Plan Review Details - Project Z19050020
Plan Review Stops For Project Z19050020
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 06-11-2019 Cont ID  
Sent By rbrown Date 06-11-2019 Time 20:03 Rev Time 0.00
Received By rbrown Date 06-11-2019 Time 20:03 Sent To  
Notes
2019-06-11 20:17:23DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. NUMBER OF ACCESSIBLE PARKING SPACES. THE PLANS DO
 NOT SHOW ANY ACCESSIBLE PARKING SPACES. UNDER THE FAIR
 HOUSING ACT 2% OF THE RESIDENTIAL PARKING SPACES SHALL
 BE ACCESSIBLE. FOR THE BUSINESS OCCUPANCY AREA, THE
 MINIMUM NUMBER OF ACCESSIBLE PARKING SPACES PROVIDED
 SHALL BE IN ACCORDANCE WITH SECTION 208.2 OF FLORIDA
 ACCESSIBILITY CODE.
  
 3. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION
 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING
 SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE.
  
 4. VAN ACCESSIBLE PARKING SPACES. PER SECTION 208.2.4
 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX
 REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE)
  
 5. ACCESSIBLE PARKING SPACE AISLE. ACCESSIBLE PARKING
 SPACE ACCESS AISLES SHALL BE LOCATED SO THAT THE USER
 IS NOT COMPELLED TO WALK OR WHEEL BEHIND ANOTHER PARKED
 VEHICLE OR IN THE TRAVEL LANE. THE ACCESS AISLES SHALL
 ALSO COMPLY WITH THE OTHER PROVISIONS OF SECTION OF
 502.3 OF FLORIDA ACCESSIBILITY CODE.
  
 6. ACCESS FROM PARKING GARAGE TO RESIDENTIAL AREAS. THE
 ACCESS GOES ACROSS THE LANDING FOR STAIR 2, BUT THE
 DOORS ARE TOO CLOSE TOGETHER FOR A WHEELCHAIR USER TO
 GO THROUGH. PER SECTION 404.2.6 OF FLORIDA
 ACCESSIBILITY CODE, THE DISTANCE BETWEEN TO HINGED
 DOORS SHALL BE 48 INCHES CLEAR BETWEEN THE DOOR SWINGS.
  
 7. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 8. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE WALL OPENINGS, OR SUFFICIENT WALL OPENINGS TO
 MEET THE DEFINITION OF AN OPEN PARKING GARAGE, IT WILL
 BE CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 9. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 11. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 12. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 13. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 06-11-2019 Cont ID  
Sent By rbrown Date 06-11-2019 Time 19:59 Rev Time 0.00
Received By rbrown Date 06-11-2019 Time 19:59 Sent To  
Notes
2019-06-11 20:02:49SEE REVIEW NO. 2 FOR BUILDING CODE COMMENTS RELATED TO
 THE SITE PLAN APPROVAL. THE COMMENTS ENTER UNDER THIS
 REVIEW WERE ENTERED UNDER THE WRONG DISCIPLINE BY THE
 PLANNER AND ARE NOT RELATED TO BUILDING CODE
 REQUIREMENTS.
  
  
2019-06-10 17:00:441. THE PROJECT CANNOT PROCEED TO DOWNTOWN ACTION
 COMMITTEE UNTIL THE DETAILS OF THE RESTRICTIVE COVENANT
 AND AMENDMENT TO THE DEVELOPMENT AGREEMENT (JULY 19,
 2004) ARE RESOLVED. PRELIMINARY REVIEW OF THE
 DOCUMENTS, SUBJECT TO LEGAL INTERPRETATION, IDENTIFY
 THE FOLLOWING:
 A. CONSTRUCTION OF FOR-SALE RESIDENTIAL CONDOMINIUM
 UNITS ON ALL FLOORS ABOVE THE GROUND FLOOR OF THE
 PROJECT.
 B. ANY BUILDING CONSTRUCTED ON THE PROPERTY SHALL
 CONTAIN A FULL SERVICE PHARMACY ON THE GROUND FLOOR NO
 LESS THAN 1500 GROSS SF IN SIZE FOR A TERM OF 3 YEARS.
 C. DEVELOPER SHALL CONSTRUCT 100 PUBLIC PARKING SPACES
 TO BE LOCATED ON LOWER 2 FLOORS OF PROJECT, SEPARATED
 FROM THE PARKING SERVING OTHER ELEMENTS OF THE PROJECT
 PLEASE ADDRESS THE INTENT OF THE APPLICANT IN REGARDS
 TO THE REQUIREMENTS OF THE RESTRICTIVE COVENANT AND
 DEVELOPER AGREEMENT IN THE JUSTIFICATION STATEMENT UPON
 RESUBMITTAL.
 2. THE PROJECT SHALL OBTAIN DAC APPROVAL OF A CLASS B
 LICENSE FOR A TYPE III GROUP HOMES .
 3. FOR GROUP HOMES PERMITTED AS A CLASS B SPECIAL USE,
 A GROUP HOME FACILITY SHALL BE LOCATED A MINIMUM OF
 1,200 FEET FROM ANOTHER SUCH FACILITY. A VARIANCE FROM
 THIS PROVISION WILL BE REQUIRED FOR THIS LOCATION.
 PLEASE PROVIDE JUSTIFICATION FROM VARIANCE IN
 JUSTIFICATION STATEMENT.
 4. PER SECTION 94-54(A)(3), FORMAL SITE PLAN APPROVALS
 INVOLVING THE TDR PROGRAM SHALL BE APPROVED BY DAC AND
 THE CERTIFICATE OF TRANSFER SHALL BE OBTAINED PRIOR TO
 THE EXPIRATION OF THE SITE PLAN APPROVAL.
 5. PLEASE INCLUDE THE AMOUNT OF TDRS NEEDED FOR THE
 SITE (SQUARE FEET) AND THE AMOUNT OF SF GRANTED BY
 RIGHT IN THE PROJECT DATA TABLE.
 6. PROJECT SHALL REQUIRE DAC SPECIAL REVIEW AND
 VARIANCE REVIEW. WITH SUBMITTAL FOR VARIANCE REVIEW,
 PLEASE RESPOND TO THE CRITERIA FOR VARIANCE REQUESTS
 FOR EACH REQUESTED VARIANCE, SEPARATELY, AS ESTABLISHED
 IN SECTION 94-38(D)(6).
 7. PLEASE CONDENSE THE TWO SEPARATE SITE PLANS SHEET
 SP-1 AND SP.1 INTO ONE SITE PLAN. PLEASE SHOW GROUND
 FLOOR USES, WITH THE OUTLINE OF UPPER LEVELS, SETBACK
 DIMENSIONS, EXISTING CURB LINE, ALL APPLICABLE
 DIMENSIONS, AND OTHER REQUIRED INFORMATION. PLEASE
 ILLUSTRATE ADJACENT BUILDING FRONTAGES AND CURB LINES
 ACROSS DIXIE HIGHWAY, DATURA STREET AND THE ALLEYWAY.
 8. THE PROPOSED DROP-OFF DOES NOT MEET THE FOLLOWING
 REQUIREMENTS:
 A. DESIGNATED PASSENGER LOADING AND DROP-OFF AREAS
 SHALL OCCUR WITHIN THE FOOTPRINT OF THE BUILDING
 ENVELOPE AND SHALL BE SUBJECT TO APPROVAL BY THE CITY
 TRAFFIC ENGINEER.
 B. CURB CUTS FOR INGRESS AND EGRESS SHALL BE NO MORE
 THAN 25 FEET, MEASURED AT THE CURB LINE.
 C. CAR QUEUING SHALL OCCUR INTERNAL TO THE LOT AND
 SHALL NOT INTERFERE WITH PEDESTRIAN CIRCULATION ON A
 PUBLIC SIDEWALK. THE PROPOSED LOCATION OF THE DROP OFF
 INTERFERES WITH PEDESTRIAN CIRCULATION.
 D. FOR REFERENCE, ?TYPE A? PORTE COCHERES SHALL BE
 ALLOWED FOR HOTELS IN THIS DISTRICT.
 STAFF RECOMMENDS CONSIDERING UTILIZING THE EXISTING
 GARAGE ENTRANCE OFF OF THE ALLEYWAY FOR COVERED DROP
 OFF.
 9. IF VALET IS PROPOSING UTILIZING EXISTING OR PROPOSED
 ON-STREET PARKING FOR VALET, THE APPLICANT SHALL PAY
 FOR THE USE OF THOSE OCCUPIED SPACES IN AMOUNT AS
 ESTABLISHED BY THE CITY AND IN LOCATIONS APPROVED BY
 THE CITY PARKING ADMINISTRATOR. THIS WOULD UTILIZE
 EXISTING ON-STREET PARKING SPACES AND NOT INTERFERE
 WITH SIDEWALK CONNECTIVITY.
 10. PLEASE INDICATE THE PROPOSED DIRECTION OF THE
 ALLEY. MANY BUSINESSES ON CLEMATIS STREET USE THIS
 ALLEY FOR PARKING AND GARBAGE COLLECTION, WHICH WILL BE
 CONSIDERED IN THE DESIGN INTENT.
 11. THE APPLICANT SHALL WORK WITH PUBLIC WORKS
 REGARDING THE EXISTING DUMPSTER THAT IS LOCATED WITHIN
 THE PROPERTY AND USED BY BUSINESSES ON THE 400 BLOCK OF
 CLEMATIS STREET.
 12. PLEASE PROVIDE TURN MOVEMENTS FOR ENTERING AND
 EXITING THE PARKING GARAGE TO ENSURE THE TURNS CAN WORK
 SAFELY.
 13. APPLICANT SHALL CONTACT PALM TRAN FOR PROPOSAL TO
 REMOVE/RELOCATE OF BUS SHELTER. STAFF RECOMMENDS THE
 USE OF THE EXISTING SHELTER LOCATED SOUTH OF THE
 PROPERTY AT 499 EVERNIA STREET (BROADSTONE). IF PALM
 TRAN DOES NOT PERMIT RELOCATION OF BUS STOP TO THIS
 LOCATION, THE APPLICANT SHALL REPLACE WITH A NEW BUS
 SHELTER, MEETING PALM TRAN STANDARDS.
 14. APPLICANT SHALL REQUIRE FDOT APPROVAL FOR ANY WORK
 DONE ON QUADRILLE BOULEVARD.
 15. PLEASE COORDINATE WITH THE CITY ENGINEERING
 DEPARTMENT ON THE PROPOSED DATURA STREET REDESIGN THAT
 IS CURRENTLY IN INITIAL DESIGN PHASE.
 16. THE PROPOSED UNDER COVER AREA ON THE GROUND FLOOR
 DOES NOT MEET THE DEFINITION OF COLONNADE FOR THE DMP
 AREA AND DOES NOT FIT INTO THE CONTEXT OF THE DIRECT
 AREA. STAFF RECOMMENDS ELIMINATION OF THE COLONNADE AS
 IT DOES NOT ACTIVATE THE PEDESTRIAN ENVIRONMENT AND
 DOES NOT IMPROVE ACTIVE USE OR TRANSPARENCY ALONG THE
 SIDEWALK.
 17. ARE ALL USES ON THE GROUND FLOOR PRIVATE? PLEASE
 CLARIFY WHICH USES ARE OPEN TO PUBLIC, IF ANY OR
 ACCESSIBLE FROM THE STREET.
 18. STAFF HAS CONCERN WITH THE SETBACK OF THE GROUND
 FLOOR USES ON THE WEST SIDE OF DATURA STREET, AS IT
 DOES NOT PROVIDE FOR ACTIVATED PEDESTRIAN SPACE AND
 INTERACTION WITH THE STREET AS OTHER RESIDENTIAL
 BUILDINGS DO WITHIN THE DMP AREA.
 19. IN ORDER TO COUNT TANDEM PARKING SPACES AS TWO
 SPACES, A RESTRICTIVE COVENANT SHALL BE REQUIRED FOR
 CONFIRMATION OF A VALET ATTENDANT IN CHARGE OF THE
 OPERATION OF THE PARKING FACILITY DURING ALL OPERATING
 HOURS.
 20. PLEASE NOTE, THE PARKING REQUIRED FOR THE
 INDEPENDENT LIVING UNITS MUST MEET THE REQUIREMENTS FOR
 RESIDENTIAL USES WITHIN THE DMP WHICH IS MINIMUM 1 PER
 UNIT PLUS 1 PER 20 UNITS FOR GUEST PARKING, MAXIMUM 2
 PER UNIT PLUS 1 PER 20 UNITS FOR GUEST PARKING. PLEASE
 SEPARATE PARKING REQUIREMENTS FOR INDEPENDENT LIVING
 FROM ASSISTED LIVING AND MEMORY CARE AND DETERMINE
 NUMBER OF PARKING SPACES REQUESTED FOR THE WAIVER. THE
 WAIVER CANNOT EXCEED 50% OF THE REQUIRED PARKING FOR
 THE PROJECT.
 21. PER SECTION 94-481(F):
 A. TO BE ELIGIBLE FOR THE SENIOR HOUSING PARKING
 WAIVER, CRITERIA MUST BE MET. PLEASE RESPOND TO THE
 CRITERIA.
 B. IF THE PARKING WAIVER IS GRANTED, A RESTRICTIVE
 COVENANT RESTRICTING THE USE OF THE PROPERTY TO SERVING
 PERSONS WHO ARE 55 YEARS AND OLDER FOR A PERIOD OF NOT
 LESS THAN 15 YEARS SHALL BE EXECUTED AND RECORDED.
 22. PLEASE SUBMIT PLANS ILLUSTRATING THE TRANSPARENCY
 REQUIREMENTS PER TABLE IV-50: BUILDING REQUIREMENTS-
 CWD 10-12 STORY RECEIVING SITES (SECTION 94-134).
 23. PLEASE PROVIDE DATA ON BUILDING FOOTPRINT MAXIMUM
 IN SITE TABLE PER TABLE IV-50.
 24. THE PROJECT DOES NOT MEET ACTIVE USE LINER
 REQUIREMENTS ALONG QUADRILLE BOULEVARD AND DATURA
 STREET. PLEASE ADDRESS VARIANCE CRITERIA IN THE
 JUSTIFICATION STATEMENT.
 25. CONSIDERING THE PROPOSED VARIANCES, PLEASE EVALUATE
 THE USE OF ADDITIONAL ARCHITECTURAL MATERIALS, CONSIDER
 THE PROPORTIONS OF THE BUILDING, ESPECIALLY REFINING
 THE PARKING GARAGE DESIGN. PLEASE TAKE INTO
 CONSIDERATION THE REDESIGN BASED ON REMOVAL OF THE
 ARCADE PORTIONS (SEE COMMENT #16).
 26. THE SUBMITTED JUSTIFICATION STATEMENT STATES THAT
 THE PROPOSED PLAN ADHERES TO ALL SETBACK REQUIREMENTS;
 HOWEVER THE REQUIRED PARKING SETBACK FOR 2 AND 3 STORY
 ALONG DATURA STREET IS NOT MET. PLEASE ADJUST TO MEET
 SETBACK REQUIREMENT.
 27. FOR SETBACK MEASUREMENTS, WHERE A CURB LOCATION
 VARIES ALONG A PROPERTY, THE BACK OF CURB SHALL BE
 DEFINED AS THE PREDOMINANT BACK OF CURB LINE FURTHEST
 FROM THE CENTER LINE OF THE ROAD. PLEASE ADJUST SETBACK
 MEASUREMENTS ALONG SOUTH DIXIE HIGHWAY TO REFLECT THIS.
 28. THE PROPOSED PRIVATE OPEN SPACE USE ALONG QUADRILLE
 BOULEVARD IS NOT AN EFFECTIVE USE OF OPEN SPACE. STAFF
 RECOMMENDS SHIFTING THE BUILDING FOOTPRINT TO THE WEST
 TO BETTER ALIGN WITH THE FOOTPRINT OF THE ADJACENT
 BROADSTONE BUILDING AND UTILIZE MORE OPEN SPACE ALONG
 DIXIE HIGHWAY, TO INCREASE PEDESTRIAN ACTIVE SPACE.
 29. PLEASE PRESERVE THE EXISTING CEMENT CANOPY ON SITE,
 PER CITY HISTORIC PRESERVATION PLANNER. THIS COULD BE
 MAINTAINED WITHIN THE OPEN SPACE.
 30. THE PROPOSED PUBLIC OPEN SPACE ALONG DATURA STREET
 CANNOT COUNT AS PUBLIC OPEN SPACE, PER THE DEFINITION
 OF PUBLIC OPEN SPACE. STAFF RECOMMENDS UTILIZING SOME
 SPACE ALONG DIXIE HIGHWAY.
 31. THE PROPOSED CANOPY EXCEEDS THE MAXIMUM HORIZONTAL
 PROJECTION FOR CANOPIES. PER SECTION TABLE IV-5, THE
 MAXIMUM PROJECTION FOR CANOPIES IS 20 FEET WITH A 12
 FOOT MAXIMUM ENCROACHMENT INTO THE ROW. PLEASE INDICATE
 THE PROPOSED HEIGHT OF THE CANOPY, THE MINIMUM HEIGHT
 FROM SIDEWALK GRADE IS 10 FEET.
 32. THE QUADRILLE BOULEVARD ELEVATION DOES NOT
 ILLUSTRATE THE EXTENT OF THE PROPOSED CANOPY. PLEASE
 ADD TO SHOW ADJUSTED CANOPY SIZE PER COMMENT #31.
 33. PLEASE PROVIDE ADDITIONAL DETAIL OF ARCHITECTURAL
 TREATMENT MATERIALS ON BUILDING ON ELEVATION PLANS.
 34. TREE GRATES ARE NOT NECESSARY WHERE THERE IS
 SUFFICIENT SIDEWALK WIDTH ADJACENT TO THE PROPOSED
 TREE. PLEASE REMOVE TREE GRATES AND USE PLANTING BEDS
 (CONSIDER 6X4 BEDS) WHERE GRATES ARE PROPOSED.
 35. PLEASE PROVIDE OAK TREES OR SIMILAR SHADE TREES AT
 CORNER OF QUADRILLE AND DATURA AND DIXIE AND DATURA AS
 THIS IS WHERE PEDESTRIANS WAIT FOR STREET CROSSINGS.
 36. PLEASE CHECK CRITERIA FOR FDOT SIGHT TRIANGLE FOR
 PROPOSED TREES AT STREET CORNERS.
 37. THE PROPOSED EXFILTRATION TRENCH RUNS WHERE TREES
 ARE PROPOSED. PLEASE REVIEW AND ADJUST AS NECESSARY.
 38. PLEASE PROVIDE A HARDSCAPE PLAN WITH DETAILS OF
 PAVERS, SEATING, ETC.
 39. PLEASE SEE TABLE IV-7 FOR OPEN SPACE STANDARDS.
 CURRENTLY THE PASSAGEWAY PUBLIC OPEN TYPEIS REQUIRED.
 STAFF IS CURRENTLY REVIEWING THIS REQUIREMENT FOR
 APPLICABILITY FOR THIS SITE.
 40. PLEASE ADDRESS SPECIFIC PRIVATE AND PUBLIC OPEN
 SPACE REQUIREMENTS PER TABLE IV-6 AND TABLE IV-7,
 INCLUDING TYPE OF OPEN SPACE (COURTYARD GARDEN,
 TERRACE, ETC.) FOR EACH OPEN SPACE AND SEE THE
 REQUIREMENTS FOR VEGETATED SPACE, SEATING, ETC.
 41. PLEASE PROVIDE ILLUSTRATIONS SHOWING PLANAR BREAK
 REQUIREMENTS AS REQUIRED BY TABLE IV-4: FA?ADE
 ARTICULATION REQUIREMENTS.
 42. PER SECTION 94-111: PARKING AND LOADING
 REQUIREMENTS, A MINIMUM THREE-FOOT BACK UP AREA SHALL
 BE PROVIDED AT THE TERMINUS OF ANY DEAD-END DRIVE AISLE
 TO ALLOW FOR VEHICLES TO SAFELY PULL OUT OF THE END
 PARKING SPACES. IN ADDITION, THE EQUIVALENT OF ONE
 PARKING SPACE AT THE TERMINUS OF A DEAD-END AISLE SHALL
 BE STRIPED AS DEDICATED PULL-IN AREA FOR TURNING
 AROUND.
 43. PLEASE PROVIDE TYPICAL PARKING SPACE AND AISLE
 WIDTH DIMENSIONS ON EACH FLOOR. PLEASE NOTE, IN THOSE
 CASES WHERE THE SIDE OF ANY STALL IS ADJACENT TO A WALL
 OR COLUMN, THE STALL WIDTHS SHALL BE INCREASED BY A
 MINIMUM OF ONE FOOT. WHERE THERE IS AN OBSTRUCTION ON
 BOTH SIDES OF THE STALL THE STALL WIDTHS SHALL BE
 INCREASE BY A MINIMUM OF TWO FEET. PLEASE DIMENSION
 THIS ADDITIONAL ONE/TWO FOOT.
 44. PER SECTION 94-111, ONE BICYCLE PARKING SPACE SHALL
 BE PROVIDED PER EVERY 15 REQUIRED PARKING SPACES, IN A
 SECURE AREA, COVERED FROM THE ELEMENTS.
 45. PER SECTION 93-113, BICYCLE PARKING FOR THE PUBLIC
 SHALL BE PROVIDED AT A MINIMUM OF ONE SPACE PER EVERY
 100 FEET OF STREET FRONTAGE. THE POST AND LOOP RACK IS
 RECOMMENDED FOR THE PUBLIC ROW. PLEASE INDICATE EXACT
 BICYCLE RACK DETAIL ON PLANS.
 46. PLEASE INCLUDE SPECIFIC DIMENSIONS OF BICYCLE
 RACKS ON THE SITE PLAN. THE POLE SHALL BE NO FURTHER
 THAN THREE FEET FROM THE EDGE OF CURB MAINTAINING A
 MINIMUM FIVE FOOT CLEARANCE FOR PEDESTRIAN CIRCULATION.
 47. PLEASE INDICATE LOCATION OF PROPOSED UTILITIES
 INCLUDING THE BACKFLOW PREVENTER, FDC CONNECTION, FPL
 TRANSFORMER, ETC. STAFF RECOMMENDS LOCATING THE
 UTILITIES WITHIN THE BUILDING FOOTPRINT AND PROVIDING
 ACCESS TO UTILITY COMPANIES, TO KEEP OFF THE PUBLIC
 ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED ALONG THE
 ALLEY SIDE OF THE BUILDING. SUFFICIENT LANDSCAPE
 SCREENING IS REQUIRED WHEN UTILITIES ARE LOCATED
 OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A MINIMUM
 OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED AT ALL
 LOCATIONS.
 48. THE CIVIL ENGINEERING PLANS SHOW PARKING SPACES
 THAT ARE NOT SHOWN ON THE SITE PLAN. PLEASE ADJUST
 ACCORDINGLY.
 49. THE MINIMUM FOOTCANDLE, AS MEASURED AT THE BACK
 EDGE OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK IS 0.6
 AND THE MAXIMUM IS 1.0 FOOTCANDLE. PLEASE ADJUST
 PHOTOMETRICS EXTENDING TO THE ROADWAY CENTERLINES AND
 PROVIDE DETAILS OF THE PROPOSED LIGHT FIXTURES AS
 NECESSARY. PLEASE COORDINATE WITH THE ENGINEERING
 DEPARTMENT TO USE THE CITY APPROVED LIGHT FIXTURE. A
 SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 50. PLEASE PROVIDE PROPOSED PHOTOMETRICS FOR THE
 PARKING GARAGE, MEETING THE REQUIREMENTS OF SECTION
 86-294.
 51. EACH ENTRANCE SHOULD HAVE ITS OWN ADDRESS WHICH IS
 USED BY 911 EMERGENCY SERVICES. THE EXISTING PRIMARY
 ADDRESS WHICH WILL BE RETIRED WHEN THE PROJECT IS
 COMPLETE. THERE WILL SEPARATE ADDRESSES FOR THE MAIN
 LOBBY AND FOR THE MEMORY CARE LOBBY. THE OWNER CAN PICK
 WHICH WILL BE THE PRIMARY ADDRESS SEEN ON PAPA. CONTACT
 MICHAEL ORIO AT [email protected] WITH ANY QUESTIONS.
 52. APPLICANT SHALL BE REQUIRED TO MEET REQUIREMENTS OF
 ART IN PUBLIC PLACES. CONTACT SYBILLE WELTER AT
 [email protected] FOR MORE INFORMATION.
 53. PLEASE BE ADVISED, APPLICANTS ARE NOW REQUIRED TO
 PRESENT THEIR CASE TO THE BOARDS INCLUDING DAC AND
 INCLUDE RESPONSES TO CRITERIA FOR SPECIAL REVIEW,
 VARIANCES, ETC. STAFF WILL PROVIDE COMMENT FOR ITEMS
 NOT ADDRESSED BY THE APPLICANT. PRESENTATIONS ARE TO BE
 SUBMITTED TO STAFF THE MONDAY PRIOR TO THE DAC MEETING
 BY MEANS OF ELECTRONIC OR FLASH DRIVE DELIVERY.
  
