Plan Review Details - Project Z19120013
| Plan Review Stops For Project Z19120013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
01-07-2020 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
01-07-2020 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
01-07-2020 |
Time |
18:45 |
Sent To |
|
|
| Notes |
| 2020-01-07 18:52:03 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. PARTIAL DEMOLITION OF THE EXISTING BUILDING. AN | | | ASBESTOS SURVEY SHALL BE PERFORMED AND AN ASBESTOS | | | ABATEMENT REPORT SUBMITTED TO THE HEALTH DEPARTMENT | | | PALM BEACH COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) | | | 837-5963, OR BY EMAIL: [email protected] | | | | | | 3. NUMBER OF ACCESSIBLE PARKING SPACES. THE PARKING | | | COMPUTATIONS TABLE ON SITE PLAN SHEET, SP-1, STATES | | | THAT 2 ACCESSIBLE PARKING SPACES ARE PROVIDED BUT THE | | | SITE PLAN ONLY SHOWS 1 ACCESSIBLE PARKING SPACE. PLEASE | | | CORRECT THE PARKING COMPUTATIONS TABLE WHEN SUBMITTING | | | FOR BUILDING PERMIT. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. OIL AND GAS INTERCEPTOR. AN OIL AND GAS INTERCEPTOR | | | WILL BE REQUIRED. PLEASE CONTACT CLIFFORD SANDERS, | | | UTILITIES O&M SUPERINTENDENT, PUBLIC UTILITIES | | | DEPARTMENT, AT (561) 835-7406, OR BY EMAIL: | | | [email protected] | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 7. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER | | | AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY, | | | INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE | | | CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF | | | NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION | | | THAT MAY AFFECT THE USE OF THEIR PROPERTY. | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
P |
Date |
06-30-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
06-30-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
06-30-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-06-30 08:33:57 | PASSED WITH PROVISOS: | | | | | | 1. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | 2. FOR FORMAL ENGINEERING SUBMITTAL, LABEL ALL CITY | | | OWNED UTILITIES PIPE SIZES AND MATERIALS IN RIGHT OF | | | WAY. | | | 3. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE ALL | | | RELEVANT CURRENT CITY OF WPB STANDARD DETAILS; ADD | | | PAVEMENT RESTORATION DETAIL GC-8 NOTE TO UTILITY | | | SHEETS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | DIRECT: (561) 494-1098 [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
02-25-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
02-25-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
02-25-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-25 07:52:23 | 1. RESPONSE LETTER ADVISES CONFLICT BOX HAS BEEN ADDED | | | TO PLANS. UNABLE TO LOCATE ON SUBMITTED UTILITY SHEET. | | | IS THE BOX A NOTE OR STRUCTURE? | | | 2. ADD FIRE FLOWS IF DETERMINED NEEDED BY DISCUSSION | | | WITH FIRE DEPT. | | | 3. PLEASE ADD PAVEMENT RESTORATION NOTE PER CITY OF WPB | | | STANDARD DETAIL GC-8. | | | 4. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29). | | | 5. PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR | | | PROPOSED SANITARY LATERALS. | | | 6. CHECK TO SEE IF FDEP FORMS FOR PROPOSED SANITARY | | | SEWER ARE REQUIRED. | | | 7. FOR FORMAL ENGINEERING SUBMITTAL, PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | 8. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE DEDICATED | | | UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY PERSONNEL TO | | | PROPOSED UTILITY WATER METERS. | | | 9. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE PROVIDE | | | ENLARGED VIEW ON PLANS OF PROPOSED LOCATION OF WATER | | | METER AND BACKFLOW PREVENTION. | | | 10. FOR FORMAL ENGINEERING SUBMITTAL, PLEASE CALLOUT | | | DOMESTIC BACKFLOW PREVENTER AS RPPA AND FIRE BACKFLOW | | | PREVENTER AS DCDA. SPECIFY LEAD FREE DESIGN ON ALL | | | BACKFLOWS. | | | | | | THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD | | | CUSTOMER SERVICE SUPERVISOR, WPB PUBLIC UTILITIES, | | | PLEASE CONTACT 561-494-2262 OR [email protected]: | | | | | | -THE BACKFLOW ASSEMBLY FOR DOMESTIC SERVICE ON SOUTHERN | | | SIDE WOULD NEED BE ADJUSTED SLIGHTLY NORTH OUT OF THE | | | 10 FT. UE WHEN METER IS RELOCATED. | | | - FOR THE WATER SERVICE AT NW AREA OF PLAN THAT IS | | | BEING REMOVED AND CAPPED AT MAIN ADD NOTE SHOWING | | | STREET BEING RESTORED TO CITY WPB STANDARDS AFTER | | | EXCAVATION. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | DIRECT: (561) 494-1098 [email protected] | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
01-07-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
01-07-2020 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
01-07-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-07 07:25:32 | SHOW ALL UTILITY CONNECTIONS. | | | LABEL METERS, SERVICES, MATERIALS, SIZE, ETC. PROVIDE | | | WATER AND SEWER DEMANDS INCLUDING FIRE FLOWS. | | | ADD NOTE: EXISTING SERVICES NOT PROPOSED FOR USE TO BE | | | CUT AND CAPPED AT MAIN. | | | SHOW ALL DRY UTILITIES IN ROW. | | | REMOVE OR RELOCATE ONSITE DRAINAGE FROM EASEMENT. | | | PROVIDE CCTV FOR SANITARY ALONG PROJECT FRONTAGES. | | | FRANCHISE UTILITY IN CONFLICT WITH PROPOSED DRAINAGE. | | | PROVIDE PROFILES OF ANY PROPOSED CROSSINGS/CONFLICTS. | | | | | | FOLLOWING COMMENTS PER MARK HURLEY, PUBLIC UTILITIES | | | CUSTOMER SERVICE SUPERVISOR, [email protected], | | | 561-822-2262 | | | | | | -PLAN SHOWS WATER LINE GOING TO CLOCK MONUMENT. IS THE | | | WATER JUST GOING TO THE EXISTING HOSE BIBS OR DOES THE | | | CLOCK MONUMENT USE WATER? | | | | | | -THE NE EXISTING WATER SERVICE IS CURRENTLY AN | | | IRRIGATION METER. WILL IT CONTINUE TO BE IRRIGATION? | | | PLAN SHOWS WATER LINE GOING TO BUILDING ? IS IT ALSO | | | FEEDING SOMETHING IN THE BUILDING? | | | | | | -DOMESTIC/GENERAL/IRRIGATION WATER SERVICES MAY NOT | | | FEED FIRE SPRINKLER SERVICES ? WOULD NEED DEDICATED | | | DETECTOR FIRELINE. | | | | | | -THERE IS A LIGHT POLE IN SIDEWALK ADJACENT NE METER. | | | IF LIGHT POLE IS TO REMAIN IN SIDEWALK, THEN SIDEWALK | | | SHOULD BE SIZE TO ALLOW FOR PEDESTRIAN TRAFFIC. IF | | | LIGHTPOLE IS RELOCATED OR ELIMINATED OUT OF SIDEWALK, | | | THEN WOULD WANT METER BOX RELOCATED OUT OF SIDEWALK AND | | | INTO GRASS U.E. | | | | | | -NEED LABELS SHOWING METER SIZE. BACKFLOW ASSEMBLIES | | | NEED TO BE DRAWN AND LABELED (THERE ARE AT LEAST 3 | | | THERE