Plan Review Details - Project Z20080005
Plan Review Stops For Project Z20080005
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-09-2020 Cont ID  
Sent By rbrown Date 09-09-2020 Time 20:06 Rev Time 0.00
Received By rbrown Date 09-09-2020 Time 20:06 Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 03-15-2021 Cont ID  
Sent By rrossano Date 03-15-2021 Time   Rev Time 0.00
Received By rrossano Date 03-15-2021 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 01-26-2021 Cont ID  
Sent By RROSSANO Date 01-26-2021 Time   Rev Time 0.00
Received By rrossano Date 01-26-2021 Time   Sent To  
Notes
2021-01-26 12:39:19ADDITIONAL COMMENTS FROM MARK HURLEY, FIELD CUSTOMER
 SERVICE SUPERVISOR
 ? CREATE A SEPARATE WATER OR UTILITY PLAN SHOWING
 EXISTING AND PROPOSED WATER SERVICES.
 RESPONSE: EXISTING UTILITIES ARE DEPICTED ON DRAWING
 E-GMY02 (SHEET 2 OF 2) FENCE FILL AND GRADE
 PLAN. NO WATER OR SEWER WORK IS PROPOSED AS PART OF THE
 PROPOSED SUBSTATION EXPANSION EXCEPT FOR
 RAISING ONSITE EXISTING SANITARY CLEANOUTS TO MATCH THE
 PROPOSED GRADE OF THE ACCESS DRIVE. THUS, A
 SEPARATE WATER AND SEWER PLAN IS NOT PROVIDED.
  
 -FOLLOWUP COMMENT TO RESPONSE: CANNOT CLEARLY SEE WATER
 METER BOX AND BACKFLOW ASSEMBLY ON E-GMY02 (SHEET 2).
 PLEASE DRAW AND LABEL THEM ON PLAN SO THEY ARE CLEARLY
 VISIBLE AND IN THE CORRECT LOCATION.
  
 EXISTING WATER METER HAS HISTORICALLY REMAINED OUTSIDE
 OF FENCE AND NEEDS TO CONTINUE
 REMAINING OUTSIDE OF ANY FENCES AND ACCESSIBLE FROM THE
 STREET. CAN RELOCATED FENCE AROUND IT
 OR RELOCATE WATER SERVICE/METER.
 RESPONSE: PER EMAIL CORRESPONDENCE WITH MR. MARK HURLEY
 ON SEPTEMBER 22, 2020, THE EXISTING
 METER IS RADIO READ EACH MONTH WITH THE READING
 LOCATION ACCESSIBLE FROM OUTSIDE OF THE EXISTING
 PERIMETER CHAIN LINK FENCE.
  
 -FOLLOWUP COMMENT TO RESPONSE: FIELD INSPECTION
 VERIFIED THAT CHAIN LINK FENCE IS CURRENTLY RUNNING
 OVER METER BOX SUCH THAT THE BOX, LID, AND METER CANNOT
 BE PROPERLY MAINTAINED. AS PART OF THIS PROJECT,
 REQUESTING THAT EXISTING CHAIN LINK FENCE BE ALTERED
 AROUND METER BOX SO THAT IT IS ACCESSIBLE FOR
 MAINTENANCE. IF THE ENTIRE FENCE IS BEING REPLACED, THE
 NEW FENCE NEEDS TO NOT RUN OVER METER BOX AND ALLOW
 COMPLETE ACCESS FROM EXTERIOR.
  
 VERIFY IF THE EXISTING WATER SERVICE AND METER IS FOR
 4301 UP THE GROVE LANE OR 5959 N
 MILITARY TRAIL. DOES 4301 NEED CITY WATER AND CURRENTLY
 USE ANY.
 RESPONSE: THE EXISTING WATER SERVICE AND METER ARE FOR
 4301 (THE GRAMERCY SUBSTATION) WHICH HAS
 A SINGLE RESTROOM WITH A TOILET AND SINK. THE GRAMERCY
 SUBSTATION IS AND UNMANNED RESTRICTED
 ACCESS FACILITY WITH FPL TWO-MAN MAINTENANCE CREWS
 AVERAGE TWO TRIPS PER MONTH TO THIS FACILITY,
 SO THE WATER USE IN MINIMAL.
  
