES | | | 11. PROPOSED CONDITION OF APPROVAL. PROPERTY AT 464 | | | FERN STREET WILL NEED TO BE RESODDED ONCE STRUCTURE IS | | | RELOCATED | | | | | | LANDSCAPE: | | | 12. SATISFIED | | | 13. SATISFIED | | | 14. PARTIALLY SATISFIED. THE SITE HAS A PRIVATE OPEN | | | SPACE REQUIREMENT OF 12%. THE TYPE OF PERMITTED PRIVATE | | | OPEN SPACE WITHIN NWD-5 CAN BE FOUND IN TABLE IV-6 IN | | | SECTION 94-109. THE REQUIREMENT FOR THE PRIVATE OPEN | | | SPACE THAT IS PICKED CAN BE FOUND IN TABLE IV-7 IN | | | SECTION 94-109. PLEASE ENSURE THAT THE TYPE OF PRIVATE | | | OPEN SPACE PICKED MEETS THE DEFINITION OF THAT PRIVATE | | | OPEN SPACE TYPE (DEFINITIONS ALSO IN SECTION 94-109) | | | | | | PRIVATE OPEN SPACE WILL NEED TO BE ADJUSTED BASED ON | | | PROPERTY SIZE ADJUSTMENT BASED ON ROW MAINTENANCE MAP | | | OF TAMARIND AVENUE. | | | | | | PLEASE INDICATE THE TYPE OF PRIVATE OPEN SPACE FROM | | | ONES THAT ARE PERMITTED IN WITHIN NWD-5 IN TABLE IV-6 | | | IN SECTION 94-109 AND SEE TABLE IV-7 IN SECTION 94-109. | | | | | | THE AREA TO THE WEST OF THE PROPOSED STRUCTURE, WHICH | | | CONTAINS RAMPS AND STAIRWAYS, AND THE AREA TO THE WEST | | | OF THE PROPOSED FUTURE DEVELOPMENT AREA IS ILLUSTRATED | | | AS PRIVATE OPEN SPACE ON SHEET SP-1.1. THESE WOULD NOT | | | COUNT TOWARDS PRIVATE OPEN SPACE. | | | | | | THE AREA BETWEEN THE STRUCTURE AND THE FUTURE | | | DEVELOPMENT AREA CAN BE COUNTED INCLUDING ALL AREAS | | | OUTSIDE THE MINIMUM SETBACK (ROOM TO EXPAND EAST). | | | PLEASE LOOK AT THE AREAS TO THE SOUTH AND EAST OF THE | | | PROPOSED STRUCTURE AND CONSIDER THE ?GARDEN? TYPE OF | | | PRIVATE OPEN SPACE. FOR THE AREA BETWEEN THE STRUCTURE | | | AND FUTURE DEVELOPMENT AREA, CONSIDER THE ?INTERIOR | | | COURTYARD? PRIVATE OPEN SPACE TYPE | | | | | | CIVIL/SURVEY: | | | 15. NOT SATISFIED. PLEASE INDICATE PROPOSED TRASH | | | COLLECTION PLAN FOR CURRENT OFFICE SPACE ? COORDINATE | | | WITH MATT HEJAZI IN PUBLIC WORKS | | | PLEASE SEE COMMENTS FROM PUBLIC WORKS | | | 16. SATISFIED | | | | | | | | | NEW COMMENTS MARCH 17, 2021: | | | | | | CIVIL: | | | 17. WATER METER AND FIRE BACKFLOW PROPOSED WITHIN ROW. | | | THESE NEED TO BE WITHIN PRIVATE PROPERTY. WHY WERE | | | THESE MOVED FROM THE FIRST PROPOSED LOCATION? CHECK | | | WITH CHIEF LEDUC REGARDING NEED FOR FDC BACKFLOW FOR | | | SMALL OFFICE STRUCTURE | | | 18. THE PROPOSED DRAINAGE THAT RUNS UNDER THE TRASH | | | CONCRETE PAD ? CHECK WITH TRACY WARD WHETHER THIS | | | CREATES ANY ISSUES FOR MAINTENANCE | | | 19. ENSURE COORDINATION WITH PROPOSED POTABLE WATER AND | | | SANITARY SEWER SERVICES WITH THE TAMARIND AVENUE | | | IMPROVEMENTS PROJECT ? COMMENT FROM SUZANNE BERGLUND | | | 20. APPEARS TO BE AN EXISTING IRRIGATION BACKFLOW IN | | | PROPERTY THAT WILL NEED TO BE RELOCATED. PLEASE CLARIFY | | | THE PROPOSE LOCATION FOR THIS. | | | 21. PRIVATE STORMWATER DRAINAGE CANNOT DRAIN INTO | | | PUBLIC SYSTEM ? CHECK WITH TRACY WARD, CITY STORMWATER | | | ENGINEER | | | 22. THE PROPOSED LOCATION OF THE DRAINAGE SYSTEM IS | | | PREVENTING TREES ON SOUTH SIDE OF STRUCTURE, PLEASE | | | REEVALUATE STORMWATER DRAINAGE SYSTEM | | | 23. PLEASE EVALUATE OTHER MEANS OF DRAINAGE OTHER THAN | | | A SWALE SURROUND PROPOSED STRUCTURE TO ALLOW FOR BETTER | | | USE OF THIS AREA | | | 24. PLEASE PROVIDE CROSS SECTION ACROSS CURB CUT THAT | | | RUNS PARALLEL TO THE ROADWAY OF 7TH STREET (EAST TO | | | WEST). NEED TO DETERMINE THAT SIDEWALK IS KEPT LEVEL AS | | | IT CROSSES THIS CURB CUT | | | | | | LANDSCAPE: | | | 25. ALL OF PROPOSED TREES ALONG WEST BORDER ARE WITHIN | | | THE PROPOSED FPL EASEMENT. AS CONVERSATIONS WITH FPL | | | CONTINUE, IT WILL NEED TO BE DETERMINED WHETHER THESE | | | TREES CAN BE WITHIN THIS EASEMENT | | | 26. PLEASE SHOW PROPOSED LANDSCAPE WITHIN THE ROW PER | | | THE APPROVED TAMARIND AVENUE STREETSCAPE PLANS | | | 27. PLEASE EXTEND PLANTER BED ON 7TH TO THE EAST, AS | | | THIS PORTION OF HARDSCAPE ADJACENT TO THE ADA RAMP IS | | | NOT NECESSARY (CONFIRMED WITH SUZANNE) | | | 28. IN EMAIL IT HAS BEEN INDICATED THAT THE STORMWATER | | | OUTFALL AT THE SOUTHEAST CORNER WILL BE REMOVED, PLEASE | | | UPDATE PLANS ACCORDINGLY | | | A. PLEASE CONTINUE LANDSCAPE BED FURTHER SOUTH WHERE | | | OUTFALL IS BEING REMOVED IF SUZANNE BERGLUND GIVES | | | APPROVAL TO DO SO | | | | | | SITE PLAN: | | | 29. LOCATION OF FPL TRANSFORMER MAY CONFLICT WITH | | | LOCATION OF PROPOSED ROLLING GATE AT 7TH STREET EGRESS. | | | AS CONVERSATIONS WITH FPL CONTINUE, THIS ROLLING GATE | | | MAY NEED TO BE RELOCATED | | | 30. THE TWO PROPOSED PARALLEL PARKING SPACES EAST OF | | | THE DRIVE WOULD NOT HAVE SUFFICIENT ROOM TO OPEN THE | | | CAR DOORS AS THEY ARE ADJACENT TO THE RAMP. THE DRIVE | | | AISLE AT THIS LOCATION CAN BE 12 FEET PER FIGURE XV-2 | | | IN ARTICLE XV. PLEASE LOOK AT OPTIONS OF PROVIDING | | | ADDITIONAL SPACE FOR CAR DOORS OR REMOVE THESE TWO | | | SPACES. | | | 31. PLEASE NOTE, A MAINTENANCE AGREEMENT FOR | | | STREETSCAPE ADJACENT TO PROPERTY SHALL BE RECORDED | | | BETWEEN THE CITY AND DEVELOPER, FOR DEVELOPER/OWNER TO | | | ASSUME MAINTENANCE RESPONSIBILITIES | | | 32. PLEASE