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561-822-1426

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 10-16-2019 Cont ID  
Sent By rrossano Date 10-16-2019 Time   Rev Time 0.00
Received By rrossano Date 10-16-2019 Time   Sent To  
Notes
2019-10-16 09:46:08PASSED WITH PROVISOS:
  
 FOR ENGINEERING SUBMITTAL -
  
 1. PLEASE LABEL ALL UTILITIES - MATERIAL, SIZE,
 PROPOSED OR EXISTING, ETC.
 2. PLEASE PROVIDE SMALL UTILITY EASEMENT FOR WATER
 METER; EXCLUDE BACKFLOWS FROM EASEMENT (BACKFLOWS MUST
 BE ON PRIVATE PROPERTY OUTSIDE OF EASEMENT).
 3. ENLARGED UTILITY DETAIL IS DIFFICULT TO READ.
 4. RELOCATE 90 DEGREE WATER JOINTS OUTSIDE OF RIGHT OF
 WAY ON TO PROJECT PROPERTY; WATER CONNECTIONS FROM CITY
 POINT OF SERVICE SHOULD RUN DIRECTLY PERPENDICULAR FROM
 WATER MAIN TO SITE.
 5. PLEASE ADD NOTE FOR CONTRACTOR TO HAND DIG/POT HOLE
 AROUND EXISTING UTILITIES.
 6. PLEASE SHOW DIRECTION OF FLOW FOR STORMWATER AND
 SANITARY LINES.
 7. PLEASE LABEL CITY POINT OF SERVICE FOR UTILITY
 CONNECTIONS AND LABEL WATER LINES AS PRIVATE WHERE
 APPLICABLE.
 8. UNABLE TO LOCATE CITY OF WPB STANDARD DETAILS P-3,
 P-6, WS-6, WS-10 (PREVIOUS COMMENT).
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO, PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401 (MAILING ADDRESS: P.O. BOX
 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200 DIRECT: (561) 494-1098
 FAX: (561) 494-1116 MOBILE: (561) 246-9525
 EMAIL: [email protected] WWW.WPB.ORG/ENGINEERING
  
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 08-29-2019 Cont ID  
Sent By rrossano Date 08-29-2019 Time   Rev Time 0.00
Received By rrossano Date 08-29-2019 Time   Sent To  
Notes
2019-08-29 12:50:06PASSED WITH PROVISOS:
  
 FOR ENGINEERING SUBMITTAL:
  
 PROVIDE CALCULATIONS ON PLANS FOR FIRE FLOW DEMANDS.
  
 PLEASE ADD NOTE FOR PAVEMENT RESTORATION (100?) ON
 UTILITY PLAN WHERE THE WATER TAP IS TO BE PERFORMED PER
 CITY OF WPB STANDARD DETAIL GC-9.
  
 PLEASE SHOW CONSTRUCTION OF DUMPSTER TO BE IN
 COMPLIANCE WITH CITY OF WPB STANDARD DETAIL GC-8.
  
 PLEASE SHOW OVERHEAD CLEARANCE DIMENSIONS WHERE
 PROPOSED DUMPSTER IS TO BE CONSTRUCTED.
  
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND FRANCHISED UTILITIES, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED IN THE
 RIGHT-OF-WAY. (FRANCHISED UTILITIES WERE NOT SHOWN ON
 RESUBMITTED PLANS.)
  
 PROVIDE CLEARANCES AT ALL UTILITY (SANITARY, WATER,
 STORMWATER) CROSSINGS.
  
 PROVIDE SEWER TIE-IN INVERT ELEVATION.
  
 SHOW DOWNSTREAM SEWER FROM CONNECTION ONTO DIXIE HWY.
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 CALL OUT SIZE OF EXISTING WATER SERVICE TO BE CUT OFF
 AT 12 IN. WATER MAIN.
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS. (NOT SHOWN ON SITE PLAN SUBMITTED WITH
 RESPONSE.)
  
 RELOCATE WATER METER BOX OUT OF SIDEWALK, ON PROPERTY,
 IN A DEDICATED EASEMENT. BACKFLOW TO BE AS CLOSE TO
 METER AS POSSIBLE (OUTSIDE OF EASEMENT).
  
 REMOVE BACKFLOW SHOWN NORTH OF PROPOSED 90 DEGREE BEND
 IN WATER SERVICE.
  
 PLEASE CALL OUT NUMBER OF FEET OF PIPE RESTRAINT PER
 CITY OF WPB STANDARD DETAIL P-3.
  
 PLEASE CROSS-REFERENCE ALL CROSS SECTIONS WITH THEIR
 CORRESPONDING SHEETS.
  
 ADD CITY OF WPB STANDARD DETAILS P-3, P-6, WS-6, WS-10.
  
 CLEARLY SHOW RIGHT OF WAY AND PROPERTY LINES.
  
 PLEASE NOTE THAT VIDEO WILL NEED TO BE PROVIDED BEFORE
 AND AFTER CONSTRUCTION BUT IS NOT REQUIRED AT THIS
 TIME.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 DIRECT: (561) 494-1098
 MOBILE: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By rrossano Date 06-07-2019 Time   Rev Time 2.00
Received By rrossano Date 06-07-2019 Time   Sent To  
Notes
2019-06-07 07:30:38THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS
 AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE
 DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER
 UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT
 PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW:
 HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W
 EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P
 ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19
 60045731D3658206F27451722716EF
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18)
  
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
  
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
  
 PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER AND
 DRAINAGE ALONG ENTIRE PROJECT FRONTAGE. DEVELOPER TO
 PROVIDE CCTV, NOT CITY (UPDATE NOTE).
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
  
 PROVIDE UTILITY EASEMENTS FOR PLACEMENT OF PROPOSED
 WATER METERS TO ALLOW ACCESS FOR CITY WATER UTILITY
 PERSONNEL.
  
 PROVIDE ONSITE CLEANOUTS AT PROPERTY LINE FOR PROPOSED
 SANITARY LATERALS.
  
 PROVIDE SANITARY MANHOLE AT POINT OF SERVICE.
  
 WATER SERVICES SHALL BE PIPED STRAIGHT INTO THE
 PROPERTY AVOIDING BENDS OR ANGLED CONNECTIONS.
  
 COORDINATE DIRECTLY WITH TINU PENA AT ENGINEERING
 SERVICES/CAPITAL IMPROVEMENTS SECTION REGARDING
 STREETSCAPE ALONG DATURA FROM QUADRILLE TO DIXIE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 08-22-2019 Cont ID  
Sent By pleduc Date 08-22-2019 Time   Rev Time 0.00
Received By pleduc Date 08-22-2019 Time 14:50 Sent To  
Notes
2019-08-22 14:52:212ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC INFORMATION PACKET AND
 RESPONSE LETTER DATED AUGUST 19, 2019, FROM INSITE
 STUDIO, TO LIZ LEVESQUE, URBAN DESIGN PLANNER, THE
 PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS
 HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 05-31-2019 Cont ID  
Sent By pleduc Date 05-31-2019 Time   Rev Time 0.00
Received By pleduc Date 05-31-2019 Time 13:12 Sent To  
Notes
2019-05-31 13:13:51THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
 THERE APPEARS TO BE MULTIPLE OCCUPANCIES PER THE FFPC,
 WILL IT BE MIXED, SEPARATED OR NON-SEPARATED OCCUPANCY.
  
 IS THE PROPOSED A HIGH RISE? THE MEASURMENT SHOWN IS
 72' 8" TO THE 8TH FLOOR; HOWEVER, THE MEASURMENT IS
 INDICATED FROM A SIDEWALK.
  
 PER NFPA 101
  
 3.3.36.7* HIGH-RISE BUILDING. A BUILDING WHERE THE
 FLOOR OF AN OCCUPIABLE STORY IS GREATER THAN 75 FT (23
 M) ABOVE THE LOWEST LEVEL OF FIRE DEPARTMENT VEHICLE
 ACCESS.
  
 THE MEASURMENT SHOULD TAKE IN CONSIDERATION THE ROAD
 LEVEL.
  
 PLEASE REVIEW AND ADJUST EMENTS ACCORDINGLY TO VERIFY
 UNDER/OVER 75 FT.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER NFPA 14 SECTION 7.12.2, HIGH-RISE BUILDINGS SHALL
 HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT
 CONNECTIONS FOR EACH ZONE.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
  
 7A) A FIRE PUMP ROOM COULD NOT BE IDENTIFIED AND IS
 MSOT LIKELY REQUIRED FOR THIS STURCTURE.
  
  
 8. A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTERS
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDCS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDCS SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 TWO REMOTELY LOCATED FDCS FOR EFFECTIVE AND EFFICIENT
 FIREGROUND OPERATIONS ARE REQUESTED. PLEASE COORDINATE
 THE LOCATIONS WITH THE OFFICE OF THE FIRE MARSHAL.
  
 12. COMMAND ROOM - REQUIRED FOR HIGH RISE
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
  
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
  
 13. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM, IF APPLICABLE, SHALL
 COMPLY WITH NFPA 101, CHAPTER 9, BUILDING SERVICE AND
 FIRE PROTECTION EQUIPMENT, INCLUDING:
  
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 5 Status P Date 02-10-2020 Cont ID  
Sent By rcaranci Date 02-10-2020 Time 12:46 Rev Time 0.00
Received By rcaranci Date 02-10-2020 Time 12:46 Sent To  
Notes
2020-02-10 12:47:25 
 FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 401 DATURA RESIDENTIAL Z19050020
 FEBRUARY 10, 2020
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE TREE DISPOSITION PLAN NEEDS TO MATCH
 THE LOCATIONS SHOWN ON THE SURVEY AND USE THE SAME
 REFERENCE NUMBERS.
 ? SATISFIED. TREE SPECIES ARE MISIDENTIFIED ON THE
 LIST. CORRECT THE SPECIES.
 TREE #24 IS A WASHINGTONIA ROBUSTA
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE.
 ONLY TREE #1 IS 20 FEET OR MORE CANOPY DIAMETER.
 MITIGATION IS 380 SQ FT.
 #22 AND 23 ARE DOUBLE WASHINGTONIA PALMS. CATEGORY 4
 ARE 50 SQ FT EACH, SO EACH DOUBLE IS 100 SQ FT CANOPY
 REMOVED.
 ALL OAKS AND 2 REMAINING BLACK OLIVE TREES ARE CATEGORY
 1 TREES AT 300 SQ FT EACH CANOPY REMOVED.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 AND SILVER TRUMPET
 #7 ARE CATEGORY 2 AND ARE EACH 150 SQ FT CANOPY
 REMOVED.
  
 ? SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 CORRECT ALL MITIGATION VALUES FOR THE ABOVE COMMENTS
 AND ADD TOTAL FOR MITIGATION DUE.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 REMOVE NOTE FOR TREE MITIGATION CALCULATED AT
 PERMITTING. MITIGATION IS BASED ON CATEGORY LIST
 PROVIDED. LIST EACH SPECIES AND CATEGORY AND TOTAL
 MITIGATION VALUE.
  
 2. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 ROYAL PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD THE
 TREE REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD
 CANOPY TREES AS REQUIRED.
 CALCULATE TREE REQUIREMENT ON S DIXIE (4) AND MEET
 REQUIREMENTS WITHIN THE RIGHT OF WAY. OPEN SPACE TREE
 CANOPY ADJACENT TO THIS AREA NEEDS TO BE DESIGNED TO
 COMPLEMENT REQUIRED STREET TREE CANOPY COVERAGE.
 12/18 THERE SHOULD BE 2 TREES NORTH OF THE PARKING, AND
 2 TREES SOUTH OF THE PARKING IN PLANTER AREA ADJACENT
 TO THE CURB.
 THE EXISTING HOLLIES ARE NOT IN GOOD CONDITION AND
 SHOULD BE REMOVED AND REPLACED WITH LIVE OAKS TO MATCH
 THE STREET PATTERN TO THE SOUTH. TWO TREES TO THE NORTH
 OF THE PARKING SPACES AND TWO TREES TO THE SOUTH WITH
 THE PUBLIC SPACE LIVE OAK TREES PROVIDING THE CANOPY TO
 THE CENTER PORTION.
  
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
  
 4. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. SUBMIT THE REASON EXISTING LIVE OAK TREES
 CANNOT BE RELOCATED OR USED IN THE PROPOSED LANDSCAPE.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 ARE NOT IN GOOD
 CONDITION AND ARE TO BE REMOVED.
 LIVE OAK TREES #4, #20 AND 21 MAY BE RELOCATED TO THE
 WEST SIDE OF QUADRILLE ROW TO REPLACE MISSING LIVE OAK
 TREES.
 THIS COMMENT TO BE RESOLVED WITH COMMENT #2 FOR
 STREETSCAPE DESIGN.
 CITY STAFF WILL EVALUATE LIVE OAK TREES FOR POSSIBLE
 RELOCATION TO WEST SIDE OF QUADRILLE BLVD.
  
 5. SATISFIED. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN
 ON SHEET MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA AS THE ALLOWED OPEN SPACE TYPE. TERRACE REQUIRES
 20% MINIMUM VEGETATED AREA. ROOFTOP GARDEN REQUIRES 30%
 VEGETATED AREA AND 20% TREE CANOPY. TREE CANOPY VALUES
 CAN BE FOUND IN SECTION 94-109 TABLE IV-8.
 AREAS ON THE GROUND LEVEL ARE NOT NAMED FOR OPEN SPACE
 TYPE, AND REQUIREMENTS ARE NOT PROVIDED. TREE CANOPY
 SQUARE FOOTAGE CREDITS ARE TO MATCH TABLE IV-8 FOR OPEN
 SPACE.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 5 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
 7. SATISFIED. SHOW LOCATIONS OF UTILITY LINES ON
 LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND BACKFLOW
 PREVENTERS AND FPL TRANSFORMERS.
  
 8. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
  
 9. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO TREES. PROVIDE A
 TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL.
 VERTICAL DETAIL IS CORRECT, OVERHEAD TYPICAL IS
 INCORRECT AND MUST MATCH THE VERTICAL DETAIL. PLANTING
 AREAS AROUND STREET TREES MAY BE EXPANDED AS LONG AS
 THE 8 FOOT SIDEWALK WIDTH IS MAINTAINED. THIS WILL
 MINIMIZE THE AREAS OF STRUCTURAL SOIL REQUIRED UNDER
 THE ADJACENT PAVED AREA. PROVIDING A SEPARATE EXHIBIT
 CLEARLY SHOWING THE LOCATIONS OF THE PLANTING AREAS AND
 STRUCTURAL SOIL IS REQUIRED FOR STAFF TO VERIFY
 ADEQUATE PLACEMENT, AND IS HELPFUL LATER IN
 CONSTRUCTION FOR BIDDING AND INSTALLATION PURPOSES.
  
 10. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 MUST INCLUDE ADDED PLANT MATERIAL NOT JUST REQUIRED.
 RECALCULATE AFTER ADJUSTMENTS FROM OTHER COMMENTS.
  
 ADDITIONAL COMMENTS 9/6/19:
  
 11. SATISFIED. ARTIFICIAL TURF DOG WALKING AREA CANNOT
 BE VIEWABLE FROM THE ROAD OR STREET PER SECTION 94-451,
 SO MUST BE FENCED TO BLOCK VIEW.
 ADDITIONAL COMMENT 10/28/19:
 12. SATISFIED. THE PLACEMENT OF THE DRAINAGE FIELD
 BENEATH THE TREES IN THE PUBLIC OPEN SPACE HAS TO BE
 ACCEPTABLE TO THE STORMWATER ENGINEER FOR THE CITY.
  
 MEETING IN NOVEMBER ESTABLISHED THAT EXFILTRATION WOULD
 BE DESIGNED TO AVOID BEING DIRECTLY UNDER THE TREES IN
 ORDER TO ALLOW FOR FUTURE MAINTENANCE WITHOUT
 DESTROYING THE TREES. THIS IS NOT SHOWN ON THE
 SUBMITTED PLAN.
  
 13. SATISFIED. THE SOUTHERN OAK TREE AT THE CORNER OF
 QUADRILLE AND DATURA IS WITHIN THE FDOT SIGHTLINE.
 CONFIRM THAT THIS WILL BE ALLOWED BY FDOT.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 12-18-2019 Cont ID  
Sent By rcaranci Date 12-18-2019 Time 17:04 Rev Time 0.00
Received By rcaranci Date 12-18-2019 Time 17:04 Sent To  
Notes
2019-12-18 17:04:56FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 401 DATURA RESIDENTIAL Z19050020
 DECEMBER 18, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE TREE DISPOSITION PLAN NEEDS TO MATCH
 THE LOCATIONS SHOWN ON THE SURVEY AND USE THE SAME
 REFERENCE NUMBERS.
 ? SATISFIED. TREE SPECIES ARE MISIDENTIFIED ON THE
 LIST. CORRECT THE SPECIES.
 TREE #24 IS A WASHINGTONIA ROBUSTA
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE.
 ONLY TREE #1 IS 20 FEET OR MORE CANOPY DIAMETER.
 MITIGATION IS 380 SQ FT.
 #22 AND 23 ARE DOUBLE WASHINGTONIA PALMS. CATEGORY 4
 ARE 50 SQ FT EACH, SO EACH DOUBLE IS 100 SQ FT CANOPY
 REMOVED.
 ALL OAKS AND 2 REMAINING BLACK OLIVE TREES ARE CATEGORY
 1 TREES AT 300 SQ FT EACH CANOPY REMOVED.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 AND SILVER TRUMPET
 #7 ARE CATEGORY 2 AND ARE EACH 150 SQ FT CANOPY
 REMOVED.
  
 ? SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 CORRECT ALL MITIGATION VALUES FOR THE ABOVE COMMENTS
 AND ADD TOTAL FOR MITIGATION DUE.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 REMOVE NOTE FOR TREE MITIGATION CALCULATED AT
 PERMITTING. MITIGATION IS BASED ON CATEGORY LIST
 PROVIDED. LIST EACH SPECIES AND CATEGORY AND TOTAL
 MITIGATION VALUE.
  
 2. PARTIALLY SATISFIED. THE STREETSCAPE CAN BE IMPROVED
 TO ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113.
 THE ROYAL PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD
 THE TREE REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING.
 ADD CANOPY TREES AS REQUIRED.
 CALCULATE TREE REQUIREMENT ON S DIXIE (4) AND MEET
 REQUIREMENTS WITHIN THE RIGHT OF WAY. OPEN SPACE TREE
 CANOPY ADJACENT TO THIS AREA NEEDS TO BE DESIGNED TO
 COMPLEMENT REQUIRED STREET TREE CANOPY COVERAGE.
 12/18 THERE SHOULD BE 2 TREES NORTH OF THE PARKING, AND
 2 TREES SOUTH OF THE PARKING IN PLANTER AREA ADJACENT
 TO THE CURB.
 THE EXISTING HOLLIES ARE NOT IN GOOD CONDITION AND
 SHOULD BE REMOVED AND REPLACED WITH LIVE OAKS TO MATCH
 THE STREET PATTERN TO THE SOUTH. TWO TREES TO THE NORTH
 OF THE PARKING SPACES AND TWO TREES TO THE SOUTH WITH
 THE PUBLIC SPACE LIVE OAK TREES PROVIDING THE CANOPY TO
 THE CENTER PORTION.
  
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
  
 4. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. SUBMIT THE REASON EXISTING LIVE OAK TREES
 CANNOT BE RELOCATED OR USED IN THE PROPOSED LANDSCAPE.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 ARE NOT IN GOOD
 CONDITION AND ARE TO BE REMOVED.
 LIVE OAK TREES #4, #20 AND 21 MAY BE RELOCATED TO THE
 WEST SIDE OF QUADRILLE ROW TO REPLACE MISSING LIVE OAK
 TREES.
 THIS COMMENT TO BE RESOLVED WITH COMMENT #2 FOR
 STREETSCAPE DESIGN.
 CITY STAFF WILL EVALUATE LIVE OAK TREES FOR POSSIBLE
 RELOCATION TO WEST SIDE OF QUADRILLE BLVD.
  
 5. SATISFIED. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN
 ON SHEET MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA AS THE ALLOWED OPEN SPACE TYPE. TERRACE REQUIRES
 20% MINIMUM VEGETATED AREA. ROOFTOP GARDEN REQUIRES 30%
 VEGETATED AREA AND 20% TREE CANOPY. TREE CANOPY VALUES
 CAN BE FOUND IN SECTION 94-109 TABLE IV-8.
 AREAS ON THE GROUND LEVEL ARE NOT NAMED FOR OPEN SPACE
 TYPE, AND REQUIREMENTS ARE NOT PROVIDED. TREE CANOPY
 SQUARE FOOTAGE CREDITS ARE TO MATCH TABLE IV-8 FOR OPEN
 SPACE.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 5 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
 7. SATISFIED. SHOW LOCATIONS OF UTILITY LINES ON
 LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND BACKFLOW
 PREVENTERS AND FPL TRANSFORMERS.
  
 8. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
  
 9. SATISFIED. SHOW LOCATIONS OF REQUIRED STRUCTURAL
 SOIL UNDER HARDSCAPE ADJACENT TO TREES. PROVIDE A
 TYPICAL FOR THE INSTALLATION OF THE STRUCTURAL SOIL.
 VERTICAL DETAIL IS CORRECT, OVERHEAD TYPICAL IS
 INCORRECT AND MUST MATCH THE VERTICAL DETAIL. PLANTING
 AREAS AROUND STREET TREES MAY BE EXPANDED AS LONG AS
 THE 8 FOOT SIDEWALK WIDTH IS MAINTAINED. THIS WILL
 MINIMIZE THE AREAS OF STRUCTURAL SOIL REQUIRED UNDER
 THE ADJACENT PAVED AREA. PROVIDING A SEPARATE EXHIBIT
 CLEARLY SHOWING THE LOCATIONS OF THE PLANTING AREAS AND
 STRUCTURAL SOIL IS REQUIRED FOR STAFF TO VERIFY
 ADEQUATE PLACEMENT, AND IS HELPFUL LATER IN
 CONSTRUCTION FOR BIDDING AND INSTALLATION PURPOSES.
  
 10. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION
 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF
 PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 MUST INCLUDE ADDED PLANT MATERIAL NOT JUST REQUIRED.
 RECALCULATE AFTER ADJUSTMENTS FROM OTHER COMMENTS.
  
 ADDITIONAL COMMENTS 9/6/19:
  
 11. SATISFIED. ARTIFICIAL TURF DOG WALKING AREA CANNOT
 BE VIEWABLE FROM THE ROAD OR STREET PER SECTION 94-451,
 SO MUST BE FENCED TO BLOCK VIEW.
 ADDITIONAL COMMENT 10/28/19:
 12. PARTIALLY SATISFIED. THE PLACEMENT OF THE DRAINAGE
 FIELD BENEATH THE TREES IN THE PUBLIC OPEN SPACE HAS TO
 BE ACCEPTABLE TO THE STORMWATER ENGINEER FOR THE CITY.
  
 MEETING IN NOVEMBER ESTABLISHED THAT EXFILTRATION WOULD
 BE DESIGNED TO AVOID BEING DIRECTLY UNDER THE TREES IN
 ORDER TO ALLOW FOR FUTURE MAINTENANCE WITHOUT
 DESTROYING THE TREES. THIS IS NOT SHOWN ON THE
 SUBMITTED PLAN.
  
 13. SATISFIED. THE SOUTHERN OAK TREE AT THE CORNER OF
 QUADRILLE AND DATURA IS WITHIN THE FDOT SIGHTLINE.
 CONFIRM THAT THIS WILL BE ALLOWED BY FDOT.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 10-28-2019 Cont ID  
Sent By rcaranci Date 10-28-2019 Time 16:55 Rev Time 0.00
Received By rcaranci Date 10-28-2019 Time 16:55 Sent To  
Notes
2019-10-28 16:55:40FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 401 DATURA RESIDENTIAL Z19050020
 OCTOBER 28, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE TREE DISPOSITION PLAN NEEDS TO MATCH
 THE LOCATIONS SHOWN ON THE SURVEY AND USE THE SAME
 REFERENCE NUMBERS.
 ? SATISFIED. TREE SPECIES ARE MISIDENTIFIED ON THE
 LIST. CORRECT THE SPECIES.
 TREE #24 IS A WASHINGTONIA ROBUSTA
 ? SATISFIED. TREES AND PALMS CANOPY SQUARE FOOTAGE TO
 BE MITIGATED BASED ON CATEGORY. ANY TREES 20 FEET OR
 MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL SQUARE
 FOOTAGE.
 ONLY TREE #1 IS 20 FEET OR MORE CANOPY DIAMETER.
 MITIGATION IS 380 SQ FT.
 #22 AND 23 ARE DOUBLE WASHINGTONIA PALMS. CATEGORY 4
 ARE 50 SQ FT EACH, SO EACH DOUBLE IS 100 SQ FT CANOPY
 REMOVED.
 ALL OAKS AND 2 REMAINING BLACK OLIVE TREES ARE CATEGORY
 1 TREES AT 300 SQ FT EACH CANOPY REMOVED.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 AND SILVER TRUMPET
 #7 ARE CATEGORY 2 AND ARE EACH 150 SQ FT CANOPY
 REMOVED.
  
 ? SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 CORRECT ALL MITIGATION VALUES FOR THE ABOVE COMMENTS
 AND ADD TOTAL FOR MITIGATION DUE.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED TREES AND PALMS.
 REMOVE NOTE FOR TREE MITIGATION CALCULATED AT
 PERMITTING. MITIGATION IS BASED ON CATEGORY LIST
 PROVIDED. LIST EACH SPECIES AND CATEGORY AND TOTAL
 MITIGATION VALUE.
  
