Plan Review Details - Project Z18080015
Plan Review Stops For Project Z18080015
Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status N Date 10-01-2018 Cont ID  
Sent By jroach Date 10-01-2018 Time 12:24 Rev Time 0.00
Received By jroach Date 10-01-2018 Time 12:24 Sent To  
Notes
2018-10-01 12:25:51PER EMAIL FROM S. WELTER, DATED OCTOBER 1, 2018, THIS
 PROJECT IS EXEMPT FROM AIPP REQUIREMENTS AS PBAU IS A
 NON-PROFIT. TAX EXEMPTION CERTIFICATE IS ATTACHED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 09-11-2018 Cont ID  
Sent By rbrown Date 09-11-2018 Time 12:56 Rev Time 0.00
Received By rbrown Date 09-11-2018 Time 10:27 Sent To  
Notes
2018-09-11 13:04:41DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT
 WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL
 HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 6. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 10-18-2018 Cont ID  
Sent By rrossano Date 10-18-2018 Time   Rev Time 0.00
Received By   Date 10-18-2018 Time   Sent To I
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 09-17-2018 Cont ID  
Sent By RRossano Date 09-18-2018 Time   Rev Time 2.00
Received By rrossano Date 09-18-2018 Time   Sent To  
Notes
2018-09-18 15:46:42THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS
 AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE
 DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER
 UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT
 PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW:
 HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W
 EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P
 ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19
 60045731D3658206F27451722716EF
  
 THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE
 FOUND HERE:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA,
 CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22,
 2008. (SUPPLEMENT NO. 18)
 CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL,
 SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER
 SERVICE FACILITIES OF THE CITY.
 THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE
 CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY
 BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS,
 BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION.
 PROVIDE CCTV VIDEO OF EXISTING SANITARY SEWER ALONG
 ENTIRE PROJECT FRONTAGE.
  
 PLEASE SUBMIT A FORMAL AS-BUILT REQUEST FOR ALL CITY OF
 WEST PALM BEACH-OWNED UTILITIES WITHIN THE PUBLIC RIGHT
 OF WAY FOR THE ENTIRE EXTENT OF THE LIMITS OF YOUR
 PROJECT. IDENTIFY TYPE OF UTILITY, LOCATION, PIPE
 MATERIAL, AGE AND SIZE. PLEASE CONTACT JANICE TARBILL
 IN THE WPB ENGINEERING SERVICES DEPARTMENT AT
 [email protected] OR 561-494-1079 FOR FURTHER
 ASSISTANCE.
  
 PROVIDE EXISTING AND PROPOSED FLOWS FOR WATER & SEWER.
 CALCULATIONS SHALL BE PER FAC 64E-6 FOR SEWER AND PER
 FAC 64-E.008 FOR WATER.
  
 AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR
 MORE INFORMATION, REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF
 ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES,
 INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND
 SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES,
 METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE
 SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING
 GRADES, PIPES SIZES, MATERIALS, ELEVATIONS,
 ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL
 INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER
 LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE
 PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN
 VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS.
  
 PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED
 UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC,
 ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION
 FACILITIES LOCATED ON THE RIGHT-OF-WAY.
  
 PROVIDE PROFILE VIEW OF ALL UTILITY CONFLICTS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 10-11-2018 Cont ID  
Sent By pleduc Date 10-11-2018 Time   Rev Time 0.00
Received By pleduc Date 10-11-2018 Time 13:29 Sent To  
Notes
2018-10-11 13:57:192ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC INFORMATION PACKET AND
 RESPONSE LETTER DATED OCTOBER 5, 2018, FROM URBAN
 DESIGN KILDAY STUDIOS, TO JOHN P. ROACH, AICP,
 PRINCIPLE PLANNER, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
 2ND REVIEW RESPONSE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 09-06-2018 Cont ID  
Sent By pleduc Date 09-06-2018 Time 10:06 Rev Time 0.00
Received By pleduc Date 09-06-2018 Time 09:48 Sent To  
Notes
2018-09-06 10:06:40THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, TO INCLUDE CHAPTER NEW HOTELS
 AND DORMITORIES, AND ALL ASSOCIATED FIRE CODES.
  
