Plan Review Details - Project Z18080018
| Plan Review Stops For Project Z18080018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
09-11-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
09-11-2018 |
Time |
13:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
09-11-2018 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2018-09-11 13:43:21 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 3. OIL/GAS INTERCEPTOR. AN INTERCEPTOR WILL BE | | | REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M | | | SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS | | | AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: | | | [email protected] | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT | | | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 | | | 1080, OR BY EMAIL: [email protected] | | | | | | 6. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
12-03-2018 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
12-03-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
12-03-2018 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
09-17-2018 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
09-18-2018 |
Time |
|
Rev Time |
2.00 |
| Received By |
rrossano |
Date |
09-18-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-18 15:55:44 | GENERAL DRIVEWAY COMMENTS | | | 1) DIMENSION DRIVEWAYS, LOCATED HORIZONTALLY AND | | | VERTICALLY. CALL OUT SETBACK. | | | 2) SHOW PROPOSED CONCRETE APRON(S), CITY STANDARD | | | DETAIL IS REQUIRED, SEE LINK BELOW: HTTP://WPB.ORG/DEPA | | | RTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICA | | | TIONS | | | 3) IF USING PAVERS IN THE APRON AREA OF THE PROPOSED | | | DRIVEWAY, YOU MUST EXECUTE A PAVER DRIVEWAY AGREEMENT, | | | WHICH CAN BE OBTAINED HERE: HTTP://WPB.ORG/DEPARTMENTS/ | | | ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | GENERAL NOTES: | | | | | | DELETE CITY OF WEST PALM BEACH FROM WATER NOTE (PBC | | | WATER) | | | | | | PROVIDE APPROVAL FROM PBC WATER & SEWER FOR PROPOSED | | | POINTS OF CONNECTION FOR WATER AND SEWER. | | | | | | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF | | | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION FACILITIES LOCATED ON | | | THE RIGHT-OF-WAY. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | |
|
|
| Review Stop |
ENG-A |
ENGINEERING FORMAL REVIEW |
| Rev No |
1 |
Status |
P |
Date |
12-03-2018 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
12-03-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
mgonzale |
Date |
12-03-2018 |
Time |
09:46 |
Sent To |
I |
|
| Notes |
| 2018-12-03 09:53:16 | NOTE: THIS "ENG-A ENGINEERING FORMAL REVIEW" STOP WAS | | | ENTERED IN ERROR ON 12/3/2018. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
09-06-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
09-06-2018 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
09-06-2018 |
Time |
12:01 |
Sent To |
|
|
| Notes |
| 2018-09-06 12:55:23 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY CLASSIFICATION, PER THE FLORIDA FIRE | | | PREVENTION CODE, AND WHETHER IT IS MIXED OR SEPARATED | | | OCCUPANCY. PLEASE REVIEW NFPA 101, CHAPTER 6, OCCUPANCY | | | CLASSIFICATION FOR GUIDANCE ON HOW TO PROVIDE FOR THE | | | LIFE SAFETY REQUIREMENTS. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | CARBON MONOXIDE DETECTION SHALL BE PROVIDED IN | | | OCCUPIABLE AREAS ADJACENT TO, OR STROAGE OF, MOTOR | | | VEHICLE OPERATION. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
01-30-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
01-30-2019 |
Time |
12:14 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
01-30-2019 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2019-01-30 12:15:11 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: PALMS GATEWAY PCD MITSUBISHI Z18080018 | | | JANUARY 30, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE INCLUDE ALL CALCULATIONS FOR THE | | | WEST AND SOUTH BUFFER PORTIONS ON THE LANDSCAPE | | | REQUIREMENT CHART TO REFLECT WHAT IS CURRENTLY APPROVED | | | OR SHOW EQUIVALENT SUBSTITUTION. THE PROPOSED PALMS AND | | | SMALL TREES DO NOT MEET REQUIREMENTS. | | | | | | 2. SATISFIED. PROVIDE A TREE AS REQUIRED AND A TERMINAL | | | LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING | | | SPACES PER SECTION 94-443(C)(3). PROVIDE INTERIOR | | | ISLANDS WITH SPACING NO MORE THAN 10 SPACES IN A ROW. | | | PROVIDE DIVIDER ISLANDS AS REQUIRED. THERE ARE MULTIPLE | | | AREAS ON THE LANDSCAPE PLAN THAT DO NOT MEET THE | | | REQUIREMENTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4). | | | | | | 4. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES | | | MEET THE 75% SHADE TREE REQUIREMENT. | | | REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS | | | ADJACENT TO PARKING SPACES. | | | | | | 5. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE | | | LANDSCAPE PLAN. | | | | | | 6. SATISFIED. SHOW ALL REQUIRED CURBS ADJACENT TO | | | LANDSCAPE AREAS. WHEEL STOPS ARE SHOWN IN SOME AREAS. | | | REDUCING THE PAVED AREA AND PLACING THE CURB WITH | | | OVERHANG IS PREFERRED. | | | | | | 7. SATISFIED. CORRECT THE BUILDING PERIMETER LANDSCAPE | | | REQUIREMENT TO REFLECT THE REQUIRED AS 30% FOR | | | COMMERCIAL USE. | | | | | | 8. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY | | | LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT | | | COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT | | | TOLERANT. | | | | | | | | | 9. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | THE LIFT STATION IS NOT SHOWN WHERE APPROVED. | | | | | | | | | 10. SATISFIED. PLEASE PROVIDE THE LANDSCAPE | | | REQUIREMENTS, FLORIDA FRIENDLY LANDSCAPE CHART, | | | CALCULATIONS, AND PLANT LIST ON ONLY ONE PAGE OF THE | | | PLANS. | | | 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | 12. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL ABOVE | | | GROUND UTILITY VALVES AND BACKFLOWS PREVENTERS. | | | ADDITIONAL COMMENTS 10/2/18: | | | | | | 13. SATISFIED. THE LIGHT POLE AND FLAGPOLE CONFLICT | | | WITH THE GREEN BUTTONWOOD TREE CANOPY IN THE LANDSCAPE | | | ISLAND IN THE WESTERN ROW OF PARKING. STAFF WOULD | | | PREFER RELOCATION OF THE LIGHT POLE TO A LOCATION THAT | | | DOES NOT INTERFERE WITH THE TREES, AND AN EXPLANATION | | | AS TO THE | | | | | | 14. SATISFIED. SITE CALCULATIONS ON THE LANDSCAPE PLAN | | | AND SITE PLAN ARE NOT CONSISTENT, PLEASE REVISE. | | | | | | 15. SATISFIED. SEE RECOMMENDATION. STAFF IS CONCERNED | | | THAT THE LACK OF A LANDSCAPE BUFFER, ESPECIALLY TREE | | | CANOPY, ON THE EAST PROPERTY LINE COMBINED WITH THE | | | OPEN ASPHALT DISPLAY AREA CREATE A LARGE HEAT ISLAND. | | | THE DESIGN FOR DISPLAY AREA RATHER THAN A PARKING AREA | | | WAS NOT ANTICIPATED WHEN THE WAIVER FOR REMOVING THE | | | REQUIREMENT FOR LANDSCAPE BUFFERS ALONG INTERNAL | | | PROPERTY LINES WAS APPROVED. | | | | | | 16. SATISFIED. CROSS SECTIONS ARE NEEDED FOR THE | | | LANDSCAPE BUFFER AREAS THAT TRANSITION FROM RETAINING | | | WALL TO SLOPE ON THE SOUTH AND EAST PROPERTY LINES. | | | ALSO, INDICATE THE CONSTRUCTION MATERIAL OF THE | | | RETAINING WALL, AS THE CROSS SECTIONS SUBMITTED | | | INDICATE A POURED SOLID WALL VERSUS THE STACKED BLOCK | | | WALL THAT WAS INSTALLED ALONG THE EAST PROPERTY LINE | | | ALONG THE SELF STORAGE AND DEL TACO PARCELS. | | | ADDITIONAL COMMENTS 12/18/18: | | | 17. SATISFIED. THE TERMINAL LANDSCAPE ISLAND AT THE | | | NORTHWEST CORNER OF THE BUILDING DOES NOT MEET THE | | | REQUIREMENT OF RUNNING THE ENTIRE LENGTH OF THE PARKING | | | SPACE. IF A PARKING SPACE CAN BE ELIMINATED, THE | | | ACCESSIBLE SIDEWALK COULD BE MOVED TO THE EAST, CLOSER | | | TO THE BUILDING AND ALLOWING THE LANDSCAPE ISLAND TO | | | EXPAND TO MEET THE REQUIREMENT. | | | 18. SATISFIED. A TREE SEEMS TO BE MISSING FROM THE | | | BUFFER AREA EAST OF THE WEST ENTRANCE INTO THE SITE | | | FROM THE ACCESS ROAD. THERE IS A LABEL -SOD A- WHERE A | | | TREE CAN BE PLACED. | | | | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
12-18-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-18-2018 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-18-2018 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2018-12-18 16:42:45 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: PALMS GATEWAY PCD MITSUBISHI Z18080018 | | | DECEMBER 12, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE INCLUDE ALL CALCULATIONS FOR THE | | | WEST AND SOUTH BUFFER PORTIONS ON THE LANDSCAPE | | | REQUIREMENT CHART TO REFLECT WHAT IS CURRENTLY APPROVED | | | OR SHOW EQUIVALENT SUBSTITUTION. THE PROPOSED PALMS AND | | | SMALL TREES DO NOT MEET REQUIREMENTS. | | | | | | 2. SATISFIED. PROVIDE A TREE AS REQUIRED AND A TERMINAL | | | LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING | | | SPACES PER SECTION 94-443(C)(3). PROVIDE INTERIOR | | | ISLANDS WITH SPACING NO MORE THAN 10 SPACES IN A ROW. | | | PROVIDE DIVIDER ISLANDS AS REQUIRED. THERE ARE MULTIPLE | | | AREAS ON THE LANDSCAPE PLAN THAT DO NOT MEET THE | | | REQUIREMENTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4). | | | | | | 4. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES | | | MEET THE 75% SHADE TREE REQUIREMENT. | | | REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS | | | ADJACENT TO PARKING SPACES. | | | | | | 5. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE | | | LANDSCAPE PLAN. | | | | | | 6. SATISFIED. SHOW ALL REQUIRED CURBS ADJACENT TO | | | LANDSCAPE AREAS. WHEEL STOPS ARE SHOWN IN SOME AREAS. | | | REDUCING THE PAVED AREA AND PLACING THE CURB WITH | | | OVERHANG IS PREFERRED. | | | | | | 7. SATISFIED. CORRECT THE BUILDING PERIMETER LANDSCAPE | | | REQUIREMENT TO REFLECT THE REQUIRED AS 30% FOR | | | COMMERCIAL USE. | | | | | | 8. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY | | | LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT | | | COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT | | | TOLERANT. | | | | | | | | | 9. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | THE LIFT STATION IS NOT SHOWN WHERE APPROVED. | | | | | | | | | 10. SATISFIED. PLEASE PROVIDE THE LANDSCAPE | | | REQUIREMENTS, FLORIDA FRIENDLY LANDSCAPE CHART, | | | CALCULATIONS, AND PLANT LIST ON ONLY ONE PAGE OF THE | | | PLANS. | | | 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | 12. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL ABOVE | | | GROUND UTILITY VALVES AND BACKFLOWS PREVENTERS. | | | ADDITIONAL COMMENTS 10/2/18: | | | | | | 13. SATISFIED. THE LIGHT POLE AND FLAGPOLE CONFLICT | | | WITH THE GREEN BUTTONWOOD TREE CANOPY IN THE LANDSCAPE | | | ISLAND IN THE WESTERN ROW OF PARKING. STAFF WOULD | | | PREFER RELOCATION OF THE LIGHT POLE TO A LOCATION THAT | | | DOES NOT INTERFERE WITH THE TREES, AND AN EXPLANATION | | | AS TO THE | | | | | | 14. SATISFIED. SITE CALCULATIONS ON THE LANDSCAPE PLAN | | | AND SITE PLAN ARE NOT CONSISTENT, PLEASE REVISE. | | | | | | 15. SATISFIED. SEE RECOMMENDATION. STAFF IS CONCERNED | | | THAT THE LACK OF A LANDSCAPE BUFFER, ESPECIALLY TREE | | | CANOPY, ON THE EAST PROPERTY LINE COMBINED WITH THE | | | OPEN ASPHALT DISPLAY AREA CREATE A LARGE HEAT ISLAND. | | | THE DESIGN FOR DISPLAY AREA RATHER THAN A PARKING AREA | | | WAS NOT ANTICIPATED WHEN THE WAIVER FOR REMOVING THE | | | REQUIREMENT FOR LANDSCAPE BUFFERS ALONG INTERNAL | | | PROPERTY LINES WAS APPROVED. | | | | | | 16. SATISFIED. CROSS SECTIONS ARE NEEDED FOR THE | | | LANDSCAPE BUFFER AREAS THAT TRANSITION FROM RETAINING | | | WALL TO SLOPE ON THE SOUTH AND EAST PROPERTY LINES. | | | ALSO, INDICATE THE CONSTRUCTION MATERIAL OF THE | | | RETAINING WALL, AS THE CROSS SECTIONS SUBMITTED | | | INDICATE A POURED SOLID WALL VERSUS THE STACKED BLOCK | | | WALL THAT WAS INSTALLED ALONG THE EAST PROPERTY LINE | | | ALONG THE SELF STORAGE AND DEL TACO PARCELS. | | | ADDITIONAL COMMENTS 12/18/18: | | | 17. THE TERMINAL LANDSCAPE ISLAND AT THE NORTHWEST | | | CORNER OF THE BUILDING DOES NOT MEET THE REQUIREMENT OF | | | RUNNING THE ENTIRE LENGTH OF THE PARKING SPACE. IF A | | | PARKING SPACE CAN BE ELIMINATED, THE ACCESSIBLE | | | SIDEWALK COULD BE MOVED TO THE EAST, CLOSER TO THE | | | BUILDING AND ALLOWING THE LANDSCAPE ISLAND TO EXPAND TO | | | MEET THE REQUIREMENT. | | | 18. A TREE SEEMS TO BE MISSING FROM THE BUFFER AREA | | | EAST OF THE WEST ENTRANCE INTO THE SITE FROM THE ACCESS | | | ROAD. THERE IS A LABEL -SOD A- WHERE A TREE CAN BE | | | PLACED. | | | | | | STAFF RECOMMENDATION: STAFF IS CONCERNED THAT THE LACK | | | OF TREE CANOPY IN THE OPEN ASPHALT DISPLAY AREA AT THE | | | EAST SIDE OF THE SITE CREATES A LARGE HEAT ISLAND. THE | | | USE OF THE PROPERTY FOR DISPLAY AREA RATHER THAN A | | | PARKING AREA WAS NOT ANTICIPATED WHEN THE WAIVER FOR | | | REMOVING THE REQUIREMENT FOR LANDSCAPE BUFFERS ALONG | | | INTERNAL PROPERTY LINES WAS APPROVED FOR THE PD. | | | PLACEMENT OF SOME TREES IN THIS AREA, ALTHOUGH NOT | | | REQUIRED, WOULD IMPROVE THE PROJECT. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
11-05-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
11-02-2018 |
Time |
13:48 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
11-02-2018 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2018-11-05 13:49:43 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: PALMS GATEWAY PCD MITSUBISHI Z18080018 | | | NOVEMBER 2, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE INCLUDE ALL CALCULATIONS FOR THE | | | WEST AND SOUTH BUFFER PORTIONS ON THE LANDSCAPE | | | REQUIREMENT CHART TO REFLECT WHAT IS CURRENTLY APPROVED | | | OR SHOW EQUIVALENT SUBSTITUTION. THE PROPOSED PALMS AND | | | SMALL TREES DO NOT MEET REQUIREMENTS. | | | | | | 2. SATISFIED. PROVIDE A TREE AS REQUIRED AND A TERMINAL | | | LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING | | | SPACES PER SECTION 94-443(C)(3). PROVIDE INTERIOR | | | ISLANDS WITH SPACING NO MORE THAN 10 SPACES IN A ROW. | | | PROVIDE DIVIDER ISLANDS AS REQUIRED. THERE ARE MULTIPLE | | | AREAS ON THE LANDSCAPE PLAN THAT DO NOT MEET THE | | | REQUIREMENTS. | | | | | | 3. SATISFIED. PROVIDE A PLAN SHOWING THE PARKING | | | LANDSCAPE AREAS COUNTED TOWARD COMPLIANCE WITH SECTION | | | 94-443(C)(3) AND (4). | | | | | | 4. SATISFIED. SHOW THAT THE REQUIRED PARKING LOT TREES | | | MEET THE 75% SHADE TREE REQUIREMENT. | | | REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS | | | ADJACENT TO PARKING SPACES. | | | | | | 5. SATISFIED. SHOW ALL PARKING SPACE ROW COUNTS ON THE | | | LANDSCAPE PLAN. | | | | | | 6. SATISFIED. SHOW ALL REQUIRED CURBS ADJACENT TO | | | LANDSCAPE AREAS. WHEEL STOPS ARE SHOWN IN SOME AREAS. | | | REDUCING THE PAVED AREA AND PLACING THE CURB WITH | | | OVERHANG IS PREFERRED. | | | | | | 7. SATISFIED. CORRECT THE BUILDING PERIMETER LANDSCAPE | | | REQUIREMENT TO REFLECT THE REQUIRED AS 30% FOR | | | COMMERCIAL USE. | | | | | | 8. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY | | | LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT | | | COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT | | | TOLERANT. | | | | | | | | | 9. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | THE LIFT STATION IS NOT SHOWN WHERE APPROVED. | | | | | | | | | 10. SATISFIED. PLEASE PROVIDE THE LANDSCAPE | | | REQUIREMENTS, FLORIDA FRIENDLY LANDSCAPE CHART, | | | CALCULATIONS, AND PLANT LIST ON ONLY ONE PAGE OF THE | | | PLANS. | | | 11. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | 12. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL ABOVE | | | GROUND UTILITY VALVES AND BACKFLOWS PREVENTERS. | | | | | | | | | ADDITIONAL COMMENTS 10/2/18: | | | | | | 13. THE LIGHT POLE AND FLAGPOLE CONFLICT WITH THE GREEN | | | BUTTONWOOD TREE CANOPY IN THE LANDSCAPE ISLAND IN THE | | | WESTERN ROW OF PARKING. STAFF WOULD PREFER RELOCATION | | | OF THE LIGHT POLE TO A LOCATION THAT DOES NOT INTERFERE | | | WITH THE TREES, AND AN EXPLANATION AS TO THE | | | | | | 14. SITE CALCULATIONS ON THE LANDSCAPE PLAN AND SITE | | | PLAN ARE NOT CONSISTENT, PLEASE REVISE. | | | | | | 15. STAFF IS CONCERNED THAT THE LACK OF A LANDSCAPE | | | BUFFER, ESPECIALLY TREE CANOPY, ON THE EAST PROPERTY | | | LINE COMBINED WITH THE OPEN ASPHALT DISPLAY AREA CREATE | | | A LARGE HEAT ISLAND. THE DESIGN FOR DISPLAY AREA RATHER | | | THAN A PARKING AREA WAS NOT ANTICIPATED WHEN THE WAIVER | | | FOR REMOVING THE REQUIREMENT FOR LANDSCAPE BUFFERS | | | ALONG INTERNAL PROPERTY LINES WAS APPROVED. | | | | | | 16. CROSS SECTIONS ARE NEEDED FOR THE LANDSCAPE BUFFER | | | AREAS THAT TRANSITION FROM RETAINING WALL TO SLOPE ON | | | THE SOUTH AND EAST PROPERTY LINES. ALSO, INDICATE THE | | | CONSTRUCTION MATERIAL OF THE RETAINING WALL, AS THE | | | CROSS SECTIONS SUBMITTED INDICATE A POURED SOLID WALL | | | VERSUS THE STACKED BLOCK WALL THAT WAS INSTALLED ALONG | | | THE EAST PROPERTY LINE ALONG THE SELF STORAGE AND DEL | | | TACO PARCELS. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
09-17-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-17-2018 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-17-2018 |
Time |
16:58 |
Sent To |
|
|
| Notes |
| 2018-09-17 16:59:35 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: PALMS GATEWAY PCD MITSUBISHI Z18080018 | | | SEPTEMBER 17, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE INCLUDE ALL CALCULATIONS FOR THE WEST AND | | | SOUTH BUFFER PORTIONS ON THE LANDSCAPE REQUIREMENT | | | CHART TO REFLECT WHAT IS CURRENTLY APPROVED OR SHOW | | | EQUIVALENT SUBSTITUTION. THE PROPOSED PALMS AND SMALL | | | TREES DO NOT MEET REQUIREMENTS. | | | | | | 2. PROVIDE A TREE AS REQUIRED AND A TERMINAL LANDSCAPE | | | ISLAND AT THE END OF EACH ROW OF PARKING SPACES PER | | | SECTION 94-443(C)(3). PROVIDE INTERIOR ISLANDS WITH | | | SPACING NO MORE THAN 10 SPACES IN A ROW. PROVIDE | | | DIVIDER ISLANDS AS REQUIRED. THERE ARE MULTIPLE AREAS | | | ON THE LANDSCAPE PLAN THAT DO NOT MEET THE | | | REQUIREMENTS. | | | | | | 3. PROVIDE A PLAN SHOWING THE PARKING LANDSCAPE AREAS | | | COUNTED TOWARD COMPLIANCE WITH SECTION 94-443(C)(3) AND | | | (4). | | | | | | 4. SHOW THAT THE REQUIRED PARKING LOT TREES MEET THE | | | 75% SHADE TREE REQUIREMENT. | | | REQUIRED TREES INCLUDE ALL TERMINAL ISLAND AND ISLANDS | | | ADJACENT TO PARKING SPACES. | | | | | | 5. SHOW ALL PARKING SPACE ROW COUNTS ON THE LANDSCAPE | | | PLAN. | | | | | | 6. SHOW ALL REQUIRED CURBS ADJACENT TO LANDSCAPE AREAS. | | | WHEEL STOPS ARE SHOWN IN SOME AREAS. REDUCING THE PAVED | | | AREA AND PLACING THE CURB WITH OVERHANG IS PREFERRED. | | | | | | 7. CORRECT THE BUILDING PERIMETER LANDSCAPE REQUIREMENT | | | TO REFLECT THE REQUIRED AS 30% FOR COMMERCIAL USE. | | | | | | 8. PLEASE CORRECT THE FLORIDA FRIENDLY LANDSCAPE CHART | | | SO THAT TREES AND SHRUBS ARE NOT COUNTED TWICE FOR EACH | | | CATEGORY OF NATIVE AND DROUGHT TOLERANT. | | | | | | | | | 9. THE LOCATIONS OF WATER AND SEWER LINES ON THE | | | LANDSCAPE PLAN SHOW MANY CONFLICTS WITH TREES AND | | | LANDSCAPING. RELOCATE UTILITY LOCATIONS OR EXPAND | | | LANDSCAPE AREAS TO ACCOMMODATE REQUIRED LANDSCAPING. | | | THE LIFT STATION IS NOT SHOWN WHERE APPROVED. | | | | | | | | | 10. PLEASE PROVIDE THE LANDSCAPE REQUIREMENTS, FLORIDA | | | FRIENDLY LANDSCAPE CHART, CALCULATIONS, AND PLANT LIST | | | ON ONLY ONE PAGE OF THE PLANS. | | | 11. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | 12. PLEASE PROVIDE SCREENING FOR ALL ABOVE GROUND | | | UTILITY VALVES AND BACKFLOWS PREVENTERS. | | | | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
P |
Date |
02-15-2019 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
02-15-2019 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
02-15-2019 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2019-02-15 11:25:19 | THE FOLLOWING COMMENTS ARE FROM THE JANUARY 23, 2019 | | | PLAN REVIEW PACKAGE: | | | | | | CONDITION FOR SITE PLAN APPROVAL: | | | 1. PROVIDE DOCUMENTATION THAT THE PROPOSED CHANGES TO | | | POND 1 ON TRACTS 3 AND 4 HAS BEEN APPROVED BY THE | | | REQUIRED PARTIES PURSUANT TO THE DECLARATION OF | | | CONVENANTS, CONDITIONS AND RESTRICTIONS AND RECIPROCAL | | | EASEMENT AGREEMENT RECORDED BEGINNING ON PAGE 1743 OF | | | PALM BEACH COUNTY OFFICIAL RECORDS BOOK 29483. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
P |
Date |
12-10-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-10-2018 |
Time |
06:25 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-10-2018 |
Time |
06:33 |
Sent To |
|
|
| Notes |
| 2018-12-10 06:32:07 | THE COMMENTS BELOW ARE FROM THE REVIEW OF THE NOVEMBER | | | 30, 2018 SUBMITTAL PACKAGE. | | | | | | THE FOLLOWING COMMENT #1 CAN BE A CONDITION OF SITE | | | PLAN APPROVAL: | | | 1. PROVIDE DOCUMENTATION THAT THE PROPOSED CHANGES TO | | | POND 1 ON TRACTS 3 AND 4 HAS BEEN APPROVED BY THE | | | REQUIRED PARTIES PURSUANT TO THE DECLARATION OF | | | CONVENANTS, CONDITIONS AND RESTRICTIONS AND RECIPROCAL | | | EASEMENT AGREEMENT RECORDED BEGINNING ON PAGE 1743 OF | | | PALM BEACH COUNTY OFFICIAL RECORDS BOOK 29483. | | | | | | 2. SUGGEST PUTTING ROOT BARRIERS BETWEEN TREES AND | | | STORM DRAINAGE SYSTEM AT THE SOUTHWEST CORNER OF THE | | | SITE. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
11-05-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
11-05-2018 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
11-05-2018 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2018-11-05 17:27:19 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE | | | OCTOBER 26, 2018 SUBMITTAL PACKAGE: | | | | | | 1. VERIFY THE PROPOSED CHANGES TO POND 1 ON TRACTS 3 | | | AND 4 WILL BE APPROVED PURSUANT TO THE DECLARATION OF | | | CONVENANTS, CONDITIONS AND RESTRICTIONS AND RECIPROCAL | | | EASEMENT AGREEMENT RECORDED BEGINNING ON PAGE 1743 OF | | | PALM BEACH COUNTY OFFICIAL RECORDS BOOK 29483. | | | SPECIFICALLY SECTION 2.1 (B) OF THE DOCUMENT STATES: | | | "... THE STORM WATER DETENTION AREAS INDICATED ON THE | | | SITE PLAN, AND ALL LINES, CONDUITS, PIPES AND OTHER | | | APPARATUS FOR WATER DRAINAGE, AND ALL STORAGE SYSTEMS | | | NECESSARY IN CONNECTION THEREWITH, SHALL BE HEREINAFTER | | | CALLED THE 'WATER DETENTION AND DRAINAGE FACILITIES'." | | | ... "THE WATER DETENTION AND DRAINAGE FACILITIES | | | REQUIRED FOR EACH TRACT SHALL INITIALLY BE CONSTRUCTED | | | BY TRACT 1 OWNER IN ACCORDANCE WITH THE SITE PLAN AND | | | PURSUANT TO PLANS APPROVED BY WAWA UNDER THE WAWA | | | LEASE, AS A PART OF THE INITIAL DEVELOPMENT OF THE WAWA | | | IMPROVEMENTS ON TRACT 1 UNDER THE WAWA LEASE. ONCE | | | CONSTRUCTED, THE WATER DETENTION AND DRAINAGE | | | FACILITITES SHALL NOT BE MODIFIED, ALTERED, RELOCATED | | | OR OTHERWISE CHANGED, WITHOUT THE PRIOR WRITTEN CONSENT | | | OF ALL OWNERS AND WAWA (DURING THE CONTINUANCE OF THE | | | WAWA LEASE)." | | | | | | 2. VERIFY THE DRAINAGE SYSTEM (AND CALCULATIONS) FOR | | | TRACT 3 INCLUDES THE RUNOFF FROM THE RIGHT-OF-WAY AS | | | SPECIFIED IN SECTION 2.1 (B) OF THE ABOVE MENTIONED | | | CONVERANTS AGREEMENT. | | | | | | 3. IT IS STAFF'S UNDERSTANING THE POND 1 LOCATED ON | | | TRACTS 3 AND 4 IS TO BE USED FOR THE RUNOFF FROM TRACT | | | 3 AND TRACT 4. THE EXISTING CONTROL STRUCTURE IN POND 1 | | | WILL RELEASE WATER OFFSITE VIA THE BLEEDER ORIFICE AS | | | WELL WHEN THE STAGES IN THE POND EXCEED THE GRATE | | | ELEVATION OF THE CONTROL STRUCTURE, SAID GRATE BEING | | | OVER 4 FEET ABOVE THE POND BOTTOM. PLEASE ADVISE HOW | | | THE PROPOSED STORMWATER EQUALIZEER PIPE SYSTEM ON TRACT | | | 3 BETWEEN POND 1 AND THE SWALE ALONG AUSTRALIAN AVE. ON | | | THE WEST SIDE OF TRACT 3 WILL MAINTAIN WATER LEVELS IN | | | POND 1 FOR WATER QUALITY TREATMENT AND PEAK FLOW | | | ATTENUATION. IT APPEARS ALL OF THE WATER ENTERING THE | | | POND WILL FLOW TO THE SWALE SINCE THE SWALE IS ABOUT 3 | | | FEET BELOW THE BOTTOM OF POND 1. | | | | | | 4. THE DRAINAGE CALCULATIONS SHOULD INCLUDE TRACT 4 | | | DEVELOPMENT'S LAND USE AREAS. | | | | | | 5. THE RESPONSES TO THE FIRST SET OF COMMENTS INDICATED | | | THE SFWMD OR FDEP ERP MODIFICATION IS INCLUDED WITH | | | THIS SUBMITTAL PACKAGE. THIS DOCUMENT WAS NOT FOUND. | | | | | | 6. VERIFY THE PROPOSED SIDEWALK ALONG THE ENTRANCE ROAD | | | ON AUSTRALIAN AVE. WILL MEET ADA CRITERIA. THE SURVEY | | | SHOWS SPOT GRADES OF 13.50 AND 11.39 APPROXIMATELY 40 | | | FEET APART ALONG THE CURB RETURN EDGE OF PAVEMENT, | | | WHICH IS STEEPER THAN 5% SLOPE. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERRING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
09-12-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-12-2018 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-12-2018 |
Time |
08:01 |
Sent To |
|
|
| Notes |
| 2018-09-12 08:01:42 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS | | | ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION | | | EQUATION TO NGVD 1929 IS PROVIDED. THE CONVERSION | | | EQUATION IS NEEDED ON THE CONCEPTUAL PAVING, DRAINAGE, | | | WATER AND WASTEWATER PLAN AND ON THE BOUNDARY SURVEY. | | | | | | 2. SHOW ON THE CONCEPTUAL ENGINEERING PLAN THE AS-BUILT | | | INFORMATION OF THE CONTROL STRUCTURE FOR THE EXISTING | | | DETENTION AREA LOCATED ON THE EAST SIDE OF THE SITE. | | | | | | 3. IT APPEARS THE PROPOSED DRAINAGE SYSTEM WILL CONNECT | | | THE EXISTING DETENTION AREA WITH THE PROPOSED SWALE ON | | | THE WEST SIDE OF THE SITE. EXPLAIN IF THIS CONNECTION | | | WILL REDUCE THE STAGING OF WATER IN THE DETENTION AREA | | | AND IF THIS ?LOST STORAGE? WILL BE MADE UP IN THE | | | SWALE. INDICATE IF OTHER PARCELS ARE USING THE | | | DETENTION AREA FOR DRAINAGE STORAGE. | | | | | | 4. AUSTRALIAN AVE AND BELVEDERE ROAD ARE MAINTAINED BY | | | PALM BEACH COUNTY. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. PROVIDE SFWMD ERP FOR THE DEVELOPMENT. | | | | | | 3. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
P |
Date |
09-12-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-12-2018 |
Time |
10:34 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-12 10:36:24 | PROVIDE CONVERSION FROM NAVD 88 TO NGVD-29 ON SURVEY | | | AND ENG. PLANS. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
07-29-2020 |
|
|
Cont ID |
|
| Sent By |
|
Date |
08-14-2020 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
07-17-2020 |
Time |
|
Sent To |
|
|
| Notes |
| 2020-07-29 12:27:45 | TRAFFIC COMMENTS: | | | | | | NO FURTHER COMMENTS. | | | | | | VALERIO ORICCHIO | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
11-01-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-01 15:03:19 | PASSED WITH THE FOLLOWING CONDITION OF APPROVAL: | | | 1. PROVIDE TPS LETTER FROM PALM BEACH COUNTY | | | | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
09-06-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-06 15:53:48 | Z18080018 WEST PALM MITSUBISHI (AUGUST 14, 2018 | | | SUBMITTAL) | | | 1. PROVIDE TPS LETTER FROM PALM BEACH COUNTY. | | | 2. SUBJECT TO COUNTY APPROVAL, PROVIDE PROVIDE RAISED | | | CHANNELIZED MEDIAN AT THE DRIVEWAY ON AUSTRALIAN | | | AVENUE. | | | 3. SUBJECT TO COUNTY APPROVAL PROVIDE A PEDESTRIAN | | | REFUGE ISLAND AT AUSTRALIAN AVENUE DRIVEWAY. | | | 4. EXTEND THE SIDEWALK TO THE EAST FOR FUTURE | | | PEDESTRIAN CONNECTION TO OTHER TRACTS IN THE CPD. | | | 5. DESCRIBE PROPOSED ROUTE FOR DELIVERY OF CARS. | | | CLARIFY IF A LOADING ZONE IS REQUIRED. | | | | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
05-06-2019 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
05-06-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
05-06-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-12-02 16:48:19 | APPROVED WITH THE FOLLOWING CONDITIONS: | | | | | | 1.) NO BUILDING PERMITS FOR THE CONSTRUCTION OF THE | | | APPROVED USES SPECIFIED IN THE TRAFFIC PERFORMANCE | | | STANDARDS (TPS) REVIEW LETTER (#180513), DATED FEBRUARY | | | 13, 2019, BY THE PALM BEACH COUNTY TRAFFIC DIVISION, | | | SHALL BE ISSUED AFTER AUGUST 5, 2022. ALL OTHER | | | EXISTING CONDITIONS IN THE PREVIOUS TPS APPROVAL LETTER | | | (#160704) ISSUED BY THE COUNTY, DATED DECEMBER 14, 2016 | | | SHALL REMAIN VALID. | | | | | | 2.) PRIOR TO BUILDING PERMIT ISSUANCE FOR THE | | | MITSUBISHI DEVELOPMENT ON TRACT #3, DOCUMENTATION THAT | | | THE PROPOSED CHANGES TO POND 1 ON TRACTS 3 AND 4 HAS | | | BEEN APPROVED BY THE REQUIRED PARTIES PURSUANT TO THE | | | DECLARATION OF COVENANTS, CONDITIONS AND RESTRICTIONS | | | AND RECIPROCAL EASEMENT AGREEMENT RECORDED BEGINNINH ON | | | PAGE 1743 OF THE PALM BEACH COUNTY OFFICIAL RECORDS | | | BOOK 29483 SHALL BE SUBMITTED TO THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 3.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF ANY | | | EXISTING BUIDLING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL TO OR GREATER THAN $750,000.00 IS SUBJECT TO | | | THE ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
01-31-2019 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
01-31-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
01-31-2019 |
Time |
|
Sent To |
|
|
| Notes |
| 2019-01-31 11:27:39 | GENERAL COMMENTS: | | | | | | 1.) A COUNTY TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW | | | LETTER, INDICATING THAT THE PROPOSED PROJECT MEETS THE | | | TPS OF THE COUNTY SHALL BE SUBMITTED TO STAFF AS A | | | PREREQUISITE FOR MOVING FORWARD TO A PUBLIC HEARING. | | | [12/18/19 REPEAT COMMENT - STAFF IS STILL WAITING ON | | | THE TPS APPROVAL LETTER FROM THE COUNTY.] | | | ANY CHANGES TO A PLAN SHALL BE REFLECTED IN ALL PLANS | | | IN THE APPLICATION PACKET FOR CONSISTENCY. | | | | | | MASTER DEVELOPMENT PLAN (SHEET MP-1) COMMENTS: | | | | | | 1.) THE INFORMATION FOR TRACT #3 IN THE MASTER | | | DEVELOPMENT PLAN (NOT TABLE) HAS NOT BEEN CHANGED. | | | STAFF HAD REQUESTED THE INFORMATION BE CHANGED FROM | | | "USES PERMITTED IN THIS CPD SHALL INCLUDE ALL USES | | | PERMITTED BY-RIGHT WITHIN THE GC ZONING DISTRICT AND | | | ADDITIONAL USES AS APPROVED PER ORDINANCE NO. 4572-15" | | | TO "UP TO 14,683 SF - GFA AND ASSOCIATED PARKING." | | | [12/18/2018 REPEAT COMMENT] | | | | | | 2.) THE LEGEND NEEDS TO BE CORRECTED BASED ON REMOVED | | | INFORMATION. PLEASE ADDRESS. | | | | | | 3.) FOR THE LAND USE AND ZONING INFORMATION AND NOTES | | | FOR TRACT #3: A) THERE ARE STILL DISCREPANCIES IN THE | | | CALCULATIONS FOR OPEN SPACE AND PERVIOUS AREA; B) | | | FIGURES FOR: IMPERVIOUS AREA, BUILDING FOOTPRINT, | | | PAVEMENT/SIDEWALK, OPEN SPACE AND PERVIOUS SURFACE DOES | | | NOT MATCH THE INFORMATION PROVIDED IN THE SITE PLAN | | | (SHEET SP-1). PLEASE ADDRESS; C) CHECK MINIMUM OPEN | | | SPACE PERCENTAGE. IT DOES NOT MATCH THE INFORMATION | | | PROVIDED IN THE SITE PLAN (SHEET SP-1). | | | | | | SITE PLAN (SHEET SP-1): | | | | | | 1.) PLEASE EXPLAIN/CLARIFY THE FOLLOWING CALCULATIONS: | | | A) IMPERVIOUS BUILDING; B) OPEN SPACE; C) PARKING FOR | | | MOTOR VEHICLES AT 9,369 SQ. FT. | | | | | | 2.) IN THE REGULATING PLAN (SHEET SP-2), SECTION C | | | DETAIL (WEST LANDSCAPE BUFFER SEEMS TO HAVE THE | | | INCORRECT MEASUREMENTS (I.E. 16 FT. DEEP PARKING STALL | | | NOT 18 FT. DEEP). PLEASE ADDRESS. | | | | | | MASTER SIGN PLAN: | | | | | | 1.) PLEASE ADD THE REVISION DATE TO THE MASTER SIGN | | | PLAN SHEETS. THE REVISION DATE IS IMPORTANT TO KEEP | | | TRACK OF ALL CHANGES TO THE MASTER SIGN PLAN. | | | | | | ARCHITECTURAL PLANS: | | | 1.) THE DIMENSIONS FOR THE NORTH ELEVATION IS NOT | | | CLEAR. PLEASE ADDRESS ON SHEET A-201. | | | | | | PHOTOMETRIC PLAN: | | | | | | 1.) PHOTOMETRIC PLAN DOES NOT MATCH THE SITE PLAN. | | | PLEASE MAKE SURE THE LATEST LAYERS FOR THE SITE PLAN | | | ARE BEING USED FOR THE PHOTOMETRIC PLAN. [12/18/19 | | | REPEAT COMMENT] | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF | | | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 | | | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 | | | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY | | | RESULT IN ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
12-18-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
12-18-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
12-18-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-12-18 16:13:54 | GENERAL COMMENTS: | | | | | | 1.) A COUNTY TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW | | | LETTER, INDICATING THAT THE PROPOSED PROJECT MEETS THE | | | TPS OF THE COUNTY SHALL BE SUBMITTED TO STAFF AS A | | | PREREQUISITE FOR MOVING FORWARD TO A PUBLIC HEARING. | | | [9/18/18 REPEAT COMMENT - STAFF IS STILL WAITING ON THE | | | TPS APPROVAL LETTER FROM THE COUNTY.] | | | | | | 2.) ANY CHANGES TO A PLAN SHALL BE REFLECTED IN ALL | | | PLANS IN THE APPLICATION PACKET FOR CONSISTENCY. | | | | | | MASTER DEVELOPMENT PLAN (SHEET MP-1) COMMENTS: | | | | | | 1.) ONLY THE INTERNAL CROSS ACCESS WITHIN THE CPD | | | SHOULD BE DEPICTED IN THE MASTER DEVELOPMENT PLAN. | | | PLEASE REMOVE THE ACCESS POINT (NEW ARROW) INTO TRACT | | | #3, AS IT IS REDUNDANT INFORMATION TO THE MASTER | | | DEVELOPMENT PLAN. | | | | | | 2.) THE INFORMATION FOR TRACT #3 IN THE MASTER | | | DEVELOPMENT PLAN (NOT TABLE) HAS NOT BEEN CHANGED. | | | STAFF HAD REQUESTED THE INFORMATION BE CHANGED FROM | | | "USES PERMITTED IN THIS CPD SHALL INCLUDE ALL USES | | | PERMITTED BY-RIGHT WITHIN THE GC ZONING DISTRICT AND | | | ADDITIONAL USES AS APPROVED PER ORDINANCE NO. 4572-15" | | | TO "UP TO 14,683 SF - GFA AND ASSOCIATED PARKING." | | | | | | 3.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE | | | OVERALL DEVELOPMENT SITE DATA: THE FAR FOR MOTOR | | | VEHICLE SALES AND SERVICE HAS YET TO BE CHANGED TO | | | 0.04. | | | | | | 4.) FOR THE LAND USE AND ZONING INFORMATION AND NOTES | | | FOR TRACT #3: A.) THE USE FOR MOTOR VEHICLE SALES AND | | | SERVICE IS ?PROPOSED? (NOT APPROVED). B.) THE BUILDING | | | SETBACKS ARE LABELED INCORRECTLY: NORTH IS THE CORNER | | | SIDE (NOT FRONT), SOUTH IS THE SIDE (NOT REAR), EAST IS | | | THE REAR (NOT SIDE), AND WEST IS THE FRONT (NOT SIDE). | | | C.) THERE ARE STILL DISCREPANCIES IN THE CALCULATIONS | | | FOR OPEN SPACE AND PERVIOUS AREA. D.) FIGURES FOR: | | | IMPERVIOUS AREA, BUILDING FOOTPRINT, PAVEMENT/SIDEWALK, | | | OPEN SPACE AND PERVIOUS SURFACE DOES NOT MATCH THE | | | INFORMATION PROVIDED IN THE SITE PLAN (SHEET SP-1). | | | PLEASE ADDRESS. E.) CHECK MINIMUM OPEN SPACE | | | PERCENTAGE. IT DOES NOT MATCH THE INFORMATION PROVIDED | | | IN THE SITE PLAN (SHEET SP-1). | | | | | | SITE PLAN (SHEET SP-1): | | | | | | 1.) FOR THE USE INFORMATION PROVIDED FOR THE PARCEL | | | IMMEDIATELY NORTH: ZONING = COMMERCIAL PLANNED | | | DEVELOPMENT (CPD) (NOT GC), AND THE USE = C-STORE W/GAS | | | SALES (NOT FAST FOOD W/DRIVE-THRU/OFFICE) AS THE PARCEL | | | IMMEDIATELY NORTH OF PARCEL #3 IS WITHIN THE PALMS | | | GATEWAY CPD (NOT OUTSIDE). | | | | | | 2.) FOR THE USE INFORMATION PROVIDED FOR THE PARCEL | | | IMMEDIATELY EAST: ZONING = COMMERCIAL PLANNED | | | DEVELOPMENT (CPD) (NOT GC), AND THE USE = SELF-STORAGE | | | FACILITY (NOT MOTOR VEHICLE SALES) AS THE PARCEL | | | IMMEDIATELY EAST OF PARCEL #3 IS WITHIN THE PALMS | | | GATEWAY CPD (NOT OUTSIDE). | | | | | | 3.) PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA | | | TABULAR: A.) ACCORDING TO THE TABLE, 1,442 SQ. FT. OF | | | CANOPY AREA WILL BE PROVIDED; HOWEVER, THIS FIGURE DOES | | | NOT ADD UP IN SHEET A-102. B.) PROVIDE AN EXPLANATION | | | TO HOW THE 10% BUILDING COVERAGE WAS CALCULATED. C.) | | | PROVIDE AN EXPLANATION TO HOW THE 80% (13,285 SQ. FT.) | | | IMPERVIOUS AREA FOR BUILDINGS WAS CALCULATED. D.) CHECK | | | PARKING CALCULATIONS. OUTDOOR STORAGE AREA TOTAL DOES | | | NOT ADD UP TO 30,590 SQ. FT. PARKING CALCULATIONS MAY | | | NEED TO BE REVISED ACCORDINGLY. | | | | | | 4.) PLEASE ADDRESS THE FOLLOWING IN THE DEVELOPMENT | | | REGULATIONS TABLE: A.) THE MINIMUM LOT SIZE REQUIRED IS | | | 5,000 SQ. FT. (NOT 5 ACRES). B.) DIMENSIONS PROVIDED | | | FOR THE WIDTH AND FRONTAGE ARE INCORRECT. C.) | | | INFORMATION PROVIDED FOR: MAXIMUM BUILDING COVERAGE, | | | MAXIMUM IMPERVIOUS, MINIMUM OPEN SPACE, MINIMUM | | | LANDSCAPING SHALL MATCH THE NUMBERS PROVIDED IN THE | | | MASTER DEVELOPMENT PLAN (SHEET MP-1) FOR CONSISTENCY. | | | D.) SETBACK DIMENSIONS ARE INCORRECT, DUE TO THE | | | LABELING OF THE SETBACKS IN THE PLANS. | | | | | | 5.) THE SITE PLAN SHOWS TWO (2) ELECTRIC CAR CHARGE | | | STATIONS COUNTED TOWARDS THE REQUIRED PARKING. SINCE | | | THESE CHARGING STATIONS ARE MEANT FOR THE APPLICANT?S | | | CUSTOMERS ONLY AND ARE NOT OPEN TO OTHER TENANTS WITHIN | | | THE CPD (DEALERSHIP IS GATED FOR SECURITY), THESE | | | CHARGING STALLS CANNOT BE COUNTED AS REQUIRED PARKING. | | | PLEASE REVISE THE SITE PLAN AND PARKING CALCULATIONS | | | ACCORDINGLY. | | | | | | 6.) IN THE REGULATING PLAN (SHEET SP-2), PLEASE ADDRESS | | | THE FOLLOWING: A.) IDENTIFY WHERE IN THE SITE PLAN IS | | | THE DETAIL FOR PARKING AND STRIPING W/OVERHANG. B.) | | | BIKE RACK DETAIL MUST SHOW A 24-INCH CLEARANCE FROM THE | | | EDGE OF THE PAD TO THE RACK ON ALL SIDES. PLEASE | | | ILLUSTRATE TO DEMONSTRATE COMPLIANCE. C.) SECTION B | | | SHOWS A 30-INCH RAILING LOCATED WITHIN THE 2 FT. CURB | | | OVERHANG FOR VEHICLES. THIS IS NOT PERMITTED. D.) ENTRY | | | GATE DETAIL SHALL READ SECURITY GATE DETAIL TO MATCH | | | LANGUAGE ON SHEET SP-1. | | | | | | 7.) PROPOSED NEW MONUMENT SIGN SHALL BE SETBACK AT | | | LEAST 24 FT. FROM THE LOT LINE OF ANOTHER LOT. SITE | | | PLAN SHOWS A SETBACK DISTANCE OF 22 FT. FROM THE | | | ADJACENT LOT TO THE SOUTH. [ZLDR S.94-408(D)((2)(E.)] | | | | | | MASTER SIGN PLAN: | | | | | | 1.) THE APPLICANT SHOULD BE AWARE THAT THERE IS AN | | | APPROVED FREESTANDING MASTER SIGN PROGRAM FOR THE PALMS | | | GATEWAY CPD. ANY PROPOSED CHANGE SHOULD BE REFLECTED IN | | | THE JUSTIFICATION STATEMENT (INCLUDE DETAILS AND | | | JUSTIFICATION FOR THE PROPOSED NEW MONUMENT SIGN, ETC.) | | | AND IN THE APPROVED FREESTANDING MASTER SIGN PROGRAM. | | | STAFF IS STILL WAITING ON THE CHANGES TO THE | | | FREESTANDING MASTER SIGN PROGRAM. | | | | | | ARCHITECTURAL PLANS: | | | | | | 1.) SHEET A-101 SHOULD SHOW THE AMOUNT OF SERVICE AREA | | | IN SQUARE FEET. | | | | | | 2.) WHY IS THERE ARE CAR PARKED IN THE MIDDLE OF THE | | | DRIVE AISLE IN THE SERVICE AREA? | | | | | | 3.) CANOPY AREA CALCULATION ON SHEET A-102 DOES NOT | | | SEEM TO ADD UP TO THE FIGURE PROVIDE IN SHEET A-101 AND | | | IN THE SITE PLAN (SHEET SP-1). PLEASE ADDRESS FOR | | | CONSISTENCY. | | | | | | 4.) TYPO FOR "SECOND FLOOR" ON SHEET A-101. | | | | | | PHOTOMETRIC PLAN: | | | | | | * PHOTOMETRIC PLAN DOES NOT MATCH THE SITE PLAN. PLEASE | | | MAKE SURE THE LATEST LAYERS FOR THE SITE PLAN ARE BEING | | | USED FOR THE PHOTOMETRIC PLAN. | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF | | | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8 ? | | | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 | | | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY | | | RESULT IN ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
11-07-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
11-07-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
11-07-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-07 09:39:35 | GENERAL COMMENTS: | | | | | | 1.) A COUNTY TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW | | | LETTER, INDICATING THAT THE PROPOSED PROJECT MEETS THE | | | TPS OF THE COUNTY SHALL BE SUBMITTED TO STAFF AS A | | | PREREQUISITE FOR MOVING FORWARD TO A PUBLIC HEARING. | | | [9/18/18 REPEAT COMMENT ? STAFF IS STILL WAITING ON THE | | | TPS APPROVAL LETTER FROM THE COUNTY.] | | | | | | | | | MASTER DEVELOPMENT PLAN (SHEET MP-1) COMMENTS: | | | | | | 1.) CORRECT THE FOLLOWING LAND USE AND ZONING: A) | | | PARCEL IMMEDIATELY WEST OF THE PALMS GATEWAY CPD HAS A | | | LAND USE: C AND ZONING: CPD (NOT LAND USE: CS AND | | | ZONING: CS), B.) THE PARCEL LOCATED AT THE NORTHWEST | | | CORNER OF BELVEDERE ROAD AND AUSTRALIAN AVENUE HAS A | | | LAND USE: C AND ZONING: CPD (NOT LAND USE: CS AND | | | ZONING: CPD). | | | | | | 2.) FOR THE LAND USE AND ZONING INFORMATION AND NOTES | | | TABLES FOR TRACTS #2 AND #4, PLEASE CORRECT "PROPOSED | | | USE" TO "APPROVED USE" AS THE SITE PLANS FOR THESE | | | TRACTS HAVE ALREADY BEEN APPROVED. | | | | | | 3.) FOR THE LAND USE AND ZONING INFORMATION AND NOTES | | | FOR TRACT #3: A) THE CORRECT FAR FOR THE OVERALL CPD IS | | | 0.04 (NOT 0.03), B) PLEASE INCLUDE "TOTAL BUILDING | | | SIZE" INFORMATION, C) CHECK AREA CALCULATIONS. THE OPEN | | | SPACE, PERVIOUS AND IMPERVIOUS SURFACE CALCULATIONS DO | | | NOT ADD UP (DIFFERENCE OF 2,280 SQ. FT.). ALSO CHECK | | | THE PERCENTAGES. [NOTE: INCONSISTENCIES WITH THE | | | CALCULATIONS HAVE BEEN CONFIRMED WITH THE CITY'S | | | LANDSCAPE PLANNER], D) ACCORDING TO THE ELEVATION | | | DRAWINGS, THE MAXIMUM HEIGHT OF THE PROPOSED BUILDING | | | IS 30 FT. (NOT 29 FT. AS NOTED). PLEASE ADDRESS FOR | | | CONSISTENCY, E) BUILDING FOOTPRINT CALCULATION DOES NOT | | | MATCH THE BUILDING FOOTPRINT CALCULATION PROVIDED IN | | | THE ARCHITECTURAL PLANS. PLEASE ADDRESS FOR | | | CONSISTENCY. | | | | | | 4.) THE FAR FOR TRACT #3 FOR THE ENTIRE DEVELOPMENT IS | | | 0.04 (NOT 0.03). PLEASE CORRECT. | | | | | | 5.) THE OVERALL FAR FOR THE ENTIRE DEVELOPMENT IS 0.37 | | | (NOT 0.36). PLEASE CORRECT. | | | | | | | | | SITE PLAN: | | | | | | 1.) SHOW SETBACK DISTANCE FROM THE LIGHT FIXTURE TO THE | | | PROPERTY LINE. SETBACK DIMENSIONS SEEM TO BE MISSING | | | FOR THE FIXTURES PROVIDED ALONG THE EAST PROPERTY LINE. | | | PLEASE NOTE THAT THE FIXTURES SHALL BE PLACED AT LEAST | | | 5 FT. FROM THE PROPERTY LINE. [ZLDR S.94-145(2)] | | | | | | 2.) CORRECT THE FUTURE LAND USE AND ZONING FOR THE | | | PARCEL ON THE WEST SIDE OF AUSTRALIAN AVENUE. THE | | | CORRECT FUTURE LAND USE IS COMMERCIAL (C) AND THE | | | CORRECT ZONING IS COMMERCIAL PLANNED DEVELOPMENT (CPD). | | | | | | 3.) PARKING CALCULATIONS INCORRECT. CALCULATION FOR | | | OUTDOOR STORAGE SHOULD INCLUDE ALL DISPLAY AREAS WITHIN | | | THE PROJECT. PLEASE REVISE CALCULATIONS. | | | | | | 4.) BICYCLE PARKING CALCULATIONS SHALL BE REVISED TO | | | REFLECT CORRECT CALCULATIONS. | | | | | | 5.) BICYCLE RACK DETAIL IS INCONSISTENT WITH THE | | | ILLUSTRATION IN THE SITE PLAN. PLEASE ADDRESS. | | | | | | 6.) ALL SECURITY GATES SHALL BE LABELED IN THE SITE | | | PLAN. | | | | | | 7.) WHERE IS THE ACCESS INTO THE LIFT STATION? PLEASE | | | ILLUSTRATE. IS THERE A PROPOSED FENCE AROUND THE LIFT | | | STATION? IF SO, PLEASE PROVIDE MORE INFORMATION (I.E. | | | HEIGHT, MATERIAL, ETC.) | | | | | | 8.) WHY IS THERE ONLY A PARTIAL RETAINING WALL ALONG | | | THE SOUTH AND EAST PROPERTY LINES? PLEASE PROVIDE AN | | | EXPLANATION. | | | | | | 9.) THE PROPOSED LOCATION OF THE FLAGPOLE MAY BE IN | | | CONFLICT WITH THE LANDSCAPING FOR THE PROJECT. PLEASE | | | VERIFY WITH THE CITY?S LANDSCAPE PLANNER, RAY CARANCI @ | | | 561-822-1462. | | | | | | 10.) INCONSISTENCIES DETECTED IN THE LOT MEASUREMENTS | | | PROVIDED IN THE DEVELOPMENT REGULATIONS TABLE WHEN | | | COMPARED TO THE SURVEY/SITE PLAN OF THE SUBJECT | | | PROPERTY AND IN THE SETBACKS (I.E. LOT FRONTAGE IS | | | AUSTRALIAN AVENUE, ETC.). PLEASE ADDRESS FOR | | | CONSISTENCY. | | | | | | 11.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE SITE | | | DATA TABULAR (SHEET SP-1): A) THE NAME OF THE CPD IS | | | "PALMS GATEWAY" (NOT "BW AUSTRALIAN AND BELVEDERE"), B) | | | "PROPOSED ZONING DISTRICT" SHOULD BE ELIMINATED, SINCE | | | THE ZONING OF THE PROPERTY IS NOT CHANGING, C) CHECK | | | THE CALCULATION FOR OPEN SPACE. THERE SEEMS TO BE A | | | DISCREPANCY WITH STAFF?S CALCULATION FOR OPEN SPACE, D) | | | ACCORDING TO THE ARCHITECTURAL ELEVATION, THE MAXIMUM | | | HEIGHT OF THE BUILDING IS 30 FT. (NOT 29 FT. AS NOTED). | | | PLEASE ADDRESS FOR CONSISTENCY, E) CALCULATIONS FOR THE | | | TOTAL PROPOSED NUMBER OF PARKING SPACES SHALL ALSO BE | | | PROVIDED IN THE DATA TABULAR, F) PER ZLDRS, ONE (1) 10 | | | FT. X 25 FT. LOADING ZONE IS REQUIRED FOR THE PROJECT. | | | PLEASE CORRECT IN THE TABLE. | | | | | | 12.) PLEASE ADDRESS THE FOLLOWING IN THE REGULATING | | | PLAN (SHEET SP-2): A) PROVIDE DIMENSIONS (I.E. HEIGHT) | | | FOR THE PROPOSED RETAINING WALL, B) PROVIDE DIMENSIONS | | | (I.E. HEIGHT) FOR THE PROPOSED RAILING. | | | | | | | | | MASTER SIGN PLAN: | | | | | | 1.) THE APPLICANT SHOULD BE AWARE THAT THERE IS AN | | | APPROVED FREESTANDING MASTER SIGN PROGRAM FOR THE PALMS | | | GATEWAY CPD. ANY PROPOSED CHANGE SHOULD BE REFLECTED IN | | | THE JUSTIFICATION STATEMENT (INCLUDE DETAILS AND | | | JUSTIFICATION FOR THE PROPOSED NEW MONUMENT SIGN, ETC.) | | | AND IN THE APPROVED FREESTANDING MASTER SIGN PROGRAM. | | | | | | 2.) WHAT IS THE WIDTH OF THE PROPOSED MONUMENT SIGN. | | | | | | 3.) PLEASE NOTE THAT THE MAXIMUM ALLOWABLE SIGN AREA | | | (BOTH SIDES OF THE SIGN STRUCTURE) IS 222.46 SQ. FT. | | | THE PROPOSED SIGN AREA (194 SQ. FT. PER SIGN FACE) | | | SEEMS TO EXCEED THE ALLOWABLE SIGN AREA. | | | | | | | | | ARCHITECTURAL PLANS: | | | | | | 1.) FLOOR AREA CALCULATIONS IN THE FLOOR PLANS DO NOT | | | MATCH THE CALCULATIONS PROVIDED IN THE MASTER/SITE | | | PLAN. PLEASE ADDRESS FOR CONSISTENCY. | | | | | | 2.) LABEL GENERATOR ON THE NORTH ELEVATION. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF | | | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8 .5 | | | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 | | | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | * PLEASE NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY | | | RESULT IN ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
09-18-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
09-18-2018 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
09-18-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-18 10:13:34 | GENERAL COMMENTS: | | | | | | 1.) A COUNTY TRAFFIC PERFORMANCE STANDARDS (TPS) REVIEW | | | LETTER, INDICATING THAT THE PROPOSED PROJECT MEETS THE | | | TPS OF THE COUNTY SHALL BE SUBMITTED TO STAFF AS A | | | PREREQUISITE FOR MOVING FORWARD TO A PUBLIC HEARING. | | | | | | 2.) TWO (2) SETS OF ADDRESSED LABELS AFFIXED TO SIZE | | | #10 STAMPED ENVELOPES SHALL BE PROVIDED FOR EACH | | | PROPERTY OWNER WITHIN 500 FEET OF THE PROPERTY LINE AND | | | SHALL HAVE THE CITY'S ADDRESS AS THE RETURN LABEL. THE | | | SETS OF ENVELOPES WERE NOT SUBMITTED WITH THE | | | APPLICATION PACKET. | | | | | | 3.) THE MASTER DEVELOPMENT PLAN IS MISSING FROM THE | | | APPLICATION PACKET. THE MASTER PLAN REQUIRES AN UPDATE | | | AS PART OF THIS AMENDMENT. | | | | | | 4.) CALCULATIONS IN THE LANDSCAPE PLAN DOES NOT MATCH | | | THE CALCULATIONS PROVIDED IN THE SITE PLAN. PLEASE | | | ENSURE THE CALCULATIONS ARE CORRECT FOR CONSISTENCY. | | | | | | 5.) PLEASE REVISE THE JUSTIFICATION STATEMENT TO | | | ADDRESS THE FOLLOWING: A.) REVISE THE LANGUAGE TO STATE | | | THAT "MOTOR VEHICLE SALES AND SERVICE USE" IS A | | | PERMITTED USE BY RIGHT IN THE PALMS GATEWAY CPD. | | | CURRENT LANGUAGE SUGGESTS THAT THE REQUEST ALSO INCLUDE | | | AN AMENDMENT TO ADD THE USE TO THE LIST OF PERMITTED | | | USES. B.) PROVIDE JUSTIFICATION TO WHY THE MASTER SIGN | | | PROGRAM REQUIRES AN AMENDMENT. DOES THE PROPOSED | | | MONUMENT SIGN MEET CURRENT SIGN CODE STANDARDS? DOES | | | THE PROPOSED SIGNAGE REQUIRE A WAIVER? | | | | | | 6.) PER ZLDR S.94-207(A)(1), THE PROPOSED DEVELOPMENT | | | MUST DEMONSTRATE INNOVATIVE LAND PLANNING AND | | | DEVELOPMENT TECHNIQUES TO CREATE A MORE DESIRABLE AND | | | ATTRACTIVE DEVELOPMENT. PLEASE EXPLAIN IN THE | | | JUSTIFICATION STATEMENT TO HOW THIS STANDARD HAS BEEN | | | ADDRESSED IN THE PROPOSED PROJECT. STAFF BELIEVES THAT | | | THE PROJECT CAN BE IMPROVED THROUGH THE INCORPORATION | | | OF ADDITIONAL LANDSCAPING AND OTHER PEDESTRIAN FEATURES | | | TO INTERCONNECT THE PROJECT TO THE ADJACENT PARCELS. | | | | | | 7.) THE "NOTE" IN THE SITE PLAN INDICATES THAT THE BASE | | | INFORMATION WAS OBTAINED FROM A SURVEY DATED 3/19/2018; | | | HOWEVER, THE SURVEY SUBMITTED WITH THE APPLICATION HAS | | | A REVISION DATED 4/4/18. PLEASE ENSURE ALL INFORMATION | | | PROVIDED IN THE SITE/LANDSCAPE PLAN IS CONSISTENT WITH | | | THE REVISED SURVEY. AN UPDATED SIGNED AND SEALED SURVEY | | | MAY BE NECESSARY WITH THE RESUBMITTAL. | | | | | | 8.) PLEASE ENSURE ALL PLANS ARE CONSISTENT (I.E. | | | REVISIONS TO THE DIGITAL LAYERS, ETC.) | | | | | | | | | SITE PLAN COMMENTS: | | | | | | 1.)PER THE LANDSCAPE PLAN (NOT DEPICTED IN THE SITE | | | PLAN), THE (RELOCATED) LIFT STATION IS LOCATED OUTSIDE | | | OF THE PBC UTILITY EASEMENT AND DOES NOT CONNECT TO | | | TRACT #1 (DEL TACO RESTAURANT) AND TRACT #2 | | | (SELF-STORAGE FACILITY), AS SHOWN IN PREVIOUSLY | | | APPROVED PLANS. THE LOCATION OF THE LIFT STATION/SEWER | | | LINE CONNECTION IS ALSO INCONSISTENT WITH THE DEPICTION | | | OF THE SEWER COLLECTION SYSTEM FOR THE OVERALL PD | | | SPECIFIED IN THE DECLARATION OF COVENANTS, CONDITIONS | | | AND RESTRICTIONS AND RECIPROCAL EASEMENT AGREEMENT (ORB | | | 29483, PG 1743). PLEASE ADDRESS AND SHOW LOCATION OF | | | THE LIFT STATION IN THE SITE PLAN. | | | | | | 2.) PER THE DECLARATION OF COVENANTS, CONDITIONS AND | | | RESTRICTIONS AND RECIPROCAL EASEMENT AGREEMENT (ORB BK | | | 29483, PG 1743), THE DRAINAGE SWALE AREA FOR PARCEL #3 | | | IS 5,374 SQ. FT. ACCORDING TO THE SITE PLAN, THE | | | DRAINAGE AREA IS 4,534 SQ. FT. PLEASE ADDRESS THIS | | | DISCREPANCY. | | | | | | 3.) THE PROPOSED SITE CIRCULATION PATTERN IS | | | INCONSISTENT WITH THE CIRCULATION PATTERN ADOPTED BY | | | THE MASTER DEVELOPMENT PLAN (SHOWS ONCE ACCESS POINT | | | INTO THE PARCEL, NOT TWO). PLEASE ADDRESS FOR | | | CONSISTENCY. | | | | | | 4.) WORK WITH THE BUILDING DEPARTMENT TO ADDRESS A.D.A. | | | COMPLIANCE AND ACCESSIBILITY TO THE SITE FROM | | | AUSTRALIAN AVENUE. | | | | | | 5.) THE SIDEWALK ALONG THE NORTH END OF THE PARCEL | | | SHALL BE EXTENDED ALONG THE ENTIRE LENGTH OF THE SITE | | | TO PROVIDE INTERCONNECTIVITY WITH THE OTHER PARCELS IN | | | THE CPD. | | | | | | 6.) THE PLAN MUST SHOW HOW THE PROPOSED PARKING SPACES | | | ON-SITE WILL BE ALLOCATED (I.E. CUSTOMER/EMPLOYEE | | | PARKING, INVENTORY, ETC.) | | | | | | 7.) THE PROPOSED SECURITY GATES AT THE ACCESS POINTS | | | INTO TRACT #3 IS LOCATED WITHIN THE SIGHT VISIBILITY | | | TRIANGLES. PLEASE RELOCATE THE GATES OUTSIDE OF THE | | | SIGHT TRIANGLES. [ZLDR S.94-305(E)] | | | | | | 8.) A DETAIL OF THE SECURITY GATE (I.E. HEIGHT AND | | | DESIGN) SHALL BE INCLUDED IN THE PLAN SET. PLEASE NOTE | | | THAT THE HEIGHT OF THE SECURITY GATE CANNOT EXCEED 8 | | | FT. IN HEIGHT. [ZLDR S.94-302(C)] | | | | | | 9.) THERE ARE SEVERAL STRUCTURES LOCATED WITHIN THE | | | PALM BEACH COUNTY UTILITY EASEMENT (I.E. SECURITY | | | GATES, LIGHT FIXTURES, PARKING AREA AND SIDEWALK). AN | | | EASEMENT CONSENT/RELEASE FROM THE COUNTY SHALL BE | | | PROVIDED FOR THESE STRUCTURAL ELEMENTS. | | | | | | 10.) LIGHT FIXTURES SHALL BE SETBACK AT LEAST 5 FT. | | | FROM THE PROPERTY LINE. PLEASE ADDRESS. [ZLDR | | | S.94-145(2)] | | | | | | 11.) ALL FREESTANDING SIGNS (EXISTING AND PROPOSED) ON | | | THE PROPERTY SHALL COMPLY WITH REQUIREMENTS IN ZLDR S. | | | 94-408(D). PLEASE PROVIDE ADDITIONAL INFORMATION ON | | | DISTANCE SEPARATION AND SIGN AREA CALCULATIONS TO | | | DEMONSTRATE COMPLIANCE. | | | | | | 12.) WHAT IS THE SETBACK DISTANCE OF THE PROPOSED | | | MONUMENT SIGN FROM AUSTRALIAN AVENUE (SHOW SETBACK | | | DIMENSION IN THE PLAN)? | | | | | | 13.) ALL DIMENSIONS PROVIDED IN THE SIGN DETAIL HAVE | | | NOT BEEN PROVIDED ON SHEET SP-2 (I.E. WIDTH OF THE | | | PROPOSED MONUMENT SIGN). PLEASE ADDRESS. | | | | | | 14.) PLEASE DIMENSION OUT ALL TERMINAL ISLANDS IN THE | | | PARKING AREA. ALL TERMINAL ISLANDS SHALL BE A MINIMUM | | | OF 8 FT. (MEASURED FROM THE INSIDE CURB) AND NOT LESS | | | THAN THE LENGTH OF THE ADJACENT PARKING STALL. [ZLDR | | | S.94-443(C)(3)] | | | | | | 15.) ONE (1) INTERIOR ISLAND SHALL BE REQUIRED FOR | | | EVERY TEN (10) PARKING SPACES IN A ROW. THERE ARE | | | SEVERAL ROWS OF PARKING THAT EXCEED THE NUMBER OF | | | PARKING SPACES WITHOUT AN INTERIOR ISLAND. [ZLDR | | | S.94-443(C)(3)] | | | | | | 16.) SHOW DIMENSION FOR ALL WALKWAYS. A MINIMUM 7 FT. | | | WIDE SIDEWALK IS REQUIRED WHERE THERE IS VEHICULAR | | | OVERHANG. [ZLDR S.94-443, FIGURE XIV-2] | | | | | | 17.) A MINIMUM OF ONE 10 FT. X 25 FT. LOADING ZONE IS | | | REQUIRED FOR THE PROJECT. PLEASE SHOW THE LOCATION OF | | | THE LOADING ZONE. ADDITIONALLY, THE LOADING ZONE SHALL | | | BE LOCATED ON THE SAME PROPERTY WHICH THE USE/STRUCTURE | | | EXISTS. [ZLDR S.94-485] | | | | | | 18.) INFORMATION IS REQUIRED ON WHERE THE VEHICULAR | | | INVENTORY WILL BE UNLOADED/LOADED ON-SITE. | | | | | | 19.) BICYCLE PARKING SHALL BE LOCATED NEAR THE | | | PRINCIPAL ENTRANCE OF THE BUILDING. [ZLDR S.94-485(Q)] | | | | | | 20.) THE NOTATED RETAINING WALLS TO THE EAST AND WEST | | | SIDE OF THE PROPERTY IS NOT CLEARLY SHOWN IN THE PLAN. | | | PLEASE SHOW. | | | | | | 21.) HOW TALL ARE THE RETAINING WALLS? INCLUDE | | | DIMENSION IN THE PLAN/DETAIL. [ZLDR S.94-302(C)] | | | | | | 22.) WHAT IS THE HATCHING ALONG THE PERIMETER OF THE | | | PROPOSED BUILDING? THERE IS NO LEGEND THAT IDENTIFIES | | | THE HATCHING, NOR IS IT CONSISTENT WITH THE DETAILS IN | | | THE LANDSCAPE PLAN. | | | | | | 23.) DIMENSIONS/SHAPE OF THE DUMPSTER ENCLOSURE IN | | | SHEET SP-1 DOES NOT MATCH THE DUMPSTER ENCLOSURE DETAIL | | | PROVIDED IN SHEET SP-2. PLEASE ADDRESS FOR CONSISTENCY. | | | | | | 24.) WHAT IS THE AREA OF THE "LOOSE STONES" AT THE | | | NORTHEAST CORNER OF THE PROPERTY? | | | | | | 25.) THE "ACCESS EASEMENT" SEEMS TO BE EXCLUDED IN MOST | | | CALCULATIONS IN THE SITE DATA AND DEVELOPMENT | | | REGULATIONS TABLES. THE ACCESS EASEMENT IS WITHIN THE | | | PROPERTY LINE OF THE PROJECT AND THEREFORE, MUST BE | | | INCLUDED IN ALL CALCULATIONS. PLEASE CORRECT THE | | | CALCULATIONS TO INCLUDE THE ACCESS EASEMENT. | | | | | | 26.) PROVIDE DETAILS FOR THE FOLLOWING ELEMENTS: A.) | | | FLAG POLE STRUCTURE, B.) SECURITY GATES, C.) VEHICULAR | | | DISPLAY AREA (I.E. IS IT ELEVATED?), D.) PARKING STALL | | | DETAIL FOR SMALLER PARKING STALLS AND FOR STALLS WITH A | | | CURB OVERHANG. | | | | | | 27.) PLEASE ADDRESS THE FOLLOWING IN THE SITE DATA | | | TABULAR: A.) PROJECT NUMBER IS PB 1670J/Z18080018, B.) | | | INCLUDE BUILDING HEIGHT INFORMATION, C.) PARKING | | | CALCULATIONS SEEM TO BE INCORRECT; ALSO INCLUDE THE | | | TOTAL NUMBER OF PARKING SPACES PROVIDED FOR THE | | | PROJECT/PARKING ALLOCATION FOR SPECIFIC USES (I.E. | | | INVENTORY, CUSTOMER, ETC.), D.) BICYCLE PARKING | | | CALCULATION MISSING, E.) LOADING ZONING CALCULATION | | | MISSING | | | | | | 28.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE | | | DEVELOPMENT REGULATIONS TABLE: A.) ZONING DISTRICT IS | | | CPD (NOT PCD), B.) CHECK PERCENT CALCULATION FOR THE | | | LANDSCAPE PROVIDED. | | | | | | | | | LANDSCAPE PLAN COMMENTS: | | | | | | 1.) LANDSCAPE BUFFER ALONG THE SOUTH PROPERTY LINE | | | COULD BE WIDENED BY ELIMINATING THE WHEEL STOPS AND | | | SHORTENING THE PARKING STALLS TO A DEPTH OF 16 FT. | | | (CURRENTLY DIMENSIONED AT 18 FT.). | | | | | | 2.) LANDSCAPED AREA SHALL BE SEPARATED FROM VEHICULAR | | | USE AREAS BY NON-MOUNTABLE, CONCRETE CURBING OF THE | | | TYPE CHARACTERIZED AS "TYPE D". THERE SEEMS TO BE | | | SEVERAL AREAS IN THE SITE PLAN MISSING THE | | | NON-MOUNTABLE CURB, ADJACENT TO LANDSCAPED AREAS. | | | PLEASE MODIFY PLAN TO SHOW CURBING. [ZLDR | | | S.94-443(C)(3)] | | | | | | 3.) ADDITIONAL COMMENTS TO BE PROVIDED BY THE CITY'S | | | LANDSCAPE PLANNER, RAY CARANCI (561) 822-1462. | | | | | | | | | ARCHITECTURAL PLANS: | | | | | | 1.) STRUCTURAL OVERHANGS SHALL NOT PROJECT MORE THAN 3 | | | FT. INTO ANY SETBACK. PLEASE DEMONSTRATE COMPLIANCE BY | | | PROVIDING DIMENSIONS IN THE ELEVATION PLANS. [ZLDR | | | S.94-305(B)(2)] | | | | | | 2.) THERE SEEMS TO BE A STRUCTURAL ELEMENT THAT | | | PROJECTS BEYOND THE PARAPET AT THE SOUTH ELEVATION. | | | PLEASE IDENTIFY THIS ELEMENT. PLEASE NOTE THAT ANY | | | MECHANICAL EQUIPMENT SHALL BE SCREENED FROM VIEW BY THE | | | PARAPET. | | | | | | 3.) WHAT IS THE SECOND STORY BUILDING SQUARE FOOTAGE? | | | | | | 4.) PLEASE PROVIDE COLORED ELEVATIONS. | | | | | | | | | LIGHTING (PHOTOMETRIC) PLAN: | | | | | | 1.) THE PHOTOMETRIC PLAN IS INCONSISTENT WITH THE SITE | | | AND LANDSCAPE PLANS. PLEASE ENSURE USE OF THE SAME CAD | | | FILE/LAYERS FOR ALL PLANS. | | | | | | 2.) LIGHT POLE FIXTURES SHALL BE SETBACK AT LEAST 5 FT. | | | FROM THE PROPERTY LINES. PLEASE ADDRESS IN BOTH THE | | | SITE/LANDSCAPE PLANS AND PHOTOMETRIC PLAN FOR | | | CONSISTENCY. [ZLDR S.94-145(2)] | | | | | | 3.) LIGHT FIXTURES ARE WITHIN THE PBC UTILITY EASEMENT | | | LOCATED AT THE NORTH END OF THE PROPERTY. RELOCATE THE | | | LIGHT FIXTURES OUT OF THE UTILITY EASEMENT OR PROVIDE A | | | UTILITY EASEMENT CONSENT/RELEASE FROM THE COUNTY FOR | | | ALL STRUCTURES WITHIN THE EASEMENT. | | | | | | 4.) ALL EXTERIOR LIGHTING SHALL BE SHIELDED TO REDUCE | | | GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE | | | AWAY FROM PUBLIC THOROUGHFARES. [ZLDR S.94-309(A)] | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF | | | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 | | | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 | | | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | * ANY CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT ($600.00) OF THE ORIGINAL | | | APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| |
Print |
|