Plan Review Details - Project Z19050019
Plan Review Stops For Project Z19050019
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 10-09-2019 Cont ID  
Sent By rbrown Date 10-09-2019 Time 12:39 Rev Time 0.00
Received By rbrown Date 10-09-2019 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 09-19-2019 Cont ID  
Sent By rbrown Date 09-19-2019 Time 19:36 Rev Time 0.00
Received By rbrown Date 09-19-2019 Time 19:36 Sent To  
Notes
2019-09-19 20:28:04DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS IS THE THIRD REVIEW. THE SUBMITTED LETTER
 RESPONSES TO THE PREVIOUS COMMENTS ARE NOTED. ALL
 INFORMATIONAL COMMENTS PROVIDED IN THE FIRST REVIEW
 STILL APPLY.
  
 2. LOCATION OF ACCESSIBLE PARKING SPACES. A SCANNED
 MARK UP OF THE SUGGESTED SOLUTION DESCRIBED BELOW CAN
 BE MADE AVAILABLE. ACCORDING TO THE ACTIVE USE
 DIAGRAMS, SHEET A0.06, AND EXISTING PARKING GARAGE
 PARKING COUNT, SHEET A0.11, ACCESS TO THE RESIDENTIAL
 OCCUPANCY WILL BE VIA THE HIBISCUS ST DOORS TO THE 1ST
 FLOOR LOBBY, OR VIA THE LEVEL 2 (PARKING LEVEL 3)
 BRIDGE FROM THE PARKING GARAGE. GIVEN THE CONVENIENCE
 AND WEATHER PROTECTION OFFERED BY THE LEVEL 2 (PARKING
 LEVEL 3) BRIDGE, AND THE TRAVEL DISTANCE FROM CAR TO
 RESIDENTIAL UNIT BEING SHORTER, AT LEAST 50% OF THE
 RESIDENTIAL SPACE OCCUPANTS WOULD BE EXPECTED TO USE
 THE BRIDGE TO GO FROM THE PARKING GARAGE TO THE NEW
 BUILDING. YET ONLY 29% (2 OUT OF 7) OF THE ACCESSIBLE
 PARKING SPACES REQUIRED BY FAIR HOUSING ACT ARE THE
 CLOSEST PARKING SPACES TO THE BRIDGE. AS STATED IN THE
 PREVIOUS REVIEW, THAT MEANS THAT SOME PEOPLE NEEDING
 ACCESSIBLE PARKING SPACES WILL BE TRAVELING FURTHER TO
 ACCESS THE BUILDING THAN PEOPLE WHO DO NOT NEED
 ACCESSIBLE PARKING SPACES. THEY WILL ALSO BE MORE
 EXPOSED TO THE ELEMENTS AND VEHICULAR TRAFFIC IF THEY
 TAKE THE ELEVATOR TO GROUND AND THEN CROSS THE STREET.
 CONSIDERING THE PROBABILITY THAT THE OCCUPANTS OF AT
 LEAST 50% OF THE RESIDENTIAL SPACE OCCUPANTS WILL
 ACCESS THE NEW BUILDING VIA THE LEVEL 2 BRIDGE, AT
 LEAST 4 OF THE 7 ACCESSIBLE PARKING SPACES REQUIRED BY
 FAIR HOUSING ACT SHOULD BE LOCATED AS THE CLOSEST
 PARKING SPACES TO THE BRIDGE ENTRANCE, BUT ONLY 2 ARE
 CURRENTLY SHOWN AS ACCESSIBLE.
 SUGGESTION: IF THE EXISTING SOUTH-EAST PARKING "END
 CAP" THAT IS CLOSEST TO THE BRIDGE WERE TO BE USED TO
 MOVE THE DRIVE LANES CLOSER TO THE CENTER OF THE
 PARKING GARAGE BUILDING, THAT MAY PROVIDE ENOUGH SPACE
 TO ADD TWO MORE ACCESSIBLE PARKING SPACES ALONG THE
 SOUTH WALL NEXT TO THE ONE ALREADY PROVIDED. THE
 WHEELCHAIR ACCESS AISLE COULD THEN BE AGAINST THE
 EXTERIOR WALL AND PROTECTED BY BOLLARDS/WHEEL STOPS.
 THE SUBJECT EXISTING SOUTH-EAST PARKING "END CAP" THAT
 IS CLOSEST TO THE BRIDGE IS PROBABLY JUST A PAINTED OUT
 AREA OF SLAB THAT COULD BE USED TO REALIGN THE DRIVE
 LANES. ALSO, THE ACCESSIBLE PARKING SPACE THAT IS
 ALREADY SHOWN COULD HAVE ITS ACCESS AISLE MOVED TO THE
 WEST SIDE OF THE PARKING SPACE SO THAT THE PARKING
 SPACE CAN BE MOVED TO THE EAST AND THE ACCESS AISLE
 SHARED WITH THE NEXT ACCESSIBLE PARKING SPACE THAT THIS
 SUGGESTION WOULD ADD. A SCANNED MARK UP OF THIS
 SUGGESTION HAS BEEN SENT TO ERIC SCHNEIDER BY EMAIL SO
 THAT HE CAN MAKE IT AVAILABLE TO YOU.
 PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE
 PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 08-21-2019 Cont ID  
Sent By rbrown Date 08-21-2019 Time 10:18 Rev Time 0.00
Received By rbrown Date 08-21-2019 Time 10:18 Sent To  
Notes
2019-08-21 10:57:17DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS IS THE SECOND REVIEW. THE SUBMITTED LETTER
 RESPONSE TO THE PREVIOUS COMMENTS IS NOTED. ALL
 INFORMATIONAL COMMENTS PROVIDED IN THE FIRST REVIEW
 STILL APPLY.
  
 2. LOCATION OF ACCESSIBLE PARKING SPACES. SITE AND
 PROJECT DATA SHEET A0.01 STATES THAT EXISTING SHARED
 PARKING WILL BE USED, AND A TOTAL OF 379 PARKING SPACES
 WILL BE PROVIDED, INCLUDING 9 ACCESSIBLE PARKING
 SPACES. BASED ON THE NUMBER OF PARKING SPACES FOR
 RESIDENTIAL USE, PER FAIR HOUSING ACT, 7 ACCESSIBLE
 PARKING SPACES MUST BE AVAILABLE FOR THE RESIDENTIAL
 OCCUPANCY. ACCORDING TO THE ACTIVE USE DIAGRAMS, SHEET
 A0.06, ACCESS TO THE RESIDENTIAL OCCUPANCY WILL BE VIA
 THE HIBISCUS ST DOORS TO THE 1ST FLOOR LOBBY, OR VIA
 THE LEVEL 2 BRIDGE FROM THE PARKING GARAGE. THEREFORE,
 THE 7 ACCESSIBLE SPACES REQUIRED BY THE FAIR HOUSING
 ACT SHOULD BE THE 7 CLOSEST PARKING SPACES TO THE
 HIBISCUS ST DOORS TO THE 1ST FLOOR LOBBY, AND THE LEVEL
 2 BRIDGE. GROUND LEVEL FLOOR PLAN, SHEET A1.01, AND 2ND
 LEVEL FLOOR PLAN, SHEET A1.02, SHOW 5 ACCESSIBLE
 PARKING SPACES AS THE CLOSEST TO THOSE ENTRANCES. THE
 REMAININING ACCESSIBLE PARKING SPACES SHOWN ON 3RD
 LEVEL THROUGH PENTHOUSE LEVEL FLOOR PLAN, SHEETS A1.03
 THROUGH A1.06, ARE FURTHER FROM THOSE TWO ENTRANCES
 THAN MANY OF THE REGULAR (NON-ACCESSIBLE) PARKING
 SPACES SHOWN ON GROUND LEVEL FLOOR PLAN, SHEET A1.01,
 AND 2ND LEVEL FLOOR PLAN, SHEET A1.02. THAT MEANS THAT
 SOME PEOPLE NEEDING ACCESSIBLE PARKING SPACES WILL BE
 TRAVELING FURTHER TO ACCESS THE BUILDING THAN SOME
 PEOPLE WHO DO NOT NEED ACCESSIBLE PARKING SPACES.
 CONSIDERING THE PROBABILITY THAT THE OCCUPANTS OF MORE
 THAN 100 OF THE CARS PARKED IN THE GARAGE FOR THE
 RESIDENTIAL OCCUPANCY WILL ACCESS THE BUILDING VIA THE
 LEVEL 2 BRIDGE, MORE THAN 2 ACCESSIBLE PARKING SPACES
 SHOULD BE LOCATED CLOSEST TO THE BRIDGE ENTRANCE, BUT
 ONLY 2 ARE CURRENTLY SHOWN. ALSO, GROUND LEVEL THROUGH
 PENTHOUSE LEVEL FLOOR PLAN, SHEETS A1.01 THROUGH A1.06,
 CURRENTLY SHOW A TOTAL OF 7 ACCESSIBLE PARKING SPACES,
 WHICH IS LESS THAN THE 9 REQUIRED ACCESSIBLE PARKING
 SPACES STATED ON SITE AND PROJECT DATA SHEET A0.01.
 PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE
 PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 06-11-2019 Cont ID  
Sent By rbrown Date 06-11-2019 Time 19:31 Rev Time 0.00
Received By rbrown Date 06-11-2019 Time 19:31 Sent To  
Notes
2019-06-11 19:42:15DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. LOCATION OF ACCESSIBLE PARKING SPACES. SITE AND
 PROJECT DATA SHEET A0.01 STATES THAT EXISTING SHARED
 PARKING WILL BE USED, BUT THE PLANS DO NOT SHOW THE
 EXISTING ACCESIBLE PARKING TO BE LOCATED CLOSEST TO THE
 ENTRANCES OF THE NEW BUILDING. PER SECTION 208.3 OF
 FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES
 ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE OF
 TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE.
 THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL COMPLY
 WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. EGRESS FROM LOBBY. GROUND LEVEL FLOOR PLAN SHEET
 A1.01 HAS A NOTE STATING THAT ONE EXIT IS REQUIRED FROM
 THE LOBBY. THE NOTE DOES NOT TAKE INTO ACCOUNT THE
 NUMBER OF PEOPLE THAT WILL BE DISCHARGED INTO THE LOBBY
 FROM STAIR 1. THE NOTE SHOULD BE CORRECTED.
  
 7. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 8. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 9. CONTRACTOR VEHICLE PARKING. PROPERTY OWNER AND
 CONTRACTOR SHALL MAKE ARRANGEMENTS FOR PARKING OF
 CONTRACTOR VEHICLES TO MINIMIZE THE IMPACT ON ALL
 NEIGHBORING PROPERTIES.
  
 10. PROTECTION OF NEIGHBORING PROPERTY. PROPERTY OWNER
 AND CONTRACTOR SHALL PROTECT ALL NEIGHBORING PROPERTY,
 INCLUDING VEHICLES, FROM DAMAGE OR DIRT CAUSED BY THE
 CONSTRUCTION, AND SHALL NOTIFY THE OCCUPANTS OF
 NEIGHBORING PROPERTIES ABOUT ALL STAGES OF CONSTRUCTION
 THAT MAY AFFECT THE USE OF THEIR PROPERTY.
  
 11. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 08-01-2019 Cont ID  
Sent By rrossano Date 08-01-2019 Time   Rev Time 0.00
Received By rrossano Date 08-01-2019 Time   Sent To  
Notes
2019-08-01 10:03:22A MEETING WAS HELD AT CITY OF WPB ENGINEERING
 DISCUSSING UTILITY DESIGN WITH MR. FITZGERALD OF KIMLEY
 HORN AND CITY ENGINEERING AND O&M PERSONNEL. THE PPRC
 SUBMITTAL Z19050019 IS PASSED WITH THE FOLLOWING
 PROVISOS AS CONDITIONS FOR THE FORMAL ENGINEERING
 SUBMITTAL:
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
  
 PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS.
  
 PER MARK HURLEY, CITY OF WPB PUBLIC UTILITIES FIELD
 CUSTOMER SERVICE SUPERVISOR:
  
 THE BACKFLOW PREVENTERS ARE NOT SHOWING ON SHEET C6.00;
 NOT SURE IF THEY ARE LABELED ON ANOTHER SHEET. ALL OF
 THE DOMESTIC/GENERAL CONTAINMENT BACKFLOW PREVENTERS
 NEED TO BE OUTSIDE, CANNOT BE LOCATED INSIDE BUILDING.
 TO FACILITATE THAT, THE METER VAULT/SERVICE MAY NEED TO
 MOVE A NUMBER OF FEET NORTH FROM CURRENT POSITION.THE 3
 INCH BACKFLOW PREVENTERS FOR THE 2 INCH METERS MAY ALSO
 BE A TIGHT FIT. EOR SHOULD VERIFY HOW HE WILL MAKE IT
 WORK.
  
 ADJUST NOTE FOR 6 INCH METER TO INCLUDE CITY OF WPB
 STANDARD DETAIL WS-6.1.
  
 ADJUST NOTE FOR 2 INCH METER TO REMOVE REFERENCE TO "3
 INCH WATER SERVICE", AND TO ADD STANDARD DETAIL NOTES
 WS-1 AND WS-7.
  
 IF FIRE MARSHAL REQUIRING DCDA IN BUILDING THEN
 BACKFLOW COVENANT SUBMISSION WOULD BE REQUIRED BY
 PROPERTY OWNERS BEFORE IT CAN PASS INSPECTION AS
 DISCUSSED IN MEETING.
  
 PLEASE NOTE THAT THE ADJACENT DROP-OFF ON HIBISCUS ST.
 WILL REQUIRE A FORMAL TRAFFIC ENGINEERING SUBMITTAL TO
 ADDRESS PEDESTRIAN SAFETY AND ADA CONCERNS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS,
 THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By rrossano Date 06-07-2019 Time   Rev Time 2.00
Received By rrossano Date 06-07-2019 Time   Sent To  
Notes
2019-06-07 07:20:10PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 PROVIDE ONSITE CLEANOUTS AT PROPERTY LINE FOR PROPOSED
 SANITARY LATERALS.
  
 PROVIDE UTILITY EASEMENTS TO ALLOW ACCESS FOR CITY
 PERSONNEL TO PROPOSED UTILITIES INCLUDING WATER METERS.
  
 DELINEATE CITY OF WPB UTILITY EASEMENTS AND/OR RIGHTS
 OF WAY. PLEASE BOLD THE 25' ACCESS & UTILITY EASEMENT
 ON SHEET C6.
  
 PROVIDE ENLARGED DETAIL ON PLANS OF PROPOSED LOCATION
 OF WATER METER AND BACKFLOW PREVENTION.
  
  
 THE FOLLOWING COMMENTS ARE FROM MARK HURLEY, FIELD
 CUSTOMER SERVICE SUPERVISOR, PUBLIC UTILITIES, CITY OF
 WEST PALM BEACH, 561-822-2262
  
 SHEET P1.01:
  
 -BACKFLOW PREVENTERS ARE LABELED AS INDOORS. SHOULD NOT
 BE INDOORS, SHOULD BE OUTSIDE CLOSE TO WATER SERVICE AS
 POSSIBLE ON PRIVATE PROPERTY OUTSIDE OF ROW/UE.
  
 -ALL OF THE BACKFLOW PREVENTERS ARE MARKED AS DOUBLE
 CHECK. THEY SHOULD BE RPZ.
  
 -VERTICAL INSTALLATION MAY NOT BE USC APPROVED OR
 MANUFACTURER APPROVED FOR THE ASSEMBLY THEY ARE
 INSTALLING. WOULD EITHER NEED FIND APPROVED-ASSEMBLY OR
 CHANGE INSTALLATION TO HORIZONTAL.
  
 -DID NOT SEE FIRELINE DCDAS ON PLAN? NOT SURE IF THEY
 ARE SHOWN ON THEIR UTILITY PLAN INSTEAD? I THINK THERE
 ARE SOME EXISTING ONES ON SITE.. THEY SHOULD PUT ON
 PLANS WITH THE EXISTING WATER SERVICES AND SHOW
 CONNECTION/DESIGN/ETC. IF THEY FORGOT TO DRAW THE DCDA,
 THEN THEY SHOULD RE-DRAW & LABEL. THEY CANNOT USE THE
 DOMESTIC WATER SERVICES FOR FIRE WATER USES SUCH AS
 FIRE SPRINKLERS.
  
