Plan Review Stops For Project Z19050015
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 06-12-2019 Cont ID  
Sent By rbrown Date 06-12-2019 Time 10:21 Rev Time 0.00
Received By rbrown Date 06-12-2019 Time 10:21 Sent To  
Notes
2019-06-11 21:00:40DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. SEWER LINE INTERCEPTOR. A SEWER LINE INTERCEPTOR
 WILL BE REQUIRED. PLEASE CONTACT JEFFREY ODOMS,
 UTILITIES O&M SUPERINTENDENT, PUBLIC UTILITIES
 DEPARTMENT, FATS OILS AND GREASE DIVISION, AT (561)
 822-2172, OR BY EMAIL: [email protected]
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 07-23-2019 Cont ID  
Sent By rrossano Date 07-23-2019 Time   Rev Time 0.00
Received By rrossano Date 07-23-2019 Time   Sent To  
Notes
2019-07-23 12:37:39THE ENGINEERING REVIEW FOR THE PPRC SUBMITTAL
 (Z19050015) HAS BEEN PASSED WITH THE FOLLOWING PROVISOS
 THAT MUST BE INCLUDED WITH THE FORMAL ENGINEERING
 SUBMITTAL. PLEASE RESPOND TO ALL COMMENTS IN WRITING
 WITH YOUR FORMAL ENGINEERING SUBMITTAL.
  
 1. PLEASE CALL OUT CITY POINT OF SERVICE.
 2. PLEASE RELOCATE EXISTING METER TO BACK OF SIDEWALK
 IN EASEMENT.
 3. SHOW AN EASEMENT LARGE ENOUGH TO ACCOMMODATE TWO
 METERS.
 4. THE SECOND SKETCH LAYOUT MAY BE MORE COST-EFFECTIVE
 ? LESS MATERIALS USED.
 5. EXISTING 6 INCH WILL NEED TO BE NOTED TO BE
 RESTRAINED. PLEASE ADD CITY OF WPB PRESSURE PIPE
 DETAILS P-3 AND P-6.
 6. 18 INCH DIAMETER STORMWATER PIPE CONNECTING TO CITY
 RIGHT OF WAY AT GREENWOOD AVE. SHALL BE CONSTRUCTED OF
 CONCRETE MATERIAL NOT HDPE.
 7. SHOW 8 INCH DIAMETER WATER MAIN AND 8 INCH SANITARY
 STUB NEAR NORTH DRIVEWAY AT MANHOLE NUMBER SSM00341.
 SEE GIS AND ASBUILT FOR YOUR USE.
 8. IDENTIFY ANY ONSITE IRRIGATION OR WATER WELLS. SEE
 SHEET C6 WHICH SHOWS AN ONSITE IRRIGATION VAULT.
 9. PLEASE IDENTIFY LINE G AS CALLED OUT ON SHEET C-10
 EXTENDING ON TO GREENWOOD AVE. (GAS?)
 10. SHOW BELLSOUTH MANHOLE ON PLANS AT SOUTH DRIVEWAY
 NEAR WATER METERS, WHICH MAY BE IN CONFLICT WITH
 PROPOSED WATER.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By rrossano Date 06-07-2019 Time   Rev Time 2.00
Received By rrossano Date 06-07-2019 Time   Sent To  
Notes
2019-06-07 07:52:47THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS
 AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE
 DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER
 UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT
 PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW:
 HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W
 EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P
 ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19
 60045731D3658206F27451722716EF
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
  
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
  
 PROVIDE CALCULATIONS ON PLANS FOR FIRE FLOW DEMANDS.
 CALCULATIONS SHALL BE PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
  
