Plan Review Details - Project Z18110014
Plan Review Stops For Project Z18110014
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-11-2018 Cont ID  
Sent By rbrown Date 12-11-2018 Time 18:51 Rev Time 0.00
Received By rbrown Date 12-11-2018 Time 18:51 Sent To  
Notes
2018-12-11 18:55:38DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 01-29-2019 Cont ID  
Sent By RRossano Date 01-29-2019 Time   Rev Time 0.00
Received By rrossano Date 01-29-2019 Time   Sent To  
Notes
2019-01-29 11:48:00PASSED WITH PROVISO:
  
 SHOW CALCULATIONS OF EXISTING AND PROPOSED DEMANDS FOR
 WATER & SEWER (AVERAGE, MAXIMUM & PEAK) ON SHEET C-600
 OF PLANS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER
 AND PER FAC 64-E.008 FOR WATER.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-06-2018 Cont ID  
Sent By RRossano Date 12-06-2018 Time   Rev Time  
Received By rrossano Date 12-06-2018 Time   Sent To I
Notes
2018-12-06 12:26:34PROVIDE CALCULATIONS OF EXISTING AND PROPOSED DEMANDS
 FOR WATER & SEWER (AVERAGE, MAXIMUM AND PEAK) AND FIRE
 FLOW DEMANDS. CALCULATIONS SHALL BE PER FAC 64E-6 FOR
 SEWER AND PER FAC 64-E.008 FOR WATER.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-04-2018 Cont ID  
Sent By pleduc Date 12-04-2018 Time   Rev Time 0.00
Received By pleduc Date 12-04-2018 Time 13:31 Sent To  
Notes
2018-12-04 13:51:25THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES. IT IS HIGHLY RECOMMENDED
 THAT ANY CONSTRUCTION GATES BE PROVIDED WITH KNOX
 PADLOCKS FOR 24 HR FIRE DEPARTMENT ACCESS IF NEEDED AND
 ALSO PROVIDE YOU SITE SECURITY AFTER AN INCIDENT.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE.
  
 NFPA 101, CHAPTER 12, NEW ASSEMBLY OCCUPANCY SHALL
 APPLY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 IT APPEARS THERE IS AN EXISTING FH AT THE PARKING AREA
 ENTRANCE AND THAT A FS SYSTEM WILL BE PROVIDED, THE FDC
 LOCATION IS NOT CLEAR BUT SHALL BE WITHIN 150' OF THE
 FH.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 THERE DOES NOT APPEAR TO BE A FIRE LANE INDICATED ON
 THE SITE PLAN. THE FIRE LANE IS WHERE THE FIRE
 APPARATUS STAGES IN AN EMERGENCY AND MAY BE LOCATED AT
 THE FDC AND/OR BUIDLING ACCESS POINTS. THE FIRE LANE
 SHALL LOCATION SHALL BE COORDINATED WITH THE OFFICE OF
 THE FIRE MARSHAL.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 03-05-2019 Cont ID  
Sent By rcaranci Date 03-05-2019 Time 14:36 Rev Time 0.00
Received By rcaranci Date 03-05-2019 Time 14:36 Sent To  
Notes
2019-03-05 14:37:23FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PB OUTLETS BLDG M Z18110014
 MARCH 5, 2019
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A TREE PROTECTION PLAN TO SHOW
 LOCATIONS OF BARRIERS AND ROOT ZONE PROTECTION AREAS
 FOR THE EXISTING TREES. ADD A DETAIL FOR BARRIERS.
  
 2. SATISFIED. PROVIDE A PLAN SHOWING THE AREAS CLAIMED
 FOR COMPLIANCE WITH PARKING LOT LANDSCAPE AREA
 REQUIREMENTS AND OTHER VEHICULAR USE AREA REQUIREMENTS
 SECTIONS. THIS AREA CAN BE INCREASED AND THE IMPACT OF
 THE CONSTRUCTION ON THE ROOT SPACE OF EXISTING TREES
 DECREASED BY PROVIDING ONE CURB AT THE FRONT OF ALL
 PARKING SPACES INSTEAD OF CURB AND WHEEL STOPS.
 THE AREAS TO BE COUNTED ARE NOT WHAT IS ELIGIBLE BY
 CODE. AREAS WITHIN THE PARKING LIMITS INCLUDING
 OVERHANG AREAS NEED TO BE QUANTIFIED.
  
