Plan Review Details - Project Z19030013
| Plan Review Stops For Project Z19030013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
04-09-2019 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
04-09-2019 |
Time |
18:51 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
04-09-2019 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2019-04-09 18:55:47 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDINGS. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF SECTION | | | R302 OF FLORIDA BUILDING CODE (RESIDENTIAL) SHALL BE | | | VERIFIED. | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT | | | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 | | | 1080, OR BY EMAIL: [email protected] | | | | | | 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
04-02-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
04-02-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
04-02-2019 |
Time |
|
Sent To |
I |
|
| Notes |
| 2019-04-02 07:57:47 | THE FOLLOWING PLANS ARE RELEVANT TO ANY PENDING SITE | | | PLAN SUBMITTAL: | | | | | | PLEASE PROVIDE ENGINEERING PLANS. PLANS SHALL SHOW | | | PROPOSED LOCATIONS AND DIMENSIONS OF ALL WATER, | | | STORMWATER, AND SANITARY AND SEWER LINES, INCLUDING | | | STUBS TO EACH PROPERTY LINE FOR WATER AND SANITARY | | | SEWERS, THE MAKE AND MODEL OF ALL VALVES, METERS, AND | | | OTHERS DEVICES TO BE INSTALLED ON THE SYSTEM, CATCH | | | BASINS, CULVERTS, DITCHES INCLUDING GRADES, PIPES | | | SIZES, MATERIALS, ELEVATIONS, ASSUMPTIONS, | | | CALCULATIONS, INVERT ELEVATIONS FOR ALL INLETS AND | | | MANHOLES AND PROFILES OF SANITARY SEWER LINES. ALL | | | AVAILABLE ELEVATION SHALL BE SHOWN ON THE PROFILE VIEW. | | | DIRECTION OF FLOW SHALL BE SHOWN ON PLAN VIEW ON PLAN | | | VIEW FOR ALL SANITARY AND STORM SEWERS. ADDITIONALLY, | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | | | | PLEASE PROVIDE SANITARY CLEANOUTS EVERY 75 FT. | | | | | | PLEASE SHOW MIN. VERTICAL CLEARANCES AT WATER/SEWER | | | CROSSINGS. | | | | | | PLEASE PROVIDE DETAILED SWPPP INCLUDING CLEARLY SHOWN | | | SILT FENCE, INLET PROTECTION (ONSITE AND ADJACENT | | | ROADWAYS), ETC. PER BMPS. | | | | | | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS | | | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE | | | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER | | | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT | | | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: | | | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W | | | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P | | | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 | | | 60045731D3658206F27451722716EF | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, | | | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, | | | 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | | | | PROVIDE CALCULATIONS ON PLANS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG | | | ENTIRE PROJECT FRONTAGE. | | | | | | SHOW VERTICAL DATUM AND DATUM CONVERSION INFORMATION | | | (NAVD 88 AND NGVD 29). | | | | | | PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF | | | WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT | | | OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR | | | PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS WITHIN | | | CITY OF WPB RIGHT OF WAY. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | CENTRAL OPERATIONS CENTER (DISPATCH): | | | 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC | | | UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
04-02-2019 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
04-02-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
04-02-2019 |
Time |
12:38 |
Sent To |
|
|
| Notes |
| 2019-04-02 12:52:39 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT; HOWEVER, THE FOLLOWING COMMENTS ARE | | | PROVIDED FOR RESPONSE/CLARIFICATION PURPOSES: | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING(S) ADDRESS(ES) SHALL BE CLEARLY VISIBLE | | | FROM ALL ACCESS ROADWAYS, INCLUDING DURING | | | CONSTRUCTION. ADDRESS NUMBERS SHALL CONTRAST WITH THEIR | | | BACKGROUND AND SHALL NOT BE LESS THAN SIX (6) INCHES IN | | | HEIGHT WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER THESE ARE APARTMENT BUILDINGS OR SINGLE | | | FAMILY TOWNHOMES SEPARATED BY THE REQUIRED FIRE | | | RESISTIVE CONSTRUCTION FEATURES. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ANY NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. IF APPLICABLE FOR APARTMENT BUIDLINGS, COMPLETE | | | LIFE SAFETY PLANS SHALL BE PROVIDED. | | | | | | 11. THE LAMBERT AVE TURNAROUND DOES NOT APPEAR TO MEET | | | THE REQUIRED DIMENSIONS OF A FIRE LANE. FIRE LANES IN | | | EXCESS OF 150 FEET SHALL PROVIDE A TURN AROUND AS | | | PROVIDED FOR IN THE FOLLOWING TABLE AND GRAPHICS. | | | CUL-DE-SAC SHOULD BE 96' WIDE WITH A 28' RADIUS. | | | | | | IS THERE ANY PROPOSAL TO IMPROVE THE EXISTING ROADWAY? | | | | | | CAN AN AUTOTURN BE PROVIDED USING STANDARD FIRE TRUCK | | | DIMENSIONS THAT SHOW A TURNAROUND CAN BE ACCOMPLISHED? | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
04-08-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-08-2019 |
Time |
13:23 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-08-2019 |
Time |
13:23 |
Sent To |
|
|
| Notes |
| 2019-04-08 13:24:47 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: RE-PLAT OF TOWNHOMES AT CONNISTON Z19030013 | | | APRIL 8, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | 1. THESE COMMENTS RELATE TO THE SITE PLAN EXAMPLE | | | PROVIDED WITH THE REPLAT SUBMITTAL, AND MAY OR MAY NOT | | | AFFECT THE PROPOSED PLAT LINES: | | | ? THE SITE PLAN SHOWS DRIVEWAY PAVERS AND LANDSCAPE | | | AREAS PAST THE REAR PROPERTY LINES OF SOME LOTS. SITE | | | IMPROVEMENTS CANNOT BE CONSTRUCTED WITHIN THE ALLEY. | | | ? THE PROPOSED SUBDIVISION WOULD CREATE INDIVIDUAL LOTS | | | THAT WOULD BE REQUIRED TO MEET THE MINIMUM LANDSCAPE | | | REQUIREMENTS FOR SINGLE FAMILY HOMES BASED ON THE LOT | | | SIZE AND BUILDING COVERAGE. | | | ? ALSO NOTE THAT THE FRONT YARD MUST MEET THE | | | REQUIREMENTS OF 75% LANDSCAPE AREA PER SECTION | | | 94-482(A). | | | THE APPLICANT NEEDS TO ACKNOWLEDGE THESE REQUIREMENTS. | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
P |
Date |
04-08-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
04-08-2019 |
Time |
12:17 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
04-08-2019 |
Time |
12:24 |
Sent To |
|
|
| Notes |
| 2019-04-08 12:19:18 | NO COMMENTS ON THE PROPOSED PLAT. | | | | | | PRELIMINARY COMMENTS FOR SITE PLAN: | | | 1. A MASTER DRAINAGE SYSTEM CONSISTING OF CATCH BASINS, | | | EXFILTRATION TRENCHES, STORM PIPES AND IS PROPOSED FOR | | | THE PROJECT. IT IS RECOMMENDED THE APPLICANT MEET WITH | | | SFWMD REGARDING REQUIRED EASEMENTS AND THE LEGAL ENTITY | | | TO BE IN PLACE TO OPERATE AND MAINTAIN THE MASTER | | | DRAINAGE SYSTEM AFTER THE SYSTEM IS CONSTRUCTED. | | | | | | 2. MASTER DRAINAGE SYSTEM TO BE DESIGNED TO SFWMD | | | CRITERIA, INCLUDING WATER QUALITY TREATMENT AND OFFSITE | | | DISCHARGE. | | | | | | 3. ENGINEERING PLANS WILL BE NEEDED FOR SITE PLAN | | | APPROVAL. | | | | | | 4. VERTICAL DATUM TO BE LISTED ON ANY PLAN SHEET WITH | | | ELEVATION DATA. THE CITY?S VERTICAL DATUM IS NGVD 1929. | | | THE CITY HAS ALLOWED THE USE OF NAVD 1988 PROVIDED THE | | | CONVERSION EQUATION TO NGVD 1929 IS PROVIDED ON THE | | | SHEET(S). | | | | | | 5. ADD THE VERTICAL DATUM CONVERSION EQUATION TO THE | | | ALTA/NSPS LAND TITLE SURVEY. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
12-05-2019 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
12-05-2019 |
Time |
07:12 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
04-08-2019 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-08-2019 |
Time |
07:26 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-04-08 07:49:34 | 1. THE PLAT WILL NOT BE APPROVED UNTIL FINAL SITE PLAN | | | AND ENGINEERING APPROVAL. | | | 2. ENGINEERING PLANS WILL NEED TO BE REVIEWED FOR ANY | | | REQUIRED EASEMENTS. | | | 3. APPLICANT SHOULD CONSIDER A CONDOMINIUM WITH THE | | | AMOUNT OF COMMON AREA BEING DISCUSSED. | | | 4. WHEN SUBMITTING FOR SITE PLAN APPROVAL, PLEASE SEE | | | NEW REQUIREMENTS IN PLANNING DEVELOPMENT APPLICATION | | | FOR ENGINEERING. | | | 5. DRIVEWAY MEDIANS SHOULD NOT ENCROACH INTO ALLEY. | | | 6. SHOW OPPOSITE SIDE OF ALLEY PAVEMENT AND | | | IMPROVEMENTS. | | | 7. COMMON AREAS SHOULD BE CLEARLY DELINEATED. | | | 8. ALLEY WILL NEED TO BE REPAVED. HOW WILL STAGING BE | | | HANDLED DURING CONSTRUCTION? | | | 9. LANDSCAPE PLAN WILL NEED TO BE REVIEWED FOR ANY | | | UTILITY CONFLICTS. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
04-10-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-04-09 16:14:30 | (REVISED 4/10/2019) | | | | | | 1. DOCUMENT THE TRIP ASSIGNMENT FROM THE SITE ACCESS TO | | | THE FIRST MAJOR THOROUGHFARE IN THE TRAFFIC STATEMENT. | | | 2. PROVIDE TPS LETTER FROM PALM BEACH COUNTY. | | | 3. PROVIDE UTILITY LETTERS. | | | 4. PROVIDE CIVIL AND LANDSCAPE PLANS. | | | 5. CITY CODE SECTION 94-342 REQUIRES THE ALLEYS TO BE | | | AT LEAST 20 FEET WIDE. ALSO, CITY CODE SECTION | | | 94-485(J) INDICATES THAT IF PARKING STALLS ARE ACCESSED | | | DIRECTLY FROM PUBLIC ALLEY AND EXISTING ALLEY WIDTH | | | DOES NOT COMPLY WITH THE MINIMUM AISLE REQUIREMENTS | | | (WHICH IS 24 FEET FOR 90-DEGREE PARKING), ADDITIONAL | | | PARKING AISLE SHALL BE PROVIDED. | | | 6. THE PROPOSED DEVELOPMENT SHOULD NOT NARROW THE | | | ALLEY. | | | 7. REMOVE GUEST PARKING ALONG THE ALLEY AND COUNT | | | ON-STREET PARKING ON LAMBERT AVENUE TOWARDS GUEST | | | PARKING REQUIREMENT. | | | 8. SHOW CURB CUTS, EDGE OF PAVEMENTS, AND DRIVEWAYS ON | | | THE OPPOSITE SIDE OF LAMBERT AVENUE, CONNISTON ROAD AND | | | THE ALLEY. | | | 9. INCLUDE PARKING REQUIREMENTS IN THE SITE DATA TABLE | | | ON THE SITE PLAN. | | | 10. PROVIDE PEDESTRIAN CURB RAMP AT THE CORNER OF | | | LAMBERT AVENUE AND CONNISTON ROAD. | | | 11. CONSIDER PROVIDING WIDER SIDEWALK ALONG LAMBERT | | | AVENUE AND CONNISTON ROAD. SIDEWALK SHOULD BE A MINIMUM | | | OF 5 FEET. | | | 12. DIMENSION THE ROADWAY WIDTH ON LAMBERT AVENUE, | | | CONNISTON ROAD AND THE ALLEY. | | | 13. CONSIDER PROVIDING A LANDSCAPED CURB EXTENSION ON | | | CONNISTON ROAD ON BOTH ENDS OF THE BLOCK ALONG THE SITE | | | FRONTAGE. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
04-03-2019 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
04-03-2019 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
04-03-2019 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2019-04-03 13:29:24 | PLAT COMMENTS: | | | | | | | | | 1.) ALL SHARED COMMON AREAS (I.E. THE COMMON WALKWAY ON | | | LOTS 6 AND 7 AS SHOWN IN THE ATTACHED PRELIMINARY SITE | | | PLAN) SHALL BE CALLED OUT IN THE PLAT DOCUMENT. | | | | | | 2.) SHOW ALL PROPOSED EASEMENTS ON THE PROPERTY. | | | | | | 3.) A NEW MAYOR WAS RECENTLY ELECTED FOR THE CITY. | | | PLEASE CHANGE THE MAYOR'S SIGNATURE BLOCK TO "KEITH | | | JAMES, MAYOR". | | | | | | 4.) THE SCHOOL CAPACITY AVAILABILITY DETERMINATION | | | (SCAD) LETTER FROM THE SCHOOL DISTRICT OF PALM BEACH | | | COUNTY IS REQUIRED AT TIME OF PLATTING. PLEASE SUBMIT. | | | [NOTE: COMPLETED SCAD FORM SIGNED BY CITY STAFF AND | | | RETURNED TO THE APPLICANT ON 3/28/19] | | | | | | | | | PRELIMINARY SITE PLAN COMMENTS: | | | | | | (THIS IS ONLY A PRELIMINARY REVIEW. A FORMAL REVIEW OF | | | THE SITE PLAN WILL BE CONDUCTED WHEN A FORMAL SUBMITTAL | | | OF THE SITE PLAN IS RECEIVED.) | | | | | | 1.) A VARIANCE TO THE FRONT SETBACK FOR AT LEAST ONCE | | | OF THE UNITS (UNIT 11) WILL BE REQUIRED. | | | | | | 2.) THE "20' FRONT SB" IS NOT ACCURATELY DIMENSIONED. | | | | | | 3.) ANY CHANGES MADE TO THE PLAT SHOULD ALSO BE | | | REFLECTED IN THE SITE PLAN. | | | | | | 4.) PLEASE NOTE THAT THE TRAFFIC PERFORMANCE STANDARDS | | | (TPS) REVIEW LETTER, ISSUED BY THE PALM BEACH COUNTY | | | TRAFFIC DIVISION MUST ACCURATELY REFLECT THE NUMBER OF | | | PROPOSED UNITS. FOR THIS PROJECT, THE SITE PLAN | | | PROPOSES 11 TOWNHOUSE UNITS; AND THE APPROVED TPS | | | LETTER, ISSUED ON NOVEMBER 27, 2018, INDICATES APPROVAL | | | FOR 12 UNITS. PLEASE ADDRESS FOR CONSISTENCY. | | | | | | 5.) FOR THE ARCHITECTURAL ELEVATIONS. PLEASE PROVIDE | | | DIMENSIONS IN THE FLOOR PLAN(S) AND ELEVATION SHEETS. | | | HEIGHT OF THE BUILDING SHALL BE MEASURED FROM GRADE | | | (NOT FF). | | | | | | 6.) ALL ARCHITECTURAL PLANS SHALL BE SIGNED, DATED AND | | | SEALED BY A FLORIDA LICENSED ARCHITECT. | | | | | | | | | INSTRUCTIONS FOR SUBMITTAL | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15 | | | PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11 | | | INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND AN | | | ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT CHANGES | | | ON THE RESUBMITTED PLANS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. | | | | | | * IF PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE | | | SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED | | | A RESUBMITTAL FEE. SUCH FEE WILL BE 20 PERCENT OF THE | | | ORIGINAL APPLICATION FEE ($600). | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE ANY | | | QUESTIONS. |
|
|
| |
Print |
|