Plan Review Details - Project Z20070014
Plan Review Stops For Project Z20070014
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 08-12-2020 Cont ID  
Sent By rbrown Date 08-12-2020 Time 20:01 Rev Time 0.00
Received By rbrown Date 08-12-2020 Time 19:56 Sent To  
Notes
2020-08-12 20:10:01DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 14 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 3. NUMBER OF ACCESSIBLE PARKING SPACES. SITE PLAN SHEET
 SP.1 SHOWS A TOTAL OF 43 PROPOSED PARKING SPACES BUT
 SHOWS ONLY 1 ACCESSIBBLE PARKING SPACE. 2 ACCESSIBLE
 PARKING SPACES ARE REQUIRED. THE TOTAL MINIMUM NUMBER
 OF ACCESSIBLE PARKING SPACES PROVIDED SHALL BE IN
 ACCORDANCE WITH SECTION 208.2 OF FLORIDA ACCESSIBILITY
 CODE.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION
 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING
 SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 5. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 CAROLINE PUELL, ADDRESSING COORDINATOR, AT (561) 805
 6659, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 01-28-2021 Cont ID  
Sent By rrossano Date 01-28-2021 Time   Rev Time 0.00
Received By rrossano Date 01-28-2021 Time   Sent To  
Notes
2021-01-28 09:54:25PLEASE PROVIDE WRITTEN RESPONSES TO THE FOLLOWING PRIOR
 COMMENTS:
  
 -ON CIVIL PLANS WHERE THE EASTERN PART OF THE PROPERTY
 ADJACENT TO BRANDYWINE IS SHOWN (C-400 ENGINEERING PLAN
 ? MATCHLINE SECTION NEAR WATER METER), PLEASE MAKE
 PROPERTY LINE VISIBLE AND LABEL IT.
  
 -ADDITIONAL UTILITY EASEMENTS MAY BE NEEDED UPON REVIEW
 DURING FORMAL ENGINEERING SUBMITTAL.
  
 -THE SETUP OF THE EXISTING FIRELINE AND FIRE HYDRANT IS
 UNUSUAL. DURING FORMAL ENGINEERING SUBMITTAL,
 ADDITIONAL FEEDBACK OR DIRECTION MAY BE PROVIDED.
  
  
  