 3. SATISFIED. PROVIDE A DETAIL OF THE LOCATION OF THE
 ACCESSIBLE SIDEWALK CONNECTION TO CONGRESS AVE. TO SHOW
 HOW IT WILL AVOID DAMAGING THE ROOT SYSTEMS OF THE
 EXISTING TREES.
  
 4. SATISFIED. THE PERGOLA FOR THE OUTDOOR DINING AREA
 SHOULD BE SHIFTED CLOSER TO THE BUILDING AND A HEDGE
 ADDED TO SEPARATE IT FROM THE DRIVE THROUGH TRAVEL
 LANE.
  
 5. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
 6. SATISFIED. SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE SECTION 94-446 (G). PROVIDE AN UPDATED CHART
 AND PROVIDE 50 POINTS FOR THE AFFECTED AREA.
  
 7. SATISFIED. THERE ARE OPPORTUNITIES TO ADD SMALL
 TREES OR PALMS IN THE SOUTHWEST BUFFER STRIP.
  
 8. SATISFIED. 75% OF THE REQUIRED PARKING AREA TREES
 MUST BE SHADE TREES TO PROVIDE SHADE FOR PARKING AND
 MINIMIZE HEAT ISLAND EFFECTS. SHOW HOW THIS REQUIREMENT
 IS MET.
 TREES WITHIN THE PARKING FIELD MATCHING COMMENT #2 NEED
 TO BE USED AS THE BASE, THEN 75% CALCULATED.
 ADDITIONAL COMMENTS 2/12/19:
 9. SATISFIED. PROVIDE SCREENING OF ABOVE GROUND
 UTILITIES.
  
 10. SATISFIED. THE TERMINAL LANDSCAPE ISLAND ADJACENT
 TO THE STORAGE ATTACHED TO THE DUMPSTER ENCLOSURE DOES
 NOT MEET CODE REQUIREMENT OF BEING THE FULL LENGTH OF
 THE PARKING SPACE.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 02-12-2019 Cont ID  
Sent By rcaranci Date 02-12-2019 Time 17:12 Rev Time 0.00
Received By rcaranci Date 02-12-2019 Time 17:12 Sent To  
Notes
2019-02-12 17:12:58FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PB OUTLETS BLDG M Z18110014
 FEBRUARY 8, 2019
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A TREE PROTECTION PLAN TO SHOW
 LOCATIONS OF BARRIERS AND ROOT ZONE PROTECTION AREAS
 FOR THE EXISTING TREES. ADD A DETAIL FOR BARRIERS.
  
 2. PARTIALLY SATISFIED. PROVIDE A PLAN SHOWING THE
 AREAS CLAIMED FOR COMPLIANCE WITH PARKING LOT LANDSCAPE
 AREA REQUIREMENTS AND OTHER VEHICULAR USE AREA
 REQUIREMENTS SECTIONS. THIS AREA CAN BE INCREASED AND
 THE IMPACT OF THE CONSTRUCTION ON THE ROOT SPACE OF
 EXISTING TREES DECREASED BY PROVIDING ONE CURB AT THE
 FRONT OF ALL PARKING SPACES INSTEAD OF CURB AND WHEEL
 STOPS.
 THE AREAS TO BE COUNTED ARE NOT WHAT IS ELIGIBLE BY
 CODE. AREAS WITHIN THE PARKING LIMITS INCLUDING
 OVERHANG AREAS NEED TO BE QUANTIFIED.
  