 2. PARTIALLY SATISFIED. THE STREETSCAPE CAN BE IMPROVED
 TO ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113.
 THE ROYAL PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD
 THE TREE REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING.
 ADD CANOPY TREES AS REQUIRED.
 CALCULATE TREE REQUIREMENT ON S DIXIE (4) AND MEET
 REQUIREMENTS WITHIN THE RIGHT OF WAY. OPEN SPACE TREE
 CANOPY ADJACENT TO THIS AREA NEEDS TO BE DESIGNED TO
 COMPLEMENT REQUIRED STREET TREE CANOPY COVERAGE.
 THE EXISTING HOLLIES ARE NOT IN GOOD CONDITION AND
 SHOULD BE REMOVED AND REPLACED WITH LIVE OAKS TO MATCH
 THE STREET PATTERN TO THE SOUTH. TWO TREES TO THE NORTH
 OF THE PARKING SPACES AND TWO TREES TO THE SOUTH WITH
 THE PUBLIC SPACE LIVE OAK TREES PROVIDING THE CANOPY TO
 THE CENTER PORTION.
  
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
  
 4. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES
 NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE
 OR RELOCATED. SUBMIT THE REASON EXISTING LIVE OAK TREES
 CANNOT BE RELOCATED OR USED IN THE PROPOSED LANDSCAPE.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 ARE NOT IN GOOD
 CONDITION AND ARE TO BE REMOVED.
 LIVE OAK TREES #4, #20 AND 21 MAY BE RELOCATED TO THE
 WEST SIDE OF QUADRILLE ROW TO REPLACE MISSING LIVE OAK
 TREES.
 THIS COMMENT TO BE RESOLVED WITH COMMENT #2 FOR
 STREETSCAPE DESIGN.
 CITY STAFF WILL EVALUATE LIVE OAK TREES FOR POSSIBLE
 RELOCATION TO WEST SIDE OF QUADRILLE BLVD.
  
 5. SATISFIED. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN
 ON SHEET MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA AS THE ALLOWED OPEN SPACE TYPE. TERRACE REQUIRES
 20% MINIMUM VEGETATED AREA. ROOFTOP GARDEN REQUIRES 30%
 VEGETATED AREA AND 20% TREE CANOPY. TREE CANOPY VALUES
 CAN BE FOUND IN SECTION 94-109 TABLE IV-8.
 AREAS ON THE GROUND LEVEL ARE NOT NAMED FOR OPEN SPACE
 TYPE, AND REQUIREMENTS ARE NOT PROVIDED. TREE CANOPY
 SQUARE FOOTAGE CREDITS ARE TO MATCH TABLE IV-8 FOR OPEN
 SPACE.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 5 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
 7. SATISFIED. SHOW LOCATIONS OF UTILITY LINES ON
 LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND BACKFLOW
 PREVENTERS AND FPL TRANSFORMERS.
  
 8. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
  
 9. PARTIALLY SATISFIED. SHOW LOCATIONS OF REQUIRED
 STRUCTURAL SOIL UNDER HARDSCAPE ADJACENT TO TREES.
 PROVIDE A TYPICAL FOR THE INSTALLATION OF THE
 STRUCTURAL SOIL.
 VERTICAL DETAIL IS CORRECT, OVERHEAD TYPICAL IS
 INCORRECT AND MUST MATCH THE VERTICAL DETAIL. PLANTING
 AREAS AROUND STREET TREES MAY BE EXPANDED AS LONG AS
 THE 8 FOOT SIDEWALK WIDTH IS MAINTAINED. THIS WILL
 MINIMIZE THE AREAS OF STRUCTURAL SOIL REQUIRED UNDER
 THE ADJACENT PAVED AREA. PROVIDING A SEPARATE EXHIBIT
 CLEARLY SHOWING THE LOCATIONS OF THE PLANTING AREAS AND
 STRUCTURAL SOIL IS REQUIRED FOR STAFF TO VERIFY
 ADEQUATE PLACEMENT, AND IS HELPFUL LATER IN
 CONSTRUCTION FOR BIDDING AND INSTALLATION PURPOSES.
  
 10. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION
 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF
 PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 MUST INCLUDE ADDED PLANT MATERIAL NOT JUST REQUIRED.
 RECALCULATE AFTER ADJUSTMENTS FROM OTHER COMMENTS.
  
 ADDITIONAL COMMENTS 9/6/19:
  
 11. NOT SATISFIED. ARTIFICIAL TURF DOG WALKING AREA
 CANNOT BE VIEWABLE FROM THE ROAD OR STREET PER SECTION
 94-451, SO MUST BE FENCED TO BLOCK VIEW.
 ADDITIONAL COMMENT 10/28/19:
 12. THE PLACEMENT OF THE DRAINAGE FIELD BENEATH THE
 TREES IN THE PUBLIC OPEN SPACE HAS TO BE ACCEPTABLE TO
 THE STORMWATER ENGINEER FOR THE CITY.
  
 13. THE SOUTHERN OAK TREE AT THE CORNER OF QUADRILLE
 AND DATURA IS WITHIN THE FDOT SIGHTLINE. CONFIRM THAT
 THIS WILL BE ALLOWED BY FDOT.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 09-09-2019 Cont ID  
Sent By rcaranci Date 09-09-2019 Time 11:40 Rev Time 0.00
Received By rcaranci Date 09-09-2019 Time 11:40 Sent To  
Notes
2019-09-09 11:41:13FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 401 DATURA RESIDENTIAL Z19050020
 SEPTEMBER 6, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE TREE DISPOSITION PLAN NEEDS TO MATCH
 THE LOCATIONS SHOWN ON THE SURVEY AND USE THE SAME
 REFERENCE NUMBERS.
 ? PARTIALLY SATISFIED. TREE SPECIES ARE MISIDENTIFIED
 ON THE LIST. CORRECT THE SPECIES.
 TREE #24 IS A WASHINGTONIA ROBUSTA
 ? PARTIALLY SATISFIED. TREES AND PALMS CANOPY SQUARE
 FOOTAGE TO BE MITIGATED BASED ON CATEGORY. ANY TREES 20
 FEET OR MORE CANOPY DIAMETER TO BE MITIGATED BY ACTUAL
 SQUARE FOOTAGE.
 ONLY TREE #1 IS 20 FEET OR MORE CANOPY DIAMETER.
 MITIGATION IS 380 SQ FT.
 #22 AND 23 ARE DOUBLE WASHINGTONIA PALMS. CATEGORY 4
 ARE 50 SQ FT EACH, SO EACH DOUBLE IS 100 SQ FT CANOPY
 REMOVED.
 ALL OAKS AND 2 REMAINING BLACK OLIVE TREES ARE CATEGORY
 1 TREES AT 300 SQ FT EACH CANOPY REMOVED.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 AND SILVER TRUMPET
 #7 ARE CATEGORY 2 AND ARE EACH 150 SQ FT CANOPY
 REMOVED.
  
 ? PARTIALLY SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE
 OF MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 CORRECT ALL MITIGATION VALUES FOR THE ABOVE COMMENTS
 AND ADD TOTAL FOR MITIGATION DUE.
 ? PARTIALLY SATISFIED. PROVIDE THE MITIGATION VALUES BY
 CATEGORY FOR THE PROPOSED TREES AND PALMS.
 REMOVE NOTE FOR TREE MITIGATION CALCULATED AT
 PERMITTING. MITIGATION IS BASED ON CATEGORY LIST
 PROVIDED. LIST EACH SPECIES AND CATEGORY AND TOTAL
 MITIGATION VALUE.
  
 2. PARTIALLY SATISFIED. THE STREETSCAPE CAN BE IMPROVED
 TO ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113.
 THE ROYAL PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD
 THE TREE REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING.
 ADD CANOPY TREES AS REQUIRED.
 CALCULATE TREE REQUIREMENT ON S DIXIE (4) AND MEET
 REQUIREMENTS WITHIN THE RIGHT OF WAY. OPEN SPACE TREE
 CANOPY ADJACENT TO THIS AREA NEEDS TO BE DESIGNED TO
 COMPLEMENT REQUIRED STREET TREE CANOPY COVERAGE.
  
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
  
 4. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES
 NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE
 OR RELOCATED. SUBMIT THE REASON EXISTING LIVE OAK TREES
 CANNOT BE RELOCATED OR USED IN THE PROPOSED LANDSCAPE.
 EAST PALATKA HOLLIES #2, 3, 5, AND 6 ARE NOT IN GOOD
 CONDITION AND ARE TO BE REMOVED.
 LIVE OAK TREES #4, #20 AND 21 MAY BE RELOCATED TO THE
 WEST SIDE OF QUADRILLE ROW TO REPLACE MISSING LIVE OAK
 TREES.
  
 5. PARTIALLY SATISFIED. PUBLIC AND PRIVATE OPEN SPACE
 AREAS SHOWN ON SHEET MUST BE BROKEN DOWN TO SHOW THE
 REQUIRED VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT
 FOR EACH AREA AS THE ALLOWED OPEN SPACE TYPE. TERRACE
 REQUIRES 20% MINIMUM VEGETATED AREA. ROOFTOP GARDEN
 REQUIRES 30% VEGETATED AREA AND 20% TREE CANOPY. TREE
 CANOPY VALUES CAN BE FOUND IN SECTION 94-109 TABLE
 IV-8.
 AREAS ON THE GROUND LEVEL ARE NOT NAMED FOR OPEN SPACE
 TYPE, AND REQUIREMENTS ARE NOT PROVIDED. TREE CANOPY
 SQUARE FOOTAGE CREDITS ARE TO MATCH TABLE IV-8 FOR OPEN
 SPACE.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 5 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
 7. SATISFIED. SHOW LOCATIONS OF UTILITY LINES ON
 LANDSCAPE PLAN, ALSO LOCATIONS OF VALVES AND BACKFLOW
 PREVENTERS AND FPL TRANSFORMERS.
  
 8. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
  
 9. PARTIALLY SATISFIED. SHOW LOCATIONS OF REQUIRED
 STRUCTURAL SOIL UNDER HARDSCAPE ADJACENT TO TREES.
 PROVIDE A TYPICAL FOR THE INSTALLATION OF THE
 STRUCTURAL SOIL.
 VERTICAL DETAIL IS CORRECT, OVERHEAD TYPICAL IS
 INCORRECT AND MUST MATCH THE VERTICAL DETAIL. PLANTING
 AREAS AROUND STREET TREES MAY BE EXPANDED AS LONG AS
 THE 8 FOOT SIDEWALK WIDTH IS MAINTAINED. THIS WILL
 MINIMIZE THE AREAS OF STRUCTURAL SOIL REQUIRED UNDER
 THE ADJACENT PAVED AREA. PROVIDING A SEPARATE EXHIBIT
 CLEARLY SHOWING THE LOCATIONS OF THE PLANTING AREAS AND
 STRUCTURAL SOIL IS REQUIRED FOR STAFF TO VERIFY
 ADEQUATE PLACEMENT, AND IS HELPFUL LATER IN
 CONSTRUCTION FOR BIDDING AND INSTALLATION PURPOSES.
  
 10. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION
 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF
 PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
 MUST INCLUDE ADDED PLANT MATERIAL NOT JUST REQUIRED.
 ADDITIONAL COMMENTS 9/6/19:
  
 11. ARTIFICIAL TURF DOG WALKING AREA CANNOT BE VIEWABLE
 FROM THE ROAD OR STREET PER SECTION 94-451, SO MUST BE
 FENCED TO BLOCK VIEW.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By rcaranci Date 06-10-2019 Time 15:42 Rev Time 0.00
Received By rcaranci Date 06-10-2019 Time 15:42 Sent To  
Notes
2019-06-10 15:43:08FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 401 DATURA RESIDENTIAL Z19050020
 JUNE 10, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? THE TREE DISPOSITION PLAN NEEDS TO MATCH THE
 LOCATIONS SHOWN ON THE SURVEY AND USE THE SAME
 REFERENCE NUMBERS.
 ? TREE SPECIES ARE MISIDENTIFIED ON THE LIST. CORRECT
 THE SPECIES.
 ? TREES AND PALMS CANOPY SQUARE FOOTAGE TO BE MITIGATED
 BASED ON CATEGORY. ANY TREES 20 FEET OR MORE CANOPY
 DIAMETER TO BE MITIGATED BY ACTUAL SQUARE FOOTAGE.
 ? PROVIDE THE TOTAL SQUARE FOOTAGE OF MITIGATION FOR
 ALL TREES AND PALMS PROPOSED TO BE REMOVED.
 ? PROVIDE THE MITIGATION VALUES BY CATEGORY FOR THE
 PROPOSED TREES AND PALMS.
  
 2. THE STREETSCAPE CAN BE IMPROVED TO ACCOMPLISH THE
 INTENT OF THE CODE SECTION 94-113. THE ROYAL PALMS MAY
 BE USED, BUT NOT AS COUNTING TOWARD THE TREE
 REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING. ADD CANOPY
 TREES AS REQUIRED.
 3. REQUIRED STREET TREES MUST MEET THE 20 FOOT HEIGHT
 REQUIREMENT AT INSTALLATION. LIST OVERALL HEIGHT ON
 PLANT LIST.
  
 4. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD
 CONDITION TO BE PRESERVED ON SITE OR RELOCATED. SUBMIT
 THE REASON EXISTING LIVE OAK TREES CANNOT BE RELOCATED
 OR USED IN THE PROPOSED LANDSCAPE.
  
 5. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN ON SHEET
 MUST BE BROKEN DOWN TO SHOW THE REQUIRED VEGETATED AREA
 AND ANY TREE CANOPY REQUIREMENT FOR EACH AREA AS THE
 ALLOWED OPEN SPACE TYPE. TERRACE REQUIRES 20% MINIMUM
 VEGETATED AREA. ROOFTOP GARDEN REQUIRES 30% VEGETATED
 AREA AND 20% TREE CANOPY. TREE CANOPY VALUES CAN BE
 FOUND IN SECTION 94-109 TABLE IV-8.
  
 6. AREA LISTED AS POOL DECK ON LEVEL 5 IS NOT AN OPEN
 SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE OPEN SPACE
 TYPE (ROOFTOP GARDEN?) AND SHOW REQUIREMENTS.
 7. SHOW LOCATIONS OF UTILITY LINES ON LANDSCAPE PLAN,
 ALSO LOCATIONS OF VALVES AND BACKFLOW PREVENTERS AND
 FPL TRANSFORMERS.
  
 8. SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO
 PROTECT UTILITY LINES.
  
 9. SHOW LOCATIONS OF REQUIRED STRUCTURAL SOIL UNDER
 HARDSCAPE ADJACENT TO TREES. PROVIDE A TYPICAL FOR THE
 INSTALLATION OF THE STRUCTURAL SOIL.
  
 10. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 4 Status P Date 02-26-2020 Cont ID  
Sent By   Date 02-26-2020 Time   Rev Time 0.00
Received By   Date 02-04-2020 Time   Sent To  
Notes
2020-02-26 14:23:47APPROVED WITH THE CONDITIONS BELOW, WHICH HAVE TO BE
 MET FOR THE BUILDING PERMIT:
 1 - THE CITY TRASH ROOM SPECIFICATIONS:
 FLOOR SHALL BE 6-INCH THICK CONCRETE.
 ROLL-UP DOOR(S) SHALL HAVE MIN. 10 FT. HEIGHT AND
 WIDTH.
 THE ROOM SHALL HAVE A DEDICATED ELECTRICAL DISCONNECT.
 THE ROOM SHALL BE CLIMATE CONTROLLED.
 2 - PRIVATE HAULER REVIEW AND INPUT OF THE PROPOSED
 AUTO TURN TO SERVICE THE 30CY SELF-CONTAINED COMPACTOR.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 3 Status F Date 11-06-2019 Cont ID  
Sent By   Date 11-06-2019 Time   Rev Time 0.00
Received By   Date 11-06-2019 Time   Sent To  
Notes
2019-11-06 08:50:40PLEASE MAKE SURE THE COMPACTOR IS:
 - A FRONT LOADER CONTAINER TYPE TO BE SERVICED BY A
 FRONT LOADER TRUCK WITH THE SIDE POCKETS STANDARD WIDTH
 - HAS WHEELS TO BE ROLLED OUT FOR EASE OF SERVICE.
 - ENCLOSED IN AN ENCLOSURE, IF STORED OUTSIDE, AND THE
 ENCLOSURE COMPLIES WITH THE LATEST REVISION OF CITY OF
 WEST PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, CG-8.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date 09-25-2019 Cont ID  
Sent By   Date 09-25-2019 Time   Rev Time 0.00
Received By   Date 09-25-2019 Time   Sent To  
Notes
2019-09-25 13:33:04PLEASE PROVIDE THE FOLLOWINGS:
 - TRASH ROOM SPECIFICATION AND DIMENSIONS FOR THE
 COMPACTORS
 - UPDATED AUTO TURN FOR THE SANITATION SERVICE,
 INDICATING THE TRUCK WIDTH OF 11 FT. (SHEET C-12)
 - CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF
 SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER)
 - DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RRECYCLE RECEPTACLE CONTAINERS.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-04-2019 Cont ID  
Sent By   Date 06-11-2019 Time   Rev Time  
Received By   Date 06-11-2019 Time   Sent To  
Notes
2019-06-11 09:52:27PLEASE PROVIDE THE FOLLOWINGS:
 - LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE OF THE
 COMPACTOR THAT WILL BE UTILIZED.
 - ENCLOSURE SPEC PER LATEST REVISION OF CITY OF WEST
 PALM BEACH GENERAL CONSTRUCTION-GARBAGE ENCLOSURE
 STANDARD, CG-8, LATEST REVISION.
 - AUTO TURN FOR THE SANITATION SERVICE
 - CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF
 SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER)
 - DESIGNATED LOCATION FOR THE BULK ITEM PICK UP AND
 RRECYCLE RECEPTACLE CONTAINERS.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 6 Status P Date 02-27-2020 Cont ID  
Sent By tward Date 02-27-2020 Time 09:45 Rev Time 0.00
Received By tward Date 02-27-2020 Time 09:45 Sent To  
Notes
2020-02-27 09:20:13THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 ENGINEERING PLAN SUBMITTAL RECEIVED 2/25/2020. THEY
 SHOULD NOT AFFECT THE SITE FOR SITE PLAN APPROVAL BUT
 WILL AFFECT THE ENGINEER PERMIT APPROVAL.
  
 1. PARTS OF THE ALLEY WILL NEED TO BE RECONSTRUCTED AS
 INVERTED CROWN WITH THE APPROPRIATE PAVEMENT SECTION
 RATHER THAN MILLED AND RESURFACED. SOME OF THE PROPOSED
 SPOT GRADES ARE NEARLY 2 INCHES LOWER THAN THE EXISTING
 ASPHALT GRADE. VALLEY GUTTER MAY BE NEEDED DOWN THE
 CENTER OF THE ALLEY TO FACILITATE DRAINAGE.
  
 2. ADDITIONAL SURVEY SPOT GRADES SHOULD BE OBTAINED
 ALONG THE NORTH RIGHT-OF-WAY LINE OF THE ALLEY TO
 CONFIRM THE PROPOSED PROFILE OF THE ALLEY WILL NOT
 AFFECT THE DRAINAGE OF THE PROPERTIES ON THE NORTH SIDE
 OF THE ALLEY. THE PLANS INDICATE THERE ARE DOORWAYS
 OPENING NEXT TO THE ALLEY WITH NOTES TO THE CONTRACTOR
 TO NOT GRADE ABOVE THE DOORWAY. THERE IS ALSO A
 PROPOSED SPOT GRADE OF 15.00 ON THE NORTH R/W SOUTH OF
 AN EXISTING SPOT GRADE OF 14.89.
  
 3. OBTAIN THE FINISHED FLOOR ELEVATION FROM THE
 ARCHITECT FOR THE SECTION OF THE BUILDING ALONG
 QUADRILLE BLVD. SHOW THIS ELEVATION ON SECTION D-D.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop STORM STORMWATER
Rev No 5 Status F Date 02-18-2020 Cont ID  
Sent By tward Date 02-18-2020 Time 16:52 Rev Time 0.00
Received By tward Date 02-19-2020 Time 09:04 Sent To  
Notes
2020-02-19 09:04:00THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 1/28/2020 SUBMITTAL PACKAGE:
  
 1. [REPEAT COMMENT] REVIEW THE PROPOSED GRADING OF THE
 ALLEY. IT APPEARS WATER WILL BE PREVENTED FROM DRAINING
 FROM THE PROPERTIES ON THE NORTH SIDE OF THE ALLEY.
 THERE IS AN EXISTING OFFSITE SPOT GRADE OF 14.10 (NEAR
 THE CROSS SECTION C-C CALLOUT). THE PROPOSED FLOW LINE
 OF THE ALLEY ADJACENT TO THE SPOT GRADE IS BETWEEN
 14.15 AND 14.85. THERE IS AN EXISTING SPOT GRADE OF
 14.05 (FURTHER TO THE EAST) AND THE PROPOSED FLOW LINE
 OF THE ALLEY IS 14.00. THE NORTH SIDE OF THE ALLEY WILL
 HAVE A VERY FLAT CROSS SLOPE AND STORMWATER RUNOFF WILL
 POOL IN THIS LOCATION, INCLUDING IN THE ADJACENT
 OFFSITE AREA.
  
 2. VERIFY THE PROPOSED FINISHED FLOOR ELEVATION OF
 15.05 FEET NAVD PROVIDED ON CROSS SECTION D-D FOR THE
 WEST PROPERTY LINE. THERE IS A PROPOSED SPOT GRADE OF
 17.65 ALONG THE WEST SDIE OF THE BUILDING.
  
 3. THE CONCRETE SIDEWALK ALONG THE WEST SIDE OF THE
 BUILDING SHALL BE CONTINUED ACROSS THE ALLEY. SHEET
 C-05 SHOWS THE SIDEWALK AREA AS MILL AND RESURFACE.
  
 4. ADD MORE PRB'S UPSTREAM OF THE EXFILTRATION TRENCHES
 TO EXTEND THEIR LIFE.
  
 5. DIMENSION THE LOW SPOT OF THE ALLEY IN SECTION C-C
 ON SHEET C-07. STAFF IS UNCLEAR IF THE NOTE ?LOW SPOT
 IS CENTER OF ALLEY? REFERS TO THE CENTER OF THE
 PROPOSED 20? ALLEY OR THE CENTER OF THE ALLEY R/W.
  
 6. IN SECTION C-C ON SHEET C-07 PROVIDE A DIMENSION FOR
 THE DISTANCE BETWEEN THE ALLEY R/W LINE AND THE SOUTH
 EDGE OF PAVEMENT.
  
 7. ALTHOUGH DRAINAGE CALCULATIONS WERE NOT PROVIDED
 WITH THIS SUBMITTAL, THEY WERE SUBMITTED WITH THE
 ENGINEERING PERMIT APPLICATION PACKAGE. THE
 EXFILTRATION CALCULATIONS DID NOT TAKE INTO ACCOUNT THE
 FLOW RESTRICTIONS OF THE ADJACENT TRENCHES ON EACH
 OTHER.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop STORM STORMWATER
Rev No 4 Status F Date 12-12-2019 Cont ID  
Sent By tward Date 12-12-2019 Time 11:29 Rev Time 0.00
Received By tward Date 12-12-2019 Time 11:47 Sent To  
Notes
2019-12-12 11:47:15THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 DECEMBER 5, 2019 REVIEW SUBMITTAL PACKAGE. NO WRITTEN
 RESPONSES WERE PROVIDED TO THE OCTOBER 2019 COMMENTS.
  
 1. SHEET C-07 CONTAINING THE CROSS SECTIONS IS NOT
 INCLUDED IN THE PACKAGE. [REPEAT COMMENT]
  
 2. PROVIDE CONDITION ASSESSMENT OF EXISTING CATCH BASIN
 IN THE ALLEY AND IF IT CAN BE MODIFIED TO ACCEPT THE
 NEW DRINAGE PIPE. [REPEAT COMMENT]
  
 3. IT APPEARS THE RECONSTRUCTION OF THE ALLEY WILL TRAP
 STORMWATER RUNOFF NORTH OF THE ALLEY. VERIFY THE MILL
 AND OVERLAY OF THE ALLEY WILL NOT AFFECT THE EXISTING
 SURFACE DRAINAGE OF THE OFFSITE AREAS. [REPEAT COMMENT]
  
 4. THE ONSITE DRAINAGE SYSTEM IS SHOWN TO BE
 EXILTRATION TRENCHES SIDE BY SIDE SIMILAR TO A DRAIN
 FIELD AND WITH TREES PLANTED OVER THE EXFILTRATION
 TRENCHES. THE FLOW OUT OF THE SIDES OF THE TRENCHES
 WILL BE AFFECTED BY THE ADJACENT TRENCHES. PROVIDE A
 DIFFERENT LAYOUT PATTERN OR CONSIDER A DIFFERENT TYPE
 OF STORAGE SYSTEM SUCH AS SUSPENDED PAVEMENT,
 STORMTRAP, CON/SPAN, ETC. [REPEAT COMMENT]
  
 5. IT APPEARS DRAINAGE STRUCTURE NO. 12 WILL BE A NEW
 STRUCTURE AND NEW STORM PIPE CROSSING DATURA ST. TO THE
 EXISTING CATCH BASIN ON THE SOUTH SIDE OF DATURA ST. IS
 STRUCTURE NO. 12 ADDED STRICTLY FOR CONNECTING THE
 OUTFALL PIPE FROM THE ONSITE EXFILTRATION SYSTEM? IS IT
 POSSIBLE TO CONNECT THE ONSITE SYSTEM TO THE EXISTING
 CATCH BASIN (CURB INLET) FURTHER TO THE EAST AT THE NW
 CORNER OF DATURA ST AND S. DIXIE HWY? [REPEAT COMMENT]
  
 6. LABEL THE STREETS ON SHEET C-05. [REPEAT COMMENT]
  
 7. LABEL THE EXISTING STORM PIPE SIZES AND PIPE
 MATERIAL. [REPEAT COMMENT]
  
 8. IT APPEARS SOME OF THE EXISTING ELEVATION DATA ON
 SHEET C-05 ARE IN REFERENCE TO NGVD1929 WHEREAS THERE
 IS A NOTE STATING ALL ELEVATION DATA ARE NAVD1988. BY
 WAY OF EXAMPLES, ALL OF THE LISTED GRATE ELEVATIONS FOR
 THE EXISTING CATCH BASINS ON THE SOUTH SIDE OF DATURA
 STREET ARE AT LEAST ONE FOOT HIGHER THAN THE GRATE
 ELEVATIONS FOR THE PROPOSED DRAINAGE STRUCTURES ON THE
 NORTH SIDE OF THE STREET. THE SOUTH INVERT ELEVATION
 FOR STRUCTURE NO. 12 IS LOWER THAN THE NORTH INVERT
 ELEVATION OF THE STRUCTURE THE DRAINAGE PIPE IS
 CONNECTING TO.
  
