Plan Review Details - Project Z20030013
| Plan Review Stops For Project Z20030013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
12-23-2020 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
12-23-2020 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
12-23-2020 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2020-12-23 11:44:19 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | REVIEW OF SITE PLAN APPROVAL APPLICATION HAS PASED. THE | | | FOLLOWING COMMENTS MUST BE ADDRESSED FOR PERMIT | | | APPLICATION: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. RENOVATION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | | | 2020-09-30 15:27:42 | SEE ZONING REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
04-08-2020 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
04-08-2020 |
Time |
19:25 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
04-08-2020 |
Time |
19:24 |
Sent To |
|
|
| Notes |
| 2020-04-08 19:46:23 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. RENOVATION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. NUMBER OF ACCESSIBLE PARKING SPACES. THE PARKING | | | DATA ON SITE PLAN SHEET 1 STATES THAT 86 PARKING SPACES | | | WILL BE PROVIDED BUT THE PLAN ONLY SHOWS 2 ACCESSIBLE | | | PARKING SPACES. PER SECTION 208.2 OF FLORIDA | | | ACCESSIBILITY CODE, 4 ACCESSIBLE PARKING SPACES ARE | | | REQUIRED. THE MINIMUM NUMBER OF ACCESSIBLE PARKING | | | SPACES PROVIDED SHALL BE IN ACCORDANCE WITH SECTION | | | 208.2 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 4. LOCATION OF ACCESSIBLE PARKING SPACES. WHEN THE | | | EDDITIONAL 2 ACCESSIBLE PARKING SPACES ARE PROVIDED, | | | THEY ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE | | | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE PER SECTION 208.3 OF FLORIDA ACCESSIBILITY | | | CODE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE | | | | | | 5. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE | | | REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE | | | AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING | | | INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561) | | | 805-6692, OR BY EMAIL: [email protected] | | | | | | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
5 |
Status |
P |
Date |
10-05-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
10-05-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
10-05-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-05 13:06:19 | REVISE ENGINEERING PLANS FOR E21070029 TO REFLECT THESE | | | PROPOSED CHANGES ONCE APPROVED BY TRAFFIC. |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
4 |
Status |
P |
Date |
03-26-2021 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
03-26-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
03-26-2021 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
F |
Date |
09-24-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
09-24-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
09-24-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-24 13:53:43 | 1. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE | | | HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF | | | CITY OF WPB DEVELOPMENT APPLICATION). | | | 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | 3. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED | | | AREAS. | | | 4. PROVIDE ONSITE CLEANOUT NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | 6. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | 7. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP | | | UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY | | | LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY. | | | 8. FOR FORMAL ENGINEERING SUBMITTAL , PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | 9. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | 11. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND | | | NPDES NOI REQUIREMENTS WILL BE ENFORCED. | | | - AN NOI IS REQUIRED FOR PROJECTS THAT: | | | - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS | | | THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF | | | DEVELOPMENT OR SALE; | | | - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE | | | STATE OR TO SURFACE WATERS OF THE STATE THROUGH A | | | MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4). | | | - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF | | | CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION | | | THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL | | | SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT | | | OF THE 10-2 CERTIFICATION. | | | 12. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | 13. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | 14. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND | | | INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER | | | (Z-XXXXXXXX). | | | | | | THANKS, | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | WPB ENGINEERING SERVICES | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | CELL: (561) 246-9525 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | CENTRAL OPERATIONS CENTER (DISPATCH): | | | 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
08-17-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
08-17-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
08-17-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-08-17 15:23:48 | COMMENTS PER MARK HURLEY, CITY OF WPB PUB. UTIL. CUST. | | | SERVICE, [email protected], OR 561-822-2262: | | | | | | -THERE IS A BACKFLOW ASSEMBLY MISSING FROM THE WATER | | | ENGINEERING PLAN. PLEASE ADD IT. | | | -DCDA BACKFLOW ASSEMBLY SHOULD NOT BE ATTACHED TO THE | | | NORTHERN METER BOX. THAT LARGE FIRELINE SHOULD BE A | | | SEPARATE WATER SERVICE TO THE WATER MAIN. PLEASE | | | CORRECT. | | | -PLEASE ADD ROOT BARRIERS BETWEEN THE TREES AND | | | CUSTOMER?S FIRELINE PIPING AFTER DCDA. | | | -ON FORMAL ENGINEERING SUBMITTAL, LABEL THE SIZES OF | | | THE WATER METERS AND BACKFLOW ASSEMBLIES. THE PRIVATE | | | DOMESTIC WATER PIPE SAYS 3 IN., BUT THE DOMESTIC METER | | | AND BACKFLOW ASSEMBLY IS SMALLER THAN THAT. IF LARGER | | | METER IS NEEDED, NEW WATER SERVICE MAY NEED TO BE | | | BUILT. LARGER METER MAY REQUIRE MORE SPACE, | | | ABOVE-GROUND INSTALLATION, AND UTILITY EASEMENTS. | | | -FOR ENGINEERING SUBMITTAL, IDENTIFY EXISTING PRIVATE | | | FIRELINE PIPING AND WHAT WILL BE HAPPENING TO IT. WILL | | | IT BE ABANDONED IN PLACE, REMOVED, OR GROUTED? | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
04-07-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
04-07-2020 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