 THERE ARE HEIGHT INDICATIONS OF THE HIGHEST FLOOR LEVEL
 AT 74'. THE DEFINITION OF A "HIGH RISE"PER NFPA 101 IS
 FOUND IN CHAPTER 3, DEFINITIONS; 3.3.36.7* HIGH-RISE
 BUILDING. A BUILDING WHERE THE FLOOR OF AN
 OCCUPIABLE STORY IS GREATER THAN 75 FT (23 M) ABOVE THE
 LOWES LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS.
  
 THE LEVEL 0" INDICATION ON THE PLAN DRAWING DOES NOT
 APPEAR TO BE AT THE LOWEST LEVEL OF FIRE DEPARTMENT
 VEHICLE ACCESS. THE FIRE DEPARTMENT VEHICLE ACCESS
 POINT COULD BE WELL BELOW THE LEVEL 0", AND THIS
 BUILDING WOULD BE CONSIDERED A HIGH RISE.
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS IF THIS IS
 NOT INTENDED TO BE A HIGH RISE.
  
 ALL FUTURE COMMENTS ARE FOR HIGH RISE BUILDINGS.
  
 6. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE.
  
 TEMPORARY STANDPIPES ARE REQUIRED WHEN THE BUILDING
 REACHES THREE LEVELS OR THIRTY FEET WHILE BEING
 CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE
 SUBMITTED, REVIEWED AND APPROVED BY THE FIRE PREVENTION
 BUREAU PRIOR TO ANY INSTALLATION.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 THERE WERE NO OBIVIOUS INDICATIONS OF FIRE HYDRANT
 LOCATIONS.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER NFPA 14 SECTION 7.12.2, HIGH-RISE BUILDINGS SHALL
 HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT
 CONNECTIONS FOR EACH ZONE.
  
 7. PER FLORIDA ADMINISTRATIVE CODE SECTION
 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS
 SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER
 SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE
 TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR
 EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN
 DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT
 FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION
 SUCH AS PRE-ENGINEERED SYSTEMS.
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. COMMAND ROOM
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 13. RADIO
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
  
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
  
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
  
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 10-19-2018 Cont ID  
Sent By rcaranci Date 10-19-2018 Time 15:26 Rev Time 0.00
Received By rcaranci Date 10-19-2018 Time 15:26 Sent To  
Notes
2018-10-19 15:26:59PROJECT: PBAU DORM BUILDING Z18080015
 OCTOBER 19, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PROVIDE A TREE DISPOSITION LIST AND PLAN
 SHOWING TREES AND PALMS THAT WILL BE AFFECTED, AND
 INDICATE IF THEY WILL BE PRESERVED, RELOCATED OR
 REMOVED.
  
 2. SATISFIED. CORRECT THE REQUIRED TREE CALCULATION TO
 1 PER 1500 SQ FT OR PORTION THEREOF.
  
 3. SATISFIED. PROVIDE THE REQUIRED NUMBER OF TREES AND
 PERCENTAGE OF PALM SUBSTITUTIONS NOT TO EXCEED 35
 PERCENT. LIGUSTRUM CANNOT BE COUNTED AS A TREE. SABAL
 AND WASHINGTONIA PALMS ARE COUNTED AT 3:1 RATIO.
  
 4. SATISFIED. PROVIDE A TREE AS REQUIRED AND A TERMINAL
 LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING
 SPACES PER SECTION 94-443(C)(3).
  
 5. SATISFIED. PROVIDE THE CALCULATIONS FOR THE
 LANDSCAPE BUFFERS FOR THE WEST AND SOUTH PROPERTY LINE,
 AND THE PORTION ADJACENT TO 900 N DIXIE.
  
  
 6. SATISFIED. PROVIDE THE CALCULATION FOR BUILDING
 PERIMETER LANDSCAPE REQUIREMENT OF 30% FOR
 NONRESIDENTIAL USE.
  
 7. SATISFIED. THE LOCATIONS OF WATER AND SEWER LINES ON
 THE LANDSCAPE PLAN SHOW CONFLICTS WITH TREES AND
 LANDSCAPING. COORDINATE LOCATIONS WITH ENGINEER TO
 AVOID CONFLICTS.
  