 A COPY OF THE CITY OF WPB WATER SERVICE CARDS FOR 5601
 AND 5601A GREENWOOD AVE. HAVE BEEN PROVIDED FOR YOUR
 USE. PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL
 CITY OF WEST PALM BEACH-OWNED UTILITIES WITHIN THE
 PUBLIC RIGHT OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS
 OF YOUR PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION,
 PIPE MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE
 TARBILL IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY. PROVIDE PROFILE AND CLEARANCES AT ALL
 UTILITY CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2 INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 RELOCATE BACKFLOW ON TO PRIVATE PROPERTY, OUTSIDE OF
 PROPOSED UTILITY EASEMENT FOR PLACEMENT OF PROPOSED
 WATER METER. A SMALLER EASEMENT MAY BE SUFFICIENT FOR
 METER PLACEMENT.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 06-04-2019 Cont ID  
Sent By pleduc Date 06-04-2019 Time   Rev Time 0.00
Received By pleduc Date 06-04-2019 Time 11:37 Sent To  
Notes
2019-06-04 11:45:06THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 CEMETORY EQUIPEMNT SHALL COMPLY WITH NFPA? 86, STANDARD
 FOR OVENS AND FURNACES, 2015 EDITION.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 A 4" FIRE LINE IS INDICATED; HOWEVER, IT IS NOT CLEAR
 WHAT THAT WILL SERVE. PLEASE CLARIFY.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THERE DID NOT APPEAR TO BE A FIRE HYDRANT LOCATED AT
 THE PROPOSED BUILDING. PLEASE CLARIFY.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED WITHIN 100' OF EACH OTHER AND
 ON THE SAME SIDE OF THE STREET OR ACCESS ROADWAY(IF
 POSSIBLE) TO ALLOW FREE ACCESS FOR OTHER ARRIVING
 EMERGENCY VEHICLES.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS, KNOW PADLOCKS OR KEY SWITCHES FOR ANY
 GATES, BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 09-20-2019 Cont ID  
Sent By rcaranci Date 09-20-2019 Time 15:50 Rev Time 0.00
Received By rcaranci Date 09-20-2019 Time 15:50 Sent To  
Notes
2019-09-20 15:50:47FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PCC& CREMATORY FACILITY Z19050015
 SEPTEMBER 20, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. DUE TO THE RECONFIGURATION OF THE LOT
 LINES FOR THE PARCEL AND THE CONSTRUCTION OF THE NEW
 BUILDING, ALL NEWLY DRAWN LOT LINES, NEW BUILDING AND
 PARKING AREAS MUST COMPLY WITH CURRENT LANDSCAPE
 REQUIREMENTS. EXISTING PARKING AND BUILDING AREAS
 SHOULD HAVE EXISTING NONCONFORMITIES REDUCED WHERE
 POSSIBLE. STAFF COMMENTS WILL ADDRESS ALL AREAS OF THE
 SITE.
 ALL NEWLY CONSTRUCTED BUILDINGS, PARKING AREAS, AND
 NEWLY DRAWN LOT LINES MUST MEET CURRENT CODE
 REQUIREMENTS.
  
 2. SATISFIED. PER SECTION 94-448 (D)(3), ALL NATIVE
 TREES AND PALMS IN GOOD CONDITION MUST BE PRESERVED ON
 SITE OR RELOCATED. THERE ARE MULTIPLE LIVE OAKS,
 MAHOGANY AND ROYAL PALMS PROPOSED TO BE REMOVED, AND
 THE SITE ELEMENTS AND UTILITIES CAN BE DESIGNED TO
 AVOID REMOVAL OR RELOCATE THEM TO LOCATIONS TO MEET
 LANDSCAPE REQUIREMENTS.
 TWO SEPARATE TREE DISPOSITION CHARTS ARE INCLUDED THAT
 ARE NOT CONSISTENT WITH THE COMMENT RESPONSE. THE CHART
 ON SHEET L-01 STILL SHOWS NATIVE TREES LISTED IN GOOD
 CONDITION AS BEING REMOVED, AND THE CHART ON SHEET L-03
 SHOWS ALL TREES TO REMAIN AND TWO TREES RELOCATED.
 PROVIDE A CONSISTENT PLAN TO MEET THE CODE REQUIREMENT.
  
 3. SATISFIED. PROVIDE AN EXHIBIT SHOWING THE PARKING
 AREA SURFACE CALCULATIONS, PARKING SPACE AREAS AND
 LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE WITH
 SECTIONS 94-443 (C)(3) AND (4).
 NEW PAVED AREAS NEED TO MEET CODE REQUIREMENTS, SEE
 FIGURE XIV-1 LANDSCAPE AREAS FOR PARKING LOTS IN
 SECTION 94-443(C)(3) FOR THE AREAS THAT QUALIFY AS
 INTERIOR LANDSCAPING FOR VEHICULAR USE AREA. REVISE
 AREAS ON SHEET L-02A WITH AREAS DEFINED PER THE FIGURE.
  
