Plan Review Details - Project Z20030013
Plan Review Stops For Project Z20030013
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 12-23-2020 Cont ID  
Sent By rbrown Date 12-23-2020 Time 11:41 Rev Time 0.00
Received By awooten Date 12-23-2020 Time 11:41 Sent To  
Notes
2020-12-23 11:44:19DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 REVIEW OF SITE PLAN APPROVAL APPLICATION HAS PASED. THE
 FOLLOWING COMMENTS MUST BE ADDRESSED FOR PERMIT
 APPLICATION:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. RENOVATION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  
2020-09-30 15:27:42SEE ZONING REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 04-08-2020 Cont ID  
Sent By rbrown Date 04-08-2020 Time 19:25 Rev Time 0.00
Received By rbrown Date 04-08-2020 Time 19:24 Sent To  
Notes
2020-04-08 19:46:23DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. RENOVATION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. NUMBER OF ACCESSIBLE PARKING SPACES. THE PARKING
 DATA ON SITE PLAN SHEET 1 STATES THAT 86 PARKING SPACES
 WILL BE PROVIDED BUT THE PLAN ONLY SHOWS 2 ACCESSIBLE
 PARKING SPACES. PER SECTION 208.2 OF FLORIDA
 ACCESSIBILITY CODE, 4 ACCESSIBLE PARKING SPACES ARE
 REQUIRED. THE MINIMUM NUMBER OF ACCESSIBLE PARKING
 SPACES PROVIDED SHALL BE IN ACCORDANCE WITH SECTION
 208.2 OF FLORIDA ACCESSIBILITY CODE.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. WHEN THE
 EDDITIONAL 2 ACCESSIBLE PARKING SPACES ARE PROVIDED,
 THEY ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE PER SECTION 208.3 OF FLORIDA ACCESSIBILITY
 CODE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 5. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. FOR INFORMATION ON THE REQUIRED TYPE, SIZE
 AND LOCATION, PLEASE CONTACT TIM LARGE, CHIEF PLUMBING
 INSPECTOR, DEVELOPMENT SERVICES DEPARTMENT, AT (561)
 805-6692, OR BY EMAIL: [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 8. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 5 Status P Date 10-05-2021 Cont ID  
Sent By rrossano Date 10-05-2021 Time   Rev Time 0.00
Received By rrossano Date 10-05-2021 Time   Sent To  
Notes
2021-10-05 13:06:19REVISE ENGINEERING PLANS FOR E21070029 TO REFLECT THESE
 PROPOSED CHANGES ONCE APPROVED BY TRAFFIC.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 03-26-2021 Cont ID  
Sent By rrossano Date 03-26-2021 Time   Rev Time 0.00
Received By rrossano Date 03-26-2021 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 09-24-2020 Cont ID  
Sent By rrossano Date 09-24-2020 Time   Rev Time 0.00
Received By rrossano Date 09-24-2020 Time   Sent To  
Notes
2020-09-24 13:53:431. CONFIRM THAT A COMPLETED LOS ANALYSIS SUMMARY TABLE
 HAS BEEN SUBMITTED DIRECTLY TO ENGINEERING (SHEET 33 OF
 CITY OF WPB DEVELOPMENT APPLICATION).
 2. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 3. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 4. PROVIDE ONSITE CLEANOUT NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 5. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 6. FOR FORMAL ENGINEERING SUBMITTAL , PLANS SHALL SHOW
 PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER,
 STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING
 STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY
 SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND
 OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH
 BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES
 SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS,
 CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND
 MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL
 AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW.
 DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN
 VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY,
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
 7. FOR FORMAL ENGINEERING SUBMITTAL , CUT AND CAP
 UTILITIES NOT IN USE, AND REMOVE ANY ABANDONED UTILITY
 LINES LARGER THAN 2 INCHES FROM CITY RIGHT OF WAY.
 8. FOR FORMAL ENGINEERING SUBMITTAL , PROVIDE DEDICATED
 UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO
 PROPOSED UTILITY WATER METERS.
 9. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER
 METER AND BACKFLOW PREVENTION.
 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT
 DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW
 PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL
 BACKFLOWS.
 11. FOR FORMAL ENGINEERING SUBMITTAL, SFWMD ERP AND
 NPDES NOI REQUIREMENTS WILL BE ENFORCED.
 - AN NOI IS REQUIRED FOR PROJECTS THAT:
 - 1) DISTURB ONE OF MORE ACRES OF LAND OR DISTURB LESS
 THAN ON ACRE OF LAND BUT ARE PART OF A COMMON PLAN OF
 DEVELOPMENT OR SALE;
 - 2) DISCHARGE STORMWATER TO SURFACE WATERS OF THE
 STATE OR TO SURFACE WATERS OF THE STATE THROUGH A
 MUNICIPAL SEPARATE STORM SEWER SYSTEM (MS4).
 - THE SFWMD ERP CAN BE OBTAINED THROUGH A 10-2 SELF
 CERTIFICATION THROUGH FDEP OR AN ERP APPLICATION
 THROUGH SFWMD. EITHER WAY, THE DEVELOPER/ENGINEER SHALL
 SUBMIT A COPY OF THE ERP PERMIT OR FDEP ACKNOWLEDGEMENT
 OF THE 10-2 CERTIFICATION.
 12. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 13. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 14. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND
 INCLUDE PROJECT NAME, ADDRESS AND PERMIT NUMBER
 (Z-XXXXXXXX).
  
 THANKS,
  
 RICK ROSSANO
 PROJECT COORDINATOR
 WPB ENGINEERING SERVICES
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 CELL: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 08-17-2020 Cont ID  
Sent By rrossano Date 08-17-2020 Time   Rev Time 0.00
Received By rrossano Date 08-17-2020 Time   Sent To  
Notes
2020-08-17 15:23:48COMMENTS PER MARK HURLEY, CITY OF WPB PUB. UTIL. CUST.
 SERVICE, [email protected], OR 561-822-2262:
  
