Plan Review Details - Project Z20090011
Plan Review Stops For Project Z20090011
Review Stop L LANDSCAPING
Rev No 1 Status P Date 10-05-2020 Cont ID  
Sent By rcaranci Date 10-05-2020 Time 12:13 Rev Time 0.00
Received By rcaranci Date 10-05-2020 Time 12:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status P Date 06-18-2021 Cont ID  
Sent By eschneid Date 06-18-2021 Time 10:11 Rev Time 4.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 04-27-2021 Cont ID  
Sent By eschneid Date 04-27-2021 Time 15:56 Rev Time 6.00
Received By eschneid Date 04-27-2021 Time 15:56 Sent To  
Notes
2021-04-27 16:00:33CASE NO. PB1559M - 2ND RESUBMITTAL
 LA CLARA UTILITY AND ARRIVAL COURT CHANGES
 1515 S. FLAGLER
  
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY JUNE 27, 2021), THE
 PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) THE REVISED WEST ELEVATION SHEET SHOWS THE SCREEN
 WALL MEETING THE SETBACK; HOWEVER, THERE IS SOMETHING
 SHOWN GENERALLY AT THE AMENITY DECK LEVEL AND AT GROUND
 LEVEL THAT IS ENCROACHING INTO THE SETBACK. PLEASE
 EXPLAIN WHAT THIS IS. NOTE: THE ELEVATION DRAWINGS
 SUBMITTED WITH THE PERMIT DOES NOT MATCH THIS ELEVATION
 DRAWING.
  
 2) THERE ARE MANY PROBLEMS WITH VARIOUS BUILDING PERMIT
 SHEETS SHOWING ENCROACHMENTS INTO THE NORTH SETBACK
 LINE. ALL THESE NEED TO BE CLEARED UP TO REFLECT THE
 CONFORMING SETBACK AS SHOWN ON ALL BUT THE WEST
 ELEVATION PLAN RESUBMITTED WITH THE MINOR AMENDMENT.
  
 3) PLEASE ENSURE THAT THE RESUBMITTAL INCLUDES THE
 LATEST VERSION OF THE FOLLOWING PLANS
  
 SITE PLAN: ?GREAT GULF - 1515 S FLAGLER DRIVE,? SHEET
 A111, PREPARED BY STANTEC ARCHITECTURE, INC
  
 FLOOR PLANS: ?GREAT GULF - 1515 S FLAGLER DRIVE,?
 SHEETS A113 THROUGH A123, PREPARED BY STANTEC
 ARCHITECTURE, INC
  
 ELEVATIONS: ?GREAT GULF - 1515 S FLAGLER DRIVE,? SHEETS
 A124 THROUGH A127, PREPARED BY STANTEC ARCHITECTURE,
 INC.
  
 LANDSCAPE PLANS: ?GREAT GULF - 1515 S FLAGLER DRIVE,?
 SHEETS L000.1, L000.2 AND L000.3, ORIGINALL PREPARED BY
 URBAN ASSOCIATES, INC., AND REVISED BY SAVINO & MILLER
 DESIGN STUDIO
  
 CIVIL PLAN: ?GREAT GULF - 1515 S FLAGLER DRIVE,? SHEETS
 C5.00, C5.10 AND C6.00, PREPARED BY KIMLEY HORN,

Review Stop Z ZONING
Rev No 2 Status F Date 01-20-2021 Cont ID  
Sent By eschneid Date 01-20-2021 Time 08:52 Rev Time 4.00
Received By eschneid Date   Time   Sent To  
Notes
2021-01-20 08:54:32CASE NO. PB1559M - 1ST RESUBMITTAL
 LA CLARA UTILITY AND ARRIVAL COURT CHANGES
 1515 S. FLAGLER
 COMMENTS REVISED 10/5/20
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY MARCH 20, 2021),
 THE PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) NORTHERN SETBACK. SHEET A114 GROUND FLOOR PLAN SHOWS
 ALL PLAN ELEMENTS COMPLYING WITH THE NORTHERN 34 FOOT
 10 INCH SETBACK. SHEET A115 AS WELL AS THE CIVIL AND
 LANDSCAPE PLANS CONTINUE TO SHOW THE COLUMNS AND/OR THE
 SCREEN WALL ENCROACHING INTO THE SETBACK. THERE WAS NO
 REVISED EAST ELEVATION SHEET PROVIDED TO SHOW
 COMPLIANCE WITH THE NORTHERN SETBACK. THE REVISED WEST
 ELEVATION SHEET SHOWS THE SCREEN WALL MEETING THE
 SETBACK; HOWEVER, THERE IS SOMETHING SHOWN GENERALLY AT
 THE AMENITY DECK LEVEL THAT IS ENCROACHING INTO THE
 SETBACK. PLEASE EXPLAIN WHAT THIS IS. NOTE: THE
 ELEVATION DRAWING SUBMITTED WITH THE PERMIT DOES NOT
 MATCH THIS ELEVATION DRAWING.
  