 4. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 5. SATISFIED. SHOW THE REQUIRED 5 FOOT WIDE LANDSCAPE
 BUFFER ALONG ALL PROPERTY LINES AND PROVIDE SEGMENT
 LENGTH AND CALCULATIONS TO SHOW REQUIRED AND PROVIDED
 BUFFER TREE COUNTS PER SECTION 94-443(B). THE CODE
 ALLOWS FLEXIBILITY THAT THE REQUIRED BUFFER TREES CAN
 BE PLACED WITHIN THE PROPERTY ADJACENT TO THE BUFFER,
 AND SCREENING HEDGES ARE REQUIRED ALONG ANY PARKING
 AREAS.
 PROVIDE THE REQUIRED BUFFER LENGTH AND REQUIRED AND
 PROVIDED TREE CALCULATIONS FOR ALL NEWLY DRAWN LOT
 LINES.
  
 6. SATISFIED. PROVIDE ROOT BARRIER LOCATIONS WHERE
 NEEDED TO PROTECT UTILITIES.
  
 7. SATISFIED. BASED ON 68064 SQ FT REQUIRED OPEN SPACE,
 REVISE THE REQUIRED TREE CALCULATIONS TO 46 REQUIRED,
 AND FLOWERING TREES TO 12.
  
 8. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE
 CHART AND PROVIDE THE REQUIRED 50 POINTS PER SECTION
 94-442(G).
 9. SATISFIED. PER SECTION 94-445 L. PLANT SPECIES. A
 MINIMUM OF 60 PERCENT OF PLANT MATERIAL ADDED SHALL BE
 FLORIDA NATIVE OR DROUGHT TOLERANT SPECIES SELECTED
 FROM THE CITY LIST OR THE LIST OF SPECIES IN THE MOST
 RECENT EDITION OF SOUTH FLORIDA WATER MANAGEMENT
 DISTRICT WATERWISE SOUTH FLORIDA LANDSCAPES. SHOW
 COMPLIANCE BY PROVIDING THE ACTUAL PERCENTAGE BASED ON
 THE PLANT LIST.
 PERCENTAGE SHOWN MUST INCLUDE ALL ADDED PLANTS ON THE
 PLANT LIST.
 10. SATISFIED. GAS LINE NEEDS TO BE SHIFTED OUT OF THE
 LANDSCAPE ISLAND.
 11. SATISFIED. CORRECT NOTES SECTION TO READ WEST PALM
 BEACH INSTEAD OF PALM BEACH COUNTY.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 07-30-2019 Cont ID  
Sent By rcaranci Date 07-30-2019 Time 17:09 Rev Time 0.00
Received By rcaranci Date 07-30-2019 Time 17:09 Sent To  
Notes
2019-07-30 17:11:19FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PCC& CREMATORY FACILITY Z19050015
 JULY 30, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PARTIALLY SATISFIED. DUE TO THE RECONFIGURATION OF
 THE LOT LINES FOR THE PARCEL AND THE CONSTRUCTION OF
 THE NEW BUILDING, ALL NEWLY DRAWN LOT LINES, NEW
 BUILDING AND PARKING AREAS MUST COMPLY WITH CURRENT
 LANDSCAPE REQUIREMENTS. EXISTING PARKING AND BUILDING
 AREAS SHOULD HAVE EXISTING NONCONFORMITIES REDUCED
 WHERE POSSIBLE. STAFF COMMENTS WILL ADDRESS ALL AREAS
 OF THE SITE.
  
 ALL NEWLY CONSTRUCTED BUILDINGS, PARKING AREAS, AND
 NEWLY DRAWN LOT LINES MUST MEET CURRENT CODE
 REQUIREMENTS.
  
 2. PARTIALLY SATISFIED. PER SECTION 94-448 (D)(3), ALL
 NATIVE TREES AND PALMS IN GOOD CONDITION MUST BE
 PRESERVED ON SITE OR RELOCATED. THERE ARE MULTIPLE LIVE
 OAKS, MAHOGANY AND ROYAL PALMS PROPOSED TO BE REMOVED,
 AND THE SITE ELEMENTS AND UTILITIES CAN BE DESIGNED TO
 AVOID REMOVAL OR RELOCATE THEM TO LOCATIONS TO MEET
 LANDSCAPE REQUIREMENTS.
  