 9. WHAT IS THE PURPOSE FOR YARD DRAINS NOS. 15 AND 16?
  
 10. CONFIRM ALL OF THE ROOF DRAINS WILL DRAIN TO THE
 ONSITE WATER MANAGEMENT SYSTEM LOCATED ON THE EAST SIDE
 OF THE PROJECT.
  
 11. IT APPEARS YARD DRAIN NO. 9 WILL BE LOCATED IN THE
 STEPS TO THE PUBLIC PLAZA.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 10-30-2019 Cont ID  
Sent By tward Date 10-30-2019 Time 16:44 Rev Time 0.00
Received By tward Date 10-30-2019 Time 17:23 Sent To  
Notes
2019-10-30 17:20:16THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 11, 2019 REVIEW SUBMITTAL PACKAGE.
  
 1. SHEET C-07 CONTAINING THE CROSS SECTIONS IS NOT
 INCLUDED IN THE PACKAGE.
  
 2. PROVIDE CONDITION ASSESSMENT OF EXISTING CATCH BASIN
 IN THE ALLEY AND IF IT CAN BE MODIFIED TO ACCEPT THE
 NEW DRINAGE PIPE.
  
 3. IT APPEARS THE RECONSTRUCTION OF THE ALLEY WILL TRAP
 STORMWATER RUNOFF NORTH OF THE ALLEY. VERIFY THE MILL
 AND OVERLAY OF THE ALLEY WILL NOT AFFECT THE EXISTING
 SURFACE DRAINAGE OF THE OFFSITE AREAS.
  
 4. THE ONSITE DRAINAGE SYSTEM IS SHOWN TO BE
 EXILTRATION TRENCHES SIDE BY SIDE SIMILAR TO A DRAIN
 FIELD AND WITH TREES PLANTED OVER THE EXFILTRATION
 TRENCHES. THE FLOW OUT OF THE SIDES OF THE TRENCHES
 WILL BE AFFECTED BY THE ADJACENT TRENCHES. PROVIDE A
 DIFFERENT LAYOUT PATTERN OR CONSIDER A DIFFERENT TYPE
 OF STORAGE SYSTEM SUCH AS SUSPENDED PAVEMENT,
 STORMTRAP, CON/SPAN, ETC.
  
 5. IT APPEARS DRAINAGE STRUCTURE NO. 12 WILL BE A NEW
 STRUCTURE AND NEW STORM PIPE CROSSING DATURA ST. TO THE
 EXISTING CATCH BASIN ON THE SOUTH SIDE OF DATURA ST. IS
 STRUCTURE NO. 12 ADDED STRICTLY FOR CONNECTING THE
 OUTFALL PIPE FROM THE ONSITE EXFILTRATION SYSTEM? IS IT
 POSSIBLE TO CONNECT THE ONSITE SYSTEM TO THE EXISTING
 CATCH BASIN FURTHER TO THE EAST AT THE NW CORNER OF
 DATURA ST AND S. DIXIE HWY?
  
 6. LABEL THE STREETS ON SHEET C-05.
  
 7. LABEL THE EXISTING STORM PIPE SIZES AND PIPE
 MATERIAL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  
  
  
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 08-29-2019 Cont ID  
Sent By tward Date 08-29-2019 Time 10:18 Rev Time 0.00
Received By tward Date 08-29-2019 Time 11:01 Sent To  
Notes
2019-08-29 11:01:16THE FOLLOWNIG COMMENTS ARE FROM THE REVIEW OF THE
 AUGUST 20, 2019 ROUTED SUBMITTAL PACKAGE.
  
 1. REVIEW THE ELEVATION INFORMATION FOR THE EXISTING
 DRAINAGE STRUCTURES ON SHEET C-05. IT MAY BE LISTING
 THE INFORMATION IN RELATION TO NGVD 1929. THE NOTE ON
 THE PLAN INDICATES NAVD 1988 IS THE VERTICAL DATUM.
  
 2. REVIEW GRATE ELEVATION FOR STRUCTURE NO. 11. IT IS
 THE SAME ELEVATION AS THE GRATE ELEVATION FOR STRUCTURE
 NO. 12 AND ALSO CREATES A 6% GUTTER SLOPE TO THE SPOT
 GRADE OF 14.55 TO THE WEST. ALSO REVIEW THE INVERT
 DIRECTIONS LISTED FOR STRUCTURE NO. 11.
  
 3. ADVERSE SLOPE FOR THE PIPE BETWEEN STRUCTURES NO. 11
 AND NO. 12.
  
 4. TWO TYPES OF MATERIAL (DIP AND RCP) INDICATED FOR
 THE PIPE SOUTH OUT OF STRUCTURE NO. 10.
  
 5. STORM PIPE CROSSING DATURA STREET TO THE EAST OF
 STRUCTURE NO. 9 WILL NEED TO BE REMOVED OR ABANDONED IN
 PLACE DEPENDING ON THE PIPE SIZE.
  
 6. SHOW MILLING AND RESURFACING LIMITS FOR THE TRENCH
 CUTS IN THE RIGHT OF WAY.
  
 7. ON THE EXFILTRATION TRENCH DETAIL ON SHEET C-06, ALL
 OF THE ELEVATIONS SHOULD BE IN REFERENCE TO NAVD1988.
 ALSO SHOW THE CONVERSION BETWEEN NAVD1988 AND NGVD1929
 ON THE SHEET.
  
 8. REVIEW THE FFE LISTED ON SHEET C-05 AND LISTED FOR
 THE CROSS SECTIONS SHOWN ON SHEET C-07.
  
 9. SHOW DIRECTIONAL FLOW ARROWS ON THE CROSS SECTIONS
 ON SHEET C-07.
  
 10. FOR SECTION A-A ON SHEET C-07, IS TYPE 'F' CURB AND
 GUTTER NEEDED IF THE PARKING STALL SLOPES TO THE VALLEY
 GUTTER? DOES THE WIDTH OF THE PARKING STALL INCLUDE THE
 2-FOOT VALLEY GUTTER.
  
 11. FOR SECTION C-C ON SHEET C-07, SHOW THE DISTANCE
 FROM THE PROPERTY LINE TO THE FACE OF CURB. PROVIDE
 CROSS SLOPE INFORMATION.
  
 12. RCP PIPE TO BE USED FOR STORMWATER WITHIN THE
 RIGHT-OF-WAY (NORTH PIPE AT STRUCTURE NO. 1).
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By tward Date 06-10-2019 Time 18:31 Rev Time 0.00
Received By tward Date 06-10-2019 Time 18:33 Sent To  
Notes
2019-06-10 18:32:52THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY?S VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED ON THE SHEET(S).
 LABEL THE VERTICAL DATUM ON THE ENGINEERING SHEETS
 CONTAINING ELEVATION INFORMATION AND PROVIDE THE
 CONVERSION EQUATION TO NGVD1929.
  
 2. REVIEW THE GRATE ELEVATION OF 15.22 FT NAVD FOR
 STRUCTURE #11. IT IS SITUATED BETWEEN SPOT GRADES OF
 14.60 AND 14.40 FOR THE VALLEY GUTTER.
  
 3. EXISTING CATCH BASIN TO THE EAST OF THE VALLEY
 GUTTER SPOT GRADE 14.40 HAS A GRATE ELEVATION OF 14.85.
  
 4. PROPOSED PIPE BETWEEN PROPOSED YARD DRAIN #4 AND
 EXISTING CATCH BASIN WILL HAVE AN ADVERSE SLOPE. SOUTH
 INVERT ELEVATION AT YARD DRAIN IS 9.50. BOTTOM
 ELEVATION OF EXISTING CATCH BASIN IS 10.80.
  
 5. PROVIDE CROSS SECTIONS FOR THE PARKING AREA AND DROP
 AREA
  
 6. PROVIDE CROSS SECTION AND PAVEMENT DESIGN FOR THE
 ALLEY.
  
 7. REVISE YARD DRAIN #5 TO HAVE THE PRB ON THE EAST
 INVERT.
  
 8. WHICH STRUCTURE WILL CONTAIN A WEIR TO SURCHARGE THE
 EXFILTRATION TRENCHES.
  
 9. S. QUADRILLE BLVD. IS MAINTAINED BY FDOT. FDOT
 PERMITS WILL BE NEEDED FOR WORK WITHIN THE QUADILLE
 BLVD. RIGHT OF WAY.
  
 10. SIDEWALKS SHOULD BE GRADED TO DIRECT RUNOFF TO THE
 ONSITE DRAINAGE SYSTEM.
  
 11. PROVIDE CCTV VIDEOS OF THE THREE DRAINAGE PIPES ON
 DATURA STREET CONNECTED TO PROPOSED STRUCTURES #4, #10
 AND #11.
  
 12. SIDEWALK EASEMENT WILL BE NEEDED ADJACENT TO THE
 DROP OFF AREA.
  
 13. PORTE-COCHERE ENCROACHES INTO THE RIGHT-OF-WAY.
  
 14. HARDSCAPE FEATURES LOCATED WITH THE RIGHT-OF-WAY.
  
 15. TREES PROPOSED OVER AND ADJACENT TO THE
 EXFILTRATION SYSTEM.
  
 16. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD
 CRITERIA FOR WATER QUALITY TREATMENT AND PEAK FLOW
 ATTENUATION.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING
 CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 6 Status P Date 02-26-2020 Cont ID  
Sent By vnoel Date 02-26-2020 Time 14:04 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-02-26 14:05:501. PASSED. REMAINING COMMENTS WILL NEED TO BE ADDRESSED
 IN ENGINEERING PERMIT REVIEW.

Review Stop SURVEY SURVEYING
Rev No 5 Status F Date 02-12-2020 Cont ID  
Sent By vnoel Date 02-12-2020 Time 08:05 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2020-02-12 08:25:491. PREVIOUS COMMENTS NOT ADDRESSED.
 2. AN ENGINEERING SUBMITTAL WAS MADE PRIOR TO SITE PLAN
 APPROVAL. SEE ADDITIONAL COMMENTS FROM MARK HURLEY W/
 CUSTOMER SERVICE, TRACY WARD AND RICK ROSSANO. PLEASE
 ADDRESS ALL COMMENTS IN WRITING AT NEXT SUBMITTAL.
 THESE WERE SENT TO THOMAS ENG. ON 2/6.
 3. FOR PLANNING - WHAT IS THE ALLOWABLE CANOPY
 ENCROACHMENT IN DATURA? HOW IS THIS CANOPY TO BE
 SUPPORTED?
  
  
  
 .FROM: RICK ROSSANO
 SENT: THURSDAY, FEBRUARY 06, 2020 1:28 PM
 TO: DANIELA MARTINAT ; JASON
 GUNTHER
 CC: MARK HURLEY ; MANUEL GONZALEZ
 ; TRACY WARD
 SUBJECT: COMMENTS FOR ENGINEERING PERMIT E20010032 -
 401 DATURA STREET, SENIOR APARTMENTS
  
 PLEASE FIND ENCLOSED COMMENTS FOR THE SUBJECT PROJECT
 FOR YOUR USE:
  
 COMMENTS FROM MARK HURLEY, CUSTOMER SERVICE SUPERVISOR,
 WPB PUBLIC UTILITIES, 561-822-2262, [email protected]
  
 -FIRE HYDRANT NEAR SE INTERSECTION SAYS ?RELOCATED?,
 BUT NOT KNOWN WHERE IT IS RELOCATED FROM. WHY DOES FIRE
 HYDRANT NEED TO BE RELOCATED INSTEAD OF EXTRA ONE
 ADDED?
  
 -EXISTING FIRE HYDRANT MISSING FROM SW INTERSECTION
 LARGE PLAN.
  
 -4 IN. DOMESTIC METER NEEDS TO BE ABOVE-GROUND
 INSTALLED USING SD WS-8 INSTEAD OF UNDERGROUND VAULT
 INSTALLED.
  
 -NEED TO HAVE ARROW POINTING FROM "4 IN. LEAD FREE RPZ"
 TO THE BACKFLOW ASSEMBLY ICON ON THE PLAN. ALSO ADD "WS
 7".
  
 -PLAN NOT SHOWING THE NEW WATER SERVICES ON DATURA
 WATER MAIN THAT FEED 499 EVERNIA ST.
  
 -SEE SOME NOTES THAT SAY "CAP WATER SERVICE AT MAIN".
 IF THOSE ARE WATER SERVICES WITH AN ASSOCIATED METER
 BOX NEED SHOW ON PLAN WHERE BOX IS AND ADD NOTE TO HAVE
 BOX REMOVED. NEED ALSO PUT WHAT HAPPENING TO OLD
 SERVICE LINE (REMOVED?)
 -NEED ARROW POINTING FROM 1 1/2 INCH RPZ TO THE ICON ON
 PLAN. ADD "WS 11"
  
 -SERVICE PIPING FOR 1 1/2 WATER SERVICE NOT LABELED
 WITH SIZE AND PIPE MATERIAL. ADD "WS 1" TO METER LABEL.
  
 -SERVICE PIPING AFTER 12 IN. X 4 IN. TAP NOT LABELED
 WITH SIZE AND PIPE MATERIAL. 4 IN. TAP WILL BE FEEDING
 4 IN. METER AND 1.5 IN. METER -> IS THAT TAP SIZE
 SUFFICIENT?
  
 -THE NEW WATER SERVICES HAVE PIPING THAT IS CROSSING
 EACH OTHER IN MULTIPLE LOCATIONS. CAN THE PIPING BE
 ADJUSTED SO THAT CROSSINGS ARE ELIMINATED?
  
 -RECOMMEND PARALLEL BACKFLOW ASSEMBLIES ON DOMESTIC
 WATER SERVICE TO ELIMINATE OUTAGES FOR CUSTOMER DURING
 BACKFLOW MAINTENANCE.
  
 -CAN POINT OF SERVICE GV FOR THE 6 IN. FIRE LINE BE
 RELOCATED SLIGHTLY NORTH INTO UE TO BE OUT OF FOOT
 TRAFFIC?
  
 -AFTER 4 IN. TAP THERE ARE TWO ICONS FOR GV?S. IS THAT
 CORRECT?
  
 -DO NOT SEE IRRIGATION USE IN THE DEMAND CHART. DOES IT
 NEED TO BE INCLUDED IN THE CHART?
  
 -LOOKS TO BE A LIGHT POLE TOO CLOSE TO FIRELINE WATER
 SERVICE. SHOULD BE 5 FEET AWAY FROM EACH OTHER.
  
 -POINT OF SERVICES LABEL INCORRECT ON DETAIL A.
  
 -ON THE NW AREA OF PLAN THERE ARE TWO SETS OF DOORS
 THAT OPEN OUTWARD INTO THE ROADWAY. DID NOT KNOW IF
 THAT IS SAFE?
  
 -IT IS VERY HARD TO SEE THE BOUNDARIES OF THE NEW
 UTILITY EASEMENT -> NEED TO MAKE CLEARER.
  
  
 THE FOLLOWING COMMENTS ARE PER TRACY L. WARD, P.E.,
 CITY OF WPB SENIOR STORMWATER ENGINEER:
  
 1. THE PROPOSED GRADING OF THE ALLEY WILL TRAP WATER ON
 THE PROPERTY ON THE NORTH SIDE OF THE ALLEY.
 2. THE SIDEWALK AT THE WEST END OF THE ALLEY SHOULD BE
 CONSTRUCTED OF CONCRETE INSTEAD OF BEING REPLACED WITH
 ASPHALT.
 3. ADD MORE PRB?S IN THE DRAINAGE STRUCTURES UPSTREAM
 OF THE EXFILTRATION TRENCHES TO EXTEND THE LIFE OF THE
 TRENCHES.
 4. THE EXFILTRATION EQUATION USED IN THE DRAINAGE
 CALCULATIONS IS NOT APPROPRIATE FOR THE LAYOUT OF THE
 TRENCHES. THE TRENCHES ARE ONLY SEPARATED BY 3 FEET AND
 EACH TRENCH WILL AFFECT THE FLOW RATE THROUGH THE SIDE
 OF THE ADJACENT TRENCH.
 5. PROPOSED SPOT GRADES OUTSIDE THE SOUTH AND WEST
 SIDES OF THE BUILDING ARE HIGHER THAN THE PROPOSED
 FINISHED FLOOR ELEVATION. SECTIONS A-A AND D-D ON SHEET
 C-07 DO NOT REFLECT THIS. THERE APPEAR TO BE DOOR
 OPENINGS ON THE WEST SIDE OF THE BUILDING.
 6. DIMENSION THE LOW SPOT OF THE ALLEY IN SECTION C-C
 ON SHEET C-07. STAFF IS UNCLEAR IF THE NOTE LOW SPOT IS
 CENTER OF ALLEY REFERS TO THE CENTER OF THE PROPOSED 20
 FT. ALLEY OR THE CENTER OF THE ALLEY R/W.
 7. IN SECTION C-C ON SHEET C-07 PROVIDE A DIMENSION FOR
 THE DISTANCE BETWEEN THE ALLEY R/W LINE AND THE SOUTH
 EDGE OF PAVEMENT.
  
 WITH REGARDS,
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS ST., 4TH FLOOR
 WEST PALM BEACH, FL 33401
 PHONE: 561-494-1120
 FAX: 561-494-1116
 CELL 561-351-0510
 [email protected]
  
  
 THE FOLLOWING COMMENTS ARE PER RICK ROSSANO, PROJ.
 COORDINATOR, ENG. SERVICES:
  
 PLEASE CLEARLY LABEL 12 IN. WATER MAIN WITH PIPE SIZE &
 MATERIAL.
  
 PLEASE ADD FIRE FLOW DEMANDS.
  
 PLEASE PROVIDE PERVIOUS/IMPERVIOUS CALCULATIONS TO
 DRAINAGE SHEET.
  
 PLEASE UPDATE STANDARD DETAIL GC-6.
  
  
 THANKS,
  
 RICK ROSSANO
 PROJECT COORDINATOR
 WPB ENGINEERING SERVICES
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 CELL: (561) 246-9525
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
  

Review Stop SURVEY SURVEYING
Rev No 4 Status F Date 12-10-2019 Cont ID  
Sent By vnoel Date 12-10-2019 Time 09:30 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-12-10 09:31:421. NO RESPONSE TO PREVIOUS SURVEY COMMENTS.

Review Stop SURVEY SURVEYING
Rev No 3 Status F Date 11-06-2019 Cont ID  
Sent By vnoel Date 11-06-2019 Time 07:23 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-11-06 07:25:151. REPLAT WILL BE REQUIRED.
 2. NO RESPONSE TO SURVEY COMMENTS IN LAST SUBMITTAL.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 09-11-2019 Cont ID  
Sent By vnoel Date 09-11-2019 Time 07:41 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-09-11 07:41:441. REMOVE VAULT FROM SIDEWALK AREA. APPROVAL FROM MARK
 HURLEY, CUSTOMER SERVICE, WILL BE REQUIRED FOR
 METER/BACKFLOW ASSEMBLY.
 2. CANOPY MAY REQUIRE AN AERIAL ENCROACHMENT EASEMENT.
 3. A LANDSCAPE/HARDSCAPE MAINTENANCE AGREEMENT WITH
 FDOT WILL BE REQUIRED. THE APPLICANT NEEDS TO PROCESS
 APPLICATION WITH FDOT FOR THE CITY TO APPROVE. THE
 OWNER WITH THEN ASSUME OBLIGATIONS OF THAT AGREEMENT
 AND ANY OTHER RIGHT-OF-WAY MAINTENANCE OBLIGATIONS
 THROUGH A SEPARATE AGREEMENT WITH THE CITY.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By vnoel Date 06-07-2019 Time 09:34 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2019-06-07 10:17:571. REPLAT WILL BE REQUIRED.
 2. THERE ARE 2 EXISTING COMPACTORS AND 2 RECYCLING
 DUMPSTERS THAT WE WOULD LIKE TO RETAIN ON-SITE.
 3. NOT SURE IF REGRADING THE ALLEY WILL BE POSSIBLE TO
 FLOW TO EASTERN CATCH BASIN.
 4. NEED TO REVIEW LOCATION OF METER AND BACKFLOW IN SW
 CORNER. WILL NEED TO SEE BLOW-UP TO SCALE WITH PROPOSED
 IMPROVEMENTS AND LANDSCAPING.
 5. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR
 IMPROVEMENTS/LANDSCAPING WITHIN RIGHT-OF-WAYS.
 QUADRILLE WILL REQUIRE A LMOA WITH THE FDOT.
 6. EASEMENT MAY BE REQUIRED FOR WIDENED ALLEY.
 7. CANOPY WITHIN DATURA WILL NEED TO BE DISCUSSED.
 8. VERTICAL DATUM NEEDS TO BE ADDED TO ALL PLANS.
 9. APPROVAL FROM FPL WILL BE REQUIRED FOR ANY EASEMENT
 ENCROACHMENT OR RELEASE.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 01-16-2020 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2020-01-16 09:39:48PASSED WITH CONDITIONS:
 1. THE DEVELOPER SHALL BE REQUIRED TO COORDINATE WITH
 CITY PARKING ADMINISTRATOR FOR PRIVATE COMMERCIAL USE
 OF CURBSIDE PARKING SPACE PER CITY CODE 94-111(L).
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 10-23-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-10-23 10:53:05SITE PLAN COMMENTS:
 1. THE BICYCLE PARKING SPACES PROVIDED UNDER CITY CODE
 94-113(D)(9) SHOULD BE PUBLICLY ACCESSIBLE. PLEASE
 VERIFY IF THE 4 BICYCLE PARKING SPACES NEAR THE PUBLIC
 PLAZA ARE OPEN FOR THE PUBLIC AS THEY APPEAR TO BE
 LOCATED WITHIN THE OUTDOOR DINING AREA.
 2. IN SHEET C-11, THE STOP BAR AT THE ALLEY SHOULD BE
 LOCATED AT LEAST 4 FEET IN ADVANCE OF THE
 SIDEWALK/CROSSWALK.
 3. PROVIDE DETECTABLE WARNINGS ON THE SIDEWALK ACROSS
 BOTH ALLEY ACCESS POINTS.
 4. THE PARALLEL PARKING SPACES ON DATURA STREET SHOULD
 BE AT LEAST 20 FEET AWAY FROM THE CROSSWALK AND AT
 LEAST 15 FEET AWAY FROM FIRE HYDRANT PER MUTCD AND
 FLORIDA STATUTES, AND SHOULD BE CLEAR OF THE PROPOSED
 FIRE DEPARTMENT CONNECTION. THE FIRST PARKING SPACE ON
 THE NORTH SIDE OF DATURA STREET EAST OF QUADRILLE
 BOULEVARD IS CURRENTLY HATCHED OUT AND IS NOT BEING
 USED FOR PARKING.
 5. PROVIDE AN ADDITIONAL ON-STREET PARKING SPACE EAST
 OF THE VALET AREA.
 6. RELOCATE THE FIRE HYDRANT NEAR DIXIE HIGHWAY OUT OF
 THE SIDEWALK AREA.
 7. THE RESPONSE INDICATED THAT THE LANDSCAPE AREA ON
 THE BUILDING SIDE HAS BEEN REDUCED TO ACCOMMODATE
 LARGER SIDEWALK AS REQUESTED, BUT THE SIDEWALK WIDTH
 REMAINS AT 10 FEET AND DID NOT CHANGE FROM THE PREVIOUS
 SUBMITTAL. PLEASE PROVIDE 12-FOOT SIDEWALK ALONG
 QUADRILLE BLVD.
 8. PAVEMENT MILL AND RESURFACE ON DATURA STREET AFTER
 UTILITY TIE-IN SHOULD INCLUDE BOTH SIDES OF THE STREET.
 9. PLEASE CLARIFY IF THE LANDSCAPE ON QUADRILLE
 BOULEVARD MEETS FDOT'S SIGHT DISTANCE REQUIREMENTS.
  
