Plan Review Details - Project Z19110020
Plan Review Stops For Project Z19110020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 10-22-2020 Cont ID  
Sent By rbrown Date 10-22-2020 Time 11:46 Rev Time 0.00
Received By rbrown Date 10-22-2020 Time 11:46 Sent To  
Notes
2020-10-22 11:48:12WHEN SUBMITTING FOR BUILDING PERMIT PLEASE ADDESS THE
 ADVISORY COMMENTS LISTED IN THE PREVIOUS REVIEW.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-10-2019 Cont ID  
Sent By fmittner Date 12-03-2019 Time 13:27 Rev Time 0.00
Received By rbrown Date 12-10-2019 Time 20:14 Sent To  
Notes
2019-12-10 20:22:48DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. VAN ACCESSIBLE PARKING SPACES. THE PLANS SHALL BE
 MARKED TO SHOW TWO VAN ACCESSIBLE PARKING SPACES WHEN
 SUBMITTED FOR PERMIT. PER SECTION 208.2.4 OF FLORIDA
 ACCESSIBILITY CODE, ONE IN EVERY SIX REQUIRED
 ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 7. GREASE INTERCEPTOR. IF ANY OF THE RETAIL SPACES WILL
 BE USED FOR RESTAURANTS A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 11. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 12. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 5 Status P Date 03-26-2021 Cont ID  
Sent By rrossano Date 03-26-2021 Time   Rev Time 0.00
Received By rrossano Date 03-26-2021 Time   Sent To  
Notes
2021-03-26 11:55:05ADDITIONAL PROVISO:
 -IRRIGATION PLAN AND DETAILS CALL OUT PVB BACKFLOW
 ASSEMBLY ADJACENT WATER METER. THAT DOES NOT MATCH
 UTILITY PLAN AND NEEDS TO BE RP TYPE INSTEAD.
 INSTALLATION OF BACKFLOW ASSEMBLY AND PIPING AROUND IT
 MUST COMPLY WITH PUBLIC UTILITIES WATER SERVICE
 STANDARD DETAIL FOR SMALL BACKFLOW ASSEMBLIES (WS-6)
 AND BE LEAD-FREE COMPLIANT AND USC-APPROVED.
  
 COMMENTS PER MARK HURLEY
 FIELD CUSTOMER SERVICE SUPERVISOR
 CITY OF WEST PALM BEACH PUBLIC UTILITIES
 561-822-2262
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 4 Status P Date 01-06-2021 Cont ID  
Sent By rrossano Date 01-06-2021 Time   Rev Time 0.00
Received By rrossano Date 01-06-2021 Time   Sent To  
Notes
2021-01-06 08:38:47PASSED WITH PROVISOS:
  
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC.
 SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected],
 561-822-2262:
 -FOR FORMAL ENGINEERING SUBMITTAL:
 1) ADD GATE VALVES AT THE INTERSECTIONS FOR THE
 REPLACEMENT 8INCH DIP WATER MAIN ON 2ND ST.
 2) VERIFY EXISTING WATER MAIN ADJACENT EAST SIDE OF
 PROPERTY ? (IT IS NOT SHOWING UP ON OUR GIS)
 3) LABEL WATER MAINS ON ROSEMARY AVE WITH PIPE MATERIAL
 TYPE AND SIZE.
 -THE INCLUDED WATER SERVICE STANDARD DETAILS STILL HAVE
 SOME WITH OUTDATED REVISION, WRONG TYPE USED, AND SOME
 ARE MISSING SUCH SMALL WATER SERVICE AND SMALL BACKFLOW
 ASSEMBLY. PLEASE ADD AND REVISE THEM AT FORMAL
 ENGINEERING SUBMITTAL.
 -IN ADDITION TO THE BACKFLOW COVENANT RECORDING
 REQUIREMENT, FIRELINE BACKFLOW ASSEMBLY USED INSIDE
 BUILDING MUST BE USC APPROVED FOR THE PROPOSED
 ORIENTATION.
 -CONFIRM THAT THE FDC IS AN ACCEPTABLE DISTANCE FROM
 THE NEAREST FIRE HYDRANT.
 -LANDSCAPE PLAN LP-1 SHOWS A TREE CLOSE TO GATE VALVES
 NEAR TAP FOR THE DOMESTIC & IRRIGATION WATER SERVICES.
 PLEASE PROVIDE MORE CLEARANCE AND/OR ADD ROOT BARRIERS.
 -WILL PROVIDE FURTHER DETAILED COMMENTS FOR MINOR
 ISSUES AT FORMAL ENGINEERING SUBMITTAL.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status F Date 12-03-2020 Cont ID  
Sent By rrossano Date 12-03-2020 Time   Rev Time 0.00
Received By rrossano Date 12-03-2020 Time   Sent To  
Notes
2020-12-03 14:03:00COMMENTS PER RICK ROSSANO, PROJ. COORD, CITY OF WPB
 ENG. SVCS., [email protected], 561-494-1098:
  
 SUBMITTED LOS ANALYSIS SUMMARY TABLE AVG. DAILY FLOWS
 DO NOT MATCH THOSE ON SHEET C2.1 OF CIVIL PLANS.
  
 FOR ENGINEERING SUBMITTAL, PROVIDE PROFILES OF ALL
 PROPOSED UTILITY CROSSINGS.
  
 FOR ENGINEERING SUBMITTAL, PROVIDE ENLARGED DETAIL ON
 PLANS OF PROPOSED LOCATION OF WATER METERS AND BACKFLOW
 PREVENTION UNITS.
  
 FOR ENGINEERING SUBMITTAL, PLEASE LABEL MATERIALS OF
 ALL EXISTING CITY WATER & SEWER INFRASTRUCTURE IN ROW.
  
 FOR ENGINEERING SUBMITTAL, PLEASE PROVIDE PROJECT
 ADDRESS.
  
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC.
 SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected],
 561-822-2262:
 -SOME PRIOR COMMENTS WERE NOT SATISFIED. WILL LIST ONES
 NEEDING ATTENTION AGAIN:
 -CIVIL PLAN WATER SERVICE STANDARD DETAILS ARE OLD
 REVISION. PLEASE REPLACE WITH MOST UPDATED REVISION.
 -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND
 INSTALLATION AND NOT UNDERGROUND VAULT INSTALLATION.
 PLEASE ADD ABOVE-GROUND WORDING TO LABEL ON C1.2 AND
 REPLACE THE VAULT STANDARD DETAIL ON C2.3 WITH THE
 ABOVE-GROUND INSTALLATION.
 -4 IN. DIP WATER SERVICE IS BRANCHED INTO 1.5 IN. AND 4
 IN. METERS. PLAN DESIGNER NEED VERIFY CUSTOMER WITH NOT
 HAVE PROBLEMS USING WATER WITH THAT SETUP.
 ADDITIONAL COMMENTS:
 -NO WATER MAIN VALVES IN THE STREETS ARE SHOWN. PLEASE
 ADD ALL EXISTING AND PROPOSED GATE VALVES TO WATER
 PLAN.
 -ON WATER PLAN, REMOVE WORDING RPZ IN PUMP ROOM SINCE
 CONTAINMENT DOMESTIC BACKFLOW ASSEMBLY WILL BE OUTSIDE
 ADJACENT THE METER.
 -WATER MAIN ON SAPODILLA IS NOT LABELED WITH PIPE
 SIZING OR MATERIAL TYPE. PLEASE ADD SO CAN VERIFY WILL
 ACCOMMODATE NEW 8IN. DIP. SIMILARLY ADD PIPE MATERIAL
 TYPE TO WATER MAIN LABELING ON ROSEMARY.
 -FIRE HYDRANT AT ROSEMARY AND 2ND IS PROPOSED TO BE IN
 THE MIDDLE OF PEDESTRIAN SIDEWALK TRAFFIC. PLEASE
 RELOCATE FIRE HYDRANT TO NEARBY AREA OUT OF PEDESTRIAN
 TRAFFIC SINCE WATER MAIN IS BEING REPLACED.
 -FDC IS PRIVATELY OWNED AND SHOULD NOT BE IN ROW.
 PLEASE RELOCATE AND MAKE SURE NEW LOCATION IS NOT IN
 PEDESTRIAN TRAFFIC.
 -THERE IS A CIRCULAR OBJECT IN SIDEWALK SLIGHTLY NE OF
 FDC. PLEASE DESCRIBE WHAT IT IS AND LABEL ON PLAN.
 -NEAR THE ENTRANCE ON 2ND ST, THERE APPEARS TO BE SOME
 FIND OF GATES ENCROACHING INTO SIDEWALK. VERIFY IF THAT
 IS ALLOWED BY CITY WPB.
 -DCDA MAY NOT BE IN UNDERGROUND VAULT. NEED UPDATE
 WATER PLAN.
 -PAVEMENT RESTORATION LIMITS NEED TO BE UPDATED TO
 REFLECT THE ENTIRE WATER MAIN THAT IS BEING REPLACED ON
 2ND ST. ALSO INCLUDE THE INTERSECTIONS.
 -EXISTING FIRE HYDRANT AT SAPODILLA AND 2ND STILL
 APPEARS TO BE MISSING FROM WATER PLAN. PLEASE ADD AND
 LABEL.
 -CANNOT LOCATE A DEMO PLAN. PLEASE SUBMIT DEMO PLAN IF
 THERE WILL BE DEMOLITION.
 -STILL CANNOT LOCATE ON WATER PLAN EXISTING SMALL WATER
 SERVICES ON 2ND AND 3RD ST. PLEASE ADD TO PLAN
 -THERE ARE SEVERAL WATER METER BOXES IN THE SIDEWALK ON
 SOUTH SIDE OF 3RD ST. PLEASE SHOW THEM ON THE PLANS AND
 LABEL WHAT IS HAPPENING TO THEM.
 -WILL ALL OF THE PROPOSED BUILDINGS FOR THE PROJECT BE
 FED BY THE WATER SERVICES ON 2ND ST?
 -LANDSCAPE TREES ON 2ND ST ARE CONFLICTING WITH THE
 PROPOSED WATER MAIN. THE WORST ONE IS NEAR THE EAST
 INTERSECTION ISLAND WHERE TREE AND WATER MAIN ARE AT
 SAME LOCATION. THE OTHER TREES ARE CLOSE TO THE WATER
 MAIN IN THE ISLANDS. PLEASE RESOLVE THOSE CONFLICTS.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 10-16-2020 Cont ID  
Sent By RROSSANO Date 10-16-2020 Time   Rev Time 0.00
Received By rrossano Date 10-16-2020 Time   Sent To  
Notes
2020-10-16 19:49:03COMMENTS PER RICK ROSSANO, PROJ. COORD, CITY OF WPB
 ENG. SVCS., [email protected], 561-494-1098:
  
 PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 FOR ENGINEERING SUBMITTAL, SHOW VERTICAL DATUM AND
 DATUM CONVERSION INFORMATION (NAVD 88 AND NGVD 29).
  
 FOR ENGINEERING SUBMITTAL, SHOW ALL FRANCHISE
 UTILITIES.
  
 FOR ENGINEERING SUBMITTAL, ADD PAVEMENT RESTORATION
 NOTE.
  
 FOR ENGINEERING SUBMITTAL, PROVIDE ENLARGED DETAIL ON
 PLANS OF PROPOSED LOCATION OF WATER METER AND BACKFLOW
 PREVENTION. PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS
 FOR CITY PERSONNEL TO PROPOSED UTILITIES INCLUDING
 WATER METERS.
  
 COMMENTS PER MARK HURLEY, FIELD CUSTOMER SVC.
 SUPERVISOR, CITY OF WPB PUB. UTIL., [email protected],
 561-822-2262:
  
 -CIVIL PLAN WATER SERVICE STANDARD DETAILS ARE OLD
 REVISION. PLEASE REPLACE WITH MOST UPDATED REVISION.
 SHEET C1.2
 -THERE APPEAR TO BE SEVERAL WATER MAIN GATE VALVES IN
 CURBS. PLEASE DO NOT LOCATE VALVE BOXES IN CURBS.
 -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND
 INSTALLATION AND NOT UNDERGROUND VAULT INSTALLATION.
 PLEASE ADD ?ABOVE-GROUND? TO LABEL AND REPLACE THE WS-6
 WITH THE CORRECT STANDARD DETAILS.
 -RECOMMEND PARALLEL/DUAL BACKFLOW ASSEMBLIES FOR THE 4
 IN. DOMESTIC WATER SERVICE TO MINIMIZE WATER OUTAGES
 DURING BACKFLOW MAINTENANCE.
 -4 IN. DIP WATER SERVICE IS BRANCHED INTO 1.5 IN. AND 4
 IN. METERS. PLAN DESIGNER NEED VERIFY CUSTOMER WITH NOT
 HAVE PROBLEMS USING WATER WITH THAT SETUP. FOR
 ENGINEERING SUBMITTAL, ALSO LABEL THAT BRANCH WITH TYPE
 OF FITTING/TAP AND WATER SERVICE PIPING FEEDING 1.5 IN.
 IRRIGATION METER.
 -FOR FORMAL ENGINEERING SUBMITTAL ADD WATER DEMAND
 CALCULATIONS TO WATER PLAN AND LABEL FIRELINE POINT OF
 SERVICE GATE VALVE.
 -UTILITY EASEMENTS ARE NEEDED AROUND WATER METERS AND
 WATER SERVICE PIPING ON PRIVATE PROPERTY. PLEASE ADD
 AND LABEL ON PLAN.
 -EXISTING FIRE HYDRANTS STILL APPEAR TO BE MISSING FROM
 PLAN. PLEASE ADD AND LABEL.
 -4 IN. DOMESTIC WATER SERVICE HAS AN ISOLATION BACKFLOW
 ASSEMBLY CALLED OUT IN FIRE ROOM. THIS MIGHT BE AN
 ERROR BETWEEN REVISIONS. CONTAINMENT BACKFLOW ASSEMBLY
 FOR DOMESTIC MAY NOT BE INSIDE BUILDING.
 -8 IN. DCDA MAY NOT BE UNDERGROUND. IF NEED TO MEET
 FIRE DEPARTMENT REQUIREMENTS REGARDING COLLAPSE ZONES,
 DCDA MAY BE LOCATED INSIDE BUILDING IF BACKFLOW
 COVENANT IS COMPLETED AND SUBMITTED BY PROPERTY OWNER.
 -SHOW EXISTING WATER SERVICES RUNNING NORTH AND SOUTH
 OF EXISTING WATER MAINS ON 2ND ST FOR FORMAL
 ENGINEERING SUBMITTAL.
 -VERIFY THAT WATER MAIN TAPS AND PAVEMENT RESTORATION
 ARE IN COMPLIANCE WITH STANDARD DETAIL P-4. IF P-4 IS
 GOING TO BE USED, ADD TO PLAN.
 -CANNOT FIND NUMERICAL PROPERTY ADDRESS ON PLAN. PLEASE
 ADD BEFORE FINAL COPY.
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-05-2019 Cont ID  
Sent By rrossano Date 12-05-2019 Time   Rev Time 4.00
Received By rrossano Date 12-05-2019 Time   Sent To  
Notes
2019-12-05 12:18:33PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND STORM
 DRAINAGE LINES ALONG ENTIRE PROJECT FRONTAGE.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PLEASE CLEARLY SHOW CITY RIGHTS OF WAY.
  
 PROVIDE PROFILE AND CLEARANCES AT ALL UTILITY
 CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS.
  
 PLEASE PROVIDE CCTV OF UPSTREAM SANITARY LINES TO
 NORTH, SOUTH AND WEST.
  
 MANHOLE ON ROSEMARY AVE. WILL REQUIRE REHAB.
  
 PROVIDE ONSITE CLEANOUTS NEAR PROPERTY LINE FOR
 PROPOSED SANITARY LATERALS.
  
 PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
  
 FOR FORMAL ENGINEERING SUBMITTAL, SHOW ALL ADJACENT
 ADDRESSES AND SANITARY LATERALS TO BE AFFECTED BY NEW
 SERVICE BEING INSTALLED ALONG 2ND ST.
  
 THE FOLLOWING COMMENTS ARE PER MARK HURLEY, PUBLIC
 UTILITIES CUSTOMER SERVICE SUPERVISOR, 561-822-2262
 [email protected]
  
 -EXISTING WATER SERVICES NOT SHOWN ? SHOULD BE SHOWN
 AND LABELED ON PLAN ALONG WITH WHAT HAPPENING TO THEM.
  
 -NEW WATER SERVICES ON 2ND ST ARE CROSSING OTHER
 UTILITIES. EACH CROSSING SHOULD BE LABELED WITH HOW
 CONFLICT IS RESOLVED.
  
 -DOMESTIC METER SHOULD BE INSTALLED ABOVE-GROUND AND
 LABELED AS SUCH ON PLAN. WOULD NEED U.E. AROUND IT.
 LOCATION AREA LOOKS THIN -> NOT SURE IF WOULD HAVE
 ENOUGH ROOM FOR IT -> NO PART OF IT INCLUDING BYPASS
 BOXES/LIDS SHOULD BE IN A SIDEWALK. ASSOCIATED BACKFLOW
 ASSEMBLY CANNOT BE INSTALLED ACROSS DRIVEWAY AND INSIDE
 BUILDING -> NEEDS TO BE IMMEDIATELY
 ADJACENT AFTER THE METERED WATER SERVICE ON PRIVATE
 PROPERTY AND NOT IN ANY ROW OR UE. CUSTOMER SHOULD
 CONSIDER PARALLEL BACKFLOW ASSEMBLIES TO MINIMIZE WATER
 OUTAGES DURING BACKFLOW MAINTENANCE.
  
 -DRIVEWAY ENTRANCE LOOKS LIKE WILL CAUSE ACCIDENTS OR
 TRAFFIC CONFUSION. IT?S ONE WAY STREET GOING EAST, BUT
 DRIVERS TURNING INTO DRIVEWAY MUST CROSS OUTGOING
 DRIVERS IN CONFLICT. COULD SOMETHING BE DONE TO
 MINIMIZE THAT CONFLICT?
  
 -FIRE DCDA SHOULD NOT BE LOCATED IN BUILDING UNLESS
 FIRE DEPT. REQUIRES IT INSIDE BUILDING. IF REQUIRED TO
 BE INSIDE BUILDING, PROPERTY OWNER WOULD HAVE TO SUBMIT
 BACKFLOW COVENANT.
  
 -PROPOSED SS ON 2ND ST. LOOKS LIKE CLOSER THAN 10? FROM
 EXISTING WATER MAIN -> UNDERSTAND THIS SHOULD BE AT
 LEAST 10? DISTANCE. CROSSINGS WITH EXISTING WATER MAINS
 AND WATER SERVICES ARE NOT SHOWN AND LABELED WITH HOW
 RESOLVED.
  
 -EXISTING WATER SERVICES FEEDING SOUTH SIDE OF 2ND ST
 FROM THE 6? WATER MAIN ARE NOT SHOWN AND LABELED. SHOW
 ALL OTHERS IN PROJECT AREA AS WELL.
  
 -PLEASE SHOW AND LABEL EXISTING FIRE HYDRANTS.
  
 -E-W ALLEY LOOKS LIKE CITY ROW -> NOT SURE IF CUSTOMER
 GOT APPROVAL TO ELIMINATE ALLEY.
  
 -SAW HISTORIC PICTURE OF LARGE TREE IN VICINITY OF NEW
 WATER SERVICES. IF TREE STILL THERE, TREE SHOULD BE
 RELOCATED OR WATER SERVICES POSITIONED FAR AWAY FROM
 IT.
  
 -OUR GIS SHOWS 30? EXISTING WATER MAIN REDUCING DOWN TO
 24? NEAR SAPODILLA. IF THAT IS CORRECT SHOULD BE SHOWN
 ON PLAN.
  
 -PLAN IS MISSING THE WATER DEMAND CALCULATIONS CHART.
  