 2) THANK YOU FOR PROVIDING CROSS SECTIONS SHOWING THAT
 THE PROPOSED ROYAL PALMS ALONG THE SOUTH PROPERTY LINE
 WILL NOT IMPACT THE FPL DUCT BANK. PLEASE PROVIDE A
 LETTER FROM FPL PERMITTING THE INSTALLATION OF THE
 ROYAL PALMS AS WELL AS THE WAX MYRTLE, THE COCONUT PALM
 AND THE SABAL PALMS (SOUTHEAST CORNER OF SITE) WITHIN
 THEIR EASEMENT.
  
 3) THE CURRENT GROUND FLOOR PLAN SHEET A114 REMOVED
 WHAT WAS PREVIOUSLY LABELED AS SPACES 58C AND 59C. THE
 NUMBERING WAS NOT ADJUSTED TO REFLECT THE REMOVAL OF
 THESE SPACES (THE COUNT SHOWN GOES TO 98 SPACES INSTEAD
 OF THE PROVIDED 96 SPACES). WHILE THE CLEANEST WAY TO
 CORRECT IS TO RENUMBER ALL THE SPACES FROM 60 TO 96,
 STAFF WILL ACCEPT CONVERTING SPACES 97 AND 98 TO 58 AND
 59.
  
 NOTE: THE PHYSICAL NUMBER OF PARKING SPACES SHOWN MEET
 BOTH THE MINIMUM PARKING REQUIREMENT AS WELL AS MINIMUM
 SIZE AND DRIVE AISLE WIDTHS.
  
 4) THE MINIMUM SETBACK FOR THE TOWER IS 47 FEET. THE
 TOWER IS THE BUILDING THAT IS LEVEL 2 AND ABOVE. WHILE
 THE WALL WITH THE DOOR TO THE POOL STORAGE ROOM IS
 APPROXIMATELY 50 FEET FROM THE PROPERTY LINE, AND
 MEETING THE MINIMUM SETBACK, IT APPEARS THAT THE AREA
 TO THE SOUTH OF THE DOOR IS A ROOFED AND WALLED IN
 AREA. THIS MOVES THE SETBACK AS SHOWN TO THE 44 FEET 9
 INCH DIMENSION LINE, WHICH ENCROACHES INTO THE
 PERMITTED SETBACK AND IS NOT ALLOWED.
  
 5) THANK YOU FOR PROVIDING THE LETTER FROM MR. CARLOS
 FRES REGARDING THE POTENTIAL EXHAUST SOUND AND ODOR.
 WHILE IT SUFFICIENTLY ADDRESSED THE ODOR AND GAS
 ISSUED, PLEASE PROVIDE A SUPPLEMENTAL LETTER FROM MR.
 FRES CLEARLY STATING THAT THE NOISE WILL NOT VIOLATE
 THE CITY'S NOISE ORDINANCE. I HAVE INCLUDED THE
 PERTINENT SECTION THAT NEEDS TO BE ADDRESSED BELOW:
  
