Plan Review Details - Project Z19050027
| Plan Review Stops For Project Z19050027 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
06-11-2019 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
06-11-2019 |
Time |
21:05 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
06-11-2019 |
Time |
21:05 |
Sent To |
|
|
| Notes |
| 2019-06-11 21:10:26 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. ACCESSIBLE ROUTE. WHEN SUBMITTED FOR PERMIT, THE | | | PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE ROUTE, | | | COMPLYING WITH SECTIONS 206.2 AND 402.2 OF FLORIDA | | | ACCESSIBILITY CODE, FROM THE PUBLIC RIGHT-OF-WAY TO ALL | | | ACCESSIBLE BUILDING OR FACILITY ENTRANCES. | | | | | | 4. ACCESSIBLE ROUTE BETWEEN BUILDINGS. WHEN SUBMITTED | | | FOR PERMIT THET PLANS SHALL SHOW AT LEAST ONE | | | ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS 206.2 AND | | | 402.2 OF FLORIDA ACCESSIBILITY CODE, CONNECTING | | | ACCESSIBLE BUILDING OR FACILITY ENTRANCES WITH ALL | | | ACCESSIBLE SPACES AND ELEMENTS WITHIN THE BUILDING OR | | | FACILITY | | | | | | 5. RAMP. SITE PLAN, SHEET 1, SEEMS TO SHOW A RAMP UP TO | | | THE COVERED PATIO BUT THE RAMP IS NOT LABELED ON THE | | | PLAN. WHEN SUBMITTED FOR PERMIT THE RAMP SHALL BE | | | LABELED AND DETAILS PROVIDED. ANY PART OF AN ACCESSIBLE | | | ROUTE WITH A SLOPE GREATER THAN 1:20 SHALL BE | | | CONSIDERED A RAMP AND SHALL COMPLY WITH SECTION 405 OF | | | FLORIDA ACCESSIBILITY CODE. | | | | | | 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
03-13-2020 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
03-13-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
03-13-2020 |
Time |
|
Sent To |
I |
|
| Notes |
| 2020-03-13 08:16:00 | PASSED WITH PROVISOS: | | | | | | GENERAL: | | | RESPOND TO ALL COMMENTS IN WRITING. | | | SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29) ON ALL RELEVANT SHEETS. | | | | | | COVER SHEET : | | | ADD PROJECT ADDRESS. | | | | | | SHEET 9: | | | PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND LEAD-FREE BACKFLOW PREVENTION. | | | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | PROVIDE PROFILES AT ALL UTILITY CONFLICTS/CROSSINGS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO, PROJECT COORDINATOR, ENGINEERING SERVICES | | | DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR WPB, FL 33401 (MAILING | | | ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 MOBILE: (561) 246-9525 | | | EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
P |
Date |
06-07-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
06-07-2019 |
Time |
|
Rev Time |
|
| Received By |
mgonzale |
Date |
06-07-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-23 14:04:11 | APPROVED WITH PROVISOS: | | | | | | #1 WATER LINES MAY NEED TO CONNECT FURTHER NORTH TO | | | EXISTING CITY WATERMAIN RATHER THAN HYDRANT LEG. THIS | | | WOULD AVOID ANY DISRUPTION OF PRIVATE FIRELINE | | | PRESSURES. | | | | | | #2 ADA ACCESS FROM ENTRANCE WILL BE REQUIRED. MAY | | | REQUIRE A ROW PERMIT. | | | | | | NO FURTHER COMMENTS. | | | | | | MANUEL GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | [email protected] | | | (561) 494-1085 | | | | | | | | | | | | | | | | | | | | 2019-06-07 08:10:52 | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS | | | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE | | | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER | | | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT | | | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: | | | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W | | | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P | | | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 | | | 60045731D3658206F27451722716EF | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, | | | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, | | | 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | | | | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG | | | ENTIRE PROJECT FRONTAGE. | | | | | | CONFIRM EXISTING SANITARY SEWER PIPE SIZE AND MATERIAL | | | ON DE SOTA RD. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST | | | FOR ALL CITY OF WEST PALM BEACH-OWNED UTILITIES WITHIN | | | THE PUBLIC RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE | | | LIMITS OF YOUR PROJECT. IDENTIFY TYPE OF UTILITY, | | | LOCATION, PIPE MATERIAL, AGE AND SIZE. PLEASE CONTACT | | | JANICE TARBILL IN THE WPB ENGINEERING SERVICES | | | DEPARTMENT AT [email protected] OR 561-494-1079 FOR | | | FURTHER ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR | | | INFORMATION ONLY. FIELD VERIFY UTILITY LOCATIONS USING | | | FIELD SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF | | | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND | | | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER | | | OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL | | | UTILITY CROSSINGS. | | | | | | SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29). | | | | | | CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY | | | ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY | | | RIGHT OF WAY. | | | | | | PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE | | | DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB | | | DEVELOPMENT APPLICATION). | | | | | | PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED | | | AREAS. | | | | | | PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION | | | OF WATER METER AND BACKFLOW PREVENTION. | | | | | | PER CITY ORDINANCE, ALL PROPOSED BACKFLOWS ARE TO BE | | | LOCATED AT POINT OF SERVICE JUST INSIDE THE PROPERTY | | | LINE. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | CENTRAL OPERATIONS CENTER (DISPATCH): | | | 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
06-04-2019 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
06-04-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
06-04-2019 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2019-06-04 12:30:08 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | A PERMIT IS REQUIRED FOR ANY PROPOSED CONTRUCTION | | | FENCING. ENSURE THAT A 20' FD ACCESS WIDTH IS PROVIDED | | | WITH A RECOMMENDED KNOX PADLOCK FOR 24 EMERGNECY | | | ACCESS. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | THE EXSITING FIRE HYDRANT LOCATION IS ACCEPTABLE. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
03-13-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
03-13-2020 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
03-13-2020 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2020-03-13 13:24:00 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: SOUTH OLIVE TENNIS CENTER Z19050027 | | | MARCH 12, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. PROPOSED LANDSCAPE TERMINAL ISLANDS DO | | | NOT MEET THE CODE REQUIREMENTS OF SECTION 94-443(C)(3) | | | A. FOR LANDSCAPE AREA WIDTH OF 8 FEET FOR THE FULL | | | LENGTH OF THE PARKING SPACE, AND THE REQUIRED TREE MUST | | | BE PROVIDED. THE PAVED ADA SPACES ARE ADJACENT TO A | | | GRASS AREA, WHICH CONFLICTS WITH THE REQUIREMENT FOR | | | LANDSCAPE AREAS TO BE PROTECTED WITH CURBS. | | | | | | 2. SATISFIED. SHOW THE EXISTING TREES TO REMAIN ON THE | | | LANDSCAPE PLAN CLEARLY AND IDENTIFY THEM WITH TAGS. | | | | | | 3. SATISFIED. INDICATE LOCATIONS OF TREE PROTECTION ON | | | THE PLAN. | | | | | | 4. SATISFIED. CORRECT ZAMIA FURFURACEA TO NONNATIVE OR | | | CHANGE SPECIES TO PUMILA THAT IS NATIVE. | | | | | | 5. SATISFIED. CHOOSE ONE MINIMUM HEIGHT SPECIFICATION | | | FOR THE SIMPSON?S STOPPER AND SILVER BUTTONWOOD TREES. | | | THE CODE ALLOWS FOR SOME VARIATION ON THE 12 FOOT | | | HEIGHT REQUIREMENT FOR NATIVE TREES WITH GOOD REASON. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