 -FIELD CUSTOMER SERVICE RECOMMENDS CUSTOMERS INSTALL
 PARALLEL BACKFLOW PREVENTERS SO CUSTOMERS STILL HAVE
 WATER DURING BACKFLOW MAINTENANCE OR PROBLEMS.PLEASE
 SEE SINGLE INSTALLATION HERE, DON'T KNOW IF THEY
 CONSIDERED DOING THAT.
  
 -CAN'T TELL IF METER BOXES/VAULTS ARE IN GRASS AND
 WHERE PROPERTY LINE AND UES ARE FROM DRAWING. PREFER
 BOXES IN GRASS AND OUT OF SIDEWALKS.SHOULD BE IN
 UE/ROW/PARKWAY.
  
 SHEET C6.00:
  
 -METER BOXES AND VAULTS APPEAR TO BE IN SIDEWALK.
 THAT'S A SAFETY HAZARD AND ALSO HAVE TO CLOSE SIDEWALK
 DURING METER MAINTENANCE. BOXES AND LIDS SHOULD BE
 LOCATED OUT OF SIDEWALKS. CUSTOMER NEEDS TO DEVELOP
 AREA PREFERABLY WITH GRASS BETWEEN SIDEWALKS AND
 BUILDING WHERE VAULTS AND METER BOXES CAN LIE AND WON'T
 BE WALKED ON IN REGULAR TRAFFIC PATHS. THEY CAN
 SET-BACK OR REDESIGN BUILDING FOOTPRINT IF NEEDED AND
 CREATE UTILITY EASEMENT.
  
 -ALL OF EXISTING UTILITIES NOT SHOWN. IN OUR BILLING
 SYSTEM I SEE EXISTING 3 IN. METER AND 8 IN. FIRELINE
 WITH DETECTOR METER.
  
 -8 IN. FIRELINE DCDA ARE PRETTY BIG. ON THE UTILITY
 DRAWING IT DOES NOT SHOW THE FOOTPRINT AND EXACT
 LOCATION OF PROP 8 IN. DCDA. CUSTOMER MAY HAVE
 DIFFICULTY FITTING THERE. THIS MAY REQUIRE SPECIAL
 PROTECTION IF LOCATED ADJACENT OUTSIDE WALL BY FIRE
 DEPARTMENT.
  
 -CUSTOMER PROPERTY LINE NOT SHOWING IN ALLEY -> NOT
 SURE IF PRIVATELY OWNED ROAD? -> UTILITY EASEMENT MAY
 NEED BE ASSIGNED TO ALL THE WATER UTILITY MAIN,
 SERVICE, AND METERS BOXES.
  
 -STANDARD DETAILS REFERENCES NOT SHOWN AND LABELED BY
 CITY WPB WSD#
  
 -VAULT IS FAR FROM EXISTING CONNECTION -> ADDITIONAL
 WATER SERVICE PIPING BEFORE VAULT SHOULD BE MINIMIZED.
  
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 05-31-2019 Cont ID  
Sent By pleduc Date 05-31-2019 Time   Rev Time 0.00
Received By pleduc Date 05-31-2019 Time 12:33 Sent To  
Notes
2019-05-31 12:35:11THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 THE LOCATION OF THE DDCV COULD NOT BE IDENTIFIED OF
 SHEET F 1.01. THE LOCATION OF THE DDCV SHALL BE CLOSELY
 COORDINATED WITH THE OFFICE OF THE FIRE MARSHAL,
 ENGINEERING, ZONING AND THE LANDSCAPE PLANNER.
  
 PER NFPA 14 SECTION 7.12.2, HIGH-RISE BUILDINGS SHALL
 HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT
 CONNECTIONS FOR EACH ZONE.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 8. A CLASS A NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTERS
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDCS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDCS SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 TWO (2) SEPARATE FDCS ARE REQUESTED FOR THIS HIGH RISE,
 SEPARATE FROM EACH OTHER, FOR EFFECTIVE AND EFFICIENT
 FIREGROUND OPERATIONS. THE LOCATION SHOULD BE
 COORDINATED THROUGH THE OFFICE OF THE FIRE MARSHAL.
  
 12. COMMAND ROOM
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
  
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 13. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
  
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
  
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
  
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
  
 16. FOR BUILDING PLAN REVIEWDICUSSION PURPOSES THE
 STAIRWAY EXIT DISCHARGE LOCATED AT THE CENTER OF THE
 BUILDING THROUGH THE ASSEMBLY SEATING AREA REMAINS A
 CONCERN. THE CODE WILL ALLOW THE EXIT THROUGH CERTAIN
 AREAS; HOWEVER, THE ASSEMBLY SEATING AREA DOES NOT
 APPEAR TO BE ONE OF THOSE AREAS.
  
 7.1.3.2.2 AN EXIT ENCLOSURE SHALL PROVIDE A CONTINUOUS
 PROTECTED
 PATH OF TRAVEL TO AN EXIT DISCHARGE.
  
 3.3.85 EXIT DISCHARGE. THAT PORTION OF A MEANS OF
 EGRESS BETWEEN
 THE TERMINATION OF AN EXIT AND A PUBLIC WAY.
  
 7.7 DISCHARGE FROM EXITS.
  
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT
 DISCHARGE SHALL BE OF THE REQUIRED WIDTH AND SIZE TO
 PROVIDE ALL
 OCCUPANTS WITH A SAFE ACCESS TO A PUBLIC WAY.
  
 A 5' AREA IS INDICATED ALONG THE WALL; HOWEVER, HOW
 WILL THIS AREA BE MAINTAINED/SEPARATED FOR THE SEATING.
 WHAT IS TO STOP ANYONE FROM MOVING TABLE AND CHAIRS
 INTO THIS EXT TRAVEL PATH?
  
 THE PPRC PLAN WILL BE APPROVED AND THIS AREA CAN BE
 ADDRESSED WITH BUILDING PLAN SUBMITTALS.
  
 17) THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 18). THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 10-22-2019 Cont ID  
Sent By rcaranci Date 10-22-2019 Time 09:31 Rev Time 0.00
Received By rcaranci Date 10-22-2019 Time 09:31 Sent To  
Notes
2019-10-22 09:31:54FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 575 ROSEMARY (MACY?S) Z19050019
 OCTOBER 15, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE WASHINGTONIA PALMS ARE CATEGORY 4,
 CANOPY VALUE IS 50 SQ FT.
 ? SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE OF
 MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED STREETSCAPE TREES AND PALMS. SEE
 BELOW.
  
 2. SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 COCONUT PALMS AND DATE PALMS MAY BE USED, BUT NOT AS
 COUNTING TOWARD THE TREE REQUIREMENT AT THE MAXIMUM 30
 FOOT SPACING. THERE ARE ALSO CONFLICTS WITH PROPOSED
 AWNING AND STREET TREES.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
 4. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. SUBMIT THE REASON THE TWO EXISTING LIVE OAK
 TREES CANNOT BE RELOCATED OR USED IN THE PROPOSED
 STREETSCAPE.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
  
 5. SATISFIED. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN
 ON SHEET A0.05 MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA. PASSAGEWAY LESS THAN 7500 SQ FT REQUIRE ZERO ANY
 OF EITHER. TERRACE REQUIRES 20% MINIMUM VEGETATED AREA.
 ROOFTOP GARDEN REQUIRES 30% VEGETATED AREA AND 20% TREE
 CANOPY. TREE CANOPY VALUES CAN BE FOUND IN SECTION
 94-109 TABLE IV-8.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 3 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
  
 7. SATISFIED. ADD COLUMNS FOR NATIVE PLANTS AND DROUGHT
 TOLERANCE/ WATER USAGE TO THE PLANT LIST SO THAT
 FLORIDA FRIENDLY POINTS CAN BE SUBSTANTIATED.
  
 8. SATISFIED. TRA IS MISSING FROM THE PLANT LIST.
  
 9. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
 BIOBARRIER IS NOT ACCEPTABLE AS ROOT BARRIER, MUST BE
 HARD PLASTIC ROOT BARRIER DEEP ROOT OR SIMILAR.
 SOME ROOT BARRIER LOCATIONS SHOWN ARE NOT APPROPRIATE,
 AS THEY SEPARATE THE ROOTS FROM REQUIRED SOIL AREAS.
 PROVIDE A ROOT BARRIER DETAIL.
  
 10. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
  
 ADDITIONAL COMMENTS 8/16/19:
  
 11. SATISFIED. PROVIDE THE 50 POINTS REQUIRED FROM THE
 FLORIDA FRIENDLY DESIGN OPTIONS FOUND IN SECTION
 94-443(G).
  
 12. SATISFIED. PER RESOLUTION NO. 304-18 UNDER 2.
 CITYPLACE CENTER B., FOUR FICUS TREES WITHIN THE PAVED
 AREAS NEED TO BE SHOWN WITH SUSPENDED PAVEMENT SYSTEM
 FOR THE ROOT ZONES OF THE TREES. PROVIDE THE LOCATIONS
 AND DETAIL FOR THE SYSTEM.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 09-18-2019 Cont ID  
Sent By rcaranci Date 09-18-2019 Time 17:21 Rev Time 0.00
Received By rcaranci Date 09-18-2019 Time 17:21 Sent To  
Notes
2019-09-18 17:22:08FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 575 ROSEMARY (MACY?S) Z19050019
 SEPTEMBER 18, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE WASHINGTONIA PALMS ARE CATEGORY 4,
 CANOPY VALUE IS 50 SQ FT.
 ? PARTIALLY SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE
 OF MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 OAKS ON GARDENIA NEED TO BE INCLUDED, AS THEY ARE IN
 THE AREA OF STREETSCAPE REQUIRED TO BE INCLUDED WITH
 THIS SITE.
 ? SATISFIED. PROVIDE THE MITIGATION VALUES BY CATEGORY
 FOR THE PROPOSED STREETSCAPE TREES AND PALMS.
  
 2. PARTIALLY SATISFIED. THE STREETSCAPE CAN BE IMPROVED
 TO ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113.
 THE COCONUT PALMS AND DATE PALMS MAY BE USED, BUT NOT
 AS COUNTING TOWARD THE TREE REQUIREMENT AT THE MAXIMUM
 30 FOOT SPACING. THERE ARE ALSO CONFLICTS WITH PROPOSED
 AWNING AND STREET TREES.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
 A COURTESY REVIEW WAS CONDUCTED ON THE PLAN COPY
 DELIVERED BY THE APPLICANT. A FORMAL SUBMITTAL WITH THE
 PLANS INCORPORATED INTO THE LANDSCAPE PLAN FOR THIS
 SITE IS REQUIRED FOR APPROVAL. AREAS OF STRUCTURAL SOIL
 MUST BE SHOWN ON ROSEMARY SECTION.
  
 3. SATISFIED. REQUIRED STREET TREES MUST MEET THE 20
 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST OVERALL
 HEIGHT ON PLANT LIST.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
 4. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. SUBMIT THE REASON THE TWO EXISTING LIVE OAK
 TREES CANNOT BE RELOCATED OR USED IN THE PROPOSED
 STREETSCAPE.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
  
 5. PARTIALLY SATISFIED. PUBLIC AND PRIVATE OPEN SPACE
 AREAS SHOWN ON SHEET A0.05 MUST BE BROKEN DOWN TO SHOW
 THE REQUIRED VEGETATED AREA AND ANY TREE CANOPY
 REQUIREMENT FOR EACH AREA. PASSAGEWAY LESS THAN 7500 SQ
 FT REQUIRE ZERO ANY OF EITHER. TERRACE REQUIRES 20%
 MINIMUM VEGETATED AREA. ROOFTOP GARDEN REQUIRES 30%
 VEGETATED AREA AND 20% TREE CANOPY. TREE CANOPY VALUES
 CAN BE FOUND IN SECTION 94-109 TABLE IV-8.
 AREAS SHOWN MUST MEET THE DEFINITION FOR THE OPEN SPACE
 TYPE IF THEY ARE TO BE COUNTED TOWARD REQUIRED OPEN
 SPACE. ZONING COMMENTS WILL INCLUDE DETAILS.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 3 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
  
 7. SATISFIED. ADD COLUMNS FOR NATIVE PLANTS AND DROUGHT
 TOLERANCE/ WATER USAGE TO THE PLANT LIST SO THAT
 FLORIDA FRIENDLY POINTS CAN BE SUBSTANTIATED.
  
 8. SATISFIED. TRA IS MISSING FROM THE PLANT LIST.
  
 9. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES.
 BIOBARRIER IS NOT ACCEPTABLE AS ROOT BARRIER, MUST BE
 HARD PLASTIC ROOT BARRIER DEEP ROOT OR SIMILAR.
 SOME ROOT BARRIER LOCATIONS SHOWN ARE NOT APPROPRIATE,
 AS THEY SEPARATE THE ROOTS FROM REQUIRED SOIL AREAS.
 PROVIDE A ROOT BARRIER DETAIL.
  
 10. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
  
 ADDITIONAL COMMENTS 8/16/19:
  
 11. SATISFIED. PROVIDE THE 50 POINTS REQUIRED FROM THE
 FLORIDA FRIENDLY DESIGN OPTIONS FOUND IN SECTION
 94-443(G).
  
 12. SATISFIED. PER RESOLUTION NO. 304-18 UNDER 2.
 CITYPLACE CENTER B., FOUR FICUS TREES WITHIN THE PAVED
 AREAS NEED TO BE SHOWN WITH SUSPENDED PAVEMENT SYSTEM
 FOR THE ROOT ZONES OF THE TREES. PROVIDE THE LOCATIONS
 AND DETAIL FOR THE SYSTEM.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 08-16-2019 Cont ID  
Sent By rcaranci Date 08-16-2019 Time 14:31 Rev Time 0.00
Received By rcaranci Date 08-16-2019 Time 14:31 Sent To  
Notes
2019-08-16 14:31:49FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 575 ROSEMARY (MACY?S) Z19050019
 AUGUST 16, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? SATISFIED. THE WASHINGTONIA PALMS ARE CATEGORY 4,
 CANOPY VALUE IS 50 SQ FT.
 ? PARTIALLY SATISFIED. PROVIDE THE TOTAL SQUARE FOOTAGE
 OF MITIGATION FOR ALL TREES AND PALMS PROPOSED TO BE
 REMOVED.
 ? PARTIALLY SATISFIED. PROVIDE THE MITIGATION VALUES BY
 CATEGORY FOR THE PROPOSED STREETSCAPE TREES AND PALMS.
 SEE BELOW.
  
 2. NOT SATISFIED. THE STREETSCAPE CAN BE IMPROVED TO
 ACCOMPLISH THE INTENT OF THE CODE SECTION 94-113. THE
 COCONUT PALMS AND DATE PALMS MAY BE USED, BUT NOT AS
 COUNTING TOWARD THE TREE REQUIREMENT AT THE MAXIMUM 30
 FOOT SPACING. THERE ARE ALSO CONFLICTS WITH PROPOSED
 AWNING AND STREET TREES.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
 3. NOT SATISFIED. REQUIRED STREET TREES MUST MEET THE
 20 FOOT HEIGHT REQUIREMENT AT INSTALLATION. LIST
 OVERALL HEIGHT ON PLANT LIST.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
 4. NOT SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. SUBMIT THE REASON THE TWO EXISTING LIVE OAK
 TREES CANNOT BE RELOCATED OR USED IN THE PROPOSED
 STREETSCAPE.
 PLANNING STAFF HAS NOT REVIEWED OR APPROVED THE
 STREETSCAPE PLANS FOR THE AREAS ADJACENT TO THIS
 PROJECT. PROVIDE THE 100% PLANS FOR REVIEW.
  
  
 5. SATISFIED. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN
 ON SHEET A0.05 MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA. PASSAGEWAY LESS THAN 7500 SQ FT REQUIRE ZERO ANY
 OF EITHER. TERRACE REQUIRES 20% MINIMUM VEGETATED AREA.
 ROOFTOP GARDEN REQUIRES 30% VEGETATED AREA AND 20% TREE
 CANOPY. TREE CANOPY VALUES CAN BE FOUND IN SECTION
 94-109 TABLE IV-8.
  