CURRENTLY). NORTHERN WATER SERVICES ARE ALSO NOT | | | DRAWN AND LABELED. | | | | | | -SOUTHERN WATER LINE SIZE AND MATERIAL IS NOT SHOWN ON | | | LABEL. | | | | | | -6 FT. CONCRETE SIDEWALK LABEL LOOKS POINTED | | | INCORRECTLY TO CURB. | | | | | | -RECOMMEND PARALLEL BACKFLOW ASSEMBLIES ON DOMESTIC | | | WATER SERVICE TO MINIMIZE OUTAGES DUE TO MAINTENANCE. | | | | | | -METER BOX ON SOUTHERN SHOULD BE RELOCATED NORTH OUT OF | | | SIDEWALK TRAFFIC INTO SMALL GRASS U.E. | | | | | | -FLOW TABLE ONLY LISTS WATER CLOSETS. DOES THAT TAKE | | | INTO ACCOUNT THINGS LIKE HOSE BIBS, SINKS, AND SODA | | | MACHINES? | | | | | | -IS THE EAST-WEST UTILITY EASEMENT RUNNING THROUGH | | | PROPERTY GOING TO REMAIN? PLAN SHOWS THAT A SIDEWALK IS | | | GOING TO BE BUILT OVER IT, BUT THAT WOULD CONFLICT WITH | | | THE USE OF THE UTILITY EASEMENT. | | | | | | -PLAN SHOWS THAT THE NW METER BOX/SERVICE TO BE | | | RELOCATED. PLAN SHOULD SHOW WHERE IT IS GOING OR | | | INSTEAD SAY IT IS BEING CUT BACK TO THE WATER MAIN. | | | | | | -SOUTHERN AND NE BACKFLOW ASSEMBLIES ARE NOT LEAD-FREE | | | COMPLIANT ? RECOMMEND REPLACEMENT OF BOTH. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 EMAIL: | | | [email protected] WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
01-03-2020 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
01-03-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
01-03-2020 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2020-01-03 14:51:53 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. FIRE HYDRANT COULD NOT BE IDENTIFIED ON THE | | | SUBMITTAL. | | | | | | ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9.THERE IS AN INDICATION OF A BASEMENT, PER NFPA 1, | | | 13.3.2.2 BASEMENTS EXCEEDING 2500 SQ FT IN NEW | | | BUILDINGS SHALL BE PROTECTED THROUGHOUT BY AN APPROVED | | | AUTOMATIC FIRE SPRINKLER SYSTEM. | | | | | | 9A) AS APPLICABLE TO THE ABOVE, THE LOCATION OF THE | | | DDCC FIRE LINE LOCATION(S) ARE NOT INDICATED; HOWEVER, | | | THEY SHALL MEET THE REQUIREMENTS OF NFPA 24 AND SHALL | | | BE COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE | | | CITY'S ENGINEERS OFFICE, THE LANDSCAPE PLANNER, AND THE | | | CITY'S PLANNING AND ZONING OFFICE. | | | | | | AS APPLICABLE TO THE ABOVE, PROVIDE FOR A FIRE | | | SPRINKLER AND/OR FIRE ALARM PER THE APPLICABLE | | | OCCUPANCY CODE. FOR ANY LIFE SAFETY ENGINEERED SYSTEM, | | | I.E FIRE SPRINKLER AND FIRE ALARM, ENSURE THEY COMPLY | | | WITH THE REQUIREMENTS OF FS 61G AND SUBMITTED WITH THE | | | MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
06-29-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-29-2020 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-29-2020 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2020-06-29 16:23:32 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 301 SOUTHERN 7 ELEVEN INFORMAL SITE PLAN | | | REVIEW Z19120013 | | | JUNE 29, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION PLAN SHEET PLP-3: | | | ? SATISFIED. TREES #8 AND #9A ARE BLACK OLIVE TREES. | | | ? SATISFIED. TREE #12 IS A GUMBO LIMBO. | | | ? SATISFIED. #9B AND #11 ARE CATEGORY 3 AND SHOULD BE | | | 100 SQ FT CANOPY REPLACEMENT VALUE. | | | ? SATISFIED. TOTAL