Plan Review Details - Project Z18100028
Plan Review Stops For Project Z18100028
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 11-13-2018 Cont ID  
Sent By rbrown Date 11-13-2018 Time 19:55 Rev Time 0.00
Received By rrossano Date 11-13-2018 Time 19:55 Sent To  
Notes
2018-11-13 19:59:01DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. DEMOLITION OF THE EXISTING BUILDING. AN ASBESTOS
 SURVEY SHALL BE PERFORMED AND AN ASBESTOS ABATEMENT
 REPORT SUBMITTED TO THE HEALTH DEPARTMENT PALM BEACH
 COUNTY OFFICE. CONTACT ALEX ORTEGA AT (561) 837-5963,
 OR BY EMAIL: [email protected]
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 11-27-2018 Cont ID  
Sent By Mgonzale Date 11-27-2018 Time   Rev Time 1.00
Received By mgonzale Date 11-27-2018 Time   Sent To I
Notes
2018-11-27 09:53:11PROVISOS:
  
 ALL PERTINENT CITY AND PROVATE UILITIES WILL BE
 ADDRESSED AT THE TIME OF DEISGN.
  
 MGPNZALEZ
 [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 01-25-2019 Cont ID  
Sent By RRossano Date 01-25-2019 Time   Rev Time 0.00
Received By   Date 01-25-2019 Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 12-11-2018 Cont ID  
Sent By RRossano Date 12-11-2018 Time   Rev Time 0.00
Received By rrossano Date 12-11-2018 Time   Sent To  
Notes
2018-12-11 14:17:01PASSED WITH PROVISO: COORDINATE WATER SERVICE WITH PALM
 BEACH COUNTY.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 11-09-2018 Cont ID  
Sent By rrossano Date 11-09-2018 Time   Rev Time  
Received By rrossano Date 11-09-2018 Time   Sent To I
Notes
2018-11-09 14:46:01COMMENTS PER MANNY GONZALEZ, SENIOR PROJECT
 COORDINATOR, CITY OF WPB ENGINEERING
 PROVIDE CONCURRENCY FROM PBC FOR WATER & SEWER
 UTILITIES
 SHOW 3 IN. FM ALONG COMMUNITY DR.
  
 COMMENTS PER RICK ROSSANO, PROJECT COORDINATOR, CITY OF
 WPB ENGINEERING
 PROVIDE PROFILES OF ANY EXISTING OR PROPOSED UTILITIES
 IN CITY OF WPB RIGHT OF WAY
 PROVIDE COPIES OF PBC & FDOT PERMITS
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 SUPPLY POLLUTION CONTROL PLAN SHOWING:
 A) WHERE SILT SCREENS WILL BE INSTALLED,
 B) SHOW THE PROTECTION OF ALL ON-SITE CATCH BASINS
 C) SHOW PROTECTION OF ALL OFF-SITE CATCH BASINS
 D) INCLUDE DETAILS AS TO THE TYPE OF PROTECTION USED ON
 THE CATCH BASINS
 E) SHOW HOW SITE DIRT WILL NOT BE TRACKED INTO THE
 ROADS
 HTTP://WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/DOCS/
 CONST_ACTIVITY.PDF
 HTTP://WWW.PBCO-NPDES.ORG/CONSTRUN.HTML
 HTTP://WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/FAQS.
 HTM
  
 GENERAL DRIVEWAY COMMENTS
 1) DIMENSION DRIVEWAYS, LOCATED HORIZONTALLY AND
 VERTICALLY. CALL OUT SETBACK.
 2) SHOW PROPOSED CONCRETE APRON(S), CITY STANDARD
 DETAIL IS REQUIRED, SEE LINK BELOW: HTTP://WPB.ORG/DEPA
 RTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICA
 TIONS
 3) IF USING PAVERS IN THE APRON AREA OF THE PROPOSED
 DRIVEWAY, YOU MUST EXECUTE A PAVER DRIVEWAY AGREEMENT,
 WHICH CAN BE OBTAINED HERE: HTTP://WPB.ORG/DEPARTMENTS/
 ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 GENERAL -
  
 THE FOLLOWING COMMENTS ARE INCLUDED FOR YOUR GENERAL
 INFORMATION AND USE. THEY MAY NOT BE SITE-SPECIFIC, BUT
 WILL SOON BE ADDED TO CITY OF WEST PALM BEACH
 DEVELOPMENT PERMIT APPLICATIONS.
  
 OBTAIN AVAILABLE UTILITIES OWNED BY THE CITY OF WEST
 PALM BEACH WITHIN THE PUBLIC RIGHT-OF-WAY FOR THE
 ENTIRE EXTENT OF THE LIMITS OF YOUR PROJECT. IDENTIFY
 TYPE OF UTILITY, LOCATION, PIPE MATERIAL, AGE AND SIZE.
 SUBMIT A FORMAL RECORDS REQUEST (WITH SUNSHINE DESIGN
 TICKET NUMBER) TO JANICE TARBILL IN THE WPB ENGINEERING
 SERVICES DEPARTMENT AT [email protected]. SUBMIT PROOF
 OF THE FORMAL RECORD REQUEST TO THE CITY. NOTE: RECORD
 INFORMATION PROVIDED BY THE CITY IS FOR REFERENCE ONLY.
 PERFORM FIELD VERIFICATION OF EXACT LOCATION AND DEPTH
 BY SOFT-DIGS, POT-HOLING, ETC.
  
 PROVIDE SCHEMATIC UTILITY ENGINEERING DRAWINGS (24IN X
 36IN FORMAT) AT A LEGIBLE ENGINEERING SCALE AND
 PREPARED BY A LICENSED PROFESSIONAL ENGINEER.
  
 PROVIDE STATEMENT, CONFIRMED BY ENGINEERING ANALYSIS,
 THAT THE EXISTING UTILITY MAINS SERVING THE PROPOSED
 PROJECT ARE ADEQUATE. PROVIDE CALCULATIONS OF EXISTING
 AND PROPOSED WATER & SEWER DEMANDS (AVERAGE, MAXIMUM,
 PEAK) AND FIRE FLOW DEMAND. CALCULATIONS SHALL BE PER
 FAC 64E-6 FOR SEWER AND PER FAC 64-E.008 FOR WATER.
  
