Plan Review Details - Project Z19090009
| Plan Review Stops For Project Z19090009 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
10-09-2019 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
10-09-2019 |
Time |
19:07 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
10-09-2019 |
Time |
19:07 |
Sent To |
|
|
| Notes |
| 2019-10-09 19:10:47 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 4. ART IN PUBLIC PLACES. THIS PROJECT MAY BE SUBJECT TO | | | ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE ON | | | THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
01-09-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
01-09-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
01-09-2020 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
10-07-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
10-07-2019 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
10-07-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-10-07 11:15:17 | 1. THE CITY OF WEST PALM BEACH HAS A NUMBER OF | | | REGULATIONS AND PERMIT REQUIREMENTS WHICH DIRECTLY | | | AFFECT THE DEVELOPMENT AND INSTALLATION OF WATER AND | | | WASTEWATER UTILITIES WITHIN THE CITY. PLEASE SEE | | | DEVELOPMENT PERMIT SUBMITTAL REQUIREMENTS AT THE LINK | | | BELOW: HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH= | | | ~\WPB_WEBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION | | | -FULL-PACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC0 | | | 2A97B1960045731D3658206F27451722716EF | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBL | | | IC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | 2. CODE OF ORDINANCES, CITY OF WEST PALM BEACH, | | | FLORIDA, CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED | | | SEPT. 22, 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. SEC. 90-7. | | | POLICY REGARDING EXTENSION OF WATER OR SEWER SERVICE | | | FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | 3. AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | 4. PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS | | | OF ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | PLEASE SHOW SLOPE % ON ALL SANITARY LINES AND CALL OUT | | | MATERIAL. ADDITIONALLY, PLAN VIEW SHALL SHOW ALL | | | EXISTING AND PROPOSED UNDERGROUND UTILITY LAYOUT, | | | INCLUDING FIBER OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL | | | UTILITY CROSSINGS. | | | 5. CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | RIGHT OF WAY. | | | 6. PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE | | | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB | | | DEVELOPMENT APPLICATION). | | | 7. PROVIDE CALCULATIONS ON PLANS OF EXISTING AND | | | PROPOSED ADDITIONAL DEMANDS FOR WATER & SEWER (AVERAGE, | | | MAXIMUM AND PEAK) AND FIRE FLOW DEMANDS. CALCULATIONS | | | SHALL BE PER FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 | | | FOR WATER. | | | 8. SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29) ON ALL SHEETS. | | | 9. PLEASE PROVIDE CALCULATIONS OF EXISTING AND REVISED | | | PERVIOUS AND IMPERVIOUS CALCULATIONS FOR THE PROPOSED | | | IMPACTED AREAS. | | | 10. COORDINATE WITH MARK HURLEY, FIELD CUSTOMER SERVICE | | | SUPERVISOR WITH CITY OF WPB PUBLIC UTILITIES, REGARDING | | | PLACEMENT OF BACKFLOW DEVICES AND WATER METERS. CONTACT | | | HIM AT 561-494-2262 OR [email protected] | | | 11. PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY | | | PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS. | | | 12. PLEASE PROVIDE 10 FT. MIN. HORIZONTAL CLEARANCE | | | BETWEEN PROPOSED WATER AND SEWER LINES. | | | 13. PLEASE PROVIDE INLET ELEVATIONS AT ANY PROPOSED | | | MANHOLES. | | | 14. SPECIFY EXISTING SANITARY LINE MATERIAL IN RIGHT OF | | | WAY. | | | 15. PLEASE SHOW VALVE SIZES AND LOCATIONS. | | | 16. LABEL WATER LINES AS PRIVATE WHERE APPLICABLE. | | | 17. PLEASE PROVIDE PROJECT ADDRESS ON PLANS. | | | 18. PLEASE ADD AND OR UPDATE CITY OF WPB STANDARD | | | DETAILS. | | | 19. PLEASE CLARIFY LOCATION OF PROPOSED GENERATOR OVER | | | EASEMENT ? MAY BE IN CONFLICT WITH EXISTING CITY WATER | | | MAIN. | | | 20. PROPOSED DRIVEWAY CONNECTING TO NORTH PARCEL MAY BE | | | IN CONFLICT WITH EXISTING CITY WATER MAIN. | | | 21. SHOW WATER MAIN IN EASEMENT THAT COULD BE IN | | | CONFLICT WITH PROPOSED STORM ADJUSTMENTS. | | | 22. WILL DRIVEWAY BE GATED? PLEASE SHOW GATE DETAILS, | | | FOOTPRINT/LAYOUT/DIMENSIONS ETC. | | | 23. PLEASE PROVIDE ADDRESS ON COVER SHEET. | | | 24. FOR FORMAL ENGINEERING SUBMITTAL , PLEASE INCLUDE | | | LATEST CITY OF WPB STANDARD DETAILS IN PLANS. | | | 25. FOR FORMAL ENGINEERING SUBMITTAL, PROVIDE PROFILES | | | OF WATER AND SEWER AND SHOW ANY CROSSINGS/CONFLICTS. | | | 26. FOR FORMAL ENGINEERING SUBMITTAL, WHEN SUBMITTING | | | APPROVED MATERIALS LIST, PLEASE PROVIDE MATERIAL/CUT | | | SHEETS FOR ALL PROPOSED BACKFLOW DEVICES SHOWING | | | SPECIFIC MODEL NUMBER AND SPECIFYING USC APPROVED | | | LEAD-FREE DESIGN. | | | 27. FOR FORMAL ENGINEERING SUBMITTAL PROVIDE SANITARY | | | ELEVATIONS AT MANHOLE TIE-IN. | | | 28. PLEASE RESPOND TO ALL COMMENTS IN WRITING AND | | | INCLUDE Z PERMIT NUMBER IN ALL CORRESPONDENCE. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | DIRECT: (561) 494-1098 [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
10-03-2019 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
10-03-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
10-03-2019 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2019-10-03 16:34:31 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT | | | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON | | | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, | | | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
6 |
Status |
P |
Date |
07-14-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
07-14-2020 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
07-14-2020 |
Time |
13:40 |
Sent To |
|
|
| Notes |
| 2020-07-14 13:41:20 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | JULY 14, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | PART A AUDITORIUM BUILDING: | | | 1. SATISFIED. THE EXISTING TREE PLAN AND DISPOSITION | | | LIST ON SHEET L102B IS OUTDATED AND DOES NOT REFLECT | | | WHAT CURRENTLY EXISTS ON SITE. SUPPLY A CURRENT PLAN | | | AND IDENTIFY THE TREES WITHIN THE AFFECTED AREA ON THE | | | TREE DISPOSITION TABULAR LIST TO DISCERN THEM FROM THE | | | REST OF THE AREAS. | | | THE LAST APPROVED LANDSCAPE PLAN MUST BE THE BASE FOR | | | THE TREE LOCATIONS, AND THEN THE TREES THAT ARE TO BE | | | REMOVED OR RELOCATED ARE TO BE IDENTIFIED. THE APPROVED | | | LANDSCAPE PLAN FOR THE NORTH PROPERTY SHOULD BE USED TO | | | SHOW THE BUFFER TREES, AND THE ONES IDENTIFIED THAT ARE | | | TO BE REMOVED OR RELOCATED. GENERATOR SIDEWALK APPEARS | | | TO CONFLICT WITH SM#2. | | | | | | 2. SATISFIED. PROVIDE A CLEAR LOCATION OF WHERE ANY | | | RELOCATED TREES AND PALMS WILL BE PLACED ON THE SITE ON | | | THE LANDSCAPE PLAN. | | | SOME OF THE LABELED RELOCATIONS AND REPLACEMENTS ARE | | | NOT CONSISTENT WITH THE LABELS ON THE EXISTING TREE | | | PLAN. QV#1 AND QV#2 MUST BE SHOWN ON THE EXISTING TREE | | | PLAN, AND REPLACEMENT LOCATIONS SHOULD ONLY BE SHOWN ON | | | THE LANDSCAPE PLAN. QV3 IS SHOWN TWICE. | | | ALL FINAL LOCATIONS FOR TREES ARE TO BE SHOWN ON THE | | | LANDSCAPE PLAN INCLUDING FOR THE NORTH PROPERTY. | | | | | | 3. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. LIVE OAK TREES #5 AND #6 ARE LISTED FOR | | | REMOVAL, BUT CONDITION WAS NOT SUPPLIED. | | | EXPLANATION OF ADJUSTMENT TO AVOID GOOD TREES PROVIDED, | | | BUT CONDITION MUST BE LISTED IN THE TREE DISPOSITION | | | FOR ALL REMOVALS AND RELOCATIONS. | | | | | | 4. SATISFIED. PROVIDE A LANDSCAPE PLAN FOR THE PROPOSED | | | ACCESS DRIVEWAY AND SHOW ANY REMOVAL OR REPLACEMENT OF | | | TREES OR SHRUBS, INCLUDING THE NORTH PROPERTY. | | | PLAN SUPPLIED FOR SOUTH PROPERTY, BUT NOTHING IS SHOWN | | | FOR THE EXISTING BUFFER TREES ON THE ADJACENT PROPERTY | | | TO THE NORTH. IF THIS IS TO BE SHOWN ON THE MAJOR | | | AMENDMENT PLAN, INDICATE THIS ON THE SUBMITTED PLAN. | | | CODE REQUIRES THE ADJACENT PROPERTY TREES WITHIN 10 | | | FEET OF THE PROPERTY LINE TO BE SHOWN ON THE PROPOSED | | | PLAN PER SECTION 94-442(B)(2)Q. | | | APPROVED AND EXISTING TREES FOR THE NORTH PROPERTY HAVE | | | NOT BEEN SHOWN. | | | | | | 5. SATISFIED. THE GENERATOR LOCATION DOES NOT SHOW | | | DETAIL FOR THE LOCATION OF THE WALL DESCRIBED IN THE | | | NARRATIVE. LOCATION OF ACCESS DOORS NEEDS TO BE SHOWN, | | | AND THE HEDGE AND TREES ON THE NORTH SIDE OF THE | | | ENCLOSURE NEED TO BE SHOWN ON THE PLAN. | | | GENERATOR ENCLOSURE IS SHOWN CROSSING OVER THE PARCEL | | | LINE, SEE COMMENT#4. | | | | | | 6. SATISFIED. STAFF DOES NOT SUPPORT REMOVAL OF THE | | | MATURE BUFFER TREES ALONG THE NORTH PROPERTY LINE THAT | | | ARE PROVIDING SHADE FOR THE EXISTING PARKING AND | | | PROVIDE ALL THE BENEFITS OF A MATURE TREE CANOPY. THE | | | APPLICANT SHOULD LOOK AT ADJUSTING THE LOCATION OF THE | | | GENERATOR TO MINIMIZE THE NEED TO RELOCATE TREES AND | | | PRESERVE THE EXISTING TREES TO MEET THE INTENT OF | | | SECTION 94-448. | | | 7. SATISFIED. INDICATE ALL CHANGES TO THE PLANT LIST | | | WITH CLOUDING AND INDICATE THE LIMITS OF THE AFFECTED | | | AREAS ON THE LANDSCAPE PLAN AND SITE PLAN. | | | | | | PART B, GENERATOR AND CONNECTION ROAD: | | | | | | 1. SATISFIED. THE HOMESAFE LANDSCAPE PLAN-1 WITH 4 | | | TREES INDICATED IN RED, 3 TO REMAIN AND I LIVE OAK TO | | | BE REMOVED DOES NOT MATCH HOMESAFE LANDSCAPE PLAN-2. | | | LA-2 MITIGATION LANDSCAPE PLAN DOES MATCH. | | | | | | 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. ARBORIST LETTER SUPPLIED DOES NOT ADDRESS | | | THE TREE CONDITIONS AS REQUESTED BUT ASKS FOR AN | | | EXCEPTION BECAUSE OF THE TIME FRAME. THE LETTER ALSO | | | REFERENCES 3 MAHOGANY TREES, BUT THE PLAN INDICATES | | | ONLY 2 MAHOGANY TREES TO BE REMOVED, SM#3 AND SM#4. | | | LIVE OAK TREES #5 AND #6 ARE LISTED FOR REMOVAL, AND | | | LIVE OAK TREES #1 AND #3 ARE NOW LISTED FOR REMOVAL. IF | | | TREES ARE TO BE REMOVED, THERE MAY BE ADDITIONAL TREES | | | REQUIRED. | | | | | | 3. SATISFIED. IF THE 6 TREES IN COMMENT 3 ARE TO BE | | | REMOVED, A DISPOSITION CHART MUST BE PROVIDED WITH THE | | | CANOPY DIAMETERS AND CONDITION SUPPLIED. CANOPY | | | MITIGATION MUST BE CALCULATED AND TOTALED. MITIGATION | | | SUPPLIED MUST ALSO BE LISTED AND TOTAL SQUARE FOOTAGE | | | PROVIDED. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | 2. ELECTRICAL CONDUIT CONNECTING THE GENERATOR TO THE | | | ELECTRIC PANEL SHALL BE INSTALLED IN A LOCATION AND | | | MANNER TO AVOID DAMAGE TO THE CRITICAL ROOT ZONE OF THE | | | EXISTING TREES. THIS WOULD INCLUDE AVOIDING DIGGING | | | LARGE TRENCHES WITHIN THE ROOT ZONE. OPTIONS SUCH AS | | | RUNNING IT UNDER PAVEMENT OR DIRECTIONAL BORING SHOULD | | | BE USED. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
5 |
Status |
F |
Date |
04-29-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-29-2020 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-29-2020 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2020-04-29 16:52:57 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | APRIL 29, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | PART A AUDITORIUM BUILDING: | | | 1. SATISFIED. THE EXISTING TREE PLAN AND DISPOSITION | | | LIST ON SHEET L102B IS OUTDATED AND DOES NOT REFLECT | | | WHAT CURRENTLY EXISTS ON SITE. SUPPLY A CURRENT PLAN | | | AND IDENTIFY THE TREES WITHIN THE AFFECTED AREA ON THE | | | TREE DISPOSITION TABULAR LIST TO DISCERN THEM FROM THE | | | REST OF THE AREAS. | | | THE LAST APPROVED LANDSCAPE PLAN MUST BE THE BASE FOR | | | THE TREE LOCATIONS, AND THEN THE TREES THAT ARE TO BE | | | REMOVED OR RELOCATED ARE TO BE IDENTIFIED. THE APPROVED | | | LANDSCAPE PLAN FOR THE NORTH PROPERTY SHOULD BE USED TO | | | SHOW THE BUFFER TREES, AND THE ONES IDENTIFIED THAT ARE | | | TO BE REMOVED OR RELOCATED. GENERATOR SIDEWALK APPEARS | | | TO CONFLICT WITH SM#2. | | | | | | 2. SATISFIED. PROVIDE A CLEAR LOCATION OF WHERE ANY | | | RELOCATED TREES AND PALMS WILL BE PLACED ON THE SITE ON | | | THE LANDSCAPE PLAN. | | | SOME OF THE LABELED RELOCATIONS AND REPLACEMENTS ARE | | | NOT CONSISTENT WITH THE LABELS ON THE EXISTING TREE | | | PLAN. QV#1 AND QV#2 MUST BE SHOWN ON THE EXISTING TREE | | | PLAN, AND REPLACEMENT LOCATIONS SHOULD ONLY BE SHOWN ON | | | THE LANDSCAPE PLAN. QV3 IS SHOWN TWICE. | | | ALL FINAL LOCATIONS FOR TREES ARE TO BE SHOWN ON THE | | | LANDSCAPE PLAN INCLUDING FOR THE NORTH PROPERTY. | | | | | | 3. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. LIVE OAK TREES #5 AND #6 ARE LISTED FOR | | | REMOVAL, BUT CONDITION WAS NOT SUPPLIED. | | | EXPLANATION OF ADJUSTMENT TO AVOID GOOD TREES PROVIDED, | | | BUT CONDITION MUST BE LISTED IN THE TREE DISPOSITION | | | FOR ALL REMOVALS AND RELOCATIONS. | | | | | | 4. SATISFIED. PROVIDE A LANDSCAPE PLAN FOR THE PROPOSED | | | ACCESS DRIVEWAY AND SHOW ANY REMOVAL OR REPLACEMENT OF | | | TREES OR SHRUBS, INCLUDING THE NORTH PROPERTY. | | | PLAN SUPPLIED FOR SOUTH PROPERTY, BUT NOTHING IS SHOWN | | | FOR THE EXISTING BUFFER TREES ON THE ADJACENT PROPERTY | | | TO THE NORTH. IF THIS IS TO BE SHOWN ON THE MAJOR | | | AMENDMENT PLAN, INDICATE THIS ON THE SUBMITTED PLAN. | | | CODE REQUIRES THE ADJACENT PROPERTY TREES WITHIN 10 | | | FEET OF THE PROPERTY LINE TO BE SHOWN ON THE PROPOSED | | | PLAN PER SECTION 94-442(B)(2)Q. | | | APPROVED AND EXISTING TREES FOR THE NORTH PROPERTY HAVE | | | NOT BEEN SHOWN. | | | | | | 5. SATISFIED. THE GENERATOR LOCATION DOES NOT SHOW | | | DETAIL FOR THE LOCATION OF THE WALL DESCRIBED IN THE | | | NARRATIVE. LOCATION OF ACCESS DOORS NEEDS TO BE SHOWN, | | | AND THE HEDGE AND TREES ON THE NORTH SIDE OF THE | | | ENCLOSURE NEED TO BE SHOWN ON THE PLAN. | | | GENERATOR ENCLOSURE IS SHOWN CROSSING OVER THE PARCEL | | | LINE, SEE COMMENT#4. | | | | | | 6. SATISFIED. STAFF DOES NOT SUPPORT REMOVAL OF THE | | | MATURE BUFFER TREES ALONG THE NORTH PROPERTY LINE THAT | | | ARE PROVIDING SHADE FOR THE EXISTING PARKING AND | | | PROVIDE ALL THE BENEFITS OF A MATURE TREE CANOPY. THE | | | APPLICANT SHOULD LOOK AT ADJUSTING THE LOCATION OF THE | | | GENERATOR TO MINIMIZE THE NEED TO RELOCATE TREES AND | | | PRESERVE THE EXISTING TREES TO MEET THE INTENT OF | | | SECTION 94-448. | | | 7. SATISFIED. INDICATE ALL CHANGES TO THE PLANT LIST | | | WITH CLOUDING AND INDICATE THE LIMITS OF THE AFFECTED | | | AREAS ON THE LANDSCAPE PLAN AND SITE PLAN. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | PART B, GENERATOR AND CONNECTION ROAD: | | | | | | 1. THE HOMESAFE LANDSCAPE PLAN-1 WITH 4 TREES INDICATED | | | IN RED, 3 TO REMAIN AND I LIVE OAK TO BE REMOVED DOES | | | NOT MATCH HOMESAFE LANDSCAPE PLAN-2. LA-2 MITIGATION | | | LANDSCAPE PLAN DOES MATCH. | | | | | | 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD | | | CONDITION TO BE PRESERVED ON SITE OR RELOCATED. | | | ARBORIST LETTER SUPPLIED DOES NOT ADDRESS THE TREE | | | CONDITIONS AS REQUESTED BUT ASKS FOR AN EXCEPTION | | | BECAUSE OF THE TIME FRAME. THE LETTER ALSO REFERENCES 3 | | | MAHOGANY TREES, BUT THE PLAN INDICATES ONLY 2 MAHOGANY | | | TREES TO BE REMOVED, SM#3 AND SM#4. LIVE OAK TREES #5 | | | AND #6 ARE LISTED FOR REMOVAL, AND LIVE OAK TREES #1 | | | AND #3 ARE NOW LISTED FOR REMOVAL. IF TREES ARE TO BE | | | REMOVED, THERE MAY BE ADDITIONAL TREES REQUIRED. | | | | | | 3. IF THE 6 TREES IN COMMENT 3 ARE TO BE REMOVED, A | | | DISPOSITION CHART MUST BE PROVIDED WITH THE CANOPY | | | DIAMETERS AND CONDITION SUPPLIED. CANOPY MITIGATION | | | MUST BE CALCULATED AND TOTALED. MITIGATION SUPPLIED | | | MUST ALSO BE LISTED AND TOTAL SQUARE FOOTAGE PROVIDED. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
03-27-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
03-27-2020 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
03-27-2020 |
Time |
11:42 |
Sent To |
|
|
| Notes |
| 2020-03-27 11:42:53 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | MARCH 27, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. THE EXISTING TREE PLAN AND DISPOSITION | | | LIST ON SHEET L102B IS OUTDATED AND DOES NOT REFLECT | | | WHAT CURRENTLY EXISTS ON SITE. SUPPLY A CURRENT PLAN | | | AND IDENTIFY THE TREES WITHIN THE AFFECTED AREA ON THE | | | TREE DISPOSITION TABULAR LIST TO DISCERN THEM FROM THE | | | REST OF THE AREAS. | | | THE LAST APPROVED LANDSCAPE PLAN MUST BE THE BASE FOR | | | THE TREE LOCATIONS, AND THEN THE TREES THAT ARE TO BE | | | REMOVED OR RELOCATED ARE TO BE IDENTIFIED. THE APPROVED | | | LANDSCAPE PLAN FOR THE NORTH PROPERTY SHOULD BE USED TO | | | SHOW THE BUFFER TREES, AND THE ONES IDENTIFIED THAT ARE | | | TO BE REMOVED OR RELOCATED. GENERATOR SIDEWALK APPEARS | | | TO CONFLICT WITH SM#2. | | | | | | 2. SATISFIED. PROVIDE A CLEAR LOCATION OF WHERE ANY | | | RELOCATED TREES AND PALMS WILL BE PLACED ON THE SITE ON | | | THE LANDSCAPE PLAN. | | | SOME OF THE LABELED RELOCATIONS AND REPLACEMENTS ARE | | | NOT CONSISTENT WITH THE LABELS ON THE EXISTING TREE | | | PLAN. QV#1 AND QV#2 MUST BE SHOWN ON THE EXISTING TREE | | | PLAN, AND REPLACEMENT LOCATIONS SHOULD ONLY BE SHOWN ON | | | THE LANDSCAPE PLAN. QV3 IS SHOWN TWICE. | | | ALL FINAL LOCATIONS FOR TREES ARE TO BE SHOWN ON THE | | | LANDSCAPE PLAN INCLUDING FOR THE NORTH PROPERTY. | | | | | | 3. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. LIVE OAK TREES #5 AND #6 ARE LISTED FOR | | | REMOVAL, BUT CONDITION WAS NOT SUPPLIED. | | | EXPLANATION OF ADJUSTMENT TO AVOID GOOD TREES PROVIDED, | | | BUT CONDITION MUST BE LISTED IN THE TREE DISPOSITION | | | FOR ALL REMOVALS AND RELOCATIONS. | | | | | | 4. SATISFIED. PROVIDE A LANDSCAPE PLAN FOR THE PROPOSED | | | ACCESS DRIVEWAY AND SHOW ANY REMOVAL OR REPLACEMENT OF | | | TREES OR SHRUBS, INCLUDING THE NORTH PROPERTY. | | | PLAN SUPPLIED FOR SOUTH PROPERTY, BUT NOTHING IS SHOWN | | | FOR THE EXISTING BUFFER TREES ON THE ADJACENT PROPERTY | | | TO THE NORTH. IF THIS IS TO BE SHOWN ON THE MAJOR | | | AMENDMENT PLAN, INDICATE THIS ON THE SUBMITTED PLAN. | | | CODE REQUIRES THE ADJACENT PROPERTY TREES WITHIN 10 | | | FEET OF THE PROPERTY LINE TO BE SHOWN ON THE PROPOSED | | | PLAN PER SECTION 94-442(B)(2)Q. | | | APPROVED AND EXISTING TREES FOR THE NORTH PROPERTY HAVE | | | NOT BEEN SHOWN. | | | | | | 5. SATISFIED. THE GENERATOR LOCATION DOES NOT SHOW | | | DETAIL FOR THE LOCATION OF THE WALL DESCRIBED IN THE | | | NARRATIVE. LOCATION OF ACCESS DOORS NEEDS TO BE SHOWN, | | | AND THE HEDGE AND TREES ON THE NORTH SIDE OF THE | | | ENCLOSURE NEED TO BE SHOWN ON THE PLAN. | | | GENERATOR ENCLOSURE IS SHOWN CROSSING OVER THE PARCEL | | | LINE, SEE COMMENT#4. | | | | | | 6. SATISFIED. STAFF DOES NOT SUPPORT REMOVAL OF THE | | | MATURE BUFFER TREES ALONG THE NORTH PROPERTY LINE THAT | | | ARE PROVIDING SHADE FOR THE EXISTING PARKING AND | | | PROVIDE ALL THE BENEFITS OF A MATURE TREE CANOPY. THE | | | APPLICANT SHOULD LOOK AT ADJUSTING THE LOCATION OF THE | | | GENERATOR TO MINIMIZE THE NEED TO RELOCATE TREES AND | | | PRESERVE THE EXISTING TREES TO MEET THE INTENT OF | | | SECTION 94-448. | | | 7. SATISFIED. INDICATE ALL CHANGES TO THE PLANT LIST | | | WITH CLOUDING AND INDICATE THE LIMITS OF THE AFFECTED | | | AREAS ON THE LANDSCAPE PLAN AND SITE PLAN. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
02-28-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
02-28-2020 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
02-28-2020 |
Time |
13:45 |
Sent To |
|
|
| Notes |
| 2020-02-28 13:45:57 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | FEBRUARY 28, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. THIS COMMENT WAS MISTAKENLY MARKED AS SATISFIED ON | | | THE LAST REVIEW. NOT SATISFIED. THE EXISTING TREE PLAN | | | AND DISPOSITION LIST ON SHEET L102B IS OUTDATED AND | | | DOES NOT REFLECT WHAT CURRENTLY EXISTS ON SITE. SUPPLY | | | A CURRENT PLAN AND IDENTIFY THE TREES WITHIN THE | | | AFFECTED AREA ON THE TREE DISPOSITION TABULAR LIST TO | | | DISCERN THEM FROM THE REST OF THE AREAS. | | | THE LAST APPROVED LANDSCAPE PLAN MUST BE THE BASE FOR | | | THE TREE LOCATIONS, AND THEN THE TREES THAT ARE TO BE | | | REMOVED OR RELOCATED ARE TO BE IDENTIFIED. THE APPROVED | | | LANDSCAPE PLAN FOR THE NORTH PROPERTY SHOULD BE USED TO | | | SHOW THE BUFFER TREES, AND THE ONES IDENTIFIED THAT ARE | | | TO BE REMOVED OR RELOCATED. GENERATOR SIDEWALK APPEARS | | | TO CONFLICT WITH SM#2. | | | | | | 2. PARTIALLY SATISFIED. PROVIDE A CLEAR LOCATION OF | | | WHERE ANY RELOCATED TREES AND PALMS WILL BE PLACED ON | | | THE SITE ON THE LANDSCAPE PLAN. | | | SOME OF THE LABELED RELOCATIONS AND REPLACEMENTS ARE | | | NOT CONSISTENT WITH THE LABELS ON THE EXISTING TREE | | | PLAN. QV#1 AND QV#2 MUST BE SHOWN ON THE EXISTING TREE | | | PLAN, AND REPLACEMENT LOCATIONS SHOULD ONLY BE SHOWN ON | | | THE LANDSCAPE PLAN. QV3 IS SHOWN TWICE. | | | ALL FINAL LOCATIONS FOR TREES ARE TO BE SHOWN ON THE | | | LANDSCAPE PLAN INCLUDING FOR THE NORTH PROPERTY. | | | | | | 3. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. LIVE OAK TREES #5 AND #6 ARE LISTED FOR | | | REMOVAL, BUT CONDITION WAS NOT SUPPLIED. | | | EXPLANATION OF ADJUSTMENT TO AVOID GOOD TREES PROVIDED, | | | BUT CONDITION MUST BE LISTED IN THE TREE DISPOSITION | | | FOR ALL REMOVALS AND RELOCATIONS. | | | | | | 4. PARTIALLY SATISFIED. PROVIDE A LANDSCAPE PLAN FOR | | | THE PROPOSED ACCESS DRIVEWAY AND SHOW ANY REMOVAL OR | | | REPLACEMENT OF TREES OR SHRUBS, INCLUDING THE NORTH | | | PROPERTY. | | | PLAN SUPPLIED FOR SOUTH PROPERTY, BUT NOTHING IS SHOWN | | | FOR THE EXISTING BUFFER TREES ON THE ADJACENT PROPERTY | | | TO THE NORTH. IF THIS IS TO BE SHOWN ON THE MAJOR | | | AMENDMENT PLAN, INDICATE THIS ON THE SUBMITTED PLAN. | | | CODE REQUIRES THE ADJACENT PROPERTY TREES WITHIN 10 | | | FEET OF THE PROPERTY LINE TO BE SHOWN ON THE PROPOSED | | | PLAN PER SECTION 94-442(B)(2)Q. | | | APPROVED AND EXISTING TREES FOR THE NORTH PROPERTY HAVE | | | NOT BEEN SHOWN. | | | | | | 5. SATISFIED. THE GENERATOR LOCATION DOES NOT SHOW | | | DETAIL FOR THE LOCATION OF THE WALL DESCRIBED IN THE | | | NARRATIVE. LOCATION OF ACCESS DOORS NEEDS TO BE SHOWN, | | | AND THE HEDGE AND TREES ON THE NORTH SIDE OF THE | | | ENCLOSURE NEED TO BE SHOWN ON THE PLAN. | | | GENERATOR ENCLOSURE IS SHOWN CROSSING OVER THE PARCEL | | | LINE, SEE COMMENT#4. | | | | | | 6. SATISFIED. STAFF DOES NOT SUPPORT REMOVAL OF THE | | | MATURE BUFFER TREES ALONG THE NORTH PROPERTY LINE THAT | | | ARE PROVIDING SHADE FOR THE EXISTING PARKING AND | | | PROVIDE ALL THE BENEFITS OF A MATURE TREE CANOPY. THE | | | APPLICANT SHOULD LOOK AT ADJUSTING THE LOCATION OF THE | | | GENERATOR TO MINIMIZE THE NEED TO RELOCATE TREES AND | | | PRESERVE THE EXISTING TREES TO MEET THE INTENT OF | | | SECTION 94-448. | | | 7. SATISFIED. INDICATE ALL CHANGES TO THE PLANT LIST | | | WITH CLOUDING AND INDICATE THE LIMITS OF THE AFFECTED | | | AREAS ON THE LANDSCAPE PLAN AND SITE PLAN. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
12-18-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-18-2019 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-18-2019 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2019-12-18 09:50:49 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | DECEMBER 18, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. THE EXISTING TREE PLAN AND DISPOSITION | | | LIST ON SHEET L102B IS OUTDATED AND DOES NOT REFLECT | | | WHAT CURRENTLY EXISTS ON SITE. SUPPLY A CURRENT PLAN | | | AND IDENTIFY THE TREES WITHIN THE AFFECTED AREA ON THE | | | TREE DISPOSITION TABULAR LIST TO DISCERN THEM FROM THE | | | REST OF THE AREAS. | | | 2. PARTIALLY SATISFIED. PROVIDE A CLEAR LOCATION OF | | | WHERE ANY RELOCATED TREES AND PALMS WILL BE PLACED ON | | | THE SITE ON THE LANDSCAPE PLAN. | | | SOME OF THE LABELED RELOCATIONS AND REPLACEMENTS ARE | | | NOT CONSISTENT WITH THE LABELS ON THE EXISTING TREE | | | PLAN. QV#1 AND QV#2 MUST BE SHOWN ON THE EXISTING TREE | | | PLAN, AND REPLACEMENT LOCATIONS SHOULD ONLY BE SHOWN ON | | | THE LANDSCAPE PLAN. QV3 IS SHOWN TWICE. | | | | | | 3. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES | | | NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE | | | OR RELOCATED. LIVE OAK TREES #5 AND #6 ARE LISTED FOR | | | REMOVAL, BUT CONDITION WAS NOT SUPPLIED. | | | EXPLANATION OF ADJUSTMENT TO AVOID GOOD TREES PROVIDED, | | | BUT CONDITION MUST BE LISTED IN THE TREE DISPOSITION | | | FOR ALL REMOVALS AND RELOCATIONS. | | | | | | 4. PARTIALLY SATISFIED. PROVIDE A LANDSCAPE PLAN FOR | | | THE PROPOSED ACCESS DRIVEWAY AND SHOW ANY REMOVAL OR | | | REPLACEMENT OF TREES OR SHRUBS, INCLUDING THE NORTH | | | PROPERTY. | | | PLAN SUPPLIED FOR SOUTH PROPERTY, BUT NOTHING IS SHOWN | | | FOR THE EXISTING BUFFER TREES ON THE ADJACENT PROPERTY | | | TO THE NORTH. IF THIS IS TO BE SHOWN ON THE MAJOR | | | AMENDMENT PLAN, INDICATE THIS ON THE SUBMITTED PLAN. | | | CODE REQUIRES THE ADJACENT PROPERTY TREES WITHIN 10 | | | FEET OF THE PROPERTY LINE TO BE SHOWN ON THE PROPOSED | | | PLAN PER SECTION 94-442(B)(2)Q. | | | | | | 5. PARTIALLY SATISFIED. THE GENERATOR LOCATION DOES NOT | | | SHOW DETAIL FOR THE LOCATION OF THE WALL DESCRIBED IN | | | THE NARRATIVE. LOCATION OF ACCESS DOORS NEEDS TO BE | | | SHOWN, AND THE HEDGE AND TREES ON THE NORTH SIDE OF THE | | | ENCLOSURE NEED TO BE SHOWN ON THE PLAN. | | | GENERATOR ENCLOSURE IS SHOWN CROSSING OVER THE PARCEL | | | LINE, SEE COMMENT#4. | | | | | | 6. SATISFIED. STAFF DOES NOT SUPPORT REMOVAL OF THE | | | MATURE BUFFER TREES ALONG THE NORTH PROPERTY LINE THAT | | | ARE PROVIDING SHADE FOR THE EXISTING PARKING AND | | | PROVIDE ALL THE BENEFITS OF A MATURE TREE CANOPY. THE | | | APPLICANT SHOULD LOOK AT ADJUSTING THE LOCATION OF THE | | | GENERATOR TO MINIMIZE THE NEED TO RELOCATE TREES AND | | | PRESERVE THE EXISTING TREES TO MEET THE INTENT OF | | | SECTION 94-448. | | | 7. SATISFIED. INDICATE ALL CHANGES TO THE PLANT LIST | | | WITH CLOUDING AND INDICATE THE LIMITS OF THE AFFECTED | | | AREAS ON THE LANDSCAPE PLAN AND SITE PLAN. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
10-08-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-08-2019 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-08-2019 |
Time |
15:59 |
Sent To |
|
|
| Notes |
| 2019-10-08 16:01:15 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: MORSELIFE Z19090009 | | | OCTOBER 8, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. THE EXISTING TREE PLAN AND DISPOSITION LIST ON SHEET | | | L102B IS OUTDATED AND DOES NOT REFLECT WHAT CURRENTLY | | | EXISTS ON SITE. SUPPLY A CURRENT PLAN AND IDENTIFY THE | | | TREES WITHIN THE AFFECTED AREA ON THE TREE DISPOSITION | | | TABULAR LIST TO DISCERN THEM FROM THE REST OF THE | | | AREAS. | | | 2. PROVIDE A CLEAR LOCATION OF WHERE ANY RELOCATED | | | TREES AND PALMS WILL BE PLACED ON THE SITE ON THE | | | LANDSCAPE PLAN. | | | | | | 3. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD | | | CONDITION TO BE PRESERVED ON SITE OR RELOCATED. LIVE | | | OAK TREES #5 AND #6 ARE LISTED FOR REMOVAL, BUT | | | CONDITION WAS NOT SUPPLIED. | | | | | | 4. PROVIDE A LANDSCAPE PLAN FOR THE PROPOSED ACCESS | | | DRIVEWAY AND SHOW ANY REMOVAL OR REPLACEMENT OF TREES | | | OR SHRUBS, INCLUDING THE NORTH PROPERTY. | | | | | | 5. THE GENERATOR LOCATION DOES NOT SHOW DETAIL FOR THE | | | LOCATION OF THE WALL DESCRIBED IN THE NARRATIVE. | | | LOCATION OF ACCESS DOORS NEEDS TO BE SHOWN, AND THE | | | HEDGE AND TREES ON THE NORTH SIDE OF THE ENCLOSURE NEED | | | TO BE SHOWN ON THE PLAN. | | | | | | 6. STAFF DOES NOT SUPPORT REMOVAL OF THE MATURE BUFFER | | | TREES ALONG THE NORTH PROPERTY LINE THAT ARE PROVIDING | | | SHADE FOR THE EXISTING PARKING AND PROVIDE ALL THE | | | BENEFITS OF A MATURE TREE CANOPY. THE APPLICANT SHOULD | | | LOOK AT ADJUSTING THE LOCATION OF THE GENERATOR TO | | | MINIMIZE THE NEED TO RELOCATE TREES AND PRESERVE THE | | | EXISTING TREES TO MEET THE INTENT OF SECTION 94-448. | | | 7. INDICATE ALL CHANGES TO THE PLANT LIST WITH CLOUDING | | | AND INDICATE THE LIMITS OF THE AFFECTED AREAS ON THE | | | LANDSCAPE PLAN AND SITE PLAN. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