MITIGATION DUE SHOULD BE 691 SQ FT | | | ? SATISFIED. THE CAD LAYER SHOWING THE TREE LOCATIONS | | | WAS NOT PRINTED WITH THE SUBMITTED COPY OF SHEET PLP-3. | | | | | | 2. SATISFIED. ADD A NOTE THAT ALL INVASIVE EXOTIC | | | PROHIBITED PLANTS WILL BE REMOVED PRIOR TO A | | | CERTIFICATE OF OCCUPANCY IS ISSUED. | | | | | | 3. SATISFIED. CORRECT THE REQUIRED SHADE TREES TO 16. | | | ONE PER 1500 SQ FT OR PORTION THEREOF. | | | | | | 4. SATISFIED. IF BLACK OLIVES ARE TO STAY IS THE | | | MAHOGANY THE BEST CHOICE FOR THE ADDITIONAL 2 TREES? | | | | | | 5. SATISFIED. CLARIFY IF OVERHEAD ELECTRIC LINES WILL | | | BE UNDERGROUNDED TO AVOID CONFLICTS WITH TREES. | | | | | | 6. SATISFIED. INDICATE IF THE CONCRETE PLANTER | | | STRUCTURE ALONG OLIVE AVE WILL BE PRESERVED. | | | | | | 7. SATISFIED. INDICATE THE LANDSCAPE BUFFER LOCATIONS | | | ON THE SITE PLAN AND LANDSCAPE PLAN FOR ALL SIDES OF | | | THE PROJECT. | | | | | | 8. SATISFIED. SHOW ALL CALCULATIONS FOR THE REQUIRED | | | TREES FOR BUFFER SEGMENTS ON THE LANDSCAPE DATA CHART | | | INCLUDING LINEAR FOOTAGE OF ALL PROPERTY LINE SEGMENTS | | | AND REMOVE NOTES FROM THE LANDSCAPE PLAN. | | | CORRECT THE REQUIRED TREES TO 9 FOR THE NORTH BUFFER D. | | | | | | 9. SATISFIED. PROVIDE AN EXHIBIT SHOWING THE PARKING | | | AREA SURFACE CALCULATIONS, PARKING SPACE AREAS AND | | | LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE WITH | | | SECTIONS 94-443 (C)(3) AND (4). | | | | | | 10. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 11. SATISFIED. THE PLAN SHOWS TWO WATER METERS AND | | | LINES TO THE BUILDING. SHOW SEWER LINE ON THE LANDSCAPE | | | PLAN. ADJUST LOCATIONS OF TREES OR UTILITY LINES TO | | | RESOLVE CONFLICTS WITH LANDSCAPING. | | | 12. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS | | | REQUIRED TO PROTECT UTILITY LINES. | | | 13. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL | | | ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C | | | UNITS, AND FPL TRANSFORMERS. | | | | | | 14. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
03-02-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
03-02-2020 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
03-02-2020 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2020-03-02 14:16:19 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 301 SOUTHERN 7 ELEVEN INFORMAL SITE PLAN | | | REVIEW Z19120013 | | | MARCH 2, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION PLAN SHEET PLP-3: | | | ? SATISFIED. TREES #8 AND #9A ARE BLACK OLIVE TREES. | | | ? SATISFIED. TREE #12 IS A GUMBO LIMBO. | | | ? SATISFIED. #9B AND #11 ARE CATEGORY 3 AND SHOULD BE | | | 100 SQ FT CANOPY REPLACEMENT VALUE. | | | ? SATISFIED. TOTAL MITIGATION DUE SHOULD BE 691 SQ FT | | | ? THE CAD LAYER SHOWING THE TREE LOCATIONS WAS NOT | | | PRINTED WITH THE SUBMITTED COPY OF SHEET PLP-3. | | | | | | 2. SATISFIED. ADD A NOTE THAT ALL INVASIVE EXOTIC | | | PROHIBITED PLANTS WILL BE REMOVED PRIOR TO A | | | CERTIFICATE OF OCCUPANCY IS ISSUED. | | | | | | 3. SATISFIED. CORRECT THE REQUIRED SHADE TREES TO 16. | | | ONE PER 1500 SQ FT OR PORTION THEREOF. | | | | | | 4. SATISFIED. IF BLACK OLIVES ARE TO STAY IS THE | | | MAHOGANY THE BEST CHOICE FOR THE