Plan Review Details - Project Z20010022
Plan Review Stops For Project Z20010022
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 02-12-2020 Cont ID  
Sent By rbrown Date 02-12-2020 Time 20:45 Rev Time 0.00
Received By rbrown Date 02-12-2020 Time 20:45 Sent To  
Notes
2020-02-12 20:55:52DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDINGS ON LOTS 1, 2,
 6 AND 7 WILL BE IN FLOOD ZONE AE, WITH A BASE FLOOD
 ELEVATION OF 6 FT NAVD. THE FIRST FLOOR OF THE
 BUILDINGS AND ALL ASSOCIATED MECHANICAL EQUIPMENT
 (CHILLERS, GENERATORS ETC.) SHALL BE 24 INCHES
 (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 6. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 CAROLINE PUELL, ADDRESSING COORDINATOR, AT (561) 805
 6659, OR BY EMAIL: [email protected]
  
 9. ART IN PUBLIC PLACES. IF THE HOMES ARE BUILT AS PART
 OF THE SAME PROJECT THAT PROJECT WILL BE SUBJECT TO ART
 IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE
 PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 02-12-2020 Cont ID  
Sent By rrossano Date 02-12-2020 Time   Rev Time 0.00
Received By rrossano Date 02-12-2020 Time   Sent To  
Notes
2020-02-12 10:10:521. THE CITY OF WEST PALM BEACH HAS A NUMBER OF
 REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY
 AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND
 WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE
 DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK
 BELOW: HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=
 ~\WPB_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION
 -FULL-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC0
 2A97B1960045731D3658206F27451722716EF
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBL
 IC-WORKS/FORMS,-PERMITS-APPLICATIONS
 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH,
 FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED
 SEPT. 22, 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. SEC. 90-7.
 POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE
 FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
 4. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY
 OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC
 RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF
 YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1040 FOR FURTHER
 ASSISTANCE.
 5. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS
 OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT
 MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL
 EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT,
 INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
 6. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
 7. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
 8. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND
 PROPOSED DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM
 AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE
 PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
 9. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
 10. PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 PROJECT FRONTAGE ON ESSEX CT. (LOTS 1 AND 5).
 11. PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
 12. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
 13. PLEASE LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 14. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE
 SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING
 PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT
 HIM AT 561-494-2262 OR [email protected]
 15. PROVIDE DEDICATED UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITY WATER METERS.
 16. PROVIDE UTILITY EASEMENTS FOR ALL PROPOSED
 UTILITIES.
 17. PLEASE LABEL ALL METERS, CLEANOUTS, ETC. AS EXIST.
 OR PROPOSED.
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES,
 PLEASE CONTACT 561-494-2262 OR [email protected]:
  
 -NEED DEMAND CHART ADDED TO UTILITY PLAN.
 -?DUAL? WATER SERVICES CANNOT BE USED. EACH WATER
 SERVICE MUST HAVE ITS OWN TAP AND WATER SERVICE LINE.
 -LATERALS AND CLEANOUTS LOOK TO CLOSE TO METERBOXES ->
 SHOULD BE 10? AWAY.
 -NO BACKFLOW ASSEMBLIES ARE SHOWN AND LABELED. WAS NOT
 SURE IF THEY WERE FORGOTTEN OR IF PLAN DESIGNER
 BELIEVED THEY WERE NOT REQUIRED. DETERMINATION CAN BE
 MADE BY PUBLIC UTILITIES (FIELD CUSTOMER SERVICE) IF
 PROVIDED DETAILED INFORMATION ON PROPERTIES BEING
 BUILT.
 -METER BOXES NOT LABELED WITH SIZE AND ASSOCIATED WATER
 SERVICE STANDARD DETAIL #.
 -CONFLICT CROSSINGS OF SEWER AND WATER MAINS NOT
 LABELED WITH RESOLUTION.
 -NEED PIPE MATERIAL ADDED TO LABEL OF EXISTING AND
 PROPOSED WATER MAINS.
 -IF E-W STREET/ROAD IS NOT CITY ROW, THEN THE ENTIRE
 WATER MAIN NEEDS TO BE IN A CREATED UTILITY EASEMENT.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, PROJECT COORDINATOR - ENGINEERING
 SERVICES DEPARTMENT
 DIRECT: (561) 494-1098 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 02-07-2020 Cont ID  
Sent By pleduc Date 02-07-2020 Time   Rev Time 0.00
Received By pleduc Date 02-07-2020 Time 11:50 Sent To  
Notes
2020-02-07 12:39:19THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS NEED
 TO BE ADDRESSED:
  