 TWO SEPARATE TREE DISPOSITION CHARTS ARE INCLUDED THAT
 ARE NOT CONSISTENT WITH THE COMMENT RESPONSE. THE CHART
 ON SHEET L-01 STILL SHOWS NATIVE TREES LISTED IN GOOD
 CONDITION AS BEING REMOVED, AND THE CHART ON SHEET L-03
 SHOWS ALL TREES TO REMAIN AND TWO TREES RELOCATED.
 PROVIDE A CONSISTENT PLAN TO MEET THE CODE REQUIREMENT.
  
 3. PARTIALLY SATISFIED. PROVIDE AN EXHIBIT SHOWING THE
 PARKING AREA SURFACE CALCULATIONS, PARKING SPACE AREAS
 AND LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE
 WITH SECTIONS 94-443 (C)(3) AND (4).
  
 NEW PAVED AREAS NEED TO MEET CODE REQUIREMENTS, SEE
 FIGURE XIV-1 LANDSCAPE AREAS FOR PARKING LOTS IN
 SECTION 94-443(C)(3) FOR THE AREAS THAT QUALIFY AS
 INTERIOR LANDSCAPING FOR VEHICULAR USE AREA. REVISE
 AREAS ON SHEET L-02A WITH AREAS DEFINED PER THE FIGURE.
  
 4. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 5. PARTIALLY SATISFIED. SHOW THE REQUIRED 5 FOOT WIDE
 LANDSCAPE BUFFER ALONG ALL PROPERTY LINES AND PROVIDE
 SEGMENT LENGTH AND CALCULATIONS TO SHOW REQUIRED AND
 PROVIDED BUFFER TREE COUNTS PER SECTION 94-443(B). THE
 CODE ALLOWS FLEXIBILITY THAT THE REQUIRED BUFFER TREES
 CAN BE PLACED WITHIN THE PROPERTY ADJACENT TO THE
 BUFFER, AND SCREENING HEDGES ARE REQUIRED ALONG ANY
 PARKING AREAS.
  
 PROVIDE THE REQUIRED BUFFER LENGTH AND REQUIRED AND
 PROVIDED TREE CALCULATIONS FOR ALL NEWLY DRAWN LOT
 LINES.
  
 6. SATISFIED. PROVIDE ROOT BARRIER LOCATIONS WHERE
 NEEDED TO PROTECT UTILITIES.
  
 7. SATISFIED. BASED ON 68064 SQ FT REQUIRED OPEN SPACE,
 REVISE THE REQUIRED TREE CALCULATIONS TO 46 REQUIRED,
 AND FLOWERING TREES TO 12.
  
 8. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE
 CHART AND PROVIDE THE REQUIRED 50 POINTS PER SECTION
 94-442(G).
  
 9. PARTIALLY SATISFIED. PER SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. SHOW COMPLIANCE BY PROVIDING THE ACTUAL
 PERCENTAGE BASED ON THE PLANT LIST.
  
 PERCENTAGE SHOWN MUST INCLUDE ALL ADDED PLANTS ON THE
 PLANT LIST.
  
 10. SATISFIED. GAS LINE NEEDS TO BE SHIFTED OUT OF THE
 LANDSCAPE ISLAND.
  
 11. SATISFIED. CORRECT NOTES SECTION TO READ WEST PALM
 BEACH INSTEAD OF PALM BEACH COUNTY.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By rcaranci Date 06-07-2019 Time 16:51 Rev Time 0.00
Received By rcaranci Date 06-07-2019 Time 16:51 Sent To  
Notes
2019-06-07 16:52:29FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PCC& CREMATORY FACILITY Z19050015
 JUNE 7, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. DUE TO THE RECONFIGURATION OF THE LOT LINES FOR THE
 PARCEL AND THE CONSTRUCTION OF THE NEW BUILDING, ALL
 NEWLY DRAWN LOT LINES, NEW BUILDING AND PARKING AREAS
 MUST COMPLY WITH CURRENT LANDSCAPE REQUIREMENTS.
 EXISTING PARKING AND BUILDING AREAS SHOULD HAVE
 EXISTING NONCONFORMITIES REDUCED WHERE POSSIBLE. STAFF
 COMMENTS WILL ADDRESS ALL AREAS OF THE SITE.
  
 2. PER SECTION 94-448 (D)(3), ALL NATIVE TREES AND
 PALMS IN GOOD CONDITION MUST BE PRESERVED ON SITE OR
 RELOCATED. THERE ARE MULTIPLE LIVE OAKS, MAHOGANY AND
 ROYAL PALMS PROPOSED TO BE REMOVED, AND THE SITE
 ELEMENTS AND UTILITIES CAN BE DESIGNED TO AVOID REMOVAL
 OR RELOCATE THEM TO LOCATIONS TO MEET LANDSCAPE
 REQUIREMENTS.
  
 3. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE
 CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS
 PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443
 (C)(3) AND (4).
  
 4. PROVIDE LOCATIONS OF LIGHTING ON THE LANDSCAPE PLAN
 TO AVOID CONFLICTS WITH LANDSCAPING.
  
 5. SHOW THE REQUIRED 5 FOOT WIDE LANDSCAPE BUFFER ALONG
 ALL PROPERTY LINES AND PROVIDE SEGMENT LENGTH AND
 CALCULATIONS TO SHOW REQUIRED AND PROVIDED BUFFER TREE
 COUNTS PER SECTION 94-443(B). THE CODE ALLOWS
 FLEXIBILITY THAT THE REQUIRED BUFFER TREES CAN BE
 PLACED WITHIN THE PROPERTY ADJACENT TO THE BUFFER, AND
 SCREENING HEDGES ARE REQUIRED ALONG ANY PARKING AREAS.
  
 6. PROVIDE ROOT BARRIER LOCATIONS WHERE NEEDED TO
 PROTECT UTILITIES.
  
 7. BASED ON 68064 SQ FT REQUIRED OPEN SPACE, REVISE THE
 REQUIRED TREE CALCULATIONS TO 46 REQUIRED, AND
 FLOWERING TREES TO 12.
  
 8. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE CHART AND
 PROVIDE THE REQUIRED 50 POINTS PER SECTION 94-442(G).
 9. PER SECTION 94-445 L. PLANT SPECIES. A MINIMUM OF 60
 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE
 OR DROUGHT TOLERANT SPECIES SELECTED FROM THE CITY LIST
 OR THE LIST OF SPECIES IN THE MOST RECENT EDITION OF
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. SHOW COMPLIANCE BY PROVIDING THE
 ACTUAL PERCENTAGE BASED ON THE PLANT LIST.
 10. GAS LINE NEEDS TO BE SHIFTED OUT OF THE LANDSCAPE
 ISLAND.
 11. CORRECT NOTES SECTION TO READ WEST PALM BEACH
 INSTEAD OF PALM BEACH COUNTY.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 06-04-2019 Cont ID  
Sent By   Date 06-04-2019 Time   Rev Time  
Received By   Date 06-04-2019 Time   Sent To  
Notes
2019-06-04 15:14:34PLEASE PROVIDE A PLAN SHOWING AUTO-TURN FOR SANITATION
 SERVICE ALONG WITH THE ENCLUSURE SPEC.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status P Date 07-29-2019 Cont ID  
Sent By tward Date 07-29-2019 Time 11:10 Rev Time 0.00
Received By tward Date 07-29-2019 Time 11:19 Sent To  
Notes
2019-07-29 11:19:04THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 7/11/19 SUBMITTAL PACKAGE:
  
 1. LABEL THE DRY RETENTION AREA AS DRY DETENTION AREA
 UNLESS IT IS SIZED TO STORE THE RUNOFF FROM THE 25-YEAR
 3-DAY DESIGN STORM WITH NO DISCHARGE.
  
 2. PROVIDE ADIDITIONAL FREEBOARD BETWEEN THE WEIR
 ELEVATION IN STRUCTURE CS AND THE TOP OF BERM AROUND
 THE RETENTION AREA.THE RETENTION AREA WILL SPILL OVER
 ONTO THE ACCESS ROAD AND DOWN THE DRIVEWAY AS WATER
 FLOWS OVER THE WEIR.
  