 6. SATISFIED. AREA LISTED AS POOL DECK ON LEVEL 3 IS
 NOT AN OPEN SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE
 OPEN SPACE TYPE (ROOFTOP GARDEN?) AND SHOW
 REQUIREMENTS.
  
 7. SATISFIED. ADD COLUMNS FOR NATIVE PLANTS AND DROUGHT
 TOLERANCE/ WATER USAGE TO THE PLANT LIST SO THAT
 FLORIDA FRIENDLY POINTS CAN BE SUBSTANTIATED.
  
 8. SATISFIED. TRA IS MISSING FROM THE PLANT LIST.
  
 9. PARTIALLY SATISFIED. SHOW LOCATIONS OF ANY ROOT
 BARRIERS REQUIRED TO PROTECT UTILITY LINES.
 BIOBARRIER IS NOT ACCEPTABLE AS ROOT BARRIER, MUST BE
 HARD PLASTIC ROOT BARRIER DEEP ROOT OR SIMILAR.
 SOME ROOT BARRIER LOCATIONS SHOWN ARE NOT APPROPRIATE,
 AS THEY SEPARATE THE ROOTS FROM REQUIRED SOIL AREAS.
 PROVIDE A ROOT BARRIER DETAIL.
  
 10. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445
 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
  
 ADDITIONAL COMMENTS 8/16/19:
  
 11. PROVIDE THE 50 POINTS REQUIRED FROM THE FLORIDA
 FRIENDLY DESIGN OPTIONS FOUND IN SECTION 94-443(G).
  
 12. PER RESOLUTION NO. 304-18 UNDER 2. CITYPLACE CENTER
 B., FOUR FICUS TREES WITHIN THE PAVED AREAS NEED TO BE
 SHOWN WITH SUSPENDED PAVEMENT SYSTEM FOR THE ROOT ZONES
 OF THE TREES. PROVIDE THE LOCATIONS AND DETAIL FOR THE
 SYSTEM.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By rcaranci Date 06-10-2019 Time 14:25 Rev Time 0.00
Received By rcaranci Date 06-10-2019 Time 14:25 Sent To  
Notes
2019-06-10 14:28:37FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 575 ROSEMARY (MACY?S) Z19050019
 JUNE 10, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. MAKE THE FOLLOWING CORRECTIONS TO THE TREE
 DISPOSITION PLAN:
 ? THE WASHINGTONIA PALMS ARE CATEGORY 4, CANOPY VALUE
 IS 50 SQ FT.
 ? PROVIDE THE TOTAL SQUARE FOOTAGE OF MITIGATION FOR
 ALL TREES AND PALMS PROPOSED TO BE REMOVED.
 ? PROVIDE THE MITIGATION VALUES BY CATEGORY FOR THE
 PROPOSED STREETSCAPE TREES AND PALMS.
  
 2. THE STREETSCAPE CAN BE IMPROVED TO ACCOMPLISH THE
 INTENT OF THE CODE SECTION 94-113. THE COCONUT PALMS
 AND DATE PALMS MAY BE USED, BUT NOT AS COUNTING TOWARD
 THE TREE REQUIREMENT AT THE MAXIMUM 30 FOOT SPACING.
 THERE ARE ALSO CONFLICTS WITH PROPOSED AWNING AND
 STREET TREES.
 3. REQUIRED STREET TREES MUST MEET THE 20 FOOT HEIGHT
 REQUIREMENT AT INSTALLATION. LIST OVERALL HEIGHT ON
 PLANT LIST.
  
 4. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD
 CONDITION TO BE PRESERVED ON SITE OR RELOCATED. SUBMIT
 THE REASON THE TWO EXISTING LIVE OAK TREES CANNOT BE
 RELOCATED OR USED IN THE PROPOSED STREETSCAPE.
  
 5. PUBLIC AND PRIVATE OPEN SPACE AREAS SHOWN ON SHEET
 A0.05 MUST BE BROKEN DOWN TO SHOW THE REQUIRED
 VEGETATED AREA AND ANY TREE CANOPY REQUIREMENT FOR EACH
 AREA. PASSAGEWAY LESS THAN 7500 SQ FT REQUIRE ZERO ANY
 OF EITHER. TERRACE REQUIRES 20% MINIMUM VEGETATED AREA.
 ROOFTOP GARDEN REQUIRES 30% VEGETATED AREA AND 20% TREE
 CANOPY. TREE CANOPY VALUES CAN BE FOUND IN SECTION
 94-109 TABLE IV-8.
  
 6. AREA LISTED AS POOL DECK ON LEVEL 3 IS NOT AN OPEN
 SPACE TYPE. CLASSIFY AS A PERMITTED PRIVATE OPEN SPACE
 TYPE (ROOFTOP GARDEN?) AND SHOW REQUIREMENTS.
  
 7. ADD COLUMNS FOR NATIVE PLANTS AND DROUGHT TOLERANCE/
 WATER USAGE TO THE PLANT LIST SO THAT FLORIDA FRIENDLY
 POINTS CAN BE SUBSTANTIATED.
  
 8. TRA IS MISSING FROM THE PLANT LIST.
  
 9. SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO
 PROTECT UTILITY LINES.
  
 10. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
 PROVIDE THE ACTUAL PERCENTAGE OF DROUGHT TOLERANT AND
 NATIVE SPECIES ADDED BASED ON THE PROPOSED PLANT LIST.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status P Date 08-20-2019 Cont ID  
Sent By   Date 08-20-2019 Time   Rev Time 0.00
Received By   Date 08-20-2019 Time   Sent To  
Notes
2019-08-20 08:29:48PUBLIC WORKS HAS NO FURTHER COMMENTS.
  
 MATT HEJAZI
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-04-2019 Cont ID  
Sent By   Date 06-11-2019 Time   Rev Time  
Received By   Date 06-11-2019 Time   Sent To  
Notes
2019-06-11 08:35:39PLEASE PROVIDE THE FOLLOWINGS:
 - LOS (LEVEL OF SERVICE ANALYSIS) TO REFLECT THE SOLID
 WASTE VOLUME PRODUCED ALONG WITH THE SIZE OF THE
 COMPACTOR THAT WILL BE UTILIZED.
 - AUTO TURN FOR THE SANITATION SERVICE
 - CONTINGENCY PLAN, FOR WHEN THE COMPACTOR IS OUT OF
 SERVICE (I.E. CITY DUMPSTER, ROLL-OFF CONTAINER)
 - DESIGNATED LOCATION FOR THE BULK ITEM PICK UP
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 4 Status P Date 10-30-2019 Cont ID  
Sent By tward Date 10-30-2019 Time 15:43 Rev Time 0.00
Received By tward Date 10-30-2019 Time 16:14 Sent To  
Notes
2019-10-30 16:04:13THE PROPOSED DRAINAGE DESIGN IN THE OCTOBER 4, 2019
 SUBMITTAL PACKAGE SHOWS THE STORMWATER RUNOFF FROM THE
 SIDEWALK AND ROOF DRAINS DIRECTED TO ONSITE
 EXFILTRATION TRENCHES WITH NO DIRECT CONNECTION TO THE
 DRAINAGE SYSTEM IN THE PUBLIC RIGHT-OF-WAY. NO DRAINAGE
 CALCULATION HAVE BEEN SUBMITTED TO INDICATE THE AMOUNT
 OF RUNOFF THE EXFILTRATION TRENCHES CAN HANDLE. THE EOR
 MAY HAVE SAID THE 5-YEAR 24-HOUR STORM COULD BE HANDLED
 BY THE SYSTEM.
  
 UNLESS THE EXFILTRATION TRENCHES ARE PERIODICALLY
 MAINTAINED, THE STORAGE AND DISPOSAL CAPACITY OF THIS
 DRAINAGE SYSTEM WILL DIMINISH OVERTIME. IT WILL TAKE
 LONGER FOR THE STORED WATER TO FLOW OUT OF THE SLOTTED
 PIPE AND INTO THE GROUND TO GROUNDWATER. EVENTUALLY,
 THE TRENCHES ALONG THE PERIMETER OF THE SITE FOR
 CAPTURING THE SIDEWALK STORMWATER RUNOFF WILL NO LONG
 PERFORM THIS FUNCTION BECAUSE THE SYSTEM WILL BE FULL.
 THE OPPOSITE WILL LIKELY OCCUR IN THAT ROOF RUNOFF WILL
 BACKFLOW THROUGH THE PERIMETER TRENCHES AND FLOW ON THE
 SIDEWALK TO THE GUTTER IN THE R/W. SUFFICIENT HEAD
 PRESSURE COULD OCCUR IN THE DRAINAGE SYSTEM FROM THE
 ROOF DRAINS TO FORCE OPEN THE MANHOLES LIDS AND
 MINI-FOUNTAINS ERUPT WITH WATER SPILLING OUT ONTO THE
 SIDEWALK. BY THIS TIME THE EXFILTRATION TRENCHES WILL
 NEED TO BE DUG UP AND REPLACED WITH CLEAN STONE/ROCKS.
  
 DUE TO THE DEVELOPER'S AGREEMENT FOR CAPTURING THE
 STORMWATER RUNOFF, THE CITY COULD ADD AS A CONDITION OF
 APPROVAL THAT THE ONSITE DRAINAGE SYSTEM BE INSPECTED
 AND CERTIFIED ANNUALLY BY A FL P.E. THAT THE DRAINAGE
 SYSTEM IS PERFORMING AS ORIGINALLY DESIGNED.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 09-11-2019 Cont ID  
Sent By tward Date 09-11-2019 Time 17:14 Rev Time 0.00
Received By tward Date 09-11-2019 Time 17:40 Sent To  
Notes
2019-09-11 17:35:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 SEPTEMBER 9, 2019 SUBMITTAL REVIEW PACKAGE:
  
 1. SHEET C0.02 - SURVEY DATA NOTE 1 STATES ELEVATIONS
 ON THE PLANS ARE BASED ON NGVD1929. A NOTE IN THE
 BOTTOM RIGHT OF THE SHEET STATES ALL ELEVATIONS SHOWN
 ON THE PLANS ARE BASED ON NAVD1988.
  
 2. SHEET C8.00 - SHOW R/W LINE ON SECTION H-H
  
 3. SHEET C8.01:
 A. SHOW R/W LINE ON THE SECTIONS.
 B. SECTION I-I - SLOT DRAIN NOT SHOWN.
 C. SECTION L-L - WHAT IS THE 8 FOOT AREA NEXT TO THE
 SIDEWALK? NOTE THE PLAN VIEW DOES NOT SHOW THE SLOT
 DRAIN IN THE 8 FOOT AREA.
  
 4. PROVIDE DETAIL OF THE SLOT DRAIN.
  
 5. INDICATE HOW ONSITE EXFILTRATION TRENCH DRAINS WILL
 BE DESIGNED/SIZED.
  
 6. PROVIDE A COPY OF THE STREETSCAPE PLANS (PERMIT NO.
 19031272) FOR THE PROPOSED PLANTING ALONG S. ROSEMARY
 AVE. AND HIBISCUS STREET.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 08-19-2019 Cont ID  
Sent By tward Date 08-19-2019 Time 10:51 Rev Time 0.00
Received By tward Date 08-19-2019 Time 11:04 Sent To  
Notes
2019-08-19 11:04:25THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JULY
 30, 2019 SUBMITTAL PACKAGE.
  
 1. IT APPEARS ONLY ROOF DRAINS AND CONDENSATE LINES ARE
 CONNECTED TO THE EXFILTRATION SYSTEMS. SINCE ALL ROOF
 DRAINAGE IS TO BE CAPTURED AND RETAINED ONSITE, WEIRS
 AND OUTFALL PIPES WILL NOT BE NECESSARY TO CONNECT TO
 THE OFFSITE DRAINAGE SYSTEMS. [REPEAT COMMENT]
  
 2. GRADING INFORMATION PROVIDED FOR THE DROPOFF AREA ON
 WEST STREET APPEARS TO SHOW A LOW SPOT ELEVATION OF
 20.13. IS THIS AREA DESIGNED TO HOLD WATER INSTEAD OF
 DRAINAGE TO AN INLET?
  
 3. PREVIOUS COMMENT REGARDING TREES PROPOSED OVER THE
 EXISTING DRAINAGE SYSTEM ON S. ROSEMARY AVE. WAS
 APPARENTLY ADDRESSED BY CROSS HATCHING THE AREA ON THE
 LANDSCAPE PLANS AND INDICATING THE AREA WAS APPROVED BY
 CITY COUNCIL (SIC) AS PART OF FACE OF THE CITY
 RESOLUTION.
  
 4. ON SHEET LH-03 ARE TWO SAND SET PAVER DETAILS.
 PLEASE INDICATE ON SHEET LH-01 WHERE EACH DETAIL
 APPLIES.
  
 5. INDICATE ON THE PGD PLAN HOW STORMWATER RUNOFF FROM
 THE PERIMETER SIDEWALK AREAS WILL BE CAPTURED ONSITE.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By tward Date 06-10-2019 Time 18:25 Rev Time 0.00
Received By tward Date 06-10-2019 Time 18:27 Sent To  
Notes
2019-06-10 18:27:23THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. CONFIRM EXISTING STORM PIPE WEST STREET (ALLEY) IS
 15? RCP. THE DRAINAGE AS-BUILTS FOR CITY PLACE PHASE I
 SHOWS 30? RCP.
  
 2. IT APPEARS ONLY ROOF DRAINS AND CONDENSATE LINES ARE
 CONNECTED TO THE EXFILTRATION SYSTEMS. SINCE ALL ROOF
 DRAINAGE IS TO BE CAPTURED AND RETAINED ONSITE, WEIRS
 AND OUTFALL PIPES WILL NOT BE NECESSARY TO CONNECT TO
 THE OFFSITE DRAINAGE SYSTEMS.
  
 3. INDICATE HOW THE ROOF DRAINAGE CONVEYED BY ROOF
 LEADERS AT THE NORTHEAST AND SOUTHEAST CORNERS OF THE
 BUILDING WILL BE RETAINED ONSITE.
  
 4. HOW WILL DRAINAGE AT THE LOADING DOCK BE HANDLED?
  
 5. INSUFFICIENT GRADING INFORMATION PROVIDED FOR THE
 DROPOFF AREA ON WEST STREET. PROVIDE GRADES AND A CROSS
 SECTION FOR THIS AREA.
  