 3. SATISFIED. PROVIDE A DETAIL OF THE LOCATION OF THE
 ACCESSIBLE SIDEWALK CONNECTION TO CONGRESS AVE. TO SHOW
 HOW IT WILL AVOID DAMAGING THE ROOT SYSTEMS OF THE
 EXISTING TREES.
  
 4. SATISFIED. THE PERGOLA FOR THE OUTDOOR DINING AREA
 SHOULD BE SHIFTED CLOSER TO THE BUILDING AND A HEDGE
 ADDED TO SEPARATE IT FROM THE DRIVE THROUGH TRAVEL
 LANE.
  
 5. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
 6. SATISFIED. SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE SECTION 94-446 (G). PROVIDE AN UPDATED CHART
 AND PROVIDE 50 POINTS FOR THE AFFECTED AREA.
  
 7. SATISFIED. THERE ARE OPPORTUNITIES TO ADD SMALL
 TREES OR PALMS IN THE SOUTHWEST BUFFER STRIP.
  
 8. PARTIALLY SATISFIED. 75% OF THE REQUIRED PARKING
 AREA TREES MUST BE SHADE TREES TO PROVIDE SHADE FOR
 PARKING AND MINIMIZE HEAT ISLAND EFFECTS. SHOW HOW THIS
 REQUIREMENT IS MET.
 TREES WITHIN THE PARKING FIELD MATCHING COMMENT #2 NEED
 TO BE USED AS THE BASE, THEN 75% CALCULATED.
 ADDITIONAL COMMENTS 2/12/19:
 9. PROVIDE SCREENING OF ABOVE GROUND UTILITIES.
  
 10. THE TERMINAL LANDSCAPE ISLAND ADJACENT TO THE
 STORAGE ATTACHED TO THE DUMPSTER ENCLOSURE DOES NOT
 MEET CODE REQUIREMENT OF BEING THE FULL LENGTH OF THE
 PARKING SPACE.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-10-2018 Cont ID  
Sent By rcaranci Date 12-10-2018 Time 10:55 Rev Time 0.00
Received By rcaranci Date 12-10-2018 Time 10:55 Sent To  
Notes
2018-12-10 10:55:46FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PB OUTLETS BLDG M Z18110014
 DECEMBER 7, 2018
 STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT
 REGULATIONS FOR THE ABOVE REFERENCED PETITION AND
 PROVIDES THE FOLLOWING COMMENTS:
  
 1. PROVIDE A TREE PROTECTION PLAN TO SHOW LOCATIONS OF
 BARRIERS AND ROOT ZONE PROTECTION AREAS FOR THE
 EXISTING TREES. ADD A DETAIL FOR BARRIERS.
  
 2. PROVIDE A PLAN SHOWING THE AREAS CLAIMED FOR
 COMPLIANCE WITH PARKING LOT LANDSCAPE AREA REQUIREMENTS
 AND OTHER VEHICULAR USE AREA REQUIREMENTS SECTIONS.
 THIS AREA CAN BE INCREASED AND THE IMPACT OF THE
 CONSTRUCTION ON THE ROOT SPACE OF EXISTING TREES
 DECREASED BY PROVIDING ONE CURB AT THE FRONT OF ALL
 PARKING SPACES INSTEAD OF CURB AND WHEEL STOPS.
  
 3. PROVIDE A DETAIL OF THE LOCATION OF THE ACCESSIBLE
 SIDEWALK CONNECTION TO CONGRESS AVE. TO SHOW HOW IT
 WILL AVOID DAMAGING THE ROOT SYSTEMS OF THE EXISTING
 TREES.
  
 4. THE PERGOLA FOR THE OUTDOOR DINING AREA SHOULD BE
 SHIFTED CLOSER TO THE BUILDING AND A HEDGE ADDED TO
 SEPARATE IT FROM THE DRIVE THROUGH TRAVEL LANE.
  
 5. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 6. SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY LANDSCAPE
 SECTION 94-446 (G). PROVIDE AN UPDATED CHART AND
 PROVIDE 50 POINTS FOR THE AFFECTED AREA.
  