 RESPECTFULLY,
  
 MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 03-08-2021 Cont ID  
Sent By rrossano Date 03-08-2021 Time   Rev Time 0.00
Received By rrossano Date 03-08-2021 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 12-04-2020 Cont ID  
Sent By rrossano Date 12-04-2020 Time   Rev Time 0.00
Received By rrossano Date 12-04-2020 Time   Sent To  
Notes
2020-12-04 08:19:35THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -CLARIFY IF THE 10FT UE FOR FIRELINE IS EXISTING OR
 PROPOSED.
 -ON CIVIL PLANS WHERE THE EASTERN PART OF THE PROPERTY
 ADJACENT TO BRANDYWINE IS SHOWN, PLEASE MAKE PROPERTY
 LINE VISIBLE AND LABEL IT.
 -ADDITIONAL UTILITY EASEMENTS MAY BE NEEDED UPON REVIEW
 DURING FORMAL ENGINEERING SUBMITTAL.
 -THE SETUP OF THE EXISTING FIRELINE AND FIRE HYDRANT IS
 UNUSUAL. DURING FORMAL ENGINEERING SUBMITTAL,
 ADDITIONAL FEEDBACK OR DIRECTION MAY BE PROVIDED.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT (561) 494-1098 [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 08-06-2020 Cont ID  
Sent By rrossano Date 08-06-2020 Time   Rev Time  
Received By rrossano Date 08-06-2020 Time   Sent To  
Notes
2020-08-06 09:29:091. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW: HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=
 ~\WPB_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION
 -FULL-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC0
 2A97B1960045731D3658206F27451722716EF
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBL
 IC-WORKS/FORMS,-PERMITS-APPLICATIONS
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 ROW.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 11. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 12. PLEASE PROVIDE ENLARGED VIEW ON PLANS OF PROPOSED
 LOCATION OF WATER METER AND BACKFLOW PREVENTION, IF
 ANY.
 13. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 14. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS AS
 NEEDED.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -WATER SERVICE SHOWN ON C-400 ENGINEERING PLAN IS ALL
 PRIVATE WATER PIPE. THE POINT OF SERVICE IS LIKELY THE
 1 IN. CITY WATER METER THAT IS ADJACENT BRANDYWINE RD.
 PROVIDE WATER DEMAND CALC. CHART ON THE PLAN TO ENSURE
 PROPERTY WILL HAVE SUFFICIENT WATER.
 -SEVERAL YEARS AGO WASTEWATER USE WAS TERMINATED AT THE
 LOCATION BECAUSE CUSTOMER SAID THEY WERE GOING TO
 RECYCLE THE WATER USED AT THE EQUIPMENT CLEANING
 STATION WITH A WATER FILTRATION BASIN. PLEASE SHOW ON
 PLAN WHERE THAT IS LOCATED AND VERIFY IF THAT WILL
 STILL BE USED FOR THE SITE WITH NO WASTEWATER GOING TO
 CITY.
 -NEED VERIFICATION THAT THE WATER SERVICE WILL NOT FEED
 FIRE SPINKLERS OR HYDRANTS.
 -PLEASE VERIFY THAT THE EXISTING WATER SERVICE PIPING
 ON C-400 IS POTABLE WATER PIPE RUNNING FROM CITY WATER
 SERVICE AND NOT NON-POTABLE WATER FROM WELLS OR
 SURROUNDING PUMPED GROUNDWATER.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 08-05-2020 Cont ID  
Sent By pleduc Date 08-05-2020 Time   Rev Time 0.00
Received By rrossano Date 08-05-2020 Time 15:22 Sent To  
Notes
2020-08-05 15:29:07THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE
 PROVIDED FOR RESPONSE PURPOSES:
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE.
  
 6A. PLEASE PROVIDE THE FETILILIZER TYPES, HOW IT IS
 PACKAGED, ANY PROPOSED RACKS, HOW HIGH ARE THE RACKS,
 SHELVING TYPE, PALLET TYPES, ETC.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 I COULD NOT IDENTIFY A FIRE HYDRANT ON THE SITE CIVIL
 PLAN. PLEASE PROVIDE THE LOCATION OF THE NEAREST FIRE
 HYDRANT.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT.
  
 9A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND
 SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL,
 THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND
 THE CITY'S PLANNING AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 GATES LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S COMMENTS OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 03-11-2021 Cont ID  
Sent By rcaranci Date 03-11-2021 Time 09:42 Rev Time 0.00
Received By rcaranci Date 03-11-2021 Time 09:42 Sent To  
Notes
2021-03-11 09:43:16FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BEAR LAKES COUNTRY CLUB Z20070014
 MARCH 11, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PREVIOUSLY SATISFIED.
  
 2. PREVIOUSLY SATISFIED.
  
 3. PREVIOUSLY SATISFIED.
  
 4. PREVIOUSLY SATISFIED.
  
 5. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 THIS COMMENT DID NOT RECEIVE A RESPONSE AS ANOTHER
 COMMENT APPEARED ON THE RESPONSE MEMO.
 RESPONSE WAS NOT CLEAR. LIGHTING IS NOT SHOWN ON SITE
 PLAN OR LANDSCAPE PLAN.
  
 6. SATISFIED. SHOW LOCATIONS OF ANY WATER AND SEWER
 LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 NEW TREES THAT ARE BEING ADDED.
  