 6. TREES PROPOSED OVER THE EXISTING DRAINAGE SYSTEM ON
 S. ROSEMARY AVE.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION PRIOR
 TO STARTING CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 08-19-2019 Cont ID  
Sent By vnoel Date 08-19-2019 Time 09:13 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-08-19 09:16:55PASSED WITH CONDITIONS:
  
 1. REVIEW OF MAINTENANCE AGREEMENT CONCERNING LIABILITY
 OF UTILITIES IN SIDEWALKS.
 2. APPROVAL BY MARK HURLEY, CUSTOMER SERVICE.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By vnoel Date 06-10-2019 Time 12:58 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2019-06-10 13:37:061. MARK HURLEY WITH CUSTOMER SERVICE (METER SHOP) WILL
 NEED TO REVIEW THE PROPOSED VERTICAL STACKS AND METER
 LOCATIONS.
 2. NEED TO REVIEW THE 6 NEW STORM MANHOLES TO BE WITHIN
 THE SIDEWALK AREA. MAY NEED TO RE-VISIT ANY MAINTENANCE
 AGREEMENTS.
 3. SHOULD DOORWAYS BE OPENING INTO SIDEWALK EASEMENTS?
 4. SURVEY IS APPROVED AS SUBMITTED.
 5. OUTDOOR SEATING WITHIN SIDEWALK EASEMENTS MAY
 REQUIRE SIDEWALK CAFE' PERMIT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 10-15-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-10-15 16:11:33PASSED WITH THE FOLLOWING CONDITIONS:
 CONDITIONS:
 1. THE DEVELOPER SHALL CONDUCT AN EVALUATION AT THE
 INTERSECTION AT THE SOUTHWEST CORNER OF THE SITE FOR
 REMOVAL OF THE EXISTING ALL-WAY STOP AND SHALL CONVERT
 TO TWO-WAY STOP IF AN ALL-WAY STOP IS NOT WARRANTED,
 ONE YEAR AFTER THE FOLLOWING CONDITIONS ARE MET:
 A. CO IS ISSUED FOR AT LEAST 50% OF THE PROPOSED
 APARTMENT, OFFICE USE, OR RETAIL USES.
 B. CO IS ISSUED FOR AT LEAST 85% OF THE PROPOSED
 APARTMENT, OFFICE USE, OR RETAIL USES.
 C. THE LAST CO IS ISSUED FOR THE PROPOSED DEVELOPMENT.
 2. THE EVALUATION SHALL INCLUDE ANALYSES OF TRAFFIC
 VOLUMES, SAFETY DATA AND SIGHT DISTANCES AND SHALL BE
 COMPLETED BY A LICENSED ENGINEER. THE NECESSARY TRAFFIC
 AND SAFETY DATA SHALL BE COLLECTED BY THE DEVELOPER FOR
 THE ANALYSES.
 3. PROVIDE SURETY FOR THE TRAFFIC EVALUATION AND
 REMOVAL OF THE ALL-WAY STOP UNTIL THE OBLIGATIONS
 RELATED TO THE TWO-WAY STOP CONVERSION ANALYSES OR
 CONSTRUCTION (#1 AND #2 ABOVE) ARE FULLY MET.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 09-18-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-09-18 09:27:58TRAFFIC STUDY COMMENTS:
 1. THE CALCULATION FOR THE TRIP GENERATION WAS
 SUBSTANTIALLY DIFFERENT THAN IN THE PREVIOUS SUBMITTAL,
 AND SOME OF THE PREVIOUSLY CORRECT CALCULATIONS WERE
 INCORRECT IN THE LATEST SUBMITTAL. FOR EXAMPLE, THE
 PASS-BY TRIP PERCENTAGE FOR THE EXISTING MACY'S RETAIL
 WAS PREVIOUSLY CORRECT AT 39%, BUT AN INCORRECT
 PERCENTAGE OF 10% WAS USED IN THE LATEST SUBMITTAL; THE
 MULTIMODAL TRIPS AND PASS-BY TRIPS SHOULD BE APPLIED TO
 THE ADJUSTED TRIPS CALCULATED IMMEDIATELY PRIOR THESE
 TRIP REDUCTIONS. PLEASE REVIEW AND REVISE.
 2. (PREVIOUS COMMENT) IN THE SYNCHRO ANALYSIS AT
 OKEECHOBEE BOULEVARD/TAMARIND AVENUE, ADD WBU VOLUMES
 ONTO WBL VOLUMES AND REMOVE WBU SINCE U-TURN CAUSES
 ISSUES WITH HCM 2000 ANALYSIS IN SYNCHRO, WHICH RESULT
 IN UNREALISTIC DELAYS. APPROPRIATE SIGNAL TIMING SHOULD
 BE USED. ALSO, PLEASE ASSUME 2 NORTHBOUND LANES WHICH
 IS A COMMITTED OFF-SITE IMPROVEMENT FROM THE KRAVIS
 CENTER DEVELOPMENT IN THE FUTURE YEAR ANALYSES.
 SITE PLAN COMMENTS:
 1. PLEASE CONSIDER HAVING THE RESIDENTIAL VALET PICK-UP
 ON THE OPPOSITE SIDE OF HIBISCUS STREET TO REDUCE
 ADDITIONAL TRAFFIC ON ROSEMARY.
 2. PLEASE CONSIDER HAVING THE OFFICE VALET DROP-OFF
 VEHICLES TO TURN AROUND IN THE ALLEY TO REDUCE
 ADDITIONAL TRAFFIC ON ROSEMARY.
 CONDITIONS:
 1. PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY, EVALUATE AND REMOVE ALL-WAY STOP AND CONVERT
 TO TWO-WAY STOP AT THE SOUTHWEST CORNER OF THE SITE IF
 ALL-WAY STOP IS NOT WARRANTED.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 08-14-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-08-14 15:19:01TRAFFIC STUDY COMMENTS:
 1. THE TRAFFIC STUDY SHOULD BE THOROUGHLY CHECKED BY
 THE PE TO MAKE SURE THE TRAFFIC ANALYSIS IS COMPLETED
 CORRECTLY AND PROPERLY REFLECTS THE EXPECTED TRAFFIC
 CONDITIONS.
 2. CLARIFY IF THE PROJECT TRIPS INCLUDE CIRCULATION DUE
 TO VALET VEHICLES, AND HOW MANY (OR PERCENTAGE OF)
 VALET VEHICLES ARE EXPECTED. IF NOT, PLEASE INCLUDE
 VALET VEHICLES IN PROJECT TRIP CALCULATIONS. ALL VALET
 VEHICLES BOUND FOR PICK-UP WOULD NEED TO CIRCULATE
 AROUND THE BLOCK USING FERN STREET, ROSEMARY AVENUE AND
 HIBISCUS STREET AND DEPART FROM SAPODILLA
 AVENUE/HIBISCUS STREET. ALL VALET VEHICLES BOUND FOR
 DROP-OFF WOULD NEED TO ACCESS THE VALET AREA FROM
 ROSEMARY AVENUE/HIBISCUS STREET.
 3. THE TRIP GENERATION RATE FOR LAND USE CODE 710
 OFFICE SHOULD BE BASED ON GROSS FLOOR AREA. THE SITE
 PLAN SHOWS A GFA OF 56,928 SF BUT 51,250 SF IS USED IN
 THE TRIP GENERATION ANALYSIS. PLEASE REVISE.
 4. THE TRIP GENERATION RATE FOR LAND USE CODE 820
 SHOPPING CENTER SHOULD BE BASED ON GROSS LEASABLE AREA.
 PLEASE VERIFY AND REVISE.
 5. TRIP GENERATION CALCULATIONS FOR SOME OF THE LAND
 USES DO NOT APPEAR TO BE CONSISTENT, E.G. THE APARTMENT
 LAND USE DURING PM PEAK HOUR. ALSO, THE PASS-BY
 PERCENTAGE FOR SHOPPING CENTER DEPENDS ON THE INTENSITY
 AND SHOULD BE VERIFIED IF THE INTENSITY IS CHANGED.
 6. IN THE INTERNAL TRIP CALCULATION, PLEASE CLARIFY THE
 SOURCE OF THE 12% UNCONSTRAINED INTERNAL TRIP CAPTURE
 RATE BETWEEN EACH INDIVIDUAL USE. ITE TRIP GENERATION
 HANDBACK 3RD EDITION SUGGESTS DIFFERENT PERCENTAGES.
 7. IN THE SYNCHRO ANALYSIS AT OKEECHOBEE
 BOULEVARD/TAMARIND AVENUE, ADD WBU VOLUMES ONTO WBL
 VOLUMES AND REMOVE WBU SINCE U-TURN CAUSES ISSUES WITH
 HCM 2000 ANALYSIS IN SYNCHRO, WHICH RESULT IN
 UNREALISTIC DELAYS. APPROPRIATE SIGNAL TIMING SHOULD BE
 USED. ALSO, PLEASE ASSUME 2 NORTHBOUND LANES WHICH IS A
 COMMITTED OFF-SITE IMPROVEMENT FROM THE KRAVIS CENTER
 DEVELOPMENT IN THE FUTURE YEAR ANALYSIS.
  
 CONDITIONS:
 1. PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY, EVALUATE AND REMOVE ALL-WAY STOP AND CONVERT
 TO TWO-WAY STOP AT THE SOUTHWEST CORNER OF THE SITE IF
 ALL-WAY STOP IS NOT WARRANTED.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 06-11-2019 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2019-06-11 18:00:231. PROVIDE BENCHES FOR THE TROLLEY STOP ON ROSEMARY
 AVENUE.
 2. CLARIFY IF THERE WILL BE VALET ON THE CURBSIDE ALONG
 HIBISCUS STREET. IF SO, PROVIDE VALET QUEUING ANALYSIS.
 3. MOVE THE DROP OFF AREA ON HIBISCUS STREET TO THE
 EAST AWAY FROM THE INTERSECTION.
 4. EVALUATE AND REMOVE ALL-WAY STOP AND CONVERT TO
 TWO-WAY STOP AT THE SOUTHWEST CORNER OF THE SITE IF
 ALL-WAY STOP IS NOT WARRANTED.
 5. PROVIDE CURBSIDE MANAGEMENT PLAN INCLUDING CURBSIDE
 USAGE MONITORING.
 6. PROVIDE BICYCLE PARKING ALONG ROSEMARY AVENUE
 7. PROVIDE FREIGHT DELIVERY PLAN IDENTIFYING THE
 DELIVERY ROUTE, HOURS AND THE TYPE OF FREIGHT VEHICLES.
 VERIFY THE FREIGHT VEHICLES CAN BE ACCOMMODATED ALONG
 THE ROUTE, AND ANY IMPACT FROM THE FREIGHT VEHICLE TO
 TRAFFIC.
 8. PROVIDE A PARKING UTILIZATION STUDY TO VERIFY
 SUFFICIENT PARKING SPACES ARE AVAILABLE IN THE GARAGE.
 9. CONSIDER PROVIDING THE FOLLOWING TRANSPORTATION
 DEMAND MANAGEMENT (TDM) STRATEGIES:
 A. UNBUNDLE PARKING SPACES FROM THE RESIDENTIAL LEASE
 B. IMPLEMENT PARKING CASH OUT PROGRAM FOR EMPLOYEES
  
 TRAFFIC STUDY COMMENTS:
 10. REPORT HCM 2010 OR HCM 6TH RESULTS INSTEAD OF
 SYNCHRO RESULTS. IF HCM 2010 OR HCM 6TH RESULTS ARE NOT
 AVAILABLE, REPORT HCM 2000 RESULTS.
 11. INTERSECTIONS WITH TRAFFIC COUNTS COLLECTED IN 2018
 SHOULD INCLUDE THE PROPOSED DEVELOPMENT TRIPS WITH NO
 CREDIT FROM THE EXISTING USE SINCE THE EXISTING USE
 CEASED TO OPERATE STARTING FROM MARCH 2017.
 12. SOME OF THE TRIP GENERATION RATES ARE NOT
 CONSISTENT WITH THE LATEST TRIP RATES FROM PALM BEACH
 COUNTY. PLEASE REVISE.
 13. CLARIFY THE INTERNAL TRIP CAPTURE METHODOLOGY, OR
 USE INTERNAL TRIP CAPTURE CALCULATIONS BASED ON ITE
 METHODOLOGY.
 14. IDENTIFY THE ACCESS POINTS OF THE PARKING GARAGE.
 15. CLARIFY IF IT IS REASONABLE TO HAVE MORE THAN 50%
 OF TRIPS USING FERN STREET TO ACCESS OKEECHOBEE
 BOULEVARD, WHILE THERE ARE SHORTER ROUTES AVAILABLE.
  
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop Z ZONING
Rev No 5 Status P Date 11-11-2019 Cont ID  
Sent By eschneid Date 11-11-2019 Time 11:35 Rev Time 0.00
Received By eschneid Date 11-11-2019 Time 11:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 10-21-2019 Cont ID  
Sent By eschneid Date 10-21-2019 Time 15:07 Rev Time 0.00
Received By eschneid Date 10-18-2019 Time 13:50 Sent To  
Notes
2019-10-21 15:08:05CASE NO. PB 950 OOOOO - OCTOBER 4, 2019 RESUBMITTAL
 REVIEW
 HIBISCUS TOWER
 575 SOUTH ROSEMARY AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - COMMENT #1 MUST BE SHOWN ON THE PLANS SUBMITTED TO
 THE PLANNING DIVISION BY NOON, FRIDAY, OCTOBER 25,
 2019, TO BE ELIGIBLE TO BE SCHEDULED FOR THE NOVEMBER
 19, 2019 PLANNING BOARD MEETING.
  
 - COMMENT #2 MUST BE ADDRESSED ON THE PLANS PRIOR TO
 THE SCHEDULING OF THE CITY COMMISSION HEARING. IF THE
 COMMENT IS ADDRESSED ON THE PLANS SUBMITTED TO THE
 PLANNING DIVISION BY NOON, FRIDAY, OCTOBER 25, 2019,
 STAFF WILL PROVIDE THE MAILER FOR THE DECEMBER 16, 2019
 CITY COMMISSION MEETING, TO BE MAILED AT THE SAME TIME
 AS THE PLANNING BOARD MAILER. OTHERWISE, THE PLANS NEED
 TO BE UPDATED BY 5 P.M., WEDNESDAY, NOVEMBER 7, 2019,
 TO RECEIVE THE MAILER FOR THE DECEMBER 16, 2019 CITY
 COMMISSION MEETING.
  
 1) UPDATED COMMENT: THANK YOU FOR INCLUDING THE ADA
 RAMP TO PROVIDE ACCESS TO THE ROSEMARY AVENUE FACING
 MAINTENANCE ROOM ON THE GROSS AREA PLANS, BUT THIS ALSO
 INCREASES THE FAR FOR THE BUILDING AS IT IS A
 PASSAGEWAY. THE RAMP NEEDS TO BE INCLUDED IN THE FAR
 CALCULATIONS. STAFF ASSUMED, INCORRECTLY, THAT YOU
 WOULD MAKE BOTH CHANGES AS PART OF THE RESUBMITTAL.
 NOTE: THE PLANS ONLY SHOW 320 SQUARE FEET AVAILABLE
 BEFORE THE 6.0 FAR IS EXCEEDED. ADDITIONALLY, IF AT THE
 TIME OF BUILDING PERMIT THE BUILDING OR FIRE PLAN
 REVIEWERS REQUIRE A DESIGNATED ROUTE FROM THE ADA RAMP
 TO THE MAINTENANCE ROOM ENTRANCE(S), THEN THE SQUARE
 FOOTAGE OF THE DESIGNATED ROUTE WILL ALSO COUNT TOWARD
 THE FAR SQUARE FOOTAGE.
  
 2) UPDATED COMMENT: THE STREETSCAPE ELEMENTS AND
 LANDSCAPE MUST BE ADDED TO THE SITE, LANDSCAPE AND
 CIVIL PLANS AND THE CROSS HATCHING REMOVED.
  
 CONDITION: THE AC UNITS MOUNTED ON RACKS ON THE WEST
 BUILDING WALL OF 477 SOUTH ROSEMARY MUST BE REMOVED
 PRIOR TO THE CONSTRUCTION OF THE 575 SOUTH ROSEMARY
 BUILDING.
  
 CONDITION: WAYFINDING SIGNS ARE REQUIRED TO DIRECT
 PEDESTRIANS FROM THE GARAGE TO THE OFFICE, RESIDENTIAL
 AND RETAIL ENTRANCES.
  
 CONDITION: THE LEVEL III SITE PLAN APPROVAL WILL
 CONTAIN THE DEVELOPMENT REGULATION THAT NO LEASES CAN
 INCLUDE DESIGNATED PARKING IN THE D GARAGE AND THAT NO
 BARRIERS MAY BE INSTALLED IN THE GARAGE TO CREATE
 SEPARATED PARKING AREAS FOR SPECIFIC TENANTS UNLESS A
 MINOR AMENDMENT IS APPROVED THAT BOTH DESIGNATES THE
 LOCATION OF THE RESERVED PARKING SPACES AND THE
 BARRIERS AS WELL AS VERIFIES THAT THERE IS SUFFICIENT
 PARKING WITHIN THE ROSEMARY SQUARE CONTROLLED GARAGES
 TO ACCOMMODATE THE REQUIRED PARKING FOR THE ENTIRE
 PROJECT.
  
 CONDITION: RECORD A PUBLIC ACCESS EASEMENT, IN A FORM
 ACCEPTABLE TO THE CITY ATTORNEY'S OFFICE, FOR THE
 PUBLIC SPACE TERMINATING THE PUBLIC OPEN SPACE -
 PASSAGE.
  