04-07-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-07 13:45:34 | 1. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY | | | OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC | | | RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF | | | YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | 2. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | 3. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS | | | OF ALL WATER, STORM WATER, AND SANITARY AND SEWER | | | LINES, INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER | | | AND SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND | | | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER | | | OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL | | | UTILITY CROSSINGS. CUT AND CAP UTILITIES NOT IN USE, | | | AND REMOVE ANY ABANDONED UTILITY LINES LARGER THAN 2 | | | INCHES FROM CITY RIGHT OF WAY. | | | 4. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE | | | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB | | | DEVELOPMENT APPLICATION). | | | 5. SHOW DIMENSIONS OF PROPOSED DUMPSTER ENCLOSURE PER | | | CURRENT CITY OF WPB STANDARD DETAIL GC-8. | | | 6. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | 7. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA | | | AND FIRE BACKFLOW PREVENTER AS DCDA. | | | 8. PROVIDE VERTICAL DATUM AND DATUM CONVERSION | | | INFORMATION (NAVD 1988 AND NGVD 1929). | | | 9. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND | | | PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM | | | AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE | | | PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | 10. COMMENT RESCINDED. | | | 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS. | | | 12. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES | | | OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD | | | RIGHT OF WAY. | | | 16. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | 17. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY MAINS | | | ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY | | | LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT | | | PARCELS. | | | 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER MAINS | | | ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL | | | ADDRESSES. | | | 19. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO | | | PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH | | | SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY | | | AREAS PER CITY OF WPB STANDARD DETAIL GC-9. | | | 20. PLEASE NOTE THAT A PRE-PPRC-SUBMITTAL MEETING WITH | | | ENGINEERING SERVICES IS HIGHLY SUGGESTED. | | | 21. PLEASE RESPOND TO ALL COMMENTS IN WRITING. | | | | | | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR | | | CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262 | | | [email protected] | | | | | | -SEE WELL ON PLAN, BUT RECORDS SHOW THAT THERE IS A | | | DEDICATED IRRIGATION SERVICE THAT IS NOT CURRENTLY | | | BEING USED. IS THE WELL BEING USED FOR IRRIGATION? | | | -ARE ALL BACKFLOW PREVENTERS INCLUDING THE EXISTING 8 | | | IN. DCDA FIRELINE BACKFLOW ASSEMBLY SHOWN ON THE SITE | | | PLAN? | | | -NEED SUBMIT UTILITY PLAN. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL | | | 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | DIRECT: (561) 494-1098 | | | MOBILE: (561) 246-9525 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
03-30-2020 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
03-30-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
03-30-2020 |
Time |
14:46 |
Sent To |
|
|
| Notes |
| 2020-03-30 14:52:52 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE PROPOSED LOCATION OF THE FIRE HYDRANT IN THE REAR | | | OF THE PROPERTY IS NOT RECOMMENDED AND IS PREFERRED TO | | | BE IN THE FRONT LOCATED WITH 100' OF ANY PROPOSED | | | FDC'S. THE LOCATIONS SHALL BE CLOSELY COORDINATED WITH | | | THE BUREAU OF FIRE PREVENTION. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PERMIT. | | | | | | 9A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE | | | LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND | | | SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL, | | | THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND | | | THE CITY'S PLANNING AND ZONING OFFICE. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
6 |
Status |
P |
Date |
10-19-2021 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-19-2021 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-19-2021 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2021-10-19 16:23:14 | SUBMITTAL FROM 9/27 WITH PAVEMENT MARKING CHANGES WAS | | | REVIEWED AND NO CHANGES WERE MADE TO THE APPROVED | | | LANDSCAPE PLAN. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
5 |
Status |
P |
Date |
06-23-2021 |
|
|
Cont ID |
|
| Sent By |
aburnett |
Date |
06-23-2021 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
aburnett |
Date |
06-23-2021 |
Time |
12:27 |
Sent To |
|
|
| Notes |
| 2021-06-23 12:29:32 | FROM: ANDREW BURNETT, LANDSCAPE PLANNER 561-822-1562 | | | PROJECT: 2808 N AUSTRALIAN AVE Z20030013 | | | JUNE 23, 2021 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | BUILDING, SITE PLAN AND LANDSCAPE PLAN HAVE CHANGED. | | | NEW COMMENTS ARE LISTED AFTER PREVIOUSLY SATISFIED | | | COMMENTS. | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE | | | DISPOSITION CHART: | | | ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE | | | OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET | | | DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300 | | | SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE, | | | CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE | | | MITIGATION DUE COLUMN. | | | PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART. | | | #17 CHANGED TO BLACK OLIVE SPECIES. | | | ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , | | | REQUIRING 50 SQ FT MITIGATION. | | | ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE | | | MITIGATION. ENTER 0 IN THE COLUMN. | | | ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE | | | AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM | | | THE PROPOSED TREE LIST. | | | RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE. | | | | | | 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED | | | MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER | | | SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF | | | 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 | | | FLOWERING TREES. | | | | | | 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF | | | PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW | | | REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE | | | NUMBER OF SUBSTITUTIONS PROPOSED. | | | | | | 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A | | | MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO | | | BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING | | | AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE | | | REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS | | | REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF | | | CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE | | | AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL | | | AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES. | | | | | | JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF | | | SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING | | | TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED | | | WILL BE MET. | | | | | | 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE | | | THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH | | | SECTIONS. | | | | | | 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS | | | FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL | | | STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE | | | OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR | | | SUPPORTING THE ROOT ZONES OF THE TREES. | | | | | | 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30 | | | FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES, | | | SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES | | | 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE | | | CORRECTIONS. | | | | | | CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA | | | CHART. | | | | | | 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET | | | IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB | | | SECTION. | | | PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR | | | DROUGHT TOLERANT LEVELS OF EACH SPECIES. | | | | | | 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION | | | 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED | | | 50 POINTS. | | | | | | 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES | | | PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER | | | SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE | | | TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES, | | | AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS, | | | USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE | | | PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND | | | SEAGRAPE ARE POSSIBLE ADDITIONS. | | | | | | | | | 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. | | | | | | PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT | | | TOLERANT PLANTS BASED ON FINAL PLANT LIST. | | | | | | 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN, | | | RESPONSE TO COMMENTS WAS NOT SUFFICIENT. | | | | | | | | | 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER, | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | ENGINEERING PLANS WERE NOT SUBMITTED. | | | | | | 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT | | | BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | | | | WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | ADDITIONAL COMMENTS 4/12/21: | | | 18. SATISFIED ADJUST TREE SIZES TO MINIMUM OF 12 FEET | | | IN HEIGHT. | | | SHADY LADY TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 19. SATISFIED 6 BA ARE SHOWN ON THE PLAN, SO THE PLANT | | | LIST NEEDS TO BE CORRECTED FROM 5 TO 6. | | | | | | 20. SATISFIED 4 BA ARE SHOWN ON THE PLAN, SO THE PLANT | | | LIST NEEDS TO BE CORRECTED FROM 5 TO 4. | | | | | | 21. SATISFIED ADD THE EXISTING LIVE OAK TREE AND BLACK | | | OLIVE TREE TO REMAIN TO THE PLANT LIST AND SHOW THE | | | IDENTIFYING NUMBER FROM THE TREE DISPOSITION. | | | | | | 22. SATISFIED SCREENING NEEDS TO BE PROVIDED FOR THE | | | GENERATOR WITH A FENCE OR HEDGE. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
F |
Date |
04-12-2021 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-12-2021 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-12-2021 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2021-04-12 11:22:23 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2808 N AUSTRALIAN AVE Z20030013 | | | APRIL 12, 2021 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | BUILDING, SITE PLAN AND LANDSCAPE PLAN HAVE CHANGED. | | | NEW COMMENTS ARE LISTED AFTER PREVIOUSLY SATISFIED | | | COMMENTS. | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE | | | DISPOSITION CHART: | | | ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE | | | OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET | | | DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300 | | | SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE, | | | CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE | | | MITIGATION DUE COLUMN. | | | PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART. | | | #17 CHANGED TO BLACK OLIVE SPECIES. | | | ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , | | | REQUIRING 50 SQ FT MITIGATION. | | | ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE | | | MITIGATION. ENTER 0 IN THE COLUMN. | | | ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE | | | AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM | | | THE PROPOSED TREE LIST. | | | RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE. | | | | | | 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED | | | MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER | | | SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF | | | 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 | | | FLOWERING TREES. | | | | | | 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF | | | PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW | | | REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE | | | NUMBER OF SUBSTITUTIONS PROPOSED. | | | | | | 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A | | | MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO | | | BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING | | | AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE | | | REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS | | | REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF | | | CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE | | | AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL | | | AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES. | | | | | | JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF | | | SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING | | | TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED | | | WILL BE MET. | | | | | | 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE | | | THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH | | | SECTIONS. | | | | | | 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS | | | FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL | | | STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE | | | OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR | | | SUPPORTING THE ROOT ZONES OF THE TREES. | | | | | | 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30 | | | FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES, | | | SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES | | | 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE | | | CORRECTIONS. | | | | | | CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA | | | CHART. | | | | | | 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET | | | IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB | | | SECTION. | | | PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR | | | DROUGHT TOLERANT LEVELS OF EACH SPECIES. | | | | | | 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION | | | 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED | | | 50 POINTS. | | | | | | 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES | | | PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER | | | SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE | | | TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES, | | | AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS, | | | USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE | | | PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND | | | SEAGRAPE ARE POSSIBLE ADDITIONS. | | | | | | | | | 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. | | | | | | PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT | | | TOLERANT PLANTS BASED ON FINAL PLANT LIST. | | | | | | 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN, | | | RESPONSE TO COMMENTS WAS NOT SUFFICIENT. | | | | | | | | | 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER, | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | ENGINEERING PLANS WERE NOT SUBMITTED. | | | | | | 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT | | | BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | | | | WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | ADDITIONAL COMMENTS 4/12/21: | | | 18. ADJUST TREE SIZES TO MINIMUM OF 12 FEET IN HEIGHT. | | | SHADY LADY TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 19. 6 BA ARE SHOWN ON THE PLAN, SO THE PLANT LIST NEEDS | | | TO BE CORRECTED FROM 5 TO 6. | | | | | | 20. 4 BA ARE SHOWN ON THE PLAN, SO THE PLANT LIST NEEDS | | | TO BE CORRECTED FROM 5 TO 4. | | | | | | 21. ADD THE EXISTING LIVE OAK TREE AND BLACK OLIVE TREE | | | TO REMAIN TO THE PLANT LIST AND SHOW THE IDENTIFYING | | | NUMBER FROM THE TREE DISPOSITION. | | | | | | 22. SCREENING NEEDS TO BE PROVIDED FOR THE GENERATOR | | | WITH A FENCE OR HEDGE. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
09-30-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-30-2020 |
Time |
16:28 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-30-2020 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2020-09-30 16:29:07 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2808 N AUSTRALIAN AVE Z20030013 | | | SEPTEMBER 30, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE | | | DISPOSITION CHART: | | | ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE | | | OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET | | | DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300 | | | SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE, | | | CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE | | | MITIGATION DUE COLUMN. | | | PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART. | | | #17 CHANGED TO BLACK OLIVE SPECIES. | | | ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , | | | REQUIRING 50 SQ FT MITIGATION. | | | ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE | | | MITIGATION. ENTER 0 IN THE COLUMN. | | | ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE | | | AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM | | | THE PROPOSED TREE LIST. | | | RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE. | | | | | | 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED | | | MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER | | | SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF | | | 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 | | | FLOWERING TREES. | | | | | | 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF | | | PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW | | | REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE | | | NUMBER OF SUBSTITUTIONS PROPOSED. | | | | | | 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A | | | MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO | | | BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING | | | AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE | | | REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS | | | REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF | | | CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE | | | AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL | | | AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES. | | | | | | JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF | | | SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING | | | TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED | | | WILL BE MET. | | | | | | 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE | | | THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH | | | SECTIONS. | | | | | | 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS | | | FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL | | | STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE | | | OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR | | | SUPPORTING THE ROOT ZONES OF THE TREES. | | | | | | 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30 | | | FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES, | | | SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES | | | 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE | | | CORRECTIONS. | | | | | | CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA | | | CHART. | | | | | | 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET | | | IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB | | | SECTION. | | | PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR | | | DROUGHT TOLERANT LEVELS OF EACH SPECIES. | | | | | | 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION | | | 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED | | | 50 POINTS. | | | | | | 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES | | | PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER | | | SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE | | | TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES, | | | AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS, | | | USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE | | | PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND | | | SEAGRAPE ARE POSSIBLE ADDITIONS. | | | | | | | | | 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA | | | CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A | | | MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE | | | FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED | | | FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST | | | RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT | | | DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. | | | | | | PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT | | | TOLERANT PLANTS BASED ON FINAL PLANT LIST. | | | | | | 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN, | | | RESPONSE TO COMMENTS WAS NOT SUFFICIENT. | | | | | | | | | 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER, | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | ENGINEERING PLANS WERE NOT SUBMITTED. | | | | | | 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT | | | BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | | | | WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