 3. PROPOSED FPL EASEMENT LINES ARE NOT SHOWN ON THE
 SITE PLAN.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-10-2019 Cont ID  
Sent By tward Date 06-10-2019 Time 18:42 Rev Time 0.00
Received By tward Date 06-10-2019 Time 18:44 Sent To  
Notes
2019-06-10 18:43:53THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. ADD VERTICAL DATUM REFERENCE TO ALL SHEETS
 CONTAINING ELEVATION INFORMATION (SHEETS C-03, C-04,
 C-05, C-09).
  
 2. WHAT ARE THE TWO TRANSVERSE STRIPED AREAS IN THE
 PARKING LOT NORTH OF THE PERSONAL CARE CENTER TO BE
 USED FOR?
  
 3. CONSIDER REDUCING THE DEPTH OF THE PARKING SPACES
 AND HAVING A TWO-FOOT OVERHANG ON THE NORTH SIDE OF THE
 PARKING LOT NORTH OF THE PERSONAL CARE CENTER.
  
 4. GREENWOOD AVE IS MAINTAINED BY PALM BEACH COUNTY.
 COUNTY PERMITS WILL BE NEEDED FOR WORK WITHIN THE
 RIGHT-OF-WAY. COUNTY DETAILS MAY NEED TO BE INCLUDED IN
 THE PLANS.
  
 5. DRAINAGE SYSTEM TO BE DESIGNED TO MEET SFWMD
 CRITERIA FOR WATER QUALITY TREATMENT AND PEAK FLOW
 ATTENUATION.
  
 6. IS CROSSWALK STRIPING NEEDED TO NEW HANDICAP PARKING
 SPACES EAST OF THE EXISTING BUILDING?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PRIOR TO STARTING
 CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 08-01-2019 Cont ID  
Sent By vnoel Date 08-01-2019 Time 08:08 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-08-01 08:10:52PASSED WITH CONDITIONS:
  
 1. REVISE SURVEY BASED ON TITLE SEARCH.
 2. APPLICATION MADE THRU PLANNING FOR MINOR
 SUBDIVISION.
 3. OBTAIN COUNTY APPROVAL FOR GREENWOOD.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-07-2019 Cont ID  
Sent By vnoel Date 06-07-2019 Time 11:30 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2019-06-07 11:38:341. REPLAT WILL BE REQUIRED. CURRENT OWNERSHIP AS
 SURVEYED IS IN TWO PARTIES.
 2. IS THERE A PROPOSED FPL EASEMENT WITHIN THE PROPOSED
 DRY RETENTION?
 3. ANY WORK WITHIN GREENWOOD WILL REQUIRE COUNTY
 PERMIT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status P Date   Cont ID  
Sent By   Date 06-12-2019 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2019-06-12 09:15:25NO COMMENTS.
  
 LINA M. CAMACHO
 SENIOR PROJECT ENGINEER
 561-494-1129
 [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 09-24-2019 Cont ID  
Sent By   Date 09-24-2019 Time   Rev Time 0.00
Received By   Date 09-24-2019 Time   Sent To  
Notes
2019-11-20 13:08:27PER APPROVAL LETTER ISSUED ON 9/24/2019.

Review Stop Z ZONING
Rev No 2 Status F Date 08-05-2019 Cont ID  
Sent By pgreilic Date 08-05-2019 Time 10:16 Rev Time 0.00
Received By pgreilic Date 08-05-2019 Time 10:16 Sent To  
Notes
2019-08-05 10:17:19PCC & CREMATORY INFORMAL SITE PLAN REVIEW
 ISPR 19-03
 Z19050015
  
 1. EXPAND WALKWAY ON SOUTH SIDE OF PROPOSED PERSONAL
 CARE CENTER TO 7 FEET, CONSISTENT WITH NORTH WALKWAY
  
 2. PROVIDE A SIDEWALK OR PEDESTRIAN ROUTE FROM
 GREENWOOD AVENUE
  
 3. ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION
  
 4. PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC
 UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT
 ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE
 WITH THE PROVISION OF THEIR SERVICES: AT&T, FPU, FPL,
 AND COMCAST
  