  
 1. THERE IS NO LENGTH DIMENSION PROVIDED AT THE
 HAMMERHEAD TURNAROUND.
  
 THE MINIMUM LENGTH DIMENSION STANDARD IS 120'.
  
  
 2. THE BUREAU'S REVIEW OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
  
 3. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status P Date 02-07-2020 Cont ID  
Sent By rcaranci Date 02-07-2020 Time 14:34 Rev Time 0.00
Received By rcaranci Date 02-07-2020 Time 14:34 Sent To  
Notes
2020-02-07 14:35:21PROPOSED SUBDIVISION WILL NOT CREATE ANY LANDSCAPE
 NONCONFORMITIES. ALL LOTS WILL HAVE TO COMPLY WITH
 MINIMUM LANDSCAPE REQUIREMENTS AT TIME OF PERMITS FOR
 CONSTRUCTION, AND TREE PROTECTION OR PERMITTING FOR
 REMOVAL OR RELOCATION.

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 02-11-2020 Cont ID  
Sent By   Date 02-11-2020 Time   Rev Time 0.00
Received By   Date 02-11-2020 Time   Sent To  
Notes
2020-02-11 12:07:50PUBLIC WORKS HAS NO OBJECTION OR COMMENTS FOR THE
 PROPOSED SUBDIVISION. FUTURE DEVELOPMENT PLAN MUST BE
 SUBMITED FOR REVIEW AND APPROVAL.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 1 Status F Date 02-10-2020 Cont ID  
Sent By tward Date 02-10-2020 Time 17:31 Rev Time 0.00
Received By tward Date 02-10-2020 Time 17:33 Sent To  
Notes
2020-02-10 17:33:28THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE OBTAINED FROM THE
 ENGINEERING SERVICES DEPARTMENT.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. DRAINAGE SYSTEM TO BE DESIGNED TO BE MEET SFWMD ERP
 CRITERIA FOR WATER QUALITY AND PEAK FLOW ATTENUATION.
  
 2. DRAINAGE FLOW SHOULD MATCH EXISTING, FLOW TOWARD S.
 FLAGLER DRIVE. DRAINAGE SYSTEM SHOULD BE PIPED ALONG S.
 FLAGLER DRIVE TO THE OUTFALL TO THE SOUTH.
  
 3. PART OF SITE FALLS WITHIN A SPECIAL FLOOD HAZARD
 AREA (SFHA). A MINIMUM OF 2 FEET OF FREEBOARD ABOVE THE
 BASE FLOOD ELEVATION IS REQUIRED FOR STRUCTURES ON
 PARCELS WITHIN A SFHA.
  
 4. INDIVIDUAL LOTS SHALL NOT SURFACE DRAIN ONTO TO
 ADJOINING LOTS OR PROPERTIES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE OBTAINED FROM THE ENGINEERING SERVICES
 DEPARTMENT.
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT PRIOR TO
 STARTING CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 02-10-2020 Cont ID  
Sent By vnoel Date 02-10-2020 Time 07:47 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-02-10 10:08:031. NO SUBDIVISION PLAT PROVIDED. HOA WILL NEED TO BE
 CREATED.
 2. THERE IS CONCERN OF DRAINAGE INTO THE SURROUNDING
 NEIGHBORHOODS AS PROPERTY IS BEING FILLED 6' +/-.
 3. SWALES ARE NOT USUALLY PERMITTED IN A UTILITY
 EASEMENT. DRAINAGE EASEMENT WILL BE REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 02-12-2020 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-02-12 09:38:07PASSED.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)
  

Review Stop Z ZONING
Rev No 1 Status F Date 02-13-2020 Cont ID  
Sent By eschneid Date 02-13-2020 Time 08:46 Rev Time 2.00
Received By eschneid Date 02-13-2020 Time 08:46 Sent To  
Notes
2020-02-13 08:46:59CASE NO. PB 1847
 ESSEX COURT MAJOR SUBDIVISION
 5200 & 5300 ESSEX COURT
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 FEBRUARY 28, 2020, TO BE ELIGIBLE TO BE SCHEDULED FOR
 THE APRIL 21, 2020 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY APRIL 13, 2020),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) COPIES OF THE PROPOSED PLAT WERE NOT SUBMITTED WITH
 THE APPLICATION.
  
 2) THE PUBLIC UTILITY (FPL, FPU, AT&T AND COMCAST) AND
 CITY UTILITY SERVICE AVAILABILITY/NO OBJECTION LETTERS
 WERE NOT PROVIDED WITH THE APPLICATION.
  
 3) SECTION 94-44(E)(2)B OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR) REQUIRES THAT CONCRETE
 SIDEWALKS SHALL BE CONSTRUCTED ALONG BOTH SIDES OF ALL
 STREETS; EXCEPT, THAT IT SHALL BE WITHIN THE DISCRETION
 OF THE CITY COMMISSION, UPON SUFFICIENT CAUSE BEING
 SHOWN, TO WAIVE THE REQUIREMENT OF SIDEWALKS ON ONE
 SIDE OF THE STREET IN RESIDENTIAL AREAS. NO SIDEWALKS
 WERE PROVIDED ON THE PROPOSED PLANS.
  
 4) SECTION 94-44(E)(2)F OF THE ZLDR REQUIRES THAT
 STREET LIGHTS SHALL BE SO LOCATED AS TO ILLUMINATE THE
 AREA ADEQUATELY DURING HOURS OF DARKNESS. NO STREET
 LIGHTS WERE PROVIDED ON THE PROPOSED PLANS.
  
 5) SECTION 94-72(A)(1)D OF THE ZLDR REQUIRES THAT THE
 FLAGLER DRIVE FRONTAGE OF LOTS 4 AND 5 IS CONSIDERED
 THE FRONT PROPERTY LINE. THIS REQUIRES A 25 FOOT FRONT
 SETBACK ALONG FLAGLER DRIVE FOR THESE TWO LOTS, NOT 15
 FEET AS SHOWN. PLEASE NOTE THAT THESE ARE DOUBLE
 FRONTAGE LOTS SO A 25 FOOT SETBACK IS ALSO REQUIRED
 FROM THE TERMINUS OF THE PROPOSED NEW RIGHT-OF-WAY.
  
 6) AS DESIGNED, LOTS 3, 6 AND 8 ARE CORNER LOTS AND
 REQUIRE 12.5 FOOT SETBACKS FROM THE CORNER SIDE
 PROPERTY LINES IN ACCORDANCE WITH SECTION 94-72(A)(2)B
 OF THE ZLDR..
  
 7) THE REAR SETBACKS FOR LOTS 1, 2, 3, 6, 7 AND 8 ARE
 ALL INCORRECTLY LISTED AS 15 FEET. THE REAR SETBACKS
 FOR THESE LOTS IS 10 PERCENT OF THE LOT DEPTH IN
 ACCORDANCE WITH SECTION 94-72(A)(2)C OF THE ZLDR.
  
 8) THE MINIMUM SIDE SETBACK FOR ALL OF THE LOTS IS 5
 FEET (TOTAL OF 15 FEET) IN ACCORDANCE WITH SECTION
 94-72(A)(2)D OF THE ZLDR.
  
 9) PLEASE DO NOT INCLUDE THE SETBACK LINES ON THE PLAT.
 ADDITIONALLY, BE AWARE THAT THE CITY DOES NOT ENFORCE
 PRIVATE DEED RESTRICTIONS.
  
 10) THE STRIP OF LAND ON THE EAST SIDE OF FLAGLER DRIVE
 IS SHOWN AS ONE 4,319 SQUARE FOOT PARCEL. DEFINE WHAT
 IS OCCURRING WITH THIS PARCEL.
  
 11) SECTION 94-312(4)B OF THE ZLDR REQUIRES THAT ALL
 LOTS IN A PROPOSED RESIDENTIAL SUBDIVISION HAVE
 FRONTAGE ON AND ACCESS FROM AN EXISTING STREET MEETING
 THE REQUIREMENTS OF CHAPTER 94 OF THE ZLDR AND SECTION
 94-342(A) OF THE ZLDR REQUIRES THAT THE WIDTH OF
 STREETS IN NEW SUBDIVISIONS SHALL BE NOT LESS THAN THE
 MINIMUM WIDTHS ESTABLISHED IN ARTICLE XI OF THE ZLDR.
  
 A. SECTION 94-342(B) OF THE ZLDR PROVIDES AS A MINIMUM
 REQUIREMENT FOR STREETS, AVENUES AND SIDEWALKS, THE
 PLAT SHALL DEDICATE A WIDTH OF AT LEAST 50 FEET, AT
 LEAST FIVE FEET THEREOF ON EACH SIDE FOR SIDEWALKS, AND
 AT LEAST 40 FEET INTERVENING BETWEEN SIDEWALKS;
 PROVIDED, THAT IN THE EVENT THAT THE CITY COMMISSION,
 UPON RECOMMENDATION BY THE CITY PLANNING BOARD, FINDS
 THAT TRAFFIC CONDITIONS AND TRANSPORTATION REQUIREMENTS
 SO DEMAND, A GREATER WIDTH MAY BE REQUIRED; AND EXCEPT
 THAT, DEAD-END STREETS NOT EXCEEDING 1,000 FEET IN
 LENGTH AND TERMINATION IN A TURNAROUND WITH A MINIMUM
 RADIUS OF 50 FEET MAY HAVE A MINIMUM WIDTH OF 40 FEET.
 THE PROPOSED SUBDIVISION PLAN DOES NOT COMPLY WITH
 THESE REQUIREMENTS.
  
 B. SECTION 94-342(D) OF THE ZLDR PERMITS DEAD END
 STREETS IF THE TRACT OF LAND IS OF SUCH SIZE OR
 LOCATION TO PREVENT A LOT ARRANGEMENT DIRECTLY RELATED
 TO NORMAL STREET DESIGN. THE DEAD END STREET SHALL
 TERMINATE IN AN OPEN SPACE HAVING A MINIMUM 50 FOOT
 RADIUS. THE T TURNAROUND THAT IS PROPOSED DOES NOT HAVE
 A 50 FOOT RADIUS AND THUS DOES NOT COMPLY WITH THE
 ZLDR.
  
 12) THE SOUTH DIMENSION LINE FOR PROPOSED LOT 5 IS
 INCORRECT.
  
 13) SECTION 94-342(G) OF THE ZLDR REQUIRES THAT THE
 CHARACTER OF DEVELOPMENT IS REVIEWED SO AS TO NOT
 DEPRECIATE THE CHARACTER OF ADJOINING PROPERTY. STAFF
 HAS PERFORMED A PARCEL ANALYSIS OF THE ESSEX LANE PLAT
 PARCELS AS WELL AS THE PARCELS TO THE IMMEDIATE NORTH
 OF THE SITE ALONG PLYMOUTH ROAD. THE PROPOSED LOTS,
 WHILE MEETING THE MINIMUM SIZE REQUIREMENTS OF THE SF7
 ARE NOT OF A SIZE THAT IS IN CHARACTER WITH THE
 ADJACENT PARCELS OR CONTAINED WITHIN THE EXISTING ESSEX
 LANE PLAT. EIGHT PROPOSED LOTS WILL BECOME EVEN SMALLER
 IN ORDER TO MEET THE MINIMUM RIGHT-OF-WAY STANDARDS
 LISTED IN THE PREVIOUS COMMENTS, AND THUS LESS IN
 CHARACTER.
  