09-09-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-09-2020 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-09-2020 |
Time |
17:06 |
Sent To |
|
|
| Notes |
| 2020-09-09 17:07:21 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2808 N AUSTRALIAN AVE Z20030013 | | | SEPTEMBER 9, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE | | | DISPOSITION CHART: | | | ? PARTIALLY SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR | | | THE LIVE OAK TREES #17 AND #19-23. IF THEY ARE LESS | | | THAN 20 FEET DIAMETER DUE TO FPL PRUNING, THEN THEY | | | WILL REQUIRE 300 SQ FT MITIGATION. IF THEY ARE 20 FEET | | | OR MORE, CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER | | | INTO THE MITIGATION DUE COLUMN. | | | PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART. | | | #17 CHANGED TO BLACK OLIVE SPECIES. | | | ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , | | | REQUIRING 50 SQ FT MITIGATION. | | | ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE | | | MITIGATION. ENTER 0 IN THE COLUMN. | | | ? PARTIALLY SATISFIED. TOTAL THE SQUARE FOOTAGE OF | | | MITIGATION DUE AND SHOW MITIGATION SQUARE FOOTAGE TOTAL | | | PROVIDED FROM THE PROPOSED TREE LIST. | | | RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE. | | | | | | 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED | | | MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER | | | SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF | | | 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 | | | FLOWERING TREES. | | | | | | 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF | | | PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW | | | REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE | | | NUMBER OF SUBSTITUTIONS PROPOSED. | | | | | | 4. PARTIALLY SATISFIED. SECTION 94-443(C)(3) REQUIRES | | | THAT A MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE | | | REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF AN OFF | | | STREET PARKING AREA SHALL BE CATEGORY 1 SHADE TREES. | | | REMOVE LANGUAGE REFERRING TO ONE TREE PER 100 SQ FT., | | | AS THIS WAS REMOVED FROM THE CODE IN 2018. SHOW THE | | | PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE | | | REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION | | | 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS. THERE | | | ARE 11 REQUIRED TREES. | | | | | | JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF | | | SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING | | | TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED | | | WILL BE MET. | | | | | | 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE | | | THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH | | | SECTIONS. | | | | | | 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS | | | FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL | | | STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE | | | OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR | | | SUPPORTING THE ROOT ZONES OF THE TREES. | | | | | | 7. PARTIALLY SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE | | | PER 30 FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 | | | TREES, SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER | | | REQUIRES 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE | | | CORRECTIONS. | | | | | | CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA | | | CHART. | | | | | | 8. PARTIALLY SATISFIED. ADJUST TREE SIZES TO MINIMUM OF | | | 12 FEET IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO | | | THE SHRUB SECTION. | | | PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM. | | | | | | 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR | | | DROUGHT TOLERANT LEVELS OF EACH SPECIES. | | | | | | 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR | | | FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION | | | 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED | | | 50 POINTS. | | | | | | 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES | | | PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER | | | SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE | | | TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES, | | | AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS, | | | USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE | | | PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND | | | SEAGRAPE ARE POSSIBLE ADDITIONS. | | | | | | | | | 12. PARTIALLY SATISFIED. REVISE THE SECTION IN THE | | | LANDSCAPE DATA CHART TO COMPLY WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | | | | PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT | | | TOLERANT PLANTS BASED ON FINAL PLANT LIST. | | | | | | 13. PARTIALLY SATISFIED. SHOW LOCATIONS OF FPL | | | TRANSFORMERS ON THE LANDSCAPE PLAN AND RESOLVE | | | CONFLICTS WITH LANDSCAPING. | | | COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN, | | | RESPONSE TO COMMENTS WAS NOT SUFFICIENT. | | | | | | | | | 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER, | | | SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN. | | | ENGINEERING PLANS WERE NOT SUBMITTED. | | | | | | 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT | | | BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 16. PARTIALLY SATISFIED. PROVIDE SCREENING FOR ALL | | | GROUND MOUNTED VALVES AND EQUIPMENT. | | | | | | WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
04-07-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-07-2020 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-07-2020 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2020-04-07 14:40:29 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2808 N AUSTRALIAN AVE Z20030013 | | | APRIL 7, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE | | | DISPOSITION CHART: | | | ? PROVIDE THE CANOPY DIAMETERS FOR THE LIVE OAK TREES | | | #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET DIAMETER | | | DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300 SQ FT | | | MITIGATION. IF THEY ARE 20 FEET OR MORE, CALCULATE THE | | | ACTUAL SQUARE FOOTAGE AND ENTER INTO THE MITIGATION DUE | | | COLUMN. | | | ? QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , REQUIRING 50 | | | SQ FT MITIGATION. | | | ? JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE MITIGATION. | | | ENTER 0 IN THE COLUMN. | | | ? TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE AND SHOW | | | MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM THE | | | PROPOSED TREE LIST. | | | | | | 2. CORRECT THE CALCULATIONS FOR REQUIRED MINIMUM SHADE | | | TREE AND FLOWERING TREE REQUIREMENTS PER SECTION | | | 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF 40%. | | | 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 FLOWERING | | | TREES. | | | | | | 3. CORRECT THE REFERENCE TO SUBSTITUTION OF PALMS FOR | | | REQUIRED TREES. SECTION 94-442(D) NOW REQUIRES A 3:1 | | | RATIO FOR SUBSTITUTION. PROVIDE THE NUMBER OF | | | SUBSTITUTIONS PROPOSED. | | | | | | 4. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75 | | | PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED | | | WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL | | | BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE REFERRING TO | | | ONE TREE PER 100 SQ FT., AS THIS WAS REMOVED FROM THE | | | CODE IN 2018. SHOW THE PERCENTAGE OF CATEGORY 1 TREES | | | PROVIDED FOR THE REQUIRED LANDSCAPE AREAS AS REQUIRED | | | BY SECTION 94-443(C)(3) FOR TERMINAL AND INTERIOR | | | ISLANDS. THERE ARE 11 REQUIRED TREES. | | | | | | 5. PROVIDE A PLAN SHOWING THE PARKING LANDSCAPE AREAS | | | COUNTED TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND | | | (4) AND PROVIDE CALCULATIONS. PROVIDE THE TOTAL | | | REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH SECTIONS. | | | | | | 6. STAFF SUGGESTS REDUCING THE PAVED AREAS FOR PARKING | | | SPACES AND USING CURBS INSTEAD OF WHEEL STOPS TO ALLOW | | | FOR PERVIOUS LANDSCAPE AREA AT THE OVERHANG. THIS ALSO | | | ALLOWS MORE LANDSCAPE AREA FOR SUPPORTING THE ROOT | | | ZONES OF THE TREES. | | | | | | 7. BUFFER LENGTHS REQUIRE ONE TREE PER 30 FEET OR | | | PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES, SOUTH | | | BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES 12 | | | TREES, WEST BUFFER REQUIRES 6 TREES. MAKE CORRECTIONS. | | | | | | 8. ADJUST TREE SIZES TO MINIMUM OF 12 FEET IN HEIGHT. | | | MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB SECTION. | | | | | | 9. ADD A COLUMN TO THE PLANT LIST FOR DROUGHT TOLERANT | | | LEVELS OF EACH SPECIES. | | | | | | 10. UPDATE THE DESIGN OPTIONS CHART FOR FLORIDA | | | FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION 94-442(G) | | | TO THE CURRENT CODE AND PROVIDE THE REQUIRED 50 POINTS. | | | | | | 11. THE DIVERSITY OF THE TREE SPECIES PROPOSED ARE VERY | | | LIMITED AND ARE MOSTLY SMALLER SPECIES. STAFF SUGGESTS | | | AT LEAST 2 SPECIES FOR THE TREES ON THE EAST AND SOUTH | | | BUFFER UNDER THE FPL LINES, AND AT LEAST 2 SPECIES ON | | | THE NORTH AND WEST BUFFERS, USING CATEGORY 1 SHADE | | | TREES TO PROVIDE SHADE FOR THE PARKING AND PEDESTRIAN | | | AREAS. GREEN BUTTONWOOD AND SEAGRAPE ARE POSSIBLE | | | ADDITIONS. | | | | | | | | | 12. REVISE THE SECTION IN THE LANDSCAPE DATA CHART TO | | | COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM | | | OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA | | | NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE | | | CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT | | | EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT | | | WATERWISE SOUTH FLORIDA LANDSCAPES. | | | PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT | | | TOLERANT PLANTS BASED ON FINAL PLANT LIST. | | | | | | 13. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | | | | 14. SHOW LOCATIONS OF ALL PROPOSED WATER, SEWER AND | | | DRAINAGE LINES ON THE LANDSCAPE PLAN. ENGINEERING PLANS | | | WERE NOT SUBMITTED. | | | | | | 15. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO | | | SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 16. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND | | | EQUIPMENT. | | | | | | 17. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE | | | LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH TREES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
09-14-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
09-14-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
09-14-2020 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
03-27-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-27-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
03-27-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-27 14:13:20 | PLEASE PROVIDE THE FOLLOWINGS: | | | | | | 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID | | | WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF | | | THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE | | | UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION | | | SERVICE. | | | | | | 2- WHERE VISIBLE TO THE PUBLIC, COMMERCIAL CONTAINERS | | | SHALL BE STORED IN A CITY APPROVED ENCLOSURE | | | OBSTRUCTING THE CONTAINERS VIEW FROM PERSONS USING THE | | | SIDEWALK, STREET, OR THE COMMERCIAL ESTABLISHMENT'S | | | FACILITIES, EXCEPT WHEN ENCLOSURES ARE PROHIBITED, SUCH | | | AS IN DOWNTOWN ALLEYS, OR OTHERWISE APPROVED BY THE | | | CITY. THIS REQUIREMENT INDICATED IN THE CODE OF | | | ORDINANCES, SECTION 74-34-A-2-D. | | | | | | 3- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE | | | DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE | | | LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL | | | CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, CG-8. | | | 4- AUTO TURN FOR THE SANITATION SERVICE, FRONT LOADER | | | TRUCK WITH THE FOLLOWING SPECS: | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
5 |
Status |
P |
Date |
06-30-2021 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-30-2021 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-30-2021 |
Time |
15:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
F |
Date |
04-14-2021 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-14-2021 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-14-2021 |
Time |
13:51 |
Sent To |
|
|
| Notes |
| 2021-04-14 13:51:40 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 3/15/21 SUBMITTAL SET OF PLANS: | | | | | | 1. [SATISFIED] INDICATE THE BACK OF SIDEWALK AT THE | | | DRIVEWAY WILL BE THE HIGH POINT FOR DRAINAGE BY ADDING | | | FLOW ARROWS FOR SURFACE DRAINAGE. | | | | | | 2. [NOT SATISFIED] THE CONCEPTUAL ENGINEERING PLAN DOES | | | NOT MATCH THE SITE PLAN. RESPONSE TO PREVIOUS COMMENT | | | WAS TO INDICATE THE DRIVELANES ON THE WEST SIDE OF THE | | | BUILDING (PARALLLEL TO AUSTRALIAN AVE) WOULD BE | | | TWO-WAY. THIS IS SHOWN THIS WAY ON THE SITE PLAN. ON | | | THE CONCEPTUAL ENGINEERING PLAN, THERE ARE TWO | | | DIRECTIONAL ARROWS POINTING IN THE SAME DIRECTION | | | (NORTH) AND STOP SIGNS AND DO NOT ENTER SIGNS SHOWN AT | | | THE NORTH END OF THESE DRIVELANES. PREVIOUOS COMMENT: | | | DRIVE LANE PARALLEL TO N. AUSTRALIAN AVE IS SHOWN AS | | | TWO LANES IN THE SAME DIRECTION. | | | | | | 3. [NOT SATISFIED] THE CONCEPTUAL ENGINEERING PLAN DOES | | | NOT MATCH THE SITE PLAN (SEE #2 ABOVE). RESPONSE TO | | | PREVIOUS COMMENT INDICATED ENTERING VEHICLES FROM | | | AUSTRALIAN AVE WOULD BE ABLE TO TURN RIGHT ONTO THE | | | DRIVELANES ON THE WEST SIDE OF THE BUILDING. THE | | | CONCEPTUAL ENGINEERING PLAN SHOWS DO NOT ENTER SIGNS AT | | | THE ENTRANCE OF THE WEST DRIVELANES, IF THE WEST | | | DRIVELANES ARE KEPT AS ONE-WAY, WHAT SIGNAGE OR | | | PAVEMENT MARKINGS WILL CONTROL EACH LANE OF TRAFFIC AT | | | THE STOP SIGN. PREVIOUS COMMENT: WHAT TRAFFIC CONTROL | | | WILL THERE BE FOR THE INTERSECTION OF THE WEST AND | | | NORTH DRIVE LANES AT THE DRIVEWAY ENTRANCE? HOW