 -THERE IS A BACKFLOW ASSEMBLY MISSING FROM THE WATER
 ENGINEERING PLAN. PLEASE ADD IT.
 -DCDA BACKFLOW ASSEMBLY SHOULD NOT BE ATTACHED TO THE
 NORTHERN METER BOX. THAT LARGE FIRELINE SHOULD BE A
 SEPARATE WATER SERVICE TO THE WATER MAIN. PLEASE
 CORRECT.
 -PLEASE ADD ROOT BARRIERS BETWEEN THE TREES AND
 CUSTOMER?S FIRELINE PIPING AFTER DCDA.
 -ON FORMAL ENGINEERING SUBMITTAL, LABEL THE SIZES OF
 THE WATER METERS AND BACKFLOW ASSEMBLIES. THE PRIVATE
 DOMESTIC WATER PIPE SAYS 3 IN., BUT THE DOMESTIC METER
 AND BACKFLOW ASSEMBLY IS SMALLER THAN THAT. IF LARGER
 METER IS NEEDED, NEW WATER SERVICE MAY NEED TO BE
 BUILT. LARGER METER MAY REQUIRE MORE SPACE,
 ABOVE-GROUND INSTALLATION, AND UTILITY EASEMENTS.
 -FOR ENGINEERING SUBMITTAL, IDENTIFY EXISTING PRIVATE
 FIRELINE PIPING AND WHAT WILL BE HAPPENING TO IT. WILL
 IT BE ABANDONED IN PLACE, REMOVED, OR GROUTED?
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 04-07-2020 Cont ID  
Sent By rrossano Date 04-07-2020 Time   Rev Time  
Received By rrossano Date 04-07-2020 Time   Sent To  
Notes
2020-04-07 13:45:341. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
 2. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 3. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORM WATER, AND SANITARY AND SEWER
 LINES, INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER
 AND SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS. CUT AND CAP UTILITIES NOT IN USE,
 AND REMOVE ANY ABANDONED UTILITY LINES LARGER THAN 2
 INCHES FROM CITY RIGHT OF WAY.
 4. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 5. SHOW DIMENSIONS OF PROPOSED DUMPSTER ENCLOSURE PER
 CURRENT CITY OF WPB STANDARD DETAIL GC-8.
 6. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY
 SEWER ARE REQUIRED.
 7. PLEASE CALLOUT DOMESTIC BACKFLOW PREVENTER AS RPPA
 AND FIRE BACKFLOW PREVENTER AS DCDA.
 8. PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION (NAVD 1988 AND NGVD 1929).
 9. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 10. COMMENT RESCINDED.
 11. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 EASEMENT FOR PLACEMENT OF PROPOSED WATER METERS.
 12. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE
 ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER
 METER AND BACKFLOW PREVENTION.
 13. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES
 OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS.
 14. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING
 APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT
 SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING
 SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED
 LEAD-FREE DESIGN.
 15. FOR FORMAL ENGINEERING SUBMITTAL CLEARLY SHOW ROAD
 RIGHT OF WAY.
 16. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY
 ELEVATIONS AT MANHOLE TIE-IN.
 17. FOR FORMAL ENGINEERING SUBMITTAL, IF SANITARY MAINS
 ARE PROPOSED IN ROW PLEASE SHOW ADJACENT SANITARY
 LATERAL LOCATIONS AND SHOW ADDRESSES OF ADJACENT
 PARCELS.
 18. FOR FORMAL ENGINEERING SUBMITTAL, IF WATER MAINS
 ARE BEING REPLACED IN ROW, SHOW ADJACENT PARCEL
 ADDRESSES.
 19. FOR FORMAL ENGINEERING SUBMITTAL, ADD NOTE TO
 PROVIDE 50 FT. PAVEMENT RESTORATION TRANSITION ON EACH
 SIDE OF PROPOSED TRENCH IN CITY MAINTAINED ROADWAY
 AREAS PER CITY OF WPB STANDARD DETAIL GC-9.
 20. PLEASE NOTE THAT A PRE-PPRC-SUBMITTAL MEETING WITH
 ENGINEERING SERVICES IS HIGHLY SUGGESTED.
 21. PLEASE RESPOND TO ALL COMMENTS IN WRITING.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES, 561-822-2262
 [email protected]
  
 -SEE WELL ON PLAN, BUT RECORDS SHOW THAT THERE IS A
 DEDICATED IRRIGATION SERVICE THAT IS NOT CURRENTLY
 BEING USED. IS THE WELL BEING USED FOR IRRIGATION?
 -ARE ALL BACKFLOW PREVENTERS INCLUDING THE EXISTING 8
 IN. DCDA FIRELINE BACKFLOW ASSEMBLY SHOWN ON THE SITE
 PLAN?
 -NEED SUBMIT UTILITY PLAN.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES
 DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR, WEST PALM BEACH, FL
 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-30-2020 Cont ID  
Sent By pleduc Date 03-30-2020 Time   Rev Time 0.00
Received By pleduc Date 03-30-2020 Time 14:46 Sent To  
Notes
2020-03-30 14:52:52THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED LOCATION OF THE FIRE HYDRANT IN THE REAR
 OF THE PROPERTY IS NOT RECOMMENDED AND IS PREFERRED TO
 BE IN THE FRONT LOCATED WITH 100' OF ANY PROPOSED
 FDC'S. THE LOCATIONS SHALL BE CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT.
  
 9A) THE LOCATION OF ANY APPLICABLE DDCV AND FIRE LINE
 LOCATIONS SHALL MEET THE REQUIREMENTS OF NFPA 24 AND
 SHALL BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL,
 THE CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND
 THE CITY'S PLANNING AND ZONING OFFICE.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 6 Status P Date 10-19-2021 Cont ID  
Sent By rcaranci Date 10-19-2021 Time 16:22 Rev Time 0.00
Received By rcaranci Date 10-19-2021 Time 16:22 Sent To  
Notes
2021-10-19 16:23:14SUBMITTAL FROM 9/27 WITH PAVEMENT MARKING CHANGES WAS
 REVIEWED AND NO CHANGES WERE MADE TO THE APPROVED
 LANDSCAPE PLAN.

Review Stop L LANDSCAPING
Rev No 5 Status P Date 06-23-2021 Cont ID  
Sent By aburnett Date 06-23-2021 Time 12:27 Rev Time 0.00
Received By aburnett Date 06-23-2021 Time 12:27 Sent To  
Notes
2021-06-23 12:29:32FROM: ANDREW BURNETT, LANDSCAPE PLANNER 561-822-1562
 PROJECT: 2808 N AUSTRALIAN AVE Z20030013
 JUNE 23, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 BUILDING, SITE PLAN AND LANDSCAPE PLAN HAVE CHANGED.
 NEW COMMENTS ARE LISTED AFTER PREVIOUSLY SATISFIED
 COMMENTS.
  
 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE
 DISPOSITION CHART:
 ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE
 OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET
 DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300
 SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE,
 CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE
 MITIGATION DUE COLUMN.
 PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART.
 #17 CHANGED TO BLACK OLIVE SPECIES.
 ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 ,
 REQUIRING 50 SQ FT MITIGATION.
 ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE
 MITIGATION. ENTER 0 IN THE COLUMN.
 ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE
 AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM
 THE PROPOSED TREE LIST.
 RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE.
  
 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED
 MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER
 SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF
 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5
 FLOWERING TREES.
  
 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW
 REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE
 NUMBER OF SUBSTITUTIONS PROPOSED.
  
 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE
 REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS
 REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL
 AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES.
  
 JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF
 SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING
 TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED
 WILL BE MET.
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS.
  
 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS
 FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL
 STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE
 OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR
 SUPPORTING THE ROOT ZONES OF THE TREES.
  
 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30
 FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES,
 SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES
 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE
 CORRECTIONS.
  
 CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA
 CHART.
  
 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET
 IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB
 SECTION.
 PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR
 DROUGHT TOLERANT LEVELS OF EACH SPECIES.
  
 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR
 FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION
 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED
 50 POINTS.
  
 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES
 PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER
 SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE
 TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES,
 AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS,
 USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE
 PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND
 SEAGRAPE ARE POSSIBLE ADDITIONS.
  
  
 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES.
  
 PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT
 TOLERANT PLANTS BASED ON FINAL PLANT LIST.
  
