Plan Review Details - Project Z19030025
Plan Review Stops For Project Z19030025
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 04-09-2019 Cont ID  
Sent By rbrown Date 04-09-2019 Time 19:33 Rev Time 0.00
Received By rbrown Date 04-09-2019 Time 19:33 Sent To  
Notes
2019-04-09 19:46:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ATTACHMENT OF COMBUSTIBLE MATERIALS TO EXISTING
 BUILDINGS. WHEN SUBMITTED FOR BUILDING PERMIT, THE
 PLANS SHALL SHOW HOW THE EXISTING BUILDINGS THAT HAVE
 NEW COMBUSTIBLE MATERIALS (TRELLISES, ETC.) ATTACHED
 WILL COMPLY WITH ALL BUILDING CONSTRUCTION TYPE,
 MATERIAL TYPE, AND FIRE PROTECTION REQUIREMENTS OF
 CHAPTERS 6, 7 AND 9 OF THE FLORIDA BUILDING CODE.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS/SPAS AND FOUNTAINS, GAS
 SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER
 AND OTHER FIRE SUPPRESSION SYSTEMS, GREASE
 INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 05-17-2019 Cont ID  
Sent By rrossano Date 05-17-2019 Time   Rev Time 0.00
Received By rrossano Date 05-17-2019 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 04-02-2019 Cont ID  
Sent By rrossano Date 04-02-2019 Time   Rev Time  
Received By rrossano Date 04-02-2019 Time   Sent To I
Notes
2019-04-02 11:32:41THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
  
 PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED
 DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK)
 AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC
 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS WITHIN
 CITY OF WPB RIGHT OF WAY.
  
 CUT AND CAP ANY UTILITIES NOT BEING USED.
  
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
  
 PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS
 FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) AND FIRE
 FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR
 SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION
 ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD
 SURVEY, POT-HOLING, SOFT DIGS ETC.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
 ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND
 PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER
 OPTIC, ELECTRIC, GAS, AND CABLEVISION &
 TELECOMMUNICATION FACILITIES LOCATED ON THE
 RIGHT-OF-WAY.
  
 PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS WITHIN
 CITY OF WPB RIGHT OF WAY.
  
 SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION
 (NAVD 88 AND NGVD 29).
  
 CUT AND CAP ANY UTILITIES NOT BEING USED.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 05-20-2019 Cont ID  
Sent By pleduc Date 05-20-2019 Time   Rev Time 0.00
Received By pleduc Date 05-20-2019 Time 11:03 Sent To  
Notes
2019-05-20 11:05:112ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM ERIC
 SCHNEIDER, PRINCIPLE PLANNER, AND THE ATTACHMENTS DATED
 MAY 13, 2019, FROM KIMBERLY HORN, THE PREVIOUSLY
 SUBMITTED FIRE PREVENTION BUREAU COMMENTS APPEAR TO
 HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 04-04-2019 Cont ID  
Sent By pleduc Date 04-04-2019 Time   Rev Time 0.00
Received By pleduc Date 04-04-2019 Time 15:01 Sent To  
Notes
2019-04-04 15:09:29FIRE HAS NO OBJECTIONS TO THE PROPOSED; HOWEVER, THE
 FOLLOWING COMMENTS ARE PROVIDED FOR DISCUSSION PURPOSES
 RELATED TO CONSTRUCTION.
  
  
 1) THERE APPEARS TO BE WOOD/COMBUSTIBLE TRELLIS TYPE
 STRUCTURES ATTACHED TO OR CLOSE TO THE MAIN CITY PLACE
 STRUCTURES.
  
 WILL THEY BE OF A COMBUSTIBLE FRAMEWORK?
  
 WILL LIVE VEGITATION BE ATTACHED TO THESE STRUCTURES?
  
 AS SOME OF THE STRUCTURES LINE EXIT ACCESS AREAS, HOW
 WILL THESE STRUCTURES BE PROTECTED?
  
 HOW WILL THE EXIT ACCESS AREAS BE PROTECTED FROM
 EXPOSURE SHOULD A FIRE INVOLVE OF THESE STRUCTURES?
  
 PLEASE REVIEW AND PROVIDE DETAILS?
  