 7. THERE ARE OPPORTUNITIES TO ADD SMALL TREES OR PALMS
 IN THE SOUTHWEST BUFFER STRIP.
  
 8. 75% OF THE REQUIRED PARKING AREA TREES MUST BE
 SHADE TREES TO PROVIDE SHADE FOR PARKING AND MINIMIZE
 HEAT ISLAND EFFECTS. SHOW HOW THIS REQUIREMENT IS MET.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 02-09-2019 Cont ID  
Sent By   Date 02-09-2019 Time   Rev Time  
Received By   Date 02-09-2019 Time   Sent To  
Notes
2019-02-09 19:12:41REDESIGN HAS PROVIDED ADEQUATE SPACE AND DEPTH.
2018-12-13 12:58:50DUMPSTER ENCLOSURE HAS BEEN DESIGNED FOR TWO DUMPSTERS
 BUT DOES NOT MEET THE DEPTH REQUIREMENTS PER STABDARD
 SPECIFCATIONS.

Review Stop STORM STORMWATER
Rev No 2 Status P Date 02-15-2019 Cont ID  
Sent By tward Date 02-15-2019 Time 11:02 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2019-02-15 11:05:56THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 JANUARY 24, 2019 SUBMITTAL PACKAGE:
  
 1. PROVIDE VERTICAL DATUM REFERNCE ON SHEETS WITH
 ELEVATION DATA (E.G. C-400, C-500).
  
 2. ON SHEET C-300, INCLUDE WRAPPING THE INLET OVER THE
 EAST 66" DRAINAGE PIPE.
  
 3. ON SHEET C-500, THE MANHOLE (NOT SHOWN) ON THE WEST
 66" DRAINAGE PIPE MAY HAVE TO BE ADJUSTED.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-11-2018 Cont ID  
Sent By tward Date 12-11-2018 Time 08:23 Rev Time 0.00
Received By tward Date 12-11-2018 Time 08:35 Sent To  
Notes
2018-12-11 08:35:38THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE SURVEY SHOULD SHOW THE DOUBLE RCP/CMP 66-INCH
 DIAMETER DRAINAGE PIPES IN THE CORRECT ALIGNMENT.
 CONTACT JANICE TARBILL (494-1079) IN THE ENGINEERING
 SERVICES DEPARTMENT FOR AN AS-BUILT DRAWING.
  