 TRAFFIC STATEMENT COMMENTS:
 10. PLEASE VERIFY THE VEHICLE CIRCULATION ROUTE FOR
 VALET ACCESS AS EASTBOUND VEHICLES ON DATURA STREET
 WOULD NOT BE ABLE TO MAKE A U-TURN TO ACCESS THE VALET
 AREA, NOR OUTBOUND VALET VEHICLES WOULD BE ABLE TO MAKE
 A U-TURN TO HEAD EAST.
 11. PROVIDE A TRAFFIC CIRCULATION ANALYSIS AT THE
 FOLLOWING INTERSECTIONS:
 A. QUADRILLE BOULEVARD/CLEMATIS STREET
 B. QUADRILLE BOULEVARD/DATURA STREET
 C. QUADRILLE BOULEVARD/FERN STREET
 D. DIXIE HIGHWAY/CLEMATIS STREET
 E. DIXIE HIGHWAY/DATURA STREET
 12. COMMITTED TRIPS FROM APPROVED DEVELOPMENTS SHOULD
 BE INCLUDED IN THE ANALYSIS.
  
  
 CONDITION:
 1. THE DEVELOPER SHALL BE REQUIRED TO COORDINATE WITH
 CITY PARKING ADMINISTRATOR FOR PRIVATE COMMERCIAL USE
 OF CURBSIDE PARKING SPACE PER CITY CODE 94-111(L).
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 09-09-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-09-09 15:15:49SITE PLAN COMMENTS:
 1. THE ON-STREET VALET DROP OFF/PICK UP AREA IS LOCATED
 WITHIN THE PUBLIC ROW AND WOULD BE CONSIDERED AS PUBLIC
 PARKING SPACES UNLESS ARRANGEMENT IS MADE WITH CITY
 PARKING ADMINISTRATOR FOR EXCLUSIVE PRIVATE COMMERCIAL
 USE PER CITY CODE 94-111(L).
 2. INCLUDE THE REQUIRED AND PROPOSED NUMBER OF BICYCLE
 PARKING SPACES IN THE SITE DATA TABLE. BICYCLE
 FACILITIES AND STORAGE SHOULD BE PROVIDED PER CITY CODE
 94-111(I) AND 94-113(D)(9). THE REQUIRED PUBLIC BICYCLE
 PARKING SPACES SHOULD BE DISTRIBUTED RELATIVELY EVENLY
 ALONG THE SITE FRONTAGE.
 3. PROVIDE AUTOTURN PATH TO SHOW THE PROVIDED
 TURNAROUND AND BACK UP SPACE ON THE GARAGE LEVEL 3 IS
 SUFFICIENT FOR A 3-POINT TURN.
 4. IN SHEET C-11, THE STOP BAR AT THE ALLEY SHOULD BE
 LOCATED AT LEAST 4 FEET IN ADVANCE OF THE
 SIDEWALK/CROSSWALK.
 5. CLARIFY THE SIGNAGE USED IN THE CIRCULAR LANDSCAPED
 AREA BY THE GARAGE ENTRANCE.
 6. THE PARALLEL PARKING SPACES ON DATURA STREET SHOULD
 BE AT LEAST 20 FEET AWAY FROM THE CROSSWALK PER MUTCD
 AND FLORIDA STATUTES.
 7. CITY CODE 94-305(D) REQUIRES A 100-FOOT SETBACK FROM
 CENTERLINE ON QUADRILLE BOULEVARD.
 8. CONSIDER REDUCING THE LANDSCAPE AREA ON THE BUILDING
 SIDE TO PROVIDE 12-FOOT SIDEWALK ALONG QUADRILLE BLVD.
 9. SINCE THE DEVELOPMENT REQUESTS PARKING WAIVER PER
 CITY CODE 94-481(F), RESTRICTIVE COVENANT THAT
 RESTRICTS THE USE OF THE PROPERTY TO SERVING PERSONS
 WHO ARE 55 YEARS OR OLDER OR PERSONS WHO ARE DISABLED
 SHALL BE EXECUTED AND RECORDED PER CITY CODE
 94-481(F)(3).
  
 TRAFFIC STATEMENT COMMENTS:
 10. PROVIDE THE COUNTY TPS LETTER
 11. PROVIDE TRIP DISTRIBUTION WITHIN THE RADIUS OF
 INFLUENCE PER PALM BEACH COUNTY TPS.
 12. PROVIDE A TRAFFIC CIRCULATION ANALYSIS AT THE
 FOLLOWING INTERSECTIONS:
 A. QUADRILLE BOULEVARD/CLEMATIS STREET
 B. QUADRILLE BOULEVARD/DATURA STREET
 C. QUADRILLE BOULEVARD/FERN STREET
 D. DIXIE HIGHWAY/CLEMATIS STREET
 E. DIXIE HIGHWAY/DATURA STREET
 F. DIXIE HIGHWAY/FERN STREET
 13. COMMITTED TRIPS FROM APPROVED DEVELOPMENTS SHOULD
 BE INCLUDED IN THE ANALYSIS.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 06-11-2019 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2019-06-11 18:06:141. FOR A 2-WAY ACCESS ALLEY, THE WIDTH SHOULD BE 20
 FEET MINIMUM
 2. PROVIDE GARBAGE CIRCULATION
 3. PROVIDE BICYCLE PARKING SPACES PER CITY CODE
 4. PROVIDE 12 FOOT SIDEWALK ALONG QUADRILLE BLVD.
 5. PROVIDE A TRAFFIC STUDY
 6. PROVIDE THE COUNTY TPS LETTER
 7. ONE OF THE REQUIREMENTS FOR THE APPLICATION IS TO
 MEET WITH THE TRANSPORTATION ENGINEERING DEPARTMENT
 BEFORE THE SITE PLAN SUBMITTAL. PLEASE SCHEDULE A
 MEETING WITH THE TEAM.
 8. THERE IS A REQUIREMENT OF 100 PARKING SPACES THAT IS
 MISSING ON THE SITE PLAN.
 9. PROVIDE AUTO TURN PATH FOR PASSENGER CARS AND
 GARBAGE TRUCKS FOR WEST ACCESS TO THE GARAGE.
 10. VALET DROP OFF/PICK UP ON STREET NEED TO BE PAID TO
 THE CITY. CITY CODE 94-111 (L)
 11. PROVIDE A QUEUING ANALYSIS FOR THE VALET DROP
 OFF/PICK UP
 12. PROVIDE TURN AROUND AND BACK UP SPACE ON THE GARAGE
 LEVEL 4
  
  
 LINA M. CAMACHO
 SENIOR PROJECT ENGINEER
 561-494-1129
 [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 02-27-2020 Cont ID  
Sent By elevesqu Date 02-27-2020 Time 11:08 Rev Time 0.00
Received By elevesqu Date 02-27-2020 Time 11:08 Sent To  
Notes
2020-02-27 11:08:57COMMENTS SHALL BE LABELED ?SATISFIED?, ?NOT SATISFIED?,
 ?PARTIALLY SATISFIED?, OR ?ONGOING?
 ANY NEW COMMENTS OR FURTHER EXPLANATION OF OLD COMMENTS
 SHALL BE BOLDED.
  
 1. SATISFIED.
 2. SATISFIED.
 3. SATISFIED.
 4. CONDITION OF APPROVAL. PER SECTION 94-54(A)(3),
 FORMAL SITE PLAN APPROVALS INVOLVING THE TDR PROGRAM
 SHALL BE APPROVED BY DAC AND THE CERTIFICATE OF
 TRANSFER SHALL BE OBTAINED PRIOR TO THE EXPIRATION OF
 THE SITE PLAN APPROVAL.
 CERTIFICATE OF APPROVAL SHALL BE OBTAINED PRIOR TO
 EXPIRATION OF SITE PLAN APPROVAL.
 5. SATISFIED.
 6. SATISFIED.
 7. SATISFIED.
 8. SATISFIED.
 9. CONIDITION OF APPROVAL. IF VALET IS PROPOSING
 UTILIZING EXISTING OR PROPOSED ON-STREET PARKING FOR
 VALET, THE APPLICANT SHALL PAY FOR THE USE OF THOSE
 OCCUPIED SPACES IN AMOUNT AS ESTABLISHED BY THE CITY
 AND IN LOCATIONS APPROVED BY THE CITY PARKING
 ADMINISTRATOR. THIS WOULD UTILIZE EXISTING ON-STREET
 PARKING SPACES AND NOT INTERFERE WITH SIDEWALK
 CONNECTIVITY.
 APPLICANT TO WORK WITH PARKING ADMINISTRATION ON
 PARKING SPACES.
 10. SATISFIED.
 11. SATISFIED.
 12. SATISFIED.
 13. CONDITION OF APPROVAL. PALM TRAN HAS PERMITTED THE
 USE OF THE BROADSTONE BUS SHELTER, BUT IT WILL NEED A
 BACK INSTALLED. THE APPLICANT SHALL PROVIDE SOME
 ARCHITECTURAL RENDERINGS OF PROPOSED BACKING TO BE
 REVIEWED BY CITY STAFF, OR THE APPLICANT SHALL PAY IN
 LIEU. THE NEW BUS SHELTER WILL NEED TO BE IN OPERATION
 PRIOR TO CLOSING THE QUADRILLE SIDEWALK FOR ANY
 CONSTRUCTION.
 14. SATISFIED.
 15. SATISFIED.
 16. SATISFIED.
 17. SATISFIED.
 18. SATISFIED.
 19. CONDITION OF APPROVAL. IN ORDER TO COUNT TANDEM
 PARKING SPACES AS TWO SPACES, A RESTRICTIVE COVENANT
 SHALL BE REQUIRED FOR CONFIRMATION OF A VALET ATTENDANT
 IN CHARGE OF THE OPERATION OF THE PARKING FACILITY
 DURING ALL OPERATING HOURS.
 APPLICANT SHALL CONTINUE TO WORK WITH CITY LEGAL
 DEPARTMENT ON RESTRICTIVE COVENANT FOR VALET PARKING.
 THIS SHALL BE A CONDITION OF APPROVAL FOR SITE PLAN.
 20. SATISFIED.
 21. SATISFIED.
 22. SATISFIED.
 23. SATISFIED.
 24. SATISFIED.
 25. SATISFIED.
 26. SATISFIED.
 27. SATISFIED.
 28. SATISFIED.
 29. CONDITION OF APPROVAL. PLEASE PRESERVE THE EXISTING
 CEMENT CANOPY ON SITE, PER CITY HISTORIC PRESERVATION
 PLANNER. THIS COULD BE MAINTAINED WITHIN THE OPEN
 SPACE.
 CONVERSATION ONGOING WITH HISTORIC PRESERVATION
 DIVISION.
 30. SATISFIED.
 31. SATISFIED.
 32. SATISFIED.
 33. SATISFIED.
 34. SATISFIED.
 35. SATISFIED.
 36. SATISFIED.
 37. SATISFIED.
 38. SATISFIED.
 39. SATISFIED.
 40. SATISFIED.
 41. SATISFIED.
 42. SATISFIED.
 43. SATISFIED.
 44. SATISFIED.
 45. SATISFIED.
 46. CONDITION OF APPROVAL. PLEASE INDICATE LOCATION OF
 PROPOSED UTILITIES INCLUDING THE BACKFLOW PREVENTER,
 FDC CONNECTION, FPL TRANSFORMER, ETC. STAFF RECOMMENDS
 LOCATING THE UTILITIES WITHIN THE BUILDING FOOTPRINT
 AND PROVIDING ACCESS TO UTILITY COMPANIES, TO KEEP OFF
 THE PUBLIC ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED
 ALONG THE ALLEY SIDE OF THE BUILDING. SUFFICIENT
 LANDSCAPE SCREENING IS REQUIRED WHEN UTILITIES ARE
 LOCATED OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A
 MINIMUM OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED
 AT ALL LOCATIONS.
 PLACEMENT OF UTILITIES SHALL BE ONGOING THROUGH
 PLANNING AND PERMIT PROCESS, SUBJECT TO REVIEW BY
 ZONING, LANDSCAPE PLANNER, AND BUILDING DEPARTMENTS.
 47. SATISFIED.
 48. CONDITION OF APPROVAL. THE MINIMUM FOOTCANDLE, AS
 MEASURED AT THE BACK EDGE OF THE CURB AND ONE FOOT
 ABOVE THE SIDEWALK IS 0.6 AND THE MAXIMUM IS 1.0
 FOOTCANDLE. PLEASE ADJUST PHOTOMETRICS EXTENDING TO THE
 ROADWAY CENTERLINES AND PROVIDE DETAILS OF THE PROPOSED
 LIGHT FIXTURES AS NECESSARY. PLEASE COORDINATE WITH THE
 ENGINEERING DEPARTMENT TO USE THE CITY APPROVED LIGHT
 FIXTURE. A SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 RELOCATE THE PROPOSED LIGHT POLE THAT IS IN THE CENTER
 OF THE SIDEWALK AT THE CORNER OF DATURA AND DIXIE.
 49. SATISFIED.
 50. SATISFIED.
 51. CONDITION OF APPROVAL. APPLICANT SHALL BE REQUIRED
 TO MEET REQUIREMENTS OF ART IN PUBLIC PLACES. CONTACT
 SYBILLE WELTER AT [email protected] FOR MORE
 INFORMATION.
 52. SATISFIED.
  
  
 NEW COMMENTS SEPTEMBER 9, 2019:
 53. SATISFIED.
 54. SATISFIED
 55. SATISFIED
 56. SATISFIED
 57. SATISFIED
 58. SATISFIED
 59. SATISFIED.
 60. SATISFIED
 61. SATISFIED
 62. SATISFIED
 63. SATISFIED
 64. SATISFIED
 65. SATISFIED.
 66. SATISFIED
 67. SATISFIED
 68. SATISFIED.
 69. SATISFIED
 70. SATISFIED
 71. SATISFIED
 72. SATISFIED
 73. SATISFIED
 74. SATISFIED
 75. SATISFIED
 76. SATISFIED.
 NEW COMMENTS NOVEMBER 5, 2019
 77. SATISFIED.
 78. SATISFIED.
 79. SATISFIED.
 80. SATISFIED
 81. SATISFIED.
 82. SATISFIED.
 83. CONDITION OF APPROVAL: TRUNCATED DOME TO BE
 ADJUSTED ? SEE CONDITION OF APPROVAL
  
  
 84. SATISFIED.
 85. SATISFIED.
 86. SATISFIED.
 87. SATISFIED.
 88. SATISFIED.
 89. SATISFIED.
 90. SATISFIED. THERE IS AN AREA ADJACENT TO THE
 INTERIOR BICYCLE RACKS THAT IS SHOWN DIFFERENTLY ON THE
 SITE PLAN COMPARED TO CIVIL PLANS. PLEASE CLARIFY
 91. SATISFIED.
 92. CONDITION OF APPROVAL. PLEASE ADDRESS THE EXITING
 TRAFFIC POLE BOXES AT PROPERTY?S SOUTHEAST CORNER.
 PLEASE INCORPORATE INTO LANDSCAPE BED.
 MAY NEED TO BE RELOCATED IF ALTERNATIVE SOLUTION CANNOT
 BE FOUND AND AGREED UPON BY STAFF.
  
 93. CONDITION OF APPROVAL.: PLEASE INDICATE PROPOSED
 LOCATION OF BACKFLOW PREVENTER. PLEASE PLAN TO LOCATE
 WITHIN LANDSCAPE BED.
 APPLICANT SHALL MAKE SURE THAT UTILITY IS SCREENED WHEN
 INSTALLED
  
 94. CONDITION OF APPROVAL: PLEASE ENSURE THAT GROUND
 MOUNTED FDC IS WITHIN A LANDSCAPE BED OR ALTERNATIVELY,
 MOUNT ON WALL.
 12/18/19: ALL FDC SHALL BE SCREENED BY LANDSCAPE AND/OR
 PAINTED TO MATCH BUILDING FA?ADE.
 95. SATISFIED.
 96. SATISFIED
 97. SATISFIED
 98. SATISFIED
 99. SATISFIED
 100. SATISFIED
 101. SATISFIED
 102. SATISFIED
 103. SATISFIED
 104. CONDITION OF APPROVAL:
 THERE CAN BE MODIFICATIONS TO THE DESIGN OF THE FIVE
 PARKING SPACES OFF THE ALLEY TO ACCOMMODATE THE
 CONCRETE COLUMNS FOR THE CONCRETE CANOPY (FOR EXAMPLE,
 A 3? WIDE LANDSCAPE ISLAND WITH THE CONCRETE COLUMN
 BASE).
 105. CONDITION OF APPROVAL:
 ALL ROOFTOP EQUIPMENT SHALL BE SCREENED TO THE HEIGHT
 OF THE EQUIPMENT.
 106. SATISFIED
 107. SATISFIED
 108. CONDITION OF APPROVAL: PLEASE INCLUDE PROPOSED
 BICYCLE RACK WITH THE REFERENCE TO THE BUS SHELTER, AS
 REQUIRED BY PALM TRAN.
 109. CONDITION OF APPROVAL: PLEASE SHIFT THE LIGHT POLE
 FROM THE CENTER OF THE PROPOSED PLAZA AT THE
 DATURA/DIXIE CORNER TO ALIGN WITH THE LIGHT POLES
 PROPOSED ALONG DATURA STREET. PLEASE SHIFT THE PROPOSED
 SOUTHERNMOST POLE ALONG QUADRILLE BOULEVARD FROM WITHIN
 THE PEDESTRIAN CONNECTION TO THE CROSSWALK.
 110. CONDITION OF APPROVAL: PLEASE COORDINATE WITH
 LANDSCAPE PLANNER AND STORMWATER ON LOCATION OF
 EXFILTRATION TRENCH PIPES.
  

Review Stop Z ZONING
Rev No 4 Status F Date 12-20-2019 Cont ID  
Sent By elevesqu Date 12-20-2019 Time 11:23 Rev Time 0.00
Received By elevesqu Date 12-20-2019 Time 11:23 Sent To  
Notes
2019-12-20 11:23:46COMMENTS SHALL BE LABELED ?SATISFIED?, ?NOT SATISFIED?,
 ?PARTIALLY SATISFIED?, OR ?ONGOING?
 ANY NEW COMMENTS OR FURTHER EXPLANATION OF OLD COMMENTS
 SHALL BE BOLDED.
  
 1. SATISFIED.
 2. SATISFIED.
 3. SATISFIED.
 4. ONGOING. PER SECTION 94-54(A)(3), FORMAL SITE PLAN
 APPROVALS INVOLVING THE TDR PROGRAM SHALL BE APPROVED
 BY DAC AND THE CERTIFICATE OF TRANSFER SHALL BE
 OBTAINED PRIOR TO THE EXPIRATION OF THE SITE PLAN
 APPROVAL.
 CERTIFICATE OF APPROVAL SHALL BE OBTAINED PRIOR TO
 EXPIRATION OF SITE PLAN APPROVAL.
 5. SATISFIED.
 6. SATISFIED.
 7. SATISFIED.
 8. SATISFIED.
 9. ONGOING. IF VALET IS PROPOSING UTILIZING EXISTING OR
 PROPOSED ON-STREET PARKING FOR VALET, THE APPLICANT
 SHALL PAY FOR THE USE OF THOSE OCCUPIED SPACES IN
 AMOUNT AS ESTABLISHED BY THE CITY AND IN LOCATIONS
 APPROVED BY THE CITY PARKING ADMINISTRATOR. THIS WOULD
 UTILIZE EXISTING ON-STREET PARKING SPACES AND NOT
 INTERFERE WITH SIDEWALK CONNECTIVITY.
 APPLICANT TO WORK WITH PARKING ADMINISTRATION ON
 PARKING SPACES. WILL NOT HOLD UP PROJECT SITE PLAN
 REVIEW (WILL BE CONDITION OF APPROVAL)
 10. SATISFIED.
 11. SATISFIED.
 12. SATISFIED.
 13. ONGOING. PALM TRAN HAS PERMITTED THE USE OF THE
 BROADSTONE BUS SHELTER, BUT IT WILL NEED A BACK
 INSTALLED. THE APPLICANT SHALL PROVIDE SOME
 ARCHITECTURAL RENDERINGS OF PROPOSED BACKING TO BE
 REVIEWED BY CITY STAFF, OR THE APPLICANT SHALL PAY IN
 LIEU. CAN BE A CONDITION OF APPROVAL FOR SITE PLAN. THE
 NEW BUS SHELTER WILL NEED TO BE IN OPERATION PRIOR TO
 CLOSING THE QUADRILLE SIDEWALK FOR ANY CONSTRUCTION.
 14. SATISFIED.
 15. SATISFIED.
 16. SATISFIED.
 17. SATISFIED.
 18. SATISFIED.
 19. ONGOING. IN ORDER TO COUNT TANDEM PARKING SPACES AS
 TWO SPACES, A RESTRICTIVE COVENANT SHALL BE REQUIRED
 FOR CONFIRMATION OF A VALET ATTENDANT IN CHARGE OF THE
 OPERATION OF THE PARKING FACILITY DURING ALL OPERATING
 HOURS.
 APPLICANT SHALL CONTINUE TO WORK WITH CITY LEGAL
 DEPARTMENT ON RESTRICTIVE COVENANT FOR VALET PARKING.
 THIS SHALL BE A CONDITION OF APPROVAL FOR SITE PLAN.
 20. SATISFIED.
 21. SATISFIED.
 22. SATISFIED.
 23. SATISFIED. PLEASE PROVIDE DATA ON BUILDING
 FOOTPRINT MAXIMUM IN SITE TABLE PER TABLE IV-50
 24. SATISFIED.
 25. SATISFIED.
 26. SATISFIED.
 27. SATISFIED.
 28. SATISFIED.
 29. ONGOING. PLEASE PRESERVE THE EXISTING CEMENT CANOPY
 ON SITE, PER CITY HISTORIC PRESERVATION PLANNER. THIS
 COULD BE MAINTAINED WITHIN THE OPEN SPACE.
 CONVERSATION ONGOING WITH HISTORIC PRESERVATION
 DIVISION. SHALL BE A CONDITION OF APPROVAL.
  
 12/18/19: SEE NEW COMMENT # 104
 30. SATISFIED.
 31. SATISFIED.
 32. SATISFIED.
 33. PARTIALLY SATISFIED. PLEASE PROVIDE ADDITIONAL
 DETAIL OF ARCHITECTURAL TREATMENT MATERIALS ON BUILDING
 ON ELEVATION PLANS.
 PLEASE PROVIDE ADDITIONAL DETAIL OF THE ALUMINUM FRAME
 ON THE PARKING GARAGE ? IS IT FULLY OPEN? ANY
 ADDITIONAL SCREENING BEHIND THE FRAME? EXAMPLE WOULD BE
 BENEFICIAL. PLEASE PROVIDE AN EXAMPLE OF THE BRICK
 ACCENT, FIXED DECORATIVE SHUTTERS, DECORATIVE BRACKETS,
 ETC.
  
 12/18/19: SEE NEW COMMENT # 102
 34. SATISFIED.
 35. SATISFIED.
 36. SATISFIED.
 37. SATISFIED.
 38. NOT SATISFIED. PLEASE PROVIDE A HARDSCAPE PLAN WITH
 DETAILS OF PAVERS, SEATING, ETC.
 SOME HARDSCAPE DETAILS ARE NEEDED FOR DAC REVIEW OF
 PAVERS, SEATING, LANDSCAPE BED AREAS (ALONG DATURA
 STREET APPEARS TO HAVE BENCHES AROUND LANDSCAPE AREA),
 ETC. PLEASE PROVIDE WHAT YOU CAN; STAFF AND THE DAC
 MEMBERS REALIZE THESE MAY CHANGE WITH PERMITTING AND
 CONSTRUCTION.
  
 12/18/19: SEE NEW COMMENT #99
  
 39. SATISFIED. PLEASE SEE TABLE IV-7 FOR OPEN SPACE
 STANDARDS. CURRENTLY THE PASSAGEWAY PUBLIC OPEN TYPE IS
 REQUIRED. STAFF IS CURRENTLY REVIEWING THIS REQUIREMENT
 FOR APPLICABILITY FOR THIS SITE.
 CODE AMENDMENT UNDERWAY THAT WILL PERMIT UPGRADING
 PRIVATE OPEN SPACE TO PUBLIC OPEN SPACE IN SOME CASES
 WITHIN THE DMP.
  