ADD SIDEWALK NORTH OF UTILITY AREA ON SHEET | | | SP-1 THAT IS SHOWN ON LANDSCAPE PLANS | | | 33. PLEASE COORDINATE WITH LT CLIFFORD HAGAN, | | | [email protected] ON THE EXISTING POLICE INFRASTRUCTURE | | | THAT IS CURRENTLY ON THE PROPERTY. THIS INFRASTRUCTURE | | | MUST REMAIN AND OR APPROVAL TO REMOVE OR RELOCATE | | | EQUIPMENT MUST BE RECEIVED. COMMENT FROM SUZANNE | | | BERGLUND | | | 34. PLEASE COORDINATE WITH PENNI REDFORD, | | | [email protected], 561-804-4981, ON THE REMOVAL OR | | | RELOCATION OF THE EXISTING SOLAR PANEL EQUIPMENT THAT | | | IS CURRENTLY ON THE PROPERTY. COMMENT FROM SUZANNE | | | BERGLUND | | | | | | | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
12-09-2020 |
|
|
Cont ID |
|
| Sent By |
elevesqu |
Date |
12-09-2020 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
elevesqu |
Date |
12-09-2020 |
Time |
13:47 |
Sent To |
|
|
| Notes |
| 2020-12-09 13:50:06 | SITE PLAN: | | | 1. PLEASE UPDATE SITE DATA TABLE TO INCLUDE THE | | | FOLLOWING INFORMATION: | | | A. REQUIRED SETBACKS (MINIMUM REQUIRED FROM TAMARIND IS | | | 10 FEET, MINIMUM REQUIRED FROM 7TH STREET IS 17?) ? | | | MEASURED FROM THE BACK OF THE CURB NOT FROM THE | | | PROPERTY LINE IN THIS ZONING DISTRICT | | | B. REQUIRED AND PROVIDED BICYCLE PARKING ? REQUIRED | | | BICYCLE PARKING IS AS FOLLOWS: | | | I. BICYCLE PARKING SHALL BE PROVIDED AT A MINIMUM OF | | | ONE SPACE PER EVERY 100 FEET OF STREET FRONTAGE AND | | | LOCATED WITHIN THE PUBLIC ROW, PARALLEL TO CURB OR AT | | | THE BACK OF THE SIDEWALK (BEST PLACEMENT CAN BE | | | EVALUATED) | | | II. COMMERCIAL DEVELOPMENTS, SHALL PROVIDE SECURE BIKE | | | RACKS AND/OR STORAGE AT A RATIO OF ONE BICYCLE PARKING | | | SPACE PER EVERY 15 PARKING SPACES, WITHIN THE PRIVATE | | | PROPERTY (FOR TENANT USE) | | | C. BUILDING FOOTPRINT PERCENTAGE (SEE TABLE IV-36 IN | | | SECTION 94-128) | | | D. REQUIRED AND PROVIDED SETBACKS | | | 2. PLEASE UPDATE SCALE ON SHEET SP-1. APPEARS TO BE | | | 1?=10? (LABEL READS 1/8?=1?) | | | 3. PLEASE PROVIDE A 5-FOOT SIDEWALK THROUGHOUT THE | | | ENTIRE TAMARIND AVENUE FRONTAGE (SOME PORTION MAY BE ON | | | PRIVATE ROW AND REQUIRE A PUBLIC ACCESS EASEMENT) | | | A. PLEASE COORDINATE WITH THE CITY OF WPB ENGINEERING | | | DEPARTMENT FOR THE PROPOSED TAMARIND AVENUE STREETSCAPE | | | PLANS | | | 4. TRAFFIC ENGINEER IS NOT COMFORTABLE WITH INGRESS | | | FROM 7TH STREET DUE TO PROXIMITY FROM RAILROAD TRACKS. | | | PLEASE REDUCE DRIVEWAY TO EGRESS ONLY. REDUCED DRIVEWAY | | | WIDTH CAN WORK WITH ANGLED PARKING. DRIVE AISLE FOR | | | ANGLED