 WATER AND SEWER LINES WERE NOT IN CONFLICT, BUT A
 DRAINAGE LINE IS SHOWN ON C-400 THAT IS PROPOSED
 DIRECTLY IN CONFLICT WITH THE NEW TREES REQUIRED FOR
 THE NEW PARKING ON THE NORTH SIDE OF THE AREA.
 OBVIOUSLY, THIS NEEDS TO BE RELOCATED AWAY FROM THE
 TREES.
 2/3/21 THE DRAINAGE STRUCTURES AND LINE ARE STILL
 DISPLACING THE REQUIRED TREES. RELOCATE THE DRAINAGE
 LINE AND STRUCTURES OUTSIDE THE LANDSCAPE ISLANDS.
  
 7. PREVIOUSLY SATISFIED.
  
 8. PREVIOUSLY SATISFIED.
  
  
 9. PREVIOUSLY SATISFIED.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 02-03-2021 Cont ID  
Sent By rcaranci Date 02-03-2021 Time 16:52 Rev Time 0.00
Received By rcaranci Date 02-03-2021 Time 16:52 Sent To  
Notes
2021-02-03 17:03:31FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BEAR LAKES COUNTRY CLUB Z20070014
 FEBRUARY 3, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PREVIOUSLY SATISFIED.
  
 2. PREVIOUSLY SATISFIED.
  
 3. PREVIOUSLY SATISFIED.
  
 4. PREVIOUSLY SATISFIED.
  
 5. NOT SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 THIS COMMENT DID NOT RECEIVE A RESPONSE AS ANOTHER
 COMMENT APPEARED ON THE RESPONSE MEMO.
 RESPONSE WAS NOT CLEAR. LIGHTING IS NOT SHOWN ON SITE
 PLAN OR LANDSCAPE PLAN.
  
 6. PARTIALLY SATISFIED. SHOW LOCATIONS OF ANY WATER AND
 SEWER LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS
 WITH NEW TREES THAT ARE BEING ADDED.
  
 WATER AND SEWER LINES WERE NOT IN CONFLICT, BUT A
 DRAINAGE LINE IS SHOWN ON C-400 THAT IS PROPOSED
 DIRECTLY IN CONFLICT WITH THE NEW TREES REQUIRED FOR
 THE NEW PARKING ON THE NORTH SIDE OF THE AREA.
 OBVIOUSLY, THIS NEEDS TO BE RELOCATED AWAY FROM THE
 TREES.
 2/3/21 THE DRAINAGE STRUCTURES AND LINE ARE STILL
 DISPLACING THE REQUIRED TREES. RELOCATE THE DRAINAGE
 LINE AND STRUCTURES OUTSIDE THE LANDSCAPE ISLANDS.
  
 7. PREVIOUSLY SATISFIED.
  
 8. PREVIOUSLY SATISFIED.
  
  
 9. PREVIOUSLY SATISFIED.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 11-19-2020 Cont ID  
Sent By rcaranci Date 11-19-2020 Time 13:15 Rev Time 0.00
Received By rcaranci Date 11-19-2020 Time 13:15 Sent To  
Notes
2020-11-19 13:15:54FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BEAR LAKES COUNTRY CLUB Z20070014
 NOVEMBER 19, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. ARECA PALMS ARE NOT CONSIDERED FULL SIZE
 PALMS THAT MUST BE MITIGATED. ADD A NOTE TO THE PLAN.
  
 2. SATISFIED. PROVIDE THE REQUIRED TREE IN THE TWO
 TERMINAL LANDSCAPE ISLANDS AT THE ENDS OF THE ROW OF
 NEW PARKING SPACES ALONG THE NORTH SIDE. PROVIDE THE
 REQUIRED INTERIOR LANDSCAPE ISLAND WITH REQUIRED TREE
 IN THE ROW OF PARKING SO THERE ARE NO MORE THAN 10
 PARKING SPACES IN A ROW.
  
 3. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS.
  
