Plan Review Details - Project Z18110018
| Plan Review Stops For Project Z18110018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
12-11-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
12-11-2018 |
Time |
18:38 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
12-11-2018 |
Time |
18:37 |
Sent To |
|
|
| Notes |
| 2018-12-11 18:41:27 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS | | | SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT | | | REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH | | | COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963, | | | OR BY EMAIL: [email protected] | | | | | | 3. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 7. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT | | | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 | | | 1080, OR BY EMAIL: [email protected] | | | | | | 8. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
P |
Date |
10-24-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
10-24-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
10-24-2019 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
04-08-2019 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
04-08-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
04-08-2019 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
12-06-2018 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
12-06-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
12-12-2018 |
Time |
11:38 |
Sent To |
I |
|
| Notes |
| 2018-12-06 12:23:37 | SHEET C1.3 - CORRECT CONTACT INFO FOR CITY OF WPB FOR | | | UTILITIES FROM DEB GRAYSON TO LAURA LE, P.E., CITY OF | | | WPB PUBLIC UTILITIES ADMIN., 561-494-1043, [email protected]. | | | AND FOR CITY OF WPB FOR ENGINEERING FROM DEB GRAYSON TO | | | MANNY GONZALEZ, SR. PROJECT COORDINATOR, 561-494-1085, | | | [email protected]. MS. GRAYSON IS NO LONGER HERE. | | | | | | SHEET C6.1 - SHOW MIN. VERTICAL CLEARANCES AT | | | WATER/SEWER CROSSINGS. | | | | | | THE FOLLOWING COMMENTS ARE INCLUDED FOR YOUR GENERAL | | | INFORMATION AND USE. THEY MAY NOT BE SITE-SPECIFIC, BUT | | | WILL SOON BE ADDED TO CITY OF WEST PALM BEACH | | | DEVELOPMENT PERMIT APPLICATIONS. | | | | | | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS | | | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE | | | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER | | | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT | | | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: | | | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W | | | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P | | | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 | | | 60045731D3658206F27451722716EF | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, | | | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, | | | 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | | | | PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS | | | FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) AND FIRE | | | FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR | | | SEWER AND PER FAC 64-E.008 FOR WATER. | | | | | | PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG | | | ENTIRE PROJECT FRONTAGE INCLUDING THE ALLEY TO THE WEST | | | OF THE PROJECT (FROM 27TH ST. TO PROJECT). | | | | | | PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF | | | WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT | | | OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR | | | PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE | | | MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL | | | IN THE WPB ENGINEERING SERVICES DEPARTMENT AT | | | [email protected] OR 561-494-1079 FOR FURTHER | | | ASSISTANCE. NOTE THAT FIELD RECORDS ARE FOR INFORMATION | | | ONLY. FIELD VERIFY UTILITY LOCATIONS USING FIELD | | | SURVEY, POT-HOLING, SOFT DIGS ETC. | | | | | | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF | | | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | ADDITIONALLY, PLAN VIEW SHALL SHOW ALL EXISTING AND | | | PROPOSED UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER | | | OPTIC, ELECTRIC, GAS, AND CABLEVISION & | | | TELECOMMUNICATION FACILITIES LOCATED ON THE | | | RIGHT-OF-WAY. | | | | | | PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS WITHIN | | | CITY OF WPB RIGHT OF WAY. | | | | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
10-28-2019 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
10-28-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
10-28-2019 |
Time |
11:59 |
Sent To |
|
|
| Notes |
| 2019-10-28 12:03:00 | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM HEATHER | | | DANFORTH, SENIOR PLANNER, DATED OCTOBER 23, 2019, AND | | | THE ATTACHED DRAWING DOCUMENTS, THE PREVIOUSLY | | | SUBMITTED FIRE PREVENTION BUREAU COMMENTS APPEAR TO | | | HAVE BEEN ADDRESSED. | | | | | | HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED | | | PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR | | | APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
12-04-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
12-04-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
12-12-2018 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2018-12-04 13:18:42 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING(S) SHALL COMPLY | | | WITH THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION | | | CODE, INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE | | | CODES. | | | | | | 6. NFPA 101, CHAPTER 30, NEW APARTMENT BUILDINGS SHALL | | | BE USED WHEN REVIEWING THIS PROJECT FOR LIFE SAFETY. | | | | | | 7. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. A NFPA 14 COMPLIANT WET | | | STANDPIPE SYSTEM MAY BE REQUIRED BASED ON THE LOWEST | | | POINT OF FIRE DEPARTMENT ACCESS TO A 30FT FLOOR LEVEL. | | | IN ADDITION, TEMPORARY STANDPIPES MAY BE REQUIRED WHEN | | | A BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. | | | | | | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | | PRIOR TO ANY INSTALLATION. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | | | | 8. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 9. THE LOCATION OF THE FACP SHALL BE COORDINATED WITH | | | THE OFFICE OF THE FIRE MARSHAL. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | ANY FABRICS/MATERIALS LOCATED ON THE EXTERIOR OF THE | | | BUILDING SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION | | | CODE, LISTED AND TESTED AS APPLICABLE TO THE | | | INSTALLATION, AND APPROVED THROUGH THE OFFICE OF THE | | | FIRE MARSHAL. | | | | | | 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 12. THERE DOES NOT APPEAR TO BE A DESIGNATED FIRE LANE | | | FOR FD APPARATUS STAGING FOR THIS PROPOSED BUILDING. | | | THE FIRE LANE WILL BE INDICATED AT THE OPTIMUM ACCESS | | | POINT OF ARRIVING FIRE APPARATUS AND COORDINATED WITH | | | THE FIRE HYDRANT, FCD, FACP, AND FD PERSONNEL ACCESS | | | POINTS. THE LOCATION OF THE FIRE LANE SHALL BE | | | COORDINATED WITH THE OFFICE OF THE FIRE MARSHAL. | | | | | | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