 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN,
 RESPONSE TO COMMENTS WAS NOT SUFFICIENT.
  
  
 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN.
 ENGINEERING PLANS WERE NOT SUBMITTED.
  
 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT
 BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
  
 WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE.
  
 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH
 TREES.
 ADDITIONAL COMMENTS 4/12/21:
 18. SATISFIED ADJUST TREE SIZES TO MINIMUM OF 12 FEET
 IN HEIGHT.
 SHADY LADY TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 19. SATISFIED 6 BA ARE SHOWN ON THE PLAN, SO THE PLANT
 LIST NEEDS TO BE CORRECTED FROM 5 TO 6.
  
 20. SATISFIED 4 BA ARE SHOWN ON THE PLAN, SO THE PLANT
 LIST NEEDS TO BE CORRECTED FROM 5 TO 4.
  
 21. SATISFIED ADD THE EXISTING LIVE OAK TREE AND BLACK
 OLIVE TREE TO REMAIN TO THE PLANT LIST AND SHOW THE
 IDENTIFYING NUMBER FROM THE TREE DISPOSITION.
  
 22. SATISFIED SCREENING NEEDS TO BE PROVIDED FOR THE
 GENERATOR WITH A FENCE OR HEDGE.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 04-12-2021 Cont ID  
Sent By rcaranci Date 04-12-2021 Time 11:21 Rev Time 0.00
Received By rcaranci Date 04-12-2021 Time 11:21 Sent To  
Notes
2021-04-12 11:22:23FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2808 N AUSTRALIAN AVE Z20030013
 APRIL 12, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 BUILDING, SITE PLAN AND LANDSCAPE PLAN HAVE CHANGED.
 NEW COMMENTS ARE LISTED AFTER PREVIOUSLY SATISFIED
 COMMENTS.
  
 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE
 DISPOSITION CHART:
 ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE
 OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET
 DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300
 SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE,
 CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE
 MITIGATION DUE COLUMN.
 PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART.
 #17 CHANGED TO BLACK OLIVE SPECIES.
 ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 ,
 REQUIRING 50 SQ FT MITIGATION.
 ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE
 MITIGATION. ENTER 0 IN THE COLUMN.
 ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE
 AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM
 THE PROPOSED TREE LIST.
 RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE.
  
 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED
 MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER
 SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF
 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5
 FLOWERING TREES.
  
 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW
 REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE
 NUMBER OF SUBSTITUTIONS PROPOSED.
  
 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE
 REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS
 REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL
 AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES.
  
 JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF
 SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING
 TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED
 WILL BE MET.
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS.
  
 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS
 FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL
 STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE
 OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR
 SUPPORTING THE ROOT ZONES OF THE TREES.
  
 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30
 FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES,
 SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES
 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE
 CORRECTIONS.
  
 CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA
 CHART.
  
 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET
 IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB
 SECTION.
 PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR
 DROUGHT TOLERANT LEVELS OF EACH SPECIES.
  
 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR
 FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION
 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED
 50 POINTS.
  
 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES
 PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER
 SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE
 TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES,
 AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS,
 USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE
 PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND
 SEAGRAPE ARE POSSIBLE ADDITIONS.
  
  
 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES.
  
 PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT
 TOLERANT PLANTS BASED ON FINAL PLANT LIST.
  
 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN,
 RESPONSE TO COMMENTS WAS NOT SUFFICIENT.
  
  
 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN.
 ENGINEERING PLANS WERE NOT SUBMITTED.
  
 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT
 BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
  
 WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE.
  
 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH
 TREES.
 ADDITIONAL COMMENTS 4/12/21:
 18. ADJUST TREE SIZES TO MINIMUM OF 12 FEET IN HEIGHT.
 SHADY LADY TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 19. 6 BA ARE SHOWN ON THE PLAN, SO THE PLANT LIST NEEDS
 TO BE CORRECTED FROM 5 TO 6.
  
 20. 4 BA ARE SHOWN ON THE PLAN, SO THE PLANT LIST NEEDS
 TO BE CORRECTED FROM 5 TO 4.
  
 21. ADD THE EXISTING LIVE OAK TREE AND BLACK OLIVE TREE
 TO REMAIN TO THE PLANT LIST AND SHOW THE IDENTIFYING
 NUMBER FROM THE TREE DISPOSITION.
  
 22. SCREENING NEEDS TO BE PROVIDED FOR THE GENERATOR
 WITH A FENCE OR HEDGE.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 09-30-2020 Cont ID  
Sent By rcaranci Date 09-30-2020 Time 16:28 Rev Time 0.00
Received By rcaranci Date 09-30-2020 Time 16:28 Sent To  
Notes
2020-09-30 16:29:07FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2808 N AUSTRALIAN AVE Z20030013
 SEPTEMBER 30, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE
 DISPOSITION CHART:
 ? SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR THE LIVE
 OAK TREES #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET
 DIAMETER DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300
 SQ FT MITIGATION. IF THEY ARE 20 FEET OR MORE,
 CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER INTO THE
 MITIGATION DUE COLUMN.
 PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART.
 #17 CHANGED TO BLACK OLIVE SPECIES.
 ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 ,
 REQUIRING 50 SQ FT MITIGATION.
 ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE
 MITIGATION. ENTER 0 IN THE COLUMN.
 ? SATISFIED. TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE
 AND SHOW MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM
 THE PROPOSED TREE LIST.
 RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE.
  
 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED
 MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER
 SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF
 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5
 FLOWERING TREES.
  
 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW
 REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE
 NUMBER OF SUBSTITUTIONS PROPOSED.
  
 4. SATISFIED. SECTION 94-443(C)(3) REQUIRES THAT A
 MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE REQUIRED TO
 BE PLANTED WITHIN THE INTERIOR OF AN OFF STREET PARKING
 AREA SHALL BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE
 REFERRING TO ONE TREE PER 100 SQ FT., AS THIS WAS
 REMOVED FROM THE CODE IN 2018. SHOW THE PERCENTAGE OF
 CATEGORY 1 TREES PROVIDED FOR THE REQUIRED LANDSCAPE
 AREAS AS REQUIRED BY SECTION 94-443(C)(3) FOR TERMINAL
 AND INTERIOR ISLANDS. THERE ARE 11 REQUIRED TREES.
  
 JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF
 SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING
 TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED
 WILL BE MET.
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS.
  
 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS
 FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL
 STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE
 OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR
 SUPPORTING THE ROOT ZONES OF THE TREES.
  
 7. SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE PER 30
 FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES,
 SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES
 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE
 CORRECTIONS.
  
 CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA
 CHART.
  
 8. SATISFIED. ADJUST TREE SIZES TO MINIMUM OF 12 FEET
 IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB
 SECTION.
 PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR
 DROUGHT TOLERANT LEVELS OF EACH SPECIES.
  
 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR
 FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION
 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED
 50 POINTS.
  
 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES
 PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER
 SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE
 TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES,
 AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS,
 USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE
 PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND
 SEAGRAPE ARE POSSIBLE ADDITIONS.
  
  
 12. SATISFIED. REVISE THE SECTION IN THE LANDSCAPE DATA
 CHART TO COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES.
  
 PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT
 TOLERANT PLANTS BASED ON FINAL PLANT LIST.
  
 13. SATISFIED. SHOW LOCATIONS OF FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
 COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN,
 RESPONSE TO COMMENTS WAS NOT SUFFICIENT.
  
  
 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN.
 ENGINEERING PLANS WERE NOT SUBMITTED.
  
 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT
 BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 16. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED
 VALVES AND EQUIPMENT.
  
 WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE.
  
 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH
 TREES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 09-09-2020 Cont ID  
Sent By rcaranci Date 09-09-2020 Time 17:06 Rev Time 0.00
Received By rcaranci Date 09-09-2020 Time 17:06 Sent To  
Notes
2020-09-09 17:07:21FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: 2808 N AUSTRALIAN AVE Z20030013
 SEPTEMBER 9, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE
 DISPOSITION CHART:
 ? PARTIALLY SATISFIED. PROVIDE THE CANOPY DIAMETERS FOR
 THE LIVE OAK TREES #17 AND #19-23. IF THEY ARE LESS
 THAN 20 FEET DIAMETER DUE TO FPL PRUNING, THEN THEY
 WILL REQUIRE 300 SQ FT MITIGATION. IF THEY ARE 20 FEET
 OR MORE, CALCULATE THE ACTUAL SQUARE FOOTAGE AND ENTER
 INTO THE MITIGATION DUE COLUMN.
 PROVIDE THE CANOPY DIAMETER FOR EACH TREE ON THE CHART.
 #17 CHANGED TO BLACK OLIVE SPECIES.
 ? SATISFIED. QUEEN PALMS #24 AND 27 ARE CATEGORY 4 ,
 REQUIRING 50 SQ FT MITIGATION.
 ? SATISFIED. JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE
 MITIGATION. ENTER 0 IN THE COLUMN.
 ? PARTIALLY SATISFIED. TOTAL THE SQUARE FOOTAGE OF
 MITIGATION DUE AND SHOW MITIGATION SQUARE FOOTAGE TOTAL
 PROVIDED FROM THE PROPOSED TREE LIST.
 RECALCULATE AFTER ANY ADJUSTMENTS FOR ABOVE.
  
 2. SATISFIED. CORRECT THE CALCULATIONS FOR REQUIRED
 MINIMUM SHADE TREE AND FLOWERING TREE REQUIREMENTS PER
 SECTION 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF
 40%. 25750 SQ FT REQUIRES 18 SHADE TREES AND 5
 FLOWERING TREES.
  
 3. SATISFIED. CORRECT THE REFERENCE TO SUBSTITUTION OF
 PALMS FOR REQUIRED TREES. SECTION 94-442(D) NOW
 REQUIRES A 3:1 RATIO FOR SUBSTITUTION. PROVIDE THE
 NUMBER OF SUBSTITUTIONS PROPOSED.
  
 4. PARTIALLY SATISFIED. SECTION 94-443(C)(3) REQUIRES
 THAT A MINIMUM OF 75 PERCENT OF ALL TREES THAT ARE
 REQUIRED TO BE PLANTED WITHIN THE INTERIOR OF AN OFF
 STREET PARKING AREA SHALL BE CATEGORY 1 SHADE TREES.
 REMOVE LANGUAGE REFERRING TO ONE TREE PER 100 SQ FT.,
 AS THIS WAS REMOVED FROM THE CODE IN 2018. SHOW THE
 PERCENTAGE OF CATEGORY 1 TREES PROVIDED FOR THE
 REQUIRED LANDSCAPE AREAS AS REQUIRED BY SECTION
 94-443(C)(3) FOR TERMINAL AND INTERIOR ISLANDS. THERE
 ARE 11 REQUIRED TREES.
  
 JAPANESE BLUEBERRY TREES ARE NOT CATEGORY 1, STAFF
 SUGGEST CHANGING THE 2 AT THE EAST END OF THE BUILDING
 TO A CATEGORY 1 SPECIES, AND THE 75% OF THE 11 REQUIRED
 WILL BE MET.
  
 5. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING
 LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. PROVIDE
 THE TOTAL REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH
 SECTIONS.
  
 6. SATISFIED. STAFF SUGGESTS REDUCING THE PAVED AREAS
 FOR PARKING SPACES AND USING CURBS INSTEAD OF WHEEL
 STOPS TO ALLOW FOR PERVIOUS LANDSCAPE AREA AT THE
 OVERHANG. THIS ALSO ALLOWS MORE LANDSCAPE AREA FOR
 SUPPORTING THE ROOT ZONES OF THE TREES.
  
 7. PARTIALLY SATISFIED. BUFFER LENGTHS REQUIRE ONE TREE
 PER 30 FEET OR PORTION THEREOF. EAST BUFFER REQUIRES 7
 TREES, SOUTH BUFFER REQUIRES 11 TREES, NORTH BUFFER
 REQUIRES 12 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE
 CORRECTIONS.
  
 CHANGE PROVIDED TREES FOR WEST BUFFER TO 6 IN DATA
 CHART.
  
 8. PARTIALLY SATISFIED. ADJUST TREE SIZES TO MINIMUM OF
 12 FEET IN HEIGHT. MOVE SPECIES THAT ARE NOT TREES TO
 THE SHRUB SECTION.
 PINK SHOWER TREE NEEDS TO BE SHOWN AT 12 FEET MINIMUM.
  
 9. SATISFIED. ADD A COLUMN TO THE PLANT LIST FOR
 DROUGHT TOLERANT LEVELS OF EACH SPECIES.
  
 10. SATISFIED. UPDATE THE DESIGN OPTIONS CHART FOR
 FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION
 94-442(G) TO THE CURRENT CODE AND PROVIDE THE REQUIRED
 50 POINTS.
  
 11. SATISFIED. THE DIVERSITY OF THE TREE SPECIES
 PROPOSED ARE VERY LIMITED AND ARE MOSTLY SMALLER
 SPECIES. STAFF SUGGESTS AT LEAST 2 SPECIES FOR THE
 TREES ON THE EAST AND SOUTH BUFFER UNDER THE FPL LINES,
 AND AT LEAST 2 SPECIES ON THE NORTH AND WEST BUFFERS,
 USING CATEGORY 1 SHADE TREES TO PROVIDE SHADE FOR THE
 PARKING AND PEDESTRIAN AREAS. GREEN BUTTONWOOD AND
 SEAGRAPE ARE POSSIBLE ADDITIONS.
  
  
 12. PARTIALLY SATISFIED. REVISE THE SECTION IN THE
 LANDSCAPE DATA CHART TO COMPLY WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
 PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT
 TOLERANT PLANTS BASED ON FINAL PLANT LIST.
  
 13. PARTIALLY SATISFIED. SHOW LOCATIONS OF FPL
 TRANSFORMERS ON THE LANDSCAPE PLAN AND RESOLVE
 CONFLICTS WITH LANDSCAPING.
 COULD NOT IDENTIFY ON LANDSCAPE OR ENGINEERING PLAN,
 RESPONSE TO COMMENTS WAS NOT SUFFICIENT.
  