 8. SATISFIED. CORRECT THE FLORIDA FRIENDLY LANDSCAPE
 CHART TO PROVIDE THE REQUIRED 50 POINTS.
 9. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
 10. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL ABOVE
 GROUND UTILITY VALVES AND BACKFLOW PREVENTERS.
  
  
 11. SATISFIED. STAFF SUGGESTS A MEETING TO DISCUSS THE
 CURRENT DESIGN AND THE REQUIREMENTS OF SECTION 94-452
 ROADWAY BEAUTIFICATION. PROVIDING SHADE FOR THE
 SIDEWALKS TO PROVIDE A PEDESTRIAN FRIENDLY ENVIRONMENT
 IS THE ULTIMATE GOAL, WHETHER ON SITE OR IN THE RIGHT
 OF WAY.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 09-18-2018 Cont ID  
Sent By rcaranci Date 09-18-2018 Time 11:35 Rev Time 0.00
Received By rcaranci Date 09-18-2018 Time 11:35 Sent To  
Notes
2018-09-18 11:35:54FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PBAU DORM BUILDING Z18080015
 SEPTEMBER 18, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PROVIDE A TREE DISPOSITION LIST AND PLAN SHOWING
 TREES AND PALMS THAT WILL BE AFFECTED, AND INDICATE IF
 THEY WILL BE PRESERVED, RELOCATED OR REMOVED.
  
 2. CORRECT THE REQUIRED TREE CALCULATION TO 1 PER 1500
 SQ FT OR PORTION THEREOF.
  
 3. PROVIDE THE REQUIRED NUMBER OF TREES AND PERCENTAGE
 OF PALM SUBSTITUTIONS NOT TO EXCEED 35 PERCENT.
 LIGUSTRUM CANNOT BE COUNTED AS A TREE. SABAL AND
 WASHINGTONIA PALMS ARE COUNTED AT 3:1 RATIO.
  
 4. PROVIDE A TREE AS REQUIRED AND A TERMINAL LANDSCAPE
 ISLAND AT THE END OF EACH ROW OF PARKING SPACES PER
 SECTION 94-443(C)(3).
  
 5. PROVIDE THE CALCULATIONS FOR THE LANDSCAPE BUFFERS
 FOR THE WEST AND SOUTH PROPERTY LINE, AND THE PORTION
 ADJACENT TO 900 N DIXIE.
  
  
 6. PROVIDE THE CALCULATION FOR BUILDING PERIMETER
 LANDSCAPE REQUIREMENT OF 30% FOR NONRESIDENTIAL USE.
  
 7. THE LOCATIONS OF WATER AND SEWER LINES ON THE
 LANDSCAPE PLAN SHOW CONFLICTS WITH TREES AND
 LANDSCAPING. COORDINATE LOCATIONS WITH ENGINEER TO
 AVOID CONFLICTS.
  
 8. CORRECT THE FLORIDA FRIENDLY LANDSCAPE CHART TO
 PROVIDE THE REQUIRED 50 POINTS.
 9. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 10. PLEASE PROVIDE SCREENING FOR ALL ABOVE GROUND
 UTILITY VALVES AND BACKFLOW PREVENTERS.
  
  
 11. STAFF SUGGESTS A MEETING TO DISCUSS THE CURRENT
 DESIGN AND THE REQUIREMENTS OF SECTION 94-452 ROADWAY
 BEAUTIFICATION. PROVIDING SHADE FOR THE SIDEWALKS TO
 PROVIDE A PEDESTRIAN FRIENDLY ENVIRONMENT IS THE
 ULTIMATE GOAL, WHETHER ON SITE OR IN THE RIGHT OF WAY.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 09-13-2018 Cont ID  
Sent By   Date 09-13-2018 Time   Rev Time  
Received By   Date 09-13-2018 Time   Sent To  
Notes
2018-10-11 14:46:21INFORMATION PROVIDED IN THE RESPONSE LETTER WILL
 SUFICE. BASED ON THE RESPONSE THE APPLICANT WILL HAVE
 TO ARRANGE AND SET UP A SCHEDULE WITH THE SANITATION
 DEPARTMENT FOR PICK UP AND THE PICK UP LOCATIONS.
2018-09-13 09:28:59BASED ON INFORMATION IN THE CURRENT PLANS A SOLID WASTE
 MANAGEMENT PLAN IS REQUIRED. DUE TO THE INCREASE IN
 OCCUPANCY HOW WILL YOU HANDLE THE GENERATED WASTE.
 WHERE WILL THE DESIGNATED PICK UP POINT BE AND WHAT
 TYPE OF SERVICE?