 -FOLLOWUP COMMENT TO RESPONSE: THE EXISTING WATER METER
 IS 1.5INCH AND ADDRESSED AS 5950 N MILITARY TRL IN OUR
 UTILITY BILLING SYSTEM. THE LAST MONTH BILLING CYCLE
 REGISTERED ALMOST 3000 GALLONS OF WATER USED VS. THE
 ESTIMATE OF 200 GALLONS PER MONTH ADVISED IN OTHER
 RESPONSES. PLEASE CHECK THIS AGAIN AND FIELD VERIFY
 THAT THIS WATER SERVICE IS NOT FEEDING 5950 N MILITARY
 TRL PROPERTY. THIS COULD POTENTIALLY BE DONE BY
 SHUTTING OFF THE BACKFLOW ASSEMBLY OR METER AND SEEING
 WHICH BUILDINGS HAVE WATER.
  
 UTILITY EASEMENT MUST BE GRANTED FOR WATER SERVICE AND
 METER BOX ON PROPERTY IF NONE EXIST.
 RESPONSE: PER EMAIL CORRESPONDENCE WITH MR. MARK HURLEY
 ON SEPTEMBER 22, 2020, THE EXISTING
 METER IS RADIO READ EACH MONTH WITH THE READING
 LOCATION ACCESSIBLE FROM OUTSIDE OF THE EXISTING
 PERIMETER CHAIN LINK FENCE.
  
 -FOLLOWUP COMMENT TO RESPONSE: RADIO-READING IS
 SEPARATE FROM UTILITY ACCESS ISSUES. FIELD INSPECTION
 FOUND THAT THE CHAIN FENCE RUNS OVER THE METER BOX
 IMPEDING MAINTENANCE ACTIVITIES. CANNOT LOCATE METER
 BOX ON PLAN E-GMY02, BUT IT APPEARS THAT THE METER BOX
 IS SLIGHTLY INSIDE THE PROPERTY LINE. IF SO, THEN METER
 BOX NEEDS SMALL UTILITY EASEMENT GRANTED AROUND IT.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 09-03-2020 Cont ID  
Sent By rrossano Date 09-03-2020 Time   Rev Time  
Received By rrossano Date 09-03-2020 Time   Sent To  
Notes
2020-09-03 09:45:43COMMENTS PER RICK ROSSANO, PROJECT COORD., CITY OF WPB
 ENG. SERVICES, 561-494-1098:
  
 1. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 2. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 3. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 4. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER IF ANY (AVERAGE,
 MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS
 SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008
 FOR WATER.
 5. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 6. PLEASE SHOW INLET PROTECTION FOR THE DRAINAGE INLET
 ON THE SOUTH SIDE OF UP THE GROVE LN. DIRECTLY ACROSS
 FROM THE PROPOSED DRIVEWAY WORK.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -CREATE SEPARATE WATER OR UTILITY PLAN SHOWING EXISTING
 AND PROPOSED WATER SERVICES.
  
 -EXISTING WATER METER HAS HISTORICALLY REMAINED OUTSIDE
 OF FENCE AND NEEDS TO CONTINUE REMAINING OUTSIDE OF ANY
 FENCES AND ACCESSIBLE FROM THE STREET. CAN RELOCATE
 FENCE AROUND IT OR RELOCATE WATER SERVICE/METER.
  
 -DEMO PLAN SHOWS AN UNDERGROUND VAULT ADJACENT WATER
 METER BOX. IF THAT CONTAINS AN UNDERGROUND BACKFLOW
 ASSEMBLY IT MUST BE CONVERTED TO ABOVE-GROUND
 INSTALLATION AND BROUGHT UP TO STANDARDS.
  
 -VERIFY WHERE BACKFLOW ASSEMBLY FOR EXISTING WATER
 SERVICE IS LOCATED.
  
 -VERIFY IF THE EXISTING WATER SERVICE AND METER IS FOR
 4301 UP THE GROVE OR 5950 N MILITARY TRL. DOES 4301
 NEED CITY WATER AND CURRENTLY USE ANY?
  
 -UTILITY EASEMENT MUST BE GRANTED FOR WATER SERVICE AND
 METER BOX ON PROPERTY IF NONE CURRENTLY EXIST.
  