 LOCATIONS, SIZES AND OTHER APPROPRIATE DESCRIPTIONS OF
 THE FOLLOWING EXISTING OR PROPOSED UTILITY FACILITIES:
 ? WATER MAINS, SERVICE CONNECTIONS, VALVES, METERS AND
 ANY SPECIAL STRUCTURES SUCH AS PUMP STATIONS;
 ? SANITARY SEWER MAINS, SERVICE CONNECTIONS AND ANY
 SPECIAL STRUCTURES OR FACILITIES SUCH AS LIFT STATIONS,
 SEPTIC SYSTEMS; AND
 ? PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER MAINS
 ALONG ENTIRE PROJECT FRONTAGE.
  STORMWATER DRAINAGE MAINS, CHANNELS, RETENTION OR
 DETENTION PONDS, AND OTHER MAJOR DRAINAGE FACILITIES;
 FLOW DIRECTION OF SURFACE RUNOFF.
  SHOW LOCATION OF ALL EXISTING DRY/FRANCHISE UTILITIES,
 AND ALL RELATED EASEMENTS ON THE SITE OR ON IMMEDIATELY
 ADJACENT PROPERTY.
 PROVIDE PROFILE VIEW OF ALL PROPOSED UTILITIES WITHIN
 THE RIGHT-OF-WAY TO BE OWNED AND MAINTAINED BY THE
 CITY. CALL OUT VERTICAL CLEARANCES OF UTILITY CROSSINGS
 WITH CITY AND DRY/FRANCHISE UTILITIES. IDENTIFY TYPE OF
 UTILITY/OWNERSHIP, LOCATION/DEPTH, PIPE MATERIAL, SIZE.
 SHOW CONDITIONS ON IMMEDIATELY ADJACENT PROPERTY THAT
 HAVE A DIRECT IMPACT ON THE PROPOSED DEVELOPMENT
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 11-01-2018 Cont ID  
Sent By pleduc Date 11-01-2018 Time   Rev Time 0.00
Received By pleduc Date 11-01-2018 Time 16:14 Sent To  
Notes
2018-11-01 16:33:36THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, INCLDING BUT NOT LIMITED TO,
 NFPA? 30, FLAMMABLE AND COMBUSTIBLE LIQUIDS CODE, 2015
 EDITION, NFPA? 30A
 CODE FOR MOTOR FUEL DISPENSING FACILITIES AND REPAIR
 GARAGES 2015 EDITION, NFPA 101 CHAPTER 36 NEW
 MERCANTILE OCCUPANCIES, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY CLASSIFICATION PER THE FLORIDA FIRE
 PREVENTION CODE. IDENTIFY ALL COOKING EQUIPMENT AND/OR
 APPLIANCES.
  
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 A FIRE HYDRANT LOCATION COULD NOT CLEARLY BE IDENTIFIED
 ON OR AROUND THIS PROPOSED PROJECT.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 A 4" FIRE LINE WAS INDICATING GOIN INTO THE PROPOSED
 STRUCTURE, WILL THE STRUCTURE BE PROTECTED WITH A FIRE
 SPRINKLER SYSTEM?
  
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 5 Status P Date 10-16-2019 Cont ID  
Sent By rcaranci Date 10-16-2019 Time 15:43 Rev Time 0.00
Received By rcaranci Date 10-16-2019 Time 15:43 Sent To  
Notes
2019-10-16 15:43:38FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC Z18100028
 OCTOBER 16, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CORRECTIONS NEED TO BE MADE TO THE TREE DISPOSITION
 PLAN:
 ? SATISFIED. PROVIDE THE CURRENT CANOPY DIAMETER FOR
 EACH TREE
 ? SATISFIED. SHOW CALCULATIONS FOR CANOPY SQUARE
 FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF UNDER
 20 FEET, ACTUAL AREA 20 FEET OR MORE.
 IF UNDER 20 FEET DIAMETER THE MITIGATION DUE IS EQUAL
 TO THE CATEGORY VALUE. OAK UNDER 20 FEET IS CATEGORY 1,
 MITIGATION IS 300 SQ FT. TOTAL MITIGATION DUE FOR
 SUBMITTED LIST IS 11,479 SQ FT.
 ? SATISFIED. INDICATE WHY TREES #19 AND #22 WILL BE
 PRESERVED, AS THEY ARE HATRACKED.
 ? SATISFIED. CORRECT ALL SPECIES, AS SOME ARE
 MISIDENTIFIED.
 2. SATISFIED. PROVIDE THE TOTAL TREE CANOPY CREDITS
 PROVIDED WITH THE PROPOSED LANDSCAPE PLAN ON THE TREE
 DISPOSITION PLAN, AS WELL AS THE TOTAL PROPOSED TO BE
 REMOVED.
 3. SATISFIED. INCLUDE THE EXISTING TREES TO REMAIN ON
 THE PLANT LIST, AS THEY ARE TO BE COUNTED TOWARD
 REQUIRED TREES.
 4. SATISFIED. PROVIDE AN EXPLANATION FOR THE SETBACK
 AND THE USE OF THE SMALL TREE SPECIES FOR THE WESTERN
 BUFFER, AND SMALL SPECIES ON THE SOUTHERN BUFFER.
 5. SATISFIED. SHOW THE PARKING LANDSCAPE AREAS COUNTED
 TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND (4) FOR
 THE AREAS WITHIN THE PARKING FIELD, AND MATCH THE TOTAL
 SHOWN ON THE REQUIREMENT CHART TO MEETING THE TOTAL OF
 BOTH SECTIONS ADDED TOGETHER.
 CALCULATIONS FOR REQUIRED AREAS ARE CORRECT, BUT AREA
 TO BE PROVIDED IS THE TOTAL OF THE TWO- 1466 SQ FT., SO
 1262 SQ FT PROVIDED DOES NOT MEET THE REQUIREMENT. ADD
 LANDSCAPE AREA WITHIN THE PARKING FIELD AND ADJUST THE
 CHARTS ON LP.1 AND LP.2 TO MATCH.
  
 6. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES
 MEET THE 75% CATEGORY ONE SHADE TREE REQUIREMENT.
 REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS
 ADJACENT TO PARKING SPACES.
 7. SATISFIED. CORRECT THE REQUIRED BUFFER TREE
 CALCULATIONS TO SHOW WHOLE NUMBERS FOR REQUIRED TREES.
 8. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE
 LANDSCAPE PLAN AND PROVIDE THE REQUIRED TREE IN THE
 TERMINAL ISLAND AT THE EAST END OF THE ROW OF PARKING
 ON THE NORTH SIDE OF THE BUILDING.
 9. SATISFIED. SHOW COMPLIANCE WITH THE BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL
 USE AND INCLUDE THE LINEAR FOOTAGE.
 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY
 LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT
 COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT
 TOLERANT. PROVIDE GRAPHIC FOR WATER USE ZONES AND ADD A
 COLUMN TO THE PLANT LIST FOR NATIVE SPECIES.
 11. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL FPL
 TRANSFORMERS AND ABOVE GROUND UTILITY VALVES AND
 BACKFLOWS PREVENTERS.
 12. SATISFIED. IDENTIFY IF UTILITIES ARE TO BE PROVIDED
 BY WPB OR PBC.
 13. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS AND
 PROVIDE A DETAIL FOR INSTALLATION.
  
 ADDITIONAL COMMENT 12/20/18:
 14. SATISFIED. ALL TREES IN GOOD CONDITION MUST BE
 PRESERVED OR RELOCATED PER SECTION 94-448(D)(3). THIS
 APPLIES TO THE TWO LARGE LIVE OAKS #23 AND #24.
 ADDITIONAL COMMENT 1/30/19:
  