 CONDITION: IF VALET SERVICE IS UTILIZED FOR THE
 RESIDENTIAL TOWER, THEN PRIOR TO THE ISSUANCE OF THE
 C.O. FOR THE RESIDENTIAL TOWER, A VALET PLAN MUST BE
 SUBMITTED TO THE CITY AND APPROVED BY THE PLANNING AND
 TRAFFIC ENGINEERING STAFF.
  
 CONDITION: IF VALET SERVICE IS UTILIZED FOR THE OFFICE
 TOWER, THEN IT MUST EITHER UTILIZE THE SERVICE ALLEY
 LOADING SPACES FOR VEHICLES TO TURN AROUND, OR AN
 ALTERNATIVE VALET PLAN MUST BE SUBMITTED TO THE CITY
 AND APPROVED BY THE PLANNING AND TRAFFIC ENGINEERING
 STAFF.
  

Review Stop Z ZONING
Rev No 3 Status F Date 09-24-2019 Cont ID  
Sent By eschneid Date 09-24-2019 Time 15:51 Rev Time 6.00
Received By eschneid Date 09-20-2019 Time 13:46 Sent To  
Notes
2019-09-24 15:52:02CASE NO. PB 950 OOOOO - 2ND RESUBMITTAL REVIEW
 HIBISCUS TOWER
 575 SOUTH ROSEMARY AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 SEPTEMBER 27, 2019, TO BE ELIGIBLE TO BE SCHEDULED FOR
 THE NOVEMBER 19, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THESE COMMENTS ARE NOT
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE ORIGINAL
 APPLICATION FEE ($600).
  
 1) UPDATED COMMENT: THANK YOU FOR PROVIDING THE
 DIMENSION LINE SHOWING THE HEIGHT OF PODIUM ALONG
 HIBISCUS STREET.
  
 A. THE PLANS SHOW THE RAILING THAT WAS AT THE EDGE OF
 THE PODIUM HAS BEEN REMOVED. DOES THIS RESULT IN THE
 5TH FLOOR RESIDENTIAL UNITS FACING HIBISCUS STREET NO
 LONGER HAVING A TERRACE? NO 5TH FLOOR PLAN WAS PROVIDED
 TO SHOW WHAT OCCURS UNDERNEATH THE BALCONIES. SINCE
 THIS AREA IS STILL THE TOP OF THE PODIUM, NO RAILING
 CAN BE PROVIDED TO CREATE TERRACES SINCE THIS WOULD
 EXCEED THE MAXIMUM PODIUM HEIGHT. IF A TERRACE IS
 DESIRED ON TOP OF THE PODIUM, THEN STAFF SUGGESTS
 LOWERING THE FLOOR HEIGHTS BY ENOUGH (BARRIER NEEDS TO
 BE 42 INCHES ABOVE THE WALKING SURFACE PER ROBERT
 BROWN, BUILDING OFFICIAL) TO ALLOW ACCESS TO THE
 TERRACE.
 B. THE COLUMNS THAT ARE SHOWN SUPPORTING THE UNDERSIDE
 OF THE BALCONIES EXTEND ABOVE THE 60 FOOT PODIUM
 MAXIMUM HEIGHT. THESE COLUMNS AT THE PODIUM LEVEL ARE
 NOT BALCONY ENCROACHMENTS (THE LOWEST LEVEL BALCONY
 SLAB MAY NOT HAVE COLUMNS UNDERNEATH IT), BUT RATHER
 PART OF THE TOWER; THEREFORE, THE TOWER DOES NOT MEET
 THE MINIMUM 50 FOOT TOWER SETBACK. NOTE: THE COLUMNS
 ARE PERMITTED ABOVE THE FIRST BALCONY SLAB.
  
  
 2) UPDATED COMMENT: STAFF HAS REVIEWED THE REVISED
 ACTIVE USE DIAGRAMS FOR THE SOUTH ROSEMARY AVENUE
 FRONTAGE AND HAS THE FOLLOWING COMMENTS:
  
 A. THANK YOU FOR PROVIDING THE REQUIRED WINDOWS FOR THE
 TWO MAINTENANCE OFFICES. PLEASE LABEL THESE ON THE
 ELEVATIONS. THE REQUIRED DIRECT VIEW FOR THE RETAIL ON
 THE 2ND STORY NEEDS TO BE SHOWN WITH THIS SUBMITTAL AND
 NOT DELAYED UNTIL THE BUILDING PERMIT SO THAT AN
 ACCURATE REPRESENTATION OF CODE COMPLIANCE CAN BE SHOWN
 AS PART OF THE PUBLIC HEARING PROCESS.
 B. THE ADDITION OF THE ADA RAMP TO PROVIDE ACCESS TO
 THE ROSEMARY AVENUE FACING MAINTENANCE ROOM INCLUDED
 THE EXPANSION OF THE TENANT STORAGE ROOM BY 50 SQUARE
 FEET (WALLS MOVED FROM ONE SIDE OF THE COLUMNS TO THE
 OTHER), YET THE STORAGE ROOM GSF CALCULATION DID NOT
 INCREASE. THE LEVEL 3 GROSS AREA DIAGRAM NEEDS TO BE
 UPDATED TO REFLECT THE EXPANDED STORAGE ROOM, THE ADA
 ACCESS RAMP AND THE REDUCTION OF THE MECHANICAL ROOM,
 WITH ALL TABLES UPDATED ACCORDINGLY.
  
 3) UPDATED COMMENT: STAFF HAS REVIEWED THE PRIVATE OPEN
 SPACE AND HAS THE FOLLOWING COMMENTS:
  
 A. LEVEL 4 OPEN SPACE AREAS A & B ARE A ROOFTOP
 GARDENS, SO THEY DOES NOT REQUIRE PUBLIC RIGHT-OF-WAY
 ABUTMENT. REMOVE THAT LINE ITEM FROM THE TABLE.
 B. LEVEL 4 OPEN SPACE AREA C DOES NOT COMPLY WITH THE
 MINIMUM PUBLIC RIGHT-OF-WAY ABUTMENT TO BE CONSIDERED A
 TERRACE. THE WEST SIDE OF THE BUILDING ABUTS AN ACCESS
 EASEMENT, NOT A PUBLIC RIGHT-OF-WAY. PRIVATE OPEN SPACE
 AT THIS LOCATION CAN ONLY BE A ROOFTOP GARDEN. PLEASE
 UPDATE THE TABLE AND PLANS ACCORDINGLY.
 C. LEVEL 5 OPEN SPACE AREA A DOES NOT COMPLY WITH THE
 MINIMUM PUBLIC RIGHT-OF-WAY ABUTMENT TO BE CONSIDERED A
 TERRACE. THE WEST SIDE OF THE BUILDING ABUTS AN ACCESS
 EASEMENT, NOT A PUBLIC RIGHT-OF-WAY. PRIVATE OPEN SPACE
 AT THIS LOCATION CAN ONLY BE A ROOFTOP GARDEN. PLEASE
 UPDATE THE TABLE AND PLANS ACCORDINGLY.
  
 4) PUBLIC OPEN SPACE - PASSAGE REQUIREMENTS
  
 A. UPDATED COMMENT: A PASSAGEWAY IS REQUIRED TO CONNECT
 TWO OR MORE PUBLIC RIGHTS-OF-WAY OR PUBLIC SPACES. THE
 ACCESS EASEMENT ON THE WEST SIDE OF THE BUILDING IS NOT
 A PUBLIC RIGHT-OF-WAY SO THIS SIDE OF THE PASSAGEWAY
 NEEDS TO TERMINATE AT A PUBLIC SPACE (GENERALLY THE
 AREA UNDER THE BUILDING ALONG THE ACCESS EASEMENT). IN
 ORDER FOR THIS AREA TO BE CLASSIFIED AS PUBLIC SPACE,
 IT WILL NEED A PUBLIC ACCESS EASEMENT RECORDED FOR IT
 AS WELL AS HAVE SEATING INSTALLED. THE PASSAGEWAY WILL
 END AT THE COVERED PUBLIC SPACE. --- THE RESPONSE
 STATES THAT THE APPLICANT AGREES TO A PUBLIC ACCESS
 EASEMENT. THIS WILL BE INCLUDED AS A REQUIREMENT PRIOR
 TO THE FINAL INSPECTION FOR THE BUILDING. THE PLANS
 FAIL TO SHOW SEATING FOR THE PUBLIC SPACE.
  
 5) UPDATED COMMENT: THE ELEMENTS PROJECTING FROM THE
 ROSEMARY AVENUE AND HIBISCUS STREET FACADES CAN FALL
 UNDER ONE OF THE FOLLOWING CLASSIFICATIONS:
 ARCHITECTURAL FEATURE, AWNING, BALCONY AND CANOPY.
  
 A. ARCHITECTURAL FEATURE: THIS IS LISTED AS KEYNOTE 15
 ON THE ELEVATION KEY AND SHOWN ON THE PLANS AS EYEBROWS
 NO MORE THAN TWO FEET (SCALED) FROM THE RESIDENTIAL
 PODIUM BUILDING FACADE. HOWEVER, THERE ARE ADDITIONAL
 ITEMS, KEYNOTE 3 GLASS AND ALUMINUM AWNINGS, LOCATED ON
 THE 2ND AND 3RD FLOORS OF THE OFFICE AND RESIDENTIAL
 PORTIONS OF THE SITE THAT ARE CALLED AWNINGS, BUT DO
 NOT MEET THE DMP DEFINITION OF AN AWNING. DUE TO THE
 DESIGN, LOCATION AND SIZE OF THESE ITEMS, THEY CAN ONLY
 BE CONSIDERED ARCHITECTURAL FEATURES, AND NEED TO BE
 DESIGNATED AS SUCH ON THE PLANS.
 B. AWNING: THERE ARE NO AWNINGS DEPICTED ON THE PLANS.
 C. BALCONY: THE BALCONY ALONG ROSEMARY AVENUE COMPLIES
 WITH THE PROJECTION STANDARDS.
 D. CANOPY: THERE ARE THREE PROJECTIONS WHICH ARE
 CONSIDERED CANOPIES (TWO ON HIBISCUS STREET AND ONE ON
 ROSEMARY AVENUE) OVER THE FIRST FLOOR ENTRIES TO THE
 RESIDENTIAL AND RETAIL AREAS. THEY ARE LISTED AS
 KEYNOTE 3 GLASS AND ALUMINUM AWNINGS. THIS DESIGNATION
 NEEDS TO CHANGE AS THEY DO NOT MEET THE DEFINITION OF
 AN AWNING (LOCATED BETWEEN, RATHER THAN ACROSS,
 SIGNIFICANT VERTICAL ARCHITECTURAL FEATURES THAT MAKE
 UP THE COMPOSITION OF THE FACADE). SINCE THESE ITEMS
 ARE CANOPIES, THEY NEED TO BE A MINIMUM OF EIGHT (8)
 FEET IN DEPTH. THIS DIMENSION LINE NEEDS TO BE SHOWN ON
 THE ELEVATION PLANS.
  
 6) UPDATED COMMENT: THE TYPICAL BALCONY PLAN DOES NOT
 MATCH THE ELEVATION PLANS FOR THE NORTHERN SIDE OF THE
 BUILDING. THE COLUMN WITHIN THE BALCONY AREA (EAST
 POINT AREA) IS SHOWN TWO FEET CLOSER TO THE BUILDING
 THAN IT IS ON THE ELEVATION DRAWINGS. THE EAST
 ELEVATION SHOWS THE BALCONY EXTENDING TWO FEET LESS
 THAN THE FLOOR PLANS.
  
 7) REPEAT COMMENT: STAFF HAS REVIEWED THE PROPOSED
 RESIDENTIAL TOWER VALET PLAN AND DOES NOT SUPPORT THE
 USE OF FERN STREET AND SOUTH ROSEMARY AVENUE TO RETURN
 THE VEHICLES. THIS PUTS ADDITIONAL VEHICLE TRIPS ON
 THESE TWO STREETS. AN ALTERNATIVE VALET PICK-UP IS
 REQUIRED. WHERE IS THE VALET AREA IN THE GARAGE?
  
 8) REPEAT COMMENT: STAFF DOES NOT SUPPORT THE USE OF
 FERN STREET AND SAPODILLA AVENUE FOR THE VALET AS THIS
 PUTS ADDITIONAL VEHICLE TRIPS ON THESE ROADWAYS. AN
 ALTERNATIVE IS TO HAVE THE VALETS USE ONE OF THE
 SERVICE AREA SPACES AS A TURNAROUND SPACE SO THEY CAN
 GET THE GARAGE WITHOUT USING THE STREET NETWORK.
  
 9) UPDATED COMMENT: THE PASSAGEWAY BICYCLE RACK DETAIL
 DOES NOT MEET CODE REQUIREMENTS. THE RACKS SHOWN ON THE
 INSTALLATION PLANS DO NOT COMPLY WITH ANY OF THE MODELS
 SHOWN ON THE BIKE RACK REQUIREMENTS DETAIL. NOTE: WHILE
 STAFF FEELS IT IS ALWAYS BETTER TO PROVIDE EXTRA SPACE
 FOR PARK BICYCLES, THE 13 FEET IS WIDER THAN IS
 REQUIRED FOR 6 BICYCLE PARKING SPACES.
  
 10) UPDATED COMMENT: PROVIDE BICYCLE RACKS ALONG
 ROSEMARY FOR THE RETAIL CUSTOMERS. THE BICYCLE RACKS
 (AND THE OTHER ROSEMARY AVENUE IMPROVEMENTS) MUST BE
 SHOWN ON THESE PLANS. NOTE: THE CITY COMMISSION DID NOT
 APPROVE 100% DRAWINGS AS PART OF THE FACE OF THE CITY
 RESOLUTION, SO THESE PLANS NEED TO BE SHOWN ON THIS SET
 OF DRAWINGS.
  
 11) UPDATED COMMENT: THE ROOF AREAS THAT ARE NOT
 INCLUDED AS OPEN SPACE OR HAVE MECHANICAL EQUIPMENT ARE
 REQUIRED TO HAVE GREEN ROOF OR SOLAR INSTALLATION. THE
 DETAILS WILL BE INCLUDED AT TIME OF BUILDING PERMIT;
 HOWEVER, THE PLANS MUST STATE THAT GREEN ROOF OR SOLAR
 INSTALLATIONS ARE REQUIRED ON THE ROOVES. NOTE: THE
 COMMENT RESPONSE SEEMS TO INDICATE THAT DUE THE
 BUILDING HAVING DIFFERENT ROOF AREAS, ONLY ONE OF THESE
 AREAS NEEDS TO HAVE GREEN OR SOLAR INSTALLATION TO
 COMPLY WITH THE DEVELOPMENT REGULATIONS, WHICH IS NOT
 CORRECT. ALL ROOF AREAS NEED TO HAVE EITHER OPEN SPACE,
 MECHANICAL OR GREEN/SOLAR.
  
 12) REPEAT COMMENT: THE PHOTOMETRIC PLAN SHOWS LIGHTING
 LEVELS AT THE CURB IN EXCESS OF THE PERMITTED ONE FOOT
 CANDLE. ---- RESUBMITTED SHEET E-0.1 STILL SHOWS LIGHT
 LEVELS AT THE CURB EXCEEDING ONE FOOTCANDLE.
  
 CONDITION: THE AC UNITS MOUNTED ON RACKS ON THE WEST
 BUILDING WALL OF 477 SOUTH ROSEMARY MUST BE REMOVED
 PRIOR TO THE CONSTRUCTION OF THE 575 SOUTH ROSEMARY
 BUILDING.
  
 CONDITION: WAYFINDING SIGNS ARE REQUIRED TO DIRECT
 PEDESTRIANS FROM THE GARAGE TO THE OFFICE, RESIDENTIAL
 AND RETAIL ENTRANCES.
  