06-18-2020 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-18-2020 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-18-2020 |
Time |
15:13 |
Sent To |
|
|
| Notes |
| 2020-06-18 15:13:37 | FROM: RAY CARANCI, SENIOR LANDSCAPE PLANNER | | | 561-822-1462 | | | PROJECT: 2823 BROADWAY MIXED USE Z18110018 | | | JUNE 19, 2020 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE DISPOSITION CHART OF THE TREES WITHIN | | | THE AFFECTED AREA AND INDICATE IF THEY WILL BE | | | PRESERVED IN PLACE, RELOCATED OR REMOVED. LIST THE | | | BOTANICAL NAME AND PROVIDE THE CANOPY DIAMETER. | | | CALCULATE THE REQUIRED MITIGATION IN SQUARE FOOTAGE. | | | THE CHART PROVIDED NEEDS TO BE CORRECTED TO MEET CODE | | | REQUIREMENTS FOR CANOPY MITIGATION DUE. | | | ? SATISFIED. SHOW CALCULATIONS FOR CANOPY SQUARE | | | FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF UNDER | | | 20 FEET, ACTUAL AREA 20 FEET OR MORE WITHIN THE | | | DISPOSITION CHART. COCONUT CATEGORY 3 IS100 SQ FT EACH | | | MITIGATION DUE FOR # 1, 17 AND 18, #6 FICUS 855 SQ FT | | | DUE, #7 MANGO 380 SQ FT DUE, MANGO #8 AND #11, 300 SQ | | | FT EACH DUE. | | | ? SATISFIED. SABAL PALMS IN GOOD CONDITION MUST BE | | | RELOCATED. IF THEY ARE NOT RELOCATABLE, MITIGATION IS | | | DUE AT 100 SQ FT EACH. (#2 AND 3, AND #12 THROUGH 16). | | | ? SATISFIED. ADD THE SUM OF ALL TREE CANOPY MITIGATION | | | TO SHOW THE TOTAL MITIGATION DUE. PROVIDE TOTAL. | | | ? SATISFIED. SHOW THE MITIGATION PROVIDED CALCULATION | | | FOR ALL TREES AND PALMS PROPOSED WITH THE LANDSCAPE | | | PLAN. PROVIDE TOTAL. | | | ? SATISFIED. #4, 5 AND 9 INVASIVE EXOTICS, NO | | | MITIGATION REQUIRED. | | | PLEASE CONTACT RAY CARANCI TO DISCUSS CORRECTIONS. | | | | | | 2. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE | | | DESIGN OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE | | | REQUIRED 50 POINTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. | | | | | | 4. SATISFIED. PROVIDE CALCULATIONS FOR REQUIRED BUFFER | | | TREES AT ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR | | | ALL BUFFER LENGTHS, AND SHOW THE NUMBER PROVIDED. | | | PROVIDE THE CALCULATIONS FOR A TREE EVERY 30 FEET FOR | | | EACH BUFFER LENGTH. BMUD CODE REQUIRES THE TREES IN THE | | | SETBACKS ADJACENT TO THE ROAD. | | | 190 FOOT BUFFER LENGTH REQUIRES 7 TREES. CANNOT DOUBLE | | | COUNT TREES AT CORNERS. ADJUST COUNTS ON CHART AND ADD | | | 1 TREE OR PALM TO THE NORTH BUFFER. | | | | | | 5. SATISFIED. SHOW THE LOCATIONS OF REQUIRED 10 FOOT | | | LANDSCAPE BUFFERS ON THE BROADWAY, 28TH AND 27TH STREET | | | SIDES OF THE PROJECT PER SECTION 94-443(D). SHOW THE | | | BUFFER WIDTH PROVIDED ON THE WEST PROPERTY LINE. | | | | | | 6. SATISFIED. PROVIDE THE REQUIRED BUFFER TREES WITHIN | | | THE PROPERTY LINE OF THE PROJECT. TREES MAY BE PLACED | | | ANYWHERE WITHIN THE AREA BETWEEN THE PROPERTY LINE AND | | | BUILDING. SHRUBS MAY BE PLACED BETWEEN THE CURB AND | | | SIDEWALK AS PART OF ROADWAY BEAUTIFICATION TO SEPARATE | | | THE PUBLIC OPEN SPACE AREAS FROM TRAFFIC. | | | STAFF REQUESTS THE DESIGN BE CHANGED ALONG BROADWAY TO | | | PLACE THE TREES BEHIND THE SIDEWALK AND ADD SHRUB | | | PLANTING STRIP BETWEEN THE SIDEWALK AND CURB. THIS WILL | | | CONFORM TO FDOT ACCEPTABLE STANDARDS. | | | | | | 7. SATISFIED. PROVIDE HEDGES TO SCREEN ALL PARKING | | | AREAS FROM ADJACENT PROPERTIES AND STREETS. | | | THE 27TH AND 28TH STREET ENDS OF THE PARKING LOT | | | REQUIRE A 36 INCH HEDGE. | | | | | | 8. SATISFIED. PROVIDE THE REQUIRED TREE OR PALM | | | EQUIVALENT IN THE CENTER LANDSCAPE ISLAND IN THE ROW OF | | | PARKING ALONG THE BUILDING. THE ISLAND CAN BE DESIGNED | | | TO PLACE THE SIDEWALK AT ONE SIDE OF THE ISLAND RATHER | | | THAN SPLITTING IT TO ACCOMMODATE A TREE. | | | | | | 9. SATISFIED. MULTIFAMILY REQUIREMENTS OF SECTION | | | 94-443(D) SHALL APPLY FOR THE ADDITIONAL TREES REQUIRED | | | AT ONE PER UNIT ADDED TO THE OVERALL SHADE TREE AND | | | FLOWERING TREE REQUIREMENT. SHOW TOTAL REQUIRED AND | | | PROVIDED. | | | BROADWAY MIXED USE DISTRICT SECTION 94-220(G) SPECIFIES | | | ALL SECTIONS OF THE LANDSCAPE CODE ARTICLE XIV SHALL | | | APPLY UNLESS OTHERWISE PROVIDED. | | | REQUIRED TREES ARE 15 PLUS 5 PLUS 52. TOTAL REQUIRED IS | | | 72. PROVIDED IS 20 SHADE TREES, 8 ROYAL PALMS, AND 55 | | | PALMS AT 3:1 (18) FOR A TOTAL OF 46. | | | | | | | | | 10. SATISFIED. SHOW LINEAR FOOTAGE OF LANDSCAPED AREA | | | ADJACENT TO THE BUILDING MEETS THE REQUIREMENT OF 40 | | | PERCENT PER SECTION 94-443(D)(2) B. | | | PROVIDE THE TOTAL LINEAR FOOTAGE OF THE BUILDING | | | PERIMETER AND PROVIDE THE LINEAR FOOTAGE OF LANDSCAPED | | | AREAS. | | | | | | 11. SATISFIED. RECONSIDER FOXTAIL PALM SPECIES | | | SELECTION, AS THEIR HIGH WATER AND FERTILIZER DEMANDS | | | IMPOSE A MAINTENANCE BURDEN OVER THE LONG TERM OF THE | | | PROJECT. | | | | | | 12. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | PROVIDE THE TOTAL PERCENTAGE BASED ON FINAL PLANT LIST. | | | | | | 13. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES | | | ON THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES | | | AND LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | THERE ARE MULTIPLE CONFLICTS BETWEEN TREES AND WATER | | | AND SEWER LINES IN THE LANDSCAPE ISLANDS ALONG THE REAR | | | OF THE BUILDING. UTILITY LOCATIONS NEED TO BE ADJUSTED. | | | | | | 14. SATISFIED. PROVIDE A DETAIL AND LOCATIONS OF ROOT | | | BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY LINES. | | | THE LOCATIONS OF THE UTILITIES AND ROOT BARRIERS REMOVE | | | MOST OF THE ROOT AREA FOR THE TREES IN THE LANDSCAPE | | | ISLANDS ALONG THE REAR OF THE BUILDING. UTILITY | | | LOCATIONS NEED TO BE ADJUSTED. | | | PROVIDE ROOT BARRIERS IN LANDSCAPE ISLANDS AND A | | | RELEASE WOULD NEED TO BE PROVIDED FOR THE TREES PLACED | | | IN THE PROPOSED UTILITY EASEMENT. | | | | | | 15. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | PLANT SPECIES NEEDS TO GROW TALL ENOUGH TO SCREEN | | | EQUIPMENT. | | | | | | 16. SATISFIED. PROVIDE THE REQUIRED HEDGE FOR THREE | | | SIDES OF THE DUMPSTER ENCLOSURE AS REQUIRED. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | ADDITIONAL COMMENTS 4/22/19: | | | 18. SATISFIED. PROVIDE THE FLOWERING TREES REQUIRED | | | BASED ON THE OPEN SPACE AT ONE PER EVERY 6000 SQ FT OR | | | PORTION THEREOF. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