  
 2) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 06-14-2019 Cont ID  
Sent By rcaranci Date 06-14-2019 Time 12:16 Rev Time 0.00
Received By rcaranci Date 06-14-2019 Time 12:16 Sent To  
Notes
2019-06-14 12:17:05FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CITYPLACE PLAZA Z19030025
 JUNE 14, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
 NOTE THAT THIS IS THE FIRST REVIEW FOR THE LANDSCAPE
 PLAN.
 1. SATISFIED. PROVIDE A TREE DISPOSITION PLAN SHOWING
 ALL TREES IN THE AFFECTED AREA AND INDICATE IF THEY
 WILL BE REMOVED, RELOCATED, OR REMAIN.
 2. SATISFIED. PROVIDE A LANDSCAPE PLAN MEETING CURRENT
 CODE REQUIREMENTS FOR THE AFFECTED AREA,AND SHOW HOW
 ANY MITIGATION DUE IS PROVIDED.
 MODIFY MITIGATION CHART TO SHOW:
 ? CANOPY MITIGATION REQUIRED OF 100 SQ FT FOR EACH DATE
 PALM REMOVED.
 ? MITIGATION VALUE OF 300 SQ FT FOR EACH BANYAN, 100 SQ
 FT FOR EACH COCONUT, AND 50 SQ FT FOR EACH MONTGOMERY
 AND ALEXANDER PALM. TOTAL ALL CANOPY CREDITS
 ? TOTAL ALL MITIGATION DUE AND CANOPY CREDITS PROPOSED.
 ADDITIONAL COMMENTS 5/23/19:
 3. SATISFIED. FLORIDA FRIENDLY POINTS ARE TAKEN FOR
 DROUGHT TOLERANT GROUND COVER, BUT PLANT LIST SHOWS
 ONLY UNDETERMINED SPECIES OF SOD UNDER GROUND COVER
 SECTION. SHOW GROUNDCOVER CLAIMED FOR CREDIT UNDER THE
 GROUND COVER SECTION.
 4. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES. CLEARLY ADD THE PERCENTAGE PROVIDED
 ON SHEET L2.01 UNDER THE PLANT LIST.
 5. SATISFIED. PROVIDE A DETAIL AND SHOW LOCATIONS OF
 ROOT BARRIERS, AS THERE ARE MANY UNDERGROUND UTILITY
 LINES THAT ARE CLOSE TO PROPOSED TREE AND PALM
 LOCATIONS.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 05-23-2019 Cont ID  
Sent By rcaranci Date 05-23-2019 Time 15:00 Rev Time 0.00
Received By rcaranci Date 05-23-2019 Time 15:00 Sent To  
Notes
2019-05-23 15:01:07FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CITYPLACE PLAZA Z19030025
 MAY 23, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
 NOTE THAT THIS IS THE FIRST REVIEW FOR THE LANDSCAPE
 PLAN.
 1. SATISFIED. PROVIDE A TREE DISPOSITION PLAN SHOWING
 ALL TREES IN THE AFFECTED AREA AND INDICATE IF THEY
 WILL BE REMOVED, RELOCATED, OR REMAIN.
 2. PARTIALLY SATISFIED. PROVIDE A LANDSCAPE PLAN
 MEETING CURRENT CODE REQUIREMENTS FOR THE AFFECTED
 AREA,AND SHOW HOW ANY MITIGATION DUE IS PROVIDED.
 MODIFY MITIGATION CHART TO SHOW:
 ? CANOPY MITIGATION REQUIRED OF 100 SQ FT FOR EACH DATE
 PALM REMOVED.
 ? MITIGATION VALUE OF 300 SQ FT FOR EACH BANYAN, 100 SQ
 FT FOR EACH COCONUT, AND 50 SQ FT FOR EACH MONTGOMERY
 AND ALEXANDER PALM. TOTAL ALL CANOPY CREDITS
 ? TOTAL ALL MITIGATION DUE AND CANOPY CREDITS PROPOSED.
 ADDITIONAL COMMENTS 5/23/19:
 3. FLORIDA FRIENDLY POINTS ARE TAKEN FOR DROUGHT
 TOLERANT GROUND COVER, BUT PLANT LIST SHOWS ONLY
 UNDETERMINED SPECIES OF SOD UNDER GROUND COVER SECTION.
 SHOW GROUNDCOVER CLAIMED FOR CREDIT UNDER THE GROUND
 COVER SECTION.
 4. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES. CLEARLY ADD THE PERCENTAGE PROVIDED ON
 SHEET L2.01 UNDER THE PLANT LIST.
 5. PROVIDE A DETAIL AND SHOW LOCATIONS OF ROOT
 BARRIERS, AS THERE ARE MANY UNDERGROUND UTILITY LINES
 THAT ARE CLOSE TO PROPOSED TREE AND PALM LOCATIONS.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-05-2019 Cont ID  
Sent By rcaranci Date 04-05-2019 Time 15:59 Rev Time 0.00
Received By rcaranci Date 04-05-2019 Time 15:59 Sent To  
Notes
2019-04-05 16:00:03FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CITYPLACE PLAZA Z19030025
 APRIL 5, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE A TREE DISPOSITION PLAN SHOWING ALL TREES IN
 THE AFFECTED AREA AND INDICATE IF THEY WILL BE REMOVED,
 RELOCATED, OR REMAIN.
 2. PROVIDE A LANDSCAPE PLAN MEETING CURRENT CODE
 REQUIREMENTS FOR THE AFFECTED AREA, AND SHOW HOW ANY
 MITIGATION DUE IS PROVIDED.
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 05-20-2019 Cont ID  
Sent By tward Date 05-20-2019 Time 13:20 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 04-08-2019 Cont ID  
Sent By tward Date 04-08-2019 Time 12:26 Rev Time 0.00
Received By tward Date 04-08-2019 Time 12:28 Sent To  
Notes
2019-04-08 12:27:25THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. REVIEW CWPB GENERAL NOTE #7 ON SHEET C0.01. MINIMUM
 TWO FEET OF FREEBOARD REQUIRED FOR STRUCTURES LOCATED
 WITHIN A SPECIAL FLOOD HAZARD AREA.
  