 -APPEARS SOMETHING TRIANGULAR AND LARGE IS BEING BUILT
 ON AND AROUND THE WATER SERVICE. PLEASE ADVISE WHAT
 THIS IS. IF THIS IS SOME KIND OF WATER RETENTION AREA,
 WATER METER AND BACKFLOW ASSEMBLY WOULD HAVE TO BE
 RELOCATED OUT OF THE AREA. STRUCTURES ALSO MAY NOT
 ENCROACH ON WATER SERVICES AND METER BOXES.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 09-09-2020 Cont ID  
Sent By pleduc Date 09-09-2020 Time   Rev Time 0.00
Received By pleduc Date 09-09-2020 Time 08:55 Sent To  
Notes
2020-09-09 09:41:58THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1) IT IS RECOMMENDED THAT FOR ANY PROPOSED GATE ACCESS
 POINTS THAT A KNOX PACLOCK BE PROVIDED FOR FD EMERGENCY
 ACCESS.
  
 2) THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 3). THE BUREAU SHALL REVIEW ANY SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 04-01-2021 Cont ID  
Sent By rcaranci Date 04-01-2021 Time 10:25 Rev Time 0.00
Received By rcaranci Date 04-01-2021 Time 10:25 Sent To  
Notes
2021-04-01 10:27:15FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FPL DSI SUBSTATION EXPANSION Z20080005
 APRIL 1, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A COMPLETE TREE SURVEY THAT
 INCLUDES ALL TREES ON THE PROPERTY AND PROVIDE A TREE
 DISPOSITION LIST AND PLAN IDENTIFYING ALL SPECIES AND
 WHETHER TREES WILL REMAIN, BE RELOCATED OR REMOVED.
 INCLUDE COLUMNS FOR CONDITION RATING AND TREE CANOPY
 DIAMETER.
 CANOPY SPREAD IN CHART NEEDS TO BE CHANGED TO CANOPY
 DIAMETER. THE LISTED NUMBERS APPEAR TO BE RADIUS FROM
 THE TREE SURVEY, SO NEED TO BE DOUBLED TO CORRECTLY
 REFLECT DIAMETER.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS.
 SUPPLY ARBORIST INFORMATION ON RELOCATION POTENTIAL, AS
 ALL TREES ARE LISTED IN GOOD CONDITION. TREES DO NOT
 HAVE TO BE RELOCATED TO THE SAME PARCEL, THERE MAY BE
 OTHER AREAS OF THE DSI WHERE TREES CAN BE ACCOMMODATED.
 PER THE PLANNING AND ZONING ADMINISTRATOR, THE REMOVAL
 AND MITIGATION BY PAYMENT IN LIEU IS GRANTED DUE TO THE
 NATURE OF THE USE OF THE SURROUNDING AREA AND THE
 UTILITY RESTRICTIONS.
 3. SATISFIED. PROVIDE THE CALCULATIONS FOR ANY
 MITIGATION DUE FOR REMOVED TREES AND PROVIDE
 CALCULATIONS OF MITIGATION TREE CANOPY PROPOSED.
 MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION
 TABLE:
 ? SATISFIED. CANOPY DIAMETERS LESS THAN 20 FEET ARE TO
 SHOW THE MITIGATION DUE AS THE CATEGORY SQUARE FOOTAGE
 ON A ONE TO ONE BASIS. CYPRESS, MAHOGANY, GREEN
 BUTTONWOOD, LAUREL OAK AND LIVE OAK ARE ALL CATEGORY 1,
 SO WOULD BE 300 SQUARE FEET EACH DUE. SILVER BUTTONWOOD
 IS CATEGORY 2, SO WOULD BE 150 SQ FT EACH DUE.
 ? SATISFIED. CANOPY DIAMETERS OF 20 FEET OR MORE MUST
 BE CALCULATED FOR ACTUAL SQUARE FOOTAGE OF CANOPY. IF
 THEY CANNOT BE RELOCATED PER COMMENT 2, THERE APPEAR TO
 BE 9 TREES THAT WOULD FALL IN THIS CATEGORY.
 ? SATISFIED. TOTALS OF MITIGATION DUE NEED TO BE
 INCLUDED ON CHART.
 ? SATISFIED. TOTALS OF MITIGATION CREDITS NEED TO BE
 CALCULATED BASED ON THE PLANT LIST BY CATEGORY AND
 TOTAL PROVIDED.
 PROPOSED OFF SITE TREES CANNOT BE COUNTED TOWARD
 MITIGATION. OPTIONS ARE TO PLACE THE TREES ON THE SITE
 OR PAYMENT IN LIEU.
  