 15. SATISFIED. REVIEWING THE SITE PLAN AND LANDSCAPE
 PLAN IT WAS ASSUMED THAT THE CURBS WERE THE STANDARD AS
 REQUIRED BY CITY CODE, AS THEY WERE NOT LABELED TO
 IDENTIFY THEM AS SOMETHING DIFFERENT THAN CODE
 REQUIREMENT OF A TYPE D CURB PER SECTION 94-443(C)(5).
 SINCE THIS IS NOT A PD, A WAIVER IS NOT POSSIBLE, AND
 THE CURBS MUST MEET CITY REQUIREMENTS. THE EXTENDED
 CONCRETE BACKERS ENCROACHING INTO THE LANDSCAPE AREAS
 ARE NOT NEEDED WITH A NON-MOUNTABLE CURB.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 10-10-2019 Cont ID  
Sent By rcaranci Date 10-10-2019 Time 12:15 Rev Time 0.00
Received By rcaranci Date 10-10-2019 Time 12:15 Sent To  
Notes
2019-10-10 12:15:43FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC Z18100028
 OCTOBER 10, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CORRECTIONS NEED TO BE MADE TO THE TREE DISPOSITION
 PLAN:
 ? SATISFIED. PROVIDE THE CURRENT CANOPY DIAMETER FOR
 EACH TREE
 ? SATISFIED. SHOW CALCULATIONS FOR CANOPY SQUARE
 FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF UNDER
 20 FEET, ACTUAL AREA 20 FEET OR MORE.
 IF UNDER 20 FEET DIAMETER THE MITIGATION DUE IS EQUAL
 TO THE CATEGORY VALUE. OAK UNDER 20 FEET IS CATEGORY 1,
 MITIGATION IS 300 SQ FT. TOTAL MITIGATION DUE FOR
 SUBMITTED LIST IS 11,479 SQ FT.
 ? SATISFIED. INDICATE WHY TREES #19 AND #22 WILL BE
 PRESERVED, AS THEY ARE HATRACKED.
 ? SATISFIED. CORRECT ALL SPECIES, AS SOME ARE
 MISIDENTIFIED.
 2. SATISFIED. PROVIDE THE TOTAL TREE CANOPY CREDITS
 PROVIDED WITH THE PROPOSED LANDSCAPE PLAN ON THE TREE
 DISPOSITION PLAN, AS WELL AS THE TOTAL PROPOSED TO BE
 REMOVED.
 3. SATISFIED. INCLUDE THE EXISTING TREES TO REMAIN ON
 THE PLANT LIST, AS THEY ARE TO BE COUNTED TOWARD
 REQUIRED TREES.
 4. SATISFIED. PROVIDE AN EXPLANATION FOR THE SETBACK
 AND THE USE OF THE SMALL TREE SPECIES FOR THE WESTERN
 BUFFER, AND SMALL SPECIES ON THE SOUTHERN BUFFER.
 5. SATISFIED. SHOW THE PARKING LANDSCAPE AREAS COUNTED
 TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND (4) FOR
 THE AREAS WITHIN THE PARKING FIELD, AND MATCH THE TOTAL
 SHOWN ON THE REQUIREMENT CHART TO MEETING THE TOTAL OF
 BOTH SECTIONS ADDED TOGETHER.
 CALCULATIONS FOR REQUIRED AREAS ARE CORRECT, BUT AREA
 TO BE PROVIDED IS THE TOTAL OF THE TWO- 1466 SQ FT., SO
 1262 SQ FT PROVIDED DOES NOT MEET THE REQUIREMENT. ADD
 LANDSCAPE AREA WITHIN THE PARKING FIELD AND ADJUST THE
 CHARTS ON LP.1 AND LP.2 TO MATCH.
  
 6. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES
 MEET THE 75% CATEGORY ONE SHADE TREE REQUIREMENT.
 REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS
 ADJACENT TO PARKING SPACES.
 7. SATISFIED. CORRECT THE REQUIRED BUFFER TREE
 CALCULATIONS TO SHOW WHOLE NUMBERS FOR REQUIRED TREES.
 8. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE
 LANDSCAPE PLAN AND PROVIDE THE REQUIRED TREE IN THE
 TERMINAL ISLAND AT THE EAST END OF THE ROW OF PARKING
 ON THE NORTH SIDE OF THE BUILDING.
 9. SATISFIED. SHOW COMPLIANCE WITH THE BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL
 USE AND INCLUDE THE LINEAR FOOTAGE.
 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY
 LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT
 COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT
 TOLERANT. PROVIDE GRAPHIC FOR WATER USE ZONES AND ADD A
 COLUMN TO THE PLANT LIST FOR NATIVE SPECIES.
 11. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL FPL
 TRANSFORMERS AND ABOVE GROUND UTILITY VALVES AND
 BACKFLOWS PREVENTERS.
 12. SATISFIED. IDENTIFY IF UTILITIES ARE TO BE PROVIDED
 BY WPB OR PBC.
 13. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS AND
 PROVIDE A DETAIL FOR INSTALLATION.
  
 ADDITIONAL COMMENT 12/20/18:
 14. SATISFIED. ALL TREES IN GOOD CONDITION MUST BE
 PRESERVED OR RELOCATED PER SECTION 94-448(D)(3). THIS
 APPLIES TO THE TWO LARGE LIVE OAKS #23 AND #24.
 ADDITIONAL COMMENT 1/30/19:
  
 15. PARTIALLY SATISFIED. REVIEWING THE SITE PLAN AND
 LANDSCAPE PLAN IT WAS ASSUMED THAT THE CURBS WERE THE
 STANDARD AS REQUIRED BY CITY CODE, AS THEY WERE NOT
 LABELED TO IDENTIFY THEM AS SOMETHING DIFFERENT THAN
 CODE REQUIREMENT OF A TYPE D CURB PER SECTION
 94-443(C)(5). SINCE THIS IS NOT A PD, A WAIVER IS NOT
 POSSIBLE, AND THE CURBS MUST MEET CITY REQUIREMENTS.
 THE EXTENDED CONCRETE BACKERS ENCROACHING INTO THE
 LANDSCAPE AREAS ARE NOT NEEDED WITH A NON-MOUNTABLE
 CURB.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 02-08-2019 Cont ID  
Sent By rcaranci Date 02-08-2019 Time 15:47 Rev Time 0.00
Received By rcaranci Date 02-08-2019 Time 15:47 Sent To  
Notes
2019-02-08 15:47:21MEMO TO FILE
 FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC Z18100028
 JANUARY 30, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CORRECTIONS NEED TO BE MADE TO THE TREE DISPOSITION
 PLAN:
 ? SATISFIED. PROVIDE THE CURRENT CANOPY DIAMETER FOR
 EACH TREE
 ? SATISFIED. SHOW CALCULATIONS FOR CANOPY SQUARE
 FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF UNDER
 20 FEET, ACTUAL AREA 20 FEET OR MORE.
 IF UNDER 20 FEET DIAMETER THE MITIGATION DUE IS EQUAL
 TO THE CATEGORY VALUE. OAK UNDER 20 FEET IS CATEGORY 1,
 MITIGATION IS 300 SQ FT. TOTAL MITIGATION DUE FOR
 SUBMITTED LIST IS 11,479 SQ FT.
 ? SATISFIED. INDICATE WHY TREES #19 AND #22 WILL BE
 PRESERVED, AS THEY ARE HATRACKED.
 ? SATISFIED. CORRECT ALL SPECIES, AS SOME ARE
 MISIDENTIFIED.
 2. SATISFIED. PROVIDE THE TOTAL TREE CANOPY CREDITS
 PROVIDED WITH THE PROPOSED LANDSCAPE PLAN ON THE TREE
 DISPOSITION PLAN, AS WELL AS THE TOTAL PROPOSED TO BE
 REMOVED.
 3. SATISFIED. INCLUDE THE EXISTING TREES TO REMAIN ON
 THE PLANT LIST, AS THEY ARE TO BE COUNTED TOWARD
 REQUIRED TREES.
 4. SATISFIED. PROVIDE AN EXPLANATION FOR THE SETBACK
 AND THE USE OF THE SMALL TREE SPECIES FOR THE WESTERN
 BUFFER, AND SMALL SPECIES ON THE SOUTHERN BUFFER.
 5. SATISFIED. SHOW THE PARKING LANDSCAPE AREAS COUNTED
 TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND (4) FOR
 THE AREAS WITHIN THE PARKING FIELD, AND MATCH THE TOTAL
 SHOWN ON THE REQUIREMENT CHART TO MEETING THE TOTAL OF
 BOTH SECTIONS ADDED TOGETHER.
 CALCULATIONS FOR REQUIRED AREAS ARE CORRECT, BUT AREA
 TO BE PROVIDED IS THE TOTAL OF THE TWO- 1466 SQ FT., SO
 1262 SQ FT PROVIDED DOES NOT MEET THE REQUIREMENT. ADD
 LANDSCAPE AREA WITHIN THE PARKING FIELD AND ADJUST THE
 CHARTS ON LP.1 AND LP.2 TO MATCH.
  