 4. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE
 CHART AND SHOW CURRENT CODE REQUIREMENT OF 50 POINTS
 USING THE DESIGN OPTIONS CONSISTENT WITH SECTION
 94-442(G). FICUS BENJAMINA DOES NOT MEET THE FLORIDA
 FRIENDLY REQUIREMENTS. STAFF SUGGESTS THE NEW HEDGE TO
 BE A NATIVE SELECTION TO MINIMIZE WATER, FERTILIZER AND
 INSECTICIDE USAGE. THEY SHOULD CONSIDER A SPECIES THAT
 THEY CAN USE ON THE ENTIRE SITE AS FICUS HEDGE IS
 REMOVED. THIS WILL SAVE MANY DOLLARS OF MAINTENANCE
 COSTS ALSO.
  
 5. NOT SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 THIS COMMENT DID NOT RECEIVE A RESPONSE AS ANOTHER
 COMMENT APPEARED ON THE RESPONSE MEMO.
  
 6. PARTIALLY SATISFIED. SHOW LOCATIONS OF ANY WATER AND
 SEWER LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS
 WITH NEW TREES THAT ARE BEING ADDED.
  
 WATER AND SEWER LINES WERE NOT IN CONFLICT, BUT A
 DRAINAGE LINE IS SHOWN ON C-400 THAT IS PROPOSED
 DIRECTLY IN CONFLICT WITH THE NEW TREES REQUIRED FOR
 THE NEW PARKING ON THE NORTH SIDE OF THE AREA.
 OBVIOUSLY, THIS NEEDS TO BE RELOCATED AWAY FROM THE
 TREES.
  
 7. SATISFIED. INDICATE CURBS AND WHEEL STOPS FOR NEW
 PARKING AREAS ADJACENT TO LANDSCAPE AREAS TO MEET THE
 CODE REQUIREMENTS OF SECTION 94-443(C)(5).
  
 8. SATISFIED. SHOW COMPLIANCE WITH THE BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL
 USE AND INCLUDE THE LINEAR FOOTAGE PER SECTION
 94-443(E)(1) FOR THE NEW BUILDING.
  
  
 9. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE PERCENTAGE BASED ON PLANT LIST.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-11-2020 Cont ID  
Sent By rcaranci Date 08-11-2020 Time 17:45 Rev Time 0.00
Received By rcaranci Date 08-11-2020 Time 17:45 Sent To  
Notes
2020-08-11 17:46:01FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: BEAR LAKES COUNTRY CLUB Z20070014
 AUGUST 11, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. ARECA PALMS ARE NOT CONSIDERED FULL SIZE PALMS THAT
 MUST BE MITIGATED. ADD A NOTE TO THE PLAN.
  
 2. PROVIDE THE REQUIRED TREE IN THE TWO TERMINAL
 LANDSCAPE ISLANDS AT THE ENDS OF THE ROW OF NEW PARKING
 SPACES ALONG THE NORTH SIDE. PROVIDE THE REQUIRED
 INTERIOR LANDSCAPE ISLAND WITH REQUIRED TREE IN THE ROW
 OF PARKING SO THERE ARE NO MORE THAN 10 PARKING SPACES
 IN A ROW.
  
 3. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS.
  
 4. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE CHART AND
 SHOW CURRENT CODE REQUIREMENT OF 50 POINTS USING THE
 DESIGN OPTIONS CONSISTENT WITH SECTION 94-442(G). FICUS
 BENJAMINA DOES NOT MEET THE FLORIDA FRIENDLY
 REQUIREMENTS. STAFF SUGGESTS THE NEW HEDGE TO BE A
 NATIVE SELECTION TO MINIMIZE WATER, FERTILIZER AND
 INSECTICIDE USAGE. THEY SHOULD CONSIDER A SPECIES THAT
 THEY CAN USE ON THE ENTIRE SITE AS FICUS HEDGE IS
 REMOVED. THIS WILL SAVE MANY DOLLARS OF MAINTENANCE
 COSTS ALSO.
  