 2. STRUCTURE D-152 AND 18" CMP WAS REMOVED WHEN A
 PORTION OF THE DOUBLE 66 INCH CULVERTS WAS REPLACED.
  
 3. SHOW ON THE ENGINEERING PLANS THE RECENTLY INSTALLED
 DRAINAGE STRUCTURES ON THE 66-INCH DIAMETER CULVERTS.
  
 4. CONGRESS AVENUE IS MAINTAINED BY PALM BEACH COUNTY.
 ANY IMPROVEMENTS WITHIN THE RIGHT-OF-WAY WILL REQUIRE A
 PERMIT FROM THE COUNTY
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE SFWMD ERP MODIFICATION FOR THE DEVELOPMENT
 PRIOR TO THE START OF CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 01-28-2019 Cont ID  
Sent By vnoel Date 01-28-2019 Time 09:21 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-11-2018 Cont ID  
Sent By vnoel Date 12-11-2018 Time 14:35 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-12-11 14:35:261. SHOW ALL EASEMENTS ON SITE PLAN, LANDSCAPE PLAN,
 ETC.
 2. ASSUMPTION THAT THIS IS A LEASE.
 3. SURVEY SHOWS EXISTING WATER SERVICE AT NORTH END OF
 PROPERTY.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 03-05-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-03-05 10:57:06PASSED.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 02-19-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-02-19 09:39:031. THE RESPONSE INDICATED THAT THE DIAGONAL STRIPED
 AREA NEAR THE EXIT OF THE DRIVE-THROUGH IS USED TO
 ACCOMMODATE LOADING TRUCK. HOWEVER, ACCORDING TO SHEET
 FSP-0.1, LOADING FOR BUILDING M IS PROVIDED BY THE 10'
 X 50' LOADING SPACES IN BUILDING J. THEREFORE, IT IS
 ASSUMED THAT NO LOADING TRUCKS WOULD BE ON-SITE IN
 BUILDING M. IF LOADING IS TO TAKE PLACE ON-SITE, PLEASE
 PROVIDE A DESIGNATED LOADING SPACE AND PROVIDE TRUCK
 AUTOTURN PATHS TO ILLUSTRATES TRUCK MOVEMENTS.
 OTHERWISE, CONSIDER USING RAISED CURB INSTEAD OF
 DIAGONAL STRIPING NEAR THE EXIT OF THE DRIVE-THROUGH
 LANE TO AVOID TWO VEHICLES LEAVING THE STOP BAR AT THE
 SAME TIME. MOUNTABLE CURB COULD BE USED TO ACCOMMODATE
 VEHICLE MOVEMENTS IF NEEDED.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 12-10-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-12-10 10:38:22Z18110014_PALM BEACH OUTLETS CPD (DATED NOVEMBER 13,
 2018) COMMENTS:
  
 1. CONSIDER USING RAISED CURB INSTEAD OF DIAGONAL
 STRIPING NEAR THE EXIT OF THE DRIVE-THROUGH LANE TO
 AVOID TWO VEHICLES LEAVING THE STOP BAR AT THE SAME
 TIME.
 2. INSTALL "DO NOT ENTER" SIGN TO PREVENT VEHICLES FROM
 ENTERING THE DRIVE-THROUGH LANE FROM THE EXIT.
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER

Review Stop Z ZONING
Rev No 3 Status P Date 05-01-2019 Cont ID  
Sent By eschneid Date 05-01-2019 Time 14:47 Rev Time 0.00
Received By eschneid Date 03-06-2019 Time 10:43 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 02-14-2019 Cont ID  
Sent By eschneid Date 02-14-2019 Time 09:26 Rev Time 0.00
Received By eschneid Date 02-13-2019 Time 10:29 Sent To  
Notes
2019-02-14 09:38:03PB 891HH -1ST RESUBMITTAL REVIEW
 ZAXBY'S @ PALM BEACH OUTLETS
 1801 PALM BEACH LAKES
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THE COMMENTS (BY APRIL 15, 2019), THE CASE
 SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL
 REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($300).
  
 1) REVISED COMMENT: THANK YOU FOR USING THE PARKING
 OVERHANG. I WAS ENVISIONING A SAW TOOTH CONFIGURATION
 ALONG THE NORTH AND WEST PARKING ROWS FOR THE
 ADDITIONAL PERVIOUS AREA THAT THE SAW TOOTH PROVIDES
 (EAST SIDE HAS THE DRAINAGE SO I UNDERSTAND WHY SAW
 TOOTH WOULD BE IMPRACTICAL THERE). PLEASE CONSIDER THE
 SAW TOOTH CONFIGURATION.
  
 2) REVISED COMMENT: THANK YOU FOR CLARIFYING THE
 LOCATION OF THE PODOCARPUS HEDGE TO SCREEN THE MENU
 BOARDS. PLEASE PROVIDE THE HEIGHTS OF THE MENU BOARD
 AND THE PRE-MENU BOARD SO THAT STAFF CAN VERIFY THE
 PROVIDED MATERIAL PROVIDES SUFFICIENT SCREENING. ONLY
 THE SIDE VIEW OF THE MAIN BOARD WAS PROVIDED.
  