 4. SATISFIED. PROVIDE A LANDSCAPE PLAN MEETING ALL THE
 REQUIREMENTS OF SECTION 94-442 (B), INCLUDING A
 COMPLETE PLANT LIST.
  
 5. SATISFIED. ADD EXISTING AND RELOCATED TREES OR PALMS
 TO THE FINAL PLANT LIST AND COUNT THEM TOWARD THE
 REQUIRED TREES.
  
 6. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED TREES
 BASED ON 40% REQUIRED OPEN SPACE AND SHOW THE TOTAL
 TREES PROVIDED.
  
 7. SATISFIED. INDICATE THE REQUIRED 5 FOOT PERIMETER
 LANDSCAPE BUFFER ON THE SITE AND LANDSCAPE PLANS.
  
 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED BUFFER
 TREES AT ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR
 EACH PROPERTY LINE SEGMENT, AND SHOW THE NUMBER
 PROVIDED PER SECTION 94-443. A CONTINUOUS HEDGE SHALL
 BE PROVIDED IN THE BUFFERS TO PROVIDE SCREENING.
 INDICATE EXISTING HEDGES.
  
  
 9. SATISFIED. THE DRAINAGE AREAS AS INDICATED DO NOT
 TAKE INTO CONSIDERATION THE ROOT SYSTEMS OF THE
 EXISTING TREES AT THE PERIMETER OF THE PROPERTY. DESIGN
 SHOULD BE ADJUSTED TO AVOID DESTRUCTION OF ROOT SYSTEMS
 AND HARM TO THE EXISTING TREES.
  
 10. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY
 POINTS BASED ON THE FINAL PLANT LIST PER SECTION
 94-443(G).
  
 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION. PAYMENT IN LIEU
 WILL BE MADE FOR 10,667 SQ FT OF TREE CANOPY
 REPLACEMENT DUE AT THE TIME OF PERMIT ISSUANCE.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 03-23-2021 Cont ID  
Sent By rcaranci Date 03-23-2021 Time 13:31 Rev Time 0.00
Received By rcaranci Date 03-23-2021 Time 13:31 Sent To  
Notes
2021-03-23 13:32:20FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FPL DSI SUBSTATION EXPANSION Z20080005
 MARCH 23, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A COMPLETE TREE SURVEY THAT
 INCLUDES ALL TREES ON THE PROPERTY AND PROVIDE A TREE
 DISPOSITION LIST AND PLAN IDENTIFYING ALL SPECIES AND
 WHETHER TREES WILL REMAIN, BE RELOCATED OR REMOVED.
 INCLUDE COLUMNS FOR CONDITION RATING AND TREE CANOPY
 DIAMETER.
 CANOPY SPREAD IN CHART NEEDS TO BE CHANGED TO CANOPY
 DIAMETER. THE LISTED NUMBERS APPEAR TO BE RADIUS FROM
 THE TREE SURVEY, SO NEED TO BE DOUBLED TO CORRECTLY
 REFLECT DIAMETER.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS.
 SUPPLY ARBORIST INFORMATION ON RELOCATION POTENTIAL, AS
 ALL TREES ARE LISTED IN GOOD CONDITION. TREES DO NOT
 HAVE TO BE RELOCATED TO THE SAME PARCEL, THERE MAY BE
 OTHER AREAS OF THE DSI WHERE TREES CAN BE ACCOMMODATED.
 PER THE PLANNING AND ZONING ADMINISTRATOR, THE REMOVAL
 AND MITIGATION BY PAYMENT IN LIEU IS GRANTED DUE TO THE
 NATURE OF THE USE OF THE SURROUNDING AREA AND THE
 UTILITY RESTRICTIONS.
 3. PARTIALLY SATISFIED. PROVIDE THE CALCULATIONS FOR
 ANY MITIGATION DUE FOR REMOVED TREES AND PROVIDE
 CALCULATIONS OF MITIGATION TREE CANOPY PROPOSED.
 MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION
 TABLE:
 ? SATISFIED. CANOPY DIAMETERS LESS THAN 20 FEET ARE TO
 SHOW THE MITIGATION DUE AS THE CATEGORY SQUARE FOOTAGE
 ON A ONE TO ONE BASIS. CYPRESS, MAHOGANY, GREEN
 BUTTONWOOD, LAUREL OAK AND LIVE OAK ARE ALL CATEGORY 1,
 SO WOULD BE 300 SQUARE FEET EACH DUE. SILVER BUTTONWOOD
 IS CATEGORY 2, SO WOULD BE 150 SQ FT EACH DUE.
 ? SATISFIED. CANOPY DIAMETERS OF 20 FEET OR MORE MUST
 BE CALCULATED FOR ACTUAL SQUARE FOOTAGE OF CANOPY. IF
 THEY CANNOT BE RELOCATED PER COMMENT 2, THERE APPEAR TO
 BE 9 TREES THAT WOULD FALL IN THIS CATEGORY.
 ? SATISFIED. TOTALS OF MITIGATION DUE NEED TO BE
 INCLUDED ON CHART.
 ? PARTIALLY SATISFIED. TOTALS OF MITIGATION CREDITS
 NEED TO BE CALCULATED BASED ON THE PLANT LIST BY
 CATEGORY AND TOTAL PROVIDED.
 PROPOSED OFF SITE TREES CANNOT BE COUNTED TOWARD
 MITIGATION. OPTIONS ARE TO PLACE THE TREES ON THE SITE
 OR PAYMENT IN LIEU.
  