 CONDITION: THE LEVEL III SITE PLAN APPROVAL WILL
 CONTAIN THE DEVELOPMENT REGULATION THAT NO LEASES CAN
 INCLUDE DESIGNATED PARKING IN THE D GARAGE AND THAT NO
 BARRIERS MAY BE INSTALLED IN THE GARAGE TO CREATE
 SEPARATED PARKING AREAS FOR SPECIFIC TENANTS UNLESS A
 MINOR AMENDMENT IS APPROVED THAT BOTH DESIGNATES THE
 LOCATION OF THE RESERVED PARKING SPACES AND THE
 BARRIERS AS WELL AS VERIFIES THAT THERE IS SUFFICIENT
 PARKING WITHIN THE ROSEMARY SQUARE CONTROLLED GARAGES
 TO ACCOMMODATE THE REQUIRED PARKING FOR THE ENTIRE
 PROJECT.
  

Review Stop Z ZONING
Rev No 2 Status F Date 08-26-2019 Cont ID  
Sent By eschneid Date 08-26-2019 Time 17:51 Rev Time 12.00
Received By eschneid Date 08-22-2019 Time 09:47 Sent To  
Notes
2019-08-26 17:51:48CASE NO. PB 950 OOOOO - 1ST RESUBMITTAL REVIEW
 HIBISCUS TOWER
 575 SOUTH ROSEMARY AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 AUGUST 30, 2019, TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 OCTOBER 15, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT SINCE PREVIOUSLY-ISSUED COMMENTS
 WERE NOT BE SUFFICIENTLY ADDRESSED, THE APPLICANT WILL
 BE ASSESSED A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE
 ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) THE SCALE BAR ON SHEET A0.04.2 PRINTED MULTIPLE
 SCALES AND IS UNREADABLE. THIS OCCURS ON A FEW SHEETS,
 SO PLEASE CORRECT.
  
 2) REPEAT COMMENT: PROVIDE THE DIMENSION LINE SHOWING
 THE FULL HEIGHT OF THE PODIUM, PLUS THE HIGHEST POINT
 OF THE HEIGHT ENCROACHMENT ON THE ELEVATION PLANS. THE
 PODIUM HEIGHT DIMENSION WAS NOT PROVIDED FOR THE
 HIBISCUS STREET FRONTAGE. THE WESTERN PORTION OF THE
 PODIUM ALONG HIBISCUS STREET (PRIMARILY THE PRIVATE
 TERRACE) SCALES TO EXCEED 60 FEET AND ADDITIONALLY HAS
 A VERTICAL ENCROACHMENT (RAILING) EXCEEDING THE 60 FOOT
 ALLOWANCE.
  
 3) UPDATED COMMENT: THANK YOU FOR PROVIDING ADDITIONAL
 INFORMATION REGARDING THE FACADE ARTICULATION. BASED ON
 THE RESUBMITTED INFORMATION, STAFF HAS IDENTIFIED THE
 FOLLOWING ITEMS WHICH STILL MUST BE PROVIDED:
  
 A. THE AMOUNT OF GROUND FLOOR TRANSPARENCY PROVIDED
 ALONG SOUTH ROSEMARY AVENUE AND HIBISCUS STREET IS NOT
 LISTED ON THE PLANS. THE ONLY CALCULATION LISTED IS HOW
 MUCH IS REQUIRED.
 B. THE AMOUNT OF FENESTRATION FOR THE PODIUM AND THE
 TOWER IS NOT LISTED ON THE PLANS. ONLY A STATEMENT THAT
 THE FENESTRATION EXCEEDS 15% IS LISTED ON THE PLANS.
 C. THE TAG LINES FOR THE WEST ELEVATIONS FOR MATERIAL
 01 AND 02 SEEM TO POINT TO THE WRONG MATERIAL.
 D. PLEASE CONSIDER ADDITIONAL WINDOWS OVERLOOKING THE
 OUTDOOR SEATING AREA FROM THE GROUND LEVEL RETAIL AND
 UPPER LEVEL OFFICE.
  
 4) UPDATED COMMENT: PLANAR BREAKS ARE REQUIRED FOR ALL
 LEVELS OF THE PODIUM. THE PLANS DO NOT CLEARLY SHOW
 EVIDENCE THAT THIS OCCURS.
  
 A. THE SOUTH ROSEMARY AVENUE FRONTAGE (GROUND FLOOR)
 ADDED DOORWAYS THAT ARE BEING COUNTED TOWARD MEETING
 THE MINIMUM LINEAR FEET OF PLANAR BREAK. IN ORDER FOR
 DOORWAYS TO COUNT TOWARD MEETING THIS REQUIREMENT, THE
 DOORWAY RECESS (THE PLANER BREAK) NEEDS TO CONTINUE
 FROM GRADE FOR THE FULL HEIGHT OF THE GROUND FLOOR. THE
 DRAWINGS DO NOT CLEARLY INDICATE THAT THE DOORWAYS
 EXTEND THE FULL HEIGHT OF THE GROUND FLOOR, AND IN FACT
 IT APPEARS THAT THE DOORWAYS ARE NOT THE FULL HEIGHT OF
 THE GROUND FLOOR.
 B. ON THE SOUTH ROSEMARY AVENUE FRONTAGE (2ND AND 3RD
 FLOOR), WHILE THE OUTDOOR SEATING RECESS AND THE OFFICE
 TERRACE COMBINE TO MEET THE MINIMUM REQUIRED PLANAR
 BREAK AND THE RETAIL ONE CONTINUES TO EXCEED THIS
 REQUIREMENT, PLEASE CHECK THE SECTION DRAWING ON SHEET
 A3.01 AS IS APPEARS THAT THE PROPOSED PLANAR BREAK IS
 NOT DEPICTED ACCURATELY.
 C. THE HIBISCUS STREET FRONTAGE (2ND FLOOR) ADDED A
 RECESS THAT IS BEING COUNTED TOWARD MEETING THE MINIMUM
 LINEAR FEET OF PLANAR BREAK. IN ORDER FOR RECESS TO
 COUNT TOWARD MEETING THIS REQUIREMENT, THE IT (THE
 PLANER BREAK) NEEDS TO CONTINUE THE FULL HEIGHT OF THE
 2ND FLOOR. THE DRAWINGS DO NOT CLEARLY INDICATE THAT
 THE RECESS EXTENDS THE FULL HEIGHT OF THE 2ND FLOOR.
  
 5) UPDATED COMMENT: STAFF HAS REVIEWED THE REVISED
 ACTIVE USE DIAGRAMS FOR THE SOUTH ROSEMARY AVENUE
 FRONTAGE AND HAS THE FOLLOWING COMMENTS:
  
 A. THE MAINTENANCE OFFICE ADDED TO THE 3RD FLOOR DOES
 NOT APPEAR TO HAVE ADA ACCESSIBILITY. PLEASE DESCRIBE
 HOW THIS SPACE WILL MEET BUILDING CODE REQUIREMENTS. IF
 THIS ROOM CANNOT BE CONSTRUCTED AS SHOWN ON THE PLANS,
 THEN IT WILL CAUSE ISSUES DURING THE PERMITTING
 PROCESS.
 B. THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT ACTIVE USES HAVE A DIRECT VIEW TO THE ADJACENT
 STREETS OR PUBLIC OPEN SPACE. THIS DOES NOT OCCUR FOR
 THE 2ND STORY RETAIL ALONG SOUTH ROSEMARY AVENUE OR
 HIBISCUS STREETS SINCE THE PROPOSED FLUTED CHANNEL
 GLASS IS NOT TRANSPARENT. ADDITIONALLY, THE TWO
 MAINTENANCE OFFICES (BOTH COUNTED AS ACTIVE USE) HAVE
 NO DIRECT VIEW TO THE ADJACENT STREETS
  
 6) UPDATED COMMENT: STAFF HAS REVIEWED THE PUBLIC OPEN
 SPACE COMPLIANCE TABLE FOR THE OUTDOOR SEATING AREA
 ALONG SOUTH ROSEMARY AVENUE AND NOTED THAT IT
 INCORRECTLY INCLUDES THE SQUARE FOOTAGE FOR THE AREA
 UNDER THE 2ND AND 3RD FLOORS OF THE BUILDING. THIS AREA
 DOES NOT MEET THE DEFINITION OF OVERHEAD COVER, WHICH
 INCLUDES AWNINGS, CANOPIES, COLONNADES, PERGOLAS,
 TRELLISES OR OTHER SIMILAR STRUCTURES. THE STAFF
 CALCULATES THE ACTUAL OPEN SPACE AREA AS APPROXIMATELY
 937 SF AND IT APPEARS THAT THE OPEN SPACE MINIMUMS HAVE
 BEEN MET AS SHOWN. UPDATE THE TABLE WITH THE ACCURATE
 OPEN SPACE AREA AND CORRESPONDING COMPLIANCE
 VERIFICATION. NOTE: THE LANDSCAPE UNDER THE BUILDING
 MAY NOT BE INCLUDED IN THE PROVIDED LANDSCAPE
 CALCULATION.
  
 7) UPDATED COMMENT: STAFF HAS REVIEWED THE PRIVATE OPEN
 SPACE AND HAS THE FOLLOWING COMMENTS:
  
 A. LEVEL 4 OPEN SPACE AREA B DOES NOT COMPLY WITH THE
 MINIMUM PUBLIC RIGHT-OF-WAY ABUTMENT TO BE CONSIDERED A
 TERRACE. THIS PRIVATE OPEN SPACE IS MORE THAN 60 FEET
 FROM THE SOUTH ROSEMARY AVENUE PUBLIC RIGHT-OF-WAY AND
 THE SEPARATION INCLUDES MECHANICAL ROOMS AND THE
 CHILLER ENCLOSURES. PRIVATE OPEN SPACE AT THIS LOCATION
 CAN ONLY BE A ROOFTOP GARDEN. PLEASE UPDATE THE TABLE
 AND PLANS ACCORDINGLY.
 B. LEVEL 4 OPEN SPACE AREA C DOES NOT COMPLY WITH THE
 MINIMUM PUBLIC RIGHT-OF-WAY ABUTMENT TO BE CONSIDERED A
 TERRACE. THE WEST SIDE OF THE BUILDING ABUTS AN ACCESS
 EASEMENT, NOT A PUBLIC RIGHT-OF-WAY. PRIVATE OPEN SPACE
 AT THIS LOCATION CAN ONLY BE A ROOFTOP GARDEN. PLEASE
 UPDATE THE TABLE AND PLANS ACCORDINGLY.
 C. LEVEL 5 OPEN SPACE INCORRECTLY CALCULATES THE AMOUNT
 OF PUBLIC RIGHT-OF-WAY ABUTMENT. ONLY THE 96 FOOT 9
 INCH SECTION OF THE TERRACE MAY COUNT (AS PREVIOUSLY
 STATED THE ACCESS EASEMENT DOES NOT MEET THE PUBLIC
 RIGHT-OF-WAY REQUIREMENT). WHILE THE MINIMUM 20% HAS
 BEEN MET, THE TABLE NEEDS TO BE UPDATED ACCORDINGLY.
 NOTE: THE SQUARE FOOTAGE ASSOCIATED WITH THIS PRIVATE
 OPEN SPACE MAY BE AFFECTED BY CORRECTING THE RAILING
 HEIGHT FROM COMMENT #2.
  
 8) UPDATED COMMENT: PLEASE DESCRIBE HOW THE LEVEL 4
 ROOFTOP GARDEN WILL BE USED (ACCESSED) BY THE RESIDENTS
 OR THE OFFICE TENANTS.
  
 9) PUBLIC OPEN SPACE - PASSAGE REQUIREMENTS
  
 A. UPDATED COMMENT: A PASSAGEWAY IS REQUIRED TO CONNECT
 TWO OR MORE PUBLIC RIGHTS-OF-WAY OR PUBLIC SPACES. THE
 ACCESS EASEMENT ON THE WEST SIDE OF THE BUILDING IS NOT
 A PUBLIC RIGHT-OF-WAY SO THIS SIDE OF THE PASSAGEWAY
 NEEDS TO TERMINATE AT A PUBLIC SPACE (GENERALLY THE
 AREA UNDER THE BUILDING ALONG THE ACCESS EASEMENT). IN
 ORDER FOR THIS AREA TO BE CLASSIFIED AS PUBLIC SPACE,
 IT WILL NEED A PUBLIC ACCESS EASEMENT RECORDED FOR IT
 AS WELL AS HAVE SEATING INSTALLED. THE PASSAGEWAY WILL
 END AT THE COVERED PUBLIC SPACE.
 B. REPEAT COMMENT: PROVIDE THE DIMENSIONS FOR THE
 NARROW POINTS SHOWN IN THE PASSAGEWAY. EX. BETWEEN THE
 BUILDING WALLS, THE EDGE OF THE LANDSCAPE AREAS AND THE
 COLUMNS. THESE ALL APPEAR TO BE CHOKE POINTS IN THE
 PASSAGEWAY.
 C. UPDATED COMMENT: THE WESTERN PORTION OF THE
 PASSAGEWAY IS COVERED BY THE UPPER RESIDENTIAL STORIES,
 INCLUDING BALCONIES. THIS AREA DOES NOT MEET THE
 DEFINITION OF OVERHEAD COVER, WHICH INCLUDES AWNINGS,
 CANOPIES, COLONNADES, PERGOLAS, TRELLISES OR OTHER
 SIMILAR STRUCTURES, BUT DOES NOT INCLUDE AN AREA THAT
 HAS THE UPPER STORIES OF THE BUILDING. THE 1,460 SQUARE
 FEET OF COVERED AREA MAY NOT BE COUNTED TOWARD MEETING
 THE OPEN SPACE REQUIREMENT. UPDATE ALL TABLES
 ACCORDINGLY.
 D. UPDATED COMMENT: THE OPEN SPACE MEASUREMENTS FOR THE
 PASSAGEWAY MAY NOT INCLUDE AREAS WITHIN THE MINIMUM
 SETBACK. PROVIDE THE REQUIRED NFPA SETBACK DIMENSION
 FOR THE WEST SIDE OF THE 477 SOUTH ROSEMARY BUILDING
 WHERE IT ABUTS THE PASSAGEWAY. THIS SETBACK AREA MAY
 NOT BE COUNTED TOWARD MEETING THE PUBLIC OPEN SPACE
 SQUARE FOOTAGE REQUIREMENT. ALTERNATIVELY, SINCE THE
 PLANS STATE THAT THE OPENINGS WILL BE PROTECTED,
 PROVIDE THE METHOD FOR THIS PROTECTION THAT WOULD
 PERMIT THE NEW 575 SOUTH ROSEMARY BUILDING TO BE BUILT
 TO THE PROPERTY LINE. NOTE: THE SQUARE FOOTAGE FOR THE
 EGRESS WALKWAY BEHIND THE TWO DOORS ON THE WEST SIDE OF
 477 SOUTH ROSEMARY AVENUE CANNOT BE INCLUDED IN THE
 PASSAGEWAY SINCE IT IS NOT PART OF THE PASSAGEWAY.
 UPDATE ALL TABLES ACCORDINGLY.
  
 10) UPDATED COMMENT: PROVIDE DIMENSION ON THE ELEVATION
 DRAWINGS FOR THE PROJECTING ELEMENTS, WHICH INCLUDE THE
 BALCONIES, BOTH RESIDENTIAL AND COMMERCIAL, THE AWNINGS
 (EX. KEYNOTE 03 ON THE NORTH ELEVATION - TEMPERED GLASS
 AND ALUMINUM AWNING).
  
 11) NEW COMMENT: PROVIDE A SAMPLE FLOOR PLAN LEVEL
 WHICH SHOWS THE SHORT BALCONIS AND ON THAT SHOWS THE
 LONG BALCONIES FOR THAT SPECIFIC FLOOR.
  
 12) UPDATED COMMENT: THE NET AREA DRAWINGS FOR THE
 RESTAURANT, RETAIL AND OFFICE USES MUST INCLUDE THE
 FOLLOWING AREAS AND ALL THE PARKING TABLES NEED TO BE
 UPDATED ACCORDINGLY:
  
 A. RESTAURANT KITCHEN AND STORAGE - THESE AREAS ARE NOT
 INCLUDED IN THE EXEMPTIONS LISTED IN THE NET INTERIOR
 AREA DEFINITION OF SECTION 94-109 OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS.
 B. DOCK MANAGER OFFICE - THE LOADING DOCKS SERVICE BOTH
 THE RESIDENTIAL AND THE NON-RESIDENTIAL COMPONENTS OF
 THE BUILDING, SO DOCK MANAGER'S OFFICE NEEDS TO BE
 INCLUDED IN THE PARKING CALCULATION.
 C. SHOP BY THE LOADING DOCKS - IF THE SHOP ONLY
 SERVICES THE RESIDENTIAL TOWER, THEN IT IS EXEMPTED;
 HOWEVER, BY ITS LOCATION, IT APPEARS TO SERVICE THE
 ENTIRE BUILDING AND MUST BE INCLUDED IN THE NET AREA.
 D. MAINTENANCE OFFICES ON LOFT LEVEL 3 - MAINTENANCE
 OFFICES SERVING THE NON-RESIDENTIAL PORTION OF THE
 BUILDING MUST BE INCLUDE IN THE NET AREA.
 E. RETAIL STORAGE - THESE AREAS ARE NOT INCLUDED IN THE
 EXEMPTIONS LISTED IN THE NET INTERIOR AREA DEFINITION
 SECTION 94-109 OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 13) UPDATED COMMENT: THE SHARED PARKING MAY ONLY BE
 USED IF THERE ARE NO PARKING SPACES DESIGNATED FOR A
 PARTICULAR USE. THE RESPONSE STATES THAT THERE ARE NO
 DESIGNATED PARKING SPACES WITHIN GARAGE D, WHEN IN FACT
 THERE IS AT LEAST ONE AREA THAT IS GATED OFF FOR THE
 USE OF THE GARDENS RESIDENTS. HOW WILL OPERATIONALLY
 THE PARKING BE PROVIDED FOR THE USERS OF THE 575 SOUTH
 ROSEMARY BUILDING- EX: WILL THE RESIDENTIAL TENANTS
 HAVE AN AREA THAT IS DESIGNATED FOR "575 TOWER
 RESIDENTIAL PARKING ONLY"? IF THIS IS THE CASE, THEN
 THE SHARED PARKING MAY NOT BE USED. IF THERE WILL BE NO
 DESIGNATED PARKING, THEN THE LEVEL III SITE PLAN
 APPROVAL WILL CONTAIN THE DEVELOPMENT REGULATION THAT
 NO LEASES CAN INCLUDE DESIGNATED PARKING IN THE D
 GARAGE AND THAT NO BARRIERS MAY BE INSTALLED IN THE
 GARAGE TO CREATE SEPARATED PARKING AREAS FOR SPECIFIC
 TENANTS.
  
 14) UPDATED COMMENT: THE RECENT PARKING TABLE PROVIDED
 BY JORDAN RATHLEV SHOWS 724 PARKING SPACES AVAILABLE IN
 GARAGE D. THIS TABLE NEEDS TO INCLUDE A SUB TABLE
 SHOWING HOW THE 724 PARKING SPACES (OR AS MODIFIED BY
 THE BUILDING DIVISION ADA COMMENT) ARE ALLOCATED TO THE
 575 SOUTH ROSEMARY AVENUE USERS (379 SPACES IF NOT
 RESERVED), THE GARDENS RESIDENCES (33 + 2 GUEST), 477
 SOUTH ROSEMARY AVENUE (RETAIL AND OFFICE - DO ANY
 OFFICE USERS HAVE RESERVED SPACES?), AND DESIGNATED
 VALET. NOTE: THE PARKING AVAILABILITY TABLE INDICATES
 THAT THERE IS EXCESS CAPACITY THROUGHOUT THE ENTIRE
 CITYPLACE CPD, BUT STAFF IS TRYING TO VERIFY THAT
 GARAGE D IS NOT OVER CAPACITY.
  
 15) UPDATED COMMENT: THE TWO LOCATIONS WHERE THE
 PEDESTRIAN CROSSING OF THE ACCESS EASEMENT NEED TO BE A
 DIFFERENT PAVING MATERIAL THAN THE ACCESS EASEMENT
 SURFACE SO THAT IT IS A VISUAL CLUE TO DRIVERS TO SLOW
 DOWN. THIS CURRENTLY OCCURS THROUGH THE USE OF THE
 EXISTING PAVER CROSSWALK, WHICH IS STAFF'S PREFERRED
 OPTION. RAISED CROSSWALKS (EQUAL TO CURB LEVEL) SHOULD
 BE EXPLORED.
  
 16) NEW COMMENT: THE SIDEWALK AT THE NORTHWEST CORNER
 OF THE TOWER INCLUDES A LANDSCAPE BED TO THE EDGE OF
 THE BUILDING WHICH NARROWS THE SIDEWALK TO FIVE (5)
 FEET IN WIDTH. THE LANDSCAPE BED NEEDS TO BE SHORTENED
 SO THAT THE SIDEWALK AT THIS BLIND CORNER IS WIDER TO
 PREVENT SITUATIONS WHERE SOMEONE NEEDS TO STEP INTO THE
 ALLEY TO PASS IN OPPOSITE DIRECTIONS.
  
 17) UPDATED COMMENT: STAFF HAS REVIEWED THE PROPOSED
 RESIDENTIAL TOWER VALET PLAN AND DOES NOT SUPPORT THE
 USE OF FERN STREET AND SOUTH ROSEMARY AVENUE TO RETURN
 THE VEHICLES. THIS PUTS ADDITIONAL VEHICLE TRIPS ON
 THESE TWO STREETS. AN ALTERNATIVE VALET PICK-UP IS
 REQUIRED. WHERE IS THE VALET AREA IN THE GARAGE?
  
 18) UPDATED COMMENT: THE PROPOSED OFFICE VALET PLAN IS
 NOT CLEAR (THE BLUE DASHED LINE STOPS ON FERN STREET.
 IT APPEARS THE INTENT IS TO HAVE THE VALETS DRIVE THE
 CARS AROUND THE BLOCK AND USE FERN STREET, SOUTH
 ROSEMARY AVENUE AND/OR SAPODILLA AVENUE. STAFF DOES NOT
 SUPPORT THE USE OF THESE STREETS FOR THE VALET AS THIS
 PUTS ADDITIONAL VEHICLE TRIPS ON THESE ROADWAYS. AN
 ALTERNATIVE IS TO HAVE THE VALETS USE ONE OF THE
 SERVICE AREA SPACES AS A TURNAROUND SPACE SO THEY CAN
 GET THE GARAGE WITHOUT USING THE STREET NETWORK.
  
 19) REPEAT COMMENT: PROVIDE THE PASSAGEWAY BICYCLE PAD
 AND RACK DETAIL AND THE DIMENSIONS ON THE PLANS. THEY
 DO NOT APPEAR TO MEET CODE REQUIREMENTS. NOTE: THE
 BICYCLE PARKING AREA ALONG THE PEDESTRIAN PASSAGE HAS 6
 RACKS, NOT 3 AS LISTED ON THE PLANS.
  
 20) REPEAT COMMENT: PROVIDE BICYCLE RACKS ALONG
 ROSEMARY FOR THE RETAIL CUSTOMERS. THE HIBISCUS AND
 ROSEMARY RECONSTRUCTION PLANS DO NOT SHOW ANY BICYCLE
 RACKS ADJACENT TO 575 SOUTH ROSEMARY.
  
 21) UPDATED COMMENT: PROVIDE GREEN ROOF DETAILS FOR
 LEVELS 4 AND 5 AND THE TOWER ROOF. NOTE: IN ACCORDANCE
 WITH THE DEVELOPMENT REGULATIONS, THE LEVEL 4 AND 5 AND
 TOWER ROOF AREA THAT DO NOT INCLUDE THE MECHANICAL AND
 SKYLIGHT AREAS MUST HAVE EITHER GREEN ROOF OR SOLAR. IF
 SOLAR IS USED THIS NEEDS TO BE SHOWN. THE PLANS NEED TO
 FACTOR THIS IN NOW.
  
 22) UPDATED COMMENT: PLEASE TURN ON THE FOREGROUND
 BUILDINGS ON THE NORTHWEST AND SOUTHWEST RENDERINGS ON
 SHEET R0.01.
  
 23) REPEAT COMMENT: PROVIDE A SHADOW STUDY. --- STAFF
 HAS NOT SEEN A SHADOW STUDY AND THE DISC WAS NOT
 INCLUDED WITH THE RESUBMITTAL.
  
 24) REPEAT COMMENT: THE PHOTOMETRIC PLAN SHOWS LIGHTING
 LEVELS AT THE CURB IN EXCESS OF THE PERMITTED ONE FOOT
 CANDLE. ---- RESUBMITTED SHEET E-0.1 STILL SHOWS LIGHT
 LEVELS AT THE CURB EXCEEDING ONE FOOTCANDLE.
  
 25) REPEAT COMMENT: WHAT IS THE CONSTRUCTION PHASING
 PLAN FOR THE BUILDING, ROSEMARY AND THE ALLEY? WILL THE
 HIBISCUS RIGHT-OF-WAY, INCLUDING THE SIDEWALK, BE
 COMPLETED PRIOR TO THE CONSTRUCTION OF THE BUILDING?
 HOW WILL ACCESS BE PROVIDED TO THE TOWNHOUSES AND THE
 SERVICE TO 477 SOUTH ROSEMARY DURING CONSTRUCTION? ----
 THE RESPONSE PRESENTED DOES NOT ADEQUATELY ADDRESS THE
 QUESTION.
  
 26) REPEAT COMMENT: EXPLAIN THE BAR IN THE RESIDENTIAL
 LOBBY AREA. WHO DOES THIS SERVE? WHAT DOES IT SERVE?
 --- THE RESPONSE PRESENTED DOES NOT ADDRESS THE
 QUESTION. IF THIS IS A BAR, THAT IN ANYWAY COULD SERVE
 THE PUBLIC, THEN YOU HAVE A NON-RESIDENTIAL USE HERE.
  
 27) UPDATED COMMENT: RESOLUTION 304-18 REQUIRES THAT
 THE ROOFTOP RAINWATER IS RETAINED ON-SITE AND IF NOT
 USED THEN IT HAS ON-SITE INFILTRATION. USING AN
 EXFILTRATION TRENCH TO DISCHARGE THE WATER OFF-SITE IS
 NOT PERMITTED. DESCRIBE HOW THE ROOFTOP RAINWATER WILL
 BE STORED ON-SITE. THE METHOD MAY IMPACT THE SITE PLAN.
 THE PAVING AND DRAINAGE PLAN DOES NOT SEEM TO COVER
 THIS REQUIREMENT.
  
 28) UPDATED COMMENT: RESOLUTION 304-18 REQUIRES THAT
 THE PLAZA AREAS OF THE SITE RETAIN THE STORMWATER
 ON-SITE. IT APPEARS THAT THE PLAZA AREA ALONG SOUTH
 ROSEMARY AVENUE IS DESIGNED TO FLOW OFF-SITE.
  
 CONDITION: THE AC UNITS MOUNTED ON RACKS ON THE WEST
 BUILDING WALL OF 477 SOUTH ROSEMARY MUST BE REMOVED
 PRIOR TO THE CONSTRUCTION OF THE 575 SOUTH ROSEMARY
 BUILDING.
  
 CONDITION: WAYFINDING SIGNS ARE REQUIRED TO DIRECT
 PEDESTRIANS FROM THE GARAGE TO THE OFFICE, RESIDENTIAL
 AND RETAIL ENTRANCES.
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-12-2019 Cont ID  
Sent By eschneid Date 06-12-2019 Time 11:28 Rev Time 12.00
Received By eschneid Date 06-12-2019 Time 11:28 Sent To  
Notes
2019-06-12 11:28:28CASE NO. PB 950 OOOOO
 HIBISCUS TOWER
 575 SOUTH ROSEMARY AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 JUNE 28, 2019, TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 AUGUST 20, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY AUGUST 12, 2019),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) THE CITYPLACE CENTER SUBAREA BOUNDARY LINE IS NOT
 SHOWN IN THE SAME PLACE ON EVERY PLAN ALONG THE WEST
 SIDE OF 477 SOUTH ROSEMARY. ALL PLANS MUST BE
 CONSISTENT.
  
 2) SHEET V-2 SHOWS A PORTION OF THE 477 SOUTH ROSEMARY
 BUILDING WITHIN THE CITYPLACE CENTER SUBAREA. THIS
 OVERLAPPING SQUARE FOOTAGE MUST BE COUNTED AS PART OF
 THE FAR CALCULATION.
  
 3) THE 50 FOOT MAXIMUM PODIUM SETBACK LINE FOR ROSEMARY
 IS NOT IN THE CORRECT LOCATION. IT SCALES TO
 APPROXIMATELY 56 FEET FROM THE ROSEMARY CENTERLINE.
  
 4) STAFF HAS REVIEWED THE FAR CALCULATIONS AND NOTED
 THE FOLLOWING:
  
 A. ON THE GROUND LEVEL, THE TWO VESTIBULES, THE SHOP
 AND THE FIRE COMMAND ROOM ARE REQUIRED TO BE COUNTED IN
 THE FAR SQUARE FOOTAGE.
 B. ON THE RESIDENTIAL LEVELS, THE VESTIBULE FOR THE
 TRASH CHUTES IS REQUIRED TO BE COUNTED IN THE FAR
 SQUARE FOOTAGE (THE TRASH CHUTES THEMSELVES ARE
 CORRECTLY NOT COUNTED).
 C. ON THE RESIDENTIAL LEVELS, PROVIDE INFORMATION ON
 WHAT THE ROOM ADJACENT TO THE TRASH CHUTE VESTIBULE IS.
 DEPENDING ON THE USE, THIS MAY NEED TO BE COUNTED IN
 THE FAR SQUARE FOOTAGE.
  
 5) PROVIDE THE DIMENSION LINE SHOWING THE FULL HEIGHT
 OF THE PODIUM, PLUS THE HIGHEST POINT OF THE HEIGHT
 ENCROACHMENT, MUST BE SHOWN ON THE ELEVATION PLANS.
 STAFF MEASURES THE HIGHEST POINT OF PODIUM, INCLUDING
 VERTICAL ENCROACHMENTS, AT APPROXIMATELY 63 FEET, WHICH
 EXCEEDS THE PERMITTED PODIUM HEIGHT ALLOWANCE. NOTE:
 INCLUDE THE CABANAS, WITH THE HEIGHT, ON THE ELEVATION
 DRAWINGS.
  
 6) THE FACADE ARTICULATION DIAGRAMS AND MATRICES DO NOT
 PROVIDE THE DIMENSIONS FOR THE VARIOUS REQUIRED
 FEATURES. STAFF MUST BE ABLE TO VERIFY COMPLIANCE WITH
 THE REQUIREMENTS. NOTE: THE LETTERS ON THE DIAGRAMS ON
 SHEETS A0.01.1 AND A0.01.2 MUST KEY TO TEXT IN THE
 TABLE.
  
 7) PLANAR BREAKS ARE REQUIRED FOR ALL LEVELS OF THE
 PODIUM. THE PLANS DO NOT SHOW EVIDENCE THAT THIS
 OCCURS.
  
 8) STAFF DOES NOT FEEL THAT THE TOWER HAS ENOUGH
 ARTICULATION GIVEN ITS SCALE, MASS AND FACADE LENGTH.
  
 9) PROVIDE DESCRIPTION OF HOW THE MATERIALS FOR THE 30
 FOOT ARCHITECTURAL TREATMENT ALONG WEST STREET (THE
 PORTION THAT IS NOT FENESTRATION) WILL SATISFY THE
 REQUIREMENT.
  
 10) THE ACTIVE USE DIAGRAMS CONTAIN INACCURACIES
 (INCONSISTENT FRONTAGES, INCORRECT TOTALS, AND
 INCORRECT MEASURE POINTS). PLEASE REVIEW THE DRAWINGS
 FOR ACCURACY. ANY CHANGES NEED TO BE REFLECTED ON THE
 ACTIVE USE SUMMARY TABLE ON SHEET A0.01
  
 A. IT APPEARS THAT THE HIBISCUS FRONTAGE MEETS THE
 ACTIVE USE REQUIREMENTS.
 B. LEVEL 3 DOES NOT MEET THE MINIMUM 60% ACTIVE USE
 REQUIREMENT. THE OUTDOOR DINING AND PASSAGEWAY MAY NOT
 BE COUNTED AS ACTIVE USE ABOVE THE GROUND FLOOR.
  