10-29-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-29-2019 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-29-2019 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2019-10-29 16:06:49 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2823 BROADWAY MIXED USE Z18110018 | | | OCTOBER 29, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE DISPOSITION CHART OF THE TREES WITHIN | | | THE AFFECTED AREA AND INDICATE IF THEY WILL BE | | | PRESERVED IN PLACE, RELOCATED OR REMOVED. LIST THE | | | BOTANICAL NAME AND PROVIDE THE CANOPY DIAMETER. | | | CALCULATE THE REQUIRED MITIGATION IN SQUARE FOOTAGE. | | | THE CHART PROVIDED NEEDS TO BE CORRECTED TO MEET CODE | | | REQUIREMENTS FOR CANOPY MITIGATION DUE. | | | ? SATISFIED. SHOW CALCULATIONS FOR CANOPY SQUARE | | | FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF UNDER | | | 20 FEET, ACTUAL AREA 20 FEET OR MORE WITHIN THE | | | DISPOSITION CHART. COCONUT CATEGORY 3 IS100 SQ FT EACH | | | MITIGATION DUE FOR # 1, 17 AND 18, #6 FICUS 855 SQ FT | | | DUE, #7 MANGO 380 SQ FT DUE, MANGO #8 AND #11, 300 SQ | | | FT EACH DUE. | | | ? SATISFIED. SABAL PALMS IN GOOD CONDITION MUST BE | | | RELOCATED. IF THEY ARE NOT RELOCATABLE, MITIGATION IS | | | DUE AT 100 SQ FT EACH. (#2 AND 3, AND #12 THROUGH 16). | | | ? PARTIALLY SATISFIED. ADD THE SUM OF ALL TREE CANOPY | | | MITIGATION TO SHOW THE TOTAL MITIGATION DUE. PROVIDE | | | TOTAL. | | | ? PARTIALLY SATISFIED. SHOW THE MITIGATION PROVIDED | | | CALCULATION FOR ALL TREES AND PALMS PROPOSED WITH THE | | | LANDSCAPE PLAN. PROVIDE TOTAL. | | | ? SATISFIED. #4, 5 AND 9 INVASIVE EXOTICS, NO | | | MITIGATION REQUIRED. | | | PLEASE CONTACT RAY CARANCI TO DISCUSS CORRECTIONS. | | | | | | 2. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE | | | DESIGN OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE | | | REQUIRED 50 POINTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. | | | | | | 4. PARTIALLY SATISFIED. PROVIDE CALCULATIONS FOR | | | REQUIRED BUFFER TREES AT ONE FOR EVERY 30 FEET OR | | | PORTION THEREOF FOR ALL BUFFER LENGTHS, AND SHOW THE | | | NUMBER PROVIDED. | | | PROVIDE THE CALCULATIONS FOR A TREE EVERY 30 FEET FOR | | | EACH BUFFER LENGTH. BMUD CODE REQUIRES THE TREES IN THE | | | SETBACKS ADJACENT TO THE ROAD. | | | 190 FOOT BUFFER LENGTH REQUIRES 7 TREES. CANNOT DOUBLE | | | COUNT TREES AT CORNERS. ADJUST COUNTS ON CHART, AND ADD | | | 1 TREE OR PALM TO THE NORTH BUFFER. | | | | | | 5. SATISFIED. SHOW THE LOCATIONS OF REQUIRED 10 FOOT | | | LANDSCAPE BUFFERS ON THE BROADWAY, 28TH AND 27TH STREET | | | SIDES OF THE PROJECT PER SECTION 94-443(D). SHOW THE | | | BUFFER WIDTH PROVIDED ON THE WEST PROPERTY LINE. | | | | | | 6. SATISFIED. PROVIDE THE REQUIRED BUFFER TREES WITHIN | | | THE PROPERTY LINE OF THE PROJECT. TREES MAY BE PLACED | | | ANYWHERE WITHIN THE AREA BETWEEN THE PROPERTY LINE AND | | | BUILDING. SHRUBS MAY BE PLACED BETWEEN THE CURB AND | | | SIDEWALK AS PART OF ROADWAY BEAUTIFICATION TO SEPARATE | | | THE PUBLIC OPEN SPACE AREAS FROM TRAFFIC. | | | STAFF REQUESTS THE DESIGN BE CHANGED ALONG BROADWAY TO | | | PLACE THE TREES BEHIND THE SIDEWALK AND ADD SHRUB | | | PLANTING STRIP BETWEEN THE SIDEWALK AND CURB. THIS WILL | | | CONFORM TO FDOT ACCEPTABLE STANDARDS. | | | | | | 7. SATISFIED. PROVIDE HEDGES TO SCREEN ALL PARKING | | | AREAS FROM ADJACENT PROPERTIES AND STREETS. | | | THE 27TH AND 28TH STREET ENDS OF THE PARKING LOT | | | REQUIRE A 36 INCH HEDGE. | | | | | | 8. SATISFIED. PROVIDE THE REQUIRED TREE OR PALM | | | EQUIVALENT IN THE CENTER LANDSCAPE ISLAND IN THE ROW OF | | | PARKING ALONG THE BUILDING. THE ISLAND CAN BE DESIGNED | | | TO PLACE THE SIDEWALK AT ONE SIDE OF THE ISLAND RATHER | | | THAN SPLITTING IT TO ACCOMMODATE A TREE. | | | | | | 9. PARTIALLY SATISFIED. MULTIFAMILY REQUIREMENTS OF | | | SECTION 94-443(D) SHALL APPLY FOR THE ADDITIONAL TREES | | | REQUIRED AT ONE PER UNIT ADDED TO THE OVERALL SHADE | | | TREE AND FLOWERING TREE REQUIREMENT. SHOW TOTAL | | | REQUIRED AND PROVIDED. | | | BROADWAY MIXED USE DISTRICT SECTION 94-220(G) SPECIFIES | | | ALL SECTIONS OF THE LANDSCAPE CODE ARTICLE XIV SHALL | | | APPLY UNLESS OTHERWISE PROVIDED. | | | REQUIRED TREES ARE 15 PLUS 5 PLUS 52. TOTAL REQUIRED IS | | | 72. PROVIDED IS 20 SHADE TREES, 8 ROYAL PALMS, AND 55 | | | PALMS AT 3:1 (18) FOR A TOTAL OF 46. | | | | | | | | | 10. SATISFIED. SHOW LINEAR FOOTAGE OF LANDSCAPED AREA | | | ADJACENT TO THE BUILDING MEETS THE REQUIREMENT OF 40 | | | PERCENT PER SECTION 94-443(D)(2) B. | | | PROVIDE THE TOTAL LINEAR FOOTAGE OF THE BUILDING | | | PERIMETER AND PROVIDE THE LINEAR FOOTAGE OF LANDSCAPED | | | AREAS. | | | | | | 11. SATISFIED. RECONSIDER FOXTAIL PALM SPECIES | | | SELECTION, AS THEIR HIGH WATER AND FERTILIZER DEMANDS | | | IMPOSE A MAINTENANCE BURDEN OVER THE LONG TERM OF THE | | | PROJECT. | | | | | | 12. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | PROVIDE THE TOTAL PERCENTAGE BASED ON FINAL PLANT LIST. | | | | | | 13. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES | | | ON THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES | | | AND LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | THERE ARE MULTIPLE CONFLICTS BETWEEN TREES AND WATER | | | AND SEWER LINES IN THE LANDSCAPE ISLANDS ALONG THE REAR | | | OF THE BUILDING. UTILITY LOCATIONS NEED TO BE ADJUSTED. | | | | | | 14. PARTIALLY SATISFIED. PROVIDE A DETAIL AND LOCATIONS | | | OF ROOT BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY | | | LINES. | | | THE LOCATIONS OF THE UTILITIES AND ROOT BARRIERS REMOVE | | | MOST OF THE ROOT AREA FOR THE TREES IN THE LANDSCAPE | | | ISLANDS ALONG THE REAR OF THE BUILDING. UTILITY | | | LOCATIONS NEED TO BE ADJUSTED. | | | PROVIDE ROOT BARRIERS IN LANDSCAPE ISLANDS AND A | | | RELEASE WOULD NEED TO BE PROVIDED FOR THE TREES PLACED | | | IN THE PROPOSED UTILITY EASEMENT. | | | | | | 15. SATISFIED. PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | VALVES AND EQUIPMENT. | | | PLANT SPECIES NEEDS TO GROW TALL ENOUGH TO SCREEN | | | EQUIPMENT. | | | | | | 16. SATISFIED. PROVIDE THE REQUIRED HEDGE FOR THREE | | | SIDES OF THE DUMPSTER ENCLOSURE AS REQUIRED. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | ADDITIONAL COMMENTS 4/22/19: | | | 18. SATISFIED. PROVIDE THE FLOWERING TREES REQUIRED | | | BASED ON THE OPEN SPACE AT ONE PER EVERY 6000 SQ FT OR | | | PORTION THEREOF. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
04-22-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-22-2019 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-22-2019 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2019-04-22 14:25:53 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2823 BROADWAY MIXED USE Z18110018 | | | APRIL 19, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PARTIALLY SATISFIED. PROVIDE A TREE DISPOSITION | | | CHART OF THE TREES WITHIN THE AFFECTED AREA AND | | | INDICATE IF THEY WILL BE PRESERVED IN PLACE, RELOCATED | | | OR REMOVED. LIST THE BOTANICAL NAME AND PROVIDE THE | | | CANOPY DIAMETER. CALCULATE THE REQUIRED MITIGATION IN | | | SQUARE FOOTAGE. | | | THE CHART PROVIDED NEEDS TO BE CORRECTED TO MEET CODE | | | REQUIREMENTS FOR CANOPY MITIGATION DUE. | | | ? SHOW CALCULATIONS FOR CANOPY SQUARE FOOTAGE BASED ON | | | DIAMETER, 1:1 SAME CATEGORY IF UNDER 20 FEET, ACTUAL | | | AREA 20 FEET OR MORE WITHIN THE DISPOSITION CHART. | | | COCONUT CATEGORY 3 IS100 SQ FT EACH MITIGATION DUE FOR | | | # 1, 17 AND 18, #6 FICUS 855 SQ FT DUE, #7 MANGO 380 SQ | | | FT DUE, MANGO #8 AND #11, 300 SQ FT EACH DUE. | | | ? SABAL PALMS IN GOOD CONDITION MUST BE RELOCATED. IF | | | THEY ARE NOT RELOCATABLE, MITIGATION IS DUE AT 100 SQ | | | FT EACH. (#2 AND 3, AND #12 THROUGH 16). | | | ? ADD THE SUM OF ALL TREE CANOPY MITIGATION TO SHOW THE | | | TOTAL MITIGATION DUE. | | | ? SHOW THE MITIGATION PROVIDED CALCULATION FOR ALL | | | TREES AND PALMS PROPOSED WITH THE LANDSCAPE PLAN. | | | ? #4, 5 AND 9 INVASIVE EXOTICS, NO MITIGATION REQUIRED. | | | PLEASE CONTACT RAY CARANCI TO DISCUSS CORRECTIONS. | | | | | | 2. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE | | | DESIGN OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE | | | REQUIRED 50 POINTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4) AND PROVIDE CALCULATIONS. | | | | | | 4. PARTIALLY SATISFIED. PROVIDE CALCULATIONS FOR | | | REQUIRED BUFFER TREES AT ONE FOR EVERY 30 FEET OR | | | PORTION THEREOF FOR ALL BUFFER LENGTHS, AND SHOW THE | | | NUMBER PROVIDED. | | | PROVIDE THE CALCULATIONS FOR A TREE EVERY 30 FEET FOR | | | EACH BUFFER LENGTH. BMUD CODE REQUIRES THE TREES IN THE | | | SETBACKS ADJACENT TO THE ROAD. | | | | | | 5. SATISFIED. SHOW THE LOCATIONS OF REQUIRED 10 FOOT | | | LANDSCAPE BUFFERS ON THE BROADWAY, 28TH AND 27TH STREET | | | SIDES OF THE PROJECT PER SECTION 94-443(D). SHOW THE | | | BUFFER WIDTH PROVIDED ON THE WEST PROPERTY LINE. | | | | | | 6. PARTIALLY SATISFIED. PROVIDE THE REQUIRED BUFFER | | | TREES WITHIN THE PROPERTY LINE OF THE PROJECT. TREES | | | MAY BE PLACED ANYWHERE WITHIN THE AREA BETWEEN THE | | | PROPERTY LINE AND BUILDING. SHRUBS MAY BE PLACED | | | BETWEEN THE CURB AND SIDEWALK AS PART OF ROADWAY | | | BEAUTIFICATION TO SEPARATE THE PUBLIC OPEN SPACE AREAS | | | FROM TRAFFIC. | | | STAFF REQUESTS THE DESIGN BE CHANGED ALONG BROADWAY TO | | | PLACE THE TREES BEHIND THE SIDEWALK AND ADD SHRUB | | | PLANTING STRIP BETWEEN THE SIDEWALK AND CURB. THIS WILL | | | CONFORM TO FDOT ACCEPTABLE STANDARDS. | | | | | | 7. PARTIALLY SATISFIED. PROVIDE HEDGES TO SCREEN ALL | | | PARKING AREAS FROM ADJACENT PROPERTIES AND STREETS. | | | THE 27TH AND 28TH STREET ENDS OF THE PARKING LOT | | | REQUIRE A 36 INCH HEDGE. | | | | | | 8. SATISFIED. PROVIDE THE REQUIRED TREE OR PALM | | | EQUIVALENT IN THE CENTER LANDSCAPE ISLAND IN THE ROW OF | | | PARKING ALONG THE BUILDING. THE ISLAND CAN BE DESIGNED | | | TO PLACE THE SIDEWALK AT ONE SIDE OF THE ISLAND RATHER | | | THAN SPLITTING IT TO ACCOMMODATE A TREE. | | | | | | 9. NOT SATISFIED. MULTIFAMILY REQUIREMENTS OF SECTION | | | 94-443(D) SHALL APPLY FOR THE ADDITIONAL TREES REQUIRED | | | AT ONE PER UNIT ADDED TO THE OVERALL SHADE TREE AND | | | FLOWERING TREE REQUIREMENT. SHOW TOTAL REQUIRED AND | | | PROVIDED. | | | BROADWAY MIXED USE DISTRICT SECTION 94-220(G) SPECIFIES | | | ALL SECTIONS OF THE LANDSCAPE CODE ARTICLE XIV SHALL | | | APPLY UNLESS OTHERWISE PROVIDED. | | | | | | | | | 10. NOT SATISFIED. SHOW LINEAR FOOTAGE OF LANDSCAPED | | | AREA ADJACENT TO THE BUILDING MEETS THE REQUIREMENT OF | | | 40 PERCENT PER SECTION 94-443(D)(2) B. | | | PROVIDE THE TOTAL LINEAR FOOTAGE OF THE BUILDING | | | PERIMETER AND PROVIDE THE LINEAR FOOTAGE OF LANDSCAPED | | | AREAS. | | | | | | 11. SATISFIED. RECONSIDER FOXTAIL PALM SPECIES | | | SELECTION, AS THEIR HIGH WATER AND FERTILIZER DEMANDS | | | IMPOSE A MAINTENANCE BURDEN OVER THE LONG TERM OF THE | | | PROJECT. | | | | | | 12. PARTIALLY SATISFIED. SHOW COMPLIANCE WITH SECTION | | | 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF | | | PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | PROVIDE THE TOTAL PERCENTAGE BASED ON FINAL PLANT LIST. | | | | | | 13. NOT SATISFIED. THE LOCATIONS OF WATER AND SEWER | | | LINES ON THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH | | | TREES AND LANDSCAPING. RELOCATE UTILITY LOCATIONS OR | | | EXPAND LANDSCAPE AREAS TO ACCOMMODATE REQUIRED | | | LANDSCAPING. SHOW LOCATIONS OF FPL TRANSFORMERS ON THE | | | LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | THERE ARE MULTIPLE CONFLICTS BETWEEN TREES AND WATER | | | AND SEWER LINES IN THE LANDSCAPE ISLANDS ALONG THE REAR | | | OF THE BUILDING. UTILITY LOCATIONS NEED TO BE ADJUSTED. | | | | | | 14. PARTIALLY SATISFIED. PROVIDE A DETAIL AND LOCATIONS | | | OF ROOT BARRIERS TO SEPARATE LANDSCAPING FROM UTILITY | | | LINES. | | | THE LOCATIONS OF THE UTILITIES AND ROOT BARRIERS REMOVE | | | MOST OF THE ROOT AREA FOR THE TREES IN THE LANDSCAPE | | | ISLANDS ALONG THE REAR OF THE BUILDING. UTILITY | | | LOCATIONS NEED TO BE ADJUSTED. | | | | | | 15. NOT SATISFIED. PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED VALVES AND EQUIPMENT. | | | PLANT SPECIES NEEDS TO GROW TALL ENOUGH TO SCREEN | | | EQUIPMENT. | | | | | | 16. SATISFIED. PROVIDE THE REQUIRED HEDGE FOR THREE | | | SIDES OF THE DUMPSTER ENCLOSURE AS REQUIRED. | | | | | | 17. SATISFIED. SHOW THE LOCATIONS OF ALL SITE LIGHTING | | | ON THE LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH | | | TREES. | | | ADDITIONAL COMMENTS 4/22/19: | | | 18. PROVIDE THE FLOWERING TREES REQUIRED BASED ON THE | | | OPEN SPACE AT ONE PER EVERY 6000 SQ FT OR PORTION | | | THEREOF. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
12-10-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-10-2018 |
Time |