WILL | | | THE TWO NORTH BOUND LANES OPERATE? | | | | | | 4. [SATISFIED] PERIMETER BERM AND/OR SWALE MAY BE | | | REQUIRED ALONG THE EAST PROPERTY LINE. | | | | | | 5. [SATISFIED] ENDWALL MAY BE REQIURED FOR PIPE IN | | | CANAL R/W. | | | | | | 6. [SATISFIED] TYPICAL SECTIONS BETWEEN PROPERTY LINE | | | AND FACE OF BUILDING AT ALL PROPERTY LINES WILL BE | | | REQUIRED FOR THE ENGINEERING PERMIT SUBMITTAL. | | | | | | NEW COMMENT: | | | | | | 7. PLEASE CLARIFY THE HATCHING SHONE ON THE CONCEPTUAL | | | ENGINEERING PLAN. THE LEGEND INDICATES THE 24' | | | DRIVELANE WILL BE 'PROPOSED ECO-FRIENDLY GRASS BLOCK". | | | THE HATCHING FOR THE PARKING SPACES DOES NOT APPEAR IN | | | THE LEGEND. THE SITE PLAN INDIACTES THE PARKING SPACES | | | ADJACENT TO THE NORTH PROPERTY LINE AND ADJACENT TO THE | | | EAST PROEPRTY LINE WILL BE PERMEABLE PAVERS. THE SITE | | | PLAN INDICATES THE PARKING SPACES FACING THE BUILDING | | | WILL BE THE SAME SURFACE AS THE DRIVE LANES. THE SITE | | | PLAN ALSO SHOWS MORE PAVER AREA ACROSS THE NORTH END OF | | | THE WEST TRAVEL LANES. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
F |
Date |
09-25-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-25-2020 |
Time |
17:55 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-25-2020 |
Time |
18:08 |
Sent To |
|
|
| Notes |
| 2020-09-25 18:08:26 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 9/23/20 SUBMITTAL SET OF PLANS: | | | | | | 1. INDICATE THE BACK OF SIDEWALK AT THE DRIVEWAY WILL | | | BE THE HIGH POINT FOR DRAINAGE BY ADDING FLOW ARROWS | | | FOR SURFACE DRAINAGE. | | | | | | 2. DRIVE LANE PARALLEL TO N. AUSTRALIAN AVE IS SHOWN AS | | | TWO LANES IN THE SAME DIRECTION. | | | | | | 3. WHAT TRAFFIC CONTROL WILL THERE BE FOR THE | | | INTERSECTION OF THE WEST AND NORTH DRIVE LANES AT THE | | | DRIVEWAY ENTRANCE? HOW WILL THE TWO NORTH BOUND LANES | | | OPERATE? | | | | | | 4. PERIMETER BERM AND/OR SWALE MAY BE REQUIRED ALONG | | | THE EAST PROPERTY LINE. | | | | | | 5. ENDWALL MAY BE REQIURED FOR PIPE IN CANAL R/W. | | | | | | 6. TYPICAL SECTIONS BETWEEN PROPERTY LINE AND FACE OF | | | BUILDING AT ALL PROPERTY LINES WILL BE REQUIRED FOR THE | | | ENGINEERING PERMIT SUBMITTAL. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
08-26-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-26-2020 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-26-2020 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2020-08-26 15:20:37 | THE FOLLOWONG COMENTS ARE FROM THE REVIEW OF THE | | | 8/5/2020 SUBMITTAL PLANS. | | | | | | 1. LOCATE THE TOP OF BANK, WATER'S EDGE AND TOE OF | | | SLOPE OF THE CANAL WHERE THE STORMWATER OUTFALL PIPE | | | WILL BE LOCATED. [SATISFIED] | | | | | | 2. IDENTIFY THE VERTICAL DATUM ON THE ENGINEERING PLANS | | | AND PROVIDE THE CONVERSION EQUATION TO NGVD 1929 IF | | | NGVD 1929 IS NOT THE VERTICAL DATUM. LIST BOTH ON EVERY | | | SHEET WITH ELEVATION INFORMATION. [PARTIALLY SATISFIED] | | | CONFIRM THE CONVERSION FACTOR IS SUBTRACTED FROM THE | | | NAVD88 ELEVATION TO OBTAIN THE NGVD29 ELEVATION. | | | | | | 3. PROVIDE THE VERTICAL DATUM CONVERSION EQUATION TO | | | NGVD 1929 ON THE SURVEY.[PARTIALLY SATISFIED] NGVD IS | | | MISLABELED AS NGVD1988 INSTEAD OF NGVD1929 ON THE | | | COMAPSS SURVEY. | | | | | | 4. AUSTRALIAN AVE IS MAINTAINED BY PALM BEACH COUNTY. | | | APPROVAL FROM THE COUNTY IS REQUIRED FOR ANY | | | IMPROVEMENTS WITHIN AUSTRALIAN AVE RIGHT OF WAY. | | | [PARTIALLY SATISFIED] THIS CAN BE A CONDITION OF SITE | | | PLAN APPROVAL. | | | | | | 5. CONSIDER REDUCING THE DEPTH OF PARKING SPACES AND | | | PROVIDE 2 FEET OF LANDSCAPE AREA OVERHANG.[SATISFIED] | | | IT APPEARS ALL OF THE PARKING SPACES FACING THE | | | PROPERTY LINES HAVE TWO FEET OF OVERHANG IN THE | | | LANSDCAPE AREA. | | | | | | 6. SHOW UTILITIES ON THE LANDSCAPE PLANS.[SATISFIED] | | | 6.1 SUGGEST MOVING THE FIRE LINE ALONG THE NORTH | | | PROPERTY LINE INTO THE PAVEMENT AREA AND/OR PROVIDE | | | ROOT BARRIERS. | | | | | | NEW COMMENTS: | | | 7. WILL THERE BE A FENCE ALONG THE NORTH PROPERTY LINE? | | | | | | 8. PROVIDE SWALES A FEW FEET FROM THE PROPERTY LINES TO | | | AVOID DIRECT RUNOFF TO THE RIGHT OF WAY OR ADJACENT | | | PROPERTIES. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 (O) | | | 561-351-0510 (M) | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
04-08-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-08-2020 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-08-2020 |
Time |
18:41 |
Sent To |
|
|
| Notes |
| 2020-04-08 18:41:01 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | | | | 1. LOCATE THE TOP OF BANK, WATER?S EDGE AND TOE OF | | | SLOPE OF THE CANAL WHERE THE STORMWATER OUTFALL PIPE | | | WILL BE LOCATED. | | | | | | 2. IDENTIFY THE VERTICAL DATUM ON THE ENGINEERING PLANS | | | AND PROVIDE THE CONVERSION EQUATION TO NGVD 1929 IF | | | NGVD 1929 IS NOT THE VERTICAL DATUM. LIST BOTH ON EVERY | | | SHEET WITH ELEVATION INFORMATION. | | | | | | 3. PROVIDE THE VERTICAL DATUM CONVERSION EQUATION TO | | | NGVD 1929 ON THE SURVEY. | | | | | | 4. AUSTRALIAN AVE IS MAINTAINED BY PALM BEACH COUNTY. | | | APPROVAL FROM THE COUNTY IS REQUIRED FOR ANY | | | IMPROVEMENTS WITHIN AUSTRALIAN AVE RIGHT OF WAY. | | | | | | 5. CONSIDER REDUCING THE DEPTH OF PARKING SPACES AND | | | PROVIDE 2 FEET OF LANDSCAPE AREA OVERHANG. | | | | | | 6. SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING | | | CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
5 |
Status |
P |
Date |
06-07-2021 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
06-07-2021 |
Time |
07:47 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-06-07 07:50:13 | PASSED, BUT WHAT IS RED LINE ALONG N AND E PROPERTY | | | LINE ON SURVEY? | | | | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
4 |
Status |
F |
Date |
03-26-2021 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
03-26-2021 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-26 09:10:30 | 1. UNDER ORIGINATION BENCHMARK, IT STILL READS NGVD | | | 1988 - S/B 1929. | | | 2. TITLE COMMITMENT REVIEW STATEMENT NEEDS TO BE | | | CURRENT AND REFERS TO THE WRONG PLAT. | | | 3. FRONT CORNERS LABELED AS "FALLS IN WALK" - WHAT WAS | | | SET FOR CORNER MONUMENTATION? |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
3 |
Status |
F |
Date |
09-23-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-23-2020 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-23 11:32:27 | 1. UNITY OF TITLE APPLICATION RECEIVED. | | | 2. UNDER "ORIGINATION BENCHMARK" CHANGE ELEV. OF NGVD | | | 1988 TO 1929. | | | 3. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
09-03-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-03-2020 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-03 09:58:00 | 1. WAITING ON RECEIPT OF REVISED SURVEY. | | | 2. WAITING ON RECEIPT OF UNITY OF TITLE APPLICATION. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
04-08-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-08-2020 |
Time |