 6. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES
 MEET THE 75% CATEGORY ONE SHADE TREE REQUIREMENT.
 REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS
 ADJACENT TO PARKING SPACES.
 7. SATISFIED. CORRECT THE REQUIRED BUFFER TREE
 CALCULATIONS TO SHOW WHOLE NUMBERS FOR REQUIRED TREES.
 8. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE
 LANDSCAPE PLAN AND PROVIDE THE REQUIRED TREE IN THE
 TERMINAL ISLAND AT THE EAST END OF THE ROW OF PARKING
 ON THE NORTH SIDE OF THE BUILDING.
 9. SATISFIED. SHOW COMPLIANCE WITH THE BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL
 USE AND INCLUDE THE LINEAR FOOTAGE.
 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY
 LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT
 COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT
 TOLERANT. PROVIDE GRAPHIC FOR WATER USE ZONES AND ADD A
 COLUMN TO THE PLANT LIST FOR NATIVE SPECIES.
 11. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL FPL
 TRANSFORMERS AND ABOVE GROUND UTILITY VALVES AND
 BACKFLOWS PREVENTERS.
 12. SATISFIED. IDENTIFY IF UTILITIES ARE TO BE PROVIDED
 BY WPB OR PBC.
 13. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS AND
 PROVIDE A DETAIL FOR INSTALLATION.
  
 ADDITIONAL COMMENT 12/20/18:
 14. SATISFIED. ALL TREES IN GOOD CONDITION MUST BE
 PRESERVED OR RELOCATED PER SECTION 94-448(D)(3). THIS
 APPLIES TO THE TWO LARGE LIVE OAKS #23 AND #24.
 ADDITIONAL COMMENT 1/30/19:
  
 15. REVIEWING THE SITE PLAN AND LANDSCAPE PLAN IT WAS
 ASSUMED THAT THE CURBS WERE THE STANDARD AS REQUIRED BY
 CITY CODE, AS THEY WERE NOT LABELED TO IDENTIFY THEM AS
 SOMETHING DIFFERENT THAN CODE REQUIREMENT OF A TYPE D
 CURB PER SECTION 94-443(C)(5). SINCE THIS IS NOT A PD,
 A WAIVER IS NOT POSSIBLE, AND THE CURBS MUST MEET CITY
 REQUIREMENTS. THE EXTENDED CONCRETE BACKERS ENCROACHING
 INTO THE LANDSCAPE AREAS ARE NOT NEEDED WITH A
 NON-MOUNTABLE CURB.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-20-2018 Cont ID  
Sent By rcaranci Date 12-20-2018 Time 14:37 Rev Time 0.00
Received By rcaranci Date 12-20-2018 Time 14:37 Sent To  
Notes
2018-12-20 14:38:24MEMO TO FILE
 FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC Z18100028
 DECEMBER 20, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CORRECTIONS NEED TO BE MADE TO THE TREE DISPOSITION
 PLAN:
 ? SATISFIED. PROVIDE THE CURRENT CANOPY DIAMETER FOR
 EACH TREE
 ? PARTIALLY SATISFIED. SHOW CALCULATIONS FOR CANOPY
 SQUARE FOOTAGE BASED ON DIAMETER, 1:1 SAME CATEGORY IF
 UNDER 20 FEET, ACTUAL AREA 20 FEET OR MORE.
 IF UNDER 20 FEET DIAMETER THE MITIGATION DUE IS EQUAL
 TO THE CATEGORY VALUE. OAK UNDER 20 FEET IS CATEGORY 1,
 MITIGATION IS 300 SQ FT. TOTAL MITIGATION DUE FOR
 SUBMITTED LIST IS 11,479 SQ FT.
 ? SATISFIED. INDICATE WHY TREES #19 AND #22 WILL BE
 PRESERVED, AS THEY ARE HATRACKED.
 ? SATISFIED. CORRECT ALL SPECIES, AS SOME ARE
 MISIDENTIFIED.
  
 2. PARTIALLY SATISFIED. PROVIDE THE TOTAL TREE CANOPY
 CREDITS PROVIDED WITH THE PROPOSED LANDSCAPE PLAN ON
 THE TREE DISPOSITION PLAN, AS WELL AS THE TOTAL
 PROPOSED TO BE REMOVED.
  
  
 3. SATISFIED. INCLUDE THE EXISTING TREES TO REMAIN ON
 THE PLANT LIST, AS THEY ARE TO BE COUNTED TOWARD
 REQUIRED TREES.
  
 4. SATISFIED. PROVIDE AN EXPLANATION FOR THE SETBACK
 AND THE USE OF THE SMALL TREE SPECIES FOR THE WESTERN
 BUFFER, AND SMALL SPECIES ON THE SOUTHERN BUFFER.
  
 5. PARTIALLY SATISFIED. SHOW THE PARKING LANDSCAPE
 AREAS COUNTED TOWARD COMPLIANCE WITH SECTION
 94-443(C)(3) AND (4) FOR THE AREAS WITHIN THE PARKING
 FIELD, AND MATCH THE TOTAL SHOWN ON THE REQUIREMENT
 CHART TO MEETING THE TOTAL OF BOTH SECTIONS ADDED
 TOGETHER.
 CALCULATIONS FOR REQUIRED AREAS ARE CORRECT, BUT AREA
 TO BE PROVIDED IS THE TOTAL OF THE TWO- 1466 SQ FT., SO
 1262 SQ FT PROVIDED DOES NOT MEET THE REQUIREMENT. ADD
 LANDSCAPE AREA WITHIN THE PARKING FIELD AND ADJUST THE
 CHARTS ON LP.1 AND LP.2 TO MATCH.
  
 6. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES
 MEET THE 75% CATEGORY ONE SHADE TREE REQUIREMENT.
 REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS
 ADJACENT TO PARKING SPACES.
  
 7. SATISFIED. CORRECT THE REQUIRED BUFFER TREE
 CALCULATIONS TO SHOW WHOLE NUMBERS FOR REQUIRED TREES.
  
  
 8. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE
 LANDSCAPE PLAN AND PROVIDE THE REQUIRED TREE IN THE
 TERMINAL ISLAND AT THE EAST END OF THE ROW OF PARKING
 ON THE NORTH SIDE OF THE BUILDING.
  
  
 9. SATISFIED. SHOW COMPLIANCE WITH THE BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL
 USE AND INCLUDE THE LINEAR FOOTAGE.
  