 -PLAN SHOULD HAVE SEPARATE ENLARGED PLAN SECTIONS JUST
 FOR THE NEW LARGE METERED WATER SERVICES SHOWING DETAIL
 OF HOW CONSTRUCTED.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 FAX:
 (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ, SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1085
 FAX: (561) 494-1116 MOBILE: (561) 644-7301 EMAIL:
 [email protected] WWW.WPB.ORG/ENGINEERING
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 10-08-2020 Cont ID  
Sent By pleduc Date 10-08-2020 Time 12:44 Rev Time 0.00
Received By pleduc Date 10-08-2020 Time 12:44 Sent To  
Notes
2020-10-08 12:49:15AFTER A REVIEW OF THE PPRC RESPONSE LETTER REGARDING
 THE GRAND FROM SHUTTS TO ANA MARIA APONTE, URBAN DESIGN
 PLANNER, DATED SEPTEMBER 28, 2020,WITH THE ATTACHED
 DRAWING DOCUMENTS, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS APPEAR TO HAVE BEEN
 ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-06-2019 Cont ID  
Sent By pleduc Date 12-06-2019 Time   Rev Time 0.00
Received By pleduc Date 12-06-2019 Time 15:47 Sent To  
Notes
2019-12-06 15:55:46THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 IT IS RECOMMENDED FOR APARTMENT BUILDINGS OF THIS SIZE
 TO HAVE TWO SEPARATE FDC LOCATIONS REMOTELY LOCATED.
  
 7A. PER NFPA 14
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 7B. PLEASE REVIEW THE DISTANCE SEPARATION OF THE
 STAIRWELLS AS THE SEPARATION DISTANCE IS NOT INDICATED.
  
 7.3.2.2* WHERE THE MOST REMOTE PORTION OF A
 NON-SPRINKLERED FLOOR OR STORY IS LOCATED IN EXCESS OF
 150 FT (45.7 M) OF TRAVEL DISTANCE FROM A HOSE
 CONNECTION IN OR ADJACENT TO A REQUIRED EXIT OR THE
 MOST REMOTE PORTION OF A SPRINKLERED FLOOR OR STORY
 IS LOCATED IN EXCESS OF 200 FT (61 M) OF TRAVEL
 DISTANCE FROM A HOSE CONNECTION IN OR ADJACENT TO A
 REQUIRED EXIT, ADDITIONAL HOSE CONNECTIONS SHALL BE
 PROVIDED, IN APPROVED LOCATIONS, WHERE REQUIRED BY THE
 LOCAL FIRE DEPARTMENT OR THE AHJ.
  
 7C. PER NFPA 1
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 7D. THE LOCATION OF THE DDCV FIRE LINE LOCATION SHALL
 MEET THE REQUIREMENTS OF NFPA 24 AND SHALL BE
 COORDINATED WITH THE OFFICE OF FIRE MARSHAL, THE CITY'S
 ENGINEERS OFFICE, THE LANSCAPE PLANNER, AND THE CITY'S
 PLANNING AND ZONING OFFICE.
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 13. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 12-03-2019 Cont ID  
Sent By fmittner Date 12-03-2019 Time 13:28 Rev Time 0.00
Received By fmittner Date 12-03-2019 Time 13:27 Sent To  
Notes
2019-12-03 13:27:013 PARCELS OF PROPOSED PROJECT FALL WITHIN THE NORTHWEST
 HISTORIC DISTRICT (LR AND NR)
  
 NO WEST ELEVATION PROVIDED, NOT ABLE TO EVALUATE.
  
 PROJECT WILL NEED COMP PLAN AND ZONING CHANGES TO
 COMPLY, ONCE THAT IS AFFECTUATED, THE FOLLOWING SHALL
 BE MODIFIED TO BE CONSISTENT WITH THE HISTORIC DISTRICT
 LDR'S, DESIGN GUIDELINES AND SOIS:
  
 1. DOG PARK PARCEL - IDENTIFY FENCING MATERIAL AND
 HEIGHT. ALUMINUM PREFERRED, IF USING CHAIN LINK SHALL
 BE FULLY SCREENED FROM VIEW WITH LANDSCAPING.
 2. 3-STORY BUILDING, WESTERN 2 PARCELS. REMOVE THIRD
 FLOOR UNIT B-1 TO BRING WESTERN PORTION INTO HEIGHT
 COMPATIBILITY WITH TWO STORY MULTI-FAMILY AT CORNER.
 MODIFY PARAPET AT THAT CORNER TO BE FLUSH WITH ROOFLINE
 NOT PROJECTING UP AT CORNER AS IS CURRENTLY INDICATED.
 B-1 UNITS ON LEVEL 1 AND 2 SHALL FEATURE CORNER WINDOWS
 IN ALUMINUM MILL FINISH FRAMES TO BE COMPATIBLE WITH
 EXISTING STRUCTURE ON CORNER. B-1 UNITS ON LEVEL 1 AND
 2 SHALL FEATURE PAINTED STAGGERED BRICK OR BREEZEBLOCKS
 FOR BALCONY RAILINGS/ENCLOSURES TO RELATE WITH
 ARCHITECTURAL FEATURES OF HISTORIC DISTRICT.
  
 NEW CONSTRUCION OF COMPONENTS OF PROJECT WITHIN
 HISTORIC DISTRICT REQUIRES SUBMITTAL OF A COA AND
 APPROVAL BY THE HISTORIC PRESERVATION BOARD.
  
 QUESTIONS, CONTACT: FRIEDERIKE MITTNER, CITY HISTORIC
 PRESERVATION PLANNER AT (561) 822-1457 OR
 [email protected]

Review Stop L LANDSCAPING
Rev No 4 Status P Date 04-14-2021 Cont ID  
Sent By rcaranci Date 04-14-2021 Time 16:09 Rev Time 0.00
Received By rcaranci Date 04-14-2021 Time 16:09 Sent To  
Notes
2021-04-14 16:11:01FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: THE GRAND Z19110020
 APRIL 14, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE. 1:1 MITIGATION IS EQUAL TO THE CATEGORY VALUE.
 MANGO CATEGORY 1 EQUALS 300 SQ FT, SABAL PALM CATEGORY
 3 EQUALS 100 SQ FT.
 THERE ARE MULTIPLE TREES THAT ARE 20 FEET OR MORE
 CANOPY DIAMETER THAT DO NOT SHOW THE ACTUAL SQUARE
 FOOTAGE OF CANOPY THAT MUST BE MITIGATED. #1, 2, 3, 13,
 17, 30, 36, 38, 74, 77, 95, 108, 110. REVISE.
 #52 AND 64 FICUS NITIDA, #94 SAPODILLA ARE NOT LISTED
 AS PROHIBITED INVASIVE IN WPB CODE. MUST BE MITIGATED.
 ? SATISFIED. INCLUDE EXISTING STREET TREES TO BE
 REMOVED AND REPLACED ON ROSEMARY AVE.
 ? SATISFIED. REVISE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED AFTER MAKING CORRECTIONS.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 SILVER BUTTONWOOD IS CATEGORY 2, FOR 150 SQ FT CREDIT.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. DESCRIBE THE METHODOLOGY USED TO DETERMINE
 CONDITION. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR. THERE APPEAR TO BE SEVERAL SABAL PALMS THAT ARE
 IN GOOD CONDITION THAT CAN BE RELOCATED.
  
 3. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD THE TREE
 REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD CANOPY
 TREES AS REQUIRED. TREE GRATES ARE NOT PREFERRED IF THE
 SIDEWALK MEETS THE MINIMUM 8 FOOT WIDTH REQUIREMENT,
 AND PLANTING AREAS SHALL BE USED INSTEAD. BANYAN
 STREETSCAPE NEEDS TO BE COORDINATED WITH THE CITY
 CAPITAL IMPROVEMENT PROJECT.
  
  
 4. SATISFIED. CALCULATIONS FOR NUMBER OF REQUIRED
 STREET TREES NEED TO BE PROVIDED. TOTAL LENGTH OF
 STREETSCAPE FROM ONE PROPERTY LINE TO THE OTHER END,
 DIVIDE BY 30, THEN INDICATE THE NUMBER OF TREES
 REQUIRED AND PROVIDED, ROUNDING UP FOR ANY PORTION
 LEFT.
 PROVIDE THE CALCULATIONS ON THE LANDSCAPE PLAN FOR EACH
 PROPERTY LINE LENGTH ADJACENT TO A STREET, THE REQUIRED
 NUMBER OF TREES AND THE NUMBER PROVIDED. PROVIDE THE
 PROPERTY LINE LENGTH FOR THE BUFFER REQUIREMENT ON THE
 WEST SIDE NOT ADJACENT TO A STREET AND PROVIDE THE
 NUMBER OF TREES REQUIRED AND PROVIDED.
  
 5. REGULATIONS HAVE CHANGED INVALIDATING THIS COMMENT.
 REQUIRED OPEN SPACE TYPES AND SQUARE FOOTAGE CANNOT BE
 DETERMINED AT THIS TIME, AS THERE IS NOT ONE CONSISTENT
 ZONING DESIGNATION FOR ALL THE PARCELS INCLUDED IN THE
 PROPOSED PROJECT.
  
 6. SATISFIED. FLORIDA FRIENDLY DESIGN OPTIONS POINTS
 CANNOT BE COUNTED MORE THAN ONCE IN EACH CATEGORY FOR
 THE SAME PLANTS. EXAMPLE: IF 51% TREES CLAIMED AS
 NATIVE, THE REMAINDER CAN ONLY BE COUNTED TOWARD
 DROUGHT TOLERANT FOR 25-50%.
  
 7. CONDITIONALLY SATISFIED. SHOW LOCATIONS OF UTILITY
 LINES ON LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND
 BACKFLOW PREVENTERS AND FPL TRANSFORMERS. SCREENING
 MUST BE PROVIDED.
 ADJUST LOCATIONS ON LANDSCAPE PLANS TO MATCH CIVIL
 DRAWINGS. FDC IS SHOWN IN CONFLICT WITH THE SIDEWALK.
 GAS AND WATER MAIN ON 2ND ST ARE IN CONFLICT WITH THE
 STREET TREE LOCATIONS, PROVIDE INFORMATION ON HOW THIS
 WILL BE RESOLVED.
 MEETING FROM 12/14 REGARDING UTILITIES AND TREE
 CONFLICTS RESULTED IN SOME POSSIBLE SOLUTIONS. SUBMIT
 REVISED PLANS.
 PLANS WERE NOT UPDATED.
  
 8. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO STREET TREES. PROVIDE
 A TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL
 AND A SEPARATE PLAN SHOWING THE LOCATIONS. AREA FOR
 STRUCTURAL SOIL AND PLANTING AREA SHOULD BE
 APPROXIMATELY 14 FEET IN LENGTH AND 9 FEET IN WIDTH
 RELATIVE TO THE BACK OF CURB. STRUCTURAL SOIL DETAIL IS
 TO SHOW THE CONSTRUCTION CROSS SECTION FOR DEPTH OF 36
 INCHES, AND PLANTING SOIL IN THE PLANTING AREA.
  
 9. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 2418/4814 IS 50% AND DOES NOT MEET THE REQUIREMENT.
 CHANGE SOME SPECIES TO NATIVE OR DROUGHT TOLERANT TO
 ACHIEVE THE MINIMUM 60%. GREEN ISLAND FICUS IS ACCEPTED
 AS LOW WATER USAGE.
  
 ADDITIONAL COMMENTS 10/20/20:
  
 10. SATISFIED. REMOVE GRAVEL FROM PLAN SHOWN ON WEST
 SIDE OF BUILDING. UNLESS IT IS GROUNDCOVER OR GRASS,
 PLANTING AREAS ARE REQUIRED TO HAVE 3 INCHES OF
 COMPACTED ORGANIC, NON-CYPRESS MULCH PER SECTION
 94-446(1)D.
  
 11. SATISFIED. SHEET A0.3 NEEDS TO IDENTIFY THE
 PRIVATE OPEN SPACE TYPE AND PROVIDE THE CALCULATIONS
 FOR THE REQUIREMENTS AS FOUND IN SECTION 94-109 TABLE
 IV-7 FOR VEGETATED AREA AND TREE CANOPY PER TABLE IV-8.
 THE LANDSCAPE PLAN SHOULD ALSO INCLUDE THE SAME
 INFORMATION.
  
 12. SATISFIED. ADD THE RELOCATED SABAL PALMS TO THE
 PLANT LIST.
  
 13. SATISFIED. STREET TREE SIZE REQUIREMENT IS 20 FEET
 HEIGHT, FLORIDA GRADE #1 OR BETTER PER SECTION 94-113.
 MAGNOLIA WILL NOT WORK TO MEET THE CANOPY REQUIREMENT
 FOR REQUIRED STREET TREE. THE ARRANGEMENT WITH THE LIVE
 OAKS CLOSER TO THE BUILDING AND GUMBO LIMBO IN THE
 STREET BULB OUTS IS ACCEPTABLE. THE CONCERN IS THAT THE
 GUMBO LIMBOS WILL TAKE SOME PRUNING MAINTENANCE TO MAKE
 SURE THE BRANCHES DEVELOP ABOVE THE 14 FOOT CLEARANCE
 NEEDED FOR THE TRAVEL LANE AND 8 FOOT CLEARANCE NEEDED
 FOR THE SIDEWALK.
  
 ADDITIONAL COMMENTS 12/14/20:
  
  
 14. PARTIALLY SATISFIED. WEST BUFFER TREES CANNOT COUNT
 OFFSITE EXISTING TREES. SEE COMMENT #15. CALCULATIONS
 FOR THE ENTIRE BUFFER LENGTH NEED TO BE USED TO
 DETERMINE THE NUMBER OF REQUIRED TREES. 12 PALMS
 PROVIDED EQUAL 4 TREES, THE 2 MAHOGANY TREES MAY BE
 COUNTED, SO CURRENTLY 6 TREES ARE PROVIDED. PROVIDE THE
 CALCULATION AND ADD TREES OR PALMS AS NEEDED.
 TOTAL PER THE SURVEY IS 70? + 57.5? +127.5 = 255 FEET.
 9 TREES ARE NEEDED.
  
 15. CONDITIONALLY SATISFIED. OFFSITE TREES #15 AND #17
 NEED TO BE EVALUATED BY A CERTIFIED ARBORIST FOR THE
 REDUCTION IN CANOPY AND ROOT SYSTEM THAT WILL BE
 REQUIRED TO CONSTRUCT THE BUILDING TO ASSURE THEY WILL
 NOT DESTABILIZE OR CAUSE DECLINE IN THE TREES. THE
 OWNERSHIP OF THE TREES ALSO NEEDS TO BE DETERMINED
 RELATIVE TO THE PROPERTY LINE.
  
 ARBORIST REPORT WAS NOT SUBMITTED WITH THE 3/22/21
 RESUBMITTAL. THIS COMMENT NEEDS TO BE RESOLVED PRIOR TO
 ISSUING THE TREE ALTERATION PERMIT FOR MITIGATION
 PURPOSES AND TO ADD REQUIRED TREES TO THE BUFFER.
  
 16. SATISFIED. STREET TREE REQUIREMENTS APPLY FOR THE N
 SAPODILLA PROPERTY LINE LENGTH FOR 2 STREET TREES, BUT
 THEY NEED TO BE IN THE RIGHT OF WAY.
  
 17. CONDITIONALLY SATISFIED. THERE IS TREE CANOPY
 MITIGATION DUE OF 8072 SQ FT. INDICATE IF THIS WILL BE
 ADDRESSED THROUGH PAYMENT IN LIEU OF $13453.00.
  
 ADDITIONAL MITIGATION WILL BE REQUIRED IF #15 AND #17
 ARE REMOVED. MITIGATION WILL BE PROVIDED WITH
 ADDITIONAL TREES PER COMMENT #14.
 NOTE THAT THE 3/22/21 SUBMITTAL CONTAINED THE SAME
 LANDSCAPE AND TREE MITIGATION PLANS FROM 12/23/20.
 PLEASE SUBMIT UPDATED PLANS.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 12-14-2020 Cont ID  
Sent By rcaranci Date 12-14-2020 Time 16:12 Rev Time 0.00
Received By rcaranci Date 12-14-2020 Time 16:12 Sent To  
Notes
2020-12-14 16:23:43FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: THE GRAND Z19110020
 DECEMBER 14, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE. 1:1 MITIGATION IS EQUAL TO THE CATEGORY VALUE.
 MANGO CATEGORY 1 EQUALS 300 SQ FT, SABAL PALM CATEGORY
 3 EQUALS 100 SQ FT.
 THERE ARE MULTIPLE TREES THAT ARE 20 FEET OR MORE
 CANOPY DIAMETER THAT DO NOT SHOW THE ACTUAL SQUARE
 FOOTAGE OF CANOPY THAT MUST BE MITIGATED. #1, 2, 3, 13,
 17, 30, 36, 38, 74, 77, 95, 108, 110. REVISE.
 #52 AND 64 FICUS NITIDA, #94 SAPODILLA ARE NOT LISTED
 AS PROHIBITED INVASIVE IN WPB CODE. MUST BE MITIGATED.
 ? SATISFIED. INCLUDE EXISTING STREET TREES TO BE
 REMOVED AND REPLACED ON ROSEMARY AVE.
 ? SATISFIED. REVISE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED AFTER MAKING CORRECTIONS.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 SILVER BUTTONWOOD IS CATEGORY 2, FOR 150 SQ FT CREDIT.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. DESCRIBE THE METHODOLOGY USED TO DETERMINE
 CONDITION. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR. THERE APPEAR TO BE SEVERAL SABAL PALMS THAT ARE
 IN GOOD CONDITION THAT CAN BE RELOCATED.
  
 3. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD THE TREE
 REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD CANOPY
 TREES AS REQUIRED. TREE GRATES ARE NOT PREFERRED IF THE
 SIDEWALK MEETS THE MINIMUM 8 FOOT WIDTH REQUIREMENT,
 AND PLANTING AREAS SHALL BE USED INSTEAD. BANYAN
 STREETSCAPE NEEDS TO BE COORDINATED WITH THE CITY
 CAPITAL IMPROVEMENT PROJECT.
  
  
 4. SATISFIED. CALCULATIONS FOR NUMBER OF REQUIRED
 STREET TREES NEED TO BE PROVIDED. TOTAL LENGTH OF
 STREETSCAPE FROM ONE PROPERTY LINE TO THE OTHER END,
 DIVIDE BY 30, THEN INDICATE THE NUMBER OF TREES
 REQUIRED AND PROVIDED, ROUNDING UP FOR ANY PORTION
 LEFT.
 PROVIDE THE CALCULATIONS ON THE LANDSCAPE PLAN FOR EACH
 PROPERTY LINE LENGTH ADJACENT TO A STREET, THE REQUIRED
 NUMBER OF TREES AND THE NUMBER PROVIDED. PROVIDE THE
 PROPERTY LINE LENGTH FOR THE BUFFER REQUIREMENT ON THE
 WEST SIDE NOT ADJACENT TO A STREET AND PROVIDE THE
 NUMBER OF TREES REQUIRED AND PROVIDED.
  
 5. REGULATIONS HAVE CHANGED INVALIDATING THIS COMMENT.
 REQUIRED OPEN SPACE TYPES AND SQUARE FOOTAGE CANNOT BE
 DETERMINED AT THIS TIME, AS THERE IS NOT ONE CONSISTENT
 ZONING DESIGNATION FOR ALL THE PARCELS INCLUDED IN THE
 PROPOSED PROJECT.
  
 6. SATISFIED. FLORIDA FRIENDLY DESIGN OPTIONS POINTS
 CANNOT BE COUNTED MORE THAN ONCE IN EACH CATEGORY FOR
 THE SAME PLANTS. EXAMPLE: IF 51% TREES CLAIMED AS
 NATIVE, THE REMAINDER CAN ONLY BE COUNTED TOWARD
 DROUGHT TOLERANT FOR 25-50%.
  
 7. PARTIALLY SATISFIED. SHOW LOCATIONS OF UTILITY LINES
 ON LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND
 BACKFLOW PREVENTERS AND FPL TRANSFORMERS. SCREENING
 MUST BE PROVIDED.
 ADJUST LOCATIONS ON LANDSCAPE PLANS TO MATCH CIVIL
 DRAWINGS. FDC IS SHOWN IN CONFLICT WITH THE SIDEWALK.
 GAS AND WATER MAIN ON 2ND ST ARE IN CONFLICT WITH THE
 STREET TREE LOCATIONS, PROVIDE INFORMATION ON HOW THIS
 WILL BE RESOLVED.
 MEETING FROM 12/14 REGARDING UTILITIES AND TREE
 CONFLICTS RESULTED IN SOME POSSIBLE SOLUTIONS. SUBMIT
 REVISED PLANS.
  
 8. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO STREET TREES. PROVIDE
 A TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL
 AND A SEPARATE PLAN SHOWING THE LOCATIONS. AREA FOR
 STRUCTURAL SOIL AND PLANTING AREA SHOULD BE
 APPROXIMATELY 14 FEET IN LENGTH AND 9 FEET IN WIDTH
 RELATIVE TO THE BACK OF CURB. STRUCTURAL SOIL DETAIL IS
 TO SHOW THE CONSTRUCTION CROSS SECTION FOR DEPTH OF 36
 INCHES, AND PLANTING SOIL IN THE PLANTING AREA.
  