 5. PROVIDE LOCATIONS OF LIGHTING ON THE LANDSCAPE PLAN
 TO AVOID CONFLICTS WITH LANDSCAPING.
  
 6. SHOW LOCATIONS OF ANY WATER AND SEWER LINES ON THE
 LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH NEW TREES
 THAT ARE BEING ADDED.
  
 7. INDICATE CURBS AND WHEEL STOPS FOR NEW PARKING AREAS
 ADJACENT TO LANDSCAPE AREAS TO MEET THE CODE
 REQUIREMENTS OF SECTION 94-443(C)(5).
  
 8. SHOW COMPLIANCE WITH THE BUILDING PERIMETER
 LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL USE AND
 INCLUDE THE LINEAR FOOTAGE PER SECTION 94-443(E)(1) FOR
 THE NEW BUILDING.
  
  
 9. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
 PROVIDE PERCENTAGE BASED ON PLANT LIST.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 4 Status P Date 03-12-2021 Cont ID  
Sent By   Date 03-12-2021 Time   Rev Time 0.00
Received By   Date 03-12-2021 Time   Sent To  
Notes
2021-03-12 13:27:01THE TRASH RECEPTACLE ENCLOSURE DETAIL SHOWN ON THE
 REVISED SITE PLAN, SHEET SP.1, ON 3/12/2021 IS
 ACCEPTABLE.
 NO FURTHER COMMENTS FROM DEPT. OF PUBLIC WORKS.
  
 MATT HEJAZI
 DEPT OF PUBLIC WORKS
 [email protected]
  

Review Stop PW PUBLIC WORKS
Rev No 3 Status F Date 03-11-2021 Cont ID  
Sent By   Date 03-11-2021 Time   Rev Time 0.00
Received By   Date 03-11-2021 Time   Sent To  
Notes
2021-03-11 12:40:23PLEASE PROVIDE REVISED SP.1, TO REFLECT THE LATEST
 REVISION OF THE DUMPSTER ENCLOSURE DETAIL. FOR A
 FREESTANDING SITE DUMPSTER ENCLOSURE, THE ENCLOSURE
 SHALL COMPLY WITH THE LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, GC-7.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 01-28-2021 Cont ID  
Sent By   Date 01-28-2021 Time   Rev Time 0.00
Received By   Date 01-28-2021 Time   Sent To  
Notes
2021-01-28 13:56:16PLEASE PROVIDE THE FOLLOWINGS:
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
 2- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE
 DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE
 LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, GC-7.
 3- AUTO TURN (DYNAMIC ENVELOPE AND THE TIRES PATH) FOR
 THE SANITATION SERVICE, FRONT LOADER TRUCK WITH THE
 FOLLOWING SPECS:
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 08-12-2020 Cont ID  
Sent By   Date 08-12-2020 Time   Rev Time  
Received By   Date 08-12-2020 Time   Sent To  
Notes
2020-08-12 16:04:38PLEASE PROVIDE DETAILS (I.E. LOS ANALYSIS, CONTAINER
 LOCATION, ENCLOSURE SPECIFICATION, AUTO TURN) ON THE
 SANITATION SERVICE.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status P Date 12-14-2020 Cont ID  
Sent By tward Date 12-14-2020 Time 19:25 Rev Time 0.00
Received By tward Date 12-14-2020 Time 19:36 Sent To  
Notes
2020-12-14 19:36:33THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 11/6/2020 SUBMITTAL PACKAGE. BOTH CAN BE ADDRESSED
 DURING ENGINEERING PERMIT SUBMITTAL.
  
 1. THE NPBCID DRAINAGE OUTFALL DETAIL ON SHEET C-420
 ASHOWS HDPE OR CAP PIPE EXTENDING INTO THE LAKE. THE
 ENGINEERING PLAN (SHEET C-400) SHOWS RCP PIPE EXISTING
 INTO THE LAKE. REMOVE THE RCP PIPES AND THE CONCRETE
 CAP CONNECTIONS BETWEEN THE RCP AND HDPE PIPES AND
 SPECIFY 84 LF 15" HDPE OUT OF STRUCTURE #02 AND 63 LF
 15" HDPE OUT OF STRUCTURE #04.
  
 2. LABEL THE TOP OF STORM PIPE ELEVATIONS IN THE
 CROSSING (CONFLICT) TABLE. IT APPEARS THERE MAY BE
 INSUFFICIENT VERTICAL CLEARANCE WITH THE WATER SERVICE
 LINES.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-13-2020 Cont ID  
Sent By tward Date 08-13-2020 Time 02:44 Rev Time 0.00
Received By tward Date 08-13-2020 Time 02:46 Sent To  
Notes
2020-08-13 02:46:17THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PROVIDE CHANGE IN LAND USE AREA FOR BUILDING,
 PAVEMENT, SIDEWALK AND PERVIOUS AREAS BETWEEN EXISTING
 AND PROPOSED DEVELOPMENT. PROVIDE A SKETCH SHOWING THE
 CHANGES.
  
 2. DESCRIBE HOW STORMWATER WATER QUALITY TREATMENT WILL
 BE PROVIDED IF THERE IS A NET DECREASE IN PERVIOUS
 AREA. CALCULATIONS WILL NEED TO BE PROVIDED WITH THE
 ENGINEERING PERMIT SUBMITTAL.
  
 3. WILL CURBING BE PROVIDED AT THE WEST AND EAST ENDS
 OF THE NORTHERN PARKING SPACES?
  
 4. ADD FLOW ARROWS SHOWING HOW SURFACE RUNOFF WILL
 FLOW.
  
 5. IT APPEARS MOST OF THE NORTHERN PARKING AREA SLOPES
 TO THE NORTH. SHOW A SWALE TO CONVEY THE RUNOFF TO THE
 CATCH BASINS.
  
 6. WHERE DOES STRUCTURE ST-07 DRAIN TO?
  
 7. ADD PRB'S TO STORM STRUCTURES #2 AND #4 TO KEEP
 FLOATABLES OUT OF THE LAKE.
  
 8. LABEL THE NORMAL (CONTROL) ELEVATION OF THE LAKE(S).
  
 9. THE ENGINEERING PLAN SHOWS ENDWALLS FOR THE NEW
 PIPES INTO THE LAKE. ENDWALLS ARE NOT SHOWN ON THE
 NPBCID DETAIL PROVIDED ON SHEET C-420.
  
 10. INDICATE HOW MUCH OF THE 6" OUTFALL PIPE WILL BE
 REMOVED. IF NOT ALL OF THE PIPE, HOW WILL THE REST OF
 THE PIPE BE ABANDONED?
  
 11. ADD FLOATING TURBIDITY BARRIERS AROUND THE OUTFALLS
 (EXISTING AND PROPOSED) IN THE LAKES.
  
 12. THE PROPOSED BUILDING APPEARS TO BE PARTIALLY
 LOCATED IN FLOOD ZONE AE. STRUCTURES WITHIN SPECIAL
 FLOOD HAZARD AREAS ARE TO HAVE TWO FEET OF FREE BOARD
 ABOVE THE BASE FLOOD ELEVATION.
  
 13. THE CITY OF WEST PALM BEACH USES NGVD1929 AS THE
 VERTICAL DATUM. PLANS AND SURVEYS CAN USE NAVD1988
 VERTICAL DATUM IF THE CONVERSION EQUATION IS PROVIDED
 ON THE DRAWING. ADD THE CONVERSION EQUATION TO THE
 SURVEY.
  
 14. CONFIRM THERE WILL BE SUFFICIENT VERTICAL CLEARANCE
 BETWEEN THE WATER SERVICE LINES AND THE PROPOSED
 DRAINAGE PIPE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE NPBCID ACCEPTANCE OF THIS
 PROJECT.
  