08:23 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-08 08:36:57 | 1. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH. | | | 2. CALL OUT VERTICAL DATUM AND CONVERSION TO NGVD-29. | | | 3. NO PRELIMINARY ENGINEERING PLANS PROVIDED. | | | 4. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE | | | THROUGH ENGINEERING SERVICES. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
03-31-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-31-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-03-31 19:00:15 | NO FURTHER COMMENTS. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-10 15:46:13 | NO FURTHER COMMENTS | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
04-07-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-07 17:24:25 | TRAFFIC STATEMENT COMMENTS: | | | 1. PROVIDE COUNTY TPS LETTER. | | | | | | | | | SITE PLAN COMMENTS: | | | 2. PROVIDE COUNTY DRIVEWAY LETTER. | | | 3. SHOW CURBS (MEDIAN) ON OPPOSITE SIDE OF STREET ALONG | | | AUSTRALIAN AVENUE. | | | 4. PROVIDE PHOTOMETRIC ANALYSIS. | | | 5. PROVIDE ENGINEERING PLAN. | | | 6. INDICATE THE LOCATION OF THE REQUIRED 10 X 25 FEET | | | LOADING AREA. | | | 7. PROVIDE ADDITIONAL BICYCLE PARKING SPACES NEAR THE | | | FRONT ENTRANCE. | | | 8. ONLY ONE ACCESS POINT ON AUSTRALIAN AVENUE ARE | | | ALLOWED PER CITY CODE SECTION 94-312. | | | 9. RELOCATE THE SOUTHERN ACCESS POINT TO RE-ALIGN WITH | | | THE PARKING AISLE OR MOVE PARKING STALLS ALONG THE | | | SOUTH SIDE OF THE PROPERTY OR CLOSE THE DRIVEWAY. | | | 10. CONSIDER RAISING THE SECTION OF DRIVE AISLE ALONG | | | THE WESTERN FRONTAGE AND EXPAND THE DECORATIVE PAVERS | | | TO COVER THE ENTIRE WESTERN DRIVE AISLE. | | | 11. IDENTIFY DROP OFF AREA, IF ANY. | | | 12. PROVIDE ADDITIONAL PEDESTRIAN ACCESS NEAR THE | | | SOUTHERN DRIVEWAY LEADING TO THE SIDE AND BACK | | | ENTRANCES. | | | 13. COORDINATE WITH COUNTY ON THE PLANNED CORRIDOR | | | IMPROVEMENT ALONG AUSTRALIAN AVENUE. | | | 14. PROVIDE A 10-FOOT EASEMENT ALONG THE EASTERN | | | FRONTAGE FOR FUTURE DEVELOPMENT OF SHARED USE PATH PER | | | CITY'S BICYCLE MASTER PLAN | | | | | | | | | VALERIO ORICCHIO | | | [email protected] | | | 561-494-1092 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
07-13-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
07-13-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-13-2021 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
04-14-2021 |
|
|
Cont ID |
|
| Sent By |
|
Date |
04-14-2021 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
04-14-2021 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-04-14 15:03:50 | 3/18/21 SUBMITTAL COMMENTS- 2808 AUSTRALIAN AVENUE- THE | | | LORDS PLACE - ISPR 20-11 | | | Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11 | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE | | | SEARCH. (SATISFIED) | | | | | | UNITY OF TITLE REQUIRED. (SATISFIED) | | | | | | PROVIDE THE RESUBMITTAL FEE OF 20% OF THE ORIGINAL | | | APPLICATION FEE, $200 FOR THE 3RD SUBMITTAL. EACH | | | SUBSEQUENT SUBMITTAL WILL BE ASSESSED A RESUBMITTAL | | | FEE. | | | _______________________________________________________ | | | ___________________________ | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS | | | OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11 | | | IN X 17 IN) | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION | | | FEE WILL BE ASSESSED. | | | | | | | | | PROVIDE SCREENING FOR THE NEWLY PROPOSED GENERATOR. | | | | | | THE MINIMUM LOADING ZONE DIMENSIONS ARE 10 FT X 25 FT. | | | | | | | | | ALANA WOOTEN | | | PLANNER | | | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | 401 CLEMATIS STREET P.O. BOX 3147 | | | WEST PALM BEACH, FL 33402 | | | 561-822-1449 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
09-30-2020 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
09-30-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
awooten |
Date |
09-30-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-10-06 09:41:29 | PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE LORDS | | | PLACE - ISPR 20-11 3RD REVIEW 9/30/2020 | | | Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11 | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE | | | SEARCH. (SATISFIED) | | | | | | UNITY OF TITLE REQUIRED. (SATISFIED) | | | | | | PROVIDE THE RESUBMITTAL FEE OF 20% OF THE ORIGINAL | | | APPLICATION FEE, $200 FOR THE 3RD SUBMITTAL. EACH | | | SUBSEQUENT SUBMITTAL WILL BE ASSESSED A RESUBMITTAL | | | FEE. (UNSATISFIED) | | | _______________________________________________________ | | | ___________________________ | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS | | | OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11 | | | IN X 17 IN) | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION | | | FEE WILL BE ASSESSED. | | | | | | ALANA WOOTEN | | | PLANNER | | | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | 401 CLEMATIS STREET P.O. BOX 3147 | | | WEST PALM BEACH, FL 33402 | | | 561-822-1449 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
09-03-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
09-03-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
09-03-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-09-03 14:44:24 | PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE LORDS | | | PLACE - ISPR 20-11 2ND REVIEW 9/3/2020 | | | Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11 | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE | | | SEARCH. | | | | | | UNITY OF TITLE REQUIRED. (UNSATISFIED) | | | _______________________________________________________ | | | ___________________________ | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS | | | OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11 | | | IN X 17 IN) | | | C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION | | | FEE WILL BE ASSESSED. | | | | | | ALANA WOOTEN | | | PLANNER | | | DEVELOPMENT SERVICES | | | PLANNING DIVISION | | | 401 CLEMATIS STREET ? P.O. BOX 3147 | | | WEST PALM BEACH, FL 33402 | | | 561-822-1449 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
04-08-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
04-08-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-04-08 11:58:58 | PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE | | | LORD?S PLACE - ISPR 20-11 | | | | | | BICYCLE RACK LOCATED AT THE REAR OF BUILDING, STAFF | | | SUGGESTS RELOCATING IT CLOSER TO THE ENTRANCE, OR | | | PROVIDE SOME IN THE FRONT AND SOME IN THE REAR. | | | | | | WHAT IS THE PURPOSE OF THE FRONT AREA DROP OFF? STAFF | | | SUGGESTS MAKING IT ONE WAY FOR SAFETY. | | | | | | STAFF SUGGESTS REMOVING THE WHEEL STOPS AND USING CURBS | | | FOR PARKING SPACES TO PROVIDING FOR MORE PERVIOUS | | | LANDSCAPE AREA. | | | | | | STAFF SUGGESTS A PEDESTRIAN/SIDEWALK CONNECTION ON | | | AUSTRALIAN AVENUE. | | | | | | PROVIDE A SURVEY BASED ON TITLE SEARCH. | | | | | | UNITY OF TITLE REQUIRED. | | | | | | ALANA WOOTEN | | | PLANNER | | | PLANNING DIVISION | | | 561-822-1449 | | | [email protected] | | | | | | |
|
|
| |
Print |
|
Account Summary | Usage Policy | Privacy Policy