 4. SATISFIED. PROVIDE A LANDSCAPE PLAN MEETING ALL THE
 REQUIREMENTS OF SECTION 94-442 (B), INCLUDING A
 COMPLETE PLANT LIST.
  
 5. SATISFIED. ADD EXISTING AND RELOCATED TREES OR PALMS
 TO THE FINAL PLANT LIST AND COUNT THEM TOWARD THE
 REQUIRED TREES.
  
 6. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED TREES
 BASED ON 40% REQUIRED OPEN SPACE AND SHOW THE TOTAL
 TREES PROVIDED.
  
 7. SATISFIED. INDICATE THE REQUIRED 5 FOOT PERIMETER
 LANDSCAPE BUFFER ON THE SITE AND LANDSCAPE PLANS.
  
 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED BUFFER
 TREES AT ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR
 EACH PROPERTY LINE SEGMENT, AND SHOW THE NUMBER
 PROVIDED PER SECTION 94-443. A CONTINUOUS HEDGE SHALL
 BE PROVIDED IN THE BUFFERS TO PROVIDE SCREENING.
 INDICATE EXISTING HEDGES.
  
  
 9. SATISFIED. THE DRAINAGE AREAS AS INDICATED DO NOT
 TAKE INTO CONSIDERATION THE ROOT SYSTEMS OF THE
 EXISTING TREES AT THE PERIMETER OF THE PROPERTY. DESIGN
 SHOULD BE ADJUSTED TO AVOID DESTRUCTION OF ROOT SYSTEMS
 AND HARM TO THE EXISTING TREES.
  
 10. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY
 POINTS BASED ON THE FINAL PLANT LIST PER SECTION
 94-443(G).
  
 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 01-27-2021 Cont ID  
Sent By rcaranci Date 01-27-2021 Time 14:09 Rev Time 0.00
Received By rcaranci Date 01-27-2021 Time 14:08 Sent To  
Notes
2021-01-27 14:16:24FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FPL DSI SUBSTATION EXPANSION Z20080005
 JANUARY 26, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PARTIALLY SATISFIED. PROVIDE A COMPLETE TREE SURVEY
 THAT INCLUDES ALL TREES ON THE PROPERTY AND PROVIDE A
 TREE DISPOSITION LIST AND PLAN IDENTIFYING ALL SPECIES
 AND WHETHER TREES WILL REMAIN, BE RELOCATED OR REMOVED.
 INCLUDE COLUMNS FOR CONDITION RATING AND TREE CANOPY
 DIAMETER.
 CANOPY SPREAD IN CHART NEEDS TO BE CHANGED TO CANOPY
 DIAMETER. THE LISTED NUMBERS APPEAR TO BE RADIUS FROM
 THE TREE SURVEY, SO NEED TO BE DOUBLED TO CORRECTLY
 REFLECT DIAMETER.
  