 9. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 2418/4814 IS 50% AND DOES NOT MEET THE REQUIREMENT.
 CHANGE SOME SPECIES TO NATIVE OR DROUGHT TOLERANT TO
 ACHIEVE THE MINIMUM 60%. GREEN ISLAND FICUS IS ACCEPTED
 AS LOW WATER USAGE.
  
 ADDITIONAL COMMENTS 10/20/20:
  
 10. SATISFIED. REMOVE GRAVEL FROM PLAN SHOWN ON WEST
 SIDE OF BUILDING. UNLESS IT IS GROUNDCOVER OR GRASS,
 PLANTING AREAS ARE REQUIRED TO HAVE 3 INCHES OF
 COMPACTED ORGANIC, NON-CYPRESS MULCH PER SECTION
 94-446(1)D.
  
 11. SATISFIED. SHEET A0.3 NEEDS TO IDENTIFY THE
 PRIVATE OPEN SPACE TYPE AND PROVIDE THE CALCULATIONS
 FOR THE REQUIREMENTS AS FOUND IN SECTION 94-109 TABLE
 IV-7 FOR VEGETATED AREA AND TREE CANOPY PER TABLE IV-8.
 THE LANDSCAPE PLAN SHOULD ALSO INCLUDE THE SAME
 INFORMATION.
  
 12. SATISFIED. ADD THE RELOCATED SABAL PALMS TO THE
 PLANT LIST.
  
 13. SATISFIED. STREET TREE SIZE REQUIREMENT IS 20 FEET
 HEIGHT, FLORIDA GRADE #1 OR BETTER PER SECTION 94-113.
 MAGNOLIA WILL NOT WORK TO MEET THE CANOPY REQUIREMENT
 FOR REQUIRED STREET TREE. THE ARRANGEMENT WITH THE LIVE
 OAKS CLOSER TO THE BUILDING AND GUMBO LIMBO IN THE
 STREET BULB OUTS IS ACCEPTABLE. THE CONCERN IS THAT THE
 GUMBO LIMBOS WILL TAKE SOME PRUNING MAINTENANCE TO MAKE
 SURE THE BRANCHES DEVELOP ABOVE THE 14 FOOT CLEARANCE
 NEEDED FOR THE TRAVEL LANE AND 8 FOOT CLEARANCE NEEDED
 FOR THE SIDEWALK.
  
 ADDITIONAL COMMENTS 12/14/20:
  
  
 14. WEST BUFFER TREES CANNOT COUNT OFFSITE EXISTING
 TREES. SEE COMMENT #15. CALCULATIONS FOR THE ENTIRE
 BUFFER LENGTH NEED TO BE USED TO DETERMINE THE NUMBER
 OF REQUIRED TREES. 12 PALMS PROVIDED EQUAL 4 TREES, THE
 2 MAHOGANY TREES MAY BE COUNTED, SO CURRENTLY 6 TREES
 ARE PROVIDED. PROVIDE THE CALCULATION AND ADD TREES OR
 PALMS AS NEEDED.
  
 15. OFFSITE TREES #15 AND #17 NEED TO BE EVALUATED BY A
 CERTIFIED ARBORIST FOR THE REDUCTION IN CANOPY AND ROOT
 SYSTEM THAT WILL BE REQUIRED TO CONSTRUCT THE BUILDING
 TO ASSURE THEY WILL NOT DESTABILIZE OR CAUSE DECLINE IN
 THE TREES. THE OWNERSHIP OF THE TREES ALSO NEEDS TO BE
 DETERMINED RELATIVE TO THE PROPERTY LINE.
  
 16. STREET TREE REQUIREMENTS APPLY FOR THE N SAPODILLA
 PROPERTY LINE LENGTH FOR 2 STREET TREES, BUT THEY NEED
 TO BE IN THE RIGHT OF WAY.
  
 17. THERE IS TREE CANOPY MITIGATION DUE OF 8072 SQ FT.
 INDICATE IF THIS WILL BE ADDRESSED THROUGH PAYMENT IN
 LIEU OF $13453.00.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 10-22-2020 Cont ID  
Sent By rcaranci Date 10-22-2020 Time 11:19 Rev Time 0.00
Received By rcaranci Date 10-22-2020 Time 11:19 Sent To  
Notes
2020-10-22 11:19:48FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: THE GRAND Z19110020
 OCTOBER 22, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? PARTIALLY SATISFIED. TREES AND PALMS CANOPY SQUARE
 FOOTAGE TO BE MITIGATED BASED ON CATEGORY. ANY TREES 20
 FEET OR MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL
 SQUARE FOOTAGE. 1:1 MITIGATION IS EQUAL TO THE CATEGORY
 VALUE. MANGO CATEGORY 1 EQUALS 300 SQ FT, SABAL PALM
 CATEGORY 3 EQUALS 100 SQ FT.
 THERE ARE MULTIPLE TREES THAT ARE 20 FEET OR MORE
 CANOPY DIAMETER THAT DO NOT SHOW THE ACTUAL SQUARE
 FOOTAGE OF CANOPY THAT MUST BE MITIGATED. #1, 2, 3, 13,
 17, 30, 36, 38, 74, 77, 95, 108, 110. REVISE.
 #52 AND 64 FICUS NITIDA, #94 SAPODILLA ARE NOT LISTED
 AS PROHIBITED INVASIVE IN WPB CODE. MUST BE MITIGATED.
 ? SATISFIED. INCLUDE EXISTING STREET TREES TO BE
 REMOVED AND REPLACED ON ROSEMARY AVE.
 ? PARTIALLY SATISFIED. REVISE THE TOTAL SQUARE FOOTAGE
 OF MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED AFTER MAKING CORRECTIONS.
 ? PARTIALLY SATISFIED. PROVIDE THE MITIGATION VALUES BY
 CATEGORY FOR THE PROPOSED TREES AND PALMS.
 SILVER BUTTONWOOD IS CATEGORY 2, FOR 150 SQ FT CREDIT.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. DESCRIBE THE METHODOLOGY USED TO DETERMINE
 CONDITION. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR. THERE APPEAR TO BE SEVERAL SABAL PALMS THAT ARE
 IN GOOD CONDITION THAT CAN BE RELOCATED.
  
 3. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD THE TREE
 REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD CANOPY
 TREES AS REQUIRED. TREE GRATES ARE NOT PREFERRED IF THE
 SIDEWALK MEETS THE MINIMUM 8 FOOT WIDTH REQUIREMENT,
 AND PLANTING AREAS SHALL BE USED INSTEAD. BANYAN
 STREETSCAPE NEEDS TO BE COORDINATED WITH THE CITY
 CAPITAL IMPROVEMENT PROJECT.
  
  
 4. PARTIALLY SATISFIED. CALCULATIONS FOR NUMBER OF
 REQUIRED STREET TREES NEED TO BE PROVIDED. TOTAL LENGTH
 OF STREETSCAPE FROM ONE PROPERTY LINE TO THE OTHER END,
 DIVIDE BY 30, THEN INDICATE THE NUMBER OF TREES
 REQUIRED AND PROVIDED, ROUNDING UP FOR ANY PORTION
 LEFT.
 PROVIDE THE CALCULATIONS ON THE LANDSCAPE PLAN FOR EACH
 PROPERTY LINE LENGTH ADJACENT TO A STREET, THE REQUIRED
 NUMBER OF TREES AND THE NUMBER PROVIDED. PROVIDE THE
 PROPERTY LINE LENGTH FOR THE BUFFER REQUIREMENT ON THE
 WEST SIDE NOT ADJACENT TO A STREET AND PROVIDE THE
 NUMBER OF TREES REQUIRED AND PROVIDED.
  
 5. REGULATIONS HAVE CHANGED INVALIDATING THIS COMMENT.
 REQUIRED OPEN SPACE TYPES AND SQUARE FOOTAGE CANNOT BE
 DETERMINED AT THIS TIME, AS THERE IS NOT ONE CONSISTENT
 ZONING DESIGNATION FOR ALL THE PARCELS INCLUDED IN THE
 PROPOSED PROJECT.
  
 6. SATISFIED. FLORIDA FRIENDLY DESIGN OPTIONS POINTS
 CANNOT BE COUNTED MORE THAN ONCE IN EACH CATEGORY FOR
 THE SAME PLANTS. EXAMPLE: IF 51% TREES CLAIMED AS
 NATIVE, THE REMAINDER CAN ONLY BE COUNTED TOWARD
 DROUGHT TOLERANT FOR 25-50%.
  
 7. PARTIALLY SATISFIED. SHOW LOCATIONS OF UTILITY LINES
 ON LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND
 BACKFLOW PREVENTERS AND FPL TRANSFORMERS. SCREENING
 MUST BE PROVIDED.
 ADJUST LOCATIONS ON LANDSCAPE PLANS TO MATCH CIVIL
 DRAWINGS. FDC IS SHOWN IN CONFLICT WITH THE SIDEWALK.
 GAS AND WATER MAIN ON 2ND ST ARE IN CONFLICT WITH THE
 STREET TREE LOCATIONS, PROVIDE INFORMATION ON HOW THIS
 WILL BE RESOLVED.
  
 8. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO STREET TREES. PROVIDE
 A TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL
 AND A SEPARATE PLAN SHOWING THE LOCATIONS. AREA FOR
 STRUCTURAL SOIL AND PLANTING AREA SHOULD BE
 APPROXIMATELY 14 FEET IN LENGTH AND 9 FEET IN WIDTH
 RELATIVE TO THE BACK OF CURB. STRUCTURAL SOIL DETAIL IS
 TO SHOW THE CONSTRUCTION CROSS SECTION FOR DEPTH OF 36
 INCHES, AND PLANTING SOIL IN THE PLANTING AREA.
  
 9. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445
 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 2418/4814 IS 50% AND DOES NOT MEET THE REQUIREMENT.
 CHANGE SOME SPECIES TO NATIVE OR DROUGHT TOLERANT TO
 ACHIEVE THE MINIMUM 60%. GREEN ISLAND FICUS IS ACCEPTED
 AS LOW WATER USAGE.
  
 ADDITIONAL COMMENTS 10/20/20:
  
 10. REMOVE GRAVEL FROM PLAN SHOWN ON WEST SIDE OF
 BUILDING. UNLESS IT IS GROUNDCOVER OR GRASS, PLANTING
 AREAS ARE REQUIRED TO HAVE 3 INCHES OF COMPACTED
 ORGANIC, NON-CYPRESS MULCH PER SECTION 94-446(1)D.
  
 11. SHEET A0.3 NEEDS TO IDENTIFY THE PRIVATE OPEN
 SPACE TYPE AND PROVIDE THE CALCULATIONS FOR THE
 REQUIREMENTS AS FOUND IN SECTION 94-109 TABLE IV-7 FOR
 VEGETATED AREA AND TREE CANOPY PER TABLE IV-8. THE
 LANDSCAPE PLAN SHOULD ALSO INCLUDE THE SAME
 INFORMATION.
  
 12. ADD THE RELOCATED SABAL PALMS TO THE PLANT LIST.
  
 13. STREET TREE SIZE REQUIREMENT IS 20 FEET HEIGHT,
 FLORIDA GRADE #1 OR BETTER PER SECTION 94-113. MAGNOLIA
 WILL NOT WORK TO MEET THE CANOPY REQUIREMENT FOR
 REQUIRED STREET TREE. THE ARRANGEMENT WITH THE LIVE
 OAKS CLOSER TO THE BUILDING AND GUMBO LIMBO IN THE
 STREET BULB OUTS IS ACCEPTABLE. THE CONCERN IS THAT THE
 GUMBO LIMBOS WILL TAKE SOME PRUNING MAINTENANCE TO MAKE
 SURE THE BRANCHES DEVELOP ABOVE THE 14 FOOT CLEARANCE
 NEEDED FOR THE TRAVEL LANE AND 8 FOOT CLEARANCE NEEDED
 FOR THE SIDEWALK.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-01-2021 Cont ID  
Sent By rcaranci Date 04-01-2021 Time 12:59 Rev Time 0.00
Received By rcaranci Date 04-01-2021 Time 12:59 Sent To  
Notes
2021-04-01 13:01:11FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER
 561-822-1462
 PROJECT: THE GRAND Z19110020
 APRIL 1, 2021
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE. 1:1 MITIGATION IS EQUAL TO THE CATEGORY VALUE.
 MANGO CATEGORY 1 EQUALS 300 SQ FT, SABAL PALM CATEGORY
 3 EQUALS 100 SQ FT.
 THERE ARE MULTIPLE TREES THAT ARE 20 FEET OR MORE
 CANOPY DIAMETER THAT DO NOT SHOW THE ACTUAL SQUARE
 FOOTAGE OF CANOPY THAT MUST BE MITIGATED. #1, 2, 3, 13,
 17, 30, 36, 38, 74, 77, 95, 108, 110. REVISE.
 #52 AND 64 FICUS NITIDA, #94 SAPODILLA ARE NOT LISTED
 AS PROHIBITED INVASIVE IN WPB CODE. MUST BE MITIGATED.
 ? SATISFIED. INCLUDE EXISTING STREET TREES TO BE
 REMOVED AND REPLACED ON ROSEMARY AVE.
 ? SATISFIED. REVISE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED AFTER MAKING CORRECTIONS.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 SILVER BUTTONWOOD IS CATEGORY 2, FOR 150 SQ FT CREDIT.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. DESCRIBE THE METHODOLOGY USED TO DETERMINE
 CONDITION. ANSI A 300 (PART 5) STANDARDS SPECIFY
 EXAMPLES OF SUITABILITY RATINGS OF GOOD, MODERATE, OR
 POOR. THERE APPEAR TO BE SEVERAL SABAL PALMS THAT ARE
 IN GOOD CONDITION THAT CAN BE RELOCATED.
  
 3. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD THE TREE
 REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD CANOPY
 TREES AS REQUIRED. TREE GRATES ARE NOT PREFERRED IF THE
 SIDEWALK MEETS THE MINIMUM 8 FOOT WIDTH REQUIREMENT,
 AND PLANTING AREAS SHALL BE USED INSTEAD. BANYAN
 STREETSCAPE NEEDS TO BE COORDINATED WITH THE CITY
 CAPITAL IMPROVEMENT PROJECT.
  
  
 4. SATISFIED. CALCULATIONS FOR NUMBER OF REQUIRED
 STREET TREES NEED TO BE PROVIDED. TOTAL LENGTH OF
 STREETSCAPE FROM ONE PROPERTY LINE TO THE OTHER END,
 DIVIDE BY 30, THEN INDICATE THE NUMBER OF TREES
 REQUIRED AND PROVIDED, ROUNDING UP FOR ANY PORTION
 LEFT.
 PROVIDE THE CALCULATIONS ON THE LANDSCAPE PLAN FOR EACH
 PROPERTY LINE LENGTH ADJACENT TO A STREET, THE REQUIRED
 NUMBER OF TREES AND THE NUMBER PROVIDED. PROVIDE THE
 PROPERTY LINE LENGTH FOR THE BUFFER REQUIREMENT ON THE
 WEST SIDE NOT ADJACENT TO A STREET AND PROVIDE THE
 NUMBER OF TREES REQUIRED AND PROVIDED.
  
 5. REGULATIONS HAVE CHANGED INVALIDATING THIS COMMENT.
 REQUIRED OPEN SPACE TYPES AND SQUARE FOOTAGE CANNOT BE
 DETERMINED AT THIS TIME, AS THERE IS NOT ONE CONSISTENT
 ZONING DESIGNATION FOR ALL THE PARCELS INCLUDED IN THE
 PROPOSED PROJECT.
  
 6. SATISFIED. FLORIDA FRIENDLY DESIGN OPTIONS POINTS
 CANNOT BE COUNTED MORE THAN ONCE IN EACH CATEGORY FOR
 THE SAME PLANTS. EXAMPLE: IF 51% TREES CLAIMED AS
 NATIVE, THE REMAINDER CAN ONLY BE COUNTED TOWARD
 DROUGHT TOLERANT FOR 25-50%.
  
 7. PARTIALLY SATISFIED. SHOW LOCATIONS OF UTILITY LINES
 ON LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND
 BACKFLOW PREVENTERS AND FPL TRANSFORMERS. SCREENING
 MUST BE PROVIDED.
 ADJUST LOCATIONS ON LANDSCAPE PLANS TO MATCH CIVIL
 DRAWINGS. FDC IS SHOWN IN CONFLICT WITH THE SIDEWALK.
 GAS AND WATER MAIN ON 2ND ST ARE IN CONFLICT WITH THE
 STREET TREE LOCATIONS, PROVIDE INFORMATION ON HOW THIS
 WILL BE RESOLVED.
 MEETING FROM 12/14 REGARDING UTILITIES AND TREE
 CONFLICTS RESULTED IN SOME POSSIBLE SOLUTIONS. SUBMIT
 REVISED PLANS.
 PLANS WERE NOT UPDATED.
  
 8. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO STREET TREES. PROVIDE
 A TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL
 AND A SEPARATE PLAN SHOWING THE LOCATIONS. AREA FOR
 STRUCTURAL SOIL AND PLANTING AREA SHOULD BE
 APPROXIMATELY 14 FEET IN LENGTH AND 9 FEET IN WIDTH
 RELATIVE TO THE BACK OF CURB. STRUCTURAL SOIL DETAIL IS
 TO SHOW THE CONSTRUCTION CROSS SECTION FOR DEPTH OF 36
 INCHES, AND PLANTING SOIL IN THE PLANTING AREA.
  
 9. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 2418/4814 IS 50% AND DOES NOT MEET THE REQUIREMENT.
 CHANGE SOME SPECIES TO NATIVE OR DROUGHT TOLERANT TO
 ACHIEVE THE MINIMUM 60%. GREEN ISLAND FICUS IS ACCEPTED
 AS LOW WATER USAGE.
  
 ADDITIONAL COMMENTS 10/20/20:
  
 10. SATISFIED. REMOVE GRAVEL FROM PLAN SHOWN ON WEST
 SIDE OF BUILDING. UNLESS IT IS GROUNDCOVER OR GRASS,
 PLANTING AREAS ARE REQUIRED TO HAVE 3 INCHES OF
 COMPACTED ORGANIC, NON-CYPRESS MULCH PER SECTION
 94-446(1)D.
  
 11. SATISFIED. SHEET A0.3 NEEDS TO IDENTIFY THE
 PRIVATE OPEN SPACE TYPE AND PROVIDE THE CALCULATIONS
 FOR THE REQUIREMENTS AS FOUND IN SECTION 94-109 TABLE
 IV-7 FOR VEGETATED AREA AND TREE CANOPY PER TABLE IV-8.
 THE LANDSCAPE PLAN SHOULD ALSO INCLUDE THE SAME
 INFORMATION.
  
 12. SATISFIED. ADD THE RELOCATED SABAL PALMS TO THE
 PLANT LIST.
  
 13. SATISFIED. STREET TREE SIZE REQUIREMENT IS 20 FEET
 HEIGHT, FLORIDA GRADE #1 OR BETTER PER SECTION 94-113.
 MAGNOLIA WILL NOT WORK TO MEET THE CANOPY REQUIREMENT
 FOR REQUIRED STREET TREE. THE ARRANGEMENT WITH THE LIVE
 OAKS CLOSER TO THE BUILDING AND GUMBO LIMBO IN THE
 STREET BULB OUTS IS ACCEPTABLE. THE CONCERN IS THAT THE
 GUMBO LIMBOS WILL TAKE SOME PRUNING MAINTENANCE TO MAKE
 SURE THE BRANCHES DEVELOP ABOVE THE 14 FOOT CLEARANCE
 NEEDED FOR THE TRAVEL LANE AND 8 FOOT CLEARANCE NEEDED
 FOR THE SIDEWALK.
  
 ADDITIONAL COMMENTS 12/14/20:
  
  
 14. PARTIALLY SATISFIED. WEST BUFFER TREES CANNOT COUNT
 OFFSITE EXISTING TREES. SEE COMMENT #15. CALCULATIONS
 FOR THE ENTIRE BUFFER LENGTH NEED TO BE USED TO
 DETERMINE THE NUMBER OF REQUIRED TREES. 12 PALMS
 PROVIDED EQUAL 4 TREES, THE 2 MAHOGANY TREES MAY BE
 COUNTED, SO CURRENTLY 6 TREES ARE PROVIDED. PROVIDE THE
 CALCULATION AND ADD TREES OR PALMS AS NEEDED.
 TOTAL PER THE SURVEY IS 70? + 57.5? +127.5 = 255 FEET.
 9 TREES ARE NEEDED.
  