 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY
 LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT
 COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT
 TOLERANT. PROVIDE GRAPHIC FOR WATER USE ZONES AND ADD A
 COLUMN TO THE PLANT LIST FOR NATIVE SPECIES.
  
 11. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL FPL
 TRANSFORMERS AND ABOVE GROUND UTILITY VALVES AND
 BACKFLOWS PREVENTERS.
  
 12. SATISFIED. IDENTIFY IF UTILITIES ARE TO BE PROVIDED
 BY WPB OR PBC.
  
 13. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS AND
 PROVIDE A DETAIL FOR INSTALLATION.
  
 ADDITIONAL COMMENT 12/20/18:
  
 14. ALL TREES IN GOOD CONDITION MUST BE PRESERVED OR
 RELOCATED PER SECTION 94-448(D)(3).THIS APPLIES TO THE
 TWO LARGE LIVE OAKS #23 AND #24.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 11-13-2018 Cont ID  
Sent By rcaranci Date 11-13-2018 Time 14:32 Rev Time 0.00
Received By rcaranci Date 11-13-2018 Time 14:32 Sent To  
Notes
2018-11-13 14:32:56FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC Z18100028
 NOVEMBER 13, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CORRECTIONS NEED TO BE MADE TO THE TREE DISPOSITION
 PLAN:
 ? PROVIDE THE CURRENT CANOPY DIAMETER FOR EACH TREE
 ? SHOW CALCULATIONS FOR CANOPY SQUARE FOOTAGE BASED ON
 DIAMETER, 1:1 SAME CATEGORY IF UNDER 20 FEET, ACTUAL
 AREA 20 FEET OR MORE.
 ? INDICATE WHY TREES #19 AND #22 WILL BE PRESERVED, AS
 THEY ARE HATRACKED.
 ? CORRECT ALL SPECIES, AS SOME ARE MISIDENTIFIED.
  
 2. PROVIDE THE TOTAL TREE CANOPY CREDITS PROVIDED WITH
 THE PROPOSED LANDSCAPE PLAN ON THE TREE DISPOSITION
 PLAN, AS WELL AS THE TOTAL PROPOSED TO BE REMOVED.
  
 3. INCLUDE THE EXISTING TREES TO REMAIN ON THE PLANT
 LIST, AS THEY ARE TO BE COUNTED TOWARD REQUIRED TREES.
  
 4. PROVIDE AN EXPLANATION FOR THE SETBACK AND THE USE
 OF THE SMALL TREE SPECIES FOR THE WESTERN BUFFER, AND
 SMALL SPECIES ON THE SOUTHERN BUFFER.
  
 5. SHOW THE PARKING LANDSCAPE AREAS COUNTED TOWARD
 COMPLIANCE WITH SECTION 94-443(C)(3) AND (4) FOR THE
 AREAS WITHIN THE PARKING FIELD, AND MATCH THE TOTAL
 SHOWN ON THE REQUIREMENT CHART TO MEETING THE TOTAL OF
 BOTH SECTIONS ADDED TOGETHER.
  
 6. SHOW THAT THE REQUIRED PARKING LOT TREES MEET THE
 75% CATEGORY ONE SHADE TREE REQUIREMENT. REQUIRED TREES
 INCLUDE ALL TERMINAL ISLAND AND ISLANDS ADJACENT TO
 PARKING SPACES.
  
 7. CORRECT THE REQUIRED BUFFER TREE CALCULATIONS TO
 SHOW WHOLE NUMBERS FOR REQUIRED TREES.
  
  
 8. SHOW ALL PARKING SPACE ROW COUNTS ON THE LANDSCAPE
 PLAN AND PROVIDE THE REQUIRED TREE IN THE TERMINAL
 ISLAND AT THE EAST END OF THE ROW OF PARKING ON THE
 NORTH SIDE OF THE BUILDING.
  
  
 9. SHOW COMPLIANCE WITH THE BUILDING PERIMETER
 LANDSCAPE REQUIREMENT OF 30% FOR COMMERCIAL USE AND
 INCLUDE THE LINEAR FOOTAGE.
  
 10. PLEASE CORRECT THE FLORIDA FRIENDLY LANDSCAPE CHART
 SO THAT TREES AND SHRUBS ARE NOT COUNTED TWICE FOR EACH
 CATEGORY OF NATIVE AND DROUGHT TOLERANT. PROVIDE
 GRAPHIC FOR WATER USE ZONES AND ADD A COLUMN TO THE
 PLANT LIST FOR NATIVE SPECIES.
  
 11. PLEASE PROVIDE SCREENING FOR ALL FPL TRANSFORMERS
 AND ABOVE GROUND UTILITY VALVES AND BACKFLOWS
 PREVENTERS.
  
 12. IDENTIFY IF UTILITIES ARE TO BE PROVIDED BY WPB OR
 PBC.
  
 13. SHOW LOCATIONS OF ANY ROOT BARRIERS AND PROVIDE A
 DETAIL FOR INSTALLATION.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 4 Status P Date 06-10-2019 Cont ID  
Sent By rrossano Date 06-10-2019 Time   Rev Time 0.00
Received By rrossano Date 06-10-2019 Time   Sent To  
Notes
2019-06-10 12:17:12PASSED WITH PROVISO:
 DRAINAGE CALCS SHOW THAT STRUCTURE D-8 (FORMERLY D-7)
 WILL FLOOD DURING A 3 YEAR 1-DAY STORM EVENT. P-
 COMMENT FROM TRACY WARD, PE, SR. STORMWATER ENGINEER,
 ENG. SERVICES. PLEASE UPDATE PLANS AND SUBMIT UNDER
 ENGINEERING SUBMITTAL E19010018.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210
  
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 02-15-2019 Cont ID  
Sent By tward Date 02-15-2019 Time 11:09 Rev Time 0.00
Received By tward Date 02-15-2019 Time 11:20 Sent To  
Notes
2019-02-15 11:20:10THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 1/23/19 SUBMITTAL:
  
 1. THE DRAINAGE MODELING RESULTS SHOW THE ROUTED PEAK
 25-YEAR 3-DAY STAGE IS 16.78. THE SPOT GRADES AT THE
 DRIVEWAYS SHOULD BE AT THIS ELEVATION OR HIGHER.
  
 2. NOTE THE EAST SIDEWALK CURB RAMP APPEARS TO SLOPE
 DOWNWARD AND THE CROWN OF THE DRIVEWAY IS SOUTH OF THE
 SIDEWALK. CREATE A HIGH POINT IN THE SIDEWALK TO
 CONTAIN THE 25-YEAR 3-DAY STORM OR MOVE THE DRIVEWAY
 HIGH POINT BEFORE THE SIDEWALK.
  
 3. SHOW AND LABLE A BERM ALONG THE EAST AND SOUTH
 PROPERTY LINES.
  
 4. CHECK THE ORIENTATION OF THE ARROW ON THE LEFT SIDE
 OF THE DRIVEWAY TO COMMUNITY DRIVE AND THE PLACMENT OF
 THE LETTERING.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 12-10-2018 Cont ID  
Sent By tward Date 12-10-2018 Time 16:21 Rev Time 0.00
Received By tward Date 12-10-2018 Time 16:21 Sent To  
Notes
2018-12-10 16:18:18THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 12/4/2018 SUBMITTAL PACKAGE:
  
 1. SHOULD SECTION D-D INCLUDE VALLEY GUTTER OR DROP
 CURB ACROSS THE DRIVEWAY?
  
 2. CHECK THE SPOT GRADES ALONG THE DRIVEWAY TO
 COMMUNITY DRIVE. THERE IS A PROPOSED GRADE OF 15.10
 BETWEEN 15.06 AND THE CATCH BASIN.
  
 3. NO DRAINAGE CALCULATIONS WERE SUBMITTED SO STAFF
 DOES NOT KNOW HOW THE WEIR ELEVATION OF 16.36 FEET WAS
 DETERMINED. NOTE THIS WEIR ELEVATION IS HIGHER THAN:
 (A) THE TRENCH GRATE ELEVATION ON THE NORTH DRIVEWAY TO
 COMMUNIITY DRIVE;
 (B) THE HIGHEST SPOT GRADE FOR THE DRIVEWAY TO MILITARY
 TRAIL; AND
 (C) THE TOP OF BANK OF THE DETENTION AREA IN THE
 SOUTHEAST AREA OF THE SITE.
  
 STORMWATER RUNOFF IN EXCESS OF THE EXFILTRATION TRENCH
 DESIGN WILL DISCHARGE OFFSITE VIA (A) AND (B) BEFORE
 FLOWING OVER THE WEIR.
  
 4. ON THE LANDSCAPE PLANS SHOW THE EXISTING STORM PIPE
 FROM THE CONTROL STRUCTURE TO THE INLET ON COMMUNITY
 DRIVE (REPEAT COMMENT).
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]

Review Stop STORM STORMWATER
Rev No 1 Status F Date 11-09-2018 Cont ID  
Sent By tward Date 11-09-2018 Time 14:12 Rev Time 0.00
Received By tward Date 11-09-2018 Time 14:32 Sent To  
Notes
2018-11-09 14:32:24THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED. THE CONVERSION
 EQUATION IS NEEDED ON THE SURVEY.
  
 2. PROVIDE THE CONVERSION EQUATION FOR THE VERTICAL
 DATUM TO NGVD1929 ON THE ENGINEERING PLANS.
  
 3. NORTH MILITARY TRAIL IS MAINTAINED BY FDOT.
 COMMUNITY DRIVE IS MAINTAINED BY THE COUNTY. PERMITS
 WILL BE NEEDED FROM EACH AGENCY FOR THE DRIVEWAY
 CONNECTIONS AND ANY OTHER WORK IN THE RIGHTS-OF-WAY.
  
 4. CHESTER LAKE DRIVE IS SHOWN AS A PRIVATE ROAD ON THE
 SURVEY. THE RIGHT-OF-WAY IS SHOWN AS DEDICATED TO PALM
 BEACH COUNTY ON PAGE 187 OF PLAT BOOK 42. PROVIDE
 DOCUMENTATION OF ANY ABANDONMENT OF THE RIGHT-OF-WAY
 AND LIST IT ON THE SURVEY.
  
 5. THE LANDSCAPE PLAN IS NOT SHOWING THE EXISTING
 OUTFALL DRAINAGE PIPE ON COMMUNITY DRIVE.
  
 6. ROOT BARRIER WILL BE NEEDED TO PROTECT THE
 EXFILTRATION TRENCHES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE SFWMD ERP MODIFICATION FOR THE DEVELOPMENT
 PRIOR TO THE START OF CONSTRUCTION.
  
 4. PROVIDE NPBCID PERMIT, IF APPLICABLE, FOR THE
 DEVELOPMENT PRIOR TO THE START OF CONSTRUCTION.
  
 5. WITH THE ANNEXATION INTO THE CITY OF WEST PALM
 BEACH, MEET WITH PUBLIC UTILITIES ABOUT ESTABLISHING A
 STORMWATER UTILITY ACCOUNT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 01-28-2019 Cont ID  
Sent By vnoel Date 01-28-2019 Time 08:36 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2019-01-28 08:33:34PASSED BUT ALSO NEED PUBLIC UTILITY LETTER FROM PALM
 BEACH COUNTY CONCERNING ENCROACHMENT INTO THEIR
 EASEMENTS.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-20-2018 Cont ID  
Sent By vnoel Date 12-20-2018 Time 07:58 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-12-20 07:57:40SITE PLAN SHOWS CHESTER LAKE DRIVE AS BEING PRIVATE,
 BUT PB 42, PAGE 187 HAS IT DEDICATED TO THE COUNTY.
 PROVIDE INFO. IF TURNED OVER TO THE HOA. EITHER WAY
 APPROVAL OF OWNER IS REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status F Date   Cont ID  
Sent By   Date 09-25-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-09-25 14:47:44TRAFFIC STUDY COMMENTS:
 1. THE TPS APPROVAL SHOWN IN THE COUNTY TPS LETTER
 DATED FEBRUARY 19, 2019 IS SUBJECT TO THE RESTRICTION
 OF THE PROPOSED COMMUNITY DRIVE DRIVEWAY TO
 RIGHT-IN/RIGHT-OUT ONLY. HOWEVER, THE SUBMITTED
 DRIVEWAY VOLUME EXHIBIT INDICATES LEFT-IN MOVEMENT. IF
 A LEFT-IN MOVEMENT HAS BEEN APPROVED, PLEASE PROVIDE A
 REVISED COUNTY TPS LETTER WITHOUT SUCH A RESTRICTION.
 2. IN EXHIBITS 2, 3 AND 4, THE SEGMENT ON COMMUNITY
 DRIVE BETWEEN MILITARY TRAIL AND VILLAGE PARKWAY SHOULD
 BE BROKEN DOWN INTO TWO AT THE SITE DRIVEWAY. THERE ARE
 ALSO A FEW TYPOS IN THESE EXHIBITS, SUCH AS THE TITLE
 "RACETRAC - LANTANA ROAD", AND THE SEGMENT DESCRIPTION
 ALONG COMMUNITY DRIVE. PLEASE REVISE.
  
 SITE PLAN COMMENTS:
 3. PROVIDE MARKED CROSSWALK CROSSING THE DRIVEWAY ON
 COMMUNITY DRIVE.
 4. PROVIDE AUTOTURN PATHS FOR FUEL DELIVERY TRUCKS,
 COMMERCIAL TRUCKS AND GARBAGE TRUCKS WITH THE DRIVEWAY
 RESTRICTIONS. ALSO, PLEASE SHOW THAT THE PORKCHOP
 ISLAND ON COMMUNITY DRIVE DRIVEWAY DOES NOT OBSTRUCT
 LEFT-IN MOVEMENT OF PASSENGER CARS AND TRUCKS IF THIS
 LEFT-IN MOVEMENT IS ALLOWED.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 01-29-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-01-29 10:39:45TRAFFIC STUDY COMMENTS:
 1. IN EXHIBITS 2, 3 AND 4, THE SEGMENT ON COMMUNITY
 DRIVE BETWEEN MILITARY TRAIL AND VILLAGE PARKWAY SHOULD
 BE BROKEN DOWN INTO TWO AT THE SITE DRIVEWAY. THERE ARE
 ALSO A FEW TYPOS IN THESE EXHIBITS, SUCH AS THE TITLE
 "RACETRAC - LANTANA ROAD", AND THE SEGMENT DESCRIPTION
 ALONG COMMUNITY DRIVE. PLEASE REVISE.
 2. PLEASE NOTE THAT COMMENTS ON THE SITE DRIVEWAYS ON
 MILITARY TRAIL AND COMMUNITY DRIVE MAY IMPACT THE TRIP
 ASSIGNMENT.
  