 2. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES
 NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE
 OR RELOCATED. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR FOR RELOCATION. PROVIDE RELOCATION POTENTIAL FOR
 THE NATIVE TREES AND PALMS.
 SUPPLY ARBORIST INFORMATION ON RELOCATION POTENTIAL, AS
 ALL TREES ARE LISTED IN GOOD CONDITION. TREES DO NOT
 HAVE TO BE RELOCATED TO THE SAME PARCEL, THERE MAY BE
 OTHER AREAS OF THE DSI WHERE TREES CAN BE ACCOMMODATED.
 3. PARTIALLY SATISFIED. PROVIDE THE CALCULATIONS FOR
 ANY MITIGATION DUE FOR REMOVED TREES AND PROVIDE
 CALCULATIONS OF MITIGATION TREE CANOPY PROPOSED.
 MAKE THE FOLLOWING CORRECTIONS TO THE TREE MITIGATION
 TABLE:
 ? CANOPY DIAMETERS LESS THAN 20 FEET ARE TO SHOW THE
 MITIGATION DUE AS THE CATEGORY SQUARE FOOTAGE ON A ONE
 TO ONE BASIS. CYPRESS, MAHOGANY, GREEN BUTTONWOOD,
 LAUREL OAK AND LIVE OAK ARE ALL CATEGORY 1, SO WOULD BE
 300 SQUARE FEET EACH DUE. SILVER BUTTONWOOD IS CATEGORY
 2, SO WOULD BE 150 SQ FT EACH DUE.
 ? CANOPY DIAMETERS OF 20 FEET OR MORE MUST BE
 CALCULATED FOR ACTUAL SQUARE FOOTAGE OF CANOPY. IF THEY
 CANNOT BE RELOCATED PER COMMENT 2, THERE APPEAR TO BE 9
 TREES THAT WOULD FALL IN THIS CATEGORY.
 ? TOTALS OF MITIGATION DUE NEED TO BE INCLUDED ON
 CHART.
 ? TOTALS OF MITIGATION CREDITS NEED TO BE CALCULATED
 BASED ON THE PLANT LIST BY CATEGORY AND TOTAL PROVIDED.
  
 4. SATISFIED. PROVIDE A LANDSCAPE PLAN MEETING ALL THE
 REQUIREMENTS OF SECTION 94-442 (B), INCLUDING A
 COMPLETE PLANT LIST.
  
 5. SATISFIED. ADD EXISTING AND RELOCATED TREES OR PALMS
 TO THE FINAL PLANT LIST AND COUNT THEM TOWARD THE
 REQUIRED TREES.
  
 6. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED TREES
 BASED ON 40% REQUIRED OPEN SPACE AND SHOW THE TOTAL
 TREES PROVIDED.
  
 7. SATISFIED. INDICATE THE REQUIRED 5 FOOT PERIMETER
 LANDSCAPE BUFFER ON THE SITE AND LANDSCAPE PLANS.
  
 8. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED BUFFER
 TREES AT ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR
 EACH PROPERTY LINE SEGMENT, AND SHOW THE NUMBER
 PROVIDED PER SECTION 94-443. A CONTINUOUS HEDGE SHALL
 BE PROVIDED IN THE BUFFERS TO PROVIDE SCREENING.
 INDICATE EXISTING HEDGES.
  
  
 9. SATISFIED. THE DRAINAGE AREAS AS INDICATED DO NOT
 TAKE INTO CONSIDERATION THE ROOT SYSTEMS OF THE
 EXISTING TREES AT THE PERIMETER OF THE PROPERTY. DESIGN
 SHOULD BE ADJUSTED TO AVOID DESTRUCTION OF ROOT SYSTEMS
 AND HARM TO THE EXISTING TREES.
  
 10. SATISFIED. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY
 POINTS BASED ON THE FINAL PLANT LIST PER SECTION
 94-443(G).
  
 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED
 ON THE PLANT LIST.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 09-08-2020 Cont ID  
Sent By rcaranci Date 09-08-2020 Time 14:24 Rev Time 0.00
Received By rcaranci Date 09-08-2020 Time 14:24 Sent To  
Notes
2020-09-08 14:25:21FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: FPL DSI SUBSTATION EXPANSION Z20080005
 SEPTEMBER 8, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE A COMPLETE TREE SURVEY THAT INCLUDES ALL
 TREES ON THE PROPERTY AND PROVIDE A TREE DISPOSITION
 LIST AND PLAN IDENTIFYING ALL SPECIES AND WHETHER TREES
 WILL REMAIN, BE RELOCATED OR REMOVED. INCLUDE COLUMNS
 FOR CONDITION RATING AND TREE CANOPY DIAMETER.
 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD
 CONDITION TO BE PRESERVED ON SITE OR RELOCATED. ANSI A
 300 (PART 5) STANDARDS SPECIFY EXAMPLES OF SUITABILITY
 RATINGS OF GOOD, MODERATE, OR POOR FOR RELOCATION.
 PROVIDE RELOCATION POTENTIAL FOR THE NATIVE TREES AND
 PALMS.
 3. PROVIDE THE CALCULATIONS FOR ANY MITIGATION DUE FOR
 REMOVED TREES AND PROVIDE CALCULATIONS OF MITIGATION
 TREE CANOPY PROPOSED.
  
 4. PROVIDE A LANDSCAPE PLAN MEETING ALL THE
 REQUIREMENTS OF SECTION 94-442 (B), INCLUDING A
 COMPLETE PLANT LIST.
  
 5. ADD EXISTING AND RELOCATED TREES OR PALMS TO THE
 FINAL PLANT LIST AND COUNT THEM TOWARD THE REQUIRED
 TREES.
  
 6. PROVIDE CALCULATIONS FOR REQUIRED TREES BASED ON 40%
 REQUIRED OPEN SPACE AND SHOW THE TOTAL TREES PROVIDED.
  
 7. INDICATE THE REQUIRED 5 FOOT PERIMETER LANDSCAPE
 BUFFER ON THE SITE AND LANDSCAPE PLANS.
  
 8. PROVIDE CALCULATIONS FOR REQUIRED BUFFER TREES AT
 ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR EACH
 PROPERTY LINE SEGMENT, AND SHOW THE NUMBER PROVIDED PER
 SECTION 94-443. A CONTINUOUS HEDGE SHALL BE PROVIDED IN
 THE BUFFERS TO PROVIDE SCREENING. INDICATE EXISTING
 HEDGES.
  
  
 9. THE DRAINAGE AREAS AS INDICATED DO NOT TAKE INTO
 CONSIDERATION THE ROOT SYSTEMS OF THE EXISTING TREES AT
 THE PERIMETER OF THE PROPERTY. DESIGN SHOULD BE
 ADJUSTED TO AVOID DESTRUCTION OF ROOT SYSTEMS AND HARM
 TO THE EXISTING TREES.
  
 10. PROVIDE THE 50 REQUIRED FLORIDA FRIENDLY POINTS
 BASED ON THE FINAL PLANT LIST PER SECTION 94-443(G).
  
 11. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. PROVIDE THE ACTUAL PERCENTAGE BASED ON THE
 PLANT LIST.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 09-08-2020 Cont ID  
Sent By   Date 09-08-2020 Time   Rev Time  
Received By   Date 09-08-2020 Time   Sent To  
Notes
2020-09-08 17:09:34NO COMMENTS.

Review Stop STORM STORMWATER
Rev No 2 Status P Date 01-26-2021 Cont ID  
Sent By tward Date 01-26-2021 Time 11:50 Rev Time 0.00
Received By tward Date 01-26-2021 Time 11:55 Sent To  
Notes
2021-01-26 11:55:21COMMENTS ON THE 1-15-2021 SUBMITTAL PACKAGE:
  
 1. CONSIDER SWITCHING GENERAL NOTES #4 AND #9 ON SHEET
 E-GMY01J (JURISDICTIONAL SITE PLAN) SO THAT NOTE #9
 WILL REFER TO THE FENCE INSTEAD OF THE FLOOD ZONE.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)

Review Stop STORM STORMWATER
Rev No 1 Status F Date 09-10-2020 Cont ID  
Sent By tward Date 09-10-2020 Time 16:55 Rev Time 0.00
Received By tward Date 09-10-2020 Time 16:58 Sent To  
Notes
2020-09-10 16:58:11THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. ON THE CIVIL PLANS, LIST THE VERTICAL DATUM ON EVERY
 SHEET THAT HAS ELEVATION DATA AND INCLUDE THE
 CONVERSTION EQUATION BETWEEN NAVD1988 AND NGVD1929.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3.. PROVIDE SFWMD ERP PERMIT MODIFICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 09-08-2020 Cont ID  
Sent By vnoel Date 09-08-2020 Time 11:24 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2020-09-08 11:24:45NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 01-19-2021 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date 01-27-2021 Time   Sent To  
Notes
2021-01-27 09:39:18TRAFFIC ENGINEERING
  