ADDITIONAL 2 TREES? | | | | | | 5. SATISFIED. CLARIFY IF OVERHEAD ELECTRIC LINES WILL | | | BE UNDERGROUNDED TO AVOID CONFLICTS WITH TREES. | | | | | | 6. SATISFIED. INDICATE IF THE CONCRETE PLANTER | | | STRUCTURE ALONG OLIVE AVE WILL BE PRESERVED. | | | | | | 7. SATISFIED. INDICATE THE LANDSCAPE BUFFER LOCATIONS | | | ON THE SITE PLAN AND LANDSCAPE PLAN FOR ALL SIDES OF | | | THE PROJECT. | | | | | | 8. PARTIALLY SATISFIED. SHOW ALL CALCULATIONS FOR THE | | | REQUIRED TREES FOR BUFFER SEGMENTS ON THE LANDSCAPE | | | DATA CHART INCLUDING LINEAR FOOTAGE OF ALL PROPERTY | | | LINE SEGMENTS AND REMOVE NOTES FROM THE LANDSCAPE PLAN. | | | CORRECT THE REQUIRED TREES TO 9 FOR THE NORTH BUFFER D. | | | | | | 9. SATISFIED. PROVIDE AN EXHIBIT SHOWING THE PARKING | | | AREA SURFACE CALCULATIONS, PARKING SPACE AREAS AND | | | LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE WITH | | | SECTIONS 94-443 (C)(3) AND (4). | | | | | | 10. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 11. SATISFIED. THE PLAN SHOWS TWO WATER METERS AND | | | LINES TO THE BUILDING. SHOW SEWER LINE ON THE LANDSCAPE | | | PLAN. ADJUST LOCATIONS OF TREES OR UTILITY LINES TO | | | RESOLVE CONFLICTS WITH LANDSCAPING. | | | 12. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS | | | REQUIRED TO PROTECT UTILITY LINES. | | | 13. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL | | | ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C | | | UNITS, AND FPL TRANSFORMERS. | | | | | | 14. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
01-07-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
01-07-2020 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
01-07-2020 |
Time |
16:33 |
Sent To |
|
|
| Notes |
| 2020-01-07 16:34:14 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 301 SOUTHERN 7 ELEVEN INFORMAL SITE PLAN | | | REVIEW Z19120013 | | | JANUARY 7, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE THE FOLLOWING CORRECTIONS TO THE TREE | | | DISPOSITION PLAN SHEET PLP-3: | | | ? TREES #8 AND #9A ARE BLACK OLIVE TREES. | | | ? TREE #12 IS A GUMBO LIMBO. | | | ? #9B AND #11 ARE CATEGORY 3 AND SHOULD BE 100 SQ FT | | | CANOPY REPLACEMENT VALUE. | | | ? TOTAL MITIGATION DUE SHOULD BE 691 SQ FT | | | | | | 2. ADD A NOTE THAT ALL INVASIVE EXOTIC PROHIBITED | | | PLANTS WILL BE REMOVED PRIOR TO A CERTIFICATE OF | | | OCCUPANCY IS ISSUED. | | | | | | 3. CORRECT THE REQUIRED SHADE TREES TO 16. ONE PER 1500 | | | SQ FT OR PORTION THEREOF. | | | | | | 4. IF BLACK OLIVES ARE TO STAY IS THE MAHOGANY THE BEST | | | CHOICE FOR THE ADDITIONAL 2 TREES? | | | | | | 5. CLARIFY IF OVERHEAD ELECTRIC LINES WILL BE | | | UNDERGROUNDED TO AVOID CONFLICTS WITH TREES. | | | | | | 6. INDICATE IF THE CONCRETE PLANTER STRUCTURE ALONG | | | OLIVE AVE WILL BE PRESERVED. | | | | | | 7. INDICATE THE LANDSCAPE BUFFER LOCATIONS ON THE SITE | | | PLAN AND LANDSCAPE PLAN FOR ALL SIDES OF THE PROJECT. | | | | | | 8. SHOW ALL CALCULATIONS FOR THE REQUIRED TREES FOR | | | BUFFER SEGMENTS ON THE LANDSCAPE DATA CHART INCLUDING | | | LINEAR FOOTAGE OF ALL PROPERTY LINE SEGMENTS AND REMOVE | | | NOTES FROM THE LANDSCAPE PLAN. | | | | | | 9. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE | | | CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS | | | PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443 | | | (C)(3) AND (4). | | | | | | 10. PROVIDE LOCATIONS OF LIGHTING ON THE LANDSCAPE PLAN | | | TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 11. THE PLAN SHOWS TWO WATER METERS AND LINES TO THE | | | BUILDING. SHOW SEWER LINE ON THE LANDSCAPE PLAN. ADJUST | | | LOCATIONS OF TREES OR UTILITY LINES TO RESOLVE | | | CONFLICTS WITH LANDSCAPING. | | | 12. SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO | | | PROTECT UTILITY LINES. | | | 13. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE | | | GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C UNITS, | | | AND FPL TRANSFORMERS. | | | | | | 14. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
02-21-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
02-21-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
02-21-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-21 07:46:19 | NO FURTHER COMMENTS FROM DEPT. OF PUBLIC WORKS. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
01-03-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-03-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
01-03-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-03 15:19:41 | 1- FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE | | | ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY | | | OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE | | | ENCLOSURE STANDARD, CG-8. | | | 2- PLEAASE PROVIDE AUTO TURN FOR THE SANITATION | | | SERVICE, FRONT LOADER TRUCK | | | - TRUCK LENGTH: 35 FT | | | - TRUCK WIDTH: 11 FT | | | - TURNING RADIUS: | | | - SAE TURNING RADIUS: 32.5 FT | | | - CURB-TO-CURB DIAMETER: 74 FT | | | - WALL-TO-WALL DIAMETER: 86.3 FT | | | | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
02-28-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
02-28-2020 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
02-28-2020 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2020-02-28 15:46:42 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | FEBRUARY 11, 2020 REVIEW SUBMITTAL PACKAGE. | | | | | | 1. NO GRADING INFORMATION WAS PROVIDED, JUST FLOW | | | ARROWS. | | | | | | 2. PROVIDE A CONDITION ASSESSMENT OF THE MANHOLE TO BE | | | MODIFIED ON CONNISTON ROAD AND CONFIRM IT IS LARGE | | | ENOUGH TO ACCEPT A PIPE CONNECTION FROM THE SOUTH WITH | | | THE THREE OTHER EXISTING PIPE CONNECTIONS. | | | | | | 3. CONSIDER CONNECTING THE ONSITE DRAIINAGE SYSTEM TO | | | THE EXISTING CATCH BASIN ON S. OLIVE AVE INSTEAD OF TO | | | THE MANHOLE ON CONNISTON ROAD. THE S.OLIVE AVE INLET IS | | | DOWNSTREAM OF THE CONNISTON RD MANHOLE. | | | | | | 4. SHOW MIILL AND RESURFACE LIMITS FOR TRENCH CUR ON | | | CONNISTON ROAD. | | | | | | 5. THE CITY'S VERTICAL DATUM IS NGVD1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD1988 PROVIDED THE CONVERSION | | | BETWEEN NAVD1988 AND NGVD1929 IS LISTED ON THE PLAN. | | | PROVIDE THE COVERSION EQUATION ON THE SURVEY. | | | | | | 6. LIST VERTICAL DATUM ON THE ENGINEERING PLANS AND | | | PROVIDE THE CONVERSION EQUATION TO NGVD1929. | | | | | | 7. SHOW/DIMENSION THE PARKING STALL OVERHANG, IF | | | APPLICABLE, ON THE CROSS SECTIONS ON THE ENGINEERING | | | PLANS. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