PARKING CAN BE REDUCED TO 12 FOOT. | | | 5. THE MAXIMUM PARKING FOR THIS COMMERCIAL PROPERTY | | | WITHIN NWD-5 IS 3/1000 SF WHICH IS 9 PARKING SPACES. | | | ANY SPACES ABOVE THE MAXIMUM PARKING COUNTS TOWARDS | | | FAR. PLEASE UPDATE FAR CALCULATION ACCORDINGLY IF | | | KEEPING OVER THE MAXIMUM | | | 6. WHAT IS PROPOSED WITHIN THE UTILITY AREA ON THE | | | SOUTH SIDE OF THE BUILDING? CAN THIS BE LOCATED | | | INTERNAL TO THE SITE OR ELSEWHERE THAT IS NOT WITHIN | | | VIEW OF A STREET FRONTAGE? | | | 7. A MONUMENT SIGN IS NOT PERMITTED FOR THIS USE | | | (SECTION 94-110) | | | 8. PLEASE RELOCATE THE EXISTING BUS STOP FURTHER NORTH | | | TO ALLOW FOR A BENCH AT THE BACK OF THE SIDEWALK FOR | | | TRANSIT RIDERS. BENCH CAN BE ACCOMMODATED WITHIN THE | | | PRIVATE OPEN SPACE REQUIREMENT. PLEASE CONSIDER THE | | | INCORPORATION OF A BUS SHELTER FOR PALM TRAN RIDERS AS | | | AN AMENITY FOR PUBLIC TRANSIT IN THIS NEIGHBORHOOD | | | 9. WHAT IS THE SIGN THAT IS SHOWN AT THE SOUTHEAST | | | CORNER AT THE 7TH STREET CROSSING? THERE IS A SIGN | | | SYMBOL ON THE PLAN BUT NO INDICATION OF WHAT THIS SIGN | | | IS (SHEET SP-1) | | | 10. PLEASE INCLUDE BICYCLE RACK SPECS WITH BUILDING | | | PERMIT SUBMITTAL. PLANNING CAN GIVE GUIDANCE ON | | | APPROVED BICYCLE RACK TYPES | | | LANDSCAPE: | | | 11. A LANDSCAPE ISLAND IS REQUIRED AT THE END OF A ROW | | | OF PARKING SPACES, MEETING REQUIREMENTS OF SECTION | | | CHAPTER XIV OF THE CITY?S ZONING AND LAND USE | | | REGULATIONS (ZLDRS) (SOUTH END OF ADA SPACE) | | | 12. PLEASE PRESERVE EXISTING LARGE MANGO TREE THROUGH | | | MEANS OF A PARKING ISLAND OR WITHIN REQUIRED PRIVATE | | | OPEN SPACE | | | 13. THE SITE HAS A PRIVATE OPEN SPACE REQUIREMENT OF | | | 12%. THE TYPE OF PERMITTED PRIVATE OPEN SPACE WITHIN | | | NWD-5 CAN BE FOUND IN TABLE IV-6 IN SECTION 94-109. THE | | | REQUIREMENT FOR THE PRIVATE OPEN SPACE THAT IS PICKED | | | CAN BE FOUND IN TABLE IV-7 IN SECTION 94-109. PLEASE | | | ENSURE THAT THE TYPE OF PRIVATE OPEN SPACE PICKED MEETS | | | THE DEFINITION OF THAT PRIVATE OPEN SPACE TYPE | | | (DEFINITIONS ALSO IN SECTION 94-109) | | | CIVIL/SURVEY: | | | 14. PLEASE INDICATE PROPOSED TRASH COLLECTION PLAN FOR | | | CURRENT OFFICE SPACE ? COORDINATE WITH MATT HEJAZI IN | | | PUBLIC WORKS | | | 15. SURVEY SHOWS TWO TRAFFIC POLES (SYMBOL 8) AT THE | | | SOUTHEAST CORNER BUT ONLY ONE TRAFFIC POLE EXISTS AT | | | THIS LOCATION. THE OTHER IS A LIGHT POLE. PLEASE REVISE | | | | | | | | | LIZ LEVESQUE, URBAN DESIGN PLANNER | | | 561 822 1426 | | | [email protected] |
|
|
| |