  
 14. SATISFIED. SHOW LOCATIONS OF ALL PROPOSED WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLAN.
 ENGINEERING PLANS WERE NOT SUBMITTED.
  
 15. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT
 BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 16. PARTIALLY SATISFIED. PROVIDE SCREENING FOR ALL
 GROUND MOUNTED VALVES AND EQUIPMENT.
  
 WATER AND FIRE BACKFLOWS NEED SCREENING HEDGE.
  
 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING
 ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH
 TREES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-07-2020 Cont ID  
Sent By rcaranci Date 04-07-2020 Time 14:40 Rev Time 0.00
Received By rcaranci Date 04-07-2020 Time 14:39 Sent To  
Notes
2020-04-07 14:40:29FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 2808 N AUSTRALIAN AVE Z20030013
 APRIL 7, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE THE FOLLOWING CORRECTIONS TO TREE
 DISPOSITION CHART:
 ? PROVIDE THE CANOPY DIAMETERS FOR THE LIVE OAK TREES
 #17 AND #19-23. IF THEY ARE LESS THAN 20 FEET DIAMETER
 DUE TO FPL PRUNING, THEN THEY WILL REQUIRE 300 SQ FT
 MITIGATION. IF THEY ARE 20 FEET OR MORE, CALCULATE THE
 ACTUAL SQUARE FOOTAGE AND ENTER INTO THE MITIGATION DUE
 COLUMN.
 ? QUEEN PALMS #24 AND 27 ARE CATEGORY 4 , REQUIRING 50
 SQ FT MITIGATION.
 ? JATROPHAS ARE NOT LARGE ENOUGH TO REQUIRE MITIGATION.
 ENTER 0 IN THE COLUMN.
 ? TOTAL THE SQUARE FOOTAGE OF MITIGATION DUE AND SHOW
 MITIGATION SQUARE FOOTAGE TOTAL PROVIDED FROM THE
 PROPOSED TREE LIST.
  
 2. CORRECT THE CALCULATIONS FOR REQUIRED MINIMUM SHADE
 TREE AND FLOWERING TREE REQUIREMENTS PER SECTION
 94-443(C)(2)B. BASED ON REQUIRED OPEN SPACE OF 40%.
 25750 SQ FT REQUIRES 18 SHADE TREES AND 5 FLOWERING
 TREES.
  
 3. CORRECT THE REFERENCE TO SUBSTITUTION OF PALMS FOR
 REQUIRED TREES. SECTION 94-442(D) NOW REQUIRES A 3:1
 RATIO FOR SUBSTITUTION. PROVIDE THE NUMBER OF
 SUBSTITUTIONS PROPOSED.
  
 4. SECTION 94-443(C)(3) REQUIRES THAT A MINIMUM OF 75
 PERCENT OF ALL TREES THAT ARE REQUIRED TO BE PLANTED
 WITHIN THE INTERIOR OF AN OFF STREET PARKING AREA SHALL
 BE CATEGORY 1 SHADE TREES. REMOVE LANGUAGE REFERRING TO
 ONE TREE PER 100 SQ FT., AS THIS WAS REMOVED FROM THE
 CODE IN 2018. SHOW THE PERCENTAGE OF CATEGORY 1 TREES
 PROVIDED FOR THE REQUIRED LANDSCAPE AREAS AS REQUIRED
 BY SECTION 94-443(C)(3) FOR TERMINAL AND INTERIOR
 ISLANDS. THERE ARE 11 REQUIRED TREES.
  
 5. PROVIDE A PLAN SHOWING THE PARKING LANDSCAPE AREAS
 COUNTED TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND
 (4) AND PROVIDE CALCULATIONS. PROVIDE THE TOTAL
 REQUIRED AND PROVIDED AS ONE TOTAL FOR BOTH SECTIONS.
  
 6. STAFF SUGGESTS REDUCING THE PAVED AREAS FOR PARKING
 SPACES AND USING CURBS INSTEAD OF WHEEL STOPS TO ALLOW
 FOR PERVIOUS LANDSCAPE AREA AT THE OVERHANG. THIS ALSO
 ALLOWS MORE LANDSCAPE AREA FOR SUPPORTING THE ROOT
 ZONES OF THE TREES.
  
 7. BUFFER LENGTHS REQUIRE ONE TREE PER 30 FEET OR
 PORTION THEREOF. EAST BUFFER REQUIRES 7 TREES, SOUTH
 BUFFER REQUIRES 11 TREES, NORTH BUFFER REQUIRES 12
 TREES, WEST BUFFER REQUIRES 6 TREES. MAKE CORRECTIONS.
  
 8. ADJUST TREE SIZES TO MINIMUM OF 12 FEET IN HEIGHT.
 MOVE SPECIES THAT ARE NOT TREES TO THE SHRUB SECTION.
  
 9. ADD A COLUMN TO THE PLANT LIST FOR DROUGHT TOLERANT
 LEVELS OF EACH SPECIES.
  
 10. UPDATE THE DESIGN OPTIONS CHART FOR FLORIDA
 FRIENDLY LANDSCAPE REQUIREMENTS PER SECTION 94-442(G)
 TO THE CURRENT CODE AND PROVIDE THE REQUIRED 50 POINTS.
  
 11. THE DIVERSITY OF THE TREE SPECIES PROPOSED ARE VERY
 LIMITED AND ARE MOSTLY SMALLER SPECIES. STAFF SUGGESTS
 AT LEAST 2 SPECIES FOR THE TREES ON THE EAST AND SOUTH
 BUFFER UNDER THE FPL LINES, AND AT LEAST 2 SPECIES ON
 THE NORTH AND WEST BUFFERS, USING CATEGORY 1 SHADE
 TREES TO PROVIDE SHADE FOR THE PARKING AND PEDESTRIAN
 AREAS. GREEN BUTTONWOOD AND SEAGRAPE ARE POSSIBLE
 ADDITIONS.
  
  
 12. REVISE THE SECTION IN THE LANDSCAPE DATA CHART TO
 COMPLY WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM
 OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA
 NATIVE OR DROUGHT TOLERANT SPECIES SELECTED FROM THE
 CITY LIST OR THE LIST OF SPECIES IN THE MOST RECENT
 EDITION OF SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 WATERWISE SOUTH FLORIDA LANDSCAPES.
 PROVIDE THE TOTAL PERCENTAGE OF NATIVE AND DROUGHT
 TOLERANT PLANTS BASED ON FINAL PLANT LIST.
  
 13. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE
 PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
  
 14. SHOW LOCATIONS OF ALL PROPOSED WATER, SEWER AND
 DRAINAGE LINES ON THE LANDSCAPE PLAN. ENGINEERING PLANS
 WERE NOT SUBMITTED.
  
 15. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO
 SEPARATE LANDSCAPING FROM UTILITY LINES.
  
 16. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND
 EQUIPMENT.
  
 17. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE
 LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH TREES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 09-14-2020 Cont ID  
Sent By   Date 09-14-2020 Time   Rev Time 0.00
Received By   Date 09-14-2020 Time   Sent To  
Notes
2020-09-14 09:14:13NO COMMENTS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 03-27-2020 Cont ID  
Sent By   Date 03-27-2020 Time   Rev Time  
Received By   Date 03-27-2020 Time   Sent To  
Notes
2020-03-27 14:13:20PLEASE PROVIDE THE FOLLOWINGS:
  
 1- LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
  
 2- WHERE VISIBLE TO THE PUBLIC, COMMERCIAL CONTAINERS
 SHALL BE STORED IN A CITY APPROVED ENCLOSURE
 OBSTRUCTING THE CONTAINERS VIEW FROM PERSONS USING THE
 SIDEWALK, STREET, OR THE COMMERCIAL ESTABLISHMENT'S
 FACILITIES, EXCEPT WHEN ENCLOSURES ARE PROHIBITED, SUCH
 AS IN DOWNTOWN ALLEYS, OR OTHERWISE APPROVED BY THE
 CITY. THIS REQUIREMENT INDICATED IN THE CODE OF
 ORDINANCES, SECTION 74-34-A-2-D.
  
 3- DUMPSTER ENCLOSURE DETAIL. FOR A FREESTANDING SITE
 DUMPSTER ENCLOSURE, THE ENCLOSURE SHALL COMPLY WITH THE
 LATEST REVISION OF CITY OF WEST PALM BEACH GENERAL
 CONSTRUCTION-GARBAGE ENCLOSURE STANDARD, CG-8.
 4- AUTO TURN FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK WITH THE FOLLOWING SPECS:
 - TRUCK LENGTH: 35 FT
 - TRUCK WIDTH: 11 FT
 - TURNING RADIUS:
 - SAE TURNING RADIUS: 32.5 FT
 - CURB-TO-CURB DIAMETER: 74 FT
 - WALL-TO-WALL DIAMETER: 86.3 FT
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 5 Status P Date 06-30-2021 Cont ID  
Sent By tward Date 06-30-2021 Time 15:03 Rev Time 0.00
Received By tward Date 06-30-2021 Time 15:04 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 4 Status F Date 04-14-2021 Cont ID  
Sent By tward Date 04-14-2021 Time 13:23 Rev Time 0.00
Received By tward Date 04-14-2021 Time 13:51 Sent To  
Notes
2021-04-14 13:51:40THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/15/21 SUBMITTAL SET OF PLANS:
  
 1. [SATISFIED] INDICATE THE BACK OF SIDEWALK AT THE
 DRIVEWAY WILL BE THE HIGH POINT FOR DRAINAGE BY ADDING
 FLOW ARROWS FOR SURFACE DRAINAGE.
  
 2. [NOT SATISFIED] THE CONCEPTUAL ENGINEERING PLAN DOES
 NOT MATCH THE SITE PLAN. RESPONSE TO PREVIOUS COMMENT
 WAS TO INDICATE THE DRIVELANES ON THE WEST SIDE OF THE
 BUILDING (PARALLLEL TO AUSTRALIAN AVE) WOULD BE
 TWO-WAY. THIS IS SHOWN THIS WAY ON THE SITE PLAN. ON
 THE CONCEPTUAL ENGINEERING PLAN, THERE ARE TWO
 DIRECTIONAL ARROWS POINTING IN THE SAME DIRECTION
 (NORTH) AND STOP SIGNS AND DO NOT ENTER SIGNS SHOWN AT
 THE NORTH END OF THESE DRIVELANES. PREVIOUOS COMMENT:
 DRIVE LANE PARALLEL TO N. AUSTRALIAN AVE IS SHOWN AS
 TWO LANES IN THE SAME DIRECTION.
  
 3. [NOT SATISFIED] THE CONCEPTUAL ENGINEERING PLAN DOES
 NOT MATCH THE SITE PLAN (SEE #2 ABOVE). RESPONSE TO
 PREVIOUS COMMENT INDICATED ENTERING VEHICLES FROM
 AUSTRALIAN AVE WOULD BE ABLE TO TURN RIGHT ONTO THE
 DRIVELANES ON THE WEST SIDE OF THE BUILDING. THE
 CONCEPTUAL ENGINEERING PLAN SHOWS DO NOT ENTER SIGNS AT
 THE ENTRANCE OF THE WEST DRIVELANES, IF THE WEST
 DRIVELANES ARE KEPT AS ONE-WAY, WHAT SIGNAGE OR
 PAVEMENT MARKINGS WILL CONTROL EACH LANE OF TRAFFIC AT
 THE STOP SIGN. PREVIOUS COMMENT: WHAT TRAFFIC CONTROL
 WILL THERE BE FOR THE INTERSECTION OF THE WEST AND
 NORTH DRIVE LANES AT THE DRIVEWAY ENTRANCE? HOW WILL
 THE TWO NORTH BOUND LANES OPERATE?
  
 4. [SATISFIED] PERIMETER BERM AND/OR SWALE MAY BE
 REQUIRED ALONG THE EAST PROPERTY LINE.
  
 5. [SATISFIED] ENDWALL MAY BE REQIURED FOR PIPE IN
 CANAL R/W.
  
 6. [SATISFIED] TYPICAL SECTIONS BETWEEN PROPERTY LINE
 AND FACE OF BUILDING AT ALL PROPERTY LINES WILL BE
 REQUIRED FOR THE ENGINEERING PERMIT SUBMITTAL.
  
 NEW COMMENT:
  
 7. PLEASE CLARIFY THE HATCHING SHONE ON THE CONCEPTUAL
 ENGINEERING PLAN. THE LEGEND INDICATES THE 24'
 DRIVELANE WILL BE 'PROPOSED ECO-FRIENDLY GRASS BLOCK".
 THE HATCHING FOR THE PARKING SPACES DOES NOT APPEAR IN
 THE LEGEND. THE SITE PLAN INDIACTES THE PARKING SPACES
 ADJACENT TO THE NORTH PROPERTY LINE AND ADJACENT TO THE
 EAST PROEPRTY LINE WILL BE PERMEABLE PAVERS. THE SITE
 PLAN INDICATES THE PARKING SPACES FACING THE BUILDING
 WILL BE THE SAME SURFACE AS THE DRIVE LANES. THE SITE
 PLAN ALSO SHOWS MORE PAVER AREA ACROSS THE NORTH END OF
 THE WEST TRAVEL LANES.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 09-25-2020 Cont ID  
Sent By tward Date 09-25-2020 Time 17:55 Rev Time 0.00
Received By tward Date 09-25-2020 Time 18:08 Sent To  
Notes
2020-09-25 18:08:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 9/23/20 SUBMITTAL SET OF PLANS:
  
 1. INDICATE THE BACK OF SIDEWALK AT THE DRIVEWAY WILL
 BE THE HIGH POINT FOR DRAINAGE BY ADDING FLOW ARROWS
 FOR SURFACE DRAINAGE.
  
 2. DRIVE LANE PARALLEL TO N. AUSTRALIAN AVE IS SHOWN AS
 TWO LANES IN THE SAME DIRECTION.
  
 3. WHAT TRAFFIC CONTROL WILL THERE BE FOR THE
 INTERSECTION OF THE WEST AND NORTH DRIVE LANES AT THE
 DRIVEWAY ENTRANCE? HOW WILL THE TWO NORTH BOUND LANES
 OPERATE?
  
 4. PERIMETER BERM AND/OR SWALE MAY BE REQUIRED ALONG
 THE EAST PROPERTY LINE.
  
 5. ENDWALL MAY BE REQIURED FOR PIPE IN CANAL R/W.
  
 6. TYPICAL SECTIONS BETWEEN PROPERTY LINE AND FACE OF
 BUILDING AT ALL PROPERTY LINES WILL BE REQUIRED FOR THE
 ENGINEERING PERMIT SUBMITTAL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)
  
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 08-26-2020 Cont ID  
Sent By tward Date 08-26-2020 Time 15:20 Rev Time 0.00
Received By tward Date 08-26-2020 Time 15:22 Sent To  
Notes
2020-08-26 15:20:37THE FOLLOWONG COMENTS ARE FROM THE REVIEW OF THE
 8/5/2020 SUBMITTAL PLANS.
  
 1. LOCATE THE TOP OF BANK, WATER'S EDGE AND TOE OF
 SLOPE OF THE CANAL WHERE THE STORMWATER OUTFALL PIPE
 WILL BE LOCATED. [SATISFIED]
  
 2. IDENTIFY THE VERTICAL DATUM ON THE ENGINEERING PLANS
 AND PROVIDE THE CONVERSION EQUATION TO NGVD 1929 IF
 NGVD 1929 IS NOT THE VERTICAL DATUM. LIST BOTH ON EVERY
 SHEET WITH ELEVATION INFORMATION. [PARTIALLY SATISFIED]
 CONFIRM THE CONVERSION FACTOR IS SUBTRACTED FROM THE
 NAVD88 ELEVATION TO OBTAIN THE NGVD29 ELEVATION.
  
 3. PROVIDE THE VERTICAL DATUM CONVERSION EQUATION TO
 NGVD 1929 ON THE SURVEY.[PARTIALLY SATISFIED] NGVD IS
 MISLABELED AS NGVD1988 INSTEAD OF NGVD1929 ON THE
 COMAPSS SURVEY.
  
 4. AUSTRALIAN AVE IS MAINTAINED BY PALM BEACH COUNTY.
 APPROVAL FROM THE COUNTY IS REQUIRED FOR ANY
 IMPROVEMENTS WITHIN AUSTRALIAN AVE RIGHT OF WAY.
 [PARTIALLY SATISFIED] THIS CAN BE A CONDITION OF SITE
 PLAN APPROVAL.
  
 5. CONSIDER REDUCING THE DEPTH OF PARKING SPACES AND
 PROVIDE 2 FEET OF LANDSCAPE AREA OVERHANG.[SATISFIED]
 IT APPEARS ALL OF THE PARKING SPACES FACING THE
 PROPERTY LINES HAVE TWO FEET OF OVERHANG IN THE
 LANSDCAPE AREA.
  
 6. SHOW UTILITIES ON THE LANDSCAPE PLANS.[SATISFIED]
 6.1 SUGGEST MOVING THE FIRE LINE ALONG THE NORTH
 PROPERTY LINE INTO THE PAVEMENT AREA AND/OR PROVIDE
 ROOT BARRIERS.
  
 NEW COMMENTS:
 7. WILL THERE BE A FENCE ALONG THE NORTH PROPERTY LINE?
  
 8. PROVIDE SWALES A FEW FEET FROM THE PROPERTY LINES TO
 AVOID DIRECT RUNOFF TO THE RIGHT OF WAY OR ADJACENT
 PROPERTIES.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 04-08-2020 Cont ID  
Sent By tward Date 04-08-2020 Time 18:38 Rev Time 0.00
Received By tward Date 04-08-2020 Time 18:41 Sent To  
Notes
2020-04-08 18:41:01THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
  
 1. LOCATE THE TOP OF BANK, WATER?S EDGE AND TOE OF
 SLOPE OF THE CANAL WHERE THE STORMWATER OUTFALL PIPE
 WILL BE LOCATED.
  
 2. IDENTIFY THE VERTICAL DATUM ON THE ENGINEERING PLANS
 AND PROVIDE THE CONVERSION EQUATION TO NGVD 1929 IF
 NGVD 1929 IS NOT THE VERTICAL DATUM. LIST BOTH ON EVERY
 SHEET WITH ELEVATION INFORMATION.
  
 3. PROVIDE THE VERTICAL DATUM CONVERSION EQUATION TO
 NGVD 1929 ON THE SURVEY.
  
 4. AUSTRALIAN AVE IS MAINTAINED BY PALM BEACH COUNTY.
 APPROVAL FROM THE COUNTY IS REQUIRED FOR ANY
 IMPROVEMENTS WITHIN AUSTRALIAN AVE RIGHT OF WAY.
  
 5. CONSIDER REDUCING THE DEPTH OF PARKING SPACES AND
 PROVIDE 2 FEET OF LANDSCAPE AREA OVERHANG.
  
 6. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING
 CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 5 Status P Date 06-07-2021 Cont ID  
Sent By vnoel Date 06-07-2021 Time 07:47 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2021-06-07 07:50:13PASSED, BUT WHAT IS RED LINE ALONG N AND E PROPERTY
 LINE ON SURVEY?
  
  

Review Stop SURVEY SURVEYING
Rev No 4 Status F Date 03-26-2021 Cont ID  
Sent By vnoel Date 03-26-2021 Time 09:03 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2021-03-26 09:10:301. UNDER ORIGINATION BENCHMARK, IT STILL READS NGVD
 1988 - S/B 1929.
 2. TITLE COMMITMENT REVIEW STATEMENT NEEDS TO BE
 CURRENT AND REFERS TO THE WRONG PLAT.
 3. FRONT CORNERS LABELED AS "FALLS IN WALK" - WHAT WAS
 SET FOR CORNER MONUMENTATION?

Review Stop SURVEY SURVEYING
Rev No 3 Status F Date 09-23-2020 Cont ID  
Sent By vnoel Date 09-23-2020 Time 11:27 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-09-23 11:32:271. UNITY OF TITLE APPLICATION RECEIVED.
 2. UNDER "ORIGINATION BENCHMARK" CHANGE ELEV. OF NGVD
 1988 TO 1929.
 3. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 09-03-2020 Cont ID  
Sent By vnoel Date 09-03-2020 Time 09:56 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-09-03 09:58:001. WAITING ON RECEIPT OF REVISED SURVEY.
 2. WAITING ON RECEIPT OF UNITY OF TITLE APPLICATION.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 04-08-2020 Cont ID  
Sent By vnoel Date 04-08-2020 Time 08:23 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2020-04-08 08:36:571. SURVEY NEEDS TO BE BASED ON A TITLE SEARCH.
 2. CALL OUT VERTICAL DATUM AND CONVERSION TO NGVD-29.
 3. NO PRELIMINARY ENGINEERING PLANS PROVIDED.
 4. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING SERVICES.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date 03-31-2021 Cont ID  
Sent By   Date 03-31-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-03-31 19:00:15NO FURTHER COMMENTS.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-09-10 15:46:13NO FURTHER COMMENTS
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 04-07-2020 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2020-04-07 17:24:25TRAFFIC STATEMENT COMMENTS:
 1. PROVIDE COUNTY TPS LETTER.
  