01-08-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
01-08-2020 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
01-08-2020 |
Time |
11:27 |
Sent To |
|
|
| Notes |
| 2020-01-08 11:27:45 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTPS:/ | | | /WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PE | | | RMITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE PROPOSED OUTFALL STORM PIPE TO CONNISTON ROAD IS | | | SHOWN GOING NEXT TO AN EXISTING MAHOGANY TREE. WHAT | | | IMPACT WILL CONSTRUCTION OF THIS PIPE HAVE ON THE TREE | | | AND CAN THE IMPACT BE MITIGATED? | | | | | | 2. NO GRADING INFORMATION WAS PROVIDED. | | | | | | 3. MINIMIZE THE AMOUNT OF IMPERVIOUS AREA RUNOFF THAT | | | WILL SHEET FLOW TOWARD THE RIGHT OF WAY AND ACROSS THE | | | SIDEWALK. | | | | | | 4. PROVIDE CROSS SECTIONS FROM THE PROPERTY LINE TO THE | | | BUILDING AND TO THE PARKING AREAS. PERIMETER BERMS | | | SHOULD BE PROVIDED TO CONTAIN THE STORMWATER RUNOFF. | | | | | | 5. PROVIDE A CONDITION ASSESSMENT OF THE CATCH BASIN TO | | | BE MODIFIED ON CONNISTON ROAD. | | | | | | 6. SOUTHERN BLVD. IS MAINTAINED BY FDOT. A PERMIT WILL | | | BE NEEDED FROM FDOT FOR ANY WORK WITHIN THE SOUTHERN | | | BLVD RIGHT OF WAY. | | | | | | 7. STORMWATER MANAGEMENT SYSTEM TO BE DESIGNED TO MEET | | | SFWMD CRITERIA FOR WATER QUALITY TREATMENT AND PEAK | | | FLOW ATTENUATION. | | | | | | 8. CONSIDER LOW IMPACT DEVELOPMENT (LID) BEST | | | MANAGEMENT PRACTICES BESIDES EXFILTRATION TRENCHES FOR | | | STORMWATER TREATMENT. CAN DEPRESSED STORMWATER | | | DETENTION AREAS BE INCORPORATED IN THE LANDSCAPE GREEN | | | SPACES AROUND THE BUILDING AND ALONG CONNISTON ROAD? | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT PRIOR TO | | | STARTING CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
02-27-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
02-27-2020 |
Time |
13:27 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-27 13:27:41 | PASSED WITH CONDITION OF REPLAT AND ANY REQUIRED | | | EASEMENTS PRIOR TO C.O. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
01-06-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
01-06-2020 |
Time |
10:40 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-06 10:40:45 | 1. REPLAT WILL BE REQUIRED. | | | 2. FDOT MAINTENANCE MAP IN RPB 8/198 NEEDS TO BE SHOWN | | | ON SURVEY. | | | 3. CORRECT RPB 8/189 SHOWN ON ENG. PLAN. | | | 4. PROVIDE COPY OF ORB 247/17. | | | 5. ACCESS EASEMENT WILL BE NEEDED FOR SIDEWALK AT SE | | | CORNER. | | | 6, PROPERTY CORNERS FALLING UNDER ASPHALT/CONCRETE DOES | | | NOT PROHIBIT THE SETTING OF THE REQUIRED CORNER | | | MONUMENTATION. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
06-26-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-26-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-06-26 11:57:54 | NO FURTHER COMMENTS. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