 3) STILL UNDER STAFF REVIEW: THE ZONING AND LAND
 DEVELOPMENT REGULATIONS REQUIRE THAT ALL UTILITIES IN A
 PLANNED DEVELOPMENT BE INSTALLED UNDERGROUND. THE
 SURVEY SHOWS THAT THE OVERHEAD ELECTRIC LINE
 PARALLELING CONGRESS AVENUE IS LOCATED WITHIN THE
 BOUNDARY OF THE PLANNED DEVELOPMENT; THEREFORE IT NEEDS
 TO BE BURIED UNDERGROUND AS PART OF THE DEVELOPMENT OF
 PAD M.
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-10-2018 Cont ID  
Sent By eschneid Date 12-10-2018 Time 18:12 Rev Time 3.00
Received By eschneid Date 12-10-2018 Time 18:11 Sent To  
Notes
2018-12-10 18:12:36PB 891HH
 ZAXBY'S @ PALM BEACH OUTLETS
 1801 PALM BEACH LAKES
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY FEBRUARY 12,
 2019), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($300).
  
 1) ADD CASE NO. PB 891HH TO THE LINE ON THE MASTER
 PLAN.
  
 2) THE PEDESTRIAN WALKWAY TO CONGRESS AVENUE SHOULD
 TURN TO THE NORTH WITHIN THE LANDSCAPE BUFFER SINCE THE
 PEDESTRIAN CROSSING POINT FOR CONGRESS AVENUE IS THE
 LIGHT AT THE OUTLETS ENTRY DRIVE.
  
 3) PROVIDE A PARKING DETAIL FOR THE ANGLED PARKING
 SPACES. PLEASE NOTE THAT THE THREE PARKING SPACES AT
 THE END OF EACH PARKING ROW DOES NOT SCALE THE MINIMUM
 REQUIRED 18 FEET IN DEPTH.
  
 4) PLEASE CONSIDER HAVING THE FRONT OF THE PARKING
 SPACES BE OVERHUNG BY THE CARS AND NOT USE A WHEEL STOP
 AND A CURB.
  
 5) THE JUSTIFICATION STATEMENT REFERENCES A PODOCARPUS
 HEDGE TO SCREEN THE MENU BOARD. THERE IS NOT PODOCARPUS
 PROVIDED BY THE MENU BOARD.
  
 6) DUMPSTER ENCLOSURE.
  
 A. THE ENCLOSURE DOES NOT MEET CITY MINIMUM DEPTH OR
 WIDTH REQUIREMENTS FOR TWO CONTAINERS.
 B. THE ENCLOSURE DETAIL ON SHEET A-1 DOES NOT MATCH THE
 DIMENSIONS SHOWN ON C-400 AND FSP-3.2.
  
 7) WHY IS THERE NO LOADING SPACE PROVIDED ON THE PLANS?
  
 8) WHY CAN THE STORAGE BUILDING NOT BE BUILT AS PART OF
 THE MAIN BUILDING?
  
 9) IT SEEMS COUNTER INTUITIVE TO HAVE THE SEATING BE ON
 THE SIDE OF THE BUILDING THAT IS CIRCLED BY THE DRIVE
 THROUGH LANE. THE BACK OF HOUSE SHOULD HAVE THE DRIVE
 THROUGH LANES WRAP AROUND IT.
  
 10) THE PATIO AREA IS DIRECTLY ADJACENT TO THE DRIVE
 THROUGH LANE STACKING. CONSIDER INSTALLING A PLANTED
 BUFFER HERE.
  
 11) PLEASE EXPLAIN WHY THE EXAMPLE PHOTO ON SHEET A-01
 HAS MUCH MORE GLAZING THAN THE PROPOSED BUILDING.
  
 12) THE ZONING AND LAND DEVELOPMENT REGULATIONS REQUIRE
 THAT ALL UTILITES IN A PLANNED DEVELOPMENT BE INSTALLED
 UNDERGROUND. THE SURVEY SHOWS THAT THE OVERHEAD
 ELECTRIC LINE PARALLELING CONGRESS AVENUE IS LOCATED
 WITHIN THE BOUNDARY OF THE PLANNED DEVELOPMENT;
 THEREFORE IT NEEDS TO BE BURIED UNDERGROUND AS PART OF
 THE DEVELOPMENT OF PAD M.
  