 15. PARTIALLY SATISFIED. OFFSITE TREES #15 AND #17 NEED
 TO BE EVALUATED BY A CERTIFIED ARBORIST FOR THE
 REDUCTION IN CANOPY AND ROOT SYSTEM THAT WILL BE
 REQUIRED TO CONSTRUCT THE BUILDING TO ASSURE THEY WILL
 NOT DESTABILIZE OR CAUSE DECLINE IN THE TREES. THE
 OWNERSHIP OF THE TREES ALSO NEEDS TO BE DETERMINED
 RELATIVE TO THE PROPERTY LINE.
  
 ARBORIST REPORT WAS NOT SUBMITTED WITH THE 3/22/21
 RESUBMITTAL. THIS COMMENT NEEDS TO BE RESOLVED PRIOR TO
 ISSUING THE TREE ALTERATION PERMIT FOR MITIGATION
 PURPOSES AND TO ADD REQUIRED TREES TO THE BUFFER.
  
 16. SATISFIED. STREET TREE REQUIREMENTS APPLY FOR THE N
 SAPODILLA PROPERTY LINE LENGTH FOR 2 STREET TREES, BUT
 THEY NEED TO BE IN THE RIGHT OF WAY.
  
 17. PARTIALLY SATISFIED. THERE IS TREE CANOPY
 MITIGATION DUE OF 8072 SQ FT. INDICATE IF THIS WILL BE
 ADDRESSED THROUGH PAYMENT IN LIEU OF $13453.00.
  
 ADDITIONAL MITIGATION WILL BE REQUIRED IF #15 AND #17
 ARE REMOVED. MITIGATION WILL BE PROVIDED WITH
 ADDITIONAL TREES PER COMMENT #14.
 NOTE THAT THE 3/22/21 SUBMITTAL CONTAINED THE SAME
 LANDSCAPE AND TREE MITIGATION PLANS FROM 12/23/20.
 PLEASE SUBMIT UPDATED PLANS.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 10-05-2020 Cont ID  
Sent By   Date 10-05-2020 Time   Rev Time 0.00
Received By   Date 10-05-2020 Time   Sent To  
Notes
2020-10-05 09:00:21NO FURTHER COMMENTS FROM PUBLIC WORKS.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 12-10-2019 Cont ID  
Sent By   Date 12-10-2019 Time   Rev Time  
Received By   Date 12-10-2019 Time   Sent To  
Notes
2019-12-10 13:18:50 
 PLEASE PROVIDE THE FOLLOWINGS:
 - LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE AND TYPE OF
 THE CONTAINER (I.E. DUMPSTER/COMPACTOR) THAT WILL BE
 UTILIZED THAT WILL BE UTILIZED FOR THE SANITATION
 SERVICE.
 - AUTO TURN FOR THE SANITATION SERVICE, FRONT LOADER
 TRUCK
  * TRUCK LENGTH: 35 FT
  * TRUCK WITH: 11 FT
  * TURNING RADIUS:
  - SAE TURNING RADIUS: 32.5 FT
  - CURB-TO-CURB DIAMETER: 74 FT
  - WALL-TO-WALL DIAMETER: 86.3 FT
 - DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RECYCLING CONTAINERS.
 - FOR A FREESTANDING SITE DUMPSTER ENCLOSURE, THE
 ENCLOSURE SHALL COMPLY WITH THE LATEST REVISION OF CITY
 OF WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE
 ENCLOSURE STANDARD, CG-8.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop STORM STORMWATER
Rev No 4 Status F Date 04-05-2021 Cont ID  
Sent By tward Date 04-05-2021 Time 20:52 Rev Time 0.00
Received By tward Date 04-05-2021 Time 23:31 Sent To  
Notes
2021-04-05 21:41:41THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 3/22/2021 SUBMITTAL PACKAGE.
  
 1. [PARTIALLY SATISFIED] EXPLAIN WHY THE PROPOSED CURB
 LINE AT THE NORTHEAST CORNER OF 2ND STREET AND
 SAPODILLA AVE IS BEING MOVED INTO THE ROAD AND
 NARROWING THE LANE WIDTH. PREVIOUS COMMENT:PROPOSED
 NORTH CURB DOES NOT ALIGN WITH THE EXISTING CURB AT THE
 WEST END OF 2ND STREET. THERE IS ALSO A GAP BETWEEN THE
 START OF THE CURB AND THE BEGINNING OF THE WESTERN
 PARALLEL PARKING AREA.
  
 2. [PARTIALLY SATISFIED] MOVE STRUCTURE S-105 WEST OR
 EAST SO THAT IT IS NOT DIRECTLY SOUTH OF THE MID-BLOCK
 CROSS WALK.PREVIOUS COMMENT: AVOID PLACEMENT OF
 MANHOLES AND OTHER STRUCTURES WITHIN THE SIDEWALK. IF
 UNAVOIDABLE, LOCATE THE STRUCTURES AWAY FROM CROSS
 WALKS WHERE POSSIBLE.
  
 3. [SATISFIED] DRAINAGE AND SANITARY SEWER PIPES AND
 STRUCTURES TO BE LOCATED A MINIMUM DISTANCE OF 3 FEET
 (5 FEET PREFERRED) FROM WATER MAINS.
  
 4. [NOT SATISFIED] SHOW 10' WIDE EASEMENT CENTERED OVER
 THE STORM PIPE. PREVIOUS COMMENT: EASEMENT WILL NEED TO
 BE PROVIDED TO THE CITY FOR THE STORM PIPE BETWEEN
 S-204 AND THE EXISTING CATCH BASIN IF THE DESIGN DOES
 NOT CHANGE.
  
 5. [NOT SATISFIED] WHAT IS THE PURPOSE OF STRUCTURE
 S-201, A TYPE 'D' DBI IN THE PARKWAY OF 3RD STREET?
  
 6. [SATISFIED] WILL CONSTRUCTION EASEMENTS BE NEEDED TO
 INSTALL THE DRAINAGE SYSTEM ALONG THE WEST PROPERTY
 BOUNDARY?
  
 7. [NOT SATISFIED] COMMENT CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL. VERIFY THE HGL BETWEEN
 STRUCTURE CS-1 AND S-101 WILL NOT EXCEED THE RIM
 ELEVATION OF S-101.
  
 8. [SATISFIED] HOW WHERE THE CROSS SECTIONS PROVIDED ON
 SHEET C3.1 ARE TAKEN. LABEL THE PARTICULAR STREET RIGHT
 OF WAY ON EACH SECTION.
  
 9. [NOT SATISFIED] COMMENT CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL. ASSUMING SECTION A IS FOR
 THE WEST PROPERTY LINE NORTH OF THE ALLEY, DIMENSION
 THE HORIZONTAL DISTANCE BETWEEN THE PROPERTY LINE AND
 THE CENTER OF THE 18" STORM PIPE.
  
 10. [NOT SATISFIED] COMMENT CAN BE ADDRESSED DURING
 ENGINEERING PERMIT SUBMITTAL. ASSUMING SECTION B IS FOR
 THE WEST PROPERTY LINE SOUTH OF THE ALLEY,DIMENSION THE
 HORIZONTAL DISTANCE BETWEEN THE PROPERTY LINE AND THE
 CENTER OF THE 18" STORM PIPE.
  
 11. [NOT SATISFIED] ASSUMING SECTION C IS FOR 2ND
 STREET (30' R/W), CREATE A DEPRESSION BETWEEN THE BACK
 OF CURB AND FRONT OF WALK TO CAPTURE THE STORMWATER
 RUNOFF FORM THE SIDEWALK. SHOW WHERE THE EXISTING C&G
 ON THE NORTH SIDE IS LOCATED IN RELATION TO THE NORTH
 R/W LINE.
  
 12. [NOT SATISFIED] PROVIDE A SECTION OF 2ND STREET
 WHERE THERE WILL NOT BE PARKING ON THE NORTH SIDE OF
 THE STREET.
  
 13. [NOT SATISFIED] CAN EXTERIOR SIDEWALK OUTSIDE THE
 LEASING LOBBY BE LOWERED, AN ELEVATED LANDING BE
 CREATED OUTSIDE THE DOORS TO THE LEASING LOBBY AND
 STEPS AND HANDICAP RAMP BE CREATED TO CONNECT THE
 EXTERIOR SIDEWALK TO THE LANDING? PREVIOUS COMMENT:
 ASSUMING SECTION D IS FOR ROSEMARY AVE, CAN THE FFE OF
 22.0 FT NAVD FOR THE LEASING LOBBY AT THE SE CORNER OF
 THE DEVELOPMENT BE LOWERED TO REDUCE THE SIDEWALK
 ELEVATION OF 21.85 FT AND THEREBY FLATTEN THE SLOPE
 BETWEEN THE SIDEWALK AND BACK OF CURB? AS CURRENTLY
 DESIGNED, THIS SLOPE IS AROUND 4:1. THE FFE OF THE REST
 OF THE DEVELOPMENT ALONG ROSEMARY AVE. IS 20.6 FT NAVD.
  
 14. [NOT SATISFIED] CONSIDER USING PERVIOUS PAVERS TO
 REDUCE THE AMOUNT OF STORMWATER RUNOFF.
  
 15. [NOT SATISFIED] ON THE DRAINAGE PLAN, THE VIEWPORT
 SCALE DOES NOT MATCH THE SHEET SCALE. THE DIMENSIONED
 LINES APPEAR TO BE 10% SHORTER USING THE SHEET SCALE.
  
 16. [NOT SATISFIED] ASSUMING SECTION E IS FOR 3RD ST.,
 THE SECTION SHOWS THE R/W AS 25 FEET WIDE AND THE
 SURVEY HAS THE RIGHT OF WAY AT 50 FEET WIDE.
  
 17. [NOT SATISFIED] THE GAP BETWEEN THE LANDSCAPE
 ISLAND AND C&G IS NOT SHOWN. PREVIOUS COMMENT: HOW WILL
 RUNOFF FLOWING INTO THE 3 PARKING SPACES DIRECTLY EAST
 OF THE MIDBLOCK CROSSWALK ON 3RD ST AND INTO THE
 PARKLING SPACES ON 2ND STREET REACH A DRAINAGE
 STRUCTURE?
  
 18. [NOT SATISFIED] ON SECTION E FOR 3RD STREET, THE
 8.0 FEET PARKING SPACE DIMENSION WOULD EXTEND FROM THE
 EDGE OF TRAVEL LANE TO THE FACE OF THE 'D' CURB AND
 WOULD INCLUDE THE 2-FOOT VALLEY GUTTER AND 6 FEET OF
 ASPHALT. THE BACK OF 'D' CURB WOULD BE 3.3 FEET FROM
 THE R/W LINE AND THE LANDSCAPE AREA BETWEEN THE
 SIDEWALK AND 'D' CURB WOULD BE 6.3 FEET WIDE INSTEAD OF
 5 FEET. PREVIOUS COMMENT: ON 3RD STREET, CONSIDER
 SLOPING THE PROPOSED PARKING TOWARD THE STREET AND
 INSTALL VALLEY GUTTER WHERE THE EXISTING TYPE 'F' C&G
 IS LOCATED. TYPE 'D' CURB CAN THEN BE INSTALLED AT THE
 HIGH SIDE OF THE PARKIG SPACE AND DRAINAGE STRUCTURES
 S-201 AND S-203 MAY NOT BE NEEDED.
  
 19. [NOT SATISFIED] PROVIDE SMALL RETENTION AREAS
 BEHIND THE NORTH SIDEWALK OF 2ND STREET BETWEEN STOOPS
 TO REDUCE THE AREA DIRECLTY DRAINING TO THE R/W.
  
 20. [PARTIALLY SATISFIED] PROPOSED GRADES WILL BE
 NEEDED FOR THE DRIVEWAY. THE PROPOSED TRENCH DRAIN AND
 CONNECTION TO THE ONSITE DRAINAGE SYSTEM SHOULD NOT
 ALLOW BYPASS OF THE PERIMETER ELEVATION FOR THE SITE.
 PREVIOUS COMMENT: INDICATE HOW THE PROPOSED DRIVEWAY TO
 SAPODILLA AVE WILL DRAIN.
  
 21. [PARTIALLY SATISFIED] ADA MATS MAY BE NEEDED ON
 EITHER SIDE OF THIS DRIVEWAY AND ON EACH SIDE OF THE
 ENDTRANCE TO THE PARKING GARAGE. PREVIOUS COMMENT: WILL
 CURB RAMPS BE NEEDED ON EITHER SIDE OF THIS DRIVEWAY?
  
 22. PROFILE VIEWS OF ALL PROPOSED STORM PIPES WITHIN
 THE RIGHT OF WAY WILL NEED TO BE PROVIDED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 NEW COMMENTS:
 23. STOP SIGN AND STOP BAR SHOULD BE BEHIND THE
 SIDEWALK FOR THE MIDBLOCK DRIVEWAY TO SAPODILLA AVE.
  
 24. PROPOSED EAST CURB LINE OF SAPODILLA AVE NEAR 3RD
 STREET WILL CREATE TOO NARROW OF A STREET FOR TRAFFIC.
  
 25. CHECK INVERT ELEVATIONS AND SLOPES OF PROPOSED
 SANITARY SEWERS.
  
 26. PIPE SIZES LISTED WITH SEWER INVERTS DO NOT MATCH
 THE PIPE SIZES CALLED OUT FOR THE EXISTING SEWERS ON
 ROSEMARY AVE.
  
 27. CAN THE SPOT GRADES OF 24.50 FEET NAVD AT 5 FEET
 FROM THE SOUTH PROPERTY LINE BE LOWERED TO 24.0 FEET?
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)
  
  
  
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 01-15-2021 Cont ID  
Sent By tward Date 01-15-2021 Time 13:28 Rev Time 0.00
Received By tward Date 01-15-2021 Time 16:34 Sent To  
Notes
2021-01-15 13:43:25THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/23/2020 SUBMITTAL PACKAGE.
  
 1. PROPOSED NORTH CURB DOES NOT ALIGN WITH THE EXISTING
 CURB AT THE WEST END OF 2ND STREET. THERE IS ALSO A GAP
 BETWEEN THE START OF THE CURB AND THE BEGINNING OF THE
 WESTERN PARALLEL PARKING AREA.
  
 2. AVOID PLACEMENT OF MANHOLES AND OTHER STRUCTURES
 WITHIN THE SIDEWALK. IF UNAVOIDABLE, LOCATE THE
 STRUCTURES AWAY FROM CROSS WALKS WHERE POSSIBLE.
  
 3. DRAINAGE AND SANITARY SEWER PIPES AND STRUCTURES TO
 BE LOCATED A MINIMUM DISTANCE OF 3 FEET (5 FEET
 PREFERRED) FROM WATER MAINS.
  
 4. EASEMENT WILL NEED TO BE PROVIDED TO THE CITY FOR
 THE STORM PIPE BETWEEN S-204 AND THE EXISTING CATCH
 BASIN IF THE DESIGN DOES NOT CHANGE.
  
 5. WHAT IS THE PURPOSE OF STRUCTURE S-201, A TYPE 'D'
 DBI IN THE PARKWAY OF 3RD STREET?
  
 6. WILL CONSTRUCTION EASEMENTS BE NEEDED TO INSTALL THE
 DRAINAGE SYSTEM ALONG THE WEST PROPERTY BOUNDARY?
  
 7. VERIFY THE HGL BETWEEN STRUCTURE CS-1 AND S-101 WILL
 NOT EXCEED THE RIM ELEVATION OF S-101.
  
 8. SHOW WHERE THE CROSS SECTIONS PROVIDED ON SHEET C3.1
 ARE TAKEN. LABEL THE PARTICULAR STREET RIGHT OF WAY ON
 EACH SECTION.
  
 9. ASSUMING SECTION A IS FOR THE WEST PROPERTY LINE
 NORTH OF THE ALLEY, DIMENSION THE HORIZONTAL DISTANCE
 BETWEEN THE PROPERTY LINE AND THE CENTER OF THE 18"
 STORM PIPE.
  
 10. ASSUMING SECTION B IS FOR THE WEST PROPERTY LINE
 SOUTH OF THE ALLEY,DIMENSION THE HORIZONTAL DISTANCE
 BETWEEN THE PROPERTY LINE AND THE CENTER OF THE 18"
 STORM PIPE.
  
 11. ASSUMING SECTION C IS FOR 2ND STREET (30' R/W),
 CREATE A DEPRESSION BETWEEN THE BACK OF CURB AND FRONT
 OF WALK TO CAPTURE THE STORMWATER RUNOFF FORM THE
 SIDEWALK. SHOW WHERE THE EXISTING C&G ON THE NORTH SIDE
 IS LOCATED IN RELATION TO THE NORTH R/W LINE.
  
 12. PROVIDE A SECTION OF 2ND STREET WHERE THERE WILL
 NOT BE PARKING ON THE NORTH SIDE OF THE STREET.
  
 13. ASSUMING SECTION D IS FOR ROSEMARY AVE, CAN THE FFE
 OF 22.0 FT NAVD FOR THE LEASING LOBBY AT THE SE CORNER
 OF THE DEVELOPMENT BE LOWERED TO REDUCE THE SIDEWALK
 ELEVATION OF 21.85 FT AND THEREBY FLATTEN THE SLOPE
 BETWEEN THE SIDEWALK AND BACK OF CURB? AS CURRENTLY
 DESIGNED, THIS SLOPE IS AROUND 4:1. THE FFE OF THE REST
 OF THE DEVELOPMENT ALONG ROSEMARY AVE. IS 20.6 FT NAVD.
  
 14. CONSIDER USING PERVIOUS PAVERS TO REDUCE THE AMOUNT
 OF STORMWATER RUNOFF.
  
 15. ON THE DRAINAGE PLAN, THE VIEWPORT SCALE DOES NOT
 MATCH THE SHEET SCALE. THE DIMENSIONED LINES APPEAR TO
 BE 10% SHORTER USING THE SHEET SCALE.
  
 16. ASSUMING SECTION E IS FOR 3RD ST., THE SECTION
 SHOWS THE R/W AS 25 FEET WIDE AND THE SURVEY HAS THE
 RIGHT OF WAY AT 50 FEET WIDE.
  
 17. HOW WILL RUNOFF FLOWING INTO THE 3 PARKING SPACES
 DIRECTLY EAST OF THE MIDBLOCK CROSSWALK ON 3RD ST AND
 INTO THE PARKLING SPACES ON 2ND STREET REACH A DRAINAGE
 STRUCTURE?
  
 18. ON 3RD STREET, CONSIDER SLOPING THE PROPOSED
 PARKING TOWARD THE STREET AND INSTALL VALLEY GUTTER
 WHERE THE EXISTING TYPE 'F' C&G IS LOCATED. TYPE 'D'
 CURB CAN THEN BE INSTALLED AT THE HIGH SIDE OF THE
 PARKIG SPACE AND DRAINAGE STRUCTURES S-201 AND S-203
 MAY NOT BE NEEDED.
  
 19. PROVIDE SMALL RETENTION AREAS BEHIND THE NORTH
 SIDEWALK OF 2ND STREET BETWEEN STOOPS TO REDUCE THE
 AREA DIRECLTY DRAINING TO THE R/W.
  
 20. INDICATE HOW THE PROPOSED DRIVEWAY TO SAPODILLA AVE
 WILL DRAIN.
  
 21. WILL CURB RAMPS BE NEEDED ON EITHER SIDE OF THIS
 DRIVEWAY?
  
 22. PROFILE VIEWS OF ALL PROPOSED STORM PIPES WITHIN
 THE RIGHT OF WAY WILL NEED TO BE PROVIDED WITH THE
 ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120 (O)
 561-351-0510 (M)
 [email protected]
  
  
  
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 11-02-2020 Cont ID  
Sent By tward Date 11-02-2020 Time 22:55 Rev Time 0.00
Received By tward Date 11-02-2020 Time 22:58 Sent To  
Notes
2020-11-02 22:58:48THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 10/2/2020 SUBMITTAL REVIEW PACKAGE:
  
 1. SHOW THE PROPERTY LINES/RIGHT OF WAY LINES.
  
 2. SHOW THE EXISTING IMPROVEMENTS TO THE OPPOSITE RIGHT
 OF WAY LINES.
  
 3. PROVIDE CROSS SECTIONS FROM ROAD CENTERLINE TO FACE
 OF BUILDING. LABEL STREET RIGHT OF WAY LINE, AND
 HORIZONTAL DIMENSIONS FOR TRAVEL LANE, EDGE OF
 PAVEMENT, RIGHT OF WAY, SIDEWALK WIDTH, LANDSCAPE WIDTH
 AND BUILDING SETBACK FROM PROPERTY LINE.
  
 4. PROVIDE CROSS SECTIONS FOR WEST PROPERTY LINE (NORTH
 AND SOUTH OF ALLEY) SHOWING PERIMETER BERM (IF
 REQUIRED) OR SWALE TO PREVENT DIRECT RUNOFF TO ADJACENT
 PROPERTY, AND BUILDING OFFSET DIMENSION.
  
 5. BULBOUTS ALONG 2ND STREET APPEAR TO TRAP WATER ALONG
 THE CURB AND GUTTER.
  
 6. CONSIDER CONNECTING S-203 TO EXISTING CURB INLET TO
 THE NORTHWEST OF STRUCTURE INSTEAD OF S-204.
  
 7. ENGINEERING PERMIT SUBMITTAL TO INCLUDE CHANGE IN
 HGL FOR 3RD STREET AND ROSEMARY AVE. DRAINAGE SYSTEMS.
  
 8. PROVIDE CONVERSION EQUATION BETWEEN NAVD1988 AND
 NGVD1929 ON ALL SHEETS WITH ELEVATION INFORMATION.
  
 9. PROVIDE CONVERSION EQUATION BETWEEN NAVD1988 AND
 CITY DATUM OF NGVD1929 ON THE SURVEY.
  
 10. SABAL PALMS PROPOSED OVER PROPOSED STORM PIPE ALONG
 WEST PROPERTY LINE.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120 (O)
 561-351-0510 (M)

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-10-2019 Cont ID  
Sent By tward Date 12-10-2019 Time 14:13 Rev Time 0.00
Received By tward Date 12-10-2019 Time 14:17 Sent To  
Notes
2019-12-10 14:15:07THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTPS://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FO
 RMS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. PER ITEM NO. 2 ON THE ENGINEERING PLANS CHECKLIST,
 PROVIDE THE CONVERSTION EQUATION TO THE CITY'S VERTICAL
 DATUM (NGVD1929) ON THE SURVEY AND ENGINEERING PLANS.
  
 2. LABEL THE VERTICAL DATUM ON THE TREE DISPOSITION
 PLAN AND PROVIDE THE CONVERSION EQUATION TO NGVD1929.
  
 3. SHOW THE EXISTING DRAINAGE SYSTEM ON 2ND ST. AND
 SAPODILLA AVE.
  
 4. SHOW THE UTILITIES ON THE LANDSCAPE PLANS.
  
 5. PROVIDE SURVEY OF THE INTERSECTIONS OF SAPODILLA AVE
 WITH 2ND STREET AND 3RD STREET.
  
 6. DRAINAGE SYSTEM TO BE DESIGNED TO SFWMD CRITERIA FOR
 WATER QUALITY AND PEAK DISCHARGE LIMITATIONS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING
 CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 10-16-2020 Cont ID  
Sent By vnoel Date 10-16-2020 Time 10:48 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-10-16 10:48:401. NEED TO CLEARLY DELINEATE R/W LINES ON ENGINEERING
 PLANS NOW, NOT AT FINAL.
 2. SIDEWALK/ACCESS/UTILITY EASEMENTS WILL BE REQUIRED
 BY PLAT. PREVIOUS PLATTING REQUIREMENT REMAINS.
 3. RELOCATE STORM MH IN SE CORNER OUT OF PAVER AREA.
 4. IT APPEARS THAT EXFILTRATION TRENCHES AND MANHOLES
 WILL BE LOCATED IN/UNDER PORTIONS OF THE SIDEWALK THAT
 FALLS ON PRIVATE PROPERTY. IF THAT IS THE CASE, CITY
 WILL NOT BE RESPONSIBLE FOR MAINTENANCE OF THE
 SIDEWALK.
 5. APPROVAL OF ALLEY ABANDONMENT WILL BE REQUIRED PRIOR
 TO SITE PLAN APPROVAL.
 6. VERTICAL DATUM AND CONVERSION NOT SHOWN ON PLANS.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-10-2019 Cont ID  
Sent By vnoel Date 12-10-2019 Time 10:20 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2019-12-10 10:56:211. ALLEY WILL NEED TO BE ABANDONED. HAS APPLICANT
 DISCUSSED WITH OWNER OF SW CORNER LOT?
 2. REPLAT WILL BE REQUIRED AND THE UNITY OF TITLE IN
 ORB 30891/307 TERMINATED. SURVEY SHOULD REFLECT
 PROPERTY SUBJECT TO UNITY OF TITLE.
 3. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR ALL
 IMPROVEMENTS WITHIN ADJACENT RIGHT-OF-WAYS.
 4. EXISTING SANITARY SEWER WITHIN ALLEY WILL NEED TO BE
 RELOCATED.
 5. ADD CONVERSION FACTOR TO NGVD-29 ON SURVEY AND
 ENGINEERING PLANS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 5 Status F Date 03-30-2021 Cont ID  
Sent By   Date 03-30-2021 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2021-03-30 19:57:25TRAFFIC STUDY COMMENTS:
 1. SATISFIED. QUEUE LENGTHS AND AVAILABLE STORAGE
 SUMMARY TABLE WAS NOT INCLUDED IN THE REPORT. PLEASE
 IDENTIFY TABLE NUMBER AND/OR REPORT PAGE SHOWCASING IT.
 1A. NOTE: TRAFFIC STUDY SHOWS SIGNIFICANT QUEUING FOR
 THE EASTBOUND-LEFT AND SOUTHBOUND-RIGHT TURNING
 MOVEMENTS AT THE BANYAN BLVD AND ROSEMARY AVE
 INTERSECTION. APPLICANT TO DISCUSS WITH CITY AND ADOPT
 TDM STRATEGIES TO MITIGATE TRAFFIC CONGESTION.
  
 SITE PLAN COMMENTS:
 2. PARTIALLY SATISFIED. PROVIDE AUTOTURN PATH FOR
 SERVICE AND DELIVERY VEHICLES. THE CITY CODE PROHIBITS
 VEHICLES FROM BACKING INTO AND OUT OF PUBLIC
 RIGHT-OF-WAY. SHEET EX-1 WAS NOT IN THE SUBMITTED
 MATERIAL. PLEASE CLARIFY.
 2A. PROVIDE DESIGN VEHICLES' MODEL DIMENSIONS
 2B. PROVIDE ANALYSIS SHOWCASING VEHICLE'S DYNAMIC
 ENVELOPE. VEHICLE PATH LINES SHOULD BE COLORED OR
 DIFFERENT WEIGHT/PATTERN FROM SURROUNDING FEATURES
 2C. PROVIDE SEPARATE OUTPUT FOR EACH VEHICLE MANEUVER
 (I.E. MANEUVER IN AND OUT)
 3. PARTIALLY SATISFIED. PROVIDE TURNAROUND SPACE AT THE
 DEAD-END ON THE 5TH FLOOR OR TOP FLOOR OF THE PARKING
 GARAGE PER CITY CODE REQUIREMENT. AUTOTURN ANALYSIS
 NEEDED TO VERIFY AND VALIDATE. SHEET A-2.6 SHOWS
 VEHICLE'S DYNAMIC ENVELOPE ENCROACHMENT WITH PARKING
 SPACE NUMBER 391. PLEASE REMOVE THE AFFECTED PARKING
 STALL AND UPDATE FINAL SITE PLAN ACCORDINGLY.
 3A. RESUBMISSION SHOWS QUESTIONABLE VEHICLE?S POSITION
 WITH RESPECT TO ITS TRAJECTORY. PLEASE REVISE ACCORDING
 TO PREVIOUS COMMENT GUIDELINES.
 4. NOT SATISFIED. CONSIDER RELOCATING THE MIDBLOCK
 CROSSWALK ON 3RD STREET TO ALIGN WITH PROPOSED
 DEVELOPMENT WALKWAY. PROVIDE SUPPORTING DOCUMENTATION
 SHOWCASING APPLICABLE SAFETY AND VISIBILITY
 REQUIREMENTS DISQUALIFYING SUCH RELOCATION. LATEST
 COMMENT SET SHOWS: "BIZI". PLEASE CLARIFY.
 4A. APPLICANT HAS NOT DISCUSSED WITH THE CITY
 5. NOT SATISFIED. COORDINATE WITH CITY STAFF FOR
 FURTHER TDM STRATEGIES. PLEASE PROVIDE ACKNOWLEDGEMENT
 OF SUCH ITEM OR LIST OF AGREED TDM STRATEGIES.
 5A. APPLICANT HAS NOT DISCUSSED WITH THE CITY
 6. PARTIALLY SATISFIED. MINIMUM TRAVEL LANE WIDTH IS 9
 FEET, NOT INCLUDING GUTTER. PLEASE REVISE SITE PLAN TO
 SHOWCASE WIDTH OF GUTTER AND TRAVEL LANES SEPARATELY ON
 2ND AND 3RD ST
 6A. PROVIDE TRAVEL LANE DIMENSIONS EXCLUDING CURB AND
 GUTTER. NOTE: MINIMUM ROADWAY WIDTH ALONG 2ND ST SHOULD
 BE 12 FEET PER CITY CODE SEC. 94-485 FIGURE XV-2 AND
 PARALLEL PARKING STALL MANEUVERABILITY REQUIREMENTS.
 6B. NO DIMENSIONS PROVIDED FOR 3RD ST. PLEASE REVISE.
 NOTE: ACCORDING TO FDOT GREENBOOK STANDARDS, THE
 MINIMUM WIDTH OF A TWO-WAY RESIDENTIAL ROADWAY SHOULD
 BE 20 FEET FROM EDGE-OF-PAVEMENT TO EDGE-OF-PAVEMENT
 (EXCLUDING CURBS AND GUTTERS).
 NOTED COMMENTS:
 - EASEMENT WILL BE REQUIRED FOR THE PORTION OF SIDEWALK
 OUTSIDE PUBLIC RIGHT-OF-WAY.
 - ALLEY ABANDONMENT SHOULD COMPLY WITH CITY CODE SEC.
 94-112, INCLUDE THE APPLICABLE ADDITIONAL OPEN SPACE
 REQUIREMENT. DEAD-END ALLEY IS PROHIBITED. PROVIDE
 RESULT OF THE ALLY ABANDONMENT APPLICATION ONCE
 COMPLETED.
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status F Date 01-05-2021 Cont ID  
Sent By   Date 01-05-2021 Time   Rev Time 0.00
Received By   Date 12-23-2020 Time   Sent To  
Notes
2021-01-05 15:08:37TRAFFIC STUDY COMMENTS:
 1. QUEUE LENGTHS AND AVAILABLE STORAGE SUMMARY TABLE
 WAS NOT INCLUDED IN THE REPORT. PLEASE IDENTIFY TABLE
 NUMBER AND/OR REPORT PAGE SHOWCASING IT.
  
 SITE PLAN COMMENTS:
 2. PROVIDE AUTOTURN PATH FOR SERVICE AND DELIVERY
 VEHICLES. THE CITY CODE PROHIBITS VEHICLES FROM BACKING
 INTO AND OUT OF PUBLIC RIGHT-OF-WAY. SHEET EX-1 WAS NOT
 IN THE SUBMITTED MATERIAL. PLEASE CLARIFY.
 3. PROVIDE TURNAROUND SPACE AT THE DEAD-END ON THE 5TH
 FLOOR OR TOP FLOOR OF THE PARKING GARAGE PER CITY CODE
 REQUIREMENT. AUTOTURN ANALYSIS NEEDED TO VERIFY AND
 VALIDATE. SHEET A-2.6 SHOWS VEHICLE?S DYNAMIC ENVELOPE
 ENCROACHMENT WITH PARKING SPACE NUMBER 391. PLEASE
 REMOVE THE AFFECTED PARKING STALL AND UPDATE FINAL SITE
 PLAN ACCORDINGLY.
 4. CONSIDER RELOCATING THE MIDBLOCK CROSSWALK ON 3RD
 STREET TO ALIGN WITH PROPOSED DEVELOPMENT WALKWAY.
 PROVIDE SUPPORTING DOCUMENTATION SHOWCASING APPLICABLE
 SAFETY AND VISIBILITY REQUIREMENTS DISQUALIFYING SUCH
 RELOCATION. LATEST COMMENT SET SHOWS: ?BIZI?. PLEASE
 CLARIFY.
 5. COORDINATE WITH CITY STAFF FOR FURTHER TDM
 STRATEGIES. PLEASE PROVIDE ACKNOWLEDGEMENT OF SUCH ITEM
 OR LIST OF AGREED TDM STRATEGIES.
 6. MINIMUM TRAVEL LANE WIDTH IS 9?, NOT INCLUDING
 GUTTER. PLEASE REVISE SITE PLAN TO SHOWCASE GUTTER AND
 TRAVEL LANES? WIDTH SEPARATELY ON 2ND AND 3RD ST
  
  
 NOTED COMMENTS:
 A) EASEMENT WILL BE REQUIRED FOR THE PORTION OF
 SIDEWALK OUTSIDE PUBLIC RIGHT-OF-WAY.
 B) ALLEY ABANDONMENT SHOULD COMPLY WITH CITY CODE SEC.
 94-112, INCLUDE THE APPLICABLE ADDITIONAL OPEN SPACE
 REQUIREMENT. DEAD-END ALLEY IS PROHIBITED. PROVIDE
 RESULT OF THE ALLY ABANDONMENT APPLICATION ONCE
 COMPLETED.
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date 12-14-2020 Cont ID  
Sent By   Date 12-14-2020 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-12-14 19:58:32TRAFFIC STUDY COMMENTS:
 1. BANYAN/ROSEMARY SYNCHRO ANALYSIS:
 1A. PLEASE CLARIFY WHY THE FUTURE SCENARIO HAS OVERALL
 LESS DELAY THAN THE BACKGROUND ONE, AS SHOWN IN TABLE 3
 AND 4, RESPECTIVELY
 1B. PLEASE PROVIDE SYNCHRO OUTPUT SHOWCASING QUEUE
 STORAGE LENGTH SETTING/ASSUMPTIOS
 1C. BACKGROUND AND FUTURE SCENARIO NETWORK SHALL BE
 CODED ACCORDING TO THE ON-GOING BANYAN BOULEVARD
 STREETSCAPE PROJECT?S ROADWAY PLANS. THE CITY CAN
 PROVIDE SUCH PLANS.
  
 SITE PLAN COMMENTS:
 2. PROVIDE AUTOTURN PATH FOR SERVICE AND DELIVERY
 VEHICLES. THE CITY CODE PROHIBITS VEHICLES FROM BACKING
 INTO AND OUT OF PUBLIC RIGHT-OF-WAY. THE ITEM WAS NOT
 PROVIDED TO THE TRAFFIC ENGINEER.
 3. PROVIDE TURNAROUND SPACE AT THE DEAD-END ON THE 5TH
 FLOOR OR TOP FLOOR OF THE PARKING GARAGE PER CITY CODE
 REQUIREMENT. AUTOTURN ANALYSIS NEEDED TO VERIFY AND
 VALIDATE. PLEASE PROVIDE REFERENCE SHEET NAME/NUMBER,
 AS THE LATEST SUBMISSION DOES NOT SHOWCASE ANY REVISION
 ON THE MATTER.
 4. REDUCE WIDTH OF THE ONE-WAY DRIVEWAY TO 12 FEET.
 PROVIDE DIMENSIONS FOR DRIVING ISLES, DRIVEWAYS AND
 PARKING STALLS. IF ALREADY PRESENTED, PLEASE PROVIDE
 REFERENCE SHEET NUMBER. LATEST SUBMISSION DOES NOT
 PROVIDE THE REQUESTED REVISIONS IN SHEET SP-1.
 5. CONSIDER RELOCATING THE MIDBLOCK CROSSWALK ON 3RD
 STREET TO ALIGN WITH PROPOSED DEVELOPMENT WALKWAY.
 PROVIDE SUPPORTING DOCUMENTATION SHOWCASING APPLICABLE
 SAFETY AND VISIBILITY REQUIREMENTS DISQUALIFYING SUCH
 RELOCATION.
 6. PROVIDE A MICRO-MOBILITY AREA WITH THE FOLLOWING
 CHARACTERISTICS:
 6A. 8? X 20? DIMENSIONS
 6B. LOCATED NEAR AN ENTRANCE AND ACCESSIBLE TO THE
 PUBLIC
 6C. PROVIDE A CONDUIT (2" SCHEDULE 40 PVC) TO THE POWER
 SOURCE WITH AN ELECTRICAL PULL BOX (240V CIRCUIT)
 7. COORDINATE WITH CITY STAFF FOR FURTHER TDM
 STRATEGIES
  
 NOTED COMMENTS:
 - EASEMENT WILL BE REQUIRED FOR THE PORTION OF SIDEWALK
 OUTSIDE PUBLIC RIGHT-OF-WAY.
 - PROVIDE DETAILS ON THE ALLEY ABANDONMENT. ALLEY
 ABANDONMENT SHOULD COMPLY WITH CITY CODE SEC. 94-112,
 INCLUDE THE APPLICABLE ADDITIONAL OPEN SPACE
 REQUIREMENT. DEAD-END ALLEY IS PROHIBITED.
  
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date 10-09-2020 Cont ID  
Sent By   Date 10-28-2020 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-10-09 12:09:20TRAFFIC STUDY COMMENTS:
 1. PROVIDE COUNTY TPS LETTER.
 2. PROVIDE INTERSECTION ANALYSIS FOR THE FOLLOWING:
 A. BANYAN AND SAPODILLA
 B. BANYAN AND ROSEMARY
 C. 3RD AND QUADRILLE
 D. 3RD AND ROSEMARY
  
 SITE PLAN COMMENTS:
 1. PROVIDE BICYCLE RACKS NEARBY MAIN ENTRANCES AND/OR
 COMMERCIAL SITE(S). RECORD THE PROVIDED NUMBER OF
 SPACES/RACKS IN THE DATA TABLE.
 2. PROVIDE AUTOTURN PATH FOR SERVICE AND DELIVERY
 VEHICLES. THE CITY CODE PROHIBITS VEHICLES FROM BACKING
 INTO AND OUT OF PUBLIC RIGHT-OF-WAY.
 3. PROVIDE TURNAROUND SPACE AT THE DEAD-END ON THE 5TH
 FLOOR OR TOP FLOOR OF THE PARKING GARAGE PER CITY CODE
 REQUIREMENT. LATEST SUBMISSION DOES NOT CLEARLY SHOW
 THE BACK OUT SPACE. AUTOTURN ANALYSIS NEEDED TO VERIFY
 AND VALIDATE.
 4. REDUCE WIDTH OF THE ONE-WAY DRIVEWAY TO 12 FEET.
 PROVIDE DIMENSIONS FOR DRIVING ISLES, DRIVEWAYS AND
 PARKING STALLS. IF ALREADY PRESENTED, PLEASE PROVIDE
 REFERENCE SHEET NUMBER.
 5. PROVIDE PARKING DATA TABLE ON SITE PLAN
 6. EASEMENT WILL BE REQUIRED FOR THE PORTION OF
 SIDEWALK OUTSIDE PUBLIC RIGHT-OF-WAY.
 7. PROVIDE DETAILS ON THE ALLEY ABANDONMENT. ALLEY
 ABANDONMENT SHOULD COMPLY WITH CITY CODE SEC. 94-112,
 INCLUDE THE APPLICABLE ADDITIONAL OPEN SPACE
 REQUIREMENT. DEAD-END ALLEY IS PROHIBITED.
 8. CONSIDER RELOCATING THE MIDBLOCK CROSSWALK ON 3RD
 STREET TO ALIGN WITH PROPOSED DEVELOPMENT WALKWAY.
 9. IMPLEMENT THE FOLLOWING TRANSPORTATION DEMAND
 MANAGEMENT (TDM) MEASURES TO BE CONSISTENT WITH THE
 CITY?S COMPREHENSIVE PLAN:
 A. UNBUNDLE PARKING FROM RESIDENTS? LEASES.
 B. PROVIDE SUBSIDIZED TRI-RAIL PASS, PALM TRAN BUS PASS
 OR SUBSIDIZED MICRO-MOBILITY SERVICE TO RESIDENTS.
  
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  
 VALERIO ORICCHIO
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 01-17-2020 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2020-01-17 16:23:14TRAFFIC STUDY COMMENTS:
 1. PROVIDE COUNTY TPS LETTER.
 2. PROVIDE TRAFFIC CIRCULATION STUDY.
 3. COORDINATE WITH ENGINEERING ON THE STUDY
 INTERSECTION REQUIREMENT.
  
