Plan Review Details - Project Z19040051
Plan Review Stops For Project Z19040051
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 08-05-2019 Cont ID  
Sent By skennedy Date 08-05-2019 Time 16:47 Rev Time 0.00
Received By skennedy Date 08-05-2019 Time 16:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 05-21-2019 Cont ID  
Sent By eschneid Date 05-21-2019 Time   Rev Time 0.00
Received By pleduc Date 05-21-2019 Time 11:15 Sent To  
Notes
2019-07-19 11:12:12 
  
2019-05-21 10:36:28PER STEVEN KENNEDY, ASSISTANT BUILDING OFFICIAL:
  
 PROVIDE INFORMATION TO VERIFY THAT THE LIFE SAFETY
 EGRESS IS BEING MAINTAINED WITH THE NEW PLAZA
 CONFIGURATION.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 07-19-2019 Cont ID  
Sent By pleduc Date 07-19-2019 Time   Rev Time 0.00
Received By pleduc Date 07-19-2019 Time 11:09 Sent To  
Notes
2019-07-19 11:13:212ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM ERIC
 SCHNEIDER, PRINCIPLE PLANNER, AND THE ATTACHMENTS DATED
 JULY 3, 2019, FROM GENTILE, GLAS, HOLLOWAY, O'MAHONEY &
 ASSOCIATES, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 05-22-2019 Cont ID  
Sent By pleduc Date 05-22-2019 Time   Rev Time 0.00
Received By pleduc Date 05-22-2019 Time 10:31 Sent To  
Notes
2019-05-22 10:40:32THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1) THERE IS NO INDICATION OF OCCUPANCY LOADS, TRAVEL
 PATHS, THAT SHOW COMPLIANCE WITH THE FLORIDA FIRE
 PREVENTION CODE.
  
 A LIFE SAFETY REVIEW IS REQUIRED TO SHOW OCCUPANCY
 LOADS, EXIT WIDTHS, TRAVEL DISTANCES, EXIT
 INDENTIFICATION/SIGNS, ETC.
  
  
  
 2) THERE ARE GATES INDICATED THAT APPEAR TO BE EXITS.
  
 HOW WILL THESE GATES OPERATE AND TYPE OF EXIT HARDWARE?
  
  
  
 3) THERE IS A SMALL ROOM/SPACE INDICATED/LABELED
 DIFFERENTLY(STORAGE/PRE-FUNCTION) ON TWO SPEARATE
 SHEETS.
  
 WHAT WILL THIS SMNALL ROOM/SPACE BE USED FOR?
  
  
  
 4) THERE APPEARS TO BE AN EXIT GATE ON THE WEST SIDE
 THAT CONVERGES ON THE EXIT WALKWAY OF THE CONVENTION
 CENTER THAT HAS MULTIPLE EXITS DOORS.
  
 PER # 1 ABOVE PLEASE INDICATE THAT THE COMBINED
 PROPOSED OCCUPANCY LOAD OF BOTH AREAS DOES NOT EXCEED
 THE WITH OF THE WALKWAY.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 07-30-2019 Cont ID  
Sent By rcaranci Date 07-30-2019 Time 14:28 Rev Time 0.00
Received By rcaranci Date 07-30-2019 Time 14:28 Sent To  
Notes
2019-07-30 14:30:59FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: CONVENTION CENTER PLAZA Z19040051
 JULY 30, 2019
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. REVISE THE TREE MITIGATION DATA TO ADD A
 LIST AND NUMBER THE BLACK IRONWOOD TREES AND PROVIDE
 CANOPY SIZES AND CONDITION OF EACH TREE. PROVIDE A
 MITIGATION SHEET SHOWING PROPOSED RELOCATED POSITIONS.
 NATIVE TREES IN GOOD CONDITION MUST BE RELOCATED.
  
 2. SATISFIED. MITIGATION FOR ANY TREES MUST BE PROVIDED
 WITH NEW TREES UNLESS THE OVERALL PLAN FOR THE SITE CAN
 BE SHOWN TO NOT EXCEED THE 35% PALM SUBSTITUTION.
  
 3. SATISFIED. ADJUST THE SHADING ON THE ROOT BARRIER
 DETAIL SO IT IS VISIBLE.
  
 4. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE
 CHART SHOWING THE REQUIRED 50 POINTS PER SECTION 94-448
 (G).
  
 5. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. PRIOR TO SUBMISSION OF THE LANDSCAPE PERMIT, THE
 FLORIDA FRIENDLY LANDSCAPE DESIGN OPTIONS CHART SHALL
 BE REVISED TO REFLECT CURRENT CODE.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-23-2019 Cont ID  
Sent By rcaranci Date 05-23-2019 Time 13:40 Rev Time 0.00
Received By rcaranci Date 05-23-2019 Time 13:39 Sent To  
Notes
2019-05-23 13:41:32FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: CONVENTION CENTER PLAZA Z19040051
 MAY 23, 2019
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. REVISE THE TREE MITIGATION DATA TO ADD A LIST AND
 NUMBER THE BLACK IRONWOOD TREES AND PROVIDE CANOPY
 SIZES AND CONDITION OF EACH TREE. PROVIDE A MITIGATION
 SHEET SHOWING PROPOSED RELOCATED POSITIONS. NATIVE
 TREES IN GOOD CONDITION MUST BE RELOCATED.
  
 2. MITIGATION FOR ANY TREES MUST BE PROVIDED WITH NEW
 TREES UNLESS THE OVERALL PLAN FOR THE SITE CAN BE SHOWN
 TO NOT EXCEED THE 35% PALM SUBSTITUTION.
  
 3. ADJUST THE SHADING ON THE ROOT BARRIER DETAIL SO IT
 IS VISIBLE.
  
 4. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE CHART SHOWING
 THE REQUIRED 50 POINTS PER SECTION 94-448 (G).
  
 5. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 08-01-2019 Cont ID  
Sent By tward Date 08-01-2019 Time 10:41 Rev Time 0.00
Received By tward Date 08-01-2019 Time 10:42 Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 05-20-2019 Cont ID  
Sent By tward Date 05-20-2019 Time 13:12 Rev Time 0.00
Received By tward Date 05-20-2019 Time 13:13 Sent To  
Notes
2019-05-20 13:12:46THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE MAY
 9, 2019 PACKAGE:
  
 1. SHOW NORTH ARROW ON SHEET A101.
 2. NO CIVIL PLANS TO REVIEW.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop Z ZONING
Rev No 2 Status P Date 08-05-2019 Cont ID  
Sent By eschneid Date 08-05-2019 Time 16:17 Rev Time 0.25
Received By eschneid Date 08-05-2019 Time 15:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 05-21-2019 Cont ID  
Sent By eschneid Date 05-21-2019 Time 10:33 Rev Time 0.75
Received By eschneid Date 05-21-2019 Time 08:56 Sent To  
Notes
2019-05-21 10:33:58CASE NO. PB 950NNNNN
 PALM BEACH COUNTY CONVENTION CENTER COURTYARD
 RECONFIGURATION
 650 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY JULY 21, 2019), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) PLEASE DESCRIBE WHAT THE AREA LISTED AS "STAGING
 AREA" ON SOME PLANS AND "SERVICE AREA" ON OTHERS WILL
 BE USED FOR. IS IT PUBLIC ACCESS?
  
 2) THE ENLARGED SITE PLAN, SHEET A102, ONLY SHOWS THE
 ?FIXED BOLLARDS?. THE ENTIRE "SCULPTURAL SCREEN" NEEDS
 TO BE SHOWN AS IT IS ON THE REMAINDER OF THE PLANS.
  