 4. PROVIDE SFWMD ERP PERMIT MODIFICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 11-18-2020 Cont ID  
Sent By vnoel Date 11-18-2020 Time 09:36 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-11-18 09:37:13PASSED - NEED SIGNED AND SEALED COPY.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 08-10-2020 Cont ID  
Sent By vnoel Date 08-10-2020 Time 12:00 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2020-08-10 12:10:511. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH. SHOW ORB
 4944/1995.
 2. INCORRECT ORB/PG FOR RELEASE OF EXISTING DE ON SITE
 PLAN.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date 11-06-2020 Cont ID  
Sent By   Date 11-06-2020 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-11-06 13:34:19NO FURTHER COMMENTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 08-13-2020 Cont ID  
Sent By   Date 08-13-2020 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2020-11-06 13:33:30NO FURTHER COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
2020-08-13 12:14:42 
 SITE PLAN COMMENTS:
 ?PER ADA REQUIREMENTS: ONE STANDARD AND ONE VAN
 ACCESSIBLE HANDICAP PARKING SHALL BE PROVIDED WHEN A
 PARKING FACILITY HAS A TOTAL OF SPACES BETWEEN 26 AND
 50
 ?IDENTIFY THE GARBAGE LOCATION
 ?IDENTIFY THE LOADING ZONE(S)
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 03-11-2021 Cont ID  
Sent By llouie Date 03-11-2021 Time   Rev Time 0.00
Received By llouie Date 03-11-2021 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 01-27-2022 Cont ID  
Sent By llouie Date 01-27-2021 Time   Rev Time 0.00
Received By llouie Date 01-27-2021 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 11-30-2020 Cont ID  
Sent By llouie Date 11-30-2020 Time   Rev Time 0.00
Received By llouie Date 11-30-2020 Time   Sent To  
Notes
2020-11-30 16:01:44GENERAL COMMENTS:
  
 1.) SERVICE LETTER FROM AT&T IS STILL MISSING. PLEASE
 PROVIDE A LETTER FROM AT&T STATING THAT THE PROPOSED
 PROJECT DOES NOT ENCROACH INTO THEIR EASEMENT OR
 OTHERWISE INTERFERE WITH THE PROVISION OF THEIR
 SERVICE.
  
 2.) ALTHOUGH THE PROJECT IS NOT EXPECTED TO GENERATE
 ANY NEGATIVE IMPACTS TO TRAFFIC, STAFF IS REQUESTING A
 TPS LETTER FROM THE PALM BEACH COUNTY TRAFFIC DIVISION
 TO CONFIRM AN DOCUMENT THAT THE COUNTY HAS REVIEWED THE
 PROJECT AND THAT THERE ARE NO ISSUES WITH TRAFFIC.
 [8/7/2020 REPEAT COMMENT: TPS LETTER HAS YET TO BE
 PROVIDED BY THE APPLICANT.]
  
  
 SITE PLAN COMMENTS:
  
 1.) STALL PAINTING DETAIL OF THE ANGLED PARKING AT THE
 NORTH END OF THE AREA OF WORK IS MISSING. PLEASE
 PROVIDE DETAIL TO DEMONSTRATE COMPLIANCE WITH THE
 ZLDRS. [ZLDR S.94-485]
  
 2.) STALL PAINTING DETAIL FOR THE 90 DEGREE PARKING
 SHOW WHEEL STOPS. PLEASE ILLUSTRATE IN THE SITE PLAN
 FOR CONSISTENCY WITH THE DETAIL
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE TWO (2) PAPER
 COPIES, ONE (1) REDUCED COPY IN 11 INCHES BY 17 INCHES,
 AND AN ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($300.00).
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-07-2020 Cont ID  
Sent By llouie Date 08-07-2020 Time   Rev Time  
Received By llouie Date 08-07-2020 Time   Sent To  
Notes
2020-08-07 09:39:44GENERAL COMMENTS:
  
 1.) PROVIDE DOCUMENTATION SHOWING THAT MR. MARIUS ILIE
 IS AUTHORIZED TO SIGN THE OWNER'S CONSENT FORM.
  