 11) THE PORTION OF THE BUILDING ALONG ROSEMARY BEHIND
 THE OUTDOOR DINING DOES NOT MEET THE SETBACK
 REQUIREMENT THAT THE BUILDING BE BETWEEN 35 AND 50 FEET
 FROM THE CENTERLINE OF ROSEMARY. IF THE OUTDOOR DINING
 AREA IS DESIGNED AS A PUBLIC OPEN SPACE, THEN THE
 BUILDING AS DESIGNED MEETS THE SETBACK ALLOWANCES.
 PLEASE PROVIDE HOW THE OUTDOOR DINING AREA COMPLIES
 WITH ONE OF THE TYPES OF PUBLIC OPEN SPACE.
  
 12) THE POOL DECK AND LEVEL 5 GREEN ROOF NEED TO HAVE
 NOTES AS TO WHICH TYPE OF PRIVATE OPEN SPACE THEY ARE,
 SO THAT STAFF CAN VERIFY COMPLIANCE WITH THE REQUIRED
 STANDARDS.
  
 13) PRIVATE OPEN SPACE IS FOR THE USE OF THE BUILDING
 RESIDENTS. PLEASE DESCRIBE HOW THE LEVEL 5 GREEN ROOF
 AND THE LEVEL 4 ROOFTOP GARDEN WILL BE USED BY THE
 RESIDENTS.
  
 14) PUBLIC OPEN SPACE IS NOT PERMITTED TO BE ADJACENT
 TO BUILDING MECHANICAL SPACES, EQUIPMENT OR SERVICE
 AREAS, ETC.
  
 A. THE PORTION OF THE PUBLIC OPEN SPACE ADJACENT TO
 WEST STREET IS ADJACENT TO TRANSFORMERS THAT ARE
 REMAINING FOR 477 SOUTH ROSEMARY. THE TRANSFORMERS MUST
 BE SCREENED FROM VIEW OF THE PROPOSED PUBLIC OPEN
 SPACE, OR THE AREA MAY NOT BE COUNTED AS PUBLIC OPEN
 SPACE.
 B. THERE ARE AC UNITS MOUNTED ON RACKS THAT ARE ON THE
 BUILDING WALL OF 477 SOUTH ROSEMARY. THIS MECHANICAL
 EQUIPMENT MUST ALSO BE SCREENED FROM THE PUBLIC OPEN
 SPACE. PLEASE NOTE: IT APPEARS THAT THIS MECHANICAL
 EQUIPMENT DIRECTLY CONFLICTS WITH THE PROPOSED TREES
 ALONG THE WALL. PROVIDE A DETAIL ON HOW THE WALL
 MOUNTED MECHANICAL EQUIPMENT DOES NOT INTERFERE WITH
 THE PROPOSED LANDSCAPE AND ITS LONG TERM GROWTH.
  
 15) PUBLIC OPEN SPACE - PASSAGE REQUIREMENTS
  
 A. THE PASSAGE IS REQUIRED TO HAVE A MINIMUM OF 25 FEET
 OPENING ON BOTH SIDES.
 B. A PASSAGEWAY IS REQUIRED TO CONNECT TWO OR MORE
 PUBLIC RIGHTS-OF-WAY OR PUBLIC SPACES. WEST STREET IS
 NOT A PUBLIC RIGHT-OF-WAY (IT IS AN ACCESS EASEMENT) SO
 IT NEEDS TO INCLUDE PUBLIC ACCESS AND VISUAL
 IMPROVEMENTS TO ALLOW IT TO QUALIFY AS A PUBLIC SPACE.
 SEE COMMENT #29 FOR ACCESS IMPROVEMENTS AND COMMENT #14
 FOR VISUAL ITEMS THAT NEED TO BE ADDRESSED.
 C. PROVIDE THE DIMENSIONS FOR THE NARROW POINTS SHOWN
 IN THE PASSAGEWAY. EX. WALL TO DECORATIVE POT,
 LANDSCAPE AREA TO COLUMNS, COLUMNS TO OFFICE ENTRANCE
 WALL, ETC. THESE ALL APPEAR TO BE CHOKE POINTS IN THE
 PASSAGEWAY.
 D. THE WESTERN PORTION OF THE PASSAGEWAY IS COVERED BY
 THE UPPER RESIDENTIAL STORIES, INCLUDING BALCONIES.
 PROVIDE THE CALCULATION TO VERIFY THAT NO MORE THAN 25%
 OF THE REQUIRED OPEN SPACE IS COVERED.
  
 16) OPEN SPACE MEASUREMENTS SHALL NOT INCLUDE AREAS
 WITHIN THE MINIMUM SETBACK. PROVIDE THE SETBACK
 DIMENSION REQUIRED BY THE NFPA REQUIREMENTS FOR THE
 PORTIONS OF THE HIBISCUS TOWER LOCATED ADJACENT TO THE
 EXISTING 477 SOUTH ROSEMARY BUILDING. THIS SETBACK AREA
 MAY NOT BE COUNTED TOWARD MEETING THE PUBLIC OPEN SPACE
 SQUARE FOOTAGE REQUIREMENT.
  
 17) THE JUSTIFICATION STATEMENT COMPLIANCE TABLE AND
 THE PLANS SHOW DIFFERING VALUES FOR THE PROVIDED AMOUNT
 OF OPEN SPACE, BOTH PRIVATE AND PUBLIC.
  
 18) PROVIDE DIMENSION ON THE ELEVATION DRAWINGS FOR THE
 PROJECTING ELEMENTS. THIS INCLUDES CLEARANCE HEIGHT
 DIMENSIONS FOR THE AWNINGS AND THE TOWER BALCONIES.
  
 19) THE ALUMINUM AWNING ALONG HIBISCUS HAS A 14 FOOT
 CLEARANCE AND WILL EXTEND INTO THE BLACK OLIVE TREES IN
 THE PLANTER AREAS ADJACENT TO THE DROP OFF. THE ZLDR DO
 NOT PERMIT HORIZONTAL ENCROACHMENTS THAT INTERFERE WITH
 NORMAL ENVELOP OF STREET TREE CANOPY.
  
 20) A 24 INCH DEEP ALUMINUM AWNING IS NOT PERMITTED.
 AWNINGS ARE REQUIRED TO PROJECT A MINIMUM OF 3 FEET
 FROM THE BUILDING. THE ELEVATION PLANS LABEL THIS AS AN
 ALUMINUM SUNSHADE. SINCE ONLY ARCHITECTURAL FEATURES
 MAY EXTEND 2 FEET FROM THE BUILDING, THIS NEEDS TO BE
 LABELED AS AN ARCHITECTURAL FEATURE ON THE PLANS.
  
 21) PROVIDE THE STREET LEVEL ELEVATION BLOW-UPS WITHOUT
 THE LANDSCAPE LAYER. STAFF IS UNABLE TO SEE DETAILS.
  
 22) THE DATA IN THE PARKING TABLE FOR THE RETAIL,
 RESTAURANT AND OFFICE LINES IS LESS SQUARE FOOTAGE THAN
 WHAT IS SHOWN IN THE PROJECT DATA TABLE. ALL VALUES
 SHALL BE CONSISTENT AND CORRECT.
  
 23) PROVIDE NET AREA DRAWINGS FOR THE RESTAURANT,
 RETAIL AND OFFICE USES SO THAT STAFF CAN VERIFY THE
 PARKING SQUARE FOOTAGE PRESENTED FOR THE PARKING
 CALCULATIONS.
  
 24) THE SHARED PARKING MAY ONLY BE USED IF THERE ARE NO
 PARKING SPACES DESIGNATED FOR A PARTICULAR USE. THIS
 THEN DOES NOT PERMIT THE ABILITY TO HAVE DESIGNATED
 PARKING FOR EITHER THE RESIDENTIAL OR OFFICE USERS.
  
 25) THE PROVIDED PARKING TABLE (RE-REVIEW ONCE COMMENT
 #S 22-24 ARE ADDRESSED) SHOWS 390 PARKING SPACES
 REQUIRED FOR THE NEW HIBISCUS TOWER VS. THE 222 PARKING
 SPACES REQUIRED FOR THE MACY?S. THE PARKING
 AVAILABILITY TABLE PROVIDED BY JORDAN RATHLEV NEEDS TO
 BE FURTHER BROKEN DOWN TO VERIFY THAT THE HIBISCUS
 TOWER, THE SAPODILLA RESIDENCES AND 477 S. ROSEMARY
 HAVE SUFFICIENT PARKING SPACES IN THE GARAGE. NOTE: THE
 PARKING AVAILABILITY TABLE INDICATES THAT THERE IS
 EXCESS CAPACITY THROUGHOUT THE ENTIRE CITYPLACE CPD.
  
 26) PROVIDE THE GARAGE PLAN SHOWING WHERE THE
 RESIDENTIAL PARKING WILL OCCUR, TO INCLUDE ANY
 BARRIERS, AS WELL AS THE LOCATIONS OF THE REQUIRED
 CHARGING STATIONS AND CAR SHARE STATION.
  
 27) THE GARAGE LAYOUT IS AFFECTED BY THE NEW BRIDGE
 LOCATION SO THIS WILL NEED TO BE INCLUDED AS PART OF
 THIS APPLICATION AND SHOWN ON THE PLANS REQUIRED AS
 PART OF #26. NOTE: A SETBACK WAIVER IS REQUIRED FOR THE
 BRIDGE.
  
 28) SHOW THE ADA ROUTE FROM THE ADA PARKING SPACES IN
 THE GARAGE TO THE OFFICE AND RETAIL ENTRANCES.
  
 29) THE WEST STREET PEDESTRIAN CROSSING LOCATIONS, TO
 INCLUDE IN FRONT OF THE LOADING DOCKS, MUST BE CLEARLY
 DEFINED, PREFERABLY THROUGH THE USE OF A DIFFERENT
 PAVING MATERIAL THAN THE ROADWAY SURFACE.
  
 30) YOU WILL BE REQUIRED TO PROVIDE WAY FINDING SIGNS
 FROM THE GARAGE TO THE OFFICE, RESIDENTIAL AND RETAIL
 ENTRANCES.
  
 31) EXPLAIN THE USE OF THE RESIDENTIAL DROP OFF. IS THE
 INTENTION TO HAVE A VALET FOR THE TOWER AT THIS
 LOCATION? IF SO, PROVIDE THE VALET OPERATION PLAN, TO
 INCLUDE WHERE THE VALET AREA IS IN THE GARAGE.
  
 32) EXPLAIN THE USE OF THE OFFICE DROP OFF. IS THE
 INTENTION TO HAVE A VALET FOR THE OFFICE AT THIS
 LOCATION? IF SO, PROVIDE THE VALET OPERATION PLAN, TO
 INCLUDE WHERE THE VALET AREA IS IN THE GARAGE.
  
 33) PROVIDE THE BICYCLE WALL INSTALLATION DETAIL AT A
 BIGGER SCALE. IT IS NOT LEGIBLE ON THE PAPER PLANS.
  
 34) PROVIDE THE DIMENSIONS OF THE BICYCLE STORAGE ROOMS
 ON THE PLANS. STAFF NEEDS TO VERIFY THE NUMBER OF
 BICYCLES THAT CAN BE STORED.
 35) PROVIDE THE PASSAGEWAY BICYCLE PAD AND RACK DETAIL
 AND THE DIMENSIONS ON THE PLANS. THEY DO NOT APPEAR TO
 MEET CODE REQUIREMENTS.
  
 36) PROVIDE BICYCLE RACKS ALONG ROSEMARY FOR THE RETAIL
 CUSTOMERS. ZONING STAFF HAS NOT SEEN THE PLANS FOR THE
 HIBISCUS OR ROSEMARY RECONSTRUCTION SO IF RACKS ARE
 INCLUDED IN THESE PLANS SHOW THEM ON THE HIBISCUS TOWER
 PLANS TO ADDRESS THIS COMMENT.
  
 37) THE LANDSCAPE PLANS SHOW TRA, BUT THIS IS NOT
 LISTED ON THE PLANT LIST.
  
 38) PROVIDE GREEN ROOF DETAILS FOR LEVELS 4 AND 5 AND
 THE TOWER ROOF. NOTE: IN ACCORDANCE WITH THE
 DEVELOPMENT REGULATIONS, THE LEVEL 4 ROOF THAT DOES NOT
 INCLUDE THE MECHANICAL AND SKYLIGHT AREAS. IF SOLAR IS
 USED THIS NEEDS TO BE SHOWN. THE PLANS NEED TO FACTOR
 THIS IN NOW.
  
 39) THE LANDSCAPE PLAN SET LABELS BOLLARDS AT THE
 CORNER OF ROSEMARY AND HIBISCUS AS LIGHT POLES.
  
 40) PROVIDE VERIFICATION THAT THE FPL TRANSFORMERS
 BEING REMOVED DO NOT SERVICE 477 SOUTH ROSEMARY. NOTE:
 ANY TRANSFORMERS THAT ARE REQUIRED TO BE RELOCATED MUST
 BE SHOWN IN THEIR NEW LOCATION AS PART OF THIS PROJECT.
  
 41) THE GROUND FLOOR PLAN ON SHEET A1.01 MUST SHOW ALL
 THE PROPOSED MECHANICAL EQUIPMENT. IT FAILS TO SHOW THE
 PROPOSED BACKFLOW AND GAS METERS ALONG THE WEST STREET
 SHOWN ON SHEET P1.01. NOTE: STAFF WILL NOT SUPPORT THE
 PROPOSED LOCATION OF THE MECHANICAL EQUIPMENT IT IS
 BLOCKING THE SIDEWALK. ADDITIONALLY, THE CITYPLACE DRI
 REQUIRES THE SCREENING OF MECHANICAL EQUIPMENT, WHICH
 THE PROPOSED PLAN DOES NOT SHOW.
  
 42) PROVIDE THE RENDERING OF THE BUILDING IN CONTEXT
 (SIMILAR TO R0.02) FROM THE NORTH, SOUTH AND WEST
  
 43) PROVIDE GROUND LEVEL RENDERINGS OF THE BUILDING
 FROM WEST ON HIBISCUS, AND NORTH AND SOUTH ALONG
 ROSEMARY.
  
 44) PROVIDE A SHADOW STUDY.
  
 45) THE PHOTOMETRIC PLAN SHOWS LIGHTING LEVELS AT THE
 CURB IN EXCESS OF THE PERMITTED ONE FOOT CANDLE.
  
 46) WHAT IS THE CONSTRUCTION PHASING PLAN FOR THE
 BUILDING, ROSEMARY AND THE ALLEY? WILL THE HIBISCUS
 RIGHT-OF-WAY, INCLUDING THE SIDEWALK, BE COMPLETED
 PRIOR TO THE CONSTRUCTION OF THE BUILDING? HOW WILL
 ACCESS BE PROVIDED TO THE TOWNHOUSES AND THE SERVICE TO
 477 SOUTH ROSEMARY DURING CONSTRUCTION?
  
 47) EXPLAIN THE BAR IN THE RESIDENTIAL LOBBY AREA. WHO
 DOES THIS SERVE? WHAT DOES IT SERVE?
  
 48) TURN THE LIFE SAFETY DISTANCE LAYER OF ON THE
 RESUBMITTAL PLANS.
  
 49) DESCRIBE HOW THE ROOFTOP RAINWATER WILL BE STORED
 ON-SITE. THE METHOD MAY IMPACT THE SITE PLAN. THE
 PAVING AND DRAINAGE PLAN DOES NOT SEEM TO COVER THIS
 REQUIREMENT.
  
 50) THE PLAZA ON-SITE STORMWATER RETENTION NEEDS TO BE
 EXPLAINED SINCE THE DIFFERING METHODS AFFECT THE SITE
 PLAN. THE PAVING AND DRAINAGE PLAN DOES NOT SEEM TO
 COVER THIS REQUIREMENT.
  
 51) STAFF IS STILL ANALYZING THE VEHICLE TRIP
 GENERATION AS IT RELATES TO THE TROLLEY OPERATION
 CONTRIBUTION.
  
  
  