17:33 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-10-2018 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2018-12-10 17:34:57 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2823 BROADWAY MIXED USE Z18110018 | | | DECEMBER 7, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE DISPOSITION CHART OF THE TREES WITHIN | | | THE AFFECTED AREA AND INDICATE IF THEY WILL BE | | | PRESERVED IN PLACE, RELOCATED OR REMOVED. LIST THE | | | BOTANICAL NAME AND PROVIDE THE CANOPY DIAMETER. | | | CALCULATE THE REQUIRED MITIGATION IN SQUARE FOOTAGE. | | | | | | 2. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE DESIGN | | | OPTIONS CHART SECTION 94-446 (G) AND PROVIDE THE | | | REQUIRED 50 POINTS. PROVIDE BACK UP INFORMATION FOR ALL | | | ITEMS CLAIMED. | | | | | | 3. PROVIDE A PLAN SHOWING THE PARKING LANDSCAPE AREAS | | | COUNTED TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND | | | (4) AND PROVIDE CALCULATIONS. | | | | | | 4. PROVIDE CALCULATIONS FOR REQUIRED BUFFER TREES AT | | | ONE FOR EVERY 30 FEET OR PORTION THEREOF FOR ALL BUFFER | | | LENGTHS, AND SHOW THE NUMBER PROVIDED. | | | | | | 5. SHOW THE LOCATIONS OF REQUIRED 10 FOOT LANDSCAPE | | | BUFFERS ON THE BROADWAY, 28TH AND 27TH STREET SIDES OF | | | THE PROJECT PER SECTION 94-443(D). SHOW THE BUFFER | | | WIDTH PROVIDED ON THE WEST PROPERTY LINE. | | | | | | 6. PROVIDE THE REQUIRED BUFFER TREES WITHIN THE | | | PROPERTY LINE OF THE PROJECT. TREES MAY BE PLACED | | | ANYWHERE WITHIN THE AREA BETWEEN THE PROPERTY LINE AND | | | BUILDING. SHRUBS MAY BE PLACED BETWEEN THE CURB AND | | | SIDEWALK AS PART OF ROADWAY BEAUTIFICATION TO SEPARATE | | | THE PUBLIC OPEN SPACE AREAS FROM TRAFFIC. | | | | | | 7. PROVIDE HEDGES TO SCREEN ALL PARKING AREAS FROM | | | ADJACENT PROPERTIES AND STREETS. | | | | | | 8. PROVIDE THE REQUIRED TREE OR PALM EQUIVALENT IN THE | | | CENTER LANDSCAPE ISLAND IN THE ROW OF PARKING ALONG THE | | | BUILDING. THE ISLAND CAN BE DESIGNED TO PLACE THE | | | SIDEWALK AT ONE SIDE OF THE ISLAND RATHER THAN | | | SPLITTING IT TO ACCOMMODATE A TREE. | | | | | | 9. MULTIFAMILY REQUIREMENTS OF SECTION 94-443(D) SHALL | | | APPLY FOR THE ADDITIONAL TREES REQUIRED AT ONE PER UNIT | | | ADDED TO THE OVERALL SHADE TREE AND FLOWERING TREE | | | REQUIREMENT. SHOW TOTAL REQUIRED AND PROVIDED. | | | | | | 10. SHOW LINEAR FOOTAGE OF LANDSCAPED AREA ADJACENT TO | | | THE BUILDING MEETS THE REQUIREMENT OF 40 PERCENT PER | | | SECTION 94-443(D)(2) B. | | | | | | 11. RECONSIDER FOXTAIL PALM SPECIES SELECTION, AS THEIR | | | HIGH WATER AND FERTILIZER DEMANDS IMPOSE A MAINTENANCE | | | BURDEN OVER THE LONG TERM OF THE PROJECT. | | | | | | 12. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | 13. THE LOCATIONS OF WATER AND SEWER LINES ON THE | | | LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | SHOW LOCATIONS OF FPL TRANSFORMERS ON THE LANDSCAPE | | | PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING. | | | | | | 14. PROVIDE A DETAIL AND LOCATIONS OF ROOT BARRIERS TO | | | SEPARATE LANDSCAPING FROM UTILITY LINES. | | | | | | 15. PROVIDE SCREENING FOR ALL GROUND MOUNTED VALVES AND | | | EQUIPMENT. | | | | | | 16. PROVIDE THE REQUIRED HEDGE FOR THREE SIDES OF THE | | | DUMPSTER ENCLOSURE AS REQUIRED. | | | | | | 17. SHOW THE LOCATIONS OF ALL SITE LIGHTING ON THE | | | LANDSCAPE PLAN AND RESOLVE ANY CONFLICTS WITH TREES. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
12-13-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
P |
Date |
08-18-2020 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
08-18-2020 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
08-18-2020 |
Time |
14:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
F |
Date |
10-23-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-23-2019 |
Time |
11:04 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
10-23-2019 |
Time |
11:53 |
Sent To |
|
|
| Notes |
| 2019-10-23 11:53:27 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 10/23/2019 SUBMITTAL PACKAGE. | | | | | | 1. THE NOTE ON SHEET C5.1 FOR THE INLET ON 28TH ST | | | SHOULD INDICATE THE WEST SIDE (INSTEAD OF NORTH SIDE) | | | TO BE CORED FOR NEW STORM PIPE. | | | | | | 2. THE TOP OF THE INLET IN COMMENT #1 WILL NEED TO BE | | | CHANGED FROM A CURB INLET IF THE ON-STREET PARKING | | | EXTENDS AROUND DRAINAGE STRUCTURE. | | | | | | 3. CONFIRM THERE IS SUFFICIENT VERTICAL AND HORIZONTAL | | | CLEARANCE FOR A CAR DOOR TO BE OPENED NEXT TO THE CURB | | | WHEN PARKED IN THE PROPOSED ON-STREET PARKING SPACES ON | | | 27TH ST AND 28TH ST. | | | | | | 4. CAN THE STEPS AND WALL BE MOVED OUT OF THE | | | RIGHT-OF-WAY? | | | | | | 5. SECTIONS A AND B ON SHEET C5.2 LIST "PROPOSED LOT | | | LINE". ARE THE LINES THE EXISTING RIGHT-OF-WAY/PROPERTY | | | LINES? | | | | | | 6. SECTIONS A AND B ON SHEET C5.2 INDICATE THE PARKING | | | SPACES WIL BE ASPHALT. PLAN VIEW SHOWS CONCRETE | | | HATCHING. | | | | | | 7. MILL AND RESURFACE LIMITS ARE MINIMUM 100 FEET IN | | | LENGTH (SEE NOTE #1 ON STANDARD DETAIL P-4). | | | | | | 8. HANDRAILS FOR STEPS APPEAR TO ENCROACH INTO THE | | | SIDEWALK AREA. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-20-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-20-2019 |
Time |
13:40 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-20-2019 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2019-05-20 13:44:27 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | 4/5/2019 PACKAGE: | | | | | | 1. ONLY USE RCP FOR DRAINAGE PIPE WITHIN PUBLIC | | | RIGHT-OF-WAY. | | | | | | 2. ADD VERTICAL DATUM REFERENCE AND CONVERSION EQUATION | | | TO NGVD1929 TO SHEET C7.1. | | | | | | 3. PROVIDE CROSS SECTIONS FOR 27TH AND 28TH STREETS | | | SHOWING THE STEPS AND PROPOSED SLOPE OF THE PAVEMENT | | | AND SIDEWALK. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
12-11-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-11-2018 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
12-12-2018 |
Time |
12:34 |
Sent To |
|
|
| Notes |
