Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 05-06-2019 Cont ID  
Sent By rbrown Date 05-06-2019 Time 19:17 Rev Time 0.00
Received By rbrown Date 05-06-2019 Time 19:17 Sent To  
Notes
2019-05-06 19:27:12DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. LOCATION OF ACCESSIBLE PARKING SPACES. SITE PLAN,
 SHEET SP-1, SHOWS THAT THE ACCESSIBLE PARKING SPACES
 ARE NOT THE CLOSEST PARKING SPACES TO THE ELEVATOR. PER
 FAIR HOUSING ACT, ACCESSIBLE PARKING SPACES ARE TO BE
 LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM
 ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE. LOCATION OF
 THE ACCESSIBLE PARKING SPACES CLOSEST TO THE ELEVATORS
 IS REQUIRED IN ORDER TO GIVE EQUIVALENT FACILITATION TO
 WHEELCHAIR USERS FOR ACCESS TO THE UNITS ON THE 2ND AND
 3RD FLOORS.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 8.ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT TO
 ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE ON
 THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 05-02-2019 Cont ID  
Sent By rrossano Date 05-02-2019 Time   Rev Time 0.00
Received By rrossano Date 05-02-2019 Time   Sent To  
Notes
2019-05-02 12:39:12PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 PLANS SHALL SHOW PROPOSED & EXISTING LOCATIONS AND
 DIMENSIONS OF ALL WATER, STORMWATER, AND SANITARY AND
 SEWER LINES, INCLUDING STUBS TO EACH PROPERTY LINE FOR
 WATER AND SANITARY SEWERS, THE MAKE AND MODEL OF ALL
 VALVES, METERS, AND OTHERS DEVICES TO BE INSTALLED ON
 THE SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PROVIDE PROFILE AND CLEARANCES AT ALL UTILITY
 CROSSINGS.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP UTILITIES NOT IN USE, AND REMOVE ANY
 ABANDONED UTILITY LINES LARGER THAN 2INCHES FROM CITY
 RIGHT OF WAY.
  
 PLEASE SUBMIT COMPLETED LOS ANALYSIS SUMMARY TABLE
 DIRECTLY TO ENGINEERING (SHEET 33 OF CITY OF WPB
 DEVELOPMENT APPLICATION).
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
  
 PROVIDE VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 1988 AND NGVD 1929).
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 THE CITY REQUESTS THE EXTENSION OF THE 8 IN. WATER LINE
 WITHIN THE ALLEY IMPROVEMENT AREA TO THE NORTH PROPERTY
 LINE.
  
 THE CITY REQUESTS THAT THE DEVELOPER PROVIDE SEPARATE
 TAPS FOR FIRE AND DOMESTIC SERVICES.
  
 SHEET 2.0: CORRECT THE CALL OUT FOR 6 IN. LINE FROM
 "C.A." TO CAST IRON.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 06-13-2019 Cont ID  
Sent By rrossano Date 06-13-2019 Time   Rev Time 0.00
Received By rrossano Date 06-13-2019 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 04-29-2019 Cont ID  
Sent By pleduc Date 04-29-2019 Time   Rev Time 0.00
Received By pleduc Date 04-29-2019 Time 16:56 Sent To  
Notes
2019-04-29 16:55:00THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 THE FOLLOWING COMMENTS MAY BE CONSIDERED MORE RELATED
 TO BUILDING CONSTRUCTION PLAN REVIEW;
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE..
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 THE PROPOSED LOCATION SUBMITTED ARE ACCETABLE. ANY
 CHANGES NEED TO BE REVIEWED THROUGH THE OFFICE OF THE
 FIRE MARSHAL.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. FIRE LANE IDENTIFICATION THAT WOULD INCLUDE CURB
 PAINTING AND SIGNAGE WOULD BE REQUIRED AROUND THE
 LANDSCAPE ISLAND. PLEASE COORDINATE WITH THE OFFICE OF
 THE FIRE MARSHAL.
  