 2.) PROVIDE WRITTEN CONFIRMATION THAT THE PUBLIC
 UTILITIES DEPARTMENT HAS REVIEWED THE PROPOSAL FOR
 WATER, SEWAGE TREATMENT, STORM DRAINAGE AND GARBAGE
 COLLECTION SERVICES. PLEASE CONTACT THE CITY'S
 ENGINEERING SERVICES DEPARTMENT FOR INFORMATION (561)
 494-1040.
  
 3.) PROVIDE LETTERS FROM THE FOLLOWING PUBLIC UTILITIES
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISION OF THEIR SERVICES: AT&T, FPU, FPL AND
 COMCAST.
  
 4.) ALTHOUGH THE PROJECT IS NOT EXPECTED TO GENERATE
 ANY NEGATIVE IMPACTS TO TRAFFIC, STAFF IS REQUESTING A
 TPS LETTER FROM THE PALM BEACH COUNTY TRAFFIC DIVISION
 TO CONFIRM AND DOCUMENT THAT THE COUNTY HAS REVIEWED
 THE PROJECT AND THAT THERE ARE NO ISSUES WITH TRAFFIC.
  
  
 SITE PLAN COMMENTS:
  
 1.) A NEW CONCRETE SLAB IS SHOWN IN THE AREA OF THE
 COVERED WASH PAD AND FUEL ISLAND PLAN (SHEET A-1).
 PLEASE ILLUSTRATE IN THE SITE PLAN FOR CONSISTENCY.
  
 2.) PROVIDE A DETAIL OF THE PROPOSED NEW MATERIAL
 STORAGE BINS (I.E. HEIGHT, ETC.).
  
 3.) IS THE FENCE DEPICTED IN THE SITE PLAN EXISTING
 (CHAIN LINK FENCE) OR IS IT A PROPOSED NEW FENCE FOR
 THE MAINTENANCE FACILITY? PLEASE CLARIFY IN THE PLANS.
 ADDITIONAL INFORMATION (I.E. MATERIAL, HEIGHT, DETAIL,
 ETC.) WILL BE REQUIRED IF THE EXISTING FENCE IS TO BE
 REPLACED.
  
 4.) EACH ROW OF PARKING SHALL BE TERMINATED BY
 LANDSCAPE ISLANDS OF NOT LESS THAN 8 FT. IN WIDTH
 MEASURED FROM INSIDE THE CURB. [ZLDR S.94-443(C)(3)A.]
  
 5.) ONE (1) INTERIOR LANDSCAPE ISLAND SHALL BE REQUIRED
 FOR EVERY TEN (10) PARKING SPACES IN A ROW. INTERIOR
 LANDSCAPE ISLANDS SHALL BE AT LEAST 8 FT. WIDE MEASURED
 FROM INSIDE THE CURB. [ZLDR S.94-443(C)(3)B.]
  
 6.) ALL PARKING AREAS WITHIN THE SITE PLAN (NEW AND
 OLD) SHALL CONFORM TO THE STALL STRIPING REQUIREMENTS
 OF THE CITY. INCLUDE A STALL STRIPING DETAIL IN THE
 PLAN TO DEMONSTRATE COMPLIANCE. [ZLDR S.94-485]
  
  
 INSTRUCTIONS FOR RESUBMITTAL:
  
 * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 * WHEN RESUBMITTING, PLEASE PROVIDE TWO (2) PAPER
 COPIES, ONE (1) REDUCED COPY IN 11 INCHES X 17 INCHES,
 AND AN ELECTRONIC COPY OF ALL PLANS AND DOCUMENTS.
  
 * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE
 ($300.00).
  