  
 SITE PLAN COMMENTS:
 1. INCLUDE THE REQUIRED AND PROVIDED BICYCLE PARKING IN
 THE SITE DATA TABLE.
 2. PROVIDE BICYCLE PARKING SPACES FOR PUBLIC USE. THESE
 BICYCLE PARKING SPACES SHOULD BE DISTRIBUTED ALONG SITE
 FRONTAGE.
 3. INCLUDE THE REQUIRED AND PROPOSED LOADING SPACE IN
 THE SITE DATA TABLE.
 4. PROVIDE AUTOTURN PATH FOR SERVICE AND DELIVERY
 VEHICLES. THE CITY CODE PROHIBITS VEHICLES FROM BACKING
 INTO AND OUT OF PUBLIC RIGHT-OF-WAY.
 5. PROVIDE TURNAROUND SPACE AT THE DEAD-END ON THE 5TH
 FLOOR OF THE PARKING GARAGE PER CITY CODE REQUIREMENT.
 6. REDUCE WIDTH OF ONE-WAY DRIVEWAY TO 12 FEET.
 7. DRIVEWAYS SHOULD MAINTAIN THE SIDEWALK ELEVATION.
 8. EASEMENT WILL BE REQUIRED FOR THE PORTION OF
 SIDEWALK OUTSIDE PUBLIC RIGHT-OF-WAY.
 9. THE INTERNAL DROP-OFF AREA IS NOT WIDE ENOUGH TO
 ALLOW CARS TO BYPASS. PLEASE VERIFY AND REVISE.
 10. PROVIDE DETAILS ON THE ALLEY ABANDONMENT. ALLEY
 ABANDONMENT SHOULD COMPLY WITH CITY CODE SEC. 94-112,
 INCLUDE THE APPLICABLE ADDITIONAL OPEN SPACE
 REQUIREMENT. DEAD-END ALLEY IS PROHIBITED.
 11. CONVERT 2ND STREET BETWEEN SAPODILLA AVENUE AND
 ROSEMARY AVENUE TO TWO-WAY STREET.
 12. RELOCATE THE MIDBLOCK CROSSWALK ON 3RD STREET TO
 THE LOCATION OF THE PUBLIC PLAZA, AND PROVIDE RAISED
 CROSSWALK WITH CURB EXTENSION ON BOTH SIDES OF THE
 CROSSWALK.
 13. IMPLEMENT THE FOLLOWING TRANSPORTATION DEMAND
 MANAGEMENT (TDM) MEASURES TO BE CONSISTENT WITH THE
 CITY?S COMPREHENSIVE PLAN:
 A. UNBUNDLE PARKING FROM RESIDENTS? LEASES.
 B. PROVIDE SUBSIDIZED TRI-RAIL PASS, PALM TRAN BUS PASS
 OR SUBSIDIZED MICRO-MOBILITY SERVICE TO RESIDENTS.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)
  

Review Stop Z ZONING
Rev No 4 Status F Date 03-30-2021 Cont ID  
Sent By aaponte Date 03-30-2021 Time 16:37 Rev Time 0.00
Received By aaponte Date 03-22-2021 Time 10:35 Sent To  
Notes
2021-03-30 13:24:38COMMENTS TO THE 11-23-20 RESUBMITTAL
 1. SATISFIED-
 2. SATISFIED.
 3. SATISFIED.
 4. PARTIALLY SATISFIED. THE SECTION INDICATES A TRAVEL
 LANE ON 2ND AS 10 FEET BUT INCLUDING THE GUTTER.
 FURTHER DISCUSSSION WITH ENGINEERING STAFF NEEDED TO
 DETERMINE IF THAT IS ACCEPTABLE.PREVIOUS COMMENT:THE
 TRAVEL LANE ON 2ND STREET IS SHOWN AS 9 FEET IN WITH
 DUE TO THE PROPOSED ON-STREET PARKING. FURTHER
 DISCUSSION WITH TRAFFIC ENGINEER IS NEEDED TO DETERMINE
 IF THAT WIDTH IS ADEQUATE OR ADJUSTMENT ARE NEEDED.
 PREVIOUS COMMENT: WHAT IS THE WIDTH OF THE TRAVEL LANES
 ON 2ND STREET? IS IT CHANGE FROM CURRENT?
 5. SATISFIED. PLEASE MODIFY TO FOLLOW THE ANGLE OF THE
 CURB OR PEOPLE WILL DESTROY THE LANDSCAPE FOLLOWING THE
 EASIER PATH OF TRAVEL. PREVIOUS COMMENT: SIDEWALK ON
 EAST SIDE OF 3RD STREET SHALL FOLLOW THE CURB
 ALIGNMENT.
 6. SATISFIED. PLEASE UPDATE SHEET A-03 TO REFLECT
 CHANGES ALONG ROSEMARY. PREVIOUS COMMENT: PROPOSED
 ON-STREET PARKING ALONG ROSEMARY WILL NOT BE POSSIBLE,
 PLEASE REMOVE PROPOSED STRIPING.
 7. NOT SATISFIED. THE SECTIONS PROVIDED INDICATE A
 POSSIBLE PROBLEM OF ELEVATION ON 2ND STREET AND
 ROSEMARY AVENUE. THE CROSS SLOPE INDICATED ON THE
 PLANTING AREA ALONG ROSEMARY AVENUE WILL CREATE A
 PROBLEMATIC RELATIONSHIP BETWEEN THE SIDEWALK AND THE
 STREET. FURTHER DISCUSSION WITH STAFF IS NEEDED TO
 SOLVE THE ISSUE.- PREVIOUS COMMENT:PLEASE PREPARE SOME
 CROSS SECTIONS FOR 2ND STREET AND 3RD STREET.
 8. SATISFIED. PLEASE JUSTIFY WHY THE FDC ON 2ND STREET
 CANNOT BE WALL MOUNTED. IF IT CANNOT BE WALL MOUNTED IT
 SHALL BE INSTALLED WITHIN THE LANDSCAPE AREA AND NOT ON
 THE SIDEWALK. PREVIOUS COMMENT: IF POSSIBLE FDC SHALL
 BE WALL MOUNTED.
 9. NOT SATISFIED. IT SEEMS ALL THE ABOVE GROUND AND
 WATER AND IRRIGATION METERS ARE NOW LOCATED ALONG THE
 GARAGE FRONTAGE ON 2ND AND WITHIN THE MINIMUM SETBACK,
 SUBSTANTIALLY REDUCING THE AREA FOR LANDSCAPING. PLEASE
 CLARIFY HOW THE UTILITIES ARE LOCATED. CAN THE
 CONNECTIONS BE LOCATED ON THE WEST SIDE OF THE GARAGE?
 PREVIOUS COMMENT: PLEASE COORDINATE WITH ENGINEERING
 FOR THE LOCATION OF THE DCDA. VALVE SHALL BE LOCATED
 BEHIND THE MINIMUM SETBACK AND SCREENED WITH LANDSCAPE.
 PREVIOUS COMMENT: DCDA INDICATED ON 2ND STREET EAST OF
 THE PARKING GARAGE IS LISTED TO BE LOCATED UNDERGROUND.
 VAULT WILL NOT BE PERMITTED BY THE PUBLIC UTILITIES
 DEPARTMENT. NEW DCDA LOCATION SHALL BE BEHIND THE
 MINIMUM SETBACK AND SCREENED WITH LANDSCAPE.
 10. SATISFIED. PROPOSED EXFILTRATION TRENCH WILL
 CONFLICT WITH THE REQUIRED STRUCTURAL SOIL FOR THE
 STREET TREE. PLEASE DISCUSS WITH LANDSCAPE PLANNER IF
 THE CONTINUOUS PLANTING AREA WILL BE SUFFICIENT FOR
 TREES AND THERE IS NO NEED FOR STRUCTURAL SOIL.
 11. SATISFIED. PLEASE CORRECT THE MAXIMUM BUILDING
 FOOTPRINT TABLE TO ACCURATELY REFLECT THE REQUIREMENT
 FOR PROPERTIES LARGER THAN 80,000SF.
 12. PARTIALLY SATISFIED CALCULATION FOR 60% ACTIVE USE
 REQUIREMENT NOT ACCURATELY SHOWN. ACTIVE USE % IS BASED
 ON THE BUILDABLE LOT FRONTAGE.-PREVIOUS COMMENT: BIKE
 STORAGE ALONG 2ND STREET CANNOT BE COUNTED AS ACTIVE
 USE. PLEASE REMOVE FROM CALCULATION. THE STREET
 FRONTAGE IS CALCULATED DISCOUNTING THE MINIMUM
 SETBACKS. PREVIOUS COMMENT: PLEASE PROVIDE A GRAPHIC TO
 CONFIRM COMPLIANCE WITH ACTIVE USE REQUIREMENT AS
 LISTED IN TABLE WITHIN SHEET A-01.
 13. SATISFIED. APPLICANT SUBMITTED FOR A VARIANCE
 REQUEST. PREVIOUS COMMENT: CODE REQUIRES AN AVERAGE
 UNIT SIZE OF 800SF. PROJECT PROPOSED AVERAGE UNIT SIZE
 OF 765SF. A VARIANCE WILL BE NECESSARY IF NOT ADJUSTED
 TO MEET REQUIREMENT.
 14. SATISFIED. ON THE 2ND FLOOR, THE AREA LISTED AS
 OPEN TO BELOW CAN BE DISCOUNTED FORM THE GBA
 CALCULATIONS. PREVIOUS COMMENT: THE SQUARE FOOTAGE
 TABLE LISTS TRASH WITHIN THE NON-LEASABLE AREA. THE
 TRASH CHUTE CAN BE EXCLUDED FROM GBA BUT THE ROOM WHERE
 THE TRASH CHUTE IS LOCATED WITHIN EACH FLOOR SHALL BE
 COUNTED AS GBA.
 15. SATISFIED. PLEASE ADJUST THE TRANSPARENCY
 CALCULATION GRAPHIC IN SHEET A-03 TO INDICATE THE 10
 FEET MARK AND CONFIRM THE CALCULATION IS BASED ON THAT
 DIMENSION. TRANSPARENCY IS ONLY REQUIRED FOR
 NON-RESIDENTIAL ACTIVE USES (LOBBY AND COMMERCIAL
 SPACE).
 16. SATISFIED. PLEASE PROVIDE GRAPHIC INFORMATION TO
 CONFIRM COMPLIANCE WITH PLANAR BREAK, HORIZONTAL
 PROJECTIONS AND ARCHITECTURAL TREATMENT FOR FACADES
 ENCLOSING NON-ACTIVE USES (GARAGE). PREVIOUS COMMENT:
 PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE WITH
 ALL THE ELEMENTS REQUIRED BY TABLE IV-4 FACADE
 ARTICULATION REQUIREMENTS.
 17. SATISFIED. PLEASE INCORPORATE THE CONDITIONS OF
 APPROVAL FROM THE HPB REVIEW AND REDESIGN THE WEST AND
 SOUTH PARKING GARAGE FACADES. PREVIOUS COMMENTS:
 FURTHER STUDY IS NECESSARY FOR THE WEST ELEVATION AS IT
 WILL BE HIGHLY VISIBLE FROM THE NEIGHBORHOOD. THE
 PARKING GARAGE FACADES NEED ADDITIONAL WORK TO COMPLY
 WITH THE REQUIREMENT FOR ARCHITECTURAL TREATMENT OF
 NON-ACTIVE USES. THE WEST STAIR CAN INCORPORATE SOME
 WINDOWS OR TREATMENT TO IMPROVE THE FACADE. THE PARKING
 GARAGE NORTH ELEVATION WILL BE ALSO VISIBLE AND NEED
 SOME IMPROVEMENTS.
 18. SATISFIED. PLEASE INDICATE THE MINIMUM REQUIRED
 GROUND SETBACK ON ALL FLOOR PLANS AND THE CONDITIONAL
 SETBACK LINE ON EACH OF THE REQUIRED LEVELS. ALSO
 CLEARLY INCLUDE THE PROPERTY LINE IN ALL DRAWINGS,
 INCLUDING CIVILS AND LANDSCAPE.
 19. SATISFIED. IN SHEET A-02 PLEASE REFER TO MAXIMUM
 PROPOSED GBA, NOT FAR.
 20. PARTIALLY SATISFIED. FENESTRATION TO COVER A
 MINIMUM OF 15% OF THE TOWNHOUSE EAST FACADE SHALL BE
 PROVIDED. PREVIOUS COMMENT:EASTERN MOST TOWN HOUSE UNIT
 SHALL BE SETBACK FOR THE SIDE INTERIOR PROPERTY LINE A
 MINIMUM OF 10 FEET. PREVIOUS COMMENT: PLEASE PROVIDE A
 SIDE INTERIOR SETBACK FOR THE EAST PROPERTY LINE.
 21. SATISFIED. PLEASE LIST THE TOTAL NUMBER OF PARKING
 SPACES REQUIRED BY CODE, AND THE TOTAL NUMBER OF BIKE
 SPACES REQUIRED BY CODE (WITHIN THE BUILDING FOR
 BUILDING TENANTS AT 1/15 PARKING SPACES, AND ALONG THE
 STREET FRONTAGE 1/100 LINEAR FEET OF FRONTAGE). THE
 TABLE LISTING THE REQUIRED PARKING BY CODE IS NOT
 ACCURATE. PLEASE USE PROVISIONS IN SEC 94-111 OF THE
 ZLDRS.
 22. SATISFIED.
 23. SATISFIED. WHAT IS THE BACK OUT SPACE AT THE GROUND
 LEVEL PARKING GARAGE?
 24. SATISFIED. PLEASE CHECK THE LABELING OF THE FACADES
 AS THEY ARE NOT ACCURATE. PREVIOUS COMMENT: PLEASE
 LOCATE THE EXISTING STRUCTURES WITHIN THE BLOCK THAT
 ARE NOT PART OF THE PROJECT FOR REFERENCE.
 25. SATISFIED. STAFF WOULD LIKE TO DISCUSS THE ARCADE
 REMOVAL IN RELATION TO POSSIBLE FUTURE TENANTS.
 PREVIOUS COMMENT: STAFF WOULD LIKE TO DISCUSS THE
 POSSIBLE RE-DESIGN OF THE RETAIL SPACE ALONG ROSEMARY
 AVENUE. ARCADES DO NOT HAVE A RECORD OF SUCCESS FOR
 COMMERCIAL SPACES.
 26. SATISFIED. PLEASE REVISE ELEVATIONS TO REFLECT THE
 CHANGE TO SWING DOOR FOR RESIDENTIAL WALK UP UNITS.
 PREVIOUS COMMENT: WALK UP UNIT DOORS SHALL BE DESIGNED
 LIKE FRONT DOORS AND NOT SLIDERS.
 27. SATISFIED. THE GARAGE ELEVATION NEEDS ENHANCEMENT
 TO COMPLY WITH THE PROVISION OF ARCHITECTURAL TREATMENT
 FOR NON-ACTIVE USES. ENHANCED DESIGN MAY INCORPORATE
 SOME OF THE CONDITIONS OF APPROVAL FROM THE HPB BOARD.
 PREVIOUS COMMENT: GARAGE HAS BIG BLANK WALL ALONG 2ND
 STREET. OPTION COULD BE TO MOVE THE BIKE STORAGE THERE.
 28. SATISFIED. THE GARAGE ELEVATION NEEDS ENHANCEMENT
 TO COMPLY WITH THE PROVISION OF ARCHITECTURAL TREATMENT
 FOR NON-ACTIVE USES. ENHANCED DESIGN MAY INCORPORATE
 SOME OF THE CONDITIONS OF APPROVAL FROM THE HPB BOARD.
 PREVIOUS COMMENT: GARAGE ELEVATION ALONG 2ND STREET
 SHALL INCLUDE ARCHITECTURAL TREATMENT.
 28A SATISFIED. STAFF RECOMMENDS THE SECONDARY ENTRANCE
 ON 2ND STREET TO BE HIGHLIGHTED TO BREAK THE CONTINUITY
 OF THE RESIDENTIAL UNITS.
 29. SATISFIED. ADDITIONAL WORK IS STILL NECESSARY IN
 COORDINATION TO THE ARCHITECTURAL TREATMENT OF THE
 PARKING GARAGE. PREVIOUS COMMENT: THE WEST ELEVATION OF
 THE RESIDENTIAL BUILDING SHALL BE ENHANCED TO PROJECT A
 GOOD FACADE TOWARDS THE RESIDENTIAL NEIGHBORHOOD. THE
 WEST HALLWAY FACADE SHALL INCORPORATE WINDOWS.
 30. SATISFIED. STREETSCAPE DESIGN ALONG ROSEMARY AVENUE
 SHALL FOLLOW THE RECOMMENDATIONS OF THE DANCE INTO THE
 SUNSET STREETSCAPE DESIGN.
 31. SATISFIED. EXISTING DECORATIVE LIGHTS ALONG 3RD
 STREET SHALL BE REPLACED FOR CURRENT DOWNTOWN STANDARD,
 AND NEW DECORATIVE FIXTURES SHALL BE INSTALLED ALONG
 2ND STREET TO MEET THE MINIMUM 0.6 FOOTCANDLE REQUIRED.
 ALONG THE ROSEMARY FRONTAGE DECORATIVE LIGHTS MATCHING
 THE NEW LIGHT FIXTURES AND POLES BEING INSTALLED BY THE
 CITY SHALL BE INSTALLED ALONG THE PROJECT FRONTAGE.
 PREVIOUS COMMENT: PROJECT IS REQUIRED TO PROVIDE
 DECORATIVE STREET LIGHT ALONG THE STREET FRONTAGE TO
 MEET THE MINIMUM 0.6 FOOT-CANDLES REQUIRED. LIGHT
 FIXTURE SHALL MATCH CITY STANDARD.
 32. SATISFIED. SEE HPB CONDITIONS OF APPROVAL. PREVIOUS
 COMMENT: A PORTION OF THE SITE IS LOCATED WITHIN THE
 HISTORIC DISTRICT, THEREFORE HPB APPROVAL FOR A COA
 WILL BE REQUIRED. PLEASE CONTACT FRIEDERIKE MITTNER AT
 561-822-1457 TO DISCUSS REQUIREMENTS FOR SUCH
 APPLICATION. THE COA SHALL BE OBTAINED BEFORE
 PROCEEDING TO DAC FOR SPECIAL REVIEW.
 33. ACKNOWLEDGED. DEMOLITION OF EXISTING BUILDINGS ON
 SITE CANNOT OCCUR UNTIL BUILDING PERMIT FOR NEW
 CONSTRUCTION HAS BEEN APPROVED.
 34. NOT SATISFIED. TO BE INCLUDED AS A CONDITION IN
 SITE PLAN APPROVAL LETTER. PREVIOUS COMMENT: A PROPERTY
 RE-PLAT WILL BE REQUIRED.
 35. SATISFIED. AN APPLICATION WAS SUBMITTED ON NOVEMBER
 12, 2020. STAFF STARTED THE PROCESS FOR THE ALLEY
 ABANDONMENT AND WILL NOTIFY THE APPLICANT IF ADDITIONAL
 INFORMATION IS NEEDED. REQUEST WILL GO THE DAC AT THE
 SAME TIME THAN THE SPECIAL REVIEW, AND TO CITY
 COMMISSION AFTER THAT. STAFF HAS DETERMINED THE OPEN
 SPACE REQUIREMENT HAS BEEN MET BY THE PROJECT THROUGH
 THE ADDITIONAL PRIVATE OPEN SPACE PROVIDED. A WAIVER
 WILL NOT BE NECESSARY. PREVIOUS COMMENT: AN APPLICATION
 SHALL BE SUBMITTED FOR THE ALLEY ABANDONMENT. THE ALLEY
 ABANDONMENT REQUIRES THAT A PUBLIC OPEN SPACE
 EQUIVALENT TO THE AREA OF THE ABANDONED ALLEY BE
 ALLOCATED ON SITE. ALLEY AREA = 15 X500=7,500SF. PLEASE
 INDICATE IF A PUBLIC OPEN SPACE EQUAL TO 7,500 SF CAN
 BE LOCATED ON SITE. IF NOT, A WAIVER OF SUCH PROVISION
 SHALL BE REQUESTED TO THE CITY COMMISSION AS PART OF
 THE ALLEY ABANDONMENT PROCESS. IS THERE ANY POSSIBILITY
 TO PROVIDE ANY PUBLIC OPEN SPACE ON SITE TO COMPLY WITH
 THE ALLEY ABANDONMENT PROVISION? SMALLER THAN THE
 REQUIRED?
 36. SATISFIED. HAS THE PROPERTY ON THE SOUTH SIDE OF
 THE ALLEY (NOT PART OF THE PROPOSED PROJECT) CONFIRMED
 SUPPORT FOR ALLEY ABANDONMENT?
 37. SATISFIED. THE PROJECT REQUIRES DAC APPROVAL FOR
 SPECIAL REVIEW. IN PREPARATION FOR THE DAC, PLEASE
 PROVIDE COLORED ELEVATIONS IN CONTEXT FOR DAC SPECIAL
 REVIEW, MORE DETAILED COLORED ELEVATIONS WITH CALL OUT
 MATERIALS AND PICTURES OF PROPOSED MATERIALS, AND
 STREET LEVEL RENDERS.
 38. ACKNOWLEDGED. EASEMENTS WILL BE INCLUDED IN
 RE-PLAT. PREVIOUS COMMENT: PROJECT WILL BE REQUIRED TO
 PROVIDE A SIDEWALK ACCESS EASEMENT FOR THE SIDEWALK
 LOCATED ON PRIVATE PROPERTY.
 39. ACKNOWLEDGED. PROJECT WILL BE RESPONSIBLE FOR THE
 MAINTENANCE OF ALL HARDSCAPE AND LANDSCAPE INSTALLED
 WITHIN THE ROW AS PART OF THIS PROJECT. A MAINTENANCE
 AGREEMENT SHALL BE SIGNED BETWEEN THE CITY AND THE
 DEVELOPER BEFORE FINAL CO.
 ADDITIONAL COMMENTS:
 40. SATISFIED. PLEASE CORRECT THE PARKING TABLE TO
 REFLECT THE ACCURATE PARKING REQUIREMENTS FOR RETAIL
 WITHIN THIS DISTRICT AS FOLLOWS: MIN-1/1,000SF; MAX
 2/1,000SF.
 41. SATISFIED.PLEASE RELOCATE AT LEAST TWO OF THE BIKE
 PARKING AT THE PEDESTRIAN EXIT ON 3RD STREET TO THE
 ROSEMARY AVENUE FRONTAGE, IN FRONT OF RETAIL AREA.
 42. NOT SATISFIED. PLEASE COORDINATE ALL THE DIFFERENT
 ISCIPLINES AS THE LANDSCAPE, CIVIL AND SITE PLAN DO NOT
 SEEM TO MATCH. IF THE ON-STREET PARKING IS ALLOWED TO
 COUNT THE GUTTER FOR THE MINIMUM 8 FEET IN WIDTH, THE
 GUTTER CLOSER TO THE TRAVEL LANE CANNOT BE INCLUDED IN
 THE WIDTH OF THE LOADING PARKING SPACE.DRAWINGS C.2.3
 SHOWS THE ON-STREET PARKING ON 3RD AS 8 FEET PLUS THE
 GUTTER. PREVIOUS COMMENT:PLEASE DISCUSS WITH
 ENGINEERING DEPT THE POSSIBILITY TO REDUCE THE PARKING
 SPACES TO 8 FEET INCLUDING THE GUTTER. THAT WILL ALLOW
 ONE ADDITIONAL FOOT TO THE AREA IN FRONT OF THE
 RESIDENTIAL UNITS ON 3RD STREET AND PROVIDE ADDITIONAL
 PRIVACY FOR THE FIRST FLOOR UNITS. IN ADDITION, THE
 PLANTING AREA NEXT TO THE CURB CAN BE REDUCED TO 4 FEET
 IN WIDTH, ALSO PROVIDING ONE ADDITIONAL FOOT THAT CAN
 BE INCORPORATED WITHIN THE FRONT YARD OF THE FIRST
 FLOOR RESIDENTIAL UNITS ON 3RD STREET.
 43. SATISFIED.PLEASE REDUCE THE PARKING GARAGE ENTRANCE
 FROM SAPODILLA AVE AND 2ND STREET TO 20 FEET IN TOTAL
 WIDTH.
 44. PARTIALLY SATISFIED. SEE COMMENT NO. 42. PREVIOUS
 COMMENT:THE PLANTING AREA NEXT TO THE CURB ALONG 3RD
 STREET MAY BE REDUCE TO 4 FEET IN WIDTH. THE SIDEWALK
 CAN BE MOVED 1 FOOT NORTH AND THE ADDITIONAL FOOT SHALL
 BE ALLOCATED TO THE FRONT PLATING AREA OF THE
 RESIDENTIAL UNITS.
  