 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 06-25-2019 Cont ID  
Sent By rcaranci Date 06-25-2019 Time 16:58 Rev Time 0.00
Received By rcaranci Date 06-25-2019 Time 16:58 Sent To  
Notes
2019-06-25 16:59:04FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: MERCER PARK APARTMENTS Z19040012
 JUNE 21, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE REVISE TREE CANOPY IMPACT PLAN
 SHEET LP-1 TO SHOW:
 ? CORRECT TREE #39 TO 491 SQ FT CANOPY
 ? ALL NATIVE TREES AND PALMS IN GOOD CONDITION MUST BE
 PRESERVED OR RELOCATED, AND NATIVE TREES #13, 43, 71,
 83, AND 99 ARE SHOWN IN GOOD CONDITION.
  
 2. SATISFIED. SOME LANDSCAPE TERMINAL ISLANDS DO NOT
 MEET THE CODE REQUIREMENTS OF SECTION 94-443(C)(3)A.
 FOR LANDSCAPE AREA WIDTH OF 8 FEET FOR THE FULL LENGTH
 OF THE PARKING SPACE. THE TERMINAL ISLANDS AND SHADE
 TREES ARE ALSO LACKING ADJACENT TO THE ELEVATOR SHAFTS.
 REVISE PLAN TO MEET REQUIREMENTS.
  
 3. SATISFIED. PROVIDE AN EXHIBIT SHOWING THE PARKING
 AREA SURFACE CALCULATIONS, PARKING SPACE AREAS AND
 LANDSCAPE AREAS PROVIDED TO DEMONSTRATE COMPLIANCE WITH
 SECTIONS 94-443 (C)(3) AND (4).
  
 4. PARTIALLY SATISFIED. TREES MUST BE ADDED TO PROVIDE
 SHADE FOR THE SIDEWALK IN THE AREA OF STREET PARKING
 ALONG ALPHA STREET. THE UTILITIES SHOULD BE RELOCATED
 TO ALLOW PLANTING AT EACH END OF THE SPACES, AND LARGER
 SHADE TREES ADDED WITHIN THE PROPERTY LINE IN THE
 CENTER TO PROVIDE SHADE.
 STAFF SUGGESTS REMOVING THE CENTER PARKING SPACE AND
 ADDING AN ISLAND AND LIVE OAK TREE.
  
  
 5. PARTIALLY SATISFIED. SHOW THE ADDITIONAL 51 TREES
 REQUIRED, ONE FOR EACH UNIT PER SECTION 94-443(D), IN
 THE LANDSCAPE DATA CHART. ADD TO THE TOTAL SHADE TREE
 AND FLOWERING TREE REQUIREMENT FOR OPEN SPACE TO SHOW
 THE TOTAL TREE REQUIREMENT. BUFFER AND PARKING LOT
 TREES ARE COUNTED TOWARD SATISFYING THIS REQUIREMENT.
 THE CHART NEEDS TO BE CLARIFIED TO SHOW REQUIRED AND
 PROVIDED SHADE TREES, FLOWERING TREES AND ADDITIONAL
 MULTIFAMILY TREES. SHOW TOTAL OF REQUIRED AND PROVIDED.
  
 6. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 7. PARTIALLY SATISFIED. SHOW EACH BUFFER SEGMENT IN THE
 BUFFER CALCULATIONS TO SHOW REQUIRED AND PROVIDED
 BUFFER TREE COUNTS.
 CHART NEEDS TO BE CLEAR, CAN BE TOTAL EACH SIDE- NORTH,
 SOUTH, EAST AND WEST BUFFERS, SHOW LINEAR FEET AND
 REQUIRED AND PROVIDED BUFFER TREES.
  
 8. SATISFIED. SHOW PROOF OF PROVIDING THE EFFICIENT
 IRRIGATION OR MOISTURE SENSOR AS CLAIMED ON THE FLORIDA
 FRIENDLY DESIGN OPTION CHART.
  
  
 9. SATISFIED. PROVIDE ROOT BARRIER LOCATIONS WHERE
 NEEDED TO PROTECT UTILITIES.
  
 10. SATISFIED. ADD TREES AND PALMS TO REMAIN OR BE
 RELOCATED ON SITE TO THE PLANT LIST.
  
 11. SATISFIED. ADJUST THE SHRUB NATIVE PERCENTAGE TO
 MATCH THE SHRUB LIST.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION AS PERMITTED AND
 INSTALLED. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-03-2019 Cont ID  
Sent By rcaranci Date 05-03-2019 Time 15:35 Rev Time 0.00
Received By rcaranci Date 05-03-2019 Time 15:35 Sent To  
Notes
2019-05-03 15:36:25FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: MERCER PARK APARTMENTS Z19
 MAY 3, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE REVISE TREE CANOPY IMPACT PLAN SHEET LP-1 TO
 SHOW:
 ? CORRECT TREE #39 TO 491 SQ FT CANOPY
 ? ALL NATIVE TREES AND PALMS IN GOOD CONDITION MUST BE
 PRESERVED OR RELOCATED, AND NATIVE TREES #13, 43, 71,
 83, AND 99 ARE SHOWN IN GOOD CONDITION.
  
 2. SOME LANDSCAPE TERMINAL ISLANDS DO NOT MEET THE CODE
 REQUIREMENTS OF SECTION 94-443(C)(3)A. FOR LANDSCAPE
 AREA WIDTH OF 8 FEET FOR THE FULL LENGTH OF THE PARKING
 SPACE. THE TERMINAL ISLANDS AND SHADE TREES ARE ALSO
 LACKING ADJACENT TO THE ELEVATOR SHAFTS. REVISE PLAN TO
 MEET REQUIREMENTS.
  
 3. PROVIDE AN EXHIBIT SHOWING THE PARKING AREA SURFACE
 CALCULATIONS, PARKING SPACE AREAS AND LANDSCAPE AREAS
 PROVIDED TO DEMONSTRATE COMPLIANCE WITH SECTIONS 94-443
 (C)(3) AND (4).
  
 4. TREES MUST BE ADDED TO PROVIDE SHADE FOR THE
 SIDEWALK IN THE AREA OF STREET PARKING ALONG ALPHA
 STREET. THE UTILITIES SHOULD BE RELOCATED TO ALLOW
 PLANTING AT EACH END OF THE SPACES, AND LARGER SHADE
 TREES ADDED WITHIN THE PROPERTY LINE IN THE CENTER TO
 PROVIDE SHADE.
  
  
 5. SHOW THE ADDITIONAL 51 TREES REQUIRED, ONE FOR EACH
 UNIT PER SECTION 94-443(D), IN THE LANDSCAPE DATA
 CHART. ADD TO THE TOTAL SHADE TREE AND FLOWERING TREE
 REQUIREMENT FOR OPEN SPACE TO SHOW THE TOTAL TREE
 REQUIREMENT. BUFFER AND PARKING LOT TREES ARE COUNTED
 TOWARD SATISFYING THIS REQUIREMENT.
  
 6. PROVIDE LOCATIONS OF LIGHTING ON THE LANDSCAPE PLAN
 TO AVOID CONFLICTS WITH LANDSCAPING.
  
 7. SHOW EACH BUFFER SEGMENT IN THE BUFFER CALCULATIONS
 TO SHOW REQUIRED AND PROVIDED BUFFER TREE COUNTS.
  
 8. SHOW PROOF OF PROVIDING THE EFFICIENT IRRIGATION OR
 MOISTURE SENSOR AS CLAIMED ON THE FLORIDA FRIENDLY
 DESIGN OPTION CHART.
  
  
 9. PROVIDE ROOT BARRIER LOCATIONS WHERE NEEDED TO
 PROTECT UTILITIES.
  
 10. ADD TREES AND PALMS TO REMAIN OR BE RELOCATED ON
 SITE TO THE PLANT LIST.
  
 11. ADJUST THE SHRUB NATIVE PERCENTAGE TO MATCH THE
 SHRUB LIST.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 RIGHT OF WAY LANDSCAPING AND IRRIGATION APPROVED WITH
 THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION AS PERMITTED AND
 INSTALLED. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY.
  