 2. ON SHEET C0.02, SURVEY DATA NOTE #1 INDICATES THE
 VERTICAL DATUM IS NGVD1929. IN THE LOWER LEFT OF SHEETS
 C2.00 AND C5.00 IS A NOTE THAT THE VERTICAL DATUM IS
 NAVD1988. ALL PLANS AND SURVEYS SHOULD REFERENCE THE
 SAME VERTICAL DATUM.
  
 3. THE CITY?S VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED ON THE SHEET(S). LIST
 THE VERTICAL DATUM AND CONVERSION EQUATION ON ALL
 SHEETS WITH ELEVATION DATA.
  
 4. PROPOSED DRAINAGE WILL BE MAINTAINED BY CITY PLACE
 STAFF OR CONTRACTORS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION PRIOR
 TO STARTING CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  
  

Review Stop SURVEY SURVEYING
Rev No 3 Status P Date 05-29-2019 Cont ID  
Sent By vnoel Date 05-29-2019 Time 06:47 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 05-20-2019 Cont ID  
Sent By vnoel Date 05-20-2019 Time 09:45 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-05-20 09:45:48NO SURVEY PROVIDED WITH RESUBMITTAL.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 04-08-2019 Cont ID  
Sent By vnoel Date 04-08-2019 Time 09:05 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2019-04-08 09:07:31NO SURVEY PROVIDED.

Review Stop Z ZONING
Rev No 3 Status P Date 06-14-2019 Cont ID  
Sent By eschneid Date 06-14-2019 Time 08:44 Rev Time 0.25
Received By eschneid Date 06-14-2019 Time 08:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 05-29-2019 Cont ID  
Sent By eschneid Date 05-29-2019 Time 15:17 Rev Time 1.00
Received By eschneid Date 05-29-2019 Time 14:00 Sent To  
Notes
2019-05-29 15:17:38CASE NO. PB 950MMMMM - 1ST RESUBMITTAL
 CITYPLACE PUBLIC PLAZA IMPROVEMENTS
 620 SOUTH ROSEMARY
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY JULY 29, 2019),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE ADDITIONAL
 (1) RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) REVISED COMMENT: PLEASE PROVIDE THE ADDITIONAL
 DIMENSIONS ON THE PLANS:
  
 A. DIMENSION BETWEEN THE "PRIVATE OUTDOOR SEATING" AND
 THE PLANTERS TO THE EAST.
  
 B. DIMENSION BETWEEN THE PLANTERS AND THE PLANTERS AT
 THE BASE OF THE ARCADE COLUMNS. THE DIMENSION GIVEN IS
 FROM THE PLANTERS TO THE TRENCH DRAIN.
  