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 12-11-2020 Cont ID  
Sent By aaponte Date 12-11-2020 Time 15:32 Rev Time 0.00
Received By aaponte Date 11-23-2020 Time 15:32 Sent To  
Notes
2020-12-11 15:33:12COMMENTS TO THE 11-23-20 RESUBMITTAL
 1. NOT SATISFIED. TABLE NEEDS TO LIST THE RESULTING GSF
 FOR EACH OF THE CATEGORIES AND TOTAL THE GBA PERMITTED
 BY RIGHT AND WITH INCENTIVES. PREVIOUS COMMENT: ON
 SHEET A-01 PLEASE CREATE A SITE DATA TABLE THAT
 INCLUDES THE THREE DIFFERENT ZONING DESIGNATION ON
 SITE, THE AREA OF EACH, THE CORRESPONDING BASE FAR AND
 RESULTING GBA ALLOWED BY RIGHT, AND THE ADDITIONAL FAR
 AND GBA ALLOWED WITH INCENTIVES FOR EACH BASE ZONING.
 THIS TABLE WILL LIST THE MAXIMUM GBA ALLOWED ON SITE BY
 RIGHT AND INCENTIVES. TABLE ALSO NEEDS TO INCLUDE THE
 PROPOSED GSF AND THE NUMBER OF TDRS NEEDED FOR THE
 PROJECT.
 2. SATISFIED. SURVEY AND CIVIL DRAWING SHALL INDICATE
 THE EXISTING CURB ACROSS STREET AND DIMENSION THE
 EXISTING TRAVEL LANES AFTER CHANGES.
 3. PARTIALLY SATISFIED. PLEASE INDICATE THE LOCATION OF
 THE EXISTING CURB AND THE PROPOSED LOCATION, IF
 CHANGED.
 4. PARTIALLY SATISFIED. THE TRAVEL LANE ON 2ND STREET
 IS SHOWN AS 9 FEET IN WITH DUE TO THE PROPOSED
 ON-STREET PARKING. FURTHER DISCUSSION WITH TRAFFIC
 ENGINEER IS NEEDED TO DETERMINE IF THAT WIDTH IS
 ADEQUATE OR ADJUSTMENT ARE NEEDED. PREVIOUS COMMENT:
 WHAT IS THE WIDTH OF THE TRAVEL LANES ON 2ND STREET? IS
 IT CHANGE FROM CURRENT?
 5. NOT SATISFIED. PLEASE MODIFY TO FOLLOW THE ANGLE OF
 THE CURB OR PEOPLE WILL DESTROY THE LANDSCAPE FOLLOWING
 THE EASIER PATH OF TRAVEL. PREVIOUS COMMENT: SIDEWALK
 ON EAST SIDE OF 3RD STREET SHALL FOLLOW THE CURB
 ALIGNMENT.
 6. PARTIALLY SATISFIED. PLEASE UPDATE SHEET A-03 TO
 REFLECT CHANGES ALONG ROSEMARY. PREVIOUS COMMENT:
 PROPOSED ON-STREET PARKING ALONG ROSEMARY WILL NOT BE
 POSSIBLE, PLEASE REMOVE PROPOSED STRIPING.
 7. NOT SATISFIED. PLEASE PREPARE SOME CROSS SECTIONS
 FOR 2ND STREET AND 3RD STREET.
 8. NOT SATISFIED. PLEASE JUSTIFY WHY THE FDC ON 2ND
 STREET CANNOT BE WALL MOUNTED. IF IT CANNOT BE WALL
 MOUNTED IT SHALL BE INSTALLED WITHIN THE LANDSCAPE AREA
 AND NOT ON THE SIDEWALK. PREVIOUS COMMENT: IF POSSIBLE
 FDC SHALL BE WALL MOUNTED.
 9. NOT SATISFIED. PLEASE COORDINATE WITH ENGINEERING
 FOR THE LOCATION OF THE DCDA. VALVE SHALL BE LOCATED
 BEHIND THE MINIMUM SETBACK AND SCREENED WITH LANDSCAPE.
 PREVIOUS COMMENT: DCDA INDICATED ON 2ND STREET EAST OF
 THE PARKING GARAGE IS LISTED TO BE LOCATED UNDERGROUND.
 VAULT WILL NOT BE PERMITTED BY THE PUBLIC UTILITIES
 DEPARTMENT. NEW DCDA LOCATION SHALL BE BEHIND THE
 MINIMUM SETBACK AND SCREENED WITH LANDSCAPE.
 10. SATISFIED. PROPOSED EXFILTRATION TRENCH WILL
 CONFLICT WITH THE REQUIRED STRUCTURAL SOIL FOR THE
 STREET TREE. PLEASE DISCUSS WITH LANDSCAPE PLANNER IF
 THE CONTINUOUS PLANTING AREA WILL BE SUFFICIENT FOR
 TREES AND THERE IS NO NEED FOR STRUCTURAL SOIL.
 11. SATISFIED. PLEASE CORRECT THE MAXIMUM BUILDING
 FOOTPRINT TABLE TO ACCURATELY REFLECT THE REQUIREMENT
 FOR PROPERTIES LARGER THAN 80,000SF.
 12. PARTIALLY SATISFIED. BIKE STORAGE ALONG 2ND STREET
 CANNOT BE COUNTED AS ACTIVE USE. PLEASE REMOVE FROM
 CALCULATION. THE STREET FRONTAGE IS CALCULATED
 DISCOUNTING THE MINIMUM SETBACKS. PREVIOUS COMMENT:
 PLEASE PROVIDE A GRAPHIC TO CONFIRM COMPLIANCE WITH
 ACTIVE USE REQUIREMENT AS LISTED IN TABLE WITHIN SHEET
 A-01.
 13. NOT SATISFIED. APPLICANT SUBMITTED FOR A VARIANCE
 REQUEST. PREVIOUS COMMENT: CODE REQUIRES AN AVERAGE
 UNIT SIZE OF 800SF. PROJECT PROPOSED AVERAGE UNIT SIZE
 OF 765SF. A VARIANCE WILL BE NECESSARY IF NOT ADJUSTED
 TO MEET REQUIREMENT.
 14. PARTIALLY SATISFIED. ON THE 2ND FLOOR, THE AREA
 LISTED AS OPEN TO BELOW CAN BE DISCOUNTED FORM THE GBA
 CALCULATIONS. PREVIOUS COMMENT: THE SQUARE FOOTAGE
 TABLE LISTS TRASH WITHIN THE NON-LEASABLE AREA. THE
 TRASH CHUTE CAN BE EXCLUDED FROM GBA BUT THE ROOM WHERE
 THE TRASH CHUTE IS LOCATED WITHIN EACH FLOOR SHALL BE
 COUNTED AS GBA.
 15. SATISFIED. PLEASE ADJUST THE TRANSPARENCY
 CALCULATION GRAPHIC IN SHEET A-03 TO INDICATE THE 10
 FEET MARK AND CONFIRM THE CALCULATION IS BASED ON THAT
 DIMENSION. TRANSPARENCY IS ONLY REQUIRED FOR
 NON-RESIDENTIAL ACTIVE USES (LOBBY AND COMMERCIAL
 SPACE).
 16. NOT SATISFIED. PLEASE PROVIDE GRAPHIC INFORMATION
 TO CONFIRM COMPLIANCE WITH PLANAR BREAK, HORIZONTAL
 PROJECTIONS AND ARCHITECTURAL TREATMENT FOR FACADES
 ENCLOSING NON-ACTIVE USES (GARAGE). PREVIOUS COMMENT:
 PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE WITH
 ALL THE ELEMENTS REQUIRED BY TABLE IV-4 FACADE
 ARTICULATION REQUIREMENTS.
 17. NOT SATISFIED. PLEASE INCORPORATE THE CONDITIONS OF
 APPROVAL FROM THE HPB REVIEW AND REDESIGN THE WEST AND
 SOUTH PARKING GARAGE FACADES. PREVIOUS COMMENTS:
 FURTHER STUDY IS NECESSARY FOR THE WEST ELEVATION AS IT
 WILL BE HIGHLY VISIBLE FROM THE NEIGHBORHOOD. THE
 PARKING GARAGE FACADES NEED ADDITIONAL WORK TO COMPLY
 WITH THE REQUIREMENT FOR ARCHITECTURAL TREATMENT OF
 NON-ACTIVE USES. THE WEST STAIR CAN INCORPORATE SOME
 WINDOWS OR TREATMENT TO IMPROVE THE FACADE. THE PARKING
 GARAGE NORTH ELEVATION WILL BE ALSO VISIBLE AND NEED
 SOME IMPROVEMENTS.
 18. SATISFIED. PLEASE INDICATE THE MINIMUM REQUIRED
 GROUND SETBACK ON ALL FLOOR PLANS AND THE CONDITIONAL
 SETBACK LINE ON EACH OF THE REQUIRED LEVELS. ALSO
 CLEARLY INCLUDE THE PROPERTY LINE IN ALL DRAWINGS,
 INCLUDING CIVILS AND LANDSCAPE.
 19. SATISFIED. IN SHEET A-02 PLEASE REFER TO MAXIMUM
 PROPOSED GBA, NOT FAR.
 20. NOT SATISFIED. EASTERN MOST TOWN HOUSE UNIT SHALL
 BE SETBACK FOR THE SIDE INTERIOR PROPERTY LINE A
 MINIMUM OF 10 FEET. PREVIOUS COMMENT: PLEASE PROVIDE A
 SIDE INTERIOR SETBACK FOR THE EAST PROPERTY LINE.
 21. SATISFIED. PLEASE LIST THE TOTAL NUMBER OF PARKING
 SPACES REQUIRED BY CODE, AND THE TOTAL NUMBER OF BIKE
 SPACES REQUIRED BY CODE (WITHIN THE BUILDING FOR
 BUILDING TENANTS AT 1/15 PARKING SPACES, AND ALONG THE
 STREET FRONTAGE 1/100 LINEAR FEET OF FRONTAGE). THE
 TABLE LISTING THE REQUIRED PARKING BY CODE IS NOT
 ACCURATE. PLEASE USE PROVISIONS IN SEC 94-111 OF THE
 ZLDRS.
 22. NOT SATISFIED. PLEASE CLEARLY INDICATE IN THE
 PARKING GARAGE THE LOCATION OF THE GUEST PARKING AND
 THE PARKING FOR THE COMMERCIAL USE. THESE SPACES SHALL
 NOT BE LOCATED BEHIND ANY CONTROL GATE.
 23. SATISFIED. WHAT IS THE BACK OUT SPACE AT THE GROUND
 LEVEL PARKING GARAGE?
 24. PARTIALLY SATISFIED. PLEASE CHECK THE LABELING OF
 THE FACADES AS THEY ARE NOT ACCURATE. PREVIOUS COMMENT:
 PLEASE LOCATE THE EXISTING STRUCTURES WITHIN THE BLOCK
 THAT ARE NOT PART OF THE PROJECT FOR REFERENCE.
 25. SATISFIED. STAFF WOULD LIKE TO DISCUSS THE ARCADE
 REMOVAL IN RELATION TO POSSIBLE FUTURE TENANTS.
 PREVIOUS COMMENT: STAFF WOULD LIKE TO DISCUSS THE
 POSSIBLE RE-DESIGN OF THE RETAIL SPACE ALONG ROSEMARY
 AVENUE. ARCADES DO NOT HAVE A RECORD OF SUCCESS FOR
 COMMERCIAL SPACES.
 26. PARTIALLY SATISFIED. PLEASE REVISE ELEVATIONS TO
 REFLECT THE CHANGE TO SWING DOOR FOR RESIDENTIAL WALK
 UP UNITS. PREVIOUS COMMENT: WALK UP UNIT DOORS SHALL BE
 DESIGNED LIKE FRONT DOORS AND NOT SLIDERS.
 27. NOT SATISFIED. THE GARAGE ELEVATION NEEDS
 ENHANCEMENT TO COMPLY WITH THE PROVISION OF
 ARCHITECTURAL TREATMENT FOR NON-ACTIVE USES. ENHANCED
 DESIGN MAY INCORPORATE SOME OF THE CONDITIONS OF
 APPROVAL FROM THE HPB BOARD. PREVIOUS COMMENT: GARAGE
 HAS BIG BLANK WALL ALONG 2ND STREET. OPTION COULD BE TO
 MOVE THE BIKE STORAGE THERE.
 28. NOT SATISFIED. THE GARAGE ELEVATION NEEDS
 ENHANCEMENT TO COMPLY WITH THE PROVISION OF
 ARCHITECTURAL TREATMENT FOR NON-ACTIVE USES. ENHANCED
 DESIGN MAY INCORPORATE SOME OF THE CONDITIONS OF
 APPROVAL FROM THE HPB BOARD. PREVIOUS COMMENT: GARAGE
 ELEVATION ALONG 2ND STREET SHALL INCLUDE ARCHITECTURAL
 TREATMENT.
 28A SATISFIED. STAFF RECOMMENDS THE SECONDARY ENTRANCE
 ON 2ND STREET TO BE HIGHLIGHTED TO BREAK THE CONTINUITY
 OF THE RESIDENTIAL UNITS.
 29. PARTIALLY SATISFIED. ADDITIONAL WORK IS STILL
 NECESSARY IN COORDINATION TO THE ARCHITECTURAL
 TREATMENT OF THE PARKING GARAGE. PREVIOUS COMMENT: THE
 WEST ELEVATION OF THE RESIDENTIAL BUILDING SHALL BE
 ENHANCED TO PROJECT A GOOD FACADE TOWARDS THE
 RESIDENTIAL NEIGHBORHOOD. THE WEST HALLWAY FACADE SHALL
 INCORPORATE WINDOWS.
 30. SATISFIED. STREETSCAPE DESIGN ALONG ROSEMARY AVENUE
 SHALL FOLLOW THE RECOMMENDATIONS OF THE DANCE INTO THE
 SUNSET STREETSCAPE DESIGN.
 31. NOT SATISFIED. EXISTING DECORATIVE LIGHTS ALONG 3RD
 STREET SHALL BE REPLACED FOR CURRENT DOWNTOWN STANDARD,
 AND NEW DECORATIVE FIXTURES SHALL BE INSTALLED ALONG
 2ND STREET TO MEET THE MINIMUM 0.6 FOOTCANDLE REQUIRED.
 ALONG THE ROSEMARY FRONTAGE DECORATIVE LIGHTS MATCHING
 THE NEW LIGHT FIXTURES AND POLES BEING INSTALLED BY THE
 CITY SHALL BE INSTALLED ALONG THE PROJECT FRONTAGE.
 PREVIOUS COMMENT: PROJECT IS REQUIRED TO PROVIDE
 DECORATIVE STREET LIGHT ALONG THE STREET FRONTAGE TO
 MEET THE MINIMUM 0.6 FOOT-CANDLES REQUIRED. LIGHT
 FIXTURE SHALL MATCH CITY STANDARD.
 32. PARTIALLY SATISFIED. SEE HPB CONDITIONS OF
 APPROVAL. PREVIOUS COMMENT: A PORTION OF THE SITE IS
 LOCATED WITHIN THE HISTORIC DISTRICT, THEREFORE HPB
 APPROVAL FOR A COA WILL BE REQUIRED. PLEASE CONTACT
 FRIEDERIKE MITTNER AT 561-822-1457 TO DISCUSS
 REQUIREMENTS FOR SUCH APPLICATION. THE COA SHALL BE
 OBTAINED BEFORE PROCEEDING TO DAC FOR SPECIAL REVIEW.
 33. ACKNOWLEDGED. DEMOLITION OF EXISTING BUILDINGS ON
 SITE CANNOT OCCUR UNTIL BUILDING PERMIT FOR NEW
 CONSTRUCTION HAS BEEN APPROVED.
 34. NOT SATISFIED. TO BE INCLUDED AS A CONDITION IN
 SITE PLAN APPROVAL LETTER. PREVIOUS COMMENT: A PROPERTY
 RE-PLAT WILL BE REQUIRED.
 35. PARTIALLY SATISFIED. AN APPLICATION WAS SUBMITTED
 ON NOVEMBER 12, 2020. STAFF STARTED THE PROCESS FOR THE
 ALLEY ABANDONMENT AND WILL NOTIFY THE APPLICANT IF
 ADDITIONAL INFORMATION IS NEEDED. REQUEST WILL GO THE
 DAC AT THE SAME TIME THAN THE SPECIAL REVIEW, AND TO
 CITY COMMISSION AFTER THAT. STAFF HAS DETERMINED THE
 OPEN SPACE REQUIREMENT HAS BEEN MET BY THE PROJECT
 THROUGH THE ADDITIONAL PRIVATE OPEN SPACE PROVIDED. A
 WAIVER WILL NOT BE NECESSARY. PREVIOUS COMMENT: AN
 APPLICATION SHALL BE SUBMITTED FOR THE ALLEY
 ABANDONMENT. THE ALLEY ABANDONMENT REQUIRES THAT A
 PUBLIC OPEN SPACE EQUIVALENT TO THE AREA OF THE
 ABANDONED ALLEY BE ALLOCATED ON SITE. ALLEY AREA = 15
 X500=7,500SF. PLEASE INDICATE IF A PUBLIC OPEN SPACE
 EQUAL TO 7,500 SF CAN BE LOCATED ON SITE. IF NOT, A
 WAIVER OF SUCH PROVISION SHALL BE REQUESTED TO THE CITY
 COMMISSION AS PART OF THE ALLEY ABANDONMENT PROCESS. IS
 THERE ANY POSSIBILITY TO PROVIDE ANY PUBLIC OPEN SPACE
 ON SITE TO COMPLY WITH THE ALLEY ABANDONMENT PROVISION?
 SMALLER THAN THE REQUIRED?
 36. SATISFIED. HAS THE PROPERTY ON THE SOUTH SIDE OF
 THE ALLEY (NOT PART OF THE PROPOSED PROJECT) CONFIRMED
 SUPPORT FOR ALLEY ABANDONMENT?
 37. PARTIALLY SATISFIED. THE PROJECT REQUIRES DAC
 APPROVAL FOR SPECIAL REVIEW. IN PREPARATION FOR THE
 DAC, PLEASE PROVIDE COLORED ELEVATIONS IN CONTEXT FOR
 DAC SPECIAL REVIEW, MORE DETAILED COLORED ELEVATIONS
 WITH CALL OUT MATERIALS AND PICTURES OF PROPOSED
 MATERIALS, AND STREET LEVEL RENDERS.