02-18-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-18 16:27:52 | PASSED WITH THE FOLLOWING CONDITIONS: | | | 1. PROVIDE BUFFERED AND PROTECTED BIKE LANES ON OLIVE | | | AVENUE, AND WIDEN SIDEWALK TO 10 FEET ON SOUTHERN | | | BOULEVARD ALONG SITE FRONTAGE. | | | 2. PROVIDE 40-FOOT CORNER CLIP RIGHT-OF-WAY DEDICATION | | | OR EASEMENT PER COUNTY?S TPS LETTER REQUIREMENT, OR | | | COORDINATE WITH COUNTY TO REDUCE THIS REQUIREMENT TO 25 | | | FEET CORNER CLIP. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
01-08-2020 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-08 16:31:02 | TRAFFIC STATEMENT COMMENTS: | | | 1. PROVIDE THE COUNTY TPS LETTER. | | | 2. PROVIDE INTERSECTION ANALYSIS AT SOUTHERN BOULEVARD | | | WITH DIXIE, OLIVE AND WASHINGTON. | | | SITE PLAN COMMENTS: | | | 3. VERIFY SUFFICIENT SIGHT-DISTANCE IS PROVIDED ON | | | SOUTHERN BOULEVARD PER FDOT STANDARDS. | | | 4. PROVIDE CYCLE TRACK ALONG SITE FRONTAGE ON SOUTHERN | | | BOULEVARD AND OLIVE AVENUE. | | | 5. PROVIDE ON-STREET PARKING ON CONNISTON ROAD WHICH | | | COULD BE COUNTED TOWARDS THE PARKING REQUIREMENT AND | | | OFF-STREET PARKING ON-SITE COULD BE REDUCED. | | | 6. PROVIDE PEDESTRIAN CONNECTIONS FROM CONNISTON ROAD. | | | 7. VERIFY THE DUMPSTER AND DELIVERY TRUCK CIRCULATION | | | AND PROVIDE AUTOTURN PATHS. | | | 8. TRAFFIC DOES NOT SUPPORT VEHICULAR ACCESS ON | | | CONNISTON ROAD AS THIS WILL INDUCE ADDITIONAL VEHICULAR | | | TRAFFIC ON RESIDENTIAL STREETS AND ENCOURAGE | | | CUT-THROUGH TRAFFIC. | | | 9. CLARIFY THE PURPOSE OF BENCHES ON CONNISTON ROAD. | | | 10. PROVIDE 25-FOOT CONCRETE-PAVED CORNER CLIP AT | | | SOUTHERN/OLIVE FOR PEDESTRIAN AND PROVIDE SIDEWALK AND | | | UTILITY EASEMENT. | | | 11. NARROW THE DRIVEWAY WIDTH AS THE WIDTH DOES NOT | | | APPEAR TO BE NEEDED FOR FUEL DELIVERY. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
07-01-2020 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
07-01-2020 |
Time |
12:19 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
07-01-2020 |
Time |
12:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
02-24-2020 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
02-24-2020 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
02-24-2020 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
01-07-2020 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
01-07-2020 |
Time |
16:30 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
01-07-2020 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2020-01-07 16:30:53 | - UNITY OF TITLE FOR THREE PARCELS REQUIRED | | | - ADDRESS INCONSISTENCY BETWEEN RENDERINGS AND | | | ELEVATIONS | | | - PLEASE PROVIDE A SIGNAGE PLAN (HIGH VS. MONUMENT) AND | | | RELOCATED HISTORIC SIGN "B" | | | - STAFF DOES NOT SUPPORT WAIVER FOR VEHICUALR ACCESS | | | 94-273(D), PLEASE REMOVE VEHICULAR ACCESS FROM | | | CONNISTON | | | - CONFIRM UTILITIES SHALL BE UNDERGROUNDED ON SITE | | | - PROVIDE ADDITIONAL BIKE RACKS | | | - RETAIN AND INCORPORATE KEYHOLE CONCRETE PLANTERS | | | ALONG OLIVE AVE. | | | - PLEASE PROVIDE INTERIOR FLOORPLAN AND CONFIRMATION | | | WINDOWS SHALL NOT BE BLOCKED WITH MERCHANDISE FACING | | | INWARD | | | - PROJECT SUBJECT TO APPROVAL OF CLASS B SPECIAL USE | | | AND COA (APPLICANT HAS APPLIED) | | | | | | QUESTIONS, PLEASE CONTACT: FRIEDERIKE MITTNER, CITY | | | HISTORIC PRESERVATION PLANNER AT (561) 822-1457 OR | | | [email protected] |
|
|
| |
Print |
|