 SEC. 34-35. - NOISES; UNNECESSARY AND EXCESSIVE
 PROHIBITED.
 IT SHALL BE UNLAWFUL FOR ANY PERSON TO MAKE, CONTINUE,
 OR CAUSE TO BE MADE OR CONTINUED ANY UNREASONABLY LOUD,
 EXCESSIVE, UNNECESSARY OR UNUSUAL NOISE. THE FOLLOWING
 ACTS, AMONG OTHERS, ARE DECLARED TO BE UNREASONABLY
 LOUD, EXCESSIVE, UNNECESSARY OR UNUSUAL NOISES IN
 VIOLATION OF THIS SECTION, BUT THIS ENUMERATION SHALL
 NOT BE DEEMED TO BE EXCLUSIVE, NAMELY:
 (5) EXHAUSTS. THE DISCHARGE INTO THE OPEN AIR OF THE
 EXHAUST OF ANY STEAM ENGINE, STATIONARY INTERNAL
 COMBUSTION ENGINE, OR MOTOR VEHICLE EXCEPT THROUGH A
 MUFFLER OR OTHER DEVICE WHICH WILL EFFECTIVELY PREVENT
 UNREASONABLY LOUD OR EXPLOSIVE NOISES THEREFROM.
  

Review Stop Z ZONING
Rev No 1 Status F Date 10-01-2020 Cont ID  
Sent By eschneid Date 10-01-2020 Time 11:10 Rev Time 5.00
Received By eschneid Date 10-01-2020 Time 11:10 Sent To  
Notes
2020-10-01 11:10:27CASE NO. PB1559M
 LA CLARA UTILITY AND ARRIVAL COURT CHANGES
 1515 S. FLAGLER
 COMMENTS REVISED 10/5/20
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446,
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY DECEMBER 5, 2020),
 THE PLANNING DIVISION MAY NOTIFY THE APPLICANT THAT THE
 CASE IS CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) SHEETS A114 AND A115 SHOW THE BUILDING ENCROACHING
 OUTSIDE OF THE NORTH SETBACK LINE AT THE TENANT STORAGE
 AND FIRE PUMP ROOMS AND YOGA ROOM AND GYM. SHEET A-001
 THAT WAS INCLUDED WITH THE BUILDING PERMIT, BUT NOT THE
 MINOR PD AMENDMENT CLEARLY SHOWS THIS DIMENSION AT 34
 FEET 5.75 INCHES, WHICH VIOLATES THE REQUIRED SETBACK
 OF 34 FEET 10 INCHES.
  
 2) THE CIVIL CROSS SECTION, THE SITE PLANS AND THE
 ELEVATIONS DO NOT SHOW THE SAME DIMENSIONS FOR THE REAR
 (WEST) PEDESTAL SETBACK. ALL PLANS NEED TO SHOW THE
 SAME, ACCURATE, COMPLIANT SETBACK DIMENSION.
  
 A. THE WESTERN ELEVATIONS SHOW THE LOUVER FOR THE
 MECHANICAL ROOM EXTENDING INTO THE REQUIRED SETBACK.
 BUILDING PERMIT PARTIAL WALL SECTION 1 A-527 SHOWS THE
 BOTTOM OF THE LOUVER RESTING ON THE GROUND, WHICH IS
 NOT PERMITTED AS A STRUCTURAL INTRUSION, BUT IS A
 SETBACK VIOLATION. THE LOUVER AT THIS LOCATION ALSO
 INVALIDATES THE STRUCTURAL INTRUSION OF THE ROOF
 ASSEMBLY.
  
 3) THE EAST ELEVATION DRAWING SHOWS SOMETHING, MOST
 LIKELY THE LOUVERED METAL SCREEN ON THE NORTH FACADE,
 EXTENDING INTO THE REQUIRED 34 FOOT 10 INCH SETBACK,
 WHICH IS NOT PERMITTED UNLESS IT IS PURELY A STRUCTURAL
 INTRUSION, WHICH MEANS IT IS NOT PERMITTED TO BE
 SUPPORTED ON THE GROUND OR ON A LOWER WALL (RETAINING,
 KNEE OR OTHERWISE). THE BUILDING PERMIT PLANS INCLUDE
 SECTION DRAWING 2 A-502 AND SHEETS S-102 AND S-721 AS
 WELL AS OTHER PLANS SHOWING THAT THE BOTTOM OF THE
 LOUVER RESTS ON THE GROUND, WHICH MEANS IT ENCROACHES
 INTO THE SETBACK AND IS NOT PERMITTED.
  