| 2018-12-11 08:22:02 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. LIST THE VERTICAL DATUM ON THE ENGINEERING PLANS. | | | THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION | | | EQUATION TO NGVD 1929 IS PROVIDED. | | | | | | 2. THE NAVD1988 / NGVD1929 CONVERSION EQUATION IS | | | NEEDED ON THE SURVEY. | | | | | | 3. BROADWAY AVE. IS MAINTAINED BY FDOT. PERMITS WILL BE | | | NEEDED FROM FDOT ANY WORK IN THE BROADWAY AVE. | | | RIGHT-OF-WAY. | | | | | | 4. ON THE SWPPP, SHOW PROTECTION FOR THE INLET ON | | | BROADWAY BLVD. | | | | | | 5. SHOW THE MILL AND RESURFACING LIMITS OF CWPB RIGHTS | | | OF WAY. SEE CWPB?S STANDARD DETAIL GC-9 TO DETERMINE | | | THE LIMITS. | | | | | | 6. SIDEWALK EASEMENTS MAY BE NEEDED FOR SIDEWALKS ALONG | | | 27TH ST. AND 28TH ST. | | | | | | 7. SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | 8. SHOW ROOT BARRIERS NEXT TO UTILITY PIPES. | | | | | | 9. SUGGEST REDUCING IMPERVIOUS AREA AND USING PERVIOUS | | | PAVERS AROUND PERIMETER OF SITE TO REDUCE THE AMOUNT OF | | | RUNOFF FLOWING UNCONTROLLED INTO THE PUBLIC | | | RIGHTS-OF-WAY. | | | | | | 10. VERIFY A FDOT TYPE ?V? INLET TOP WILL FIT ON | | | STRUCTURES DS-28 AND DS-29. | | | | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP APPROVAL PRIOR TO | | | STARTING CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
12-11-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
12-11-2018 |
Time |
14:19 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-12-11 14:19:00 | 1. NEED SIGNED AND SEALED SURVEY. REPLAT WILL ALSO BE | | | REQUIRED. | | | 2. ABANDONMENT OF ALLEY WILL CREATE A DEAD-END ALLEY | | | WHICH IS NOT ALLOWED. AN ACCESSIBLE ROUTE AND EASEMENT | | | THRU PARKING LOT TO AN ADJACENT STREET WILL BE | | | REQUIRED. | | | 3, UTILITY DEPT. IS LOOKING INTO POSSIBLE ABANDONMENT | | | OF WATER AND SEWER IN ALLEY. | | | 4. AS THERE ARE 2 DIFFERENT OWNERS, TIMING WILL NEED TO | | | BE DISCUSSED. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
4 |
Status |
P |
Date |
08-12-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-12-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-08-12 12:55:14 | NO FURTHER COMMENTS. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
11-01-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-11-01 10:49:55 | SITE PLAN COMMENTS: | | | 1. COORDINATE WITH FDOT ON A MAINTENANCE AGREEMENT FOR | | | THE USE OF PAVERS WITHIN FDOT RIGHT-OF-WAY. (THIS | | | COMMENT WILL BE PART OF THE CONDITIONS OF APPROVAL) | | | 2. PROVIDE A BUS STOP EASEMENT OF 14 FEET BY 8 FEET | | | WITHIN THE PROPERTY RIGHT-OF-WAY AT THE NORTHEAST | | | CORNER OF THE SITE. | | | 3. PROVIDE AUTOTURN PATHS FOR SERVICE VEHICLES TURNING | | | IN AND OUT OF THE ALLEY, AND SHOW THAT A DELIVER | | | VEHICLE PARKING IN THE LOADING ZONE WOULD NOT IMPEDE | | | VEHICLE MANEUVERS. | | | 4. MAINTAIN THE SAME SIDEWALK LEVEL CROSS THE DRIVEWAYS | | | ON BOTH 27TH STREET AND 28TH STREET. | | | 5. REPAVE BOTH SIDES OF 27TH STREET AND 28TH STREET AND | | | FOR 50 FEET FROM EITHER SIDE OF THE UTILITY TIE IN PER | | | ENGINEERING STANDARD. | | | 6. RECONSTRUCT THE CROSSWALKS ACROSS 27TH STREET AND | | | 28TH STREET AT BROADWAY DUE TO CURB RECONSTRUCTION. | | | | | | | | | TRAFFIC STUDY COMMENTS: | | | 7. (PREVIOUS COMMENT) PROVIDE COUNTY TPS LETTER. | | | 8. (PREVIOUS COMMENT) TABLES 2 AND 5: SOME OF THE | | | OPERATIONAL ANALYSIS RESULTS DO NOT MATCH THE RESULTS | | | IN THE SYNCHRO OUTPUTS. PLEASE REVISE. | | | 9. PLEASE INCLUDE SYNCHRO OUTPUTS FOR THE FUTURE | | | CONDITIONS WITH PROJECT TRAFFIC. APPENDICES D AND E ARE | | | MISSING. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
04-10-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-04-10 11:14:07 | SITE PLAN COMMENTS: | | | | | | 1. (PREVIOUS COMMENT) CLARIFY THE PROPOSED LAND USES. | | | THE SITE PLAN (C4.1) INDICATES 52 RESIDENTIAL UNITS | | | WITH 1,920 SF OF COMMERCIAL USES, WHILE THE TRAFFIC | | | STUDY INDICATES 52 RESIDENTIAL UNITS WITH 1,000 SF OF | | | RETAIL AND 1,000 SF OF SHARED WORK SPACE. | | | 2. (PREVIOUS COMMENT) PARALLEL PARKING 27TH AND 28TH. | | | PLACE TREE OPENING IN THE MIDDLE OF THE SPACE, NOT AT | | | THE ENDS OF THE PARKING SPACE. PROVIDE A 16 TO 18 INCH | | | WALKING BAND BETWEEN THE FACE OF CURB AND TREE PIT. THE | | | WALKING BAND CAN INCLUDE THE TOP OF THE CURB. | | | 3. COMMIT TO PROVIDE A TRANSIT SHELTER ONCE THE LANE | | | ELIMINATION PROJECT ON BROADWAY IS APPROVED. | | | 4. IF THE REQUIRED LOADING SPACE IS NOT PROVIDED PER | | | CITY CODE 94-485, PLEASE INCLUDE A WAIVER REQUEST. | | | 5. REDUCE THE TRAVEL LANES ON 27TH AND 28TH STREETS TO | | | 10 FEET. THE EXTRA WIDTH CAN BE ADDED TO THE SIDEWALK. | | | ALSO, PROVIDE CROSS-SECTIONS ON 27TH AND 28TH STREETS. | | | 6. SOME OF THE PARKING AREA LIGHT POLES MAY BE IN | | | CONFLICT WITH THE 2-FOOT PARKING OVERHANG ZONE. PLEASE | | | REVISE. ALSO, VERIFY THE TREES PLANTED ON THE BUFFER | | | ARE NOT IN CONFLICT WITH THE 2-FOOT PARKING OVERHANG | | | ZONE. | | | 7. VERIFY THE TREES AT THE DRIVEWAY ON 27TH STREET AND | | | 28TH STREET WOULD NOT OBSTRUCT VISIBILITY OF EGRESS | | | VEHICLES. | | | 8. SHOW THE SIGHT DISTANCE FOR EASTBOUND ON | | | BROADWAY/27TH STREET AND BROADWAY/28TH STREET PER FDOT | | | REQUIREMENTS. | | | 9. BROADWAY IS ON THE EAST COAST GREENWAY. SHIFT | | | BUILDING H TOWARDS THE WEST TO PROVIDE AN UNOBSTRUCTED | | | PATH OF 10 FEET ON BROADWAY. | | | 10. COORDINATE WITH FDOT ON A MAINTENANCE AGREEMENT FOR | | | THE LANDSCAPE WITHIN FDOT RIGHT-OF-WAY. (THIS COMMENT | | | WILL BE PART OF THE CONDITIONS OF APPROVAL) | | | | | | TRAFFIC STUDY COMMENTS: | | | | | | 11. (PREVIOUS COMMENT) PROVIDE COUNTY TPS LETTER. | | | 12. (PREVIOUS COMMENT) PAGE 3, METHODOLOGY, CORRECT THE | | | TYPO OF "CITY OF PALM BEACH" AND "WEST PALM BEACH | | | COUNTY" TO "CITY OF WEST PALM BEACH" AND "PALM BEACH | | | COUNTY". | | | 13. TABLES 2 AND 5, SOME OF THE OPERATIONAL ANALYSIS | | | RESULTS DO NOT MATCH THE RESULTS IN THE SYNCHRO | | | OUTPUTS. PLEASE REVISE. | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] | | | (IN-HOUSE ON TUESDAYS AND WEDNESDAYS) |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
12-10-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-12-10 09:46:30 | Z18110018_ARTS ON BROADWAY (DATED NOVEMBER 13, 2018) | | | COMMENTS: | | | | | | SITE PLAN | | | 1. CLARIFY THE PROPOSED LAND USES. THE SITE PLAN (C4.1) | | | INDICATES 52 RESIDENTIAL UNITS WITH 1,920 SF OF | | | COMMERCIAL USES, WHILE THE TRAFFIC STUDY INDICATES 52 | | | RESIDENTIAL UNITS WITH 1,000 SF OF RETAIL AND 1,000 SF | | | OF SHARED WORK SPACE. | | | 2. ONE INTERIOR LANDSCAPE ISLAND IS REQUIRED FOR EVERY | | | TEN PARKING SPACES IN A ROW PER CITY CODE 94-443. | | | PLEASE REVISE. | | | 3. ONE LOADING SPACE IS REQUIRED FOR COMMERCIAL USES OF | | | 1,920 SF PER CITY CODE 94-485. PLEASE REVISE. | | | 4. THE DISABLED PARKING SPACES DO NOT MEET THE CITY'S | | | DIMENSION REQUIREMENT OF 12 FEET X 18 FEET. IF A | | | TWO-FOOT OVERHANG ON THE PEDESTRIAN PATHWAY IS USED FOR | | | PARKING, PLEASE REMOVE THE WHEEL STOP AND ADJUST THE | | | SIGN LOCATION. | | | 5. PROVIDE A MINIMUM OF AN 8 FEET WIDE SIDEWALK IN AN | | | EASEMENT ALONG BROADWAY. | | | 6. A SECTION OF THE SIDEWALK ALONG 28TH STREET APPEARS | | | TO BE LESS THAN CITY?S MINIMUM REQUIREMENT OF 5 FEET. | | | PLEASE VERIFY AND REVISE. | | | 7. PROVIDE SIDEWALK EASEMENT FOR THE PORTION OF | | | SIDEWALK WITHIN PRIVATE RIGHT-OF-WAY. | | | 8. COORDINATE WITH FDOT ON A MAINTENANCE AGREEMENT FOR | | | THE LANDSCAPE WITHIN FDOT RIGHT-OF-WAY. REVISED | | | 12/12/18 - CITY WILL HAVE TO ENTER INTO AGREEMENT WITH | | | FDOT, APPLICANT WILL ENTER INTO AGREEMENT WITH CITY. | | | 9. SHOW THE 20-FOOT VISIBILITY TRIANGLE REQUIRED PER | | | CITY CODE 94-305. | | | 10. 27TH AND 28TH STREETS. THE TRAVEL LANE AND | | | ON-STREET PARALLEL PARKING SPACE CAN BE REDUCED TO 10' | | | AND 8' RESPECTIVELY. THE VALLEY GUTTER CAN BE COUNTED | | | AS PART OF THE PARALLEL PARKING SPACE. | | | 11. CONSIDER PARALLEL PARKING ON BROADWAY. THE PARKED | | | CARS WOULD PROVIDE A BUFFER TO THE SITE. | | | 12. LABEL MATERIAL LOCATED AT BACK OF CURB ALONG | | | BROADWAY. IS THIS AREA LANDSCAPED OR HARDSCAPED? | | | 13. END PARALLEL PARKING SPACES CAN BE REDUCED TO 20' | | | LENGTH. | | | 13B. COORDINATE WITH PALM TRAN FOR A POTENTIAL TRANSIT | | | SHELTER LOCATION. | | | 13C. PARALLEL PARKING 27TH AND 28TH. PLACE TREE OPENING | | | IN THE MIDDLE OF THE SPACE, NOT AT THE ENDS OF THE | | | PARKING SPACE. PROVIDE A 16 TO 18 INCH WALKING BAND | | | BETWEEN THE FACE OF CURB AND TREE PIT. THE WALKING BAND | | | CAN INCLUDE THE TOP OF THE CURB. (ADDED ON 12/13/18) | | | | | | TRAFFIC STUDY | | | 14. PROVIDE COUNTY TPS LETTER. | | | 15. TABLE 1: 25TH STREET WEST OF US 1 IS NOT A STATE | | | ROAD. LOS D SERVICE VOLUME THRESHOLD NEEDS TO BE | | | ADJUSTED FOR NON-STATE FACILITIES. | | | 16. INTERNAL TRIPS BETWEEN RESIDENTIAL USES AND RETAIL, | | | AND PASS-BY TRIPS FOR RETAIL SHOULD BE CONSIDERED IN | | | THE TRIP GENERATION. | | | 17. IF THE TRIPS ARE CALCULATED BASED ON THE EQUATION, | | | PLEASE INDICATE SO AND INCLUDE THE EQUATION BUT NOT THE | | | TRIP RATE IN TABLE 3. | | | 18. THE SITE DRIVEWAYS ARE ON 27TH STREET AND 28TH | | | STREET BUT FIGURE 5 SHOWS THE DRIVEWAY ON BROADWAY. | | | PLEASE REVISE THE TRIP ASSIGNMENT AROUND SITE | | | DRIVEWAYS. | | | 19. LANE CONFIGURATIONS FOR THE EASTBOUND APPROACH AT | | | BROADWAY/25TH STREET IS NOT CORRECT. PLEASE REVISE. | | | 20. PAGE 3 - METHODOLOGY- CORRECT TO CITY OF WEST PALM | | | BEACH AND PALM BEACH COUNTY, NOT CITY OF PALM BEACH AND | | | COUNTY OF WEST PALM BEACH. | | | | | | | | | ERIK D. FERGUSON, P.E. | | | CITY TRANSPORTATION ENGINEER | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
08-18-2020 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
08-18-2020 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
awooten |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2020-08-18 12:20:06 | CASE NUMBER: FSPR18?06 ? FORMAL SITE PLAN REVIEW | | | PROJECT NAME: 2823 BROADWAY | | | ZONING CONTACTS: ALANA WOOTEN | | | 561? 822?1449 | | | [email protected] | | | | | | PROCESS COMMENTS | | | ? PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | ? PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. THE APPLICANT WILL | | | BE ACCESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF | | | THE ORIGINAL APPLICATION FEE ($469.60). | | | | | | - PLEASE PROVIDE RESUBMITTAL FEE OF $469.60 TO THE CITY | | | (20% OF THE ORIGINAL APPLICATION FEE). | | | | | | COMMENTS | | | | | | ??REPLAT (MAJOR SUBDIVISION) REQUIRED PRIOR TO ISSUANCE | | | OF CO | | | | | | ??FDOT APPROVAL IS REQUIRED FOR ALL BROADWAY AVENUE | | | RIGHT?OF? WAY APPROVALS, REQUIRED AS A PART OF REPLAT | | | APPLICATION. | | | | | | ??WPB ENGINEERING ROW APPROVAL REQUIRED FOR ALL 27TH | | | AND 28TH STREET APPROVALS, REQUIRED AS A PART OF REPLAT | | | APPLICATION. | | | | | | ??MAINTENANCE AGREEMENTS MAY BE REQUIRED FOR ROW | | | IMPROVEMENTS AND LANDSCAPE, REQUIRED AS A PART OF | | | REPLAT APPLICATION. | | | | | | ??ALL REQUIRED ACCESS AND UTILITY EASEMENTS MUST | | | RECORDED PRIOR TO ISSUANCE FOR CO, REQUIRED AS A PART | | | OF REPLAT APPLICATION. | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
11-05-2019 |
|
|
Cont ID |
|
| Sent By |
|
Date |
11-05-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-05-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-11-05 15:03:11 | CASE NUMBER:FSPR18-06- FORMAL SITE PLAN REVIEW | | | PROJECT NAME: 2823 BROADWAY | | | | | | ZONING CONTACTS: HEATHER DANFORTH | | | 561- 822-1562 | | | [email protected] | | | | | | PROCESS COMMENTS | | | | | | - PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF EIGHT | | | (8) FULL SIZE PRINT COPIES AND ALL FILES ELECTRONIC IN | | | PDF FORMAT. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THESE COMMENTS (BY JANUARY 6, 2020), | | | THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER | | | ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. THE APPLICANT WILL | | | BE ACCESSED A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF | | | THE ORIGINAL APPLICATION FEE ($469.60). | | | | | | | | | COMMENTS | | | | | | --PROVIDE PALM BEACH COUNTY TPS APPROVAL. | | | | | | --REPLAT (MAJOR SUBDIVISION) REQUIRED PRIOR TO ISSUANCE | | | OF CO | | | | | | --UNIQUE ADDRESSING WILL BE ASSIGNED FOR THE PRIMARY | | | ADDRESS FOR PROJECT. CONTACT MICHAEL ORIO BEFORE PERMIT | | | SUBMITTAL AT 561.494.1080 [email protected] | | | | | | --FDOT APPROVAL IS REQUIRED FOR ALL BROADWAY AVENUE | | | RIGHT-OF- WAY APPROVALS | | | | | | --WPB ENGINEERING ROW APPROVAL REQUIRED FOR ALL 27TH | | | AND 28TH STREET APPROVALS. | | | | | | --MAINTENANCE AGREEMENTS MAY BE REQUIRED FOR ROW | | | IMPROVEMENTS AND LANDSCAPE. | | | | | | --ALL REQUIRED ACCESS AND UTILITY EASEMENTS MUST | | | RECORDED PRIOR TO ISSUANCE FOR CO | | | | | | --ALL MURALS, DESIGNS AND PRINTED GRAPHICS VISIBLE FROM | | | THE PUBLIC FROM THE ROW SHALL BE REQUIRED TO BE | | | APPROVED THROUGH THE ART AND PUBLIC PLACES COMMITTEE. | | | | | | --MURALS, DESIGNS AND PRINTED GRAPHICS ON THE BUILDINGS | | | ARE INTENDED TO MEET 94-220(D) AND NOT THE AIPP | | | REQUIREMENT, PROVIDE LOCATIONS WITH DIMENSIONS OF EACH | | | THAT WILL BE PROVIDED WITH FOR EACH TYPE. | | | | | | --UPDATE SITE DATA TO REFERENCE COMMENTS IN TPS LETTER | | | AND LABEL LOCATIONS OF EACH USE COMMERCIAL USE TYPE. | | | | | | --PROVIDE ADA ACCESSIBLE ROUTE TO PUBLIC SPACE. | | | | | | --CORRECT SIDEWALK EASEMENT LOCATIONS TO MATCH PLANS. | | | | | | --ADDRESS THE MONITORING WELL. | | | | | | --PROVIDE DOCUMENTATION THAT PANEL FA?ADE SYSTEM AND | | | TEXTILE FA?ADE SYSTEM MEETING FIRE AND BUILDING CODE | | | REQUIREMENTS. | | | | | | --MAINTENANCE BUILDINGS DO NOT MEET ZONING CODE | | | ARCHITECTURAL REQUIREMENTS. | | | | | | --SHEET C4.1 AND L3- CLARIFY REAR FENCE START AND STOP | | | LOCATIONS | | | | | | --SHEET C4.1: NOTE 7. ARE BOTH OF THE CENTER COMMERCIAL | | | BUILDINGS SUPPOSED TO ENTER ONTO THE COURT? | | | | | | --IT APPEARS THAT THE STAIRWELLS ON THE CORNERS OF | | | BROADWAY AND 27TH AND 28TH APPEAR TO BE IN THE SIGHT | | | TRIANGLE AND THE HANDRAILS APPEAR TO ENCROACH INTO THE | | | SIDEWALK. | | | | | | --PROVIDE FPL UTILITY APPROVAL LETTER. | | | | | | --PROVIDE APPROVAL OF TREES ALLOWED IN UTILITY | | | EASEMENT. | | | | | | --TREES SHOULD BE PLANTED IN ALL LANDSCAPE ISLANDS | | | FRONTING BROADWAY FOR CONTINUITY. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
07-25-2019 |
|
|
Cont ID |
|
| Sent By |
pgreilic |
Date |
07-25-2019 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
07-25-2019 |
Time |
09:46 |
Sent To |
|
|
| Notes |
| 2019-07-25 09:46:39 | 1.) ALL MURALS VISIBLE TO THE PUBLIC FROM THE ROW SHALL | | | BE REQUIRED TO BE APPROVED THROUGH THE ART IN PUBLIC | | | PLACES COMMITTEE | | | 2.) MURALS ON THE BUILDINGS ARE INTENDED TO MEET | | | 94-220(D) AND NOT THE AIPP REQUIREMENT, WHICH IS TO BE | | | FULFILLED AT BUILDING PERMIT | | | 3.) A REPLAT IS REQUIRED PRIOR TO ISSUANCE OF FINAL | | | CERTIFICATE OF OCCUPANCY | | | 4.) PROVIDE ANY MISSING LETTERS FROM ALL OF THE | | | FOLLOWING PUBLIC UTILITIES CONFIRMING THAT THE PROPOSED | | | PROJECT DOES NOT ENCROACH INTO THEIR EASEMENTS OR | | | OTHERWISE INTERFERE WITH THE PROVISIONS OF THE SERVICES | | | AT&T, FPU, FPL, AND COMCAST | | | 5.) MAINTENANCE AGREEMENTS MAY BE REQUIRED FOR ROW | | | IMPROVEMENTS AND LANDSCAPE | | | 6.) PLEASE PROVIDE CITY STANDARD DETAILS FOR PARKING | | | SPACES AND BIKE RACKS | | | | | | PAUL GREILICH, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
|
Date |
12-11-2018 |
|
|
Cont ID |
|
| Sent By |
hmtribou |
Date |
12-11-2018 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
hmtribou |
Date |
12-11-2018 |
Time |
16:36 |
Sent To |
|
|
| Notes |
| 2018-12-11 16:37:05 | CASE NUMBER:FSPR18-06- FORMAL SITE PLAN REVIEW | | | PROJECT NAME: 2823 BROADWAY | | | | | | ZONING CONTACTS: HEATHER M. TRIBOU & PAUL GREILICH | | | 561- 822-1562 & 561-822-1443 | | | [email protected] & [email protected] | | | | | | PROCESS COMMENTS | | | | | | - PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN | | | (11) FULL SIZE PRINT COPIES AND ALL FILES ELECTRONIC IN | | | PDF FORMAT. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY | | | FEBRUARY 11, 2019), THE CASE SHALL BE CONSIDERED | | | WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW | | | DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | | | | | | | COMMENTS | | | | | | | | | --PROVIDE PALM BEACH COUNTY TPS APPROVAL. | | | | | | --REQUEST WILL REQUIRE SUBMITTAL OF A ZONING BOARD OF | | | APPEALS APPLICATION FOR APPROVAL OF REQUESTED | | | VARIANCES, ADDRESSING EACH VARIANCES STANDARD OUTLINED | | | IN SECTION 94-38(D)(6) OF ZLDR. | | | | | | --ALLEY ABANDONMENT REQUIRED FOR SITE PLAN APPROVAL | | | | | | --REPLAT (MAJOR SUBDIVISION) REQUIRED PRIOR TO ISSUANCE | | | OF CO | | | | | | --UNIQUE ADDRESSING WILL BE ASSIGNED FOR THE PRIMARY | | | ADDRESS FOR PROJECT. CONTACT MICHAEL ORIO BEFORE PERMIT | | | SUBMITTAL AT 561.494.1080 [email protected] | | | | | | --FDOT APPROVAL IS REQUIRED FOR ALL BROADWAY AVENUE | | | RIGHT-OF- WAY APPROVALS | | | | | | --WPB ENGINEERING ROW APPROVAL REQUIRED FOR ALL 27TH | | | AND 28TH STREET APPROVALS. | | | | | | --MAINTENANCE AGREEMENTS MAY BE REQUIRED FOR ROW | | | IMPROVEMENTS AND LANDSCAPE. | | | | | | --ALL REQUIRED ACCESS AND UTILITY EASEMENTS MUST | | | RECORDED PRIOR TO ISSUANCE FOR CO | | | | | | --ALL MURALS VISIBLE TO THE PUBLIC FROM THE ROW SHALL | | | BE REQUIRED TO BE APPROVED THROUGH THE ART AND PUBLIC | | | PLACES COMMITTEE. | | | | | | --MURALS ON THE BUILDINGS ARE INTENDED TO MEET | | | 94-220(D) AND NOT THE AIPP REQUIREMENT, WHICH IS TO BE | | | FULFILLED AT BUILDING PERMIT. | | | | | | -MEET MINIMUM GLAZING REQUIREMENT OF 25% CLEAR GLAZED | | | AREA OR OPENING ON THE REAR FACADES PER SECTION 94-220 | | | (5) | | | | | | --APPLICANT SHOULD CONSIDER THE INCLUSION OF SKYBIKE | | | KIOSK | | | | | | --SHEET C4.1- IS THERE A PROPOSED FENCE LOCATED AT REAR | | | PROPERTY LINE, PLEASE LABEL ANY FENCES AND REFERENCE OR | | | PROVIDE DETAIL. IS THIS THE DETAIL ON L6? | | | | | | --SHEET C4.1-IDENTIFY LOCATIONS OF STUCCO WALL AND | | | GATES ON A0.01. | | | | | | --SHEET C4.1- FUTURE LAND USE IS MIXED USE, PLEASE | | | UPDATE SITE DATA | | | | | | --SHEET C4.1- PROVIDE NUMBER OF RESIDENTIAL UNITS AND | | | SQUARE FOOTAGE OF COMMERCIAL USES. PLEASE NOTE THAT | | | ALLOWABLE USES ARE LISTED UNDER OFFICE COMMERCIAL | | | ZONING (OC) PERMITTED USES. | | | | | | --SHEET C4.1- PARKING LAYOUT WILL NEED TO BE ADJUSTED | | | TO PROVIDE ACCESS TO THE ALLEY AND MEET LANDSCAPE | | | ISLAND REQUIREMENTS. | | | | | | --SHEET C4.1- LABEL LOCATION OF DOORS ON COMMERCIAL | | | BUILDINGS TO MEET SECTION 94-220(4) | | | | | | --SHEET C4.1- LABEL ENTIRE DEPTH OF SIDEWALK ALONG | | | BROADWAY AVENUE. | | | | | | --SHEET C4.1- PROVIDE LIGHTING AND FURNISHINGS | | | LOCATIONS | | | | | | --PROVIDE LOCATION OF ANY SIGNAGE SEC. 94-220 (E) | | | | | | --PROVIDE DETAILS FOR ALL PARKING SPACES TYPES AND | | | DUMPSTER TO MEET CITY OF WEST PALM BEACH STANDARDS. | | | | | | --SHEET L3- PROVIDE LOCATIONS OF ALL WALL AND FENCES | | | AND GATES. | | | | | | --SHEET L3- PROVIDE LOCATIONS OF FPL POLES AND LINES. | | | | | | --SHEET L4- PROVIDE ROOT BARRIER DETAIL | | | | | | --L7- DETAIL FURNISHINGS TO BE LOCATED ALONG BROADWAY | | | AVENUE. | | | | | | --A0.01-PROVIDE OVERALL BUILDING HEIGHTS | | | | | | --A0.01- PROVIDE AWNING DETAILS | | | | | | --A0.01-PROVIDE LOCATION AND DIMENSIONS OF ANY SIGNAGE | | | | | | --A0.01- PROVIDE FURTHER CLARIFICATION ON VARIANCES NOT | | | RELATED TO CONSTRUCTION TYPE. | | | | | | --A0.01- PROVIDE MORE INFORMATION ON FRAMING OR DETAIL | | | OF TEXTILE FA?ADE SYSTEM. | | | | | | --A0.10 AND A1.01- PROVIDE FURTHER CLARIFICATION ON | | | FOOT PRINT OF BUILDINGS OF O A1.01 AND HOW THEY RELATE | | | TO A0.10 FOR UNIT COUNTS | | | | | | --A1.02 & A1.030- LABEL ALL USABLE AND UNUSABLE OUTDOOR | | | PUBLIC AND PRIVATE SPACE. | | | | | | --PROVIDE MISSING LETTERS FROM ALL OF THE FOLLOWING | | | PUBLIC UTILITIES CONFIRMING THAT THE PROPOSED PROJECT | | | DOES NOT ENCROACH INTO THEIR EASEMENTS OR OTHERWISE | | | INTERFERE WITH THE PROVISIONS OF THEIR SERVICES: AT&T, | | | FPU, FPL, AND COMCAST. | | | | | | |
|
|
| |