  
 SITE PLAN COMMENTS:
 2. PROVIDE COUNTY DRIVEWAY LETTER.
 3. SHOW CURBS (MEDIAN) ON OPPOSITE SIDE OF STREET ALONG
 AUSTRALIAN AVENUE.
 4. PROVIDE PHOTOMETRIC ANALYSIS.
 5. PROVIDE ENGINEERING PLAN.
 6. INDICATE THE LOCATION OF THE REQUIRED 10 X 25 FEET
 LOADING AREA.
 7. PROVIDE ADDITIONAL BICYCLE PARKING SPACES NEAR THE
 FRONT ENTRANCE.
 8. ONLY ONE ACCESS POINT ON AUSTRALIAN AVENUE ARE
 ALLOWED PER CITY CODE SECTION 94-312.
 9. RELOCATE THE SOUTHERN ACCESS POINT TO RE-ALIGN WITH
 THE PARKING AISLE OR MOVE PARKING STALLS ALONG THE
 SOUTH SIDE OF THE PROPERTY OR CLOSE THE DRIVEWAY.
 10. CONSIDER RAISING THE SECTION OF DRIVE AISLE ALONG
 THE WESTERN FRONTAGE AND EXPAND THE DECORATIVE PAVERS
 TO COVER THE ENTIRE WESTERN DRIVE AISLE.
 11. IDENTIFY DROP OFF AREA, IF ANY.
 12. PROVIDE ADDITIONAL PEDESTRIAN ACCESS NEAR THE
 SOUTHERN DRIVEWAY LEADING TO THE SIDE AND BACK
 ENTRANCES.
 13. COORDINATE WITH COUNTY ON THE PLANNED CORRIDOR
 IMPROVEMENT ALONG AUSTRALIAN AVENUE.
 14. PROVIDE A 10-FOOT EASEMENT ALONG THE EASTERN
 FRONTAGE FOR FUTURE DEVELOPMENT OF SHARED USE PATH PER
 CITY'S BICYCLE MASTER PLAN
  
  
 VALERIO ORICCHIO
 [email protected]
 561-494-1092

Review Stop Z ZONING
Rev No 5 Status P Date 07-13-2021 Cont ID  
Sent By   Date 07-13-2021 Time   Rev Time 0.00
Received By   Date 07-13-2021 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 04-14-2021 Cont ID  
Sent By   Date 04-14-2021 Time   Rev Time 0.00
Received By   Date 04-14-2021 Time   Sent To  
Notes
2021-04-14 15:03:503/18/21 SUBMITTAL COMMENTS- 2808 AUSTRALIAN AVENUE- THE
 LORDS PLACE - ISPR 20-11
 Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE
 SEARCH. (SATISFIED)
  
 UNITY OF TITLE REQUIRED. (SATISFIED)
  
 PROVIDE THE RESUBMITTAL FEE OF 20% OF THE ORIGINAL
 APPLICATION FEE, $200 FOR THE 3RD SUBMITTAL. EACH
 SUBSEQUENT SUBMITTAL WILL BE ASSESSED A RESUBMITTAL
 FEE.
 _______________________________________________________
 ___________________________
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS
 OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11
 IN X 17 IN)
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION
 FEE WILL BE ASSESSED.
  
  
 PROVIDE SCREENING FOR THE NEWLY PROPOSED GENERATOR.
  
 THE MINIMUM LOADING ZONE DIMENSIONS ARE 10 FT X 25 FT.
  
  
 ALANA WOOTEN
 PLANNER
 DEVELOPMENT SERVICES
 PLANNING DIVISION
 401 CLEMATIS STREET P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status F Date 09-30-2020 Cont ID  
Sent By awooten Date 09-30-2020 Time   Rev Time 0.00
Received By awooten Date 09-30-2020 Time   Sent To  
Notes
2020-10-06 09:41:29PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE LORDS
 PLACE - ISPR 20-11 3RD REVIEW 9/30/2020
 Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE
 SEARCH. (SATISFIED)
  
 UNITY OF TITLE REQUIRED. (SATISFIED)
  
 PROVIDE THE RESUBMITTAL FEE OF 20% OF THE ORIGINAL
 APPLICATION FEE, $200 FOR THE 3RD SUBMITTAL. EACH
 SUBSEQUENT SUBMITTAL WILL BE ASSESSED A RESUBMITTAL
 FEE. (UNSATISFIED)
 _______________________________________________________
 ___________________________
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS
 OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11
 IN X 17 IN)
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION
 FEE WILL BE ASSESSED.
  
 ALANA WOOTEN
 PLANNER
 DEVELOPMENT SERVICES
 PLANNING DIVISION
 401 CLEMATIS STREET P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 09-03-2020 Cont ID  
Sent By   Date 09-03-2020 Time   Rev Time 0.00
Received By   Date 09-03-2020 Time   Sent To  
Notes
2020-09-03 14:44:24PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE LORDS
 PLACE - ISPR 20-11 2ND REVIEW 9/3/2020
 Z20030013 | 2808 N AUSTRALIAN AVENUE | ISPR 20-11
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 PROVIDE AN ELECTRONIC COPY OF THE SURVEY BASED ON TITLE
 SEARCH.
  
 UNITY OF TITLE REQUIRED. (UNSATISFIED)
 _______________________________________________________
 ___________________________
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A. WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
 B. PROVIDE AN ELECTRONIC COPY OF ALL PLANS AND 2 SETS
 OF PHYSICAL PLANS, ALONG WITH ONE (1) REDUCED COPY (11
 IN X 17 IN)
 C. PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
 D. IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
 E. A RESUBMITTAL FEE OF 20% OF THE ORIGINAL APPLICATION
 FEE WILL BE ASSESSED.
  
 ALANA WOOTEN
 PLANNER
 DEVELOPMENT SERVICES
 PLANNING DIVISION
 401 CLEMATIS STREET ? P.O. BOX 3147
 WEST PALM BEACH, FL 33402
 561-822-1449
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 04-08-2020 Time   Rev Time  
Received By   Date 04-08-2020 Time   Sent To  
Notes
2020-04-08 11:58:58PPRC ZONING COMMENTS- 2808 AUSTRALIAN AVENUE- THE
 LORD?S PLACE - ISPR 20-11
  
 BICYCLE RACK LOCATED AT THE REAR OF BUILDING, STAFF
 SUGGESTS RELOCATING IT CLOSER TO THE ENTRANCE, OR
 PROVIDE SOME IN THE FRONT AND SOME IN THE REAR.
  
 WHAT IS THE PURPOSE OF THE FRONT AREA DROP OFF? STAFF
 SUGGESTS MAKING IT ONE WAY FOR SAFETY.
  
 STAFF SUGGESTS REMOVING THE WHEEL STOPS AND USING CURBS
 FOR PARKING SPACES TO PROVIDING FOR MORE PERVIOUS
 LANDSCAPE AREA.
  
 STAFF SUGGESTS A PEDESTRIAN/SIDEWALK CONNECTION ON
 AUSTRALIAN AVENUE.
  
 PROVIDE A SURVEY BASED ON TITLE SEARCH.
  
 UNITY OF TITLE REQUIRED.
  
 ALANA WOOTEN
 PLANNER
 PLANNING DIVISION
 561-822-1449
 [email protected]
  
  