Plan Review Details - Project Z19010004
| Plan Review Stops For Project Z19010004 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
02-12-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
02-12-2019 |
Time |
20:44 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
02-12-2019 |
Time |
20:42 |
Sent To |
|
|
| Notes |
| 2019-02-12 20:56:50 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 4. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
07-25-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
07-25-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
07-25-2019 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
01-28-2019 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
01-28-2019 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
01-28-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-01-28 11:24:38 | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF | | | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND | | | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER | | | OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. | | | | | | PLEASE PROVIDE CALCULATIONS OF EXISTING AND PROPOSED | | | DEMANDS FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) | | | AND FIRE FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC | | | 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER. | | | | | | PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND | | | IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED | | | AREAS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
01-28-2019 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
01-28-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
01-28-2019 |
Time |
16:02 |
Sent To |
|
|
| Notes |
| 2019-01-28 16:16:59 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE NEW CONSTRUCTION SHALL COMPLY WITH THE 6TH | | | EDITION OF THE FLORIDA FIRE PREVENTION CODE, INCLUDING | | | NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT WILL BE A MIXED OR SEPARATED OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ANY FIRE LINES, FDC'S AND/OR FIRE HYDRANTS PROPOSED TO | | | BE OUT OF SERVICE FOR THIS PROJECT SHALL BE COORDINATED | | | THROUGH THE OFFICE OF THE FIRE MARSHAL. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM (OR | | | THE EXTENSION OF EXISTING LIFE SAFETY SYSTEMS) PER THE | | | APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY OR | | | NEWLY CREATED SPACE SHALL BE PROVIDED THAT ILLUSTRATE | | | OCCUPANT LOADS, TRAVEL DISTANCES, COMMON PATHS OF | | | TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, EMERGENCY | | | LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS (OR KNOX | | | KEYS BE UPDATED) FOR ENTRY DOOR LOCKS BE PROVIDED FOR | | | 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
09-23-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-23-2019 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-23-2019 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2019-09-23 16:11:31 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: ST MARY?S CSPD Z19010004 | | | SEPTEMBER 23, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE | | | FOLLOWING: | | | ? SATISFIED. ALL TREES BELOW 20 FOOT CANOPY AND PALMS | | | ARE TO BE MITIGATED ONE FOR ONE AND THE CANOPY VALUE | | | NEEDS TO BE CORRECTED TO THE CATEGORY VALUE. I.E. | | | CATEGORY 1, IS A 300 SQ FT CANOPY VALUE, CATEGORY 2 IS | | | A 150 SQ FT CANOPY VALUE. VEITCHI PALM CATEGORY 3 IS A | | | 100 SQ FT CANOPY VALUE. CORRECT VALUE TOTAL. | | | CORRECT CANOPY VALUES FOR LESS THAN 20 FEET CANOPY TO | | | THE VALUE OF THE CATEGORY. PROVIDE THE TOTAL SQUARE | | | FOOTAGE OF CANOPY MITIGATION DUE. | | | ? SATISFIED. CHANGE NOTE TO REFERENCE CORRECT CODE | | | LANGUAGE- TREES THAT ARE 20 FEET OR MORE IN CANOPY SIZE | | | SHALL BE MITIGATED BASED ON CANOPY SIZE. | | | ? SATISFIED. INCLUDE A COLUMN ON THE TREE DISPOSITION | | | LIST FOR CATEGORY. | | | ? SATISFIED. PROVIDE A LIST OF CANOPY CREDIT FOR THE | | | TREES TO BE INSTALLED AS SHOWN ON THE PROPOSED | | | LANDSCAPE PLAN. | | | ASSIGN CANOPY CREDIT BASED ON CATEGORY FOR ALL TREES | | | AND PALMS ON THE PLANT LIST AND PROVIDE THE TOTAL | | | CANOPY CREDITS PROVIDED. | | | | | | 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE | | | TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR | | | RELOCATED. THERE IS 1 LIVE OAK, 12 SABAL PALMS AND | | | 1DAHOON HOLLY THAT CAN BE PRESERVED OR RELOCATED ON | | | SITE TO AREAS WITHOUT TREES. THIS LARGE LIVE OAK TREE | | | IS NOT WITHIN THE LIMITS OF DEMOLITION OR CONSTRUCTION | | | AND CAN BE PRESERVED BY DESIGNING THE PROPOSED SIDEWALK | | | LAYOUT TO AVOID IT. | | | SIDEWALK IS STILL SHOWN TOO CLOSE TO TREE, ADJUST | | | LOCATION TO AVOID CRITICAL ROOT ZONE OF THE TREE AND | | | PREVENT DAMAGE TO TREE ROOTS. IF IT IS NECESSARY, | | | RELOCATE SABAL PALMS TO ALLOW SIDEWALK ADJUSTMENT. | | | | | | 3. SATISFIED. THE GREEN BUTTONWOOD TREES PLACED CLOSE | | | TO THE BUILDING MAY BE A MAINTENANCE ISSUE IN THE | | | FUTURE, IF MOVED OUT AWAY FROM THE BUILDING, THE TREE | | | CANOPY CAN REACH FULL POTENTIAL. | | | | | | 4. SATISFIED. PROVIDE THE AMOUNT OF OPEN SPACE AND | | | LANDSCAPE AREA ON THE LANDSCAPE PLAN FOR THE AFFECTED | | | AREA AND SHOW THE CHANGE FROM EXISTING CONDITION. | | | | | | 5. SATISFIED. PROVIDE THE NUMBER OF TREES PROPOSED | | | COMPARED TO THE NUMBER OF TREES FROM THE APPROVED | | | LANDSCAPE PLAN FOR THE AFFECTED AREA. | | | 6. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL | | | ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C | | | UNITS, ETC. | | | | | | 7. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES | | | ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS | | | REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE | | | PLAN. | | | | | | 8. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | CALCULATION FOR PERCENTAGE IS FOR ADDED PLANT MATERIAL, | | | NOT REQUIRED. REVISE AND PROVIDE PERCENTAGE. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
08-09-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
08-09-2019 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
08-09-2019 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2019-08-09 13:57:05 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: ST MARY?S CSPD Z19010004 | | | AUGUST 1, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE | | | FOLLOWING: | | | ? PARTIALLY SATISFIED. ALL TREES BELOW 20 FOOT CANOPY | | | AND PALMS ARE TO BE MITIGATED ONE FOR ONE AND THE | | | CANOPY VALUE NEEDS TO BE CORRECTED TO THE CATEGORY | | | VALUE. I.E. CATEGORY 1, IS A 300 SQ FT CANOPY VALUE, | | | CATEGORY 2 IS A 150 SQ FT CANOPY VALUE. VEITCHI PALM | | | CATEGORY 3 IS A 100 SQ FT CANOPY VALUE. CORRECT VALUE | | | TOTAL. | | | CORRECT CANOPY VALUES FOR LESS THAN 20 FEET CANOPY TO | | | THE VALUE OF THE CATEGORY. PROVIDE THE TOTAL SQUARE | | | FOOTAGE OF CANOPY MITIGATION DUE. | | | ? SATISFIED. CHANGE NOTE TO REFERENCE CORRECT CODE | | | LANGUAGE- TREES THAT ARE 20 FEET OR MORE IN CANOPY SIZE | | | SHALL BE MITIGATED BASED ON CANOPY SIZE. | | | ? SATISFIED. INCLUDE A COLUMN ON THE TREE DISPOSITION | | | LIST FOR CATEGORY. | | | ? PARTIALLY SATISFIED. PROVIDE A LIST OF CANOPY CREDIT | | | FOR THE TREES TO BE INSTALLED AS SHOWN ON THE PROPOSED | | | LANDSCAPE PLAN. | | | ASSIGN CANOPY CREDIT BASED ON CATEGORY FOR ALL TREES | | | AND PALMS ON THE PLANT LIST AND PROVIDE THE TOTAL | | | CANOPY CREDITS PROVIDED. | | | | | | 2. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES | | | NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE | | | OR RELOCATED. THERE IS 1 LIVE OAK, 12 SABAL PALMS AND | | | 1DAHOON HOLLY THAT CAN BE PRESERVED OR RELOCATED ON | | | SITE TO AREAS WITHOUT TREES. THIS LARGE LIVE OAK TREE | | | IS NOT WITHIN THE LIMITS OF DEMOLITION OR CONSTRUCTION | | | AND CAN BE PRESERVED BY DESIGNING THE PROPOSED SIDEWALK | | | LAYOUT TO AVOID IT. | | | SIDEWALK IS STILL SHOWN TOO CLOSE TO TREE, ADJUST | | | LOCATION TO AVOID CRITICAL ROOT ZONE OF THE TREE AND | | | PREVENT DAMAGE TO TREE ROOTS. IF IT IS NECESSARY, | | | RELOCATE SABAL PALMS TO ALLOW SIDEWALK ADJUSTMENT. | | | | | | 3. SATISFIED. THE GREEN BUTTONWOOD TREES PLACED CLOSE | | | TO THE BUILDING MAY BE A MAINTENANCE ISSUE IN THE | | | FUTURE, IF MOVED OUT AWAY FROM THE BUILDING, THE TREE | | | CANOPY CAN REACH FULL POTENTIAL. | | | | | | 4. SATISFIED. PROVIDE THE AMOUNT OF OPEN SPACE AND | | | LANDSCAPE AREA ON THE LANDSCAPE PLAN FOR THE AFFECTED | | | AREA AND SHOW THE CHANGE FROM EXISTING CONDITION. | | | | | | 5. SATISFIED. PROVIDE THE NUMBER OF TREES PROPOSED | | | COMPARED TO THE NUMBER OF TREES FROM THE APPROVED | | | LANDSCAPE PLAN FOR THE AFFECTED AREA. | | | 6. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL | | | ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C | | | UNITS, ETC. | | | | | | 7. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES | | | ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS | | | REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE | | | PLAN. | | | | | | 8. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 | | | L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | CALCULATION FOR PERCENTAGE IS FOR ADDED PLANT MATERIAL, | | | NOT REQUIRED. REVISE AND PROVIDE PERCENTAGE. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
02-12-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
02-12-2019 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
02-12-2019 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2019-02-12 13:10:31 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: ST MARY?S CSPD Z19010004 | | | FEBRUARY 12, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE | | | FOLLOWING: | | | ? ALL TREES BELOW 20 FOOT CANOPY AND PALMS ARE TO BE | | | MITIGATED ONE FOR ONE AND THE CANOPY VALUE NEEDS TO BE | | | CORRECTED TO THE CATEGORY VALUE. I.E. CATEGORY 1, IS A | | | 300 SQ FT CANOPY VALUE, CATEGORY 2 IS A 150 SQ FT | | | CANOPY VALUE. VEITCHI PALM CATEGORY 3 IS A 100 SQ FT | | | CANOPY VALUE. CORRECT VALUE TOTAL. | | | ? CHANGE NOTE TO REFERENCE CORRECT CODE LANGUAGE- TREES | | | THAT ARE 20 FEET OR MORE IN CANOPY SIZE SHALL BE | | | MITIGATED BASED ON CANOPY SIZE. | | | ? INCLUDE A COLUMN ON THE TREE DISPOSITION LIST FOR | | | CATEGORY. | | | ? PROVIDE A LIST OF CANOPY CREDIT FOR THE TREES TO BE | | | INSTALLED AS SHOWN ON THE PROPOSED LANDSCAPE PLAN. | | | | | | 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD | | | CONDITION TO BE PRESERVED ON SITE OR RELOCATED. THERE | | | IS 1 LIVE OAK, 12 SABAL PALMS AND 1DAHOON HOLLY THAT | | | CAN BE PRESERVED OR RELOCATED ON SITE TO AREAS WITHOUT | | | TREES. THIS LARGE LIVE OAK TREE IS NOT WITHIN THE | | | LIMITS OF DEMOLITION OR CONSTRUCTION AND CAN BE | | | PRESERVED BY DESIGNING THE PROPOSED SIDEWALK LAYOUT TO | | | AVOID IT. | | | 3. THE GREEN BUTTONWOOD TREES PLACED CLOSE TO THE | | | BUILDING MAY BE A MAINTENANCE ISSUE IN THE FUTURE, IF | | | MOVED OUT AWAY FROM THE BUILDING, THE TREE CANOPY CAN | | | REACH FULL POTENTIAL. | | | | | | 4. PROVIDE THE AMOUNT OF OPEN SPACE AND LANDSCAPE AREA | | | ON THE LANDSCAPE PLAN FOR THE AFFECTED AREA AND SHOW | | | THE CHANGE FROM EXISTING CONDITION. | | | | | | 5. PROVIDE THE NUMBER OF TREES PROPOSED COMPARED TO THE | | | NUMBER OF TREES FROM THE APPROVED LANDSCAPE PLAN FOR | | | THE AFFECTED AREA. | | | 6. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE GROUND | | | UTILITY VALVES, BACKFLOW PREVENTERS, A/C UNITS, ETC. | | | | | | 7. SHOW LOCATIONS OF WATER AND SEWER LINES ON THE | | | LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO PROTECT | | | UTILITY LINES AND LABEL THEM ON THE PLAN. | | | | | | 8. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
02-09-2019 |
|
|
Cont ID |
|
| Sent By |
|
Date |
02-09-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
02-09-2019 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
P |
Date |
09-12-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-12-2019 |
Time |
09:01 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-12-2019 |
Time |
09:02 |
Sent To |
|
|
| Notes |
| 2019-09-12 09:02:07 | PASSED FOR 9/6/19 SUBMITTAL REVIEW PACKAGE. |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
07-29-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
07-29-2019 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
07-29-2019 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2019-07-29 12:01:12 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 7/11/19 SUBMITTAL PACKAGE: | | | | | | 1. LABEL VERTICAL DATUM AND PROVIDE CONVERSION TO | | | NGVD1929 ON ALL SHEETS WITH ELEVATION DATA.[REPEAT | | | COMMENT] | | | | | | 2. CROSS SLOPE OF ROADWAY ADJACENT TO EMERGENCY | | | ENTRANCE APPEARS TO BE UP TO 4.8% SLOPE.[REPEAT | | | COMMENT] | | | | | | 3. GENERAL CONSTRUCTION NOTES [REPEAT COMMENT] | | | A. #13 CITY TO RECEIVE COPY OF FDEP ACCEPTED NOI. | | | B. #21 CITY NAME MISSING. | | | | | | 4. NO WRITTEN RESPONSES PROVIDED FOR FIRST ROUND OF | | | STORMWATER COMMENTS. | | | | | | 5. WATER AND SEWER NOTES [REPEAT COMMENT] | | | A. #4 MAX. DEFLECTION MAY BE LIMITED TO 75% OF | | | MANUFACTURER'S RECOMMENDATION. SEE CWPB STANDARD DETAIL | | | P-12. | | | B. #13 MATERIAL FOR UTILITIES TO BE MAINTAINED BY THE | | | CITY OF WEST PALM BEACH TO BE PER THE CITY'S APPROVED | | | MATERIALS LIST. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
02-15-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
02-15-2019 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
02-15-2019 |
Time |
10:28 |
Sent To |
|
|
| Notes |
| 2019-02-15 10:28:15 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. LABEL VERTICAL DATUM AND PROVIDE CONVERSION TO | | | NGVD1929 ON ALL SHEETS WITH ELEVATION DATA. | | | | | | 2. CROSS SLOPE OF ROADWAY ADJACENT TO EMERGENCY | | | ENTRANCE APPEARS TO BE UP TO 4.8% SLOPE. | | | | | | 3. GENERAL CONSTRUCTION NOTES | | | A. #13 CITY TO RECEIVE COPY OF FDEP ACCEPTED NOI. | | | B. #21 CITY NAME MISSING. | | | | | | 4. SURVEY DATA NOTES | | | A. #3 PROVIDE CONVERSION EQUATION BETWEEN NAVD1988 AND | | | NGVD1929. | | | | | | 5. WATER AND SEWER NOTES | | | A. #4 MAX. DEFLECTION MAY BE LIMITED TO 75% OF | | | MANUFACTURER?S RECOMMENDATION. | | | B. #13 MATERIAL FOR UTILITIES TO BE MAINTAINED BY THE | | | CITY OF WEST PALM BEACH TO BE PER THE CITY?S APPROVED | | | MATERIALS LIST. | | | | | | 6. STERILE BUILDING PLANS ? | | | A. DO EXISTING SANITARY SEWER AND STORM SEWER NEED TO | | | REMAIN UNDER THE PROPOSED BUILDING. | | | B. EXISTING UTILITIES SHOULD BE TV PRIOR TO START OF | | | CONSTRUCTION. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION PRIOR | | | TO STARTING CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
09-11-2019 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-11-2019 |
Time |
08:23 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-09-11 08:23:47 | PREVIOUS COMMENTS NOT ADDRESSED. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
02-01-2019 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
02-01-2019 |
Time |
08:14 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-02-01 08:14:21 | 1. NEED SIGNED AND SEALED COPY OF SURVEY. | | | 2. ADD CONVERSION FACTOR FROM NAVD TO NGVD TO SURVEY | | | AND ENG. PLANS. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
09-17-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-09-17 12:16:20 | PASSED. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
07-24-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-07-24 11:49:37 | PASSED, WITH THE FOLLOWING CONDITIONS OF APPROVAL: | | | | | | 1. PROVIDE COUNTY TPS LETTER. | | | 2. IN THE PROPOSED EMERGENCY DEPARTMENT EXPANSION, "DO | | | NOT ENTER" AND "STOP" SIGNS SHOULD BE PROVIDED AT THE | | | EXITS OF THE PORTE COCHERE DURING PERMITTING. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
02-06-2019 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-02-06 14:30:52 | 1. PROVIDE COUNTY TPS LETTER. | | | 2. CLARIFY THE INCREASE IN INTENSITY. THE JUSTIFICATION | | | STATEMENT INDICATES AN INCREASE OF 10,500 S.F. OF | | | BUILDING AREA, THE OVERALL SITE PLAN (SHEET C-1200) | | | INDICATES AN INCREASE OF 4,200 S.F., AND THE TRAFFIC | | | STUDY INDICATES AN INCREASE OF 10,020 S.F. (742,965 | | | S.F. MINUS 732,945 S.F.). | | | 3. JUSTIFICATION STATEMENT INDICATES THERE IS NO | | | INCREASE IN TRAFFIC IMPACT, BUT THE TRAFFIC STATEMENT | | | SHOWS THAT THE OVERALL TRIP GENERATION INCREASES, WHICH | | | WOULD REQUIRE A MAJOR AMENDMENT. | | | 4. IN THE PROPOSED EMERGENCY DEPARTMENT EXPANSION, | | | PROVIDE "DO NOT ENTER" AND "STOP" SIGNS AT THE EXITS OF | | | THE PORTE COCHERE. | | | 5. THE TRAFFIC STUDY NEEDS TO BE SIGNED AND SEALED. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
08-13-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
08-13-2019 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2019-08-13 10:42:20 | ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT | | | OF AN EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION | | | COSTS ARE EQUAL OR GREATER THAN $750,000 IS | | | SUBJECT TO THE ART IN PUBLIC PLACES REQUIREMENTS OF | | | CHAPTER 78, ARTICLE V, OF THE CITY?S CODE OF | | | ORDINANCES. CONTACT SYBILLE WELTER @ 561-822-1521 OR | | | [email protected] FOR ADDITIONAL | | | INFORMATION. | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
02-12-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
02-12-2019 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2019-02-12 11:36:17 | ST. MARY?S CSPD MINOR AMENDMENT | | | PLATS AND PLANS REVIEW COMMITTEE ? 2/13/19 | | | PB 1068HH - Z1901004 | | | | | | 1) PLEASE PROVIDE A MORE LEGIBLE OVERALL MASTER PLAN | | | 2) PLEASE PROVIDE A BREAKDOWN (CHART) OF SQUARE FOOTAGE | | | AND ACCOMPANYING USES OF 1.) WHAT HAS BEEN PREVIOUSLY | | | APPROVED 2.) WHAT IS BEING PROPOSED 3.) WHAT HAS BEEN | | | CONSTRUCTED OVERALL IN THE ST MARY?S CSPD | | | 3) PLEASE PROVIDE ARCHITECTURAL ELEVATIONS FOR PROPOSED | | | EXPANSIONS. CLEARLY INDICATE AREA OF EXPANSION | | | 4) STAFF SUPPORTS THE ADDITION OF BIKE RACKS PLACED AT | | | STRATEGIC LOCATIONS THROUGHOUT THE PROPERTY TO BE MADE | | | AVAILABLE TO HOSPITAL STAFF. PROVIDE CITY-STANDARD | | | DETAIL ON PLANS | | | 5) INDICATE AREA OF PROPOSED BUILDING EXPANSIONS ON | | | SITE PLAN BY SHADING OR HATCHING AREA OF EXPANSION | | | 6) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE | | | ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT | | | SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR | | | ADDITIONAL INFORMATION | | | | | | WHEN RESUBMITTING, PLEASE PROVIDE A TEN (10) PAPER | | | COPIES AND AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE | | | CHANGES ON THE RESUBMITTED PLAN MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443 IF | | | THERE ARE ANY QUESTIONS | | | |
|
|
| |