 4) ALONG THE SOUTHWEST PROPERTY LINE RETAINING WALL,
 PLEASE EXPLAIN WHY THE EXTERIOR GRADE IS NOW SHOWN AT
 14 FEET, WHEN IT WAS PREVIOUSLY SHOWN AT 11.5 FEET IN
 THE SAME LOCATION. THIS IS BOTH ON AND OFF SITE. YOU
 ARE NOT PERMITTED TO FILL THE NEIGHBOR?S PROPERTY AS
 PART OF THIS PERMIT APPLICATION.
  
 5) THE LANDSCAPE BASE PLAN NEEDS TO REFLECT THE SAME
 CONDITIONS AS THE CIVIL PLANS:
  
 A. SOUTHERN BUFFER AT WEST SIDE OF SITE SHOWS A
 STORMWATER LINE WITH THE ROYAL PALMS PLANTED ON TOP
 THAT IS NOT SHOWN ON THE CIVIL PLANS. WHICH PLAN IS
 ACCURATE?
  
 B. THE OLD RETAINING WALL LOCATION WAS NOT REMOVED FROM
 THE SOUTH PROPERTY LINE.
  
 C. THE NEW STORMWATER LINE ALONG THE SOUTHERN BUFFER
 NEEDS TO BE SHOWN. ONCE THIS IS CORRECTLY SHOWN WITH
 THE PROPOSED LANDSCAPE, THE PLANS WILL BE CIRCULATED TO
 THE CITY STORMWATER ENGINEER FOR REVIEW.
  
 D. THE NEW FPL EASEMENT AND DUCT BANK NEED TO BE SHOWN
 ALONG THE SOUTH, EAST AND NORTH PROPERTY LINES AND THE
 TREES ADJUSTED AS NEEDED.
  
 E. THERE IS A NEW FPL TRANSFORMER SHOWN ALONG ARKONA
 CT. ON THE UTILITY PLAN THAT IS NOT SHOWN ON THE
 LANDSCAPE PLAN. IT APPEARS THERE MAY BE CONFLICT WITH A
 TREE. ADDITIONALLY, THE SHRUB PLAN DOES NOT SHOW IT
 BEING SCREENED.
  
 F. THE ARRIVAL COURT DOES NOT MATCH THE SITE PLAN AT
 THE TURN AROUND SPACE.
  
 6) PARKING - THE BUILDING REQUIRES 181 PARKING SPACES.
 THE DATA TABLE SHOWS THAT 183 ARE PROVIDED (THIS
 EXCLUDES THE 11 REQUIRED PUBLIC PARKING SPACES ALONG
 ARKONA CT), WHICH IS NOT CORRECT AS PROVIDED BELOW.
  
 A. THE ON-STREET PARKING LINE ON SHEET A114 UNDER
 PARKING REQUIRED INCORRECTLY STATES THAT THE ORIGINAL
 MODERN APPROVAL HAD 13 ON-STREET PARKING SPACES. ONLY
 11 PARALLEL PARKING SPACES WERE REQUIRED TO BE PROVIDED
 FOR PUBLIC USE AS PART OF THAT APPROVAL, SO ONLY 11
 NEED TO BE MAINTAINED FOR PUBLIC USE AS PART OF THE
 CURRENT PROJECT. THE 2 ADDITIONAL PARALLEL PARKING
 SPACES THAT ARE PROVIDED MAY COUNT TOWARD MEETING THE
 LA CLARA PARKING REQUIREMENT AND BE MARKED AS LA CLARA
 PARKING ONLY. PLEASE REVISE ACCORDINGLY.
  
 B. BASEMENT PARKING SPACE 51(C) ON SHEET A113 DOES NOT
 HAVE THE REQUIRED 24 FOOT BACK-UP AND MAY NOT BE
 COUNTED AS A PARKING SPACE. THIS LOCATION MAY NOT BE
 INCLUDED AS A PARKING SPACE ON THE PLANS OR THE DATA
 TABLE. IT MAY BE DESIGNATED AS A VALET ONLY LOCATION.
  