  
  

Review Stop PW PUBLIC WORKS
Rev No 2 Status F Date   Cont ID  
Sent By   Date 05-13-2019 Time   Rev Time 0.00
Received By   Date 05-03-2019 Time   Sent To  
Notes
2019-05-13 09:51:20PLEASE PROVIDE THE UPDATED PLANS TO REFLECT THE
 COMPLAINCE TO OUR DUMPSTER ENCLOSURE SPECIFICATION,
 ATTACHED.
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop PW PUBLIC WORKS
Rev No 1 Status F Date 05-03-2019 Cont ID  
Sent By   Date 06-26-2019 Time   Rev Time 0.00
Received By   Date 06-26-2019 Time   Sent To  
Notes
2019-05-07 16:34:19PLEASE PROVIDE A PLAN SHOWING (SANITATION TRUCK) AUTO
 TURN FROM THE INBOUND DIRECTIONS AND THROUGH THE
 OUTBOUND FOR BOTH DUMPSTERS ON THE EAST AND WEST SIDES.
  
  
 MATT HEJAZI
 DEPT. OF PUBLIC WORKS
 [email protected]
 561-822-2045

Review Stop STORM STORMWATER
Rev No 2 Status F Date 06-26-2019 Cont ID  
Sent By tward Date 06-26-2019 Time 19:26 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2019-06-26 19:42:37THE COMMENTS BELOW ARE FROM THE REVIEW OF THE 6/10/19
 SUBMITTAL PACKAGE.
  
 IF ANOTHER SUBMITTAL IS NOT NEEDED FOR SITE PLAN
 APPROVAL THEN THESE COMMENTS CAN BE PROVISIONAL AND
 ADDRESSED ON THE PLANS THAT WILL BE INCLUDED WITH THE
 ENGINEERING PERMIT SUBMITTAL.
 1. CALL OUT WEIR FOR PARALLEL PARKING DRAINAGE SYSTEM
 (EITHER IN STRUCTURE S-301 OR S-302 (PREFERED).
  
 2. PROVIDE A MEANS TO ACCESS THE WEST END OF THE
 PARALLEL PARKING EXFILTRATION TRENCH.
  
 3. INCLUDE PRB CALLOUTS AND DIRECTIONS (N,S,E,W ETC.)
 IN THE DRAINAGE STRUCTURE CALLOUTS.
  
 4. THERE APPEARS TO BE A LOW SPOT WHERE THE 10-FOOT
 DRAINAGE EASEMENT IS IN THE ALLEY.
  
 5. CONFIRM THE STORMWATER RUNOFF FROM THE NORTH END OF
 THE PAVER ALLEY WILL REACH A DRAINAGE STRUCTURE AND NOT
 POND IN THE ALLEY OR DRAIN TO ANOTHER LOT.
  
 6. INCLUDE PAVEMENT FLOW ARROWS FOR THE ALLEY.
  
 7. PROVIDE TYPICAL CROSS SECTIONS FOR:
 A. ALPHA STREET RIGHT OF WAY WEST AND EAST (SHOWING
 PARALLEL PARKING) OF THE ALLEY
 B. ALLEY
  
 8. PROVIDE A PROFILE VIEW OF THE STORM PIPE BETWEEN
 STRUCTURES S-104 AND S-303. PROFILE ONLY NEEDS TO BE OF
 THE RIGHT-OF-WAY AND INCLUDE ALL UTILITY
 CROSSINGS/CONFLICTS WITH THE STORM PIPE.
  
 9. SIDEWALK ACCESS EASEMENT WILL BE NEEDED AT THE
 SOUTHEAST CORNER OF THE EAST PARCEL.
  
 10. CCTV OF EXISTING STORM SYSTEM WILL BE NEEDED
 (REPEAT COMMENT).
  
 11. BERMS AND/OR SWALES MAY BE NEEDED TO PREVENT RUNOFF
 ONTO ADJACENT PROPERTIES.
  
 12. THE ONSITE AREAS BEHIND THE SIDEWALKS IN THE
 RIGHT-OF-WAY ARE TO BE DEPRESSED TO PREVENT ONSITE
 STORMWATER RUNOFF FROM CROSSING THE SIDEWALK.
  
 13. ROOF DRAINS SHOULD CONNECT DIRECTLY TO THE DRAINAGE
 SYSTEM OR BE DIRECTED TO DISCHARGE ONTO PERVIOUS AREAS.
  
 14. SHOW A REPLACEMENT WATER SERVICE FROM THE NEW WATER
 MAIN TO THE PROPERTY ON THE SOUTH SIDE OF ALPHA STREET
 SOUTH OF BUILDING 'B'. (REPEAT COMMENT)
  
 15. EXISTING CURB RAMPS LEADING TO NEW PAVMENT OR TO
 MILLED AND OVERLAID PAVEMENT ARE TO BE CONSTRUCTED TO
 CURRENT ADA STANDARDS.
  
 16. TWO-WAY SIGN ON WEST SIDE OF THE ALLEY SHOWN ON
 PRIVATE PROPERTY.
  
 17. CURBING SOUTH OF SIGN REFERENCED IN COMMENT #16
 ABOVE APPEARS TO CROSS PRIVATE PROPERTY.
  
 18. DUE TO THE LARGE DROP OFF, A FENCE WILL BE NEEDED
 NEAR OR ON TOP OF THE RETAINING WALL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 05-07-2019 Cont ID  
Sent By tward Date 05-07-2019 Time 18:23 Rev Time 0.00
Received By tward Date 05-07-2019 Time 18:26 Sent To  
Notes
2019-05-07 18:25:49THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY?S VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED ON THE SHEET(S).
 PROVIDE NAVD1988 TO NGVD1929 CONVERSION EQUATION ON THE
 ENGINEERING PLANS.
  
 2. END OF PAVERS IN THE ALLEY DO NOT ALIGN WITH THE
 EXISTING ASPHALT ROADWAY.
  
 3. CHECK SIDEWALK SLOPE BETWEEN NEW APARTMENTS AND BACK
 OF SIDEWALKS ON ALPHA ST. AND MERCER ST. STEPS MAY BE
 REQUIRED.
  
 4. SHOW MILLING AND RESURFACING LIMITS FOR PAVEMENT
 CUTS IN THE RIGHT-OF-WAY.
  
 5. PIPE BETWEEN STRUCTURES S-204 AND S-102 MISLABELED
 AS OUTFALL.
  
 6. SHOW DRAINAGE FLOW ARROWS FOR SURFACE RUNOFF ON THE
 CONCEPTUAL PG&D PLAN.
  
 7. PROVIDE WATER QUALITY TREATMENT FOR THE PROPOSED
 PARKING SPACES ON ALPHA ST.
  
 8. PROVIDE CCTV OF THE STORMWATER PIPES IN MERCER AVE.
  
 9. TRANSFER WATER SERVICES ON EXISTING WATER MAIN TO
 NEW WATER MAIN ON ALPHA ST.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT PRIOR TO
 STARTING CONSTRUCTION.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 06-25-2019 Cont ID  
Sent By vnoel Date 06-25-2019 Time 07:30 Rev Time 0.00
Received By tward Date 06-26-2019 Time 20:16 Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 05-07-2019 Cont ID  
Sent By vnoel Date 05-07-2019 Time 10:46 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-05-07 11:14:041. REPLAT OF PROPERTY WILL BE REQUIRED.
 2. IT APPEARS THAT THE WESTERN DRIVEWAY OFF THE ALLEY
 CLIPS THE CORNER OF THE ADJACENT PROPERTY.
 3. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR
 IMPROVEMENTS WITHIN R/W AND IN THE ALLEY..
 4. ACCESS EASEMENT MAY BE REQUIRED FOR NORTH BOUND
 ENTRANCE.
 5. A PRIVATE UNDERGROUND UTILITY EASEMENT WILL BE
 REQUIRED FOR DRAINAGE CROSSING THE ALLEY.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 06-18-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-06-18 15:08:19PASSED, WITH THE FOLLOWING CONDITIONS OF APPROVAL:
 1. CONSTRUCT BUFFERED BIKE LANES ON BOTH SIDES OF
 MERCER AVENUE BETWEEN WILKINS AVENUE AND OLD OKEECHOBEE
 ROAD PRIOR TO ISSUANCE OF THE FIRST CERTIFICATE OF
 OCCUPANCY.
 2. COORDINATE WITH CITY ON STREETLIGHT DURING
 PERMITTING.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 04-30-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-04-30 17:23:121. IN THE TRAFFIC STUDY, INCLUDE TRIP DISTRIBUTION ON
 CITY ROADWAYS WITHIN THE RADIUS OF INFLUENCE OF 0.5
 MILES.
 2. CONDUCT QUEUING ANALYSIS AT THE ALLEY/INTERNAL
 EAST-WEST DRIVEWAY INTERSECTION TO VERIFY THE
 NORTHBOUND QUEUE DOESN?T BACK UP ONTO ALPHA STREET.
 3. SHOW THE CURB RADII AT THE ALLEY/INTERNAL EAST-WEST
 DRIVEWAY INTERSECTION. CONSIDER USING SMALLER CURB
 RADII AT THE SOUTHEAST AND SOUTHWEST CORNERS. SERVICE
 VEHICLES SHOULD BE ALLOWED TO USE ALL PAVEMENT AREAS.
 4. SHOW 20-FOOT VISIBILITY TRIANGLE AT THE CORNERS OF
 ALPHA STREET AND ALLEY.
 5. PROVIDE SIDEWALK EASEMENT FOR THE PORTION OF
 SIDEWALK WHICH IS OUTSIDE PUBLIC ROW, IF ANY.
 6. PROVIDE ACCESS EASEMENT FOR THE PORTION OF DRIVEWAY
 WHICH IS OUTSIDE PUBLIC ROW BUT REQUIRED FOR ALLEY
 ACCESS.
 7. PROVIDE TWO-WAY SIGN (W6-3) AT THE ENTRANCE OF
 ALLEY.
 8. SHOW DRIVEWAYS AND CURB CUTS ON BOTH SIDES OF ALPHA
 STREET AND MERCER AVENUE.
 9. ON EX1 AND EX2, SHOW DIMENSIONS OF THE GARBAGE
 TRUCK.
 10. INCLUDE AUTOTURN EXHIBIT OF FIRE TRUCKS.
 11. PROVIDE BUFFERED BIKE LANES ON BOTH SIDES OF MERCER
 AVENUE BETWEEN WILKINS AVENUE AND OLD OKEECHOBEE ROAD.
 USE 6-FOOT BIKE LANE, AND 2-FOOT BUFFER WITH 10-FOOT
 TRAVEL LANE. REMOVE NORTHBOUND LEFT-TURN LANE AT MERCER
 STREET/OLD OKEECHOBEE ROAD. INCLUDE CROSS-SECTION OF
 MERCER STREET.
 12. THE CURB RAMP AT THE NORTHWEST CORNER OF ALPHA
 STREET/MERCER AVENUE IS DIFFERENT BETWEEN SHEET C1.0
 AND SP-1. PLEASE REVISE.
 13. INDICATE THE LOCATION OF THE PROPOSED BICYCLE
 STORAGE ROOM ON THE SITE PLAN.
 14. INCLUDE THE REQUIRED AND PROPOSED BICYCLE PARKING
 SPACES UNDER PARKING DATA ON THE SITE PLAN.
 15. MILL AND RESURFACE ALPHA STREET AND MERCER AVENUE
 ADJACENT TO THE PROPERTY.
 16. PROVIDE STREET LIGHT ALONG MERCER AVENUE ADJACENT
 TO THE PROPERTY.
 17. CONSIDER PROVIDING LOCATION FOR SHARED
 MICROMOBILITY INSTEAD OF ?SKYBIKE? TYPE BIKE SHARING
 SYSTEM.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop Z ZONING
Rev No 2 Status F Date 06-24-2019 Cont ID  
Sent By pgreilic Date 06-24-2019 Time 10:38 Rev Time 0.00
Received By pgreilic Date 06-24-2019 Time 10:38 Sent To  
Notes
2019-06-24 10:38:54STAFF SUPPORTS THE INCLUSION OF AN AFFORDABLE HOUSING
 COMPONENT INTO THE PROPOSED RESIDENTIAL PLANNED
 DEVELOPMENT
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 05-07-2019 Cont ID  
Sent By pgreilic Date 05-07-2019 Time 15:24 Rev Time 0.00
Received By pgreilic Date 05-07-2019 Time 15:24 Sent To  
Notes
2019-05-07 15:25:15CASE NUMBER: PB1831 ? Z19040012
 PROJECT NAME: MERCER PARK RESIDENTIAL PLANNED
 DEVELOPMENT
 ADDRESS: 1315-1321 ALPHA STREET
  
 -- CONTACT PAUL GREILICH @ (561) 822-1443
 -- PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
 -- WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF
 ELEVEN (11) PAPER COPIES AND AN ELECTRONIC COPY IN
 .PNG/.PDF FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES
 ON THE RESUBMITTED PLANS OR THE SUBMITTAL OF
 INFORMATION/PLANS TO ADDRESS THE COMMENTS MAY RESULT IN
 ADDITIONAL COMMENTS.
 -- PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 7/8/19), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
 -- PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1.) PROVIDE LETTERS FROM ALL OF THE FOLLOWING PUBLIC
 UTILITIES CONFIRMING THAT THE PROPOSED PROJECT DOES NOT
 ENCROACH INTO THEIR EASEMENTS OR OTHERWISE INTERFERE
 WITH THE PROVISION OF THEIR SERVICES: AT&T, FPU, FPL,
 AND COMCAST.
 2.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION
 3.) A REPLAT OF THE SUBJECT PROPERTIES WILL BE REQUIRED
 4.) STAFF SUPPORTS THE INCLUSION OF AN AFFORDABLE
 HOUSING COMPONENT INTO THE PROPOSED RESIDENTIAL PLANNED
 DEVELOPMENT
 5.) THE OPEN SPACE/PARK AREA SHOULD BE OVERALL ENHANCED
 AND REWORKED TO ELIMINATE ANY DEAD END PATHS.
 6.) ADDITIONAL SCREENING SHOULD BE PROVIDED BETWEEN THE
 PROPERTIES ADJACENT TO THE NORTH, STAFF SUPPORTS
 ALTERNATIVE MATERIAL TO PVC
 7.) NARROW 24 FOOT DRIVE AISLES TO 20 FEET AND TIGHTEN
 CURB RADII. DOING SO WILL INCREASE LANDSCAPING IN
 TERMINAL ISLANDS AND SLOW VEHICLES TO HELP MINIMIZE
 CONFLICTS AT PROPOSED INTERSECTIONS
 8.) STAFF SUPPORTS REDUCING THE DEPTH OF PARKING SPACES
 BY INCLUDING A 2-FOOT GRASS OVERHANG. THE CURB WOULD
 FUNCTION AS WHEEL STOPS. ALSO CONSIDER THE INCLUSION OF
 SMALL CAR SPACES TO REDUCE OVERALL IMPERVIOUS SURFACE
 AREA
 9.) EXPAND SIDEWALK BETWEEN REAR OR BUILDINGS AND
 PARKING AREA TO, SUGGESTED EIGHT FEET TO INCREASE SPACE
 BETWEEN VEHICLES AND REAR BUILDING OVERHANGS
 10.) REVISE ARCHITECTURAL PLANS, PARTICULARLY ALONG
 ALPHA STREET AND MERCER AVE. SPECIFICALLY, FIRST FLOOR
 ENTRIES SHOULD BE RAISED TO HAVE STEPS AND FRONT DOORS
 RATHER THAN SLIDING DOORS
 11.) ADD PEDESTRIAN-SCALE LIGHTING ALONG ALPHA STREET
 AND IN THE PARK/OPEN SPACE AREA
 12.) PROVIDE CITY-STANDARD BIKE RACK DETAIL
  
  