 5. A REPLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO
 ISSUANCE OF FINAL CERTIFICATE OF OCCUPANCY FOR THE
 PROPOSED PERSONAL CARE CENTER
  
 6. STAFF SUPPORTS ADDING ARCHITECTURAL
 FEATURES/EMBELLISHMENT ON THE PROPOSED BUILDING,
 PARTICULARLY THE EAST ELEVATION, WHICH COMPLEMENT THE
 EXISTING ARCHITECTURE OF THE EXISTING BUILDING AND
 ENHANCE THE SITE
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-12-2019 Cont ID  
Sent By pgreilic Date 06-12-2019 Time 09:42 Rev Time 0.00
Received By pgreilic Date 06-12-2019 Time 09:42 Sent To  
Notes
2019-06-12 09:43:11PCC & CREMATORY INFORMAL SITE PLAN REVIEW
 ISPR 19-03
 Z19050015
  
 ---ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION
  
 ---PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC
 UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT
 ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE
 WITH THE PROVISION OF THEIR SERVICES: AT&T, FPU, FPL,
 AND COMCAST
  
 ---REDUCE THE DEPTH OF PARKING SPACES WHERE POSSIBLE BY
 INCLUDING A 2-FOOT GRASS OVERHANG. THE CURB WOULD
 FUNCTION AS WHEEL STOPS. ALSO CONSIDER THE INCLUSION OF
 SMALL CAR SPACES TO REDUCE OVERALL IMPERVIOUS SURFACE
 AREA
  
 ---A REPLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO
 ISSUANCE OF FINAL CERTIFICATE OF OCCUPANCY FOR THE
 PROPOSED PERSONAL CARE CENTER
  
 ---PROVIDE BIKE RACK ON SITE WITH CURRENT CITY DETAIL
 PURSUANT TO SECTION 94-485
  
 ---PROVIDE CITY OF WEST PALM BEACH STANDARD DETAILS FOR
 PARKING SPACES, BIKE RACKS, DUMPSTER
  
 ---ENHANCE PEDESTRIAN ACCESS AND CIRCULATION TO AND
 THROUGHOUT THE SITE. THIS CAN BE ACCOMPLISHED BY
 PROVIDING A SIDEWALK CONNECTION FROM GREENWOOD AVENUE
 TO CONNECT TO EXISTING SIDEWALKS, ADDING STRATEGICALLY
 PLACED LINKS, AND BY STRIPING CROSSWALKS INTERNAL TO
 THE SITE. THERE SHOULD ALSO BE A DESIGNATED PEDESTRIAN
 ROUTE BETWEEN THE EXISTING AND PROPOSED BUILDING TO
 ACCOMMODATE INTERNAL PEDESTRIAN CIRCULATION AND ACCESS
 BETWEEN THE TWO BUILDINGS
  
 ---EXPAND THE SIDEWALK ON THE SOUTH SIDE OF THE
 PROPOSED BUILDING TO 7 FEET, CONSISTENT WITH THE
 SIDEWALK ON THE NORTH SIDE OF THE BUILDING
  
 ---RELOCATE THE PROPOSED CHAIN LINK FENCE TO ALONG THE
 PROPERTY LINE AND PROVIDE LANDSCAPE SCREENING
  
 ---STAFF SUPPORTS A THOUGHTFUL CONSIDERATION OF WHERE
 THE REQUIRED LANDSCAPING SHOULD BE PLACED ON THE SITE.
 FOR EXAMPLE, THE REQUIRED TREES ON THE NORTHERN BUFFER
 OF THE SITE CAN BE STAGGERED AT INTERVALS ON EITHER
 SIDE OF THE ROAD TO FRAME THE NEW ACCESS ROAD, AND
 PROVIDE A FOCAL POINT FOR THE ACCESS ROAD
  
 ---STAFF SUPPORTS ADDING ARCHITECTURAL
 FEATURES/EMBELLISHMENT ON THE PROPOSED BUILDING,
 PARTICULARLY THE EAST ELEVATION, WHICH COMPLEMENT THE
 EXISTING ARCHITECTURE OF THE EXISTING BUILDING AND
 ENHANCE THE SITE
  
  
 ***WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15
 (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON
 THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS.
  
 ***PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 ***CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443
 IF THERE ARE ANY QUESTIONS
  