Review Stop STORM STORMWATER
Rev No 2 Status F Date 10-19-2018 Cont ID  
Sent By tward Date 10-19-2018 Time 16:15 Rev Time 0.00
Received By tward Date 10-19-2018 Time 16:17 Sent To  
Notes
2018-10-19 16:17:08THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 OCTOBER 10, 2018 REVIEW SUBMITTAL PACKAGE.
  
 1. NAVD TO NGVD CONVERSION EQUATION MISSING FROM THE
 SURVEY.
  
 2. MOVE THE YARD DRAINS AND ANY FLOOR GRATES OFF OF THE
 SOUTH PROPERTY LINE.
  
 3. TCE WILL LIKELY BE NEEDED FOR GROUT FILLING THE
 STORM PIPE UNDER THE BUILDING AT THE SOUTHEAST CORNER
 OF S. DIXIE HWY AND OKEECHOBEE BLVD.
  
 4. ADD A LABEL ON THE ENGINEERING PLANS FOR THE LINE
 WORK CONSISTING OF DASH LINE BETWEEN SMALL RECTANGLES.
 THE ENGINEERING PLANS SHOW AN EXISTING DRAINAGE PIPE
 CONNECTING TO THIS SYSTEM ON DIXIE HIGHWAY.
  
 5. THE SURVEY DOES NOT SHOW THE DRAINAGE MANHOLE THAT
 THE EXISTING DRAINAGE PIPE UNDER THE BUILDING MENTIONED
 IN #3 ABOVE CONNECTS TO AS SHOWN ON THE ENGINEERING
 PLANS. CONFIRM THERE IS AN EXISTING STRUCTURE OR IF ONE
 IS PROPOSED.
  
 6. AN EASEMENT WILL BE NEEDED FROM THE ADJACENT
 PROPERTY OWNER FOR THE PROPOSED DRAINAGE SYSTEM BETWEEN
 S-107 AND S-106 ON THEIR PROPERTY. DID YOU CONSIDER
 RUNNING A PIPE SOUTH OUT OF S-106 AND TYING INTO THE
 CURB INLET ON DIXIE HWY?
  
 7. WHY IS THERE A BREAK IN THE EXFILTRATION TRENCH
 BETWEEN S-104 AND S-105?
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 09-12-2018 Cont ID  
Sent By tward Date 09-12-2018 Time 07:44 Rev Time 0.00
Received By tward Date 09-12-2018 Time 07:45 Sent To  
Notes
2018-09-12 07:45:31THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED. THE CONVERSION
 EQUATION IS NEEDED ON THE SURVEY.
  
 2. MOVE DRAINAGE STRUCTURE S-101 OUT OF THE
 RIGHT-OF-WAY FOR PEMBROKE PLACE.
  
 3. INDICATE IF THERE IS A DRAINAGE EASEMENT FOR THE
 STORM PIPE CROSSING THE PROPERTY TO THE NORTH.
  
 4. INDICATE THE CURB CUT ON DIXIE HIGHWAY WILL BE
 REMOVED AND THE SIDEWALK ALONG THE CURB CUT WILL BE
 REPLACED.
  
 5. INDICATE ON THE ENGINEERING PLANS THE LIMITS OF
 CONSTRUCTION ON PEMBROKE PLACE INCLUDING MILLING AND
 RESURFACING LIMITS.
  
 6. REVIEW THE CONSTRUCTABILITY OF MAKING FUTURE REPAIRS
 OR REPLACEMENT OF THE STORM PIPE OR EXFILTRATION TRENCH
 WITH THEIR PROXIMITY TO THE BUILDING.
  