06-06-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-06-2019 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-06-2019 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2019-06-06 16:54:19 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: SOUTH OLIVE TENNIS CENTER Z19050027 | | | JUNE 6, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. PROPOSED LANDSCAPE TERMINAL ISLANDS DO NOT MEET THE | | | CODE REQUIREMENTS OF SECTION 94-443(C)(3) A. FOR | | | LANDSCAPE AREA WIDTH OF 8 FEET FOR THE FULL LENGTH OF | | | THE PARKING SPACE, AND THE REQUIRED TREE MUST BE | | | PROVIDED. THE PAVED ADA SPACES ARE ADJACENT TO A GRASS | | | AREA, WHICH CONFLICTS WITH THE REQUIREMENT FOR | | | LANDSCAPE AREAS TO BE PROTECTED WITH CURBS. | | | | | | 2. SHOW THE EXISTING TREES TO REMAIN ON THE LANDSCAPE | | | PLAN CLEARLY AND IDENTIFY THEM WITH TAGS. | | | | | | 3. INDICATE LOCATIONS OF TREE PROTECTION ON THE PLAN. | | | | | | 4. CORRECT ZAMIA FURFURACEA TO NONNATIVE OR CHANGE | | | SPECIES TO PUMILA THAT IS NATIVE. | | | | | | 5. CHOOSE ONE MINIMUM HEIGHT SPECIFICATION FOR THE | | | SIMPSON?S STOPPER AND SILVER BUTTONWOOD TREES. THE CODE | | | ALLOWS FOR SOME VARIATION ON THE 12 FOOT HEIGHT | | | REQUIREMENT FOR NATIVE TREES WITH GOOD REASON. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
03-13-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
03-13-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
03-13-2020 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
06-04-2019 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-04-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
06-04-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-04 14:36:43 | PLEASE PROVIDE A PLAN SHOWING AUTO-TURN FOR SANITATION | | | SERVICE ALONG WITH THE ENSLOSURE SPEC. | | | | | | MATT HEJAZI | | | DEPT. OF PUBLIC WORKS | | | [email protected] | | | 561-822-2045 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
P |
Date |
03-16-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
03-16-2020 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
03-16-2020 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2020-03-16 14:42:24 | ON MARCH 16, 2020, THE CITY'S PROJECT MANAGER EMAILED A | | | REVISED SURVEY LISTING THE NGVD-NAVD VERTICAL DATUM | | | CONVERSION FACTOR AS 1.52 FEET AND A LETTER FROM THE | | | ARCHITECT THAT THE REMAINING COMMENTS WILL BE ADDRESSED | | | FOR THE ENGINEERING PERMIT APPLICATION SUBMITTAL. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
03-12-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
03-12-2020 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
03-12-2020 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2020-03-12 16:59:42 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | FEBRUARY 2020 DATED CIVIL PLANS: | | | | | | 1. THE CITY'S VERTICAL DATUM IS NGVD1929. THE | | | ENGINEERING PLANS ARE USING NAVD1988. LIST FHE VERTICAL | | | DATUM BASIS AND CONVERSION EQUATION TO NGVD1929 ON | | | EVERY SHEET WITH ELEVATION INFORMATION, INCLUDING THE | | | SURVEY. [REPEAT COMMENT] | | | | | | 2. ADJUST THE SILT FENCE TO INCLUDE THE NEW WATER MAIN | | | CONSTRUCTION. [REPEAT COMMENT] | | | | | | 3. STORMWATER WATER QUALITY TREATMENT AND PEAK FLOW | | | ATTENUATION TO BE PROVIDED FOR THE NEW CONSTRUCTION. | | | [REPEAT COMMENT] | | | | | | 4. CONFLICTING CALLOUTS FOR STOIRM PIPE MATERIAL FOR | | | CONSTRUCTING THE PIPE (RCP) AND CONNECTING TO CATCH | | | BASINS (PVC). | | | | | | 5. CLEANOUT CALLED OUT FOR ROOF DRAIN LATERAL | | | CONNECTION TO RCP PIPE. | | | | | | 6. ADD THE CITY'S PROJECT NUMBER TO THE COVER SHEET. | | | | | | 7. SHOW LIMITS OF CONCRETE REPLACEMENT ALONG EAST SIDE | | | OF TENNIS COURTS WHERE THE SANITARY SEWER IS BEING | | | INSTALLED. | | | | | | 8. IS SILT FENCE NEEDED ALONG THE EAST SIDE OF THE | | | TENNIS COURTS? | | | | | | 9. WHERE IS DRAINAGE STRUCTURE S-2? | | | | | | 10. REPLACE THE WATER MAIN BETWEEN THE PROPOSED 6" X 6" | | | X 2" TEE AND THE PROPOSED 45-DEGREE BEND. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
06-10-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-10-2019 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-10-2019 |
Time |
18:46 |
Sent To |
|
|
| Notes |
| 2019-06-10 18:46:32 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE EXISTING SURVEY AND CIVIL PLANS DO NOT LIST THE | | | VERTICAL DATUM REFERENCE. THE CITY?S VERTICAL DATUM IS | | | NGVD 1929. THE CITY HAS ALLOWED THE USE OF NAVD 1988 | | | PROVIDED THE CONVERSION EQUATION TO NGVD 1929 IS | | | PROVIDED ON THE SHEET(S). | | | | | | 2. IT APPEARS THE WATER MAIN REPLACEMENT WILL GO | | | OUTSIDE THE FENCED CONSTRUCTION AREA. ADJUST THE SILT | | | FENCE TO OUTSIDE THE CONSTRUCTION LIMITS. | | | | | | 3. THE EXISTING STORMWATER SYSTEM WILL NEED TO BE | | | RELOCATED FROM UNDER THE PROPOSED RESTROOM BUILDING. | | | | | | 4. STORMWATER WATER QUALITY TREATMENT AND PEAK FLOW | | | ATTENUATION TO BE PROVIDED FOR THE NEW CONSTRUCTION. | | | | | | 5. CAN HANDBALL COURT PAVEMENT BE REMOVED TO REDUCE THE | | | AMOUNT OF IMPERVIOUSNESS? | | | | | | 6. CALLOUT/LABEL ROOT BARRIERS ON THE LANDSCAPE PLANS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING | | | CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
03-16-2020 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
03-16-2020 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
06-07-2019 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
06-07-2019 |
Time |
12:36 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-07 12:51:42 | 1. PROVIDE COPY OF SIGNED AND SEALED SURVEY. | | | 2. SHOW VERTICAL DATUM ON ALL PLANS. | | | 3. SHOW CONNECTION TO EXISTING SANITARY TO SEE IF | | | PROPOSED SANITARY IS FEASIBLE. | | | 4. RE-ROUTE EXISTING STORM FROM UNDER PROPOSED | | | RESTROOMS. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
03-17-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-03-17 11:50:03 | PASSED. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
06-12-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-06-12 11:26:47 | 1. PROVIDE BICYCLE PARKING. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
06-12-2019 |
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
06-12-2019 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
06-12-2019 |
Time |
10:19 |
Sent To |
|
|
| Notes |
| 2019-06-12 10:20:05 | SOUTH OLIVE TENNIS CENTER INFORMAL SITE PLAN REVIEW | | | ISPR 19-04 | | | Z19050027 | | | | | | ---PROVIDE A SITE PLAN (SEPARATE FROM ENGINEERING | | | PLANS) THAT SATISFIES THE REQUIREMENTS LISTED IN THE | | | DEVELOPMENT APPLICATION. ALSO PROVIDE AN OVERALL SITE | | | PLAN WHICH CONSIDERS HOW THE SITE FUNCTIONS AS A WHOLE | | | | | | ---IT IS UNCLEAR WHY THE UNIMPROVED GRASS AREA IS BEING | | | USED AS A PARKING LOT, WHILE THERE EXISTS A DESIGNATED, | | | PAVED AND STRIPED EXISTING PARKING LOT TO THE EAST OF | | | THE FACILITY. PARKING ON THE GRASS AREA SHOULD BE | | | DISCOURAGED BY ERECTING A FENCE AND/OR HEDGE ALONG | | | SUMMA STREET WHICH WILL PROHIBIT ACCESS TO THE GRASSED | | | AREA AND ENHANCE SUMMA STREET | | | | | | ---ADD PEDESTRIAN CONNECTIONS FROM THE PARKING AREA TO | | | THE FACILITY, AND BETWEEN THE PROPOSED BUILDING AND | | | RESTROOM BUILDING. CROSSWALKS SHOULD BE PROVIDED WHERE | | | PEDESTRIANS WILL ACCESS THE SITE FROM THE DESIGNATED | | | PARKING LOT | | | | | | ---ADD STRATEGICALLY PLACED BICYCLE RACKS NEAR BUILDING | | | ENTRIES PER SECTION 94-485, ZLDR | | | | | | ---CONSIDER ADDING AND/OR STRIPING DESIGNATED DROP OFF | | | SPACES OFF OF THE EXISTING CUL DE SAC TO ALLOW FOR SAFE | | | AND EFFICIENT LOADING AND UNLOADING | | | | | | ---CONSIDER ADDING A LANDSCAPE FEATURE IN THE CENTER | | | ISLAND OF THE CUL DE SAC THAT WILL ENHANCE THE SITE AND | | | PROVIDE A FOCAL POINT ENTERING THE FACILITY | | | | | | ---PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC | | | UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT | | | ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE | | | WITH THE PROVISION OF THEIR SERVICES: AT&T, FPU, FPL, | | | AND COMCAST. | | | | | | ***WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15 | | | (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN | | | ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON | | | THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | ***PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | ***CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443 | | | IF THERE ARE ANY QUESTIONS | | | |
|
|
| |