 2) THE PLANS CALL OUT "HARDSCAPE TREATMENTS TO BE
 DETERMINED". WHAT TYPES OF HARDSCAPE ARE BEING
 CONTEMPLATED? PAVERS, WOOD, CONCRETE SLAB? STAFF WOULD
 LIKE TO HAVE AN IDEA FOR FUTURE REVIEW.
  
 3) THE PLANS DO NOT PROVIDE DETAILS OF THE COVERED
 STRUCTURE FOR THE PRIVATE SEATING AREA. THIS WILL
 REQUIRE A SEPARATE MINOR AMENDMENT SUBMITTAL WITH THE
 FULL DETAILS AND APPROVAL PRIOR TO THE BUILDING PERMIT
 SUBMITTAL FOR THE STRUCTURE.
  

Review Stop Z ZONING
Rev No 1 Status F Date 04-05-2019 Cont ID  
Sent By eschneid Date 04-05-2019 Time 15:05 Rev Time 1.00
Received By eschneid Date 04-05-2019 Time 15:03 Sent To  
Notes
2019-04-05 15:04:55CASE NO. PB 950MMMMM
 CITYPLACE PUBLIC PLAZA IMPROVEMENTS
 620 SOUTH ROSEMARY
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM FIVE (5)
 PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT OF
 ALL PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED
 PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS
 THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY JUNE 10, 2019),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) PROVIDE A SURVEY FOR THE LIMITS OF WORK.
  
 2) SUBMIT A LANDSCAPE PLAN COMPLETED BY A LANDSCAPE
 ARCHITECT.
  
 3) PROVIDE DIMENSIONS ON THE PLANS. THIS MUST INCLUDE
 THE SIZE OF THE VARIOUS FEATURES AND THE DIMENSIONS
 BETWEEN THE VARIOUS FEATURES.
  
 4) THE NARRATIVE, THE PLANS AND THE COLOR RENDERINGS
 PROVIDE THAT THERE ARE TRELLISES AND A BAR IN THE PLAZA
 AREA. PROVIDE THE DETAILS AND ACCURATE LOCATIONS FOR
 ALL OF THESE FEATURES.
  
 5) SEATING
  
 A. THE NOTES STATE THAT THE BENCH DETAILS ARE STILL IN
 PROGRESS. PLEASE PROVIDE THE FINAL DETAILS WITH THE
 RESUBMITTAL FOR BOTH THE CONCRETE BENCHES AND THE WOOD
 SEATS.
 B. PROVIDE INFORMATION ON WHERE THE PUBLIC SEATING AND
 WHERE THE PRIVATE SEATING WILL BE. THIS MUST INCLUDE
 THE NUMBERS OF SEATING AND A COMPARISON WITH THE
 EXISTING PUBLIC SEATING NUMBERS.
 C. THE AREAS THAT APPEAR FROM THE PLANS TO BE PUBLIC
 SEATING SEEM TO ALL LACK BACKRESTS. YOU NEED TO PROVIDE
 SOME OF THE PUBLIC SEATING WITH BACKRESTS. PROVIDE THE
 DETAILS AND THE LOCATIONS FOR THIS SEATING STYLE.
  
 6) RENDERINGS SHOW GROUND MOUNTED LIGHTING THAT IS NOT
 SHOWN ON THE PLANS.
  
 7) THE RENDERINGS SHOW PLANTING BEDS AGAINST THE ARCADE
 THAT ARE NOT SHOWN ON THE PLANS.
  
 8) IN THE PAST, CITYPLACE HAS EXPRESSED THAT SOME
 RETAILERS OCCUPYING THE BAYS UNDER THE ARCADE ALONG THE
 PLAZA COMPLAINED ABOUT THE POOR SIGHT LINES TO THEIR
 SIGNAGE. THE RENDERINGS SHOW THE PROPOSED TRELLIS
 FEATURES AND CREEPING VINES BLOCKING VIRTUALLY ALL OF
 THE SIGN ZONES FOR THE GROUND FLOOR TENANT SPACES FOR
 THE LENGTH OF THE PLAZA. THE PLANNING STAFF WILL NOT
 GRANT WAIVERS TO THE SIGN ZONE PLACEMENT BASED ON THE
 PLAZA DESIGN OBSTRUCTING THE SIGN ZONES.
  