 SITE PLAN COMMENTS:
 3. PROVIDE DRIVEWAY APPROVAL LETTER AND TPS LETTER FROM
 PALM BEACH COUNTY.
 4. THE MINIMUM CORNER CLEARANCE DISTANCE IS NEEDED FOR
 SAFETY REASONS. EGRESS VEHICLES AT THE MILITARY TRAIL
 DRIVEWAY MAY NOT EXPECT VEHICLES TURNING RIGHT FROM
 CHESTERLAKE DRIVE AND VICE VERSA IF THE TWO CONNECTIONS
 ARE TOO CLOSE TO EACH OTHER. CONSIDER SHIFTING THE
 MILITARY TRAIL DRIVEWAY TO THE NORTH (WITH FDOT
 APPROVAL), ELIMINATING THE MILITARY TRAIL DRIVEWAY, OR
 RESTRICTING IT TO A RIGHT-IN ONLY DRIVEWAY.
 5. COUNTY REQUESTED THE COMMUNITY DRIVE DRIVEWAY BE
 RESTRICTED TO RIGHT-IN RIGHT-OUT ONLY. CLARIFY IF THIS
 DRIVEWAY WILL STILL BE USED FOR FUEL DELIVERY AS THE
 AUTOTURN PATHS SHOWN FOR FUEL DELIVERY IS NOW
 RESTRICTED. IF NOT, REDUCE THE WIDTH OF THE DRIVEWAY TO
 24 FEET.
 6. REMOVE THE RIGHT-TURN ONLY PAVEMENT MARKING IN THE
 INBOUND LANE AT THE COMMUNITY DRIVE DRIVEWAY.
 7. PROVIDED REVISED AUTOTURN PATHS FOR FUEL DELIVERY
 TRUCKS, COMMERCIAL TRUCKS AND GARBAGE TRUCKS WITH THE
 DRIVEWAY RESTRICTIONS.
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status   Date   Cont ID  
Sent By   Date 12-18-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-12-18 14:53:47Z18100025, FILED UNDER Z18100028 RACETRAC - 2970 NORTH
 MILITARY TRAIL (OCTOBER 9, 2018 SUBMITTAL)
  
 1. PROVIDE TRAFFIC STUDY. PREVIOUS COMMENT. APPLICANT
 RESPONSE TO PRIOR REVIEW COMMENT STATED "SURVEY".
 2. PROVIDE DRIVEWAY APPROVAL LETTER AND TPS LETTER FROM
 PALM BEACH COUNTY. PREVIOUS COMMENT.
 3. THE CITY PREFERS NO DRIVEWAYS ON MILITARY TRAIL DUE
 TO THE PROXIMITY OF THE DRIVEWAY TO CHESTER LAKE DRIVE
 AND COMMUNITY DRIVE. CONSIDER REMOVING THE DRIVEWAY ON
 MILITARY TRAIL OR CHANGE IT TO A RIGHT-IN ONLY
 DRIVEWAY. PREVIOUS COMMENT.
 4. THE CORNER CLEARANCE FOR THE MILITARY TRAIL DRIVEWAY
 DOES NOT MEET THE MINIMUM CORNER CLEARANCE DISTANCE OF
 75 FEET PER CITY CODE SECTION 94-312. PLEASE REVISE.
 5. FUEL DELIVERY TRUCK PATH ANALYSIS PROVIDED SHOWS
 MILITARY TRAIL DRIVEWAY IS NOT REQUIRED FOR FUEL
 DELIVERY. THIS FURTHER SUPPORTS OUR REQUEST TO
 ELIMINATE THE MILITARY TRAIL DRIVEWAY.
 6. REDUCE THE WIDTH OF THE TWO-WAY DRIVEWAYS TO 24
 FEET. CITY WILL ONLY ACCEPT A WIDER DRIVEWAY IF
 DOCUMENTATION IS PROVIDED FROM THE PERMITTING AUTHORITY
 THAT THEY WILL NOT PERMIT A 24? WIDE DRIVEWAY.
 7. MOVE THE STOP BAR AT THE MILITARY TRAIL DRIVEWAY TO
 BE IN FRONT OF THE CROSSWALK, IF THE EGRESS IS
 MAINTAINED. PREVIOUS COMMENT. SHEET C9 - SIGNING AND
 PAVEMENT MARKING PLAN WAS NOT INCLUDED IN OUR PLAN SET
 FROM WGI FOR OUR REVIEW. REVIEW SITE PLAN FOR
 CONSISTENCY WITH SIGNING AND PAVEMENT MARKING PLAN.
 8. PROVIDE SIDEWALK EASEMENT FOR THE PORTION OF
 SIDEWALK OR CROSSWALK WITHIN THE PROPERTY RIGHT-OF-WAY.
 EASEMENT DOES NOT NEED TO BE SHOWN ON THE SITE PLAN.
 9. SHEET C-4 - ADD PLAN SHEET CROSS REFERENCE FOR
 SECTIONS. WE ASSUMED SHEET C3.1 IS CROSS REFERENCE FOR
 OUR REVIEW.
 10. SITE PLAN SHOWS CHESTERLAKE DRIVE AS PRIVATE WITH
 35 MPH SPEED LIMIT. CONFIRM. PLAT BOOK SHOWS ROAD AS
 PUBLIC.
 11. A PERMIT MAY BE REQUIRED FOR THE CHESTERLAKE DRIVE
 DRIVEWAY. CONFIRM WHO IS THE REGULATORY AGENCY AND
 PROVIDE DOCUMENTATION THAT THE DRIVEWAY WILL BE
 ALLOWED. THE TRAFFIC DIVISION SUPPORTS A DRIVEWAY ON
 CHESTERLAKE DR. AS IT WOULD ALLOW LOCAL TRIPS TO ACCESS
 THE SITE WITHOUT ENTERING MILITARY TRAIL, A HIGH SPEED
 ARTERIAL.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 11-09-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-11-09 14:59:30Z18100025, 026, 027, 028, 029 RACETRAC - 2970 NORTH
 MILITARY TRAIL (OCTOBER 9, 2018 SUBMITTAL)
 1. PROVIDE TRAFFIC STUDY.
 2. PROVIDE DRIVEWAY APPROVAL LETTER AND TPS LETTER FROM
 PALM BEACH COUNTY.
 3. THE CITY PREFERS NO DRIVEWAYS ON MILITARY TRAIL DUE
 TO THE PROXIMITY OF THE DRIVEWAY TO CHESTER LAKE DRIVE
 AND COMMUNITY DRIVE. CONSIDER REMOVING THE DRIVEWAY ON
 MILITARY TRAIL OR CHANGE IT TO A RIGHT-IN ONLY
 DRIVEWAY.
 4. THE CORNER CLEARANCE FOR THE MILITARY TRAIL DRIVEWAY
 DOES NOT MEET THE MINIMUM CORNER CLEARANCE DISTANCE OF
 75 FEET PER CITY CODE SECTION 94-312. PLEASE REVISE.
 5. REDUCE THE WIDTH OF THE TWO-WAY DRIVEWAYS TO 24
 FEET.
 6. MOVE THE STOP BAR AT THE MILITARY TRAIL DRIVEWAY TO
 BE IN FRONT OF THE CROSSWALK, IF THE EGRESS IS
 MAINTAINED. THE STOP SIGN SHOULD ALIGN WITH THE STOP
 BAR. ALSO, CONSIDER SHIFTING THE CROSSWALK CLOSER TO
 MILITARY TRAIL.
 7. PROVIDE SIDEWALK EASEMENT FOR THE PORTION OF
 SIDEWALK OR CROSSWALK WITHIN THE PROPERTY RIGHT-OF-WAY.
 8. PROVIDE ADA CURB RAMPS FOR CROSSWALKS ACROSS ALL
 DRIVEWAYS
 9. CONSIDER PROVIDING 8-FOOT SIDEWALK ALONG SITE
 FRONTAGE.
 10. PROVIDE PEDESTRIAN CONNECTIONS FROM CHESTER LAKE
 DRIVE AND MILITARY TRAIL TO THE RACETRAC MARKET.
 11. PROVIDE AUTOTURN TRUCK PATHS FOR GARBAGE, DELIVERY
 AND FUEL TRUCKS.
 12. SHOW RIGHT OF WAY WIDTH FROM CENTERLINE AND FULL
 RIGHT OF WAY WIDTH.
 13. CONSIDER REDUCING THE NUMBER OF PARKING SPACES.
 14. THE LINEWORK FOR EXISTING FEATURES ARE TOO LIGHT ON
 THE SITE PLAN. PLEASE REVISE.
  
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date   Cont ID  
Sent By   Date 10-16-2019 Time   Rev Time 0.00
Received By pgreilic Date 10-16-2019 Time 15:36 Sent To  
Notes
2019-10-16 15:37:221.) AIPP CONTRIBUTION REQUIRED PRIOR TO ISSUANCE OF
 FINAL C.O.
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 07-03-2019 Cont ID  
Sent By pgreilic Date 07-03-2019 Time 14:54 Rev Time 0.00
Received By pgreilic Date 07-03-2019 Time 14:53 Sent To  
Notes
2019-07-03 14:54:53RACETRAC ? MILITARY & COMMUNITY
 PROJECT NO: Z18100028
  
  
 1.) A TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY TRAFFIC DIVISION, VERIFYING
 THAT THE PROJECT MEETS THE TPS STANDARDS OF THE COUNTY
 WILL BE REQUIRED
  
 2.) SHOW CITY STANDARD DETAILS FOR PARKING STALLS, BIKE
 RACKS, DUMPSTER ON SITE PLAN SHEETS
  
 3.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION.
  
  
 ***WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15
 (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON
 THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS.
  
 ***RESUBMITAL FEE WILL BE 20 PERCENT OF THE ORIGINAL
 APPLICATION FEE.
  
 ***CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443
 IF THERE ARE ANY QUESTIONS
  

Review Stop Z ZONING
Rev No 2 Status F Date 12-18-2018 Cont ID  
Sent By   Date 12-18-2018 Time   Rev Time 0.00
Received By pgreilic Date 12-18-2018 Time 08:58 Sent To  
Notes
2018-12-18 09:07:48RACETRAC ? MILITARY & COMMUNITY
 PROJECT NO: Z18100028
 RESUMITTAL 11-29-18
  
  
 1.) A TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY TRAFFIC DIVISION, VERIFYING
 THAT THE PROJECT MEETS THE TPS STANDARDS OF THE COUNTY
 WILL BE REQUIRED
  
 2.) PROVIDE UPDATED AND ACCURATE LEVEL OF SERVICE
 ANALYSIS
  
 3.) SHOW CITY STANDARD DETAILS FOR PARKING STALLS, BIKE
 RACKS, DUMPSTER ON SITE PLAN SHEETS
  
 4.) PROVIDE ALL REQUIRED PUBLIC UTILITY LETTERS
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISION OF THEIR SERVICES
  
 5.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION.
  
  
 ***WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15
 (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X
 11 INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON
 THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS.
  
 ***RESUBMITAL FEE WILL BE 20 PERCENT OF THE ORIGINAL
 APPLICATION FEE.
  
 ***CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443
 IF THERE ARE ANY QUESTIONS
  
  
  
  
  
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 11-09-2018 Cont ID  
Sent By   Date 11-09-2018 Time   Rev Time 0.00
Received By pgreilic Date 11-09-2018 Time 15:11 Sent To  
Notes
2018-11-09 15:12:112970 N MILITARY TRAIL ANNEXATION
  
  
 1) IT IS HIGHLY RECOMMENDED THAT THE WIDTH OF ALL
 PROPOSED INGRESS/EGRESSES AND PROPOSED DRIVE AISLES BE
 REDUCED TO 24 FEET. DOING SO WOULD SATISFY CODE
 REQUIREMENTS AND ALLOW FOR WIDER LANDSCAPE BUFFERS
 PARTICULARLY ALONG COMMUNITY DRIVE AND CHESTER LAKE
 DRIVE
 2) STAFF SUPPORTS ELIMINATING THE PROPOSED
 INGRESS/EGRESS ON CHESTER LAKE DRIVE AS THE STREET
 EXCLUSIVELY SERVES RESIDENTIAL TRAFFIC
 3) THE PLAN IS PROPOSING 15 PARKING SPACES ABOVE WHAT
 IS REQUIRED. STAFF SUPPORTS ELIMINATING EXCESS PARKING
 SPACES TO PROVIDE FOR MORE GREEN SPACE. ADDITIONALLY,
 REDUCE THE DEPTH OF PARKING SPACES BY INCLUDING A
 2-FOOT GRASS OVERHANG. THE CURB WOULD FUNCTION AS WHEEL
 STOPS. ALSO CONSIDER THE INCLUSION OF SMALL CAR SPACES
 TO REDUCE OVERALL IMPERVIOUS SURFACE AREA. UP TO 30% OF
 SPACES MAY BE DESIGNATED FOR SMALL CAR USE. REDUCE
 WIDTH OF SPACES TO 8.5 FEET
 4) PROVIDE A CROSSWALK FROM THE SIDEWALK ALONG CHESTER
 LAKE DRIVE TO PROPOSED RACETRAC MARKET
 5) A TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW LETTER
 FROM THE PALM BEACH COUNTY TRAFFIC DIVISION, VERIFYING
 THAT THE PROJECT MEETS THE TPS STANDARDS OF THE COUNTY
 WILL BE REQUIRED
 6) PROVIDE CITY STANDARD DETAILS FOR PARKING STALLS,
 BIKE RACKS, DUMPSTER
 7) PROVIDE ALL REQUIRED PUBLIC UTILITY LETTERS
 CONFIRMING THAT THE PROPOSED PROJECT DOES NOT ENCROACH
 INTO THEIR EASEMENTS OR OTHERWISE INTERFERE WITH THE
 PROVISION OF THEIR SERVICES
 8) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION.
  
 INSTRUCTIONS FOR RESUBMITTAL
  
 *PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT
  
 *WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) COPIES, ONE REDUCED COPY IN 8.5X11, ONE SET IN
 11X17 AND AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE
 THAT THE CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 *PLEASE NOTE THAT YOU WILL PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
  
 *CONTACT PAUL GREILICH @ 561-822-1443 OR
 [email protected] FOR ANY QUESTIONS.
  