10-10-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
10-10-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-10-09 11:25:36 | NO COMMENTS. |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
12-12-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-12-2019 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-12-2019 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2019-12-12 11:56:26 | THE FOLLOWING COMMENT IS FROM THE REVIEW OF THE | | | DECEMBER 5, 2019 REVIEW SUBMITTAL PACKAGE: | | | | | | 1. MAINTAIN THE MINIMUM PERIMETER ELEVATION (USE THE | | | HIGHER OF TWO PROPERTIES) FOR THE DRIVE CONNECTION TO | | | THE PROPERTY TO THE NORTH UNLESS BOTH PROPERTIES SHARE | | | THE SAME STORMWATER MANAGEMENT SYSTEM AND WATER LEVELS | | | ON BOTH SIDES OF THE PROPERTY LINE ARE CONTROLLED BY | | | THE SAME CONTROL STRUCTURE. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
10-08-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-08-2019 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
10-08-2019 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2019-10-08 16:44:30 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | 1. IT APPEARS THE DRIVEWAY CONNECTION AND CONVERTING AN | | | INLET TO A MANHOLE WILL AFFECT DRAINAGE ALONG THE | | | COMMON PARCEL LINE. | | | | | | 2. THE SURFACE WATER MANAGEMENT SYSTEM NEEDS TO BE | | | DESIGNED TO CURRENT SFWMD CRITERIA. PROVIDE | | | CALCULATIONS SIGNED AND SEALED BY A PROFESSIONAL | | | ENGINEER SHOWING HOW THE PEAK STAGES AND PEAK | | | DISCHARGES ARE NOT AFFECTED BY THE FILLING OF THE LAKE | | | FOR THE AUDITORIUM BUILDING AND THE ADDITIONAL | | | IMPERVIOUS AREA. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION PRIOR | | | TO STARTING CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
02-26-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-02-26 13:51:49 | PASSED | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
01-09-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-01-09 10:44:26 | 1. PROVIDE PEDESTRIAN CONNECTION INCLUDING MARKED | | | CROSSWALK AND PEDESTRIAN ADA RAMPS ALONG THE PROPOSED | | | ACCESS ROAD CONNECTING TO EXISTING BUILDINGS. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
10-08-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-10-08 16:47:47 | SITE PLAN COMMENTS: | | | 1. PROVIDE PEDESTRIAN CONNECTION ALONG THE PROPOSED | | | ACCESS ROAD. | | | 2. CLARIFY THE LOCATIONS OF THE ACCESS GATE, IF ANY, | | | NEAR THE PROPOSED ACCESS ROAD. | | | 3. A MEDIAN/CURB SEPARATOR IS SHOWN IMMEDIATELY NORTH | | | OF THE PROPOSED ACCESS ROAD. PLEASE CLARIFY THE VEHICLE | | | CIRCULATION IN THIS AREA, AS WELL AS VEHICLE ACCESS TO | | | THE GATED AREA. | | | 4. CLARIFY IF A DITCH IS RUNNING UNDERNEATH THE | | | PROPOSED ACCESS ROAD. IF SO, A CULVERT STRUCTURE WOULD | | | BE REQUIRED. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
F |
Date |
04-30-2020 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
04-30-2020 |
Time |
16:58 |
Rev Time |
0.75 |
| Received By |
eschneid |
Date |
04-30-2020 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2020-04-30 16:56:45 | CASE NO. PB1248GG ? 3RD RESUBMITTAL REVIEW | | | MORSELIFE AUDITORIUM & GENERATOR | | | 4920 LORING DRIVE | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE | | | (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THE COMMENTS (BY JUNE 7, 2020), THE CASE | | | SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60). | | | | | | GENERATOR | | | | | | 1) UPDATED COMMENT: STAFF HAS REVIEWED THE BUILDING | | | PERMIT FOR THE GENERATOR. | | | | | | A. IN ORDER TO MATCH THE BUILDING PERMIT, THE MASTER | | | PLAN AND THE SITE PLAN NEED TO REFLECT THE GENERATOR | | | SLAB AT 49 FEET 6 INCHES X 14 FEET 6 INCHES (TO SCALE). | | | NOTE: THIS INCLUDES THE GENERATOR ENCLOSURE AND THE | | | STAIRS, WHICH MAY BE SHOWN SUPERIMPOSED ON THE SLAB AT | | | YOUR OPTION. REGARDLESS OF IF THE STAIRS ARE SHOWN | | | SUPERIMPOSED, THE WALKWAYS FROM THE STAIR BASES TO THE | | | CURB NEED TO BE SHOWN. CURRENTLY, THE PLANS DO NOT SHOW | | | THE OUTSIDE LIMITS OF THE SLAB. THIS ALSO NEEDS TO BE | | | SHOWN ON THE LANDSCAPE PLAN. | | | | | | B. THE OVERALL HEIGHT OF THE GENERATOR, INCLUDING THE | | | EXHAUST PIPE, IS 16.67 FEET. THE PLANS NEED TO INCLUDE | | | THIS CORRECT HEIGHT DIMENSION. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
03-23-2020 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
03-23-2020 |
Time |
10:35 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
03-23-2020 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2020-03-23 14:55:18 | 1) ON THE BUILDING PERMIT SUBMITTAL, THE LIFE SAFETY | | | PLAN, FLOOR PLAN AND ELEVATIONS SHOW ONLY ONE DOOR ON | | | THE WEST FACADE OF THE BUILDING. THE SITE PLAN THAT YOU | | | SUBMITTED SHOWS TWO ENTRY POINTS, PLEASE CORRECT TO | | | BRING IN LINE WITH THE PERMIT PLANS. | | | | | | 2) THE CIVIL PLANS (BOTH SUBMITTED WITH THE ZONING | | | APPLICATION AND THE BUILDING PERMIT) SHOW 16 FOOT DEEP | | | PARKING SPACES WITH A TWO FOOT SIDEWALK OVERHANG | | | INSTEAD OF WHEEL STOPS ON THE EAST SIDE OF THE | | | AUDITORIUM. THE SITE PLAN THAT YOU SUBMITTED SHOWS THE | | | TRADITIONAL 18 FOOT DEEP SPACES WITH WHEEL STOPS, | | | PLEASE CORRECT TO BRING IN LINE WITH THE PERMIT PLANS. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
03-05-2020 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
03-05-2020 |
Time |
13:09 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
03-04-2020 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2020-03-05 13:12:10 | CASE NO. PB1248GG - 2ND RESUBMITTAL REVIEW | | | MORSELIFE AUDITORIUM & GENERATOR | | | 4920 LORING DRIVE | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE | | | (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THE COMMENTS (BY MAY 7, 2020), THE CASE | | | SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT SINCE PREVIOUSLY-ISSUED COMMENTS | | | WERE NOT ADDRESSED, THE APPLICANT IS ASSESSED A | | | RESUBMITTAL FEE. SUCH FEE IS 20% OF THE ORIGINAL | | | APPLICATION FEE ($60). | | | | | | GENERATOR | | | | | | 1) UPDATED COMMENT: THE MASTER PLAN AND SITE PLAN SHOW | | | THE GENERATOR ENCLOSURE (INCLUDING THE STAIRS) | | | DIMENSION AS 24 FEET X 50 FEET AND 15 FEET IN HEIGHT. | | | NO DIMENSIONS ARE PROVIDED ON THE CIVIL PLAN. THE | | | GENERATOR ENCLOSURE DRAWING SHOWS THE DIMENSIONS AS 14 | | | FEET X 47.35 FEET AND 16.67 FEET IN HEIGHT. THE PLANS | | | DO NOT SHOW THE GENERATOR ENCLOSURE AS THAT LARGE (IT | | | SCALES TO MATCH THE ENCLOSURE DRAWING). THE PLANS NEED | | | TO CLEARLY STATE THE CORRECT GENERATOR ENCLOSURE | | | DIMENSIONS. | | | | | | 2) UPDATED COMMENT: THE PROPOSED GENERATOR IS | | | STRADDLING THE PROPERTY LINE BETWEEN THE MORSELIFE SITE | | | AND THE FORMER HOMESAFE SITE. THIS WILL NEED TO BE | | | ADDRESSED AS A SPECIFIC DEVELOPMENT REGULATION | | | ALLOWANCE WITH THE FORTHCOMING MAJOR PLANNED | | | DEVELOPMENT AMENDMENT FOR THE PACE RELOCATION AND | | | HOSPICE CONSTRUCTION. STAFF IS UNCLEAR IF YOU ARE | | | CONTINUING TO INCLUDE THE GENERATOR WITH THIS | | | SUBMITTAL. AT THE PPRC MEETING FOR THE AUDITORIUM IT | | | WAS DISCUSSED THAT THE GENERATOR WOULD NO LONGER BE | | | WITH THIS MINOR AMENDMENT. PLEASE CLARIFY. | | | | | | 3) NEW COMMENT: THE EXISTING TREE PLAN IS NOT THE PLAN | | | (SHEET L102B) SHOWING THE CURRENTLY INSTALLED | | | CONDITIONS BASED ON THE RYNA GREENBAUM DRIVE | | | RECONFIGURATION. IT SHOWS PRE-RYNA GREENBAUM | | | CONDITIONS. USE THE CURRENT LANDSCAPE PLAN AS THE BASE. | | | | | | CONNECTION | | | | | | 4) REPEAT COMMENT: NO LANDSCAPE PLAN SHOWING THE AREA | | | AROUND THE CONNECTION WAS PROVIDED. THE ONLY PLAN | | | PROVIDED IS A TREE MITIGATION PLAN (SHEET LA-2 MIT). | | | THE MITIGATION PLAN DOES NOT ACCURATELY SHOW THE | | | LANDSCAPE ON THE HOMESAFE SIDE OF THE PROPERTY LINE (AS | | | SHOWN ON THE APPROVED LANDSCAPE PLAN AND THE PALM BEACH | | | COUNTY PICTOMETRY PHOTOS). THE LANDSCAPE PLAN NEEDS TO | | | SHOW CODE COMPLIANT LANDSCAPE FOR THE FINAL CONNECTION | | | LAYOUT - EX. THE TERMINAL ISLAND ADJACENT TO THE NEW | | | CONNECTION IS REQUIRED TO HAVE A TERMINAL ISLAND TREE. | | | | | | 5) NEW COMMENT: THE COMMENT RESPONSE STATES THAT THE | | | MITIGATION WILL BE SHOWN ON THE MAJOR AMENDMENT. YOU | | | ARE REQUIRED TO PROVIDE THE MITIGATION FOR THE TREES | | | REMOVED AS PART OF THIS PROJECT WITH THIS APPLICATION. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
01-08-2020 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
01-08-2020 |
Time |
08:38 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
01-07-2020 |
Time |
09:50 |
Sent To |
|
|
| Notes |
| 2020-01-08 08:38:23 | CASE NO. PB1248GG - 1ST RESUBMITTAL REVIEW | | | MORSELIFE AUDITORIUM & GENERATOR | | | 4920 LORING DRIVE | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE | | | (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM | | | THE DATE OF THE COMMENTS (BY MARCH, 7, 2020), THE CASE | | | SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL | | | REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF | | | PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE | | | SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED | | | A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL | | | APPLICATION FEE ($60). | | | | | | GENERATOR | | | | | | 1) UPDATED COMMENT: THE MASTER PLAN PROVIDES THE | | | GENERATOR ENCLOSURE DIMENSION AS 24 FEET X 50 FEET, YET | | | NONE OF THE PLANS SHOW THE GENERATOR ENCLOSURE AS THAT | | | LARGE. THE PLANS SEEM TO SHOW THE SAME SIZED GENERATOR | | | ALL IN THE SAME LOCATION, BUT STAFF IS UNABLE TO VERIFY | | | DUE TO THE CONFLICTING INFORMATION. THE PLANS NEED TO | | | CLEARLY SHOW GENERATOR ENCLOSURE DIMENSIONS | | | | | | 2) REPEAT COMMENT: THE PLANS NEED TO INDICATE THE 12 | | | FOOT TALL GENERATOR WALLS AND WHERE THE GATE OPENINGS | | | ARE. NO DETAIL OF THE GENERATOR ENCLOSURE, INCLUDING | | | THE GENERATOR AND THE WALLS, WAS PROVIDED. | | | | | | 3) REPEAT COMMENT: THE PLANS NEED TO SHOW THE DIMENSION | | | OF THE GENERATOR WALL FROM THE END OF THE PARKING | | | SPACES AND DRIVE AISLE CURB LINE. THIS NEEDS TO BE A | | | MINIMUM OF FIVE (5) FEET TO INCLUDE THE LANDSCAPE | | | SCREENING LISTED IN THE JUSTIFICATION LETTER. PLEASE | | | REMEMBER THAT THE PARKING SPACES ALONG RYNA GREENBAUN | | | DRIVE WERE CONSTRUCTED WITH THE TWO (2) FOOT OVERHANG, | | | SO THIS OFF SET NEEDS TO BE INCLUDED SEVEN (7) FEET | | | TOTAL. NO DIMENSIONS SHOWN ON THE PLANS. | | | | | | 4) UPDATED COMMENT: THE PROPOSED GENERATOR IS | | | STRADDLING THE PROPERTY LINE BETWEEN THE MORSELIFE SITE | | | AND THE FORMER HOMESAFE SITE. THIS WILL NEED TO BE | | | ADDRESSED AS A SPECIFIC DEVELOPMENT REGULATION | | | ALLOWANCE WITH THE FORTHCOMING MAJOR PLANNED | | | DEVELOPMENT AMENDMENT FOR THE PACE RELOCATION AND | | | HOSPICE CONSTRUCTION. STAFF NEEDS TO REVIEW THE | | | GENERATOR ENCLOSURE DETAIL (COMMENT #2) TO DETERMINE | | | HOW THIS WILL BE ADDRESSED WITH THE MAJOR PLANNED | | | DEVELOPMENT. | | | | | | CONNECTION | | | | | | 5) UPDATED COMMENT: NO LANDSCAPE PLAN SHOWING THE AREA | | | AROUND THE CONNECTION WAS PROVIDED. THE LANDSCAPE ON | | | THE NORTHERN PARCEL IS NOT SHOWN. | | | | | | GENERAL | | | | | | 6) REPEAT COMMENT: WHERE IS THE "HOMESAFE OFFICE" | | | REFERRED TO ON THE MASTER SITE DATA TABLE? THIS 6,111 | | | SQUARE FOOT BUILDING DOES NOT APPEAR ON THE MASTER | | | PLAN. THE 12,200 SQUARE FEET ON THE NORTH PARCEL | | | INCLUDE THE THREE BUILDINGS WHICH CURRENTLY EXIST. THIS | | | WAS NOT REMOVED FROM THE MASTER SITE DATA TABLE (AND IS | | | STILL SHOWN ON THE HOSPICE/PACE EXPANSION MAJOR | | | AMENDMENT MASTER SITE DATA TABLE). | | | | | | 7) REPEAT COMMENT: THE HOUSING BREAKDOWN TABLE HAS | | | ADDED 10 BEDS UNDER THE TRADITION PHASE II RESIDENTIAL | | | LINE ITEM WHICH PREVIOUSLY DID NOT EXIST. THESE HOSPICE | | | BEDS WERE NOT REMOVED FROM THE HOUSING BREAKDOWN TABLE. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
10-09-2019 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
10-09-2019 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
10-09-2019 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2019-10-09 14:38:41 | CASE NO. PB1248GG | | | MORSELIFE AUDITORIUM & GENERATOR | | | 4920 LORING DRIVE | | | | | | - CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | | | | - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE | | | (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT | | | OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THE PPRC MEETING (BY DECEMBER 10, | | | 2019), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY | | | FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT | | | APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60). | | | | | | 1) THE CHECK SUBMITTED WITH THE ORIGINAL APPLICATION | | | DID NOT COVER THE FULL FEES FOR THE APPLICATION. YOU | | | STILL OWE THE CITY $1,288. PLEASE SEE THE PREVIOUS | | | E-MAIL TO ALEX AHRENHOLZ FOR THE BACK UP ON THE FEE | | | CALCULATION. | | | | | | AUDITORIUM | | | | | | 2) IT APPEARS THERE ARE TWO WALKWAYS LEADING TO THE | | | SIDEWALK ON THE EAST SIDE OF THE PROPOSED AUDITORIUM | | | THAT ARE NOT SHOWN ON THE CIVIL PLAN. | | | | | | 3) PROVIDE VERIFICATION FROM THE CITY'S BUILDING | | | DIVISION THAT THE ENTRIES SHOWN ON THE EAST SIDE OF THE | | | AUDITORIUM DO NOT REQUIRE THE ADDITION OF ADA PARKING | | | SPACES. | | | | | | GENERATOR | | | | | | 4) THE PLANS NEED TO INCLUDE THE GENERATOR ENCLOSURE | | | DIMENSIONS. IT IS UNCLEAR FROM THE PROVIDED PLANS IF | | | THE GENERATOR "BOX" IS THE PAD OR THE ENCLOSURE WALLS. | | | | | | 5) THE PLANS NEED TO INDICATE THE 12 FOOT TALL | | | GENERATOR WALLS AND WHERE THE GATE OPENINGS ARE. | | | | | | 6) THE PLANS NEED TO SHOW THE DIMENSION OF THE | | | GENERATOR WALL FROM THE END OF THE PARKING SPACES AND | | | DRIVE AISLE CURB LINE. THIS NEEDS TO BE A MINIMUM OF | | | FIVE (5) FEET TO INCLUDE THE LANDSCAPE SCREENING LISTED | | | IN THE JUSTIFICATION LETTER. PLEASE REMEMBER THAT THE | | | PARKING SPACES ALONG RYNA GREENBAUN DRIVE WERE | | | CONSTRUCTED WITH THE TWO (2) FOOT OVERHANG, SO THIS OFF | | | SET NEEDS TO BE INCLUDED. THE LANDSCAPE PLAN APPEARS TO | | | ONLY HAVE A FOUR (4) FOOT PLANTING AREA DUE TO THE | | | PROXIMITY TO THE OVERHANG. | | | | | | 7) IT APPEARS THAT THE GENERATOR "BOX" IS SHOWN | | | DIFFERENTLY (SIZE AND SETBACKS) ON THE MASTER PLAN, | | | LANDSCAPE PLAN AND THE CIVIL PLAN. IT CLEARLY AVOIDS | | | THE 12 FOOT UTILITY EASEMENT ON THE CIVIL PLAN, BUT | | | SINCE THIS EASEMENT IS NOT SHOWN ON THE MASTER PLAN OR | | | THE LANDSCAPE PLAN, STAFF IS UNABLE TO TELL IF THE | | | GENERATOR ENCLOSURE IS LOCATED OUTSIDE OF THE EASEMENT. | | | | | | 8) THE LANDSCAPE SCREEN HEDGE IS NOT PROVIDED ON THE | | | NORTH SIDE OF THE GENERATOR ENCLOSURE. | | | | | | 9) THE RELOCATED FENCE IS NOT SHOWN ON THE LANDSCAPE | | | PLAN OR THE MASTER PLAN. | | | | | | 10) THE PROPOSED GENERATOR IS STRADDLING THE PROPERTY | | | LINE BETWEEN THE MORSELIFE SITE AND THE FORMER HOMESAFE | | | SITE. THIS WILL NEED TO BE ADDRESSED AS A SPECIFIC | | | DEVELOPMENT REGULATION ALLOWANCE WITH THE FORTHCOMING | | | MAJOR PLANNED DEVELOPMENT AMENDMENT FOR THE PACE | | | RELOCATION AND HOSPICE CONSTRUCTION. | | | | | | CONNECTION | | | | | | 11) A PEDESTRIAN ROUTE, SEPARATED FROM THE VEHICULAR | | | TRAVEL LANES, NEEDS TO BE INCLUDED WITH THE VEHICULAR | | | CONNECTION BETWEEN THE TWO SITES. THE PEDESTRIAN ROUTE | | | NEEDS TO CONNECT THE SIDEWALK NETWORK ON THE MORSELIFE | | | SITE WITH THE SIDEWALK NETWORK ON THE FORMER HOMESAFE | | | SITE. | | | | | | 12) THE RESUBMITTED MASTER PLAN AND CIVIL PLAN NEED TO | | | SHOW THE FINAL CONNECTION LAYOUT WITHOUT THE EXISTING | | | CURBS, PARKING SPACES, ETC., SINCE THIS WILL BE THE | | | APPROVED LAYOUT. | | | | | | 13) PLEASE CLARIFY IF THE DIVIDER MEDIAN IN THE DRIVE | | | AISLE BY THE NEW VEHICULAR CONNECTION IS BEING REMOVED. | | | THE LINE WORK ON THE CIVIL PLAN SEEMS TO INDICATE THIS, | | | BUT IT IS NOT NOTED ON THE PLAN. | | | | | | 14) NO LANDSCAPE PLAN SHOWING THE AREA AROUND THE | | | CONNECTION WAS PROVIDED. | | | | | | 15) SHOW THE PROPOSED GATE DETAILS AT THE CONNECTION. | | | | | | GENERAL | | | | | | 16) WHERE IS THE "HOMESAFE OFFICE" REFERRED TO ON THE | | | MASTER SITE DATA TABLE? THIS 6,111 SQUARE FOOT BUILDING | | | DOES NOT APPEAR ON THE MASTER PLAN. THE 12,200 SQUARE | | | FEET ON THE NORTH PARCEL INCLUDE THE THREE BUILDINGS | | | WHICH CURRENTLY EXIST. | | | | | | 17) THE HOUSING BREAKDOWN TABLE HAS ADDED 10 BEDS UNDER | | | THE TRADITION PHASE II RESIDENTIAL LINE ITEM WHICH | | | PREVIOUSLY DID NOT EXIST. WHAT ARE THESE? IF BEDS HAVE | | | BEEN ADDED AT THE EXPENSE OF UNITS, THEN THE UNIT COUNT | | | NEEDS TO BE REDUCED ACCORDINGLY. NOTE: THERE ARE ONLY 4 | | | UNITS AVAILABLE TO CONVERT TO BEDS IN THE PROJECT IF | | | THE NUMBER OF UNITS IN TRADITIONS PHASE II REMAINS AT | | | 182. | | | |
|
|
| |