 NO FURTHER COMMENTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 09-10-2020 Cont ID  
Sent By   Date 09-10-2020 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2020-09-10 12:59:05TRAFFIC COMMENTS:
  
 1) INSTALL STOP SIGN AND STOP BAR AT THE DRIVEWAY
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 03-12-2021 Cont ID  
Sent By llouie Date 03-12-2021 Time   Rev Time 0.00
Received By llouie Date 03-12-2021 Time   Sent To  
Notes
2021-03-12 11:19:43PER DISCUSSIONS WITH AVANN, P&Z ADMINISTRATOR, THE
 PROPOSED USE OF 6 STRANDS OF BARBED WIRE ON V ARMS IS
 PERMITTED FOR THE PROJECT, AS IT IS CURRENTLY EXISTING
 WITHIN OTHER AREAS OF THE FPL SITE AND IT IS NECESSARY
 FOR SAFETY, PROVIDED THAT THE ARMS DO NOT EXTEND BEYOND
 THE PROPERTY LINES.

Review Stop Z ZONING
Rev No 2 Status F Date 01-20-2021 Cont ID  
Sent By llouie Date 01-20-2021 Time   Rev Time 0.00
Received By llouie Date 01-20-2021 Time   Sent To  
Notes
2021-01-20 10:47:41SITE PLAN COMMENTS:
  
 1.) NO MORE THAN THREE STRANDS OF BARBED WIRE MAY BE
 USED AT THE TOP OF A FENCE/WALL. THE STRANDS MUST BE
 LOCATED AT LEAST 6 FT. ABOVE GRADE OR MOUNTED
 VERTICALLY OR AT AN ANGLE PROJECTING INTERIOR TO THE
 PROPERTY AND MUST NOT ENCROACH BEYOND THE PROPERTY
 LINE. ACCORDING TO A NOTE IN THE PLANS, THERE WILL BE
 SIX STRANDS OF BARBED WIRE, WHICH IS NOT PERMITTED.
 ALSO, PROVIDE A DETAIL TO DEMONSTRATE COMPLIANCE WITH
 THE REQUIREMENTS FOR A BARBED WIRE FENCE. [ZLDR S.
 94-302(C)(2)]
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE YOUR RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES, ONE REDUCED COPY IN 11 INCHES X 17
 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS AND
 DOCUMENTS.
  
 * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE NOT TO BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($60.00).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 09-08-2020 Cont ID  
Sent By llouie Date 09-08-2020 Time   Rev Time  
Received By llouie Date 09-08-2020 Time   Sent To  
Notes
2020-09-08 10:56:25SITE PLAN COMMENTS:
  
 1.) WHAT IS THE SETBACK DISTANCE FROM THE EDGE OF THE
 EXTENDED YARD AREA TO THE PROPERTY LINE(S)? PLEASE
 PROVIDE THE DIMENSION(S) IN THE PLAN.
  
 2.) WHAT IS THE HEIGHT OF THE PROPOSED 5-LF FIBERGLASS
 ISOLATION FENCE, LOCATED ON THE SOUTH SIDE OF THE
 EXTENDED YARD? PLEASE PROVIDE THE HEIGHT INFORMATION IN
 THE PLAN.
  
 3.) PLEASE LABEL ALL EXISTING/PROPOSED DRY/WET
 DETENTION AREAS IN THE SITE PLAN
  
 4.) A CONTINUOUS 5 FT. WIDE LANDSCAPE BUFFER ALONG THE
 ENTIRE PERIMETER OF THE PROPERTY IS REQUIRED. [ZLDR
 S.94-443, TABLE XIV-1]
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF THREE
 (3) PAPER COPIES, ONE (1) REDUCED COPY IN 11 INCHES X
 17 INCHES, AND AN ELECTRONIC COPY OF ALL PLANS.
  
 * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY
 RESULT IN ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($60).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  