 38. ACKNOWLEDGED. EASEMENTS WILL BE INCLUDED IN
 RE-PLAT. PREVIOUS COMMENT: PROJECT WILL BE REQUIRED TO
 PROVIDE A SIDEWALK ACCESS EASEMENT FOR THE SIDEWALK
 LOCATED ON PRIVATE PROPERTY.
 39. ACKNOWLEDGED. PROJECT WILL BE RESPONSIBLE FOR THE
 MAINTENANCE OF ALL HARDSCAPE AND LANDSCAPE INSTALLED
 WITHIN THE ROW AS PART OF THIS PROJECT. A MAINTENANCE
 AGREEMENT SHALL BE SIGNED BETWEEN THE CITY AND THE
 DEVELOPER BEFORE FINAL CO.
 ADDITIONAL COMMENTS:
 40. PLEASE CORRECT THE PARKING TABLE TO REFLECT THE
 ACCURATE PARKING REQUIREMENTS FOR RETAIL WITHIN THIS
 DISTRICT AS FOLLOWS: MIN-1/1,000SF; MAX 2/1,000SF.
 41. PLEASE RELOCATE AT LEAST TWO OF THE BIKE PARKING AT
 THE PEDESTRIAN EXIT ON 3RD STREET TO THE ROSEMARY
 AVENUE FRONTAGE, IN FRONT OF RETAIL AREA.
 42. PLEASE DISCUSS WITH ENGINEERING DEPT THE
 POSSIBILITY TO REDUCE THE PARKING SPACES TO 8 FEET
 INCLUDING THE GUTTER. THAT WILL ALLOW ONE ADDITIONAL
 FOOT TO THE AREA IN FRONT OF THE RESIDENTIAL UNITS ON
 3RD STREET AND PROVIDE ADDITIONAL PRIVACY FOR THE FIRST
 FLOOR UNITS. IN ADDITION, THE PLANTING AREA NEXT TO THE
 CURB CAN BE REDUCED TO 4 FEET IN WIDTH, ALSO PROVIDING
 ONE ADDITIONAL FOOT THAT CAN BE INCORPORATED WITHIN THE
 FRONT YARD OF THE FIRST FLOOR RESIDENTIAL UNITS ON 3RD
 STREET.
 43. PLEASE REDUCE THE PARKING GARAGE ENTRANCE FROM
 SAPODILLA AVE AND 2ND STREET TO 20 FEET IN TOTAL WIDTH.
 44. THE PLANTING AREA NEXT TO THE CURB ALONG 3RD STREET
 MAY BE REDUCE TO 4 FEET IN WIDTH. THE SIDEWALK CAN BE
 MOVED 1 FOOT NORTH AND THE ADDITIONAL FOOT SHALL BE
 ALLOCATED TO THE FRONT PLATING AREA OF THE RESIDENTIAL
 UNITS.
 FOR RESUBMITTAL PLEASE PROVIDE ONE COPY OF THE
 DRAWINGS, RESPONSE LETTER AND ANY OTHER REQUIRED
 SUPPORTING DOCUMENTATION, AND ONE CD WITH ELECTRONIC
 COPIES OF ALL DOCUMENTS SUBMITTED.
 TO CONTINUE THE PROCESS TO THE DAC FOR SPECIAL REVIEW
 AND VARIANCE APPROVAL AT THE JANUARY 13, 2021 MEETING,
 REVISED DRAWINGS WERE REQUIRED BY DECEMBER 8, 2020.
 CONSIDERING THE EXPEDITED REQUEST BY THE APPLICANT
 STAFF WILL ACCEPT REVISED DRAWING AS LATE AS WEDNESDAY
 DECEMBER 23RD, 2020. IF REVISED DRAWINGS ARE NOT
 RECEIVED BY THE DECEMBER 23, 2020 EXTENDED DEADLINE THE
 CASE WILL BE CONTINUED TO THE FEBRUARY 10, 2021
 MEETING.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 10-27-2020 Cont ID  
Sent By aaponte Date 10-27-2020 Time 16:36 Rev Time 0.00
Received By aaponte Date 10-27-2020 Time 16:36 Sent To  
Notes
2020-10-27 16:38:291. ON SHEET A-01 PLEASE CREATE A SITE DATA TABLE THAT
 INCLUDES THE THREE DIFFERENT ZONING DESIGNATION ON
 SITE, THE AREA OF EACH, THE CORRESPONDING BASE FAR AND
 RESULTING GBA ALLOWED BY RIGHT, AND THE ADDITIONAL FAR
 AND GBA ALLOWED WITH INCENTIVES FOR EACH BASE ZONING.
 THIS TABLE WILL LIST THE MAXIMUM GBA ALLOWED ON SITE BY
 RIGHT AND INCENTIVES. TABLE ALSO NEEDS TO INCLUDE THE
 PROPOSED GSF AND THE AMOUNT OF TDRS NEEDED FOR THE
 PROJECT.
 2. SURVEY AND CIVIL DRAWING SHALL INDICATE THE EXISTING
 CURB ACROSS STREET AND DIMENSION THE EXISTING TRAVEL
 LANES AFTER CHANGES.
 3. PLEASE INDICATE THE LOCATION OF THE EXISTING CURB
 AND THE PROPOSED LOCATION, IF CHANGED.
 4. WHAT IS THE WIDTH OF THE TRAVEL LANES ON 2ND STREET?
 IS IT CHANGE FROM CURRENT?
 5. SIDEWALK ON EAST SIDE OF 3RD STREET SHALL FOLLOW THE
 CURB ALIGNMENT.
 6. PROPOSED ON-STREET PARKING ALONG ROSEMARY WILL NOT
 BE POSSIBLE, PLEASE REMOVE PROPOSED STRIPING.
 7. PLEASE PREPARE SOME CROSS SECTIONS FOR 2ND STREET
 AND 3RD STREET.
 8. IF POSSIBLE FDC SHALL BE WALL MOUNTED.
 9. DCDA INDICATED ON 2ND STREET EAST OF THE PARKING
 GARAGE IS LISTED TO BE LOCATED UNDERGROUND. VAULT WILL
 NOT BE PERMITTED BY THE PUBLIC UTILITIES DEPARTMENT.
 NEW DCDA LOCATION SHALL BE BEHIND THE MINIMUM SETBACK
 AND SCREENED WITH LANDSCAPE.
 10. PROPOSED EXFILTRATION TRENCH WILL CONFLICT WITH THE
 REQUIRED STRUCTURAL SOIL FOR THE STREET TREE. PLEASE
 DISCUSS WITH LANDSCAPE PLANNER IF THE CONTINUOUS
 PLANTING AREA WILL BE SUFFICIENT FOR TREES AND THERE IS
 NO NEED FOR STRUCTURAL SOIL.
 11. PLEASE CORRECT THE MAXIMUM BUILDING FOOTPRINT TABLE
 TO ACCURATELY REFLECT THE REQUIREMENT FOR PROPERTIES
 LARGER THAN 80,000SF.
 12. PLEASE PROVIDE A GRAPHIC TO CONFIRM COMPLIANCE WITH
 ACTIVE USE REQUIREMENT AS LISTED IN TABLE WITHIN SHEET
 A-01.
 13. CODE REQUIRES AN AVERAGE UNIT SIZE OF 800SF.
 PROJECT PROPOSED AVERAGE UNIT SIZE OF 765SF. A VARIANCE
 WILL BE NECESSARY IF NOT ADJUSTED TO MEET REQUIREMENT.
 14. SQUARE FOOTAGE TABLE LISTS TRASH WITHIN THE
 NON-LEASABLE AREA. THE TRASH CHUTE CAN BE EXCLUDED FROM
 GBA BUT THE ROOM WHERE THE TRASH CHUTE IS LOCATED
 WITHIN EACH FLOOR SHALL BE COUNTED AS GBA.
 15. PLEASE ADJUST THE TRANSPARENCY CALCULATION GRAPHIC
 IN SHEET A-03 TO INDICATE THE 10 FEET MARK AND CONFIRM
 THE CALCULATION IS BASED ON THAT DIMENSION.
 TRANSPARENCY IS ONLY REQUIRED FOR NON-RESIDENTIAL
 ACTIVE USES (LOBBY AND COMMERCIAL SPACE).
 16. PLEASE PROVIDE INFORMATION TO CONFIRM COMPLIANCE
 WITH ALL THE ELEMENTS REQUIRED BY TABLE IV-4 FA?ADE
 ARTICULATION REQUIREMENTS.
 17. FURTHER STUDY IS NECESSARY FOR THE WEST ELEVATION
 AS IT WILL BE HIGHLY VISIBLE FROM THE NEIGHBORHOOD. THE
 PARKING GARAGE FACADES NEED ADDITIONAL WORK TO COMPLY
 WITH THE REQUIREMENT FOR ARCHITECTURAL TREATMENT OF
 NON-ACTIVE USES. THE WEST STAIR CAN INCORPORATE SOME
 WINDOWS OR TREATMENT TO IMPROVE THE FA?ADE. THE PARKING
 GARAGE NORTH ELEVATION WILL BE ALSO VISIBLE AND NEED
 SOME IMPROVEMENTS.
 18. PLEASE INDICATE THE MINIMUM REQUIRED GROUND SETBACK
 ON ALL FLOOR PLANS AND THE CONDITIONAL SETBACK LINE ON
 EACH OF THE REQUIRED LEVELS. ALSO CLEARLY INCLUDE THE
 PROPERTY LINE IN ALL DRAWINGS, INCLUDING CIVILS AND
 LANDSCAPE.
 19. IN SHEET A-02 PLEASE REFER TO MAXIMUM PROPOSED GBA,
 NOT FAR.
 20. PLEASE PROVIDE A SIDE INTERIOR SETBACK FOR THE EAST
 PROPERTY LINE.
 21. PLEASE LIST THE TOTAL NUMBER OF PARKING SPACES
 REQUIRED BY CODE, AND THE TOTAL NUMBER OF BIKE SPACES
 REQUIRED BY CODE (WITHIN THE BUILDING FOR BUILDING
 TENANTS AT 1/15 PARKING SPACES, AND ALONG THE STREET
 FRONTAGE 1/100 LINEAR FEET OF FRONTAGE). THE TABLE
 LISTING THE REQUIRED PARKING BY CODE IS NOT ACCURATE.
 PLEASE USE PROVISIONS IN SEC 94-111 OF THE ZLDRS.
 22. PLEASE CLEARLY INDICATE IN THE PARKING GARAGE THE
 LOCATION OF THE GUEST PARKING AND THE PARKING FOR THE
 COMMERCIAL USE. THESE SPACES SHALL NOT BE LOCATED
 BEHIND ANY CONTROL GATE.
 23. WHAT IS THE BACK OUT SPACE AT THE GROUND LEVEL
 PARKING GARAGE?
 24. PLEASE LOCATE THE EXISTING STRUCTURES WITHIN THE
 BLOCK THAT ARE NOT PART OF THE PROJECT FOR REFERENCE.
 25. STAFF WOULD LIKE TO DISCUSS THE POSSIBLE RE-DESIGN
 OF THE RETAIL SPACE ALONG ROSEMARY AVENUE. ARCADES DO
 NOT HAVE A RECORD OF SUCCESS FOR COMMERCIAL SPACES.
 26. WALK UP UNIT DOORS SHALL BE DESIGNED LIKE FRONT
 DOORS AND NOT SLIDERS.
 27. GARAGE HAS BIG BLANK WALL ALONG 2ND STREET. OPTION
 COULD BE TO MOVE THE BIKE STORAGE THERE.
 28. GARAGE ELEVATION ALONG 2ND STREET SHALL INCLUDE
 ARCHITECTURAL TREATMENT.
 28A STAFF RECOMMENDS THE SECONDARY ENTRANCE ON 2ND
 STREET TO BE HIGHLIGHTED TO BREAK THE CONTINUITY OF THE
 RESIDENTIALL UNITS.
 29. THE WEST ELEVATION OF THE RESIDENTIAL BUILDING
 SHALL BE ENHANCED TO PROJECT A GOOD FA?ADE TOWARDS THE
 RESIDENTIAL NEIGHBORHOOD. THE WEST HALLWAY FA?ADE SHALL
 INCORPORATE WINDOWS.
 30. STREETSCAPE DESIGN ALONG ROSEMARY AVENUE SHALL
 FOLLOW THE RECOMMENDATIONS OF THE DANCE INTO THE SUNSET
 STREETSCAPE DESIGN.
 31. PROJECT IS REQUIRED TO PROVIDE DECORATIVE STREET
 LIGHT ALONG THE STREET FRONTAGE TO MEET THE MINIMUM 0.6
 FOOT-CANDLES REQUIRED. LIGHT FIXTURE SHALL MATCH CITY
 STANDARD.
 32. A PORTION OF THE SITE IS LOCATED WITHIN THE
 HISTORIC DISTRICT, THEREFORE HPB APPROVAL FOR A COA
 WILL BE REQUIRED. PLEASE CONTACT FRIEDERIKE MITTNER AT
 561-822-1457 TO DISCUSS REQUIREMENTS FOR SUCH
 APPLICATION. THE COA SHALL BE OBTAINED BEFORE
 PROCEEDING TO DAC FOR SPECIAL REVIEW.
 33. DEMOLITION OF EXISTING BUILDINGS ON SITE CANNOT
 OCCUR UNTIL BUILDING PERMIT FOR NEW CONSTRUCTION HAS
 BEEN APPROVED.
 34. A PROPERTY RE-PLAT WILL BE REQUIRED.
 35. AN APPLICATION SHALL BE SUBMITTED FOR THE ALLEY
 ABANDONMENT. THE ALLEY ABANDONMENT REQUIRES THAT A
 PUBLIC OPEN SPACE EQUIVALENT TO THE AREA OF THE
 ABANDONED ALLEY BE ALLOCATED ON SITE. ALLEY AREA = 15
 X500=7,500SF. PLEASE INDICATE IF A PUBLIC OPEN SPACE
 EQUAL TO 7,500 SF CAN BE LOCATED ON SITE. IF NOT, A
 WAIVER OF SUCH PROVISION SHALL BE REQUESTED TO THE CITY
 COMMISSION AS PART OF THE ALLEY ABANDONMENT PROCESS. IS
 THERE ANY POSSIBILITY TO PROVIDE ANY PUBLIC OPEN SPACE
 ON SITE TO COMPLY WITH THE ALLEY ABANDONMENT PROVISION?
 SMALLER THAN THE REQUIRED?
 36. HAS THE PROPERTY ON THE SOUTH SIDE OF THE ALLEY
 (NOT PART OF THE PROPOSED PROJECT) CONFIRMED SUPPORT
 FOR ALLEY ABANDONMENT?
 37. THE PROJECT REQUIRES DAC APPROVAL FOR SPECIAL
 REVIEW. IN PREPARATION FOR THE DAC, PLEASE PROVIDE
 COLORED ELEVATIONS IN CONTEXT FOR DAC SPECIAL REVIEW,
 MORE DETAILED COLORED ELEVATIONS WITH CALL OUT
 MATERIALS AND PICTURES OF PROPOSED MATERIALS, AND
 STREET LEVEL RENDERS.
 38. PROJECT WILL BE REQUIRED TO PROVIDE A SIDEWALK
 ACCESS EASEMENT FOR THE SIDEWALK LOCATED ON PRIVATE
 PROPERTY.
 39. PROJECT WILL BE RESPONSIBLE FOR THE MAINTENANCE OF
 ALL HARDSCAPE AND LANDSCAPE INSTALLED WITHIN THE ROW AS
 PART OF THIS PROJECT. A MAINTENANCE AGREEMENT SHALL BE
 SIGNED BETWEEN THE CITY AND THE DEVELOPER BEFORE FINAL
 CO.
 FOR RESUBMITTAL PLEASE PROVIDE ONE COPY OF THE
 DRAWINGS, RESPONSE LETTER AND ANY OTHER REQUIRED
 SUPPORTED DOCUMENTATION, AND ONE CD WITH ELECTRONIC
 COPIES OF ALL DOCUMENTS SUBMITTED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-11-2019 Cont ID  
Sent By aaponte Date 12-11-2019 Time 13:19 Rev Time 0.00
Received By aaponte Date 12-11-2019 Time 13:19 Sent To  
Notes
2019-12-11 13:20:50- PROJECT DOES NOT COMPLY WITH CURRENT ZONING
 REQUIREMENTS FOR NWD-5, NWD-R-C1, OR NWD-2. THE SITE IS
 NOT ZONED NWD-8. THE CITY HAS RETAINED THE SERVICES OF
 A CONSULTING FIRM TO STUDY THE AREA AND MAKE
 RECOMMENDATIONS ON CHANGES TO THE ZONING REGULATIONS TO
 ACCOMMODATE HIGHER INTENSITY DEVELOPMENT COMPATIBLE
 WITH THE HISTORIC DISTRICT. ANY CHANGES TO THE CURRENT
 ZONING WOULD REQUIRE AND AMENDMENT TO THE COMPREHENSIVE
 PLAN AND ZONING AND LAND DEVELOPMENT REGULATIONS.
 - AN APPLICATION FOR THE ALLEY ABANDONMENT SHALL BE
 SUBMITTED FOR REVIEW. IF ALLEY IS ABANDONED, THE TOTAL
 SQUARE FOOTAGE OF THE ALLEY SHALL BE DEDICATED AS A
 PUBLIC OPEN SPACE ON SITE, IN ADDITION TO ANY PUBLIC
 OPEN SPACE REQUIRED.
 - HAS THE PROPERTY ON THE SOUTH SIDE OF THE ALLEY (NOT
 PART OF THE PROPOSED PROJECT) CONFIRM SUPPORT FOR ALLEY
 ABANDONMENT?
 - STREETSCAPE DESIGN ALONG ROSEMARY AVENUE SHALL FOLLOW
 THE RECOMMENDATIONS OF THE DANCE INTO THE SUNSET
 STREETSCAPE DESIGN.
 - A PORTION OF THE SITE IS LOCATED WITHIN THE HISTORIC
 DISTRICT, THEREFORE HPB APPROVAL WILL BE REQUIRED.
 - DEMOLITION OF EXISTING BUILDINGS ON SITE CANNOT OCCUR
 UNITL BUILDING PERMIT FOR NEW CONSTRUCTION HAS BEEN
 APPROVED.
 - A PROPERTY RE-PLAT WILL BE REQUIRED.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.
  

  Print