 C. PARKING SPACES 58(C) AND 59(C) ON THE GROUND FLOOR
 PLAN (SHEET A114) ARE INCORRECTLY SHOWN AS HAVING A 30
 DEGREE ANGLE. THESE ARE 60 DEGREE SPACES AND THUS
 REQUIRE AN 18 FOOT DRIVE AISLE, WHICH IS NOT PROVIDED.
 ADDITIONALLY, SPACE 9(C) DOES NOT APPEAR TO HAVE AN 18
 FOOT WIDE DRIVE AISLE BEHIND IT DUE TO THE EXTENT OF
 SPACE 59(C). THIS RESULTS IN 3 ADDITIONAL PARKING
 SPACES NOT MEETING CODE AND NOT BEING ABLE TO BE USED
 TO MEET THE PARKING REQUIREMENTS.
  
 D. THE PARKING COUNT NOTE ON SHEET A114 SHOULD
 SPECIALLY BREAK OUT THE 4 PARKING SPACES THAT ARE ON
 THE ARRIVAL COURT AS PART OF THE 113 PARKING SPACE
 TOTAL. IT IS CONFUSING AS WRITTEN.
  
 E. PLEASE EXPLAIN WHY THERE IS A TURN AROUND SPACE AT
 THE ARRIVAL COURT. BASED ON THE TRAFFIC PATTERN, THERE
 IS NO NEED FOR ANYONE TO TURN AROUND. THIS COULD
 POSSIBLY BE REVISED INTO A PARKING SPOT OR TWO (MAY
 NEED TO BE COMPACT) TO MAKE UP FOR THE LOST SPOTS IN
 THE BASEMENT.
  
 F. WITH THE FOUR PARKING SPACES THAT MUST BE REMOVED
 FROM THE PARKING COUNT (BASEMENT 51, GROUND FLOOR 9, 58
 AND 59), THE SITE ONLY PROVIDES 179, NOT THE REQUIRED
 181 PARKING SPACES (EXCLUDING THE REQUIRED 11 ON-STREET
 PUBLIC PARKING SPACES).
  
 G. DUE TO THE LARGE (MOVING) TRUCK TURNING MOVEMENT,
 PARKING SPACES 1 - 4 ON SHEET A114 MUST BE LABELED AS
 EMPLOYEE PARKING. THESE SPACES MUST BE ABLE TO BE USED
 FOR MANEUVERING DURING LOADING IN/OUT.
  
 7) IS THERE AN OPPORTUNITY TO ADD CLEAR FENESTRATION ON
 THE NORTH SIDE OF THE PET GROOMING ROOM?
  
 8) EXPLAIN WHAT IS HAPPENING SOUTH OF THE ADMIN ROOM
 AND POOL RESTROOMS. THE LAST APPROVED PLAN HAD A 48
 FOOT 9 INCH SETBACK TO THE BUILDING AT THIS LOCATION.
 THE PROPOSED PLANS SHOW A REDUCED SETBACK OF 44 FEET 9
 INCHES.
  
 9) THE ROOF PLAN SHOWS A SECTION OF THE ROOF BEING
 RAISED TO 305 FEET 7 INCH NGVD (TOP OF STAIR TOWER?),
 YET THIS HEIGHT DIMENSION IS NOT REFLECTED ON THE
 ELEVATION DRAWINGS.
  
 10) THE SOUTHERN ELEVATION NEEDS TO BE ACCURATELY
 REPRESENTED ON THE PLANS. THE MATERIAL IS CALLED OUT
 BUT NOT SHOWN. THE CURRENTLY APPROVED PLANS SHOW A
 DECORATIVE TILE SCORED PATTERN. A DECORATIVE PATTERN IS
 REQUIRED. STAFF HAS STILL NOT SEEN THE DETAILS OF THE
 EXHAUST VENTS/LOUVERS TO VERIFY THAT THESE DO NOT
 VIOLATE THE DEVELOPMENT REGULATIONS. THESE NEED TO BE
 PROVIDED WITH THE RESUBMITTAL. ADDITIONALLY, NOT ALL
 THE EXHAUST LOUVERS ARE SHOWN. EX. THE GENERATOR.
  