 7. THE PROPOSED SITE PLAN APPEARS TO BE MISALIGNED ON
 THE CONCEPTUAL ENGINEERING PLANS.
  
 8. PROVIDE VALLEY GUTTER BETWEEN DROP AREA AND TRAVEL
 LANE ON PEMBROKE PLACE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE MODIFIED SFWMD ERP APPROVAL
 PRIOR TO STARTING CONSTRUCTION.
  
 4. SOUTH DIXIE HIGHWAY IS MAINTAINED BY FLORIDA
 DEPARTMENT OF TRANSPORTATION. PROVIDE A COPY OF FDOT
 APPROVAL FOR ALL WORK PROPOSED WITHIN THE DIXIE HWY
 RIGHT-OF-WAY.
  
 5. PROVIDE FDOT APPROVAL FOR DRAINAGE CONNECTION TO THE
 ROADWAY DRAINAGE SYSTEM.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 10-18-2018 Cont ID  
Sent By vnoel Date 10-18-2018 Time 09:13 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2018-10-18 09:17:36PASSED WITH PROVISOS:
  
 1. REPLAT PRIOR TO C.O.
 2. DRAINAGE EASEMENT FROM ADJOINING OWNER REQUIRED
 PRIOR TO BUILDING PERMIT. VERIFY THAT DRAINAGE LINE
 ACTUALLY DOES LIE UNDER BUILDING.
 3. MAINTENANCE AND SIDEWALK EASEMENTS PRIOR TO C.O.
 4. FPL ACKNOWLEDGMENT TO ABANDON EASEMENT. PROVIDED
 LETTER IS SERVICE LETTER ONLY.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 09-11-2018 Cont ID  
Sent By vnoel Date 09-11-2018 Time 14:14 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-09-11 14:48:321. MAY NEED TO BREAK OUT PORTION OF SURVEY FRO JUST THE
 AREA IN QUESTION.
 2. 6' FPL EASEMENT WILL NEED TO BE TERMINATED.
 3. REPLAT WILL BE REQUIRED.
 4. SHOW DATUM CONVERSION TO NGVD-29.
 5. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR R/W
 IMPROVEMENTS.
 6. EASEMENT FOR SIDEWALK/DROP - OFF AREA WILL BE
 REQUIRED.
 7. STORM MH S-101 NEEDS TO BE RELOCATED INSIDE
 PROPERTY.
 8. DOORS CANNOT OPEN INTO RIGHT-OF-WAY. UTILITIES WILL
 REVIEW SAN. MH #1 IN SIDEWALK AND WATER CONNECTIONS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 10-17-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-10-17 16:03:161. PROVIDE TPS LETTER FROM PALM BEACH COUNTY.
 2. PROVIDE FDOT DRIVEWAY APPROVAL LETTER FOR THE
 DRIVEWAY PROPOSED ON S DIXIE HIGHWAY.
 3. CONNECT THE PEDESTRIAN PATHWAY FROM SOUTH DIXIE
 HIGHWAY TO BICYCLE PARKING SPACES AND ENTRY AT THE BACK
 OF THE BUILDING.
 4. REVISE THE FOLLOWING RELATED TO PARKING SPACE
 DIMENSIONS:
 O THE LAST PARKING SPACE ON THE PARKING AISLE FROM S
 DIXIE HIGHWAY DOES NOT MEET THE MINIMUM PARKING SPACE
 DIMENSION.
 O THE WIDTH OF THE NORTHERN HANDICAPPED PARKING SPACE
 APPEARS TO BE SLIGHTLY LESS THAN THE REQUIRED MINIMUM
 WIDTH OF 12 FEET. PLEASE VERIFY.
 O THE TERMINAL ISLANDS AT THE INGRESS FROM OKEECHOBEE
 BOULEVARD SHOULD BE A MINIMUM OF 8-FOOT WIDE.
 O THE DIMENSIONS OF THE EXISTING PARKING SPACES DO NOT
 APPEAR TO MEET CITY CODE REQUIREMENT. PLEASE ADJUST THE
