Plan Review Details - Project Z18110023
Plan Review Stops For Project Z18110023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 12-11-2018 Cont ID  
Sent By rbrown Date 12-11-2018 Time 19:11 Rev Time 0.00
Received By tward Date 02-15-2019 Time 10:36 Sent To  
Notes
2018-12-11 19:28:17DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. FLOOD ZONE. ACCORDING TO THE ADOPTED FLOOD INSURANCE
 RATE MAPS (FIRMS), THE PROPOSED BUILDING IS IN FLOOD
 ZONE AE, WITH A BASE FLOOD ELEVATION OF 12 FT NAVD. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 3. NUMBER OF ACCESSIBLE PARKING SPACES. SHEET C101,
 DEMOLITION PLAN, SHOWS THE REMOVAL OF 4 ACCESSIBLE
 PARKING SPACES, BUT SHEET C301, SITE PLAN, SHOWS ONLY 2
 ACCESSIBLE PARKING SPACES BEING REINSTATED. THE PARKING
 REQUIREMENTS TABLES ON BOTH SHEET C300 AND C301, SITE
 PLAN, STATE THAT 8 ACCESSIBLE SPACES (6 + 2) ARE
 PROPOSED, BUT THE PLANS ONLY SHOW THE LOCATION OF 2 OF
 THOSE SPACES. THE MINIMUM NUMBER OF ACCESSIBLE PARKING
 SPACES PROVIDED SHALL BE IN ACCORDANCE WITH SECTION
 208.2 OF FLORIDA ACCESSIBILITY CODE.
  
 4. LOCATION OF ACCESSIBLE PARKING SPACES. PER SECTION
 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING
 SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE
 OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE
 ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL
 COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 9. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By rbrown Date 12-11-2018 Time 19:10 Sent To  
Notes
2018-12-10 10:57:30Z18110023_JFK NORTH HOSPITAL MAJOR PD AMENDMENT
 (NOVEMBER 13, 2018 SUBMITTAL)
 TRAFFIC STUDY
 1. PLEASE PROVIDE COUNTY TPS LETTER.
 2. IN THE TRAFFIC STUDY, THE SOUTHERN DRIVEWAY DOES NOT
 PERMIT EGRESS VEHICLES TO MAKE LEFT-TURN. PLEASE REVISE
 THE TRIP ASSIGNMENT.
 SITE PLAN
 3. ON SHEET C300, PROVIDE CROSSWALK FROM THE BUILDING
 TO THE OPPOSITE SIDE OF THE INTERNAL ROADWAY. ALSO
 PROVIDE PEDESTRIAN CURB RAMP.
 4. ON SHEET C301, PROVIDE AUTOTURN PATH TO VERIFY IF A
 PASSENGER CAR CAN MAKE RIGHT-TURN INTO THE FIRST
 PARKING AISLE ON THE SOUTH.
 5. ON SHEET C301, PROVIDE PEDESTRIAN CONNECTION BETWEEN
 THE EXISTING PEDESTRIAN CONNECTION NEAR THE MATCH LINE
 WITH SHEET C300 AND THE PROPOSED BUILDING .
 6. PROVIDE BICYCLE PARKING NEAR THE PROPOSED BUILDINGS.
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 05-31-2019 Cont ID  
Sent By rrossano Date 05-31-2019 Time   Rev Time 0.00
Received By rrossano Date 05-31-2019 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 04-08-2019 Cont ID  
Sent By rrossano Date 04-08-2019 Time   Rev Time 0.00
Received By rrossano Date 04-08-2019 Time   Sent To  
Notes
2019-04-08 11:01:20PLEASE PROVIDE VERTICAL DATUM AND DATUM CONVERSION
 INFORMATION NOTE (NAVD 1988 AND NGVD 1929) ON ALL
 UTILITY RELATED SHEETS.
  
 PLEASE PROVIDE CALCULATIONS OF REVISED PERVIOUS AND
 IMPERVIOUS CALCULATIONS FOR THE PROPOSED IMPACTED
 AREAS.
  
 PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS
 FOR WATER & SEWER (AVERAGE, MAXIMUM & PEAK) AND FIRE
 FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR
 SEWER AND PER FAC 64-E.008 FOR WATER.
  
 SHEETS C400 AND C401: REMOVE "CITY OF ATLANTIS" FROM
 NOTE 5 ON EACH PAGE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-06-2018 Cont ID  
Sent By RRossano Date 12-06-2018 Time   Rev Time  
Received By rrossano Date 12-06-2018 Time   Sent To I
Notes
2018-12-06 12:30:07PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS
 FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) AND FIRE
 FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR
 SEWER AND PER FAC 64-E.008 FOR WATER.
  
 PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS AT NEW
 BUILDINGS OVER EXISTING UTILITIES.
  
 IDENTIFY OWNERSHIP OF WATER MAIN (CITY OF WPB VS.
 PRIVATE).
  
 SHOW CITY OF WPB POINT OF SERVICE.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-04-2018 Cont ID  
Sent By pleduc Date 12-04-2018 Time   Rev Time 0.00
Received By pleduc Date 12-04-2018 Time 14:01 Sent To  
Notes
2018-12-04 14:11:37THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION
 DISTANCES FROM MAIN STRUCTURES AS WELL AS OTHER
 TRAILERS SHALL BE CLOSELY MONITORED FOR THE
 REQUIREMENTS OF FIRE SPRINKLER PROTECTION.
  
 PLEASE PROVIDE DETAILS ON HOW THIS CONSTRUCTION
 WILL/CAN BE ISOLATED FROM THE EXISTING BUIDLING(S) AND
 WILL NOT AFFECT ANY LIFE SAFETY OR EXITING CONDITIONS.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 IF THE EXISTING FIRE SPRINKLER OR FIRE ALARM SYSTEM(S)
 WILL BE EXTENDED INTO THE NEW AREAS, PROVIDE SPECIFIC
 DETAILS THAT THE EXISTING SYSTEM(S) CAN ACCOMDATE THE
 ADDITION(S).
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 5 Status P Date 08-27-2019 Cont ID  
Sent By rcaranci Date 08-27-2019 Time 15:48 Rev Time 0.00
Received By rcaranci Date 08-27-2019 Time 15:47 Sent To  
Notes
2019-08-27 15:48:32FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: WEST PALM HOSPITAL CSPD Z18110023
 AUGUST 27, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE
 FOLLOWING:
 ? SATISFIED. ALL TREES BELOW 20 FOOT CANOPY ARE TO BE
 MITIGATED ONE FOR ONE AND THE CANOPY VALUE NEEDS TO BE
 CORRECTED TO THE CATEGORY VALUE. I.E. LIVE OAK CATEGORY
 1, IS A 300 SQ FT CANOPY VALUE. BOTTLEBRUSH CATEGORY 2
 IS A 150 SQ FT CANOPY VALUE. SABAL PALM CATEGORY 3 IS A
 100 SQ FT CANOPY VALUE. CORRECT VALUE AS SHOWN IS
 16,395 SQ FT.
 TREE CANOPY DIAMETER AND CANOPY VALUES MUST BE SHOWN
 FOR EACH TREE TO BE REMOVED.
 ? SATISFIED. TREES REMAINING WITHIN THE CONSTRUCTION
 LIMITS NEED TO BE SHOWN AS REQUIRING ROOT PROTECTION.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. THERE ARE MULTIPLE LIVE OAKS THAT CAN BE
 RELOCATED ON SITE TO AREAS WITHOUT TREES. THERE ARE
 LARGE TREES WITHIN THE LIMITS OF CONSTRUCTION THAT CAN
 BE PRESERVED BY DESIGNING THE PROPOSED SIDEWALK LAYOUT
 TO AVOID THEM.
 LIVE OAK TREES 311, 314 AND 315 CAN BE PRESERVED IF THE
 SIDEWALK CAN BE REDESIGNED, AND IF NOT, SINCE THEIR
 CONDITION IS LISTED AS ?GOOD? ON THE TREE DISPOSITION
 LIST, THEY MUST BE RELOCATED.
 LIVE OAK TREES 363, 386, 387, 390, 391, 392, 393, 395,
 396, AND SABAL PALM 394 ARE REQUIRED TO BE RELOCATED AS
 THEIR CONDITION IS LISTED AS ?GOOD? ON THE TREE
 DISPOSITION LIST.
  
 3. SATISFIED. PROVIDE THE AMOUNT OF OPEN SPACE AND
 LANDSCAPE AREA ON THE LANDSCAPE PLAN FOR THE AFFECTED
 AREA AND SHOW THE CHANGE FROM APPROVED PLAN.
 THE CALCULATIONS AS SHOWN ARE NOT CLEAR, AND DO NOT ADD
 UP.
 THE CALCULATIONS NEED TO BE SHOWN FOR THE ENTIRE SITE,
 AS ADDITIONAL AREA IS BEING ADDED TO THE PD. THE
 REQUIRED OPEN SPACE FOR CS IS 40%. OPEN SPACE IS ALL
 NON-BUILDING AREA. LANDSCAPE AREA SHOULD BE EQUAL OR
 GREATER THAN 15%.
  
 4. SATISFIED. PROVIDE THE NUMBER OF TREES PROPOSED
 COMPARED TO THE NUMBER OF TREES FROM THE APPROVED
 LANDSCAPE PLAN FOR THE AFFECTED AREA.
  
 5. SATISFIED. PROVIDE A CORRECTED CHART SHOWING CURRENT
 CODE FOR COMPLIANCE WITH FLORIDA FRIENDLY REQUIREMENTS
 PER SECTION 94-442 (G) AND PROVIDE THE REQUIRED 50
 POINTS.
  
 6. SATISFIED. ADD COLUMNS TO THE PLANT LIST FOR NATIVE
 PLANT AND DROUGHT TOLERANCE.
  
 7. SATISFIED. SHOW ALL EXISTING TREES TO REMAIN WITH
 IDENTIFYING TAGS ON THE PLAN AND INCLUDE ON THE PLANT
 LIST.
  
  
 8. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 9. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL
 ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C
 UNITS, ETC.
  
 10. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES
 ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE
 PLAN.
  
 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 SHOW THE CALCULATION OF THE PERCENTAGE ON THE LANDSCAPE
 PLAN BASED ON THE PROPOSED PLANT LIST.
 ADDITIONAL COMMENTS 2/19/19:
 12. SATISFIED. SHEET L006 DOES NOT REPRESENT ANY
 MISSING TREES FROM THE APPROVED PLANS BEING REPLACED AT
 SOME OF THE TERMINAL ISLANDS AND THE LANDSCAPE BUFFERS
 ALONG THE PROPERTY LINES. ALL TREES AS APPROVED NEED TO
 BE SHOWN AS BEING REPLACED.
  
 13. SATISFIED. THE WAX MYRTLE AS SPECIFIED ARE NOT A
 SUCCESSFUL SPECIES WHEN USED IN PARKING LOT ISLANDS.
 CHANGE TO A MORE DEPENDABLE AND SUSTAINABLE SPECIES.
 ADDITIONAL COMMENTS 4/22/19:
 14. SATISFIED. TWO NEW TERMINAL ISLANDS AND ONE
 INTERIOR ISLAND IN THE PARKING AREA SOUTH OF THE NEW
 BUILDING ON SHEET L102 DO NOT SHOW THE REQUIRED TREE.
 THESE ARE NEW LANDSCAPE AREAS AND ARE REQUIRED TO MEET
 CODE.
 TERMINAL LANDSCAPE ISLANDS REQUIRE A TREE. THESE ARE
 NEWLY CONSTRUCTED PARKING FEATURES AND MUST MEET THE
 CODE REQUIREMENT.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 06-06-2019 Cont ID  
Sent By rcaranci Date 06-06-2019 Time 11:19 Rev Time 0.00
Received By rcaranci Date 06-06-2019 Time 11:19 Sent To  
Notes
2019-06-06 11:27:18FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: WEST PALM HOSPITAL CSPD Z18110023
 JUNE 6, 2019
 RESPONSES TO COMMENTS DID NOT REFLECT COMMENTS FROM
 4/22/19 REVIEW.
 ALL COMMENTS WERE SATISFIED EXCEPT COMMENT 14.
  
 14. PARTIALLY SATISFIED. TWO NEW TERMINAL ISLANDS AND
 ONE INTERIOR ISLAND IN THE PARKING AREA SOUTH OF THE
 NEW BUILDING ON SHEET L102 DO NOT SHOW THE REQUIRED
 TREE.
 THESE ARE NEW LANDSCAPE AREAS AND ARE REQUIRED TO MEET
 CODE.
  
 TERMINAL LANDSCAPE ISLANDS REQUIRE A TREE. THESE ARE
 NEWLY CONSTRUCTED PARKING FEATURES AND MUST MEET THE
 CODE REQUIREMENT.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 04-22-2019 Cont ID  
Sent By rcaranci Date 04-22-2019 Time 15:58 Rev Time 0.00
Received By rcaranci Date 04-22-2019 Time 15:58 Sent To  
Notes
2019-04-22 15:59:16FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: WEST PALM HOSPITAL CSPD Z18110023
 APRIL 22, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE
 FOLLOWING:
 ? SATISFIED. ALL TREES BELOW 20 FOOT CANOPY ARE TO BE
 MITIGATED ONE FOR ONE AND THE CANOPY VALUE NEEDS TO BE
 CORRECTED TO THE CATEGORY VALUE. I.E. LIVE OAK CATEGORY
 1, IS A 300 SQ FT CANOPY VALUE. BOTTLEBRUSH CATEGORY 2
 IS A 150 SQ FT CANOPY VALUE. SABAL PALM CATEGORY 3 IS A
 100 SQ FT CANOPY VALUE. CORRECT VALUE AS SHOWN IS
 16,395 SQ FT.
 TREE CANOPY DIAMETER AND CANOPY VALUES MUST BE SHOWN
 FOR EACH TREE TO BE REMOVED.
 ? SATISFIED. TREES REMAINING WITHIN THE CONSTRUCTION
 LIMITS NEED TO BE SHOWN AS REQUIRING ROOT PROTECTION.
  
 2. SATISFIED. SECTION 94-448 (D)(3) REQUIRES NATIVE
 TREES IN GOOD CONDITION TO BE PRESERVED ON SITE OR
 RELOCATED. THERE ARE MULTIPLE LIVE OAKS THAT CAN BE
 RELOCATED ON SITE TO AREAS WITHOUT TREES. THERE ARE
 LARGE TREES WITHIN THE LIMITS OF CONSTRUCTION THAT CAN
 BE PRESERVED BY DESIGNING THE PROPOSED SIDEWALK LAYOUT
 TO AVOID THEM.
 LIVE OAK TREES 311, 314 AND 315 CAN BE PRESERVED IF THE
 SIDEWALK CAN BE REDESIGNED, AND IF NOT, SINCE THEIR
 CONDITION IS LISTED AS ?GOOD? ON THE TREE DISPOSITION
 LIST, THEY MUST BE RELOCATED.
 LIVE OAK TREES 363, 386, 387, 390, 391, 392, 393, 395,
 396, AND SABAL PALM 394 ARE REQUIRED TO BE RELOCATED AS
 THEIR CONDITION IS LISTED AS ?GOOD? ON THE TREE
 DISPOSITION LIST.
  
 3. SATISFIED. PROVIDE THE AMOUNT OF OPEN SPACE AND
 LANDSCAPE AREA ON THE LANDSCAPE PLAN FOR THE AFFECTED
 AREA AND SHOW THE CHANGE FROM APPROVED PLAN.
 THE CALCULATIONS AS SHOWN ARE NOT CLEAR, AND DO NOT ADD
 UP.
 THE CALCULATIONS NEED TO BE SHOWN FOR THE ENTIRE SITE,
 AS ADDITIONAL AREA IS BEING ADDED TO THE PD. THE
 REQUIRED OPEN SPACE FOR CS IS 40%. OPEN SPACE IS ALL
 NON-BUILDING AREA. LANDSCAPE AREA SHOULD BE EQUAL OR
 GREATER THAN 15%.
  
 4. SATISFIED. PROVIDE THE NUMBER OF TREES PROPOSED
 COMPARED TO THE NUMBER OF TREES FROM THE APPROVED
 LANDSCAPE PLAN FOR THE AFFECTED AREA.
  
 5. SATISFIED. PROVIDE A CORRECTED CHART SHOWING CURRENT
 CODE FOR COMPLIANCE WITH FLORIDA FRIENDLY REQUIREMENTS
 PER SECTION 94-442 (G) AND PROVIDE THE REQUIRED 50
 POINTS.
  
 6. SATISFIED. ADD COLUMNS TO THE PLANT LIST FOR NATIVE
 PLANT AND DROUGHT TOLERANCE.
  
 7. SATISFIED. SHOW ALL EXISTING TREES TO REMAIN WITH
 IDENTIFYING TAGS ON THE PLAN AND INCLUDE ON THE PLANT
 LIST.
  
  
 8. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 9. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL
 ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C
 UNITS, ETC.
  
 10. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES
 ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE
 PLAN.
  
 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 SHOW THE CALCULATION OF THE PERCENTAGE ON THE LANDSCAPE
 PLAN BASED ON THE PROPOSED PLANT LIST.
 ADDITIONAL COMMENTS 2/19/19:
 12. SATISFIED. SHEET L006 DOES NOT REPRESENT ANY
 MISSING TREES FROM THE APPROVED PLANS BEING REPLACED AT
 SOME OF THE TERMINAL ISLANDS AND THE LANDSCAPE BUFFERS
 ALONG THE PROPERTY LINES. ALL TREES AS APPROVED NEED TO
 BE SHOWN AS BEING REPLACED.
  
 13. SATISFIED. THE WAX MYRTLE AS SPECIFIED ARE NOT A
 SUCCESSFUL SPECIES WHEN USED IN PARKING LOT ISLANDS.
 CHANGE TO A MORE DEPENDABLE AND SUSTAINABLE SPECIES.
 ADDITIONAL COMMENTS 2/19/19:
 14. TWO NEW TERMINAL ISLANDS AND ONE INTERIOR ISLAND IN
 THE PARKING AREA SOUTH OF THE NEW BUILDING ON SHEET
 L102 DO NOT SHOW THE REQUIRED TREE. THESE ARE NEW
 LANDSCAPE AREAS AND ARE REQUIRED TO MEET CODE.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 02-19-2019 Cont ID  
Sent By rcaranci Date 02-19-2019 Time 17:04 Rev Time 0.00
Received By rcaranci Date 02-19-2019 Time 17:03 Sent To  
Notes
2019-02-19 17:04:34FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: WEST PALM HOSPITAL CSPD Z18110023
 FEBRUARY 19, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE
 FOLLOWING:
 ? NOT SATISFIED. ALL TREES BELOW 20 FOOT CANOPY ARE TO
 BE MITIGATED ONE FOR ONE AND THE CANOPY VALUE NEEDS TO
 BE CORRECTED TO THE CATEGORY VALUE. I.E. LIVE OAK
 CATEGORY 1, IS A 300 SQ FT CANOPY VALUE. BOTTLEBRUSH
 CATEGORY 2 IS A 150 SQ FT CANOPY VALUE. SABAL PALM
 CATEGORY 3 IS A 100 SQ FT CANOPY VALUE. CORRECT VALUE
 AS SHOWN IS 16,395 SQ FT.
 TREE CANOPY DIAMETER AND CANOPY VALUES MUST BE SHOWN
 FOR EACH TREE TO BE REMOVED.
 ? SATISFIED. TREES REMAINING WITHIN THE CONSTRUCTION
 LIMITS NEED TO BE SHOWN AS REQUIRING ROOT PROTECTION.
  
 2. PARTIALLY SATISFIED. SECTION 94-448 (D)(3) REQUIRES
 NATIVE TREES IN GOOD CONDITION TO BE PRESERVED ON SITE
 OR RELOCATED. THERE ARE MULTIPLE LIVE OAKS THAT CAN BE
 RELOCATED ON SITE TO AREAS WITHOUT TREES. THERE ARE
 LARGE TREES WITHIN THE LIMITS OF CONSTRUCTION THAT CAN
 BE PRESERVED BY DESIGNING THE PROPOSED SIDEWALK LAYOUT
 TO AVOID THEM.
 LIVE OAK TREES 311, 314 AND 315 CAN BE PRESERVED IF THE
 SIDEWALK CAN BE REDESIGNED, AND IF NOT, SINCE THEIR
 CONDITION IS LISTED AS ?GOOD? ON THE TREE DISPOSITION
 LIST, THEY MUST BE RELOCATED.
 LIVE OAK TREES 363, 386, 387, 390, 391, 392, 393, 395,
 396, AND SABAL PALM 394 ARE REQUIRED TO BE RELOCATED AS
 THEIR CONDITION IS LISTED AS ?GOOD? ON THE TREE
 DISPOSITION LIST.
  
 3. PARTIALLY SATISFIED. PROVIDE THE AMOUNT OF OPEN
 SPACE AND LANDSCAPE AREA ON THE LANDSCAPE PLAN FOR THE
 AFFECTED AREA AND SHOW THE CHANGE FROM APPROVED PLAN.
 THE CALCULATIONS AS SHOWN ARE NOT CLEAR, AND DO NOT ADD
 UP.
 THE CALCULATIONS NEED TO BE SHOWN FOR THE ENTIRE SITE,
 AS ADDITIONAL AREA IS BEING ADDED TO THE PD. THE
 REQUIRED OPEN SPACE FOR CS IS 40%. OPEN SPACE IS ALL
 NON-BUILDING AREA. LANDSCAPE AREA SHOULD BE EQUAL OR
 GREATER THAN 15%.
  
 4. SATISFIED. PROVIDE THE NUMBER OF TREES PROPOSED
 COMPARED TO THE NUMBER OF TREES FROM THE APPROVED
 LANDSCAPE PLAN FOR THE AFFECTED AREA.
  
 5. SATISFIED. PROVIDE A CORRECTED CHART SHOWING CURRENT
 CODE FOR COMPLIANCE WITH FLORIDA FRIENDLY REQUIREMENTS
 PER SECTION 94-442 (G) AND PROVIDE THE REQUIRED 50
 POINTS.
  
 6. SATISFIED. ADD COLUMNS TO THE PLANT LIST FOR NATIVE
 PLANT AND DROUGHT TOLERANCE.
  
 7. SATISFIED. SHOW ALL EXISTING TREES TO REMAIN WITH
 IDENTIFYING TAGS ON THE PLAN AND INCLUDE ON THE PLANT
 LIST.
  
  
 8. SATISFIED. PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 9. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL
 ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C
 UNITS, ETC.
  
 10. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES
 ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE
 PLAN.
  
 11. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445
 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 SHOW THE CALCULATION OF THE PERCENTAGE ON THE LANDSCAPE
 PLAN BASED ON THE PROPOSED PLANT LIST.
 ADDITIONAL COMMENTS 2/19/19:
 12. SHEET L006 DOES NOT REPRESENT ANY MISSING TREES
 FROM THE APPROVED PLANS BEING REPLACED AT SOME OF THE
 TERMINAL ISLANDS AND THE LANDSCAPE BUFFERS ALONG THE
 PROPERTY LINES. ALL TREES AS APPROVED NEED TO BE SHOWN
 AS BEING REPLACED.
  
 13. THE WAX MYRTLE AS SPECIFIED ARE NOT A SUCCESSFUL
 SPECIES WHEN USED IN PARKING LOT ISLANDS. CHANGE TO A
 MORE DEPENDABLE AND SUSTAINABLE SPECIES.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-10-2018 Cont ID  
Sent By rcaranci Date 12-10-2018 Time 12:27 Rev Time 0.00
Received By rcaranci Date 12-10-2018 Time 12:27 Sent To  
Notes
2018-12-10 12:27:37FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: WEST PALM HOSPITAL CSPD Z18110023
 DECEMBER 10, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. CORRECT THE TREE DISPOSITION PLAN AND LIST FOR THE
 FOLLOWING:
 ? ALL TREES BELOW 20 FOOT CANOPY ARE TO BE MITIGATED
 ONE FOR ONE AND THE CANOPY VALUE NEEDS TO BE CORRECTED
 TO THE CATEGORY VALUE. I.E. LIVE OAK CATEGORY 1, IS A
 300 SQ FT CANOPY VALUE. BOTTLEBRUSH CATEGORY 2 IS A 150
 SQ FT CANOPY VALUE. SABAL PALM CATEGORY 3 IS A 100 SQ
 FT CANOPY VALUE. CORRECT VALUE AS SHOWN IS 16,395 SQ
 FT.
 ? TREES REMAINING WITHIN THE CONSTRUCTION LIMITS NEED
 TO BE SHOWN AS REQUIRING ROOT PROTECTION.
  
 2. SECTION 94-448 (D)(3) REQUIRES NATIVE TREES IN GOOD
 CONDITION TO BE PRESERVED ON SITE OR RELOCATED. THERE
 ARE MULTIPLE LIVE OAKS THAT CAN BE RELOCATED ON SITE TO
 AREAS WITHOUT TREES. THERE ARE LARGE TREES WITHIN THE
 LIMITS OF CONSTRUCTION THAT CAN BE PRESERVED BY
 DESIGNING THE PROPOSED SIDEWALK LAYOUT TO AVOID THEM.
  
 3. PROVIDE THE AMOUNT OF OPEN SPACE AND LANDSCAPE AREA
 ON THE LANDSCAPE PLAN FOR THE AFFECTED AREA AND SHOW
 THE CHANGE FROM APPROVED PLAN.
  
 4. PROVIDE THE NUMBER OF TREES PROPOSED COMPARED TO THE
 NUMBER OF TREES FROM THE APPROVED LANDSCAPE PLAN FOR
 THE AFFECTED AREA.
  
 5. PROVIDE A CORRECTED CHART SHOWING CURRENT CODE FOR
 COMPLIANCE WITH FLORIDA FRIENDLY REQUIREMENTS PER
 SECTION 94-442 (G) AND PROVIDE THE REQUIRED 50 POINTS.
  
 6. ADD COLUMNS TO THE PLANT LIST FOR NATIVE PLANT AND
 DROUGHT TOLERANCE.
  
 7. SHOW ALL EXISTING TREES TO REMAIN WITH IDENTIFYING
 TAGS ON THE PLAN AND INCLUDE ON THE PLANT LIST.
  
  
 8. PROVIDE LOCATIONS OF LIGHTING ON THE LANDSCAPE PLAN
 TO AVOID CONFLICTS WITH LANDSCAPING.
  
 9. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE GROUND
 UTILITY VALVES, BACKFLOW PREVENTERS, A/C UNITS, ETC.
  
 10. SHOW LOCATIONS OF WATER AND SEWER LINES ON THE
 LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
 SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO PROTECT
 UTILITY LINES AND LABEL THEM ON THE PLAN.
  
 11. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 12-13-2018 Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 4 Status P Date 06-05-2019 Cont ID  
Sent By tward Date 06-05-2019 Time 17:30 Rev Time 0.00
Received By tward Date 06-05-2019 Time 17:32 Sent To  
Notes
2019-06-05 17:32:15NO COMMENTS ON THE MAY 28, 2019 REVIEW SUBMITTAL.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 3 Status F Date 04-08-2019 Cont ID  
Sent By tward Date 04-08-2019 Time 14:04 Rev Time 0.00
Received By tward Date 04-08-2019 Time 14:09 Sent To  
Notes
2019-04-08 14:09:16THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE APRIL
 3, 2019 SUBMITTAL PACKAGE:
  
 1. [REPEAT COMMENT] THE CITY'S VERTICAL DATUM IS NGVD
 1929. THE CITY HAS ALLOWED THE USED OF NAVD 1988
 PROVIDED THE CONVERSION BETWEEN NAVD 1988 AND NGVD 1929
 IS ADDED TO THE PLANS. LABEL THE VERTICAL DATUM AND THE
 NAVD1988 / NGVD1929 RELATIONSHIP ON EACH SHEET WITH
 ELEVATION DATA.
  
 2. [REPEAT COMMENT] COMPLETE THE GENERAL CONSTRUCTION
 NOTE #21 ON SHEET C001:
 "21 THE CONTRACTOR SHALL ENSURE THAT ANY TREE " ...
 "SHALL CONFORM TO THE CITY OF NAME STANDARD DETAILS.".
  
 3. COMPLETE SURVEY DATA NOTE #3 ON SHEET C001:
 "3. ALL ELEVATIONS ON THE PLANS OR REFERENCED IN THE
 SPECIFICATIONS ARE BASED ON [NAME OF DATUM] DATUM OF
 [YEAR] (X.X.X.X. XX)."
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 02-15-2019 Cont ID  
Sent By tward Date 02-15-2019 Time 10:31 Rev Time 0.00
Received By tward Date 02-15-2019 Time 10:36 Sent To  
Notes
2019-02-15 10:36:38THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 4, 2019 SUBMITTAL PACKAGE:
  
 1. THE CITY'S VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USED OF NAVD 1988 PROVIDED THE CONVERSION
 BETWEEN NAVD 1988 AND NGVD 1929 IS ADDED TO THE PLANS.
 LABEL THE VERTICAL DATUM AND THE NAVD1988 / NGVD1929
 RELATIONSHIP ON EACH SHEET WITH ELEVATION DATA.
  
 2. COMPLETE THE GENERAL CONSTRUCTION NOTE #21 ON SHEET
 C001.
  
 3. TOPOGRAPHIC SURVEY MISSING.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-11-2018 Cont ID  
Sent By tward Date 12-11-2018 Time 08:37 Rev Time 0.00
Received By tward Date 12-11-2018 Time 08:41 Sent To  
Notes
2018-12-11 08:41:49THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. LIST THE VERTICAL DATUM ON THE ENGINEERING PLANS.
 THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED.
  
 2. THE NAVD1988 / NGVD1929 CONVERSION EQUATION IS
 NEEDED ON THE SURVEY.
  
 3. MINIMUM 2 FEET OF FREEBOARD ABOVE THE FLOOD
 ELEVATION IS REQUIRED FOR STRUCTURES WITHIN SPECIAL
 FLOOD HAZARD AREAS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE SFWMD ERP MODIFICATION FOR THE DEVELOPMENT.
  
 3. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 3 Status P Date 04-09-2019 Cont ID  
Sent By vnoel Date 04-09-2019 Time 10:18 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-04-09 10:21:39SURVEY RECEIVED BUT NO RESPONSE TO ENGINEERING COMMENTS
 IN RESPONSE LETTER.

Review Stop SURVEY SURVEYING
Rev No 2 Status F Date 02-08-2019 Cont ID  
Sent By vnoel Date 02-08-2019 Time 10:13 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-02-08 10:14:261, WILL REVIEW WHEN REVISED SURVEY IS PROVIDED.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-12-2018 Cont ID  
Sent By vnoel Date 12-12-2018 Time 06:51 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-12-12 06:51:121. SURVEY INCOMPLETE.
 2. MISSING ITEMS INCLUDE:
 TITLE
 LINE WORK
 KEY MAP
 BOUNDARY ANNOTATION
 SHEET NUMBERS
 MATCH LINES, ETC.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 5 Status P Date 08-28-2019 Cont ID  
Sent By eschneid Date 08-28-2019 Time 17:21 Rev Time 0.00
Received By eschneid Date 08-28-2019 Time 17:21 Sent To  
Notes
2019-08-28 17:21:28PEDESTRIAN CONNECTION PROVIDED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 06-04-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-06-04 14:02:231. (PREVIOUS COMMENT) ON SHEET C301, PROVIDE PEDESTRIAN
 CONNECTION FROM THE SIDEWALK ON THE WEST SIDE OF THE
 INTERNAL ROADWAY TO THE ENTRANCE OF THE SOUTH BUILDING.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 04-10-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-04-10 11:18:311. (PREVIOUS COMMENT) ON SHEET C301, PROVIDE PEDESTRIAN
 CONNECTION FROM THE SIDEWALK ON THE WEST SIDE OF THE
 INTERNAL ROADWAY TO THE ENTRANCE OF THE SOUTH BUILDING.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 02-13-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-02-13 15:14:411. PLEASE PROVIDE COUNTY TPS LETTER.
 2. ON SHEET C301, THE EXISTING PEDESTRIAN CONNECTION,
 WHICH CONNECTS TO THE EXISTING SIDEWALK ALONG THE
 INTERNAL ROADWAY AND RUNS ALONG THE WEST SIDE OF THE
 INTERNAL ROADWAY NEAR THE SOUTH BUILDING, WAS REMOVED
 IN THE PROPOSED SITE PLAN. PLEASE MAINTAIN THE EXISTING
 PEDESTRIAN CONNECTION BY PROVIDING THE CONNECTION ON
 EITHER THE EAST SIDE OR WEST SIDE OF THE ROADWAY.
 PROVIDE MARKED CROSSWALK ALONG THIS PEDESTRIAN
 CONNECTION AS APPROPRIATE.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 12-10-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-12-12 10:19:08Z18110023_JFK NORTH HOSPITAL MAJOR PD AMENDMENT
 (NOVEMBER 13, 2018 SUBMITTAL)
 TRAFFIC STUDY
 1. PLEASE PROVIDE COUNTY TPS LETTER.
 2. IN THE TRAFFIC STUDY, THE SOUTHERN DRIVEWAY DOES NOT
 PERMIT EGRESS VEHICLES TO MAKE LEFT-TURN. PLEASE REVISE
 THE TRIP ASSIGNMENT.
 SITE PLAN
 3. ON SHEET C300, PROVIDE CROSSWALK FROM THE BUILDING
 TO THE OPPOSITE SIDE OF THE INTERNAL ROADWAY. ALSO
 PROVIDE PEDESTRIAN CURB RAMP.
 4. ON SHEET C301, PROVIDE AUTOTURN PATH TO VERIFY IF A
 PASSENGER CAR CAN MAKE RIGHT-TURN INTO THE FIRST
 PARKING AISLE ON THE SOUTH.
 5. ON SHEET C301, PROVIDE PEDESTRIAN CONNECTION BETWEEN
 THE EXISTING PEDESTRIAN CONNECTION NEAR THE MATCH LINE
 WITH SHEET C300 AND THE PROPOSED BUILDING .
 6. PROVIDE BICYCLE PARKING NEAR THE PROPOSED BUILDINGS.
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]

Review Stop Z ZONING
Rev No 5 Status P Date 09-16-2019 Cont ID  
Sent By eschneid Date 09-16-2019 Time 11:26 Rev Time 0.00
Received By eschneid Date 08-28-2019 Time 17:20 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 4 Status F Date 06-19-2019 Cont ID  
Sent By eschneid Date 06-19-2019 Time 10:36 Rev Time 6.00
Received By eschneid Date 06-07-2019 Time 14:44 Sent To  
Notes
2019-06-19 15:06:42PB 1223I - MAY 24, 2019 RESUBMITTAL REVIEW
 JFK NORTH BEHAVIORAL HEALTH EXPANSION
 2201 45TH STREET
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE ITEMS IN COMMENTS #1 AND 2 MUST BE SUBMITTED TO
 THE PLANNING DIVISION BY 5 PM ON FRIDAY, JUNE 21, 2019,
 OR THE CASE WILL NOT BE SCHEDULED FOR THE JULY 16, 2019
 PLANNING BOARD MEETING.
  
 - THE COMMENTS THAT ARE PRECEDED WITH *** ARE ITEMS
 THAT WILL NOT HOLD UP THE CASE PROCEEDING TO PLANNING
 BOARD, HOWEVER, THEY MUST BE SUFFICIENTLY ADDRESSED
 PRIOR TO THE CASE BEING SCHEDULED FOR CITY COMMISSION.
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) THE PLANS WERE NOT PROVIDED IN .PNG FORMAT. THE
 JUSTIFICATION STATEMENT NEEDS TO BE PROVIDED IN WORD
 FORMAT.
  
 2) THE REQUIRED $600 RESUBMITTAL FEE WAS NOT INCLUDED
 WITH THE MAY 24, 2019 RESUBMITTAL.
  
 3) *** REPEAT COMMENT: THE UPDATED PALM BEACH COUNTY
 TRAFFIC PERFORMANCE STANDARDS LETTER BASED ON THE
 SQUARE FOOTAGE PROVIDED IN THE MAY 24, 2019 REVISED
 TRAFFIC IMPACT EVALUATION WAS NOT SUBMITTED.
  
 4) *** REPEAT COMMENT: THE LEGAL DESCRIPTION PROVIDED
 WITH THE SURVEY OF THE ENTIRE CAMPUS, CREATED BY DAVID
 LINDLEY (UPDATED ON JUNE 19, 2019 BASED ON CITY
 SURVEYOR REVIEW OF THE PREVIOUSLY PROVIDED INCORRECT
 LEGAL DESCRIPTION), DOES NOT MATCH THE LEGAL
 DESCRIPTION IN THE UNITY OF TITLE. THE LEGAL
 DESCRIPTION PROVIDED FOR THE UNITY OF TITLE (WHICH
 COVERS THE ENTIRE AREA FOR THE EXPANDED JFK NORTH
 CAMPUS CSPD) LISTS THE ENTIRE PARCEL AS HAVING 26.82
 ACRES, YET THE NEW SURVEY LISTS THE ENTIRE PARCEL AS
 HAVING 27.03 ACRES. STAFF WILL BE USING THE INFORMATION
 FROM THE JUNE 19, 2019 SURVEY AS THE ACREAGE FOR THE
 ENTIRE CSPD. THE DATA TABLES ON THE SITE AND LANDSCAPE
 PLANS NEED TO BASE THE DEVELOPMENT CALCULATIONS ON THE
 ACCURATE PARCEL ACREAGE OF 27.03 ACRES.
  
 5) *** NEW COMMENT: DUE TO THE EXPRESSED DESIRE TO
 INCLUDE THE REGULATIONS FOR THE FUTURE SUBDIVISION OF
 THE CSPD, IN ACCORDANCE WITH THE ZONING AND LAND
 DEVELOPMENT REGULATIONS, THE SETBACKS FOR THE CSPD ARE:
  
 25 FEET FOR THE FRONT - 45TH STREET
 25 FEET FOR THE CORNER SIDE - CONGRESS AVENUE
 15 FEET FOR THE SIDES - WEST PROPERTY LINE AND ALONG
 THE 2151 45TH STREET PARCEL
 15 FEET FOR THE REAR - NORTH PROPERTY LINE
  
 THESE SETBACK LINES NEED TO BE CORRECTED ON THE OVERALL
 SITE PLAN.
  
 6) REVISED COMMENT: THE MAY 24, 2019 JUSTIFICATION
 STATEMENT LISTS DEVELOPMENT REGULATIONS BASED ON
 WAIVERS TO PROVISIONS OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS TO PERMIT THE FUTURE
 SUBDIVISION OF THE PROPERTY WITHIN THE CSPD. NOTE: THE
 CITY WILL NOT RELEASE THE UNITY OF TITLE UNTIL THE
 APPLICATION FOR THE MINOR SUBDIVISION PLAT HAS BEEN
 SUBMITTED, REVIEWED, APPROVED AND THE PLAT IS READY FOR
 RECORDATION. STAFF HAS REVIEWED THE PROPOSED WAIVERS
 AND HAS THE FOLLOWING COMMENTS:
  
 A. INTERNAL ROW WITH MORE THAN 10 PARKING SPACES -
 EXISTING ROWS EXCEEDING 10 SPACES ARE SHOWN ON THE
 OVERALL SITE PLAN AND MAY REMAIN (EXISTING CONDITION
 WAIVER); HOWEVER, NEW OR RECONFIGURED PARKING AREAS
 MUST COMPLY WITH THE ZLDR IN PLACE AT THE TIME OF
 PERMITTING FOR THE PARKING AREA.
  
 B. LANDSCAPE BUFFER WIDTH - NO INTERNAL LANDSCAPE
 BUFFERS ARE REQUIRED FOR ANY INDIVIDUAL PARCELS THAT
 MIGHT BE CREATED VIA SUBDIVISION, EXCEPT WHERE THE
 PROPERTY LINE OF SUCH SUBDIVIDED LOT IS CONCURRENT WITH
 A CSPD PERIMETER LOT LINE. IN THAT CASE A MINIMUM FIVE
 (5) FOOT WIDE LANDSCAPE BUFFER IS REQUIRED.
  
 C. LANDSCAPE BUFFER MATERIAL - LANDSCAPE MATERIAL IS
 REQUIRED IN ANY REQUIRED LANDSCAPE BUFFER. ALL MISSING
 MATERIAL IN THE PERIMETER BUFFERS IS TO BE INSTALLED AS
 PART OF THE CSPD EXPANSION.
  
 D. FOUNDATION LANDSCAPE - STAFF WILL NOT SUPPORT ANY
 FOUNDATION PLANTING WAIVER.
  
 E. SITE IMPROVEMENTS - NEW PARCEL LINES MAY NOT CREATE
 SETBACK CONFLICTS WHERE THEY DO NOT CURRENTLY EXIST.
 NOTE: STAFF WILL SUPPORT A 5 FOOT SETBACK FOR NEW
 INTERIOR PARCEL LINES, PROVIDED THAT THE ALL FLORIDA
 BUILDING CODE REQUIREMENTS ARE MET.
  
 F. MONUMENT SIGNS - SAME AS OVERALL SITE, MAY NOT BE
 REBUILT IN THE EASEMENT.
  
 G. PARKING - CROSS PARKING IS PERMITTED WITHIN THE JFK
 NORTH COMMUNITY SERVICE PLANNED DEVELOPMENT. AN
 INDIVIDUAL PARCEL IS NOT REQUIRED TO PROVIDE ITS ENTIRE
 PARKING REQUIREMENT ON-SITE; HOWEVER, THE ENTIRE JFK
 NORTH CSPD IS REQUIRED TO MEET MINIMUM PARKING
 REQUIREMENTS. CROSS PARKING AND ACCESS AGREEMENTS MUST
 BE RECORDED IN THE PUBLIC RECORD.
  
 H. FAR - STAFF DOES NOT OBJECT TO ANY SPECIFIC PARCEL
 EXCEEDING 1.0 FAR; HOWEVER, NO INDIVIDUAL PARCEL SHALL
 NOT EXCEED 1.5 FAR.
  
 I. ALL NEW PARCELS WILL NEED TO FRONT ON A DEDICATED
 RIGHT-OF-WAY.
  
 7) *** NEW COMMENT: IN ORDER TO MITIGATE THE IMPACTS OF
 NOT PROVIDING INTERIOR PARCEL LANDSCAPE BUFFERS THE
 EXISTING PERIMETER LANDSCAPE BUFFERS MUST BE ENHANCED.
 HEDGES, CONFORMING TO THE ZLDR, MUST BE INSTALLED WHERE
 MISSING. TREES, CONFORMING TO THE ZLDR MUST BE
 INSTALLED UNLESS THE FPL EASEMENT PROHIBITS THE
 PLACEMENT OF THE TREES.
  
 8) *** NEW COMMENT: THE LANDSCAPE PLANS NEED TO BE
 REVISED TO SHOW THAT ALL THE EXISTING TERMINAL AND
 INTERIOR PARKING ISLANDS CONTAIN TREES IN ACCORDANCE
 WITH THE ZLDR AND EVIDENCE (STUMPS) THAT TREES HAVE
 BEEN REMOVED.
  
 9) *** NEW COMMENT: PARKING TABLE: THE LISTED NUMBER OF
 REQUIRED PARKING SPACES IS MORE THAN ARE REQUIRED. IT
 APPEARS THAT THE 2% ADA SPACES WERE CALCULATED IN
 ADDITION TO THE TOTAL NUMBER OF REQUIRED PARKING
 SPACES. PLEASE NOTE THAT THE CITY REQUIRES THAT THE
 NUMBER OF REQUIRED ADA SPACES (IN THIS CASE 2% OF THE
 TOTAL) TO BE PROVIDED AS A SUBSET OF THE TOTAL NUMBER
 OF REQUIRED SPACES, NOT IN ADDITION TO THE NUMBER OF
 REQUIRED SPACES. SO FOR JFK NORTH, 676 PARKING SPACES
 ARE REQUIRED (BASED ON BEDS, DOCTORS AND OFFICE SQUARE
 FOOTAGE). OF THE 676 REQUIRED PARKING SPACES, 14 ARE
 REQUIRED TO BE ADA PARKING SPACES. THE PARKING
 REQUIREMENTS PORTION OF THE TABLE NEEDS TO BE UPDATED
 ACCORDINGLY. NOTE: THE TABLE SHOWS THAT THE SITE HAS
 EXCESS PARKING PROVIDED.
  
 10) *** BICYCLE PARKING
  
 A. REVISED COMMENT: BASED ON THE 676 REQUIRED PARKING
 SPACES, ONLY 34 BICYCLE PARKING SPACES ARE REQUIRED.
 UPDATE THE TABLE ACCORDINGLY.
  
 B. REVISED COMMENT: THE TABLE LISTS 36 BICYCLE PARKING
 SPACES AS PROVIDED, YET THE PLANS LIST 40 BICYCLE
 PARKING SPACES.
  
 C. REPEAT COMMENT: ALL NEW BICYCLE RACKS MUST INCLUDE
 THE DIMENSIONS ON THE PLANS (SHEETS C002 AND C003). NO
 DIMENSIONS WERE INCLUDED FOR THE NEW BICYCLE PARKING
 PAD AT MEDICAL OFFICE BUILDING 1.
  
 D. NEW COMMENT: THE NEW BICYCLE PARKING PAD NEAR THE ER
 ENTRANCE SHOWS FIVE RACKS (10 PARKING SPACES) BUT LISTS
 EIGHT PARKING SPACES. NOTE: SEE COMMENT #10A - MANY OF
 THESE ARE NOT REQUIRED TO MEET CODE MINIMUM.
  
 11) *** REPEAT COMMENT (BASED ON LANDSCAPE PLANNER SITE
 VISIT): THE ADDITION TO THE NORTHERNMOST BEHAVIORAL
 HEALTH BUILDING HAS RESULTED IN THE RECONSTRUCTION OF
 THE CURRENT ACCESS DRIVE, INCLUDING A NEW DRAINAGE
 LINE, NORTH OF THE BUILDING. THE PLANS AS PRESENTED
 CAUSE THE REMOVAL OF MATURE TREES 311, 314 AND 315.
 THESE TREES MUST BE PROTECTED.
  
 A. SHIFT THE DRAINAGE LINE TO THE SOUTH AND DESIGN SO
 THAT THE CURB DRAIN AVOIDS TREE NUMBER 311.
 B. THE ROADWAY, CURB AND SIDEWALK SHOULD EITHER BE 1)
 SHIFTED SOUTH, 2) NARROW THE PAVEMENT WIDTH FROM 25
 FEET TO 20 FEET, 3) NARROW THE SIDEWALK TO SIX FEET, OR
 4) A COMBINATION OF THE ABOVE IN ORDER TO PERMIT TREES
 311, 314 AND 315 TO REMAIN IN PLACE.
  
 12) *** REPEAT COMMENT (FROM LANDSCAPE REVIEWER
 COMMENT): THE TWO TERMINAL ISLANDS IN THE NEW PARKING
 AREA SOUTH OF THE SOUTHERN BEHAVIORAL HEALTH BUILDING
 EXPANSION THAT WERE BUILT OVER THE EXISTING SEWER LINE
 MUST BE WIDENED TO ACCOMMODATE THE REQUIRED TERMINAL
 ISLAND TREES. THE SITE CONTAINS EXCESS PARKING SPACES,
 SO THE ISLANDS CAN BE WIDENED BY REMOVING THE ADJACENT
 PARKING SPACES. NOTE: THE PROVIDED LINE OF THE PARKING
 TABLE MUST BE UPDATED ACCORDINGLY.
  
 13) *** REPEAT COMMENT (FROM CITY'S TRANSPORTATION
 ENGINEERING DIVISION COMMENT): THE SIDEWALK CONNECTION
 TO THE WEST OF THE SOUTHERN BEHAVIORAL HEALTH BUILDING
 NEEDS TO FOLLOW THE OPTION #3 MODEL PROPOSED BY THE
 APPLICANT. HOWEVER, IT MUST NOT ONLY MEANDER AROUND
 EXISTING TREE 378, BUT ALSO AVOID EXISTING TREE 364 AS
 IT TIES INTO THE SIDEWALK ALONG THE WEST SIDE OF THE
 BUILDING.
  
 14) *** NEW COMMENT: DUE TO THE ADDITIONAL DETAIL
 PROVIDED BY THESE PLANS, STAFF HAS NOTED THAT THE
 REVISED OXYGEN TANK ENCLOSE (EXPANDED AS PART OF THE ER
 EXPANSION PROJECT) ENCROACHES INTO THE DRIVE AISLE
 AROUND THE BUILDING AND REDUCES IT TO SUBSTANDARD
 TWO-WAY DIMENSION. IT NEEDS TO HAVE AT LEAST 18 FEET OF
 TRAVEL LANE (20 FEET IS PREFERRED).
  
 15) WAIVERS REQUIRED BASED ON EXISTING CONDITIONS
 IDENTIFIED BY STAFF THAT STAFF CAN SUPPORT:
  
 A. INSTANCES OF PARKING ROWS WITH MORE THAN 10 SPACES.
 - FIVE PARKING ROWS CONTAIN MORE THAN 10 PARKING
 SPACES. ANY RECONSTRUCTION OF THESE PARKING AREAS WILL
 NEED TO MEET ZLDR REQUIREMENTS.
 B. AREAS WHERE THE MINIMUM FIVE FOOT LANDSCAPE BUFFER
 AND MATERIAL IS NOT PROVIDED.
 - TWO LOCATIONS AT THE SOUTHWEST CORNER OF THE SITE
 (DRIVEWAY AND PARKING SPACE)
 - NORTH OF THE NORTHERN CONGRESS AVENUE ENTRANCE,
 BETWEEN THE TWO PARKING BAYS AND CONGRESS AVENUE.
 BUFFER WIDTH IS AS SHOWN ON SITE AND LANDSCAPE PLANS.
 - ALONG 2145 45TH STREET
 - ALONG A PORTION OF THE WEST PROPERTY LINE, WEST OF
 THE MAIN HOSPITAL BUILDING
  
 THESE AREAS ARE SHOWN ON THE SITE AND LANDSCAPE PLANS.
 NOTE: IF ANY OF THE AREAS REFERENCED IN COMMENTS #15A
 AND #15B ARE RECONSTRUCTED, THEY MUST COMPLY WITH THE
 ZLDR IN PLACE AT THE TIME OF PERMITTING FOR THE
 RECONSTRUCTION.
  
 16) IF REBUILT, ANY SIGNS CURRENTLY LOCATED WITHIN AN
 FPL EASEMENT MUST BE MOVE OUT OF THE EASEMENT.
  

Review Stop Z ZONING
Rev No 3 Status F Date 04-30-2019 Cont ID  
Sent By eschneid Date 04-30-2019 Time 11:30 Rev Time 6.00
Received By eschneid Date 04-24-2019 Time 13:34 Sent To  
Notes
2019-04-30 11:35:19PB 1223I - FIRST RESUBMITTAL REVIEW
 JFK NORTH BEHAVIORAL HEALTH EXPANSION
 2201 45TH STREET
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 MAY 24, 2019 TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 JULY 16, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THESE COMMENTS (BY JUNE 30, 2019), THE CASE
 SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT PREVIOUSLY-ISSUED COMMENTS WERE NOT
 SUFFICIENTLY ADDRESSED, SO THE APPLICATION IS ASSESSED
 A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE ORIGINAL
 APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) REVISED COMMENT: THANK YOU FOR PROVIDING THE PALM
 BEACH COUNTY TRAFFIC APPROVAL LETTER; HOWEVER, THE
 FOLLOWING ITEMS NEED TO BE EXPLAINED/CORRECTED:
  
 A. THE LETTER (AND THE TRAFFIC STUDY THAT WAS
 SUBMITTED) INCLUDES THE SQUARE FOOTAGE/VEHICLE TRIPS
 FOR PCN 74434306000001070, WHICH IS NOT PART OF THE JFK
 NORTH CAMPUS CSPD. PLEASE EXPLAIN WHY THIS PARCEL WAS
 INCLUDED IN THE TRAFFIC STATEMENT AND THUS THE TRAFFIC
 APPROVAL LETTER FOR THE JFK NORTH CAMPUS CSPD. THIS
 ADDS TWO MEDICAL OFFICE BUILDINGS TOTALING 36,750
 SQUARE FEET (PAPA) TO THE TRAFFIC IMPACT OF THE JFK
 NORTH CSPD.
 B. THE TRAFFIC STUDY AND THE TRAFFIC LETTER LIST THE
 EXISTING HOSPITAL AS HAVING 124,817 SQUARE FEET, WHICH
 IS SHOWN BY PAPA AS THE SQUARE FOOTAGE OF BUILDING 1 OF
 THE JFK NORTH CAMPUS CSPD. PAPA SHOWS MULTIPLE HOSPITAL
 BUILDINGS TOTALING 194,630 SQUARE FEET. THE BUILDING
 SQUARE FOOTAGE LISTED ON SHEET C002 TOTALS 206,703
 SQUARE FEET OF EXISTING HOSPITAL. YOU NEED TO RECTIFY
 THE EXISTING HOSPITAL SQUARE FOOTAGE ON ALL PLANS AND
 DOCUMENTS. THEN THE TRAFFIC STATEMENT AND THE
 CORRESPONDING TRAFFIC LETTER NEED TO BE UPDATED TO SHOW
 ACCURATE CONDITIONS. CURRENTLY, THE EXISTING HOSPITAL
 SQUARE FOOTAGE TRAFFIC IMPACT IS SIGNIFICANTLY LESS
 THAN ACTUAL CONDITIONS ACCORDING TO THE TRAFFIC
 STATEMENT.
  
 2) NEW COMMENT: PLEASE PROVIDE THE LEGAL DESCRIPTION
 FOR THE ENTIRE NEW JFK NORTH CAMPUS CSPD BOUNDARY IN
 WORD. ADDITIONALLY, PLEASE EXPLAIN WHY THE LEGAL
 DESCRIPTION PROVIDED FOR THE UNITY OF TITLE (WHICH
 COVERS THE ENTIRE AREA FOR THE EXPANDED JFK NORTH
 CAMPUS CSPD) LISTS THE ENTIRE PARCEL AS HAVING 26.82
 ACRES, YET THE NEW SURVEY LISTS THE ENTIRE PARCEL AS
 HAVING ONLY 25.39 ACRES. THE ACREAGE AND LEGAL
 DESCRIPTIONS ON THE UNITY OF TITLE AND THE SURVEY NEED
 TO DESCRIBE THE SAME PROPERTY.
  
 3) NEW COMMENT: ALL OF THE SITE FEATURES NEED TO HAVE A
 UNIFORMLY DARK LINE WIDTH SO THAT THEY ARE LEGIBLE ON
 THE PLANS.
  
 4) REPEAT COMMENT: PROVIDE THE SETBACK DIMENSION TO THE
 EXISTING FREE STANDING MONUMENT SIGNS. PLEASE NOTE THAT
 THE SURVEY SHOWS THE TWO SIGNS ALONG 45TH STREET IN THE
 FPL EASEMENT WHICH IS NOT WHERE THEY WERE APPROVED ON
 THE BUILDING PERMIT. THE ACTUAL SIGN SETBACKS NEED TO
 BE VERIFIED.
  
 5) REVISED COMMENT: THE MARCH 22, 2019 JUSTIFICATION
 STATEMENT DOES NOT ADDRESS THE FUTURE SUBDIVISION OF
 THE PROPERTY. AT SUCH TIME AS JFK NORTH APPLIES TO
 SUBDIVIDE THE PROPERTY, A MAJOR AMENDMENT TO ADDRESS
 ALL OF THE DEVELOPMENT REGULATIONS AND ANY ASSOCIATED
 WAIVERS WILL BE REQUIRED. PLEASE NOTE THAT MITIGATION
 FOR NEWLY CREATED WAIVERS MAY BE REQUIRED WITH THE
 FUTURE MAJOR AMENDMENT.
  
 6) REVISED COMMENT: SINCE THERE IS NO SUBDIVISION, NO
 CLARIFICATION ON PARKING USE IS REQUIRED WITH THIS
 APPLICATION.
  
 7) REVISED COMMENT: THE DATA TABLES ON THE SITE AND
 LANDSCAPE PLANS NEED TO BASE THE DEVELOPMENT
 CALCULATIONS ON THE ACCURATE PARCEL ACREAGE. THE SITE
 AND LANDSCAPE PLANS DO NOT LIST THE IDENTICAL AMOUNT OF
 ACREAGE, NOR DOES EITHER ONE OF THESE MATCH THE ACREAGE
 LISTED ON EITHER OF THE LEGAL DESCRIPTIONS REFERENCED
 IN COMMENT #2.
  
 8) REPEAT COMMENT: THE SITE DATA TABLE ON SHEETS C002
 AND C003 NEEDS TO LIST THE SQUARE FOOTAGE FOR EACH
 BUILDING AND ITS USE. IF A BUILDING CONTAINS BEDS, THE
 NUMBER OF BEDS WITHIN THE BUILDING NEEDS TO BE LISTED
 AS WELL. THE TWO MEDICAL OFFICE BUILDINGS WILL NEED TO
 PROVIDE THE TOTAL SQUARE FOOTAGE OF THE BUILDINGS.
 ----- THE DATA TABLES ON THE REVISED PLANS DO NOT
 ACCURATELY REFLECT THE SQUARE FOOTAGE OF THE TWO STORY
 MEDICAL OFFICE BUILDINGS, BUT RATHER IS ONLY PROVIDED
 AS IF THEY ARE ONE STORY BUILDINGS. SEE COMMENT #1 FOR
 ADDITIONAL DISCREPANCIES WHICH NEED TO BE RECTIFIED.
 THE NUMBER OF BEDS IN EACH BUILDING WAS NOT PROVIDED SO
 THAT STAFF CAN VERIFY THE REQUIRED PARKING COUNTS.
  
 9) PARKING TABLE:
  
 A. REVISED COMMENT: STAFF HAS COUNTED 793 REGULAR
 PARKING SPACES FOR THE ENTIRE SITE, NOT 792 AS LISTED.
 PLEASE VERIFY THE COUNTS.
  
 B. NEW COMMENT: THE PARKING REQUIREMENT FOR THE TWO
 MEDICAL OFFICE BUILDINGS WAS NOT PROVIDED ON THE
 PARKING TABLE. MEDICAL OFFICE REQUIRES 1 PARKING SPACE
 PER 200 SQUARE FEET. PROVIDE A LINE ITEM AND UPDATE THE
 TOTAL REQUIRED. STAFF'S INITIAL CALCULATION SHOWS THAT
 YOU REQUIRE 846 PARKING SPACES (EXCLUDES THE AMBULANCE
 SPACES), WHILE THE PARKING TABLE ONLY SHOWS THAT THE
 PROPOSED SITE PLAN PROVIDES 826 PARKING SPACES. AN
 ADDITIONAL 20 PARKING SPACES ARE REQUIRED.
  
 10) SHEET C300 - REVISED COMMENT: I SPOKE WITH THE
 SAMANTHA HILL IN THE BUILDING DIVISION REGARDING ADA
 PARKING SPACES IN THE PARKING FIELD TO THE NORTH OF
 THIS PROPOSED BUILDING. YOU NEED TO SHOW THE LOCATIONS
 OF THE ENTRANCES TO THE BUILDING FOR BOTH PUBLIC AND
 EMPLOYEES AND THE ROUTE OF TRAVEL TO THE ENTRANCES. THE
 CLOSEST PARKING SPACES ALONG THE ROUTE NEED TO BE THE
 ADA PARKING SPACES. ---- THE REVISED SITE PLAN SHOWS A
 DOOR ON THE NORTH SIDE OF THE EXISTING BUILDING AS
 "RESTRICTED ENTRY". WHO USES THIS ENTRANCE? IF
 EMPLOYEES USE THE ENTRANCE, IT STILL REQUIRES ADA
 PARKING SPACES IN THE NEARBY PARKING FIELD AND AN
 ACCESSIBLE ROUTE FROM THE PARKING AREA TO THE BUILDING.
  
 11) SHEET C301
  
 A. REVISE COMMENT: THE NORTHERN OF THE TWO NEW WESTERN
 PARKING FIELDS STILL HAS A 22 FOOT WIDE AISLE WIDTH
 DIMENSION (SHOWN CLEARLY ON SHEET C003) AND ONE OF THE
 AISLES SHOWS 24 FEET ON SHEET C301 YET ONLY 22 FEET ON
 SHEET C003. ALL PLANS NEED TO SHOW SAME, CORRECT 24
 FOOT CONDITION.
  
 B. REVISED COMMENT: I SPOKE WITH THE SAMANTHA HILL IN
 THE BUILDING DIVISION REGARDING ADA PARKING SPACES FOR
 THE REVISED PARKING FIELD. YOU NEED TO SHOW THE
 LOCATIONS OF THE ENTRANCES TO THE BUILDING FOR BOTH
 PUBLIC AND EMPLOYEES AND THE ROUTE OF TRAVEL TO THE
 ENTRANCES. THE CLOSEST PARKING SPACES ALONG THE ROUTE
 NEED TO BE THE ADA PARKING SPACES. THIS MIRRORS HOW TO
 VERIFY THE SIMILAR BUILDING DIVISION COMMENT FROM PPRC.
 ------- NO ENTRANCES ARE SHOWN NEAR THESES PARKING
 SPACES. WHO DO THEY SERVE? YOU HAVE FAILED TO LABEL
 WHAT APPEAR TO BE DOORS IN THIS AREA. THEY NEED TO BE
 LABELED. IF THERE ARE MULTIPLE ACCESSIBLE ENTRANCES,
 THEN THE SPACES NEED TO BE DISTRIBUTED TO SERVICE THEM.
 CONVERSELY, DEPENDING ON WHAT THESE DOORS ARE USED OR,
 YOU MAY NOT NEED THE ADA PARKING SPACES AT THIS
 LOCATION.
  
 12) BICYCLE PARKING REVISED COMMENTS
  
 A. THE DATA TABLE FOR THE NUMBER OF REQUIRED BICYCLE
 PARKING SPACES NEEDS TO BE UPDATED TO REFLECT THE
 ACTUAL NUMBER OF REQUIRED PARKING SPACES FROM COMMENT
 #9B. PLEASE NOTE THAT THE CITY ONLY REQUIRES ONE
 PARKING SPACE PER 20 REQUIRED PARKING SPACES, SO YOU
 WILL REQUIRE LESS BICYCLE PARKING SPACES THAN THE 55
 LISTED.
  
 B. EVERY PRINCIPAL ENTRANCE MUST HAVE BICYCLE PARKING
 TO COMPLY WITH THE CODE. GROUPING THE MAJORITY OF THE
 BICYCLE PARKING SPACES AS SHOWN ON SHEET C301 IS NOT
 ACCEPTABLE AS NO BUILDING ENTRANCES WERE LISTED AS
 BEING AT THIS LOCATION.
  
 C. ALL NEW AND ENLARGED BICYCLE RACKS MUST INCLUDE THE
 DIMENSIONS ON THE PLANS (SHEETS C002 AND C003).
  
 D. MEDICAL OFFICE BUILDING 1 REQUIRES BICYCLE PARKING
 AT THE ENTRANCE.
  
 E. MEDICAL OFFICE BUILDING 2 HAS A WAVE STYLE BICYCLE
 RACK THAT IS NOT CALLED OUT ON THE PLANS. PROVIDE THE
 DIMENSIONS OF THE RACK AND HOW IT SITS ON THE PAD SO
 THAT STAFF CAN DETERMINE HOW MANY BICYCLES IT CAN PARK.
 THIS WILL THEN BE REFLECTED ON THE NUMBER OF SPACES
 PROVIDED TABLE.
  
 13) REPEAT COMMENT: PROVIDE THE UTILITY RELEASE
 LETTERS. THERE ARE TREES AND MODIFIED PARKING BEING
 PROPOSED FOR THE FPL EASEMENT ALONG THE EAST PROPERTY
 LINE. THIS NEEDS TO BE ADDRESSED IN THE RELEASE LETTER.
  
 14) NEW COMMENT: THE LANDSCAPE PLANS SHOW A LINE
 PATTERN THAT IS DESIGNATED AS THE "PROPERTY LINE"? AND
 A SEPARATE LINE PATTERN THAT IS DESIGNATED THE "LIMITS
 OF THE WEST PALM HOSPITAL CSPD". THESE TWO LINES MUST
 BE THE SAME.
  
 15) NEW COMMENT: THERE ARE AREAS ALONG THE CSPD
 BOUNDARY THAT DO NOT CONTAIN THE MINIMUM REQUIRED FIVE
 FOOT WIDE LANDSCAPE BUFFER. PROVIDE A FIVE FOOT OFFSET
 LINE TO SHOW THE REQUIRED BUFFER LOCATION ON THE
 LANDSCAPE PLAN. WHERE THE BUFFER IS NOT MET, PROVIDE
 THE ACTUAL DIMENSION OF THE BUFFER. STAFF NEEDS THESE
 DIMENSIONS TO ADDRESS THE EXISTING NON-CONFORMITIES IN
 THE DEVELOPMENT REGULATIONS.
  
 16) NEW COMMENT: THE LANDSCAPE PLAN FAILS TO CLEARLY
 SHOW THE 12 FOOT WIDE FPL EASEMENT ON THE NORTH, SOUTH
 AND WEST PROPERTY LINES.
  
 17) NEW COMMENT: SHEET C003 SHOWS PARKING STALLS HAVING
 A 17 FOOT DEPTH WITH A LANDSCAPE DIVIDER MEDIAN IN
 FRONT OF THEM. SOME OF THESE HAVE A 25 FOOT AND SOME
 HAVE A 24 FOOT DRIVE AISLE BEHIND THEM (SOME SHARE A 25
 FOOT DRIVE AISLE). THE ZONING AND LAND DEVELOPMENT
 REGULATIONS PERMIT AN OVERHANG INTO THE DIVIDER MEDIAN;
 HOWEVER, THE TOTAL SPACE DEPTH PLUS A TWO FOOT OVERHANG
 MUST TOTAL 18 FEET. FIELD VERIFY THE DIMENSIONS OF THE
 SPACES, INCLUDING THE WHEEL STOP LOCATION AND PROVIDE A
 DETAIL OF EACH OF THE ROWS SHOWING 17 FOOT DEEP PARKING
 SPACES. STAFF NEEDS THESE DIMENSIONS TO ADDRESS ANY
 EXISTING NON-CONFORMITIES IN THE DEVELOPMENT
 REGULATIONS.
  
 18) NO LANDSCAPE SHEET WAS PROVIDED FOR THE NORTHWEST
 QUADRANT OF THE SITE. THIS NEEDS TO BE PROVIDED AND
 CORRECTLY REFLECTED ON ALL THE LANDSCAPE DATA TABLES.
  
 19) WAIVERS REQUIRED BASED ON EXISTING CONDITIONS
 IDENTIFIED BY STAFF:
  
 A. INSTANCES OF PARKING ROWS WITH MORE THAN 10 SPACES.
 B. AREAS WHERE THE MINIMUM FIVE FOOT LANDSCAPE BUFFER
 IS NOT PROVIDED.
 C. THE REQUIRED LANDSCAPE BUFFER MATERIAL IS NOT
 PROVIDED ALONG THE NORTH, SOUTH AND WEST PROPERTY LINES
 WHERE THE FPL EASEMENT IS LOCATED.
 D. THE REQUIRED LANDSCAPE BUFFER MATERIAL OR WIDTH
 PROVIDED ALONG PORTIONS OF THE EAST PROPERTY LINE.
  

Review Stop Z ZONING
Rev No 2 Status F Date 03-01-2019 Cont ID  
Sent By eschneid Date 03-01-2019 Time 15:16 Rev Time 3.00
Received By eschneid Date   Time   Sent To  
Notes
2019-03-01 15:17:12PB 1223I - FIRST RESUBMITTAL REVIEW
 JFK NORTH BEHAVIORAL HEALTH EXPANSION
 2201 45TH STREET
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 MARCH 29, 2019 TO BE ELIGIBLE TO BE SCHEDULED FOR THE
 MAY 21, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THESE COMMENTS (BY MAY 1, 2019), THE CASE
 SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT PREVIOUSLY-ISSUED COMMENTS WERE NOT
 SUFFICIENTLY ADDRESSED, SO THE APPLICANTION IS ASSESSED
 A RESUBMITTAL FEE. SUCH FEE IS 20% OF THE ORIGINAL
 APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) REPEAT COMMENT: PROVIDE THE PALM BEACH COUNTY
 TRAFFIC APPROVAL LETTER.
  
 2) REPEAT COMMENT: THE SURVEY PROVIDED WITH THE
 APPLICATION DOES NOT REFLECT THE BOUNDARY OF THE WEST
 PALM BEACH HOSPITAL COMMUNITY SERVICE PLANNED
 DEVELOPMENT AS DESCRIBED IN ORDINANCE NO. 4503-14.
  
 3) REVISED COMMENT: SHEET C002
  
 A. THE OVERALL SITE PLAN THAT WAS PROVIDED FAILS TO
 PROVIDE ANY DIMENSIONAL INFORMATION, SUCH AS SETBACKS,
 LANDSCAPE AREAS, BUFFER WIDTHS, WALK WAY AND DRIVE
 AISLE WIDTHS, PARKING STALL WIDTH AND DEPTH, AND
 BUILDING DIMENSIONS (IF THE PLANS NEED TO BE ON
 MULTIPLE SHEETS FOR THE INFORMATION TO BE LEGIBLE, THIS
 MUST BE DONE). ADDITIONALLY, THE LOCATIONS OF
 FREESTANDING SIGNS, INTERNAL DIRECTIONAL SIGNS,
 MECHANICAL EQUIPMENT, FENCES/WALLS, GAZEBOS AND OTHER
 SITE FEATURES NEED TO BE SHOWN AND LABELED.
  
 B. THE APPLICATION IS BEING REVISED TO EXPAND THE CSPD
 BOUNDARY, BASED ON THE STATED DESIRE TO SELL PORTIONS
 OF THE PROPERTY. THE JUSTIFICATION STATEMENT IS
 REQUESTING WAIVERS TO ALLOW THE REMOVAL OF THE UNITY OF
 TITLE AND THEN THE FUTURE SALE OF PROPERTY WITHOUT THE
 NEED FOR A FUTURE MAJOR PLANNED DEVELOPMENT AMENDMENT.
 IN ORDER TO INCORPORATE THE WAIVERS IN THE CURRENT
 DEVELOPMENT REGULATIONS, YOU WILL NEED TO PROVIDE A
 TABLE SHOWING ALL OF THE ZONING INFORMATION ON THE
 PLANS SO THAT STAFF CAN DETERMINE WHAT WAIVERS ARE
 REQUIRED. THIS INCLUDES WHERE THE PROPOSED PROPERTY
 LINES WILL BE (A SUBDIVISION MAY BE REQUIRED), SETBACKS
 TO NEW INTERNAL PROPERTY LINES, FUTURE PARCEL SQUARE
 FOOTAGE, FAR, LANDSCAPE COVERAGE, PERVIOUS SURFACE,
 ETC.
  
 C. YOU WILL NEED TO CLARIFY HOW PARKING WILL FUNCTION
 AMONG THE PROPOSED PARCELS - EX. STAND ALONE OR SHARED.
  
 D. THE SETBACK TABLE IS FOR THE ENTIRE CSPD, NOT THE
 PROPOSED BUILDINGS.
  
 4) REQUIRES SURVEY TO VERIFY: THE SITE AND LANDSCAPE
 PLANS NEED TO SHOW THE ACCURATE CSPD BOUNDARIES AND
 THIS NEEDS TO BE REFLECTED ON THE SITE DATA TABLES FOR
 BOTH THE SITE AND LANDSCAPE PLANS.
  
 5) REPEAT COMMENT: EACH BUILDING ON SHEET C002 NEEDS TO
 BE LABELED. THE SITE DATA TABLE ON SHEET C002 NEEDS TO
 LIST THE SQUARE FOOTAGE FOR EACH BUILDING AND ITS USE.
 IF A BUILDING CONTAINS BEDS, THE NUMBER OF BEDS WITHIN
 THE BUILDING NEEDS TO BE LISTED AS WELL. THE TWO
 MEDICAL OFFICE BUILDINGS WILL NEED TO PROVIDE THE TOTAL
 SQUARE FOOTAGE OF THE BUILDINGS.
  
 6) PARKING TABLE:
  
 A. REPEAT COMMENT: THE PARKING COUNT IS INCORRECT FOR
 THE ENTIRE SITE (PROPOSED CSPD). STAFF HAS COUNTED 783
 REGULAR AND 34 ADA PARKING SPACES FOR THE ENTIRE SITE.
 PLEASE NOTE THAT THIS NUMBER WILL BE REDUCED WHEN THE
 PARKING ROW WITH 12 PARKING SPACES IS CORRECTED.
  
 B. REPEAT COMMENT: THE PARKING TABLE NEEDS TO LIST ONLY
 THE PARKING COUNTS AFTER THE PROJECT IS COMPLETED. THE
 EXISTING CONDITIONS NEED TO BE STATED IN THE
 JUSTIFICATION STATEMENT. ---- DO NOT INCLUDE THE
 EXISTING PARKING COUNTS ON THE PARKING TABLE.
  
 C. NEW COMMENT: ALL OF THE PARKING SPACES SHOWN ON
 SHEET C002 NEED TO BE STRIPED AND COUNTED. THERE ARE
 THREE PARKING BAYS ON THE WEST SIDE OF THE SITE THAT DO
 NOT SHOW THE REQUIRED STRIPING AND THERE IS A PARKING
 BAY THAT DOES NOT LABEL THE TWO EXISTING PARKING
 SPACES. THERE ARE PARKING SPACES IN THE PARKING AREAS
 AT THE SOUTHEAST CORNER OF THE SITE THAT DO NOT SHOW
 THE REQUIRED STRIPING.
  
 7) SHEET C300 - REVISED COMMENT: I SPOKE WITH THE
 SAMANTHA HILL IN THE BUILDING DIVISION REGARDING ADA
 PARKING SPACES IN THE PARKING FIELD TO THE NORTH OF
 THIS PROPOSED BUILDING. YOU NEED TO SHOW THE LOCATIONS
 OF THE ENTRANCES TO THE BUILDING FOR BOTH PUBLIC AND
 EMPLOYEES AND THE ROUTE OF TRAVEL TO THE ENTRANCES. THE
 CLOSEST PARKING SPACES ALONG THE ROUTE NEED TO BE THE
 ADA PARKING SPACES.
  
 8) SHEET C301
  
 A. REVISED COMMENT: THANK YOU FOR PROVIDING DIMENSION
 LINES FOR ALL THE NEWLY STRIPED PARKING ROWS, BOTH
 WIDTH AND DEPTH; HOWEVER, THERE ARE INSTANCES WHERE THE
 DIMENSION TAG DOES NOT GO FROM CURB FACE TO CURB FACE
 TO SHOW THE PROPER BAY DIMENSION.
  
 B. REPEAT COMMENT: ONE OF THE RE-STRIPED PARKING ROWS
 SHOWS A PARKING STALL DEPTH DIMENSION OF ONLY 15 FEET.
 THIS NEEDS TO BE A MINIMUM OF 18 FEET. ---- THE
 COMMENTS STATE THAT DIMENSION LINES WERE ADDED FOR THIS
 PARKING BAY, BUT THEY WERE NOT.
  
 C. NEW COMMENT: THE REVISED PARKING FIELD SHOWS A ROW
 WITH 12 PARKING SPACES (EXCEEDS THE 10 IN A ROW
 PERMITTED BY THE ZLDR) AND A ROW THAT HAS 8 PARKING
 SPACES, YET IS LABELED AS 7 PARKING SPACES. BOTH OF
 THESE NEED TO BE CORRECTED.
  
 D. STAFF RECOMMENDATION: DO NOT USE BOTH WHEEL STOPS
 AND CURBS AT THE HEAD OF A PARKING SPACE. FOR SPACES
 THAT HAVE CURBS, THE CURB SHOULD BE MOVED TO CREATE A
 TWO (2) FOOT OVERHANG (REPLACE THE WHEEL STOP WITH THE
 CURB AND THE CAR HANGS OVER TWO FEET OF WIDENED
 SIDEWALK OR LANDSCAPE).
  
 E. REVISED COMMENT: THANK YOU FOR PROVIDING THE 22 FOOT
 WIDE AISLE WIDTH DIMENSION IN THE WESTERN PARKING FIELD
 THAT IS BEING RECONSTRUCTED AND RE-STRIPED. THIS
 DIMENSION DOES NOT COMPLY WITH THE REQUIRED MINIMUM 24
 FOOT AISLE WIDTH FOR PARKING LOTS THAT HAVE 90 DEGREE
 PARKING, SO IT MUST BE CORRECTED.
  
 F. REVISED COMMENT: I SPOKE WITH THE SAMANTHA HILL IN
 THE BUILDING DIVISION REGARDING ADA PARKING SPACES FOR
 THE REVISED PARKING FIELD. YOU NEED TO SHOW THE
 LOCATIONS OF THE ENTRANCES TO THE BUILDING FOR BOTH
 PUBLIC AND EMPLOYEES AND THE ROUTE OF TRAVEL TO THE
 ENTRANCES. THE CLOSEST PARKING SPACES ALONG THE ROUTE
 NEED TO BE THE ADA PARKING SPACES. THIS MIRRORS HOW TO
 VERIFY THE SIMILAR BUILDING DIVISION COMMENT FROM PPRC
 .
  
 9) REPEAT COMMENT: THE SITE PLANS SHOW THAT THE SITE IS
 DEFICIENT IN BICYCLE PARKING SO CODE COMPLIANT BICYCLE
 PARKING MUST BE PROVIDED THROUGHOUT THE CAMPUS AND THE
 DATA TABLES AND SITE DETAILS UPDATED ACCORDINGLY.
  
 A. THE DATA TABLES WERE NOT UPDATED TO REFLECT THE
 REQUIRED OR PROVIDED BICYCLE PARKING COUNTS. NO BICYCLE
 PARKING IS SHOWN FOR THE TWO MEDICAL OFFICE BUILDINGS.
 EXISTING OR ADDING BICYCLE PARKING TO THESE TWO
 LOCATIONS WILL INCREASE THE "PROVIDED" COUNTS.
  
 B. THE PROPOSED 8 SPACE BICYCLE RACK NEEDS TO HAVE THE
 DIMENSIONS INCLUDED ON THE SITE PLAN AS WELL AS A
 BICYCLE RACK DETAIL. THE ZLDR REQUIRE THAT BICYCLE
 PARKING BE LOCATED AS NEAR THE PRINCIPAL ENTRANCE OF
 THE BUILDING AS PRACTICABLE, SO STAFF WILL USE THE
 ENTRANCE PLANS REQUIRED BY COMMENTS 7 AND 8F TO
 EVALUATE THE LOCATION OF THIS PROPOSED BICYCLE RACK.
  
 10) REPEAT COMMENT: PROVIDE THE UTILITY RELEASE
 LETTERS.
  
 11) REPEAT COMMENT: SHEET C101 STATES THAT THERE IS
 STRIPING BEING REMOVED FROM THE WESTERN PORTION OF THE
 PARKING AREA, YET SHEET C301 DOES NOT CALL OUT THAT
 THIS AREA IS BEING RE-STRIPED (INDICATES THAT THE
 STRIPING IS EXISTING). THE COMMENT RESPONSE STATES THAT
 THERE IS NO CURRENT STRIPING IN THIS PARKING AREA,
 WHICH MEANS THAT SHEET C301 DEFINITELY NEEDS TO SHOW
 NEW, CODE COMPLIANT STRIPING WITH DIMENSIONS.
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-11-2018 Cont ID  
Sent By eschneid Date 12-11-2018 Time 16:06 Rev Time 3.00
Received By eschneid Date 12-11-2018 Time 10:26 Sent To  
Notes
2018-12-11 16:07:01PB 1223I
 JFK NORTH BEHAVIORAL HEALTH EXPANSION
 2201 45TH STREET
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 DECEMBER 28, 2018, TO BE ELIGIBLE TO BE SCHEDULED FOR
 THE FEBRUARY 19, 2019 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 FEBRUARY 12, 2019), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) PROVIDE THE PALM BEACH COUNTY TRAFFIC APPROVAL
 LETTER.
  
 2) THE SURVEY PROVIDED WITH THE APPLICATION DOES NOT
 REFLECT THE BOUNDARY OF THE WEST PALM BEACH HOSPITAL
 COMMUNITY SERVICE PLANNED DEVELOPMENT AS DESCRIBED IN
 ORDINANCE NO. 4503-14.
  
 3) PROVIDE A SITE AND LANDSCAPE PLAN FOR THE ENTIRE
 CSPD WHICH SHOWS COMPLIANCE WITH ZONING AND LAND
 DEVELOPMENT REGULATION REQUIREMENTS.
  
 4) THE SITE AND LANDSCAPE PLANS NEED TO SHOW THE
 ACCURATE CSPD BOUNDARIES AND THIS NEEDS TO BE REFLECTED
 ON THE SITE DATA TABLES FOR BOTH THE SITE AND LANDSCAPE
 PLANS.
  
 5) EACH BUILDING ON SHEET C002 NEEDS TO BE LABELED. THE
 SITE DATA TABLE ON SHEET C002 NEEDS TO LIST THE SQUARE
 FOOTAGE FOR EACH BUILDING AND ITS USE. IF A BUILDING
 CONTAINS BEDS, THE NUMBER OF BEDS WITHIN THE BUILDING
 NEEDS TO BE LISTED AS WELL.
  
 6) PARKING TABLE:
  
 A. THE PARKING COUNT IS INCORRECT FOR THE CSPD. WITHIN
 THE CSPD THERE ARE 664 REGULAR AND 30 ADA PARKING
 SPACES FOR THE PROPOSED PROJECT. THE SITE DATA TABLE
 INCORRECTLY INCLUDES SPACES FOR THE MEDICAL OFFICE
 BUILDING THAT IS OUTSIDE OF THE CSPD AND EXCLUDES SOME
 SPACES WITHIN THE CSPD.
 B. THE PARKING TABLE NEEDS TO LIST ONLY THE PARKING
 COUNTS AFTER THE PROJECT IS COMPLETED. THE EXISTING
 CONDITIONS NEED TO BE STATED IN THE JUSTIFICATION
 STATEMENT.
 C. PLEASE CONFIRM THAT THERE WILL BE NO ADDITIONAL
 DOCTORS ADDED TO PROVIDE TREATMENT FOR THE ADDITIONAL
 13,000 SQUARE FEET OF BEHAVIORAL HEALTH TREATMENT
 FACILITIES.
  
 7) BOTH THE CSPD AND THE COMMUNITY SERVICE ZONED
 PORTIONS OF THE COMMUNITY HOSPITAL OF THE PB, INC.,
 OWNED PROPERTY HAVE A UNITY OF TITLE, WHICH PERMITTED
 THE INSTALLATION OF THE SIGNS ALONG 45TH STREET. SINCE
 THE PROPERTIES ARE UNIFIED, THIS IS A CORNER LOT WITH
 45TH STREET BEING THE FRONT PROPERTY LINE AND CONGRESS
 AVENUE BEING THE CORNER SIDE PROPERTY LINE. THE SETBACK
 TABLE MUST REFLECT THIS. THE DIMENSION LINES FOR THE
 CLOSEST BUILDING POINTS TO THE PROPERTY LINE NEED TO BE
 SHOWN. NOTE: THE DIMENSION TO THE CONGRESS AVENUE
 (CORNER SIDE) DO NOT NEED TO BE SHOWN FOR THE TWO
 PROPOSED BUILDINGS, SINCE THERE ARE INTERVENING
 BUILDINGS WHICH WILL SHOW SETBACK COMPLIANT DIMENSION
 LINES.
  
 8) SHEET C300
  
 A. REMOVE THE SITE DATA TABLE. IT IS NOT REQUIRED ON
 EACH INDIVIDUAL SHEET, JUST THE OVERALL SITE PLAN.
 B. WHERE DOES THE WALKWAY BY THE DOOR ON THE WEST SIDE
 OF THE BUILDING LEAD TO? IT IS DANGEROUS TO DISCHARGE
 FOLKS INTO THE DRIVEWAY.
 C. PLEASE VERIFY WITH THE CONSTRUCTION SERVICES
 DIVISION THAT NO ADA PARKING SPACES ARE REQUIRED IN THE
 PARKING FIELD TO THE NORTH OF THIS PROPOSED BUILDING.
  
 9) SHEET C301
  
 A. REMOVE THE SITE DATA TABLE. IT IS NOT REQUIRED ON
 EACH INDIVIDUAL SHEET, JUST THE OVERALL SITE PLAN.
 B. PROVIDE DIMENSION LINES FOR ALL THE NEWLY STRIPED
 PARKING ROWS, BOTH WIDTH AND DEPTH.
 C. ONE OF THE RE-STRIPED PARKING ROWS SHOWS A PARKING
 STALL DEPTH DIMENSION OF ONLY 15 FEET. THIS NEEDS TO BE
 A MINIMUM OF 18 FEET.
 D. STRIPING NOT "A" INCORRECTLY CALLS OUT 6 INCH WHITE
 STRIPES FOR THE PARKING SPACES - THEY ARE TO BE 4
 INCHES AS SHOWN ON THE PARKING DETAIL.
 E. WHAT IS THE 19 FOOT MOUNTABLE AREA?
 F. WHY DO SOME PARKING STALLS HAVE WHEEL STOPS AND
 OTHERS NOT HAVE WHEEL STOPS. IF CURBING IS TO BE USED,
 THEN HAVE THE SPACES 16 FEET DEEP WITH A TWO FOOT OVER
 HANG.
 G. WHY ARE SOME PARKING SPACES 9 FEET WIDE AND OTHERS
 10 FEET WIDE?
 H. CLEARLY LABEL THE D CURBING.
 I. INCLUDE AISLE WIDTH DIMENSION LINES IN THE WESTERN
 PARKING FIELD THAT IS BEING RECONSTRUCTED AND
 RE-STRIPED.
 J. PROVIDE THE DRIVE AISLE WITH BEHIND THE 90 DEGREE
 PARKING INTO THE MAIN CAMPUS ROADWAY TO VERIFY THAT IT
 IS A MINIMUM OF 24 FEET WIDE AT THIS POINT.
 K. PLEASE VERIFY WITH THE CONSTRUCTION SERVICES
 DIVISION THAT THE LOCATION OF THE ADA PARKING SPACES
 COMPLIES WITH THE REQUIREMENT THAT THE ADA PARKING
 SPACES ARE CLOSEST TO THE ENTRANCE. THE TWO PROPOSED
 ADA PARKING SPACES APPEAR TO SERVE NOT BUILDING
 ENTRANCE.
  
 10) NEITHER THE SITE PLANS NOT THE ELEVATIONS SHOW ANY
 MECHANICAL EQUIPMENT. PLEASE SHOW THE MECHANICAL
 EQUIPMENT ON THE PLANS. PLEASE REMEMBER THAT BOTH
 ROOFTOP AND GROUND MOUNTED MECHANICAL EQUIPMENT MUST BE
 SCREENED.
  
 11) THE SITE PLANS SHOW THAT THE SITE IS DEFICIENT IN
 BICYCLE PARKING SO CODE COMPLIANT BICYCLE PARKING MUST
 BE PROVIDED THROUGHOUT THE CAMPUS AND THE DATA TABLES
 AND SITE DETAILS UPDATED ACCORDINGLY.
  
 12) PROVIDE THE UTILITY RELEASE LETTERS.
  
 13) THE INFORMATION ON SHEET C101 REGARDING THE REMOVAL
 OF STRIPING IS NOT REFLECTED ON SHEET C301 WHERE THIS
 AREA IS BEING RE-STRIPED.
  
  
  
  

  Print