 40. SATISFIED. PLEASE ADDRESS SPECIFIC PRIVATE AND
 PUBLIC OPEN SPACE REQUIREMENTS PER TABLE IV-6 AND TABLE
 IV-7, INCLUDING TYPE OF OPEN SPACE (COURTYARD GARDEN,
 TERRACE, ETC.) FOR EACH OPEN SPACE AND SEE THE
 REQUIREMENTS FOR VEGETATED SPACE, SEATING, ETC.
 CODE AMENDMENT UNDERWAY THAT WILL PERMIT UPGRADING
 PRIVATE OPEN SPACE TO PUBLIC OPEN SPACE IN SOME CASES
 WITHIN THE DMP. SATISFIED.
 41. SATISFIED.
 42. SATISFIED.
 43. SATISFIED.
 44. PARTIALLY SATISFIED. PER SECTION 93-113, BICYCLE
 PARKING FOR THE PUBLIC SHALL BE PROVIDED AT A MINIMUM
 OF ONE SPACE PER EVERY 100 FEET OF STREET FRONTAGE. THE
 POST AND LOOP RACK IS RECOMMENDED FOR THE PUBLIC ROW.
 PLEASE INDICATE EXACT BICYCLE RACK DETAIL ON PLANS.
 THE SITE PLAN SHEET SP-1 SHOWS A DIFFERENT TYPE OF
 BICYCLE RACK, PLEASE AMEND.
 45. SATISFIED.
 46. ONGOING. PLEASE INDICATE LOCATION OF PROPOSED
 UTILITIES INCLUDING THE BACKFLOW PREVENTER, FDC
 CONNECTION, FPL TRANSFORMER, ETC. STAFF RECOMMENDS
 LOCATING THE UTILITIES WITHIN THE BUILDING FOOTPRINT
 AND PROVIDING ACCESS TO UTILITY COMPANIES, TO KEEP OFF
 THE PUBLIC ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED
 ALONG THE ALLEY SIDE OF THE BUILDING. SUFFICIENT
 LANDSCAPE SCREENING IS REQUIRED WHEN UTILITIES ARE
 LOCATED OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A
 MINIMUM OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED
 AT ALL LOCATIONS.
 SEE COMMENT 94. PLACEMENT OF UTILITIES SHALL BE ONGOING
 THROUGH PLANNING AND PERMIT PROCESS, SUBJECT TO REVIEW
 BY ZONING, LANDSCAPE PLANNER, AND BUILDING DEPARTMENTS.
 THIS SHALL BE A SITE PLAN CONDITION OF APPROVAL.
 47. SATISFIED.
 48. NOT SATISFIED. THE MINIMUM FOOTCANDLE, AS MEASURED
 AT THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK IS 0.6 AND THE MAXIMUM IS 1.0 FOOTCANDLE.
 PLEASE ADJUST PHOTOMETRICS EXTENDING TO THE ROADWAY
 CENTERLINES AND PROVIDE DETAILS OF THE PROPOSED LIGHT
 FIXTURES AS NECESSARY. PLEASE COORDINATE WITH THE
 ENGINEERING DEPARTMENT TO USE THE CITY APPROVED LIGHT
 FIXTURE. A SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 THE PHOTOMETRIC PLAN DOES NOT MATCH THE SITE PLAN OR
 LANDSCAPE PLAN. THERE IS A LIGHT POLE PROPOSED WHERE A
 TREE IS PROPOSED ON THE CORNER OF DATURA AND QUADRILLE
 ON THE DATURA SIDE. PLEASE RELOCATE THE PROPOSED LIGHT
 POLE THAT IS IN THE CENTER OF THE SIDEWALK AT THE
 CORNER OF DATURA AND DIXIE. THE PLAN SHOWS A LIGHT POLE
 PROPOSED IN THE ON STREET PARKING ALONG DIXIE HIGHWAY.
  
 12/18/19: SEE NEW COMMENT # 109
  
 49. SATISFIED.
 50. SATISFIED.
 51. ONGOING. APPLICANT SHALL BE REQUIRED TO MEET
 REQUIREMENTS OF ART IN PUBLIC PLACES. CONTACT SYBILLE
 WELTER AT [email protected] FOR MORE INFORMATION.
 12/18/19: STAFF RECOMMENDS CONTACTING AIPP COORDINATOR
 AS SOON AS POSSIBLE TO GET PROCESS MOVING. AIPP WILL
 HOLD UP C.O. IF REQUIREMENT NOT COMPLETED.
 52. SATISFIED.
  
  
 NEW COMMENTS SEPTEMBER 9, 2019:
 53. SATISFIED.
 54. SATISFIED
 55. SATISFIED
 56. SATISFIED
 57. SATISFIED
 58. SATISFIED
 59. SATISFIED.
 60. SATISFIED
 61. SATISFIED
 62. SATISFIED
 63. SATISFIED
 64. SATISFIED
 65. PARTIALLY SATISFIED. PLEASE UPDATE THE ELEVATIONS
 TO INCLUDE LANDSCAPE PLANS. PLEASE INCLUDE ADDITIONAL
 ARCHITECTURAL MATERIAL LABELS INCLUDING GLASS, FAUX
 GLASS, STUCCO, ETC.
 PLEASE INCLUDE ADDITIONAL INFORMATION
  
 12/18/19: SEE NEW COMMENT # 102
 66. SATISFIED
 67. SATISFIED
 68. SATISFIED.
 69. SATISFIED
 70. SATISFIED
 71. SATISFIED
 72. SATISFIED
 73. SATISFIED
 74. SATISFIED
 75. SATISFIED
 76. SATISFIED.
 NEW COMMENTS NOVEMBER 5, 2019
 77. SATISFIED.
 78. SATISFIED.
 79. SATISFIED.
 80. NOT SATISFIED: PLEASE CONSIDER THE ADDITION OF
 ARCHITECTURAL TREATMENT ON THE STAIRWAYS TO ALLEVIATE
 THE ACTIVE USE LINER VARIANCE.
 12/18/19: SIGNAGE CANNOT COUNT TOWARDS ARCHITECTURAL
 TREATMENT. PER DAC CONDITION, PLEASE INCLUDE ADDITIONAL
 ARCHITECTURAL TREATMENT AS APPROPRIATE FOR THE FA?ADE
 TO BREAK UP THE BLANK WALL.
 81. SATISFIED.
 82. SATISFIED.
 83. NOT SATISFIED: TRUNCATED DOME FOR ADA COMPLIANCE IS
 NOT APPARENT ON ANY PLANS. PLEASE CLARIFY INTERSECTION
 CROSSWALK CONNECTIVITY
  
 12/18/19: TRUNCATED DOMES ARE NOT ILLUSTRATED ON PLANS.
 PLEASE INCLUDE.
  
 84. SATISFIED.
 85. ONGOING. PLEASE ADJUST THE DROP OFF AREA ON DATURA
 STREET TO THE SIZE OF A PARALLEL PARKING SPACE (22
 FEET) TO ACCOMMODATE THE REQUIRED SHADE TREE PER EVERY
 30 FEET
 SEE NEW COMMENT # 98
  
 86. NOT SATISFIED. PLEASE ADD A SHADE TREE TO THE SOUTH
 SIDE OF DIXIE HIGHWAY NEAR THE DIXIE AND DATURA
 INTERSECTION (REMOVE HOLLY TREES PER LANDSCAPE COMMENTS
 AND REPLACE WITH OAK TREES)
 12/18/19: COMMENT NOT ADDRESSED.
  
 87. PARTIALLY SATISFIED. PLEASE REMOVE THE LOW WALL
 FROM THE BISTRO OUTDOOR AREA AS THIS AREA IS BEING
 CONSIDERED PUBLIC OPEN SPACE (IN TIME FOR DAC SUBMITTAL
 ? ON PLANS SUBMITTED NO LATER THAN 11/27)
 12/18/19: WALL REMOVED, BUT STAFF HAS QUESTION ABOUT
 PLANTER BED. SEE NEW COMMENT # 100
  
 88. SATISFIED.
 89. SATISFIED.
 90. PARTIALLY SATISFIED. THERE IS AN AREA ADJACENT TO
 THE INTERIOR BICYCLE RACKS THAT IS SHOWN DIFFERENTLY ON
 THE SITE PLAN COMPARED TO CIVIL PLANS. PLEASE CLARIFY
 12/18/19: BICYCLE RACK LOCATION STILL SHOWN IN OLD
 LOCATION ON SHEET SP-1.
  
 91. SATISFIED.
 92. ONGOING. PLEASE ADDRESS THE EXITING TRAFFIC POLE
 BOXES AT PROPERTY?S SOUTHEAST CORNER. PLEASE
 INCORPORATE INTO LANDSCAPE BED.
  
 12/18/19: PLEASE ADDRESS PER DAC CONDITION OF APPROVAL.
 PLEASE LOOK AT ALL EXISTING BOXES AND PROVIDE DESIGNS
 TO INCORPORATE INTO A LANDSCAPE BED. THE PEDESTRIAN
 PATH OF TRAVEL CANNOT BE IMPEDED OR REDIRECTED AROUND
 BOXES. MAY NEED TO BE RELOCATED IF ALTERNATIVE SOLUTION
 CANNOT BE FOUND AND AGREED UPON BY STAFF.
  
 93. C.O.A.: PLEASE INDICATE PROPOSED LOCATION OF
 BACKFLOW PREVENTER. PLEASE PLAN TO LOCATE WITHIN
 LANDSCAPE BED.
 12/18/19: APPLICANT SHALL MAKE SURE THAT UTILITY IS
 SCREENED WHEN INSTALLED
  
 94. C.O.A.: PLEASE ENSURE THAT GROUND MOUNTED FDC IS
 WITHIN A LANDSCAPE BED OR ALTERNATIVELY, MOUNT ON WALL.
 12/18/19: ALL FDC SHALL BE SCREENED BY LANDSCAPE AND/OR
 PAINTED TO MATCH BUILDING FA?ADE.
  
 95. ONGOING. PLEASE PROVIDE GROUND LEVEL 3D RENDERINGS
 FOR DAC APPLICATION (NO LATER THAN 11/27) ? INCLUDE
 LANDSCAPE AT PLANTING LEVEL. PLEASE INCLUDE DAY TIME
 RENDERING.
 ADDITIONAL RENDERINGS NEEDED: FOR EXAMPLE FOR DATURA
 STREET, QUADRILLE/ALLEY CORNER, FULL HEIGHT FROM GROUND
 OF DIXIE/ALLEY CORNER
  
 96. ONGOING: PLEASE NOTE, NEXT SITE PLAN RESUBMITTAL
 WILL HAVE A REQUIRED RESUBMITTAL FEE OF $300
 (RESUBMITTAL FEE, CHARGED AFTER 1ST RESUBMITTAL)
 12/18/19: RESUBMITTAL FEE OF $300 REQUIRED FOR NEXT
 RESUBMITTAL
  
 NEW COMMENTS DEC. 18, 2019
 97. PLEASE PROVIDE EXAMPLE OF RAISED DECORATIVE PANEL.
 PAINTED THE SAME COLOR, WITH A DEPTH OF ONLY 2? AT THE
 8TH FLOOR, WOULD THIS FEATURE BE NOTICEABLE? PERHAPS AN
 ALTERNATIVE FEATURE SHOULD BE USED IF THIS WON?T BE
 APPARENT AT THE GROUND LEVEL.
 98. STAFF RECOMMENDS A COMPROMISE TO THE PROPOSED
 CANOPY, TO PROVIDE SHADE TREES EVERY 35? TO ACCOMMODATE
 DAC RECOMMENDATION WITH REQUIREMENT FOR SHADE TREES.
 99. PLEASE PROVIDE DETAIL ON THE BANDED FEATURE WITHIN
 THE PLAZA AT THE PROJECT?S SOUTHEAST CORNER. ARE THESE
 STEPS?
 100. IS THERE A PLANTER BED PROPOSED AROUND THE BISTRO
 AREA? PLEASE PROVIDE THE PROPOSED HEIGHT OF PLANTING
 SURROUNDING THE AREA. THE PATIO AREA CANNOT BE TREATED
 AS A PRIVATE OPEN SPACE AREA AS IT IS INCLUDED IN THE
 PUBLIC OPEN SPACE CALCULATIONS. THE COVER SHEET
 ELEVATION STILL SHOWS A LOW WALL, PLEASE AMEND.
 101. SIGNAGE CANNOT BE CONSIDERED ARCHITECTURAL
 TREATMENT. ADDITIONALLY, PLEASE CHECK REQUIREMENT FOR
 VERTICAL SIGNS IN SECTION 94-110. SIGN BANDS CANNOT BE
 UTILIZED IF A VERTICAL SIGN IS USED.
 102. PLEASE PROVIDE ADDITIONAL MATERIAL (IMAGES AND
 EXAMPLES) OF THE BRICK ACCENT, GARAGE SCREENING, FIXED
 DECORATIVE SHUTTER,
 103. LANDSCAPE IS ILLUSTRATED ON THE PROPOSED RENDERING
 AT QUADRILLE/DATURA STREET ABOVE THE 3RD STORY. THE
 FLOOR PLANS SHOW THIS AREA TO BE UNPLANTED, BUT STAFF
 RECOMMENDS KEEPING THIS LANDSCAPE AREA TO ENHANCE THAT
 CORNER, ESPECIALLY IN LIEU OF ACTIVE USE LINER.
 104. THERE CAN BE MODIFICATIONS TO THE DESIGN OF THE
 FIVE PARKING SPACES OFF THE ALLEY TO ACCOMMODATE THE
 CONCRETE COLUMNS FOR THE CONCRETE CANOPY (FOR EXAMPLE,
 A 3? WIDE LANDSCAPE ISLAND WITH THE CONCRETE COLUMN
 BASE).
 105. PLEASE INCLUDE A NOTE STATING THAT ALL ROOFTOP
 EQUIPMENT SHALL BE SCREENED TO THE HEIGHT OF THE
 EQUIPMENT AND/OR PAINTED TO MATCH THE BUILDING FA?ADE
 COLOR. PLEASE INCLUDE A NOTE ON THE ELEVATIONS THAT ALL
 WALL-MOUNTED ELECTRICAL EQUIPMENT SHALL BE PAINTED TO
 MATCH THE BUILDING COLOR. THESE TYPES OF ITEMS COULD
 HOLD UP ZONING SIGN OFF AT TIME OF CO.
 106. THERE APPEARS TO BE SOME DISCREPANCY BETWEEN THE
 WIDTH OF PORTIONS OF THE WALL (FOR EXAMPLE, WIDTH
 BETWEEN WALL ALONG DIXIE HIGHWAY TO FIRST WINDOW AND
 THE LINE OF VERTICAL WINDOWS CLOSEST TO THE ALLEY ALONG
 THE DIXIE ELEVATION ) WHEN COMPARING THE ELEVATIONS TO
 THE FLOOR PLAN. PLEASE ENSURE THAT THE PROPOSED
 ELEVATIONS FULLY ALIGN WITH PROPOSED FLOOR PLANS.
 107. ALONG FACADES WHERE THERE ARE VERTICAL ALIGNMENT
 OF WINDOWS, THERE ARE SOME FLOORS WHERE THE WINDOWS ARE
 NOT CONTINUED. PLEASE REORIENTATE THE UNITS TO INCLUDE
 WINDOWS TO CONTINUE THE RHYTHM OF FENESTRATION, OR LOOK
 AT OPTIONS FOR FAUX WINDOWS TO PREVENT GAPS AND BLANK
 STUCCO PORTIONS. (EXAMPLES: DIXIE/DATURA CORNER-
 WINDOWS ON FLOORS 5-8, NOT ON FLOOR 3 AND 4.
 DIXIE/ALLEY (ALLEY SIDE)- WINDOWS ON FLOOR 5-8, NOT ON
 3 AND 4. DIXIE FA?ADE ? NO WINDOWS FLOOR 3 AND 4).
 108. PLEASE INCLUDE PROPOSED BICYCLE RACK WITH THE
 REFERENCE TO THE BUS SHELTER, AS REQUIRED BY PALM TRAN.
 109. PLEASE SHIFT THE LIGHT POLE FROM THE CENTER OF THE
 PROPOSED PLAZA AT THE DATURA/DIXIE CORNER TO ALIGN WITH
 THE LIGHT POLES PROPOSED ALONG DATURA STREET. PLEASE
 SHIFT THE PROPOSED SOUTHERNMOST POLE ALONG QUADRILLE
 BOULEVARD FROM WITHIN THE PEDESTRIAN CONNECTION TO THE
 CROSSWALK.
 110. PLEASE COORDINATE WITH LANDSCAPE PLANNER AND
 STORMWATER ON LOCATION OF EXFILTRATION TRENCH PIPES.
 PREVIOUS LANDSCAPE COMMENT FOR RELOCATING FROM UNDER
 TREES WAS NOT ADDRESSED.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 11-05-2019 Cont ID  
Sent By elevesqu Date 11-05-2019 Time 16:48 Rev Time 0.00
Received By elevesqu Date 11-05-2019 Time 16:46 Sent To  
Notes
2019-11-05 16:48:26ONGOING COMMENTS FROM PREVIOUS REVIEWS:
  
 13. ONGOING. PALM TRAN HAS PERMITTED THE USE OF THE
 BROADSTONE BUS SHELTER, BUT IT WILL NEED A BACK
 INSTALLED. THE APPLICANT SHALL PROVIDE SOME
 ARCHITECTURAL RENDERINGS OF PROPOSED BACKING TO BE
 REVIEWED BY CITY STAFF. CAN BE A CONDITION OF APPROVAL
 FOR SITE PLAN. THE NEW BUS SHELTER WILL NEED TO BE IN
 OPERATION PRIOR TO CLOSING THE QUADRILLE SIDEWALK FOR
 ANY CONSTRUCTION.
  
 19. ONGOING. IN ORDER TO COUNT TANDEM PARKING SPACES AS
 TWO SPACES, A RESTRICTIVE COVENANT SHALL BE REQUIRED
 FOR CONFIRMATION OF A VALET ATTENDANT IN CHARGE OF THE
 OPERATION OF THE PARKING FACILITY DURING ALL OPERATING
 HOURS.
 APPLICANT SHALL CONTINUE TO WORK WITH CITY LEGAL
 DEPARTMENT ON RESTRICTIVE COVENANT FOR VALET PARKING.
 THIS SHALL BE A CONDITION OF APPROVAL FOR SITE PLAN.
  
 29. ONGOING. PLEASE PRESERVE THE EXISTING CEMENT CANOPY
 ON SITE, PER CITY HISTORIC PRESERVATION PLANNER. THIS
 COULD BE MAINTAINED WITHIN THE OPEN SPACE.
 CONVERSATION ONGOING WITH HISTORIC PRESERVATION
 DIVISION. SHALL BE A CONDITION OF APPROVAL.
  
 33. PARTIALLY SATISFIED. PLEASE PROVIDE ADDITIONAL
 DETAIL OF ARCHITECTURAL TREATMENT MATERIALS ON BUILDING
 ON ELEVATION PLANS.
 PLEASE PROVIDE ADDITIONAL DETAIL OF THE ALUMINUM FRAME
 ON THE PARKING GARAGE ? IS IT FULLY OPEN? ANY
 ADDITIONAL SCREENING BEHIND THE FRAME? EXAMPLE WOULD BE
 BENEFICIAL. PLEASE PROVIDE AN EXAMPLE OF THE BRICK
 ACCENT, FIXED DECORATIVE SHUTTERS, DECORATIVE BRACKETS,
 ETC. THIS ARE REQUESTED FOR DAC REVIEW. (NEED IN TIME
 FOR DAC SUBMITTAL ? ON PLANS SUBMITTED NO LATER THAN
 11/27)
  
 36. PARTIALLY SATISFIED. PLEASE CHECK CRITERIA FOR FDOT
 SIGHT TRIANGLE FOR PROPOSED TREES AT STREET CORNERS.
 A TREE AT THE CORNER OF QUADRILLE AND DATURA IS STILL
 WITHIN THE SIGHT TRIANGLE.
  
 38. NOT SATISFIED. PLEASE PROVIDE A HARDSCAPE PLAN WITH
 DETAILS OF PAVERS, SEATING, ETC.
 SOME HARDSCAPE DETAILS ARE NEEDED FOR DAC REVIEW OF
 PAVERS, SEATING, LANDSCAPE BED AREAS (ALONG DATURA
 STREET APPEARS TO HAVE BENCHES AROUND LANDSCAPE AREA),
 ETC. PLEASE PROVIDE WHAT YOU CAN; STAFF AND THE DAC
 MEMBERS REALIZE THESE MAY CHANGE WITH PERMITTING AND
 CONSTRUCTION.
  
 39. SATISFIED. PLEASE SEE TABLE IV-7 FOR OPEN SPACE
 STANDARDS. CURRENTLY THE PASSAGEWAY PUBLIC OPEN TYPE IS
 REQUIRED. STAFF IS CURRENTLY REVIEWING THIS REQUIREMENT
 FOR APPLICABILITY FOR THIS SITE.
 CODE AMENDMENT UNDERWAY THAT WILL PERMIT UPGRADING
 PRIVATE OPEN SPACE TO PUBLIC OPEN SPACE IN SOME CASES
 WITHIN THE DMP.
  
  
 44. NOT SATISFIED. PER SECTION 93-113, BICYCLE PARKING
 FOR THE PUBLIC SHALL BE PROVIDED AT A MINIMUM OF ONE
 SPACE PER EVERY 100 FEET OF STREET FRONTAGE. THE POST
 AND LOOP RACK IS RECOMMENDED FOR THE PUBLIC ROW. PLEASE
 INDICATE EXACT BICYCLE RACK DETAIL ON PLANS.
 STAFF CALCULATES THE REQUIRED PRIVATE BICYCLE PARKING
 TO BE 7 SPACES, WITH APPROXIMATELY 670 FEET OF ROW.
 ADDITIONALLY, THE LOCATION OF THE PUBLIC BICYCLE RACKS
 WITHIN THE PRIVATE OUTDOOR DINING AREA DOES NOT SATISFY
 REQUIREMENTS. PLEASE RELOCATE FOR A PUBLIC USE.
  
 46. ONGOING. PLEASE INDICATE LOCATION OF PROPOSED
 UTILITIES INCLUDING THE BACKFLOW PREVENTER, FDC
 CONNECTION, FPL TRANSFORMER, ETC. STAFF RECOMMENDS
 LOCATING THE UTILITIES WITHIN THE BUILDING FOOTPRINT
 AND PROVIDING ACCESS TO UTILITY COMPANIES, TO KEEP OFF
 THE PUBLIC ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED
 ALONG THE ALLEY SIDE OF THE BUILDING. SUFFICIENT
 LANDSCAPE SCREENING IS REQUIRED WHEN UTILITIES ARE
 LOCATED OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A
 MINIMUM OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED
 AT ALL LOCATIONS.
 SEE NEW COMMENT 94. PLACEMENT OF UTILITIES SHALL BE
 ONGOING THROUGH PLANNING AND PERMIT PROCESS, SUBJECT TO
 REVIEW BY ZONING, LANDSCAPE PLANNER, AND BUILDING
 DEPARTMENTS. THIS SHALL BE A SITE PLAN CONDITION OF
 APPROVAL.
  
 48. NOT SATISFIED. THE MINIMUM FOOTCANDLE, AS MEASURED
 AT THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK IS 0.6 AND THE MAXIMUM IS 1.0 FOOTCANDLE.
 PLEASE ADJUST PHOTOMETRICS EXTENDING TO THE ROADWAY
 CENTERLINES AND PROVIDE DETAILS OF THE PROPOSED LIGHT
 FIXTURES AS NECESSARY. PLEASE COORDINATE WITH THE
 ENGINEERING DEPARTMENT TO USE THE CITY APPROVED LIGHT
 FIXTURE. A SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 THE PHOTOMETRIC PLAN DOES NOT MATCH THE SITE PLAN OR
 LANDSCAPE PLAN. THERE IS A LIGHT POLE PROPOSED WHERE A
 TREE IS PROPOSED ON THE CORNER OF DATURA AND QUADRILLE
 ON THE DATURA SIDE. PLEASE RELOCATE THE PROPOSED LIGHT
 POLE THAT IS IN THE CENTER OF THE SIDEWALK AT THE
 CORNER OF DATURA AND DIXIE. THE PLAN SHOWS A LIGHT POLE
 PROPOSED IN THE ON STREET PARKING ALONG DIXIE HIGHWAY.
  
 65. PARTIALLY SATISFIED. PLEASE UPDATE THE ELEVATIONS
 TO INCLUDE LANDSCAPE PLANS. PLEASE INCLUDE ADDITIONAL
 ARCHITECTURAL MATERIAL LABELS INCLUDING GLASS, FAUX
 GLASS, STUCCO, ETC.
 PLEASE INCLUDE ADDITIONAL INFORMATION ? SEE COMMENT 33
  
 76. PLEASE INCLUDE ADA PARKING SPACES. SEE BUILDING
 COMMENTS.
  
 NEW COMMENTS NOVEMBER 5, 2019
 77. THERE IS A DISCREPANCY BETWEEN THE NUMBER OF BEDS
 FOR GROUP HOMES LISTED IN THE VEHICULAR PARKING AREA
 COMPARED TO THE UNIT PROGRAM DEVELOPMENT SUMMARY BED
 NUMBER. PLEASE UPDATE AS NECESSARY.
 78. AS THE CODE AMENDMENT BEING PROCESSED TO PERMIT
 PRIVATE OPEN SPACE ON THE GROUND FLOOR LEVEL WILL TREAT
 THE OPEN SPACE AS PUBLIC, THE VARIANCE FOR THE SETBACK
 FROM DIXIE HIGHWAY IS NOT REQUIRED. PLEASE REMOVE FROM
 DATA TABLES AND FROM THE JUSTIFICATION STATEMENT (AND
 DAC APPLICATION IF NECESSARY)
 79. PLEASE SHOW THE GROUND FLOOR PLAN ON SITE PLAN
 SHEET SP.1
 80. PLEASE CONSIDER THE ADDITION OF ARCHITECTURAL
 TREATMENT ON THE STAIRWAYS TO ALLEVIATE THE ACTIVE USE
 LINER VARIANCE.
 81. THE NORTHERN PORTION OF FA?ADE ALONG DIXIE HIGHWAY
 THAT IS ADJACENT TO PARKING SPOTS CANNOT BE COUNTED
 TOWARDS ACTIVE USE. HOWEVER, THE PORTION OF THE DINING
 ROOM FA?ADE THAT IS SET FURTHER BACK BUT FRONTS DIXIE
 HIGHWAY CAN BE COUNTED. PLEASE ADJUST.
 82. PLEASE ADD A CONTEXTUAL MASSING ELEVATION FOR
 DATURA STREET FACING NORTH FOR DAC SUBMITTAL (NO LATER
 THAN 11/27)
 83. TRUNCATED DOME FOR ADA COMPLIANCE IS NOT APPARENT
 ON ANY PLANS. PLEASE CLARIFY INTERSECTION CROSSWALK
 CONNECTIVITY
 84. ADA PARKING SPACES ARE REQUIRED EVEN FOR VALET
 OPERATION. PLEASE ADJUST AS NECESSARY. MUST BE DONE
 PRIOR TO DAC (PLANS CHANGED NO LATER THAN 11/27)
 85. PLEASE ADJUST THE DROP OFF AREA ON DATURA STREET TO
 THE SIZE OF A PARALLEL PARKING SPACE (22 FEET) TO
 ACCOMMODATE THE REQUIRED SHADE TREE PER EVERY 30 FEET
 86. PLEASE ADD A SHADE TREE TO THE SOUTH SIDE OF DIXIE
 HIGHWAY NEAR THE DIXIE AND DATURA INTERSECTION (REMOVE
 HOLLY TREES PER LANDSCAPE COMMENTS AND REPLACE WITH OAK
 TREES)
 87. PLEASE REMOVE THE LOW WALL FROM THE BISTRO OUTDOOR
 AREA AS THIS AREA IS BEING CONSIDERED PUBLIC OPEN SPACE
 (IN TIME FOR DAC SUBMITTAL ? ON PLANS SUBMITTED NO
 LATER THAN 11/27)
 88. PLEASE REMOVE REFERENCE TO ?PRIVATE TERRACE ALONG
 DATURA STREET? FROM THE SOUTH DIXIE HIGHWAY SIDE
 ELEVATION ON SHEET A-3.2 AS THIS IS BEING TREATED AS
 PUBLIC OPEN SPACE (IN TIME FOR DAC SUBMITTAL ? ON PLANS
 SUBMITTED NO LATER THAN 11/27)
 89. PLEASE CONSIDER THE ADDITION OF COLOR INTO THE
 LANDSCAPE PALETTE ALONG DIXIE HIGHWAY AND QUADRILLE
 BOULEVARD
 90. THERE IS AN AREA ADJACENT TO THE INTERIOR BICYCLE
 RACKS THAT IS SHOWN DIFFERENTLY ON THE SITE PLAN
 COMPARED TO CIVIL PLANS. PLEASE CLARIFY
 91. CONSIDER A CORRIDOR OR DOOR FROM THE OUTSIDE TO
 ACCESS THE INTERIOR BICYCLE RACKS TO ELIMINATE THE NEED
 FOR CYCLISTS TO CROSS OVER THE GARAGE RAMP ENTRANCE.
 THE LOCATION OF THE RACKS DOES NOT WORK WELL FOR
 INGRESS AND EGRESS
 92. PLEASE ADDRESS THE EXITING TRAFFIC POLE BOXES AT
 PROPERTY?S SOUTHEAST CORNER. PLEASE INCORPORATE INTO
 LANDSCAPE BED.
 93. PLEASE INDICATE PROPOSED LOCATION OF BACKFLOW
 PREVENTER. PLEASE PLAN TO LOCATE WITHIN LANDSCAPE BED.
 94. PLEASE ENSURE THAT GROUND MOUNTED FDC IS WITHIN A
 LANDSCAPE BED OR ALTERNATIVELY, MOUNT ON WALL.
 95. PLEASE PROVIDE GROUND LEVEL 3D RENDERINGS FOR DAC
 APPLICATION (NO LATER THAN 11/27) ? INCLUDE LANDSCAPE
 AT PLANTING LEVEL. PLEASE INCLUDE DAY TIME RENDERING.
 96. PLEASE NOTE, NEXT SITE PLAN RESUBMITTAL WILL HAVE A
 REQUIRED RESUBMITTAL FEE OF $300 (RESUBMITTAL FEE,
 CHARGED AFTER 1ST RESUBMITTAL)
 97. THE STAIRWELL ALONG QUADRILLE BOULEVARD HAS A
 DOORWAY THAT OPENS INTO THE SIDEWALK AREA, WHICH DOES
 NOT WORK. THIS WILL NEED TO BE RECESSED.
  
  
 ELIZABETH LEVESQUE, AICP, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426

Review Stop Z ZONING
Rev No 2 Status F Date 09-09-2019 Cont ID  
Sent By elevesqu Date 09-09-2019 Time 16:30 Rev Time 0.00
Received By elevesqu Date 09-09-2019 Time 16:30 Sent To  
Notes
2019-09-09 16:30:091. ONGOING. THE PROJECT CANNOT PROCEED TO DOWNTOWN
 ACTION COMMITTEE UNTIL THE DETAILS OF THE RESTRICTIVE
 COVENANT AND AMENDMENT TO THE DEVELOPMENT AGREEMENT
 (JULY 19, 2004) ARE RESOLVED. PRELIMINARY REVIEW OF THE
 DOCUMENTS, SUBJECT TO LEGAL INTERPRETATION, IDENTIFY
 THE FOLLOWING:
 A. CONSTRUCTION OF FOR-SALE RESIDENTIAL CONDOMINIUM
 UNITS ON ALL FLOORS ABOVE THE GROUND FLOOR OF THE
 PROJECT.
 B. ANY BUILDING CONSTRUCTED ON THE PROPERTY SHALL
 CONTAIN A FULL SERVICE PHARMACY ON THE GROUND FLOOR NO
 LESS THAN 1500 GROSS SF IN SIZE FOR A TERM OF 3 YEARS.
 C. DEVELOPER SHALL CONSTRUCT 100 PUBLIC PARKING SPACES
 TO BE LOCATED ON LOWER 2 FLOORS OF PROJECT, SEPARATED
 FROM THE PARKING SERVING OTHER ELEMENTS OF THE PROJECT
 PLEASE ADDRESS THE INTENT OF THE APPLICANT IN REGARDS
 TO THE REQUIREMENTS OF THE RESTRICTIVE COVENANT AND
 DEVELOPER AGREEMENT IN THE JUSTIFICATION STATEMENT UPON
 RESUBMITTAL.
 2. ONGOING. THE PROJECT SHALL OBTAIN DAC APPROVAL OF A
 CLASS B LICENSE FOR A TYPE III GROUP HOMES .
 3. ONGOING. FOR GROUP HOMES PERMITTED AS A CLASS B
 SPECIAL USE, A GROUP HOME FACILITY SHALL BE LOCATED A
 MINIMUM OF 1,200 FEET FROM ANOTHER SUCH FACILITY. A
 VARIANCE FROM THIS PROVISION WILL BE REQUIRED FOR THIS
 LOCATION. PLEASE PROVIDE JUSTIFICATION FROM VARIANCE IN
 JUSTIFICATION STATEMENT.
 4. ONGOING. PER SECTION 94-54(A)(3), FORMAL SITE PLAN
 APPROVALS INVOLVING THE TDR PROGRAM SHALL BE APPROVED
 BY DAC AND THE CERTIFICATE OF TRANSFER SHALL BE
 OBTAINED PRIOR TO THE EXPIRATION OF THE SITE PLAN
 APPROVAL.
 5. NOT SATISFIED. PLEASE INCLUDE THE AMOUNT OF TDRS
 NEEDED FOR THE SITE (SQUARE FEET) AND THE AMOUNT OF SF
 GRANTED BY RIGHT IN THE PROJECT DATA TABLE.
 CANNOT LOCATE BREAKDOWN OF SF IN PROJECT DATA TABLE.
 PLEASE INCLUDE SPECIFIC SF BY RIGHT, AND SF REQUESTED
 BY TDRS.
 6. ONGOING. PROJECT SHALL REQUIRE DAC SPECIAL REVIEW
 AND VARIANCE REVIEW. WITH SUBMITTAL FOR VARIANCE
 REVIEW, PLEASE RESPOND TO THE CRITERIA FOR VARIANCE
 REQUESTS FOR EACH REQUESTED VARIANCE, SEPARATELY, AS
 ESTABLISHED IN SECTION 94-38(D)(6).
 7. PARTIALLY SATISFIED. PLEASE ILLUSTRATE ADJACENT
 BUILDING FRONTAGES AND CURB LINES ACROSS DIXIE HIGHWAY,
 DATURA STREET AND THE ALLEYWAY.
 8. SATISFIED.
 9. ONGOING. IF VALET IS PROPOSING UTILIZING EXISTING OR
 PROPOSED ON-STREET PARKING FOR VALET, THE APPLICANT
 SHALL PAY FOR THE USE OF THOSE OCCUPIED SPACES IN
 AMOUNT AS ESTABLISHED BY THE CITY AND IN LOCATIONS
 APPROVED BY THE CITY PARKING ADMINISTRATOR. THIS WOULD
 UTILIZE EXISTING ON-STREET PARKING SPACES AND NOT
 INTERFERE WITH SIDEWALK CONNECTIVITY.
 10. ONGOING. SUBJECT TO FURTHER COMMENT. EFFORTS FOR
 ALLEY AND STREETSCAPE SHALL BE COORDINATED WITH CITY
 ENGINEERS.
 11. SATISFIED.
 12. SATISFIED.
 13. ONGOING. STAFF CAN HELP COORDINATE WITH PALM TRAN.
 14. SATISFIED.
 15. SATISFIED.
 16. SATISFIED.
 17. SATISFIED.
 18. NOT SATISFIED. STAFF HAS CONCERN WITH THE SETBACK
 OF THE GROUND FLOOR USES ON THE WEST SIDE OF DATURA
 STREET, AS IT DOES NOT PROVIDE FOR ACTIVATED PEDESTRIAN
 SPACE AND INTERACTION WITH THE STREET AS OTHER
 RESIDENTIAL BUILDINGS DO WITHIN THE DMP AREA.
 PLEASE SEE NEW COMMENT # 55
 19. ONGOING. IN ORDER TO COUNT TANDEM PARKING SPACES AS
 TWO SPACES, A RESTRICTIVE COVENANT SHALL BE REQUIRED
 FOR CONFIRMATION OF A VALET ATTENDANT IN CHARGE OF THE
 OPERATION OF THE PARKING FACILITY DURING ALL OPERATING
 HOURS.
 20. PARTIALLY SATISFIED. PLEASE NOTE, THE PARKING
 REQUIRED FOR THE INDEPENDENT LIVING UNITS MUST MEET THE
 REQUIREMENTS FOR RESIDENTIAL USES WITHIN THE DMP WHICH
 IS MINIMUM 1 PER UNIT PLUS 1 PER 20 UNITS FOR GUEST
 PARKING, MAXIMUM 2 PER UNIT PLUS 1 PER 20 UNITS FOR
 GUEST PARKING. PLEASE SEPARATE PARKING REQUIREMENTS FOR
 INDEPENDENT LIVING FROM ASSISTED LIVING AND MEMORY CARE
 AND DETERMINE NUMBER OF PARKING SPACES REQUESTED FOR
 THE WAIVER. THE WAIVER CANNOT EXCEED 50% OF THE
 REQUIRED PARKING FOR THE PROJECT.
 PLEASE SEE NEW COMMENT #70. DEPENDING ON AMOUNT OF
 PROVIDED PARKING SPACES, ONLY ONE VARIANCE FOR PARKING
 MAY BE REQUIRRED, TO REDUCE THE AMOUNT OF VARIANCES
 REQUESTED. THE CURRENT PROVIDED PARKING SPACES (TOTAL,
 INCLUDING ON-STREET SPACES) WOULD NOT REQUIRE BOTH
 VARIANCES.
 21. ONGOING. PER SECTION 94-481(F):
 A. TO BE ELIGIBLE FOR THE SENIOR HOUSING PARKING
 WAIVER, CRITERIA MUST BE MET. PLEASE RESPOND TO THE
 CRITERIA.
 B. IF THE PARKING WAIVER IS GRANTED, A RESTRICTIVE
 COVENANT RESTRICTING THE USE OF THE PROPERTY TO SERVING
 PERSONS WHO ARE 55 YEARS AND OLDER FOR A PERIOD OF NOT
 LESS THAN 15 YEARS SHALL BE EXECUTED AND RECORDED.
 22. PARTIALLY SATISFIED. PLEASE SUBMIT PLANS
 ILLUSTRATING THE TRANSPARENCY REQUIREMENTS PER TABLE
 IV-50: BUILDING REQUIREMENTS- CWD 10-12 STORY RECEIVING
 SITES (SECTION 94-134).
 PLEASE ADDRESS TRANSPARENCY ALONG DIXIE HIGHWAY.
 23. PARTIALLY SATISFIED. PLEASE PROVIDE DATA ON
 BUILDING FOOTPRINT MAXIMUM IN SITE TABLE PER TABLE
 IV-50.
 THE BUILDING FOOTPRINT EXCEEDS THE MAXIMUM ON LEVEL
 FOUR.
 24. ONGOING. THE PROJECT DOES NOT MEET ACTIVE USE LINER
 REQUIREMENTS ALONG QUADRILLE BOULEVARD AND DATURA
 STREET. PLEASE ADDRESS VARIANCE CRITERIA IN THE
 JUSTIFICATION STATEMENT.
 25. SATISFIED.
 26. ONGOING. THE SUBMITTED JUSTIFICATION STATEMENT
 STATES THAT THE PROPOSED PLAN ADHERES TO ALL SETBACK
 REQUIREMENTS; HOWEVER THE REQUIRED PARKING SETBACK FOR
 2 AND 3 STORY ALONG DATURA STREET IS NOT MET. PLEASE
 ADJUST TO MEET SETBACK REQUIREMENT.
 27. SATISFIED.
 28. PARTIALLY SATISFIED. THE PRIVATE OPEN SPACE ALONG
 QUADRILLE BOULEVARD DOES NOT MEET THE DEFINITION OR
 INTENT OF PRIVATE OPEN SPACE. SEE LANDSCAPE COMMENTS.
 29. NOT SATISFIED. PLEASE PRESERVE THE EXISTING CEMENT
 CANOPY ON SITE, PER CITY HISTORIC PRESERVATION PLANNER.
 THIS COULD BE MAINTAINED WITHIN THE OPEN SPACE.
 TO BE DISCUSSED INTERNALLY WITH HISTORIC PRESERVATION
 PLANNER. CONVERSATION ONGOING.
 30. NOT SATISFIED. THE PROPOSED PUBLIC OPEN SPACE ALONG
 DATURA STREET CANNOT COUNT AS PUBLIC OPEN SPACE, PER
 THE DEFINITION OF PUBLIC OPEN SPACE. STAFF RECOMMENDS
 UTILIZING SOME SPACE ALONG DIXIE HIGHWAY.
 SEE NEW COMMENT #60 AND LANDSCAPE COMMENTS.
 31. SATISFIED.
 32. SATISFIED.
 33. PARTIALLY SATISFIED. PLEASE PROVIDE ADDITIONAL
 DETAIL OF ARCHITECTURAL TREATMENT MATERIALS ON BUILDING
 ON ELEVATION PLANS.
 PLEASE PROVIDE ADDITIONAL DETAIL OF ALLEY GARAGE
 SCREENING MATERIAL. SEE NEW COMMENT #66
 34. PARTIALLY SATISFIED. LANDSCAPE BEDS CAN BE
 ENLARGED. SEE LANDSCAPE COMMENTS.
 35. SATISFIED.
 36. PARTIALLY SATISFIED. PLEASE CHECK CRITERIA FOR FDOT
 SIGHT TRIANGLE FOR PROPOSED TREES AT STREET CORNERS.
 PLEASE CHECK CORNER OF QUADRILLE AND DATURA. SEE
 LANDSCAPE COMMENTS.
 37. SATISFIED.
 38. NOT SATISFIED. PLEASE PROVIDE A HARDSCAPE PLAN WITH
 DETAILS OF PAVERS, SEATING, ETC.
 HARDSCAPE DETAILS ARE NEEDED FOR REVIEW OF PAVERS,
 SEATING, LANDSCAPE BED AREAS (ALONG DATURA STREET
 APPEARS TO HAVE BENCHES AROUND LANDSCAPE AREA), ETC.
 39. NOT SATISFIED. PLEASE SEE TABLE IV-7 FOR OPEN SPACE
 STANDARDS. CURRENTLY THE PASSAGEWAY PUBLIC OPEN TYPE IS
 REQUIRED. STAFF IS CURRENTLY REVIEWING THIS REQUIREMENT
 FOR APPLICABILITY FOR THIS SITE.
 TABLE IV-7 WILL BE UPDATED AFTER THE SECOND COMMISSION
 READING ON SEPTEBMER 9, 2019. PLEASE CONTACT STAFF FOR
 UPDATED TABLE, WHICH PERMITS ADDITIONAL TYPES OF OPEN
 SPACE IN CWD-CD AT DISCRETION OF P&Z. EXACT TYPE OF
 OPEN SPACE NEEDS TO BE CALLED OUT. SEE LANDSCAPE
 COMMENTS.
 40. NOT SATISFIED. PLEASE ADDRESS SPECIFIC PRIVATE AND
 PUBLIC OPEN SPACE REQUIREMENTS PER TABLE IV-6 AND TABLE
 IV-7, INCLUDING TYPE OF OPEN SPACE (COURTYARD GARDEN,
 TERRACE, ETC.) FOR EACH OPEN SPACE AND SEE THE
 REQUIREMENTS FOR VEGETATED SPACE, SEATING, ETC.
 SEE LANDSCAPE COMMENTS.
 41. SATISFIED.
 42. ONGOING. PER SECTION 94-111: PARKING AND LOADING
 REQUIREMENTS, A MINIMUM THREE FOOT BACK UP AREA SHALL
 BE PROVIDED AT THE TERMINUS OF ANY DEAD-END DRIVE
 AISLE, SHALL BE RESTRIPED AS DEDICATED PULL-IN AREA FOR
 TURNING AROUND.
 SUBJECT TO FURTHER REVIEW BY CITY ENGINEER AS PRESENTED
 TURNAROUND IS NOT THE TYPICAL FOR CODE REQUIREMENTS.
 43. SATISFIED.
 44. ONGOING. PER SECTION 94-111, ONE BICYCLE PARKING
 SPACE SHALL BE PROVIDED PER EVERY 15 REQUIRED PARKING
 SPACES, IN A SECURE AREA, COVERED FROM THE ELEMENTS.
 PLEASE ADJUST WITH UPDATED REQUIRED PARKING NUMBER. SEE
 NEW COMMENT 70
 45. NOT SATISFIED. PER SECTION 93-113, BICYCLE PARKING
 FOR THE PUBLIC SHALL BE PROVIDED AT A MINIMUM OF ONE
 SPACE PER EVERY 100 FEET OF STREET FRONTAGE. THE POST
 AND LOOP RACK IS RECOMMENDED FOR THE PUBLIC ROW. PLEASE
 INDICATE EXACT BICYCLE RACK DETAIL ON PLANS.
 ONE ADDITIONAL SPACE REQUIRED. PLEASE SHIFT BICYCLE
 RACKS TO ALLOW FOR THREE FEET FROM THE POST TO THE EDGE
 OF PAVER AREA.
 46. NOT SATISFIED. PLEASE INCLUDE SPECIFIC DIMENSIONS
 OF BICYCLE RACKS ON THE SITE PLAN. THE POLE SHALL BE NO
 FURTHER THAN THREE FEET FROM THE EDGE OF CURB
 MAINTAINING A MINIMUM FIVE FOOT CLEARANCE FOR
 PEDESTRIAN CIRCULATION.
 THERE IS A DIFFERENCE BETWEEN BICYCLE RACK DETAILS ON
 CIVIL PLANS AND ARCHITECTURAL PLANS. PLEASE COORDINATE.
 47. ONGOING. PLEASE INDICATE LOCATION OF PROPOSED
 UTILITIES INCLUDING THE BACKFLOW PREVENTER, FDC
 CONNECTION, FPL TRANSFORMER, ETC. STAFF RECOMMENDS
 LOCATING THE UTILITIES WITHIN THE BUILDING FOOTPRINT
 AND PROVIDING ACCESS TO UTILITY COMPANIES, TO KEEP OFF
 THE PUBLIC ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED
 ALONG THE ALLEY SIDE OF THE BUILDING. SUFFICIENT
 LANDSCAPE SCREENING IS REQUIRED WHEN UTILITIES ARE
 LOCATED OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A
 MINIMUM OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED
 AT ALL LOCATIONS.
 PLEASE UTILIZE WALLMOUNTED FDC SUBJECT TO FD
 REQUIREMENTS. PLACEMENT OF UTILITIES SHALL BE ONGOING
 THROUGH PLANNING AND PERMIT PROCESS, SUBJECT TO REVIEW
 BY ZONING, LANDSCAPE PLANNER, AND BUILDING DEPARTMENTS.
 48. SATISFIED.
 49. NOT SATISFIED. THE MINIMUM FOOTCANDLE, AS MEASURED
 AT THE BACK EDGE OF THE CURB AND ONE FOOT ABOVE THE
 SIDEWALK IS 0.6 AND THE MAXIMUM IS 1.0 FOOTCANDLE.
 PLEASE ADJUST PHOTOMETRICS EXTENDING TO THE ROADWAY
 CENTERLINES AND PROVIDE DETAILS OF THE PROPOSED LIGHT
 FIXTURES AS NECESSARY. PLEASE COORDINATE WITH THE
 ENGINEERING DEPARTMENT TO USE THE CITY APPROVED LIGHT
 FIXTURE. A SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 NO PHOTOMETRIC PLANS SUBMITTED.
 50. NOT SATISFIED. PLEASE PROVIDE PROPOSED PHOTOMETRICS
 FOR THE PARKING GARAGE, MEETING THE REQUIREMENTS OF
 SECTION 86-294.
 NO PHOTOMETRIC PLANS SUBMITTED.
 51. SATISFIED.
 52. ONGOING. APPLICANT SHALL BE REQUIRED TO MEET
 REQUIREMENTS OF ART IN PUBLIC PLACES. CONTACT SYBILLE
 WELTER AT [email protected] FOR MORE INFORMATION.
 53. SATISFIED.
  
 NEW COMMENTS SEPTEMBER 9, 2019:
 54. PLEASE UPDATE THE CONTEXTUAL MAP AND BUILDING
 MASSING EXHIBIT WITH BROADSTONE BUILDING.
 55. STAFF HAS CONCERN WITH ONLY ONE ENTRANCE ALONG
 DATURA STREET AND NO OPENINGS ALONG QUADRILLE BOULEVARD
 AS THIS DOES NOT MEET THE INTENT AND DEFINITION OF
 ACTIVE USE. BASED ON PREVIOUS DISCUSSION, THE
 UTILIZATION OF THE SPACES FOR RETAIL/SERVICES OPEN TO
 THE GENERAL PUBLIC WERE BEING CONSIDERED. WITHOUT
 PUBLIC ACCESS, STAFF HAS CONCERN WITH THE RELATIONSHIP
 OF THE BUILDING TO THE PUBLIC STREET.
 56. PLEASE CONSIDER THE HEIGHT OF THE COMPACTOR ROOM
 FOR THE RESIDENTIAL USE. STAFF WILL DISCUSS WITH PUBLIC
 WORKS TO ENSURE THE CORRECT HEIGHT IS USED.
 57. PLEASE PROVIDE BUILDING SECTIONS WITH RESUBMITTAL.
 58. PLEASE EXPLAIN THE OPEN FLOOR PARKING GARAGE ON THE
 4TH FLOOR. IN LIGHT OF THE RESTRICTIVE COVENANT FOR 50
 PUBLIC PARKING SPACES, THIS SPACE COULD BE UTILIZED FOR
 ADDITIONAL PARKING SPACES.
 59. THE COVERED TERRACE ALONG DATURA STREET CANNOT BE
 COUNTED TOWARDS PRIVATE OPEN SPACE PER PRIVATE OPEN
 SPACE DEFINITION.
 60. EXCEEDING THE MAXIMUM SETBACK ALONG DIXIE STREET
 CAN ONLY BE PERMITTED IF THE OPEN SPACE IS PUBLIC OPEN
 SPACE, NOT PRIVATE.
 61. PLEASE CONSIDER WINDOWS OR ARCHITECTURAL TREATMENT
 FOR THE ACTIVE USE AT THE CORNER OF DIXIE HIGHWAY AND
 DATURA STREET.
 62. PLEASE PROVIDE THE SETBACK FROM THE ALLEY TO THE
 PORCH RAILINGS ON THE UPPER LEVELS.
 63. STAFF HAS CONCERN WITH THE ARCHITECTURAL TREATMENT
 OF THE ALLEY PARKING GARAGE LEVELS, ESPECIALLY ABOVE
 THE SECOND FLOOR. THE ADJACENT STRUCTURE IS ONLY TWO
 STORIES AND THE LEVELS ABOVE WOULD BE VERY VISIBLE FROM
 THE PUBLIC ROW.
 64. THE STORAGE AREA ALONG DATURA STREET CANNOT BE
 COUNTED FOR ACTIVE USE. PLEASE AMEND ACTIVE USE
 CALCULATIONS.
 65. PLEASE EXPLAIN WHY THE NORTHERN EDGE OF THE
 STRUCTURE ALONG QUADRILLE BOULEVARD IS OPEN AIR
 66. PLEASE UPDATE THE ELEVATIONS TO INCLUDE LANDSCAPE
 PLANS. PLEASE INCLUDE ADDITIONAL ARCHITECTURAL MATERIAL
 LABELS INCLUDING GLASS, FAUX GLASS, STUCCO, ETC.
 67. PLEASE INCLUDE BUMPER STOPS FOR THE FIVE PARKING
 SPOTS ALONG THE ALLEY.
 68. PLEASE ADJUST THE SETBACK MEASUREMENT AT ALL
 LOCATIONS TO BE FROM THE BACK OF CURB, NOT FRONT (SEE
 DATURA MEASUREMENT) AND MEASURE TO FURTHER PROJECTION.
 69. THE PARKING DATA APPEARS TO BE INCORRECT AS IT IS
 BASED ON 58 BEDS, RATHER THAN 56 AS MENTIONED IN THE
 SITE DATA. PLEASE ADJUST AS NECESSARY.
 70. BASED ON THE CURRENT PROVIDED PARKING, ONLY ONE
 VARIANCE MAY BE REQUIRED (FROM EITHER SENIOR LIVING, OR
 ASSISTED LIVING). PLEASE ADJUST AS NECESSARY,
 COORDINATING WITH NEW COMMENT 58.
 71. PLEASE CLARIFY THE 2,021 SF OF OFFICE SPACE, AS
 COUNTED IN THE PARKING DATA TABLE.
 72. THE FAR CALCULATIONS WOULD INCLUDE THE STAIRWELL
 ALONG QUADRILLE BOULEVARD AS THE STAIRWELL CONNECTS TO
 THE RESIDENTIAL BUILDING. SEE DEFINITION OF GROSS SF IN
 SECTION 94-109.
 73. PLEASE NOTE, IF THE GARAGE STORAGE IS NOT COUNTED
 TOWARDS FAR, THESE AREAS CANNOT BE UNDER AC AND CAN
 NEVER BE UNDER AC UNLESS THE FAR IS NOT EXCEEDED. IF
 NOT UNDER AC, PLEASE MAKE NOTES ON ARCHITECTURAL PLANS.
 74. IT APPEARS THAT THE STAIRWELL ON QUADRILLE
 BOULEVARD MAY SHIFT AS IT CONNECTS TO THE RESIDENTIAL
 PORTION ON LEVEL 6. PLEASE ADJUST FAR DIAGRAM AS
 NECESSARY. IT MAY BE THAT A SEPARATE FAR DIAGRAM FOR
 LEVEL 6 IS REQUIRED IF DIFFERENT FROM LEVEL 7 AND 8.
 75. PLEASE AMEND THE MASSING STUDY WITH THE UPDATED
 ELEVATION AND INCLUDE THE ADJACENT BROADSTONE BUILDING.
 76. A STRIP OF PAVERS THAT APPEARS ON THE ARCHITECTURAL
 PLANS DOES NOT APPEAR ON THE CIVIL PLANS. WHAT IS THE
 PURPOSE OF THIS STRIP? PLEASE COORDINATE PLANS.
 77. PLEASE INCLUDE ADA PARKING SPACES. SEE BUILDING
 COMMENTS.
  
 LIZ LEVESQUE, URBAN DESIGN PLANNER
 [email protected]
 561 822 1426
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By elevesqu Date 06-10-2019 Time 17:00 Rev Time 0.00
Received By elevesqu Date 06-10-2019 Time 17:00 Sent To  
Notes
2019-06-12 08:37:081. THE PROJECT CANNOT PROCEED TO DOWNTOWN ACTION
 COMMITTEE UNTIL THE DETAILS OF THE RESTRICTIVE COVENANT
 AND AMENDMENT TO THE DEVELOPMENT AGREEMENT (JULY 19,
 2004) ARE RESOLVED. PRELIMINARY REVIEW OF THE
 DOCUMENTS, SUBJECT TO LEGAL INTERPRETATION, IDENTIFY
 THE FOLLOWING:
 A. CONSTRUCTION OF FOR-SALE RESIDENTIAL CONDOMINIUM
 UNITS ON ALL FLOORS ABOVE THE GROUND FLOOR OF THE
 PROJECT.
 B. ANY BUILDING CONSTRUCTED ON THE PROPERTY SHALL
 CONTAIN A FULL SERVICE PHARMACY ON THE GROUND FLOOR NO
 LESS THAN 1500 GROSS SF IN SIZE FOR A TERM OF 3 YEARS.
 C. DEVELOPER SHALL CONSTRUCT 100 PUBLIC PARKING SPACES
 TO BE LOCATED ON LOWER 2 FLOORS OF PROJECT, SEPARATED
 FROM THE PARKING SERVING OTHER ELEMENTS OF THE PROJECT
 PLEASE ADDRESS THE INTENT OF THE APPLICANT IN REGARDS
 TO THE REQUIREMENTS OF THE RESTRICTIVE COVENANT AND
 DEVELOPER AGREEMENT IN THE JUSTIFICATION STATEMENT UPON
 RESUBMITTAL.
 2. THE PROJECT SHALL OBTAIN DAC APPROVAL OF A CLASS B
 LICENSE FOR A TYPE III GROUP HOMES .
 3. FOR GROUP HOMES PERMITTED AS A CLASS B SPECIAL USE,
 A GROUP HOME FACILITY SHALL BE LOCATED A MINIMUM OF
 1,200 FEET FROM ANOTHER SUCH FACILITY. A VARIANCE FROM
 THIS PROVISION WILL BE REQUIRED FOR THIS LOCATION.
 PLEASE PROVIDE JUSTIFICATION FROM VARIANCE IN
 JUSTIFICATION STATEMENT.
 4. PER SECTION 94-54(A)(3), FORMAL SITE PLAN APPROVALS
 INVOLVING THE TDR PROGRAM SHALL BE APPROVED BY DAC AND
 THE CERTIFICATE OF TRANSFER SHALL BE OBTAINED PRIOR TO
 THE EXPIRATION OF THE SITE PLAN APPROVAL.
 5. PLEASE INCLUDE THE AMOUNT OF TDRS NEEDED FOR THE
 SITE (SQUARE FEET) AND THE AMOUNT OF SF GRANTED BY
 RIGHT IN THE PROJECT DATA TABLE.
 6. PROJECT SHALL REQUIRE DAC SPECIAL REVIEW AND
 VARIANCE REVIEW. WITH SUBMITTAL FOR VARIANCE REVIEW,
 PLEASE RESPOND TO THE CRITERIA FOR VARIANCE REQUESTS
 FOR EACH REQUESTED VARIANCE, SEPARATELY, AS ESTABLISHED
 IN SECTION 94-38(D)(6).
 7. PLEASE CONDENSE THE TWO SEPARATE SITE PLANS SHEET
 SP-1 AND SP.1 INTO ONE SITE PLAN. PLEASE SHOW GROUND
 FLOOR USES, WITH THE OUTLINE OF UPPER LEVELS, SETBACK
 DIMENSIONS, EXISTING CURB LINE, ALL APPLICABLE
 DIMENSIONS, AND OTHER REQUIRED INFORMATION. PLEASE
 ILLUSTRATE ADJACENT BUILDING FRONTAGES AND CURB LINES
 ACROSS DIXIE HIGHWAY, DATURA STREET AND THE ALLEYWAY.
 8. THE PROPOSED DROP-OFF DOES NOT MEET THE FOLLOWING
 REQUIREMENTS:
 A. DESIGNATED PASSENGER LOADING AND DROP-OFF AREAS
 SHALL OCCUR WITHIN THE FOOTPRINT OF THE BUILDING
 ENVELOPE AND SHALL BE SUBJECT TO APPROVAL BY THE CITY
 TRAFFIC ENGINEER.
 B. CURB CUTS FOR INGRESS AND EGRESS SHALL BE NO MORE
 THAN 25 FEET, MEASURED AT THE CURB LINE.
 C. CAR QUEUING SHALL OCCUR INTERNAL TO THE LOT AND
 SHALL NOT INTERFERE WITH PEDESTRIAN CIRCULATION ON A
 PUBLIC SIDEWALK. THE PROPOSED LOCATION OF THE DROP OFF
 INTERFERES WITH PEDESTRIAN CIRCULATION.
 D. FOR REFERENCE, ?TYPE A? PORTE COCHERES SHALL BE
 ALLOWED FOR HOTELS IN THIS DISTRICT.
 STAFF RECOMMENDS CONSIDERING UTILIZING THE EXISTING
 GARAGE ENTRANCE OFF OF THE ALLEYWAY FOR COVERED DROP
 OFF.
 9. IF VALET IS PROPOSING UTILIZING EXISTING OR PROPOSED
 ON-STREET PARKING FOR VALET, THE APPLICANT SHALL PAY
 FOR THE USE OF THOSE OCCUPIED SPACES IN AMOUNT AS
 ESTABLISHED BY THE CITY AND IN LOCATIONS APPROVED BY
 THE CITY PARKING ADMINISTRATOR. THIS WOULD UTILIZE
 EXISTING ON-STREET PARKING SPACES AND NOT INTERFERE
 WITH SIDEWALK CONNECTIVITY.
 10. PLEASE INDICATE THE PROPOSED DIRECTION OF THE
 ALLEY. MANY BUSINESSES ON CLEMATIS STREET USE THIS
 ALLEY FOR PARKING AND GARBAGE COLLECTION, WHICH WILL BE
 CONSIDERED IN THE DESIGN INTENT.
 11. THE APPLICANT SHALL WORK WITH PUBLIC WORKS
 REGARDING THE EXISTING DUMPSTER THAT IS LOCATED WITHIN
 THE PROPERTY AND USED BY BUSINESSES ON THE 400 BLOCK OF
 CLEMATIS STREET.
 12. PLEASE PROVIDE TURN MOVEMENTS FOR ENTERING AND
 EXITING THE PARKING GARAGE TO ENSURE THE TURNS CAN WORK
 SAFELY.
 13. APPLICANT SHALL CONTACT PALM TRAN FOR PROPOSAL TO
 REMOVE/RELOCATE OF BUS SHELTER. STAFF RECOMMENDS THE
 USE OF THE EXISTING SHELTER LOCATED SOUTH OF THE
 PROPERTY AT 499 EVERNIA STREET (BROADSTONE). IF PALM
 TRAN DOES NOT PERMIT RELOCATION OF BUS STOP TO THIS
 LOCATION, THE APPLICANT SHALL REPLACE WITH A NEW BUS
 SHELTER, MEETING PALM TRAN STANDARDS.
 14. APPLICANT SHALL REQUIRE FDOT APPROVAL FOR ANY WORK
 DONE ON QUADRILLE BOULEVARD.
 15. PLEASE COORDINATE WITH THE CITY ENGINEERING
 DEPARTMENT ON THE PROPOSED DATURA STREET REDESIGN THAT
 IS CURRENTLY IN INITIAL DESIGN PHASE.
 16. THE PROPOSED UNDER COVER AREA ON THE GROUND FLOOR
 DOES NOT MEET THE DEFINITION OF COLONNADE FOR THE DMP
 AREA AND DOES NOT FIT INTO THE CONTEXT OF THE DIRECT
 AREA. STAFF RECOMMENDS ELIMINATION OF THE COLONNADE AS
 IT DOES NOT ACTIVATE THE PEDESTRIAN ENVIRONMENT AND
 DOES NOT IMPROVE ACTIVE USE OR TRANSPARENCY ALONG THE
 SIDEWALK.
 17. ARE ALL USES ON THE GROUND FLOOR PRIVATE? PLEASE
 CLARIFY WHICH USES ARE OPEN TO PUBLIC, IF ANY OR
 ACCESSIBLE FROM THE STREET.
 18. STAFF HAS CONCERN WITH THE SETBACK OF THE GROUND
 FLOOR USES ON THE WEST SIDE OF DATURA STREET, AS IT
 DOES NOT PROVIDE FOR ACTIVATED PEDESTRIAN SPACE AND
 INTERACTION WITH THE STREET AS OTHER RESIDENTIAL
 BUILDINGS DO WITHIN THE DMP AREA.
 19. IN ORDER TO COUNT TANDEM PARKING SPACES AS TWO
 SPACES, A RESTRICTIVE COVENANT SHALL BE REQUIRED FOR
 CONFIRMATION OF A VALET ATTENDANT IN CHARGE OF THE
 OPERATION OF THE PARKING FACILITY DURING ALL OPERATING
 HOURS.
 20. PLEASE NOTE, THE PARKING REQUIRED FOR THE
 INDEPENDENT LIVING UNITS MUST MEET THE REQUIREMENTS FOR
 RESIDENTIAL USES WITHIN THE DMP WHICH IS MINIMUM 1 PER
 UNIT PLUS 1 PER 20 UNITS FOR GUEST PARKING, MAXIMUM 2
 PER UNIT PLUS 1 PER 20 UNITS FOR GUEST PARKING. PLEASE
 SEPARATE PARKING REQUIREMENTS FOR INDEPENDENT LIVING
 FROM ASSISTED LIVING AND MEMORY CARE AND DETERMINE
 NUMBER OF PARKING SPACES REQUESTED FOR THE WAIVER. THE
 WAIVER CANNOT EXCEED 50% OF THE REQUIRED PARKING FOR
 THE PROJECT.
 21. PER SECTION 94-481(F):
 A. TO BE ELIGIBLE FOR THE SENIOR HOUSING PARKING
 WAIVER, CRITERIA MUST BE MET. PLEASE RESPOND TO THE
 CRITERIA.
 B. IF THE PARKING WAIVER IS GRANTED, A RESTRICTIVE
 COVENANT RESTRICTING THE USE OF THE PROPERTY TO SERVING
 PERSONS WHO ARE 55 YEARS AND OLDER FOR A PERIOD OF NOT
 LESS THAN 15 YEARS SHALL BE EXECUTED AND RECORDED.
 22. PLEASE SUBMIT PLANS ILLUSTRATING THE TRANSPARENCY
 REQUIREMENTS PER TABLE IV-50: BUILDING REQUIREMENTS-
 CWD 10-12 STORY RECEIVING SITES (SECTION 94-134).
 23. PLEASE PROVIDE DATA ON BUILDING FOOTPRINT MAXIMUM
 IN SITE TABLE PER TABLE IV-50.
 24. THE PROJECT DOES NOT MEET ACTIVE USE LINER
 REQUIREMENTS ALONG QUADRILLE BOULEVARD AND DATURA
 STREET. PLEASE ADDRESS VARIANCE CRITERIA IN THE
 JUSTIFICATION STATEMENT.
 25. CONSIDERING THE PROPOSED VARIANCES, PLEASE EVALUATE
 THE USE OF ADDITIONAL ARCHITECTURAL MATERIALS, CONSIDER
 THE PROPORTIONS OF THE BUILDING, ESPECIALLY REFINING
 THE PARKING GARAGE DESIGN. PLEASE TAKE INTO
 CONSIDERATION THE REDESIGN BASED ON REMOVAL OF THE
 ARCADE PORTIONS (SEE COMMENT #16).
 26. THE SUBMITTED JUSTIFICATION STATEMENT STATES THAT
 THE PROPOSED PLAN ADHERES TO ALL SETBACK REQUIREMENTS;
 HOWEVER THE REQUIRED PARKING SETBACK FOR 2 AND 3 STORY
 ALONG DATURA STREET IS NOT MET. PLEASE ADJUST TO MEET
 SETBACK REQUIREMENT.
 27. FOR SETBACK MEASUREMENTS, WHERE A CURB LOCATION
 VARIES ALONG A PROPERTY, THE BACK OF CURB SHALL BE
 DEFINED AS THE PREDOMINANT BACK OF CURB LINE FURTHEST
 FROM THE CENTER LINE OF THE ROAD. PLEASE ADJUST SETBACK
 MEASUREMENTS ALONG SOUTH DIXIE HIGHWAY TO REFLECT THIS.
 28. THE PROPOSED PRIVATE OPEN SPACE USE ALONG QUADRILLE
 BOULEVARD IS NOT AN EFFECTIVE USE OF OPEN SPACE. STAFF
 RECOMMENDS SHIFTING THE BUILDING FOOTPRINT TO THE WEST
 TO BETTER ALIGN WITH THE FOOTPRINT OF THE ADJACENT
 BROADSTONE BUILDING AND UTILIZE MORE OPEN SPACE ALONG
 DIXIE HIGHWAY, TO INCREASE PEDESTRIAN ACTIVE SPACE.
 29. PLEASE PRESERVE THE EXISTING CEMENT CANOPY ON SITE,
 PER CITY HISTORIC PRESERVATION PLANNER. THIS COULD BE
 MAINTAINED WITHIN THE OPEN SPACE.
 30. THE PROPOSED PUBLIC OPEN SPACE ALONG DATURA STREET
 CANNOT COUNT AS PUBLIC OPEN SPACE, PER THE DEFINITION
 OF PUBLIC OPEN SPACE. STAFF RECOMMENDS UTILIZING SOME
 SPACE ALONG DIXIE HIGHWAY.
 31. THE PROPOSED CANOPY EXCEEDS THE MAXIMUM HORIZONTAL
 PROJECTION FOR CANOPIES. PER SECTION TABLE IV-5, THE
 MAXIMUM PROJECTION FOR CANOPIES IS 20 FEET WITH A 12
 FOOT MAXIMUM ENCROACHMENT INTO THE ROW. PLEASE INDICATE
 THE PROPOSED HEIGHT OF THE CANOPY, THE MINIMUM HEIGHT
 FROM SIDEWALK GRADE IS 10 FEET.
 32. THE QUADRILLE BOULEVARD ELEVATION DOES NOT
 ILLUSTRATE THE EXTENT OF THE PROPOSED CANOPY. PLEASE
 ADD TO SHOW ADJUSTED CANOPY SIZE PER COMMENT #31.
 33. PLEASE PROVIDE ADDITIONAL DETAIL OF ARCHITECTURAL
 TREATMENT MATERIALS ON BUILDING ON ELEVATION PLANS.
 34. TREE GRATES ARE NOT NECESSARY WHERE THERE IS
 SUFFICIENT SIDEWALK WIDTH ADJACENT TO THE PROPOSED
 TREE. PLEASE REMOVE TREE GRATES AND USE PLANTING BEDS
 (CONSIDER 6X4 BEDS) WHERE GRATES ARE PROPOSED.
 35. PLEASE PROVIDE OAK TREES OR SIMILAR SHADE TREES AT
 CORNER OF QUADRILLE AND DATURA AND DIXIE AND DATURA AS
 THIS IS WHERE PEDESTRIANS WAIT FOR STREET CROSSINGS.
 36. PLEASE CHECK CRITERIA FOR FDOT SIGHT TRIANGLE FOR
 PROPOSED TREES AT STREET CORNERS.
 37. THE PROPOSED EXFILTRATION TRENCH RUNS WHERE TREES
 ARE PROPOSED. PLEASE REVIEW AND ADJUST AS NECESSARY.
 38. PLEASE PROVIDE A HARDSCAPE PLAN WITH DETAILS OF
 PAVERS, SEATING, ETC.
 39. PLEASE SEE TABLE IV-7 FOR OPEN SPACE STANDARDS.
 CURRENTLY THE PASSAGEWAY PUBLIC OPEN TYPEIS REQUIRED.
 STAFF IS CURRENTLY REVIEWING THIS REQUIREMENT FOR
 APPLICABILITY FOR THIS SITE.
 40. PLEASE ADDRESS SPECIFIC PRIVATE AND PUBLIC OPEN
 SPACE REQUIREMENTS PER TABLE IV-6 AND TABLE IV-7,
 INCLUDING TYPE OF OPEN SPACE (COURTYARD GARDEN,
 TERRACE, ETC.) FOR EACH OPEN SPACE AND SEE THE
 REQUIREMENTS FOR VEGETATED SPACE, SEATING, ETC.
 41. PLEASE PROVIDE ILLUSTRATIONS SHOWING PLANAR BREAK
 REQUIREMENTS AS REQUIRED BY TABLE IV-4: FA?ADE
 ARTICULATION REQUIREMENTS.
 42. PER SECTION 94-111: PARKING AND LOADING
 REQUIREMENTS, A MINIMUM THREE-FOOT BACK UP AREA SHALL
 BE PROVIDED AT THE TERMINUS OF ANY DEAD-END DRIVE AISLE
 TO ALLOW FOR VEHICLES TO SAFELY PULL OUT OF THE END
 PARKING SPACES. IN ADDITION, THE EQUIVALENT OF ONE
 PARKING SPACE AT THE TERMINUS OF A DEAD-END AISLE SHALL
 BE STRIPED AS DEDICATED PULL-IN AREA FOR TURNING
 AROUND.
 43. PLEASE PROVIDE TYPICAL PARKING SPACE AND AISLE
 WIDTH DIMENSIONS ON EACH FLOOR. PLEASE NOTE, IN THOSE
 CASES WHERE THE SIDE OF ANY STALL IS ADJACENT TO A WALL
 OR COLUMN, THE STALL WIDTHS SHALL BE INCREASED BY A
 MINIMUM OF ONE FOOT. WHERE THERE IS AN OBSTRUCTION ON
 BOTH SIDES OF THE STALL THE STALL WIDTHS SHALL BE
 INCREASE BY A MINIMUM OF TWO FEET. PLEASE DIMENSION
 THIS ADDITIONAL ONE/TWO FOOT.
 44. PER SECTION 94-111, ONE BICYCLE PARKING SPACE SHALL
 BE PROVIDED PER EVERY 15 REQUIRED PARKING SPACES, IN A
 SECURE AREA, COVERED FROM THE ELEMENTS.
 45. PER SECTION 93-113, BICYCLE PARKING FOR THE PUBLIC
 SHALL BE PROVIDED AT A MINIMUM OF ONE SPACE PER EVERY
 100 FEET OF STREET FRONTAGE. THE POST AND LOOP RACK IS
 RECOMMENDED FOR THE PUBLIC ROW. PLEASE INDICATE EXACT
 BICYCLE RACK DETAIL ON PLANS.
 46. PLEASE INCLUDE SPECIFIC DIMENSIONS OF BICYCLE
 RACKS ON THE SITE PLAN. THE POLE SHALL BE NO FURTHER
 THAN THREE FEET FROM THE EDGE OF CURB MAINTAINING A
 MINIMUM FIVE FOOT CLEARANCE FOR PEDESTRIAN CIRCULATION.
 47. PLEASE INDICATE LOCATION OF PROPOSED UTILITIES
 INCLUDING THE BACKFLOW PREVENTER, FDC CONNECTION, FPL
 TRANSFORMER, ETC. STAFF RECOMMENDS LOCATING THE
 UTILITIES WITHIN THE BUILDING FOOTPRINT AND PROVIDING
 ACCESS TO UTILITY COMPANIES, TO KEEP OFF THE PUBLIC
 ROW. ALTERNATIVELY, UTILITIES CAN BE LOCATED ALONG THE
 ALLEY SIDE OF THE BUILDING. SUFFICIENT LANDSCAPE
 SCREENING IS REQUIRED WHEN UTILITIES ARE LOCATED
 OUTSIDE OF THE BUILDING AND WITHIN THE ROW. A MINIMUM
 OF 5 FOOT SIDEWALK CLEARANCE MUST BE MAINTAINED AT ALL
 LOCATIONS.
 48. THE CIVIL ENGINEERING PLANS SHOW PARKING SPACES
 THAT ARE NOT SHOWN ON THE SITE PLAN. PLEASE ADJUST
 ACCORDINGLY.
 49. THE MINIMUM FOOTCANDLE, AS MEASURED AT THE BACK
 EDGE OF THE CURB AND ONE FOOT ABOVE THE SIDEWALK IS 0.6
 AND THE MAXIMUM IS 1.0 FOOTCANDLE. PLEASE ADJUST
 PHOTOMETRICS EXTENDING TO THE ROADWAY CENTERLINES AND
 PROVIDE DETAILS OF THE PROPOSED LIGHT FIXTURES AS
 NECESSARY. PLEASE COORDINATE WITH THE ENGINEERING
 DEPARTMENT TO USE THE CITY APPROVED LIGHT FIXTURE. A
 SPECIFIC FIXTURE IS REQUIRED FOR ALL ROW.
 50. PLEASE PROVIDE PROPOSED PHOTOMETRICS FOR THE
 PARKING GARAGE, MEETING THE REQUIREMENTS OF SECTION
 86-294.
 51. EACH ENTRANCE SHOULD HAVE ITS OWN ADDRESS WHICH IS
 USED BY 911 EMERGENCY SERVICES. THE EXISTING PRIMARY
 ADDRESS WHICH WILL BE RETIRED WHEN THE PROJECT IS
 COMPLETE. THERE WILL SEPARATE ADDRESSES FOR THE MAIN
 LOBBY AND FOR THE MEMORY CARE LOBBY. THE OWNER CAN PICK
 WHICH WILL BE THE PRIMARY ADDRESS SEEN ON PAPA. CONTACT
 MICHAEL ORIO AT [email protected] WITH ANY QUESTIONS.
 52. APPLICANT SHALL BE REQUIRED TO MEET REQUIREMENTS OF
 ART IN PUBLIC PLACES. CONTACT SYBILLE WELTER AT
 [email protected] FOR MORE INFORMATION.
 53. PLEASE BE ADVISED, APPLICANTS ARE NOW REQUIRED TO
 PRESENT THEIR CASE TO THE BOARDS INCLUDING DAC AND
 INCLUDE RESPONSES TO CRITERIA FOR SPECIAL REVIEW,
 VARIANCES, ETC. STAFF WILL PROVIDE COMMENT FOR ITEMS
 NOT ADDRESSED BY THE APPLICANT. PRESENTATIONS ARE TO BE
 SUBMITTED TO STAFF THE MONDAY PRIOR TO THE DAC MEETING
 BY MEANS OF ELECTRONIC OR FLASH DRIVE DELIVERY.
  