 PARKING AISLE WIDTH AND STALL DEPTH AND WIDTH TO BRING
 THEM UP TO CODE REQUIREMENT.
 5. PROVIDE SIDEWALK EASEMENT FOR PORTION OF SIDEWALK
 OUTSIDE OF R/W ON PEMBROKE PLACE.
 6. INSTALL SIGNAGE TO DESIGNATE THE TWO PUBLIC
 ON-STREET PARKING SPACES ON PEMBROKE PLACE AS PASSENGER
 PICK-UP/DROP-OFF AREA
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 09-06-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-09-06 14:49:30Z18080015 PBAU DORMITORY (AUGUST 14, 2018 SUBMITTAL)
 1. PROVIDE TPS LETTER FROM PALM BEACH COUNTY.
 2. REVISE LOADING AREA TO ON-STREET PUBLIC PARKING
 SPACE.
 3. OUR PREFERENCE IS TO MAINTAIN THE EXISTING LANDSCAPE
 BUFFER BETWEEN THE SIDEWALK AND CURB ALONG PEMBROKE
 PLACE
 4. HOW WILL WATER QUALITY AND QUANTITY BE PROVIDED FOR
 THE LOSS OF EXISTING LANDSCAPE BUFFER IN THE RIGHT OF
 WAY ON PEMBROKE PLACE?
 5. SHOW THE REQUIRED 20-FOOT VISIBILITY TRIANGLE.
 6. PROVIDE BICYCLE STORAGE SPACES FOR STUDENT
 RESIDENTS.
 7. PROVIDE EASEMENT AND INSTALL A BUS SHELTER AT THE
 EXISTING BUS STOP ON OKEECHOBEE BOULEVARD UPON APPROVAL
 FROM PALMTRAN.
 8. DIMENSION THE PARKING SPACES AND PARKING AISLE
 WIDTH. THE DIMENSIONS OF THE PARKING SPACES, INCLUDING
 THE DISABLED PARKING SPACES, DO NOT APPEAR MEET THE
 CITY CODE REQUIREMENT. PLEASE VERIFY AND REVISE. ALSO,
 THE TERMINAL ISLANDS SHOULD BE A MINIMUM OF 8-FOOT
 WIDE, AND INTERIOR ISLANDS SHOULD BE PROVIDED FOR EVERY
 10 PARKING SPACES.
 9. A LANE REPURPOSING IS PROPOSED FOR S. DIXIE. PLEASE,
 SCHEDULE A SEPARATE MEETING TO DISCUSS COORDINATING
 IMPROVEMENTS.
 10. ELIMINATE EXISTING DROP CUB ON S. DIXIE.
 11. SHOW CURB LINES AND RIGHT OF WAY ON OTHER SIDES OF
 THE STREETS. THIS IS A REQUIREMENT ON THE SITE PLAN
 CHECKLIST. OUR REVIEW IS PRELIMINARY AS THE SITE PLAN
 THAT WAS SUBMITTED DOES NOT MEET SUFFICIENCY
 REQUIREMENTS.
 12. PROVIDE SIDEWALK EASEMENT FOR PORTION OF SIDEWALK
 OUTSIDE OF R/W ON PEMBROKE PLACE.
 13. PROVIDE TYPICAL SECTION FOR PEMBROKE PLACE.
 14. SOUTH DIXIE AND OKEECHOBEE HAVE ADDITIONAL RIGHT OF
 WAY SETBACK REQUIREMENTS. REFERENCE 94-305 TABLE X-1
 AND COMP. PLAN TRANSPORTATION ELEMENT.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status F Date 10-26-2018 Cont ID  
Sent By jroach Date 10-26-2018 Time 12:46 Rev Time 0.00
Received By jroach Date 10-26-2018 Time 12:46 Sent To  
Notes
2018-10-26 12:46:34PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 10.23.2018
 PROJECT NO.: Z18080015
 CASE NO.: PB 1111UU
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. AN APPROVED TRAFFIC CONCURRENCY STATEMENT SHALL BE
 PROVIDED FROM THE PALM BEACH COUNTY TRAFFIC DIVISION.
  
 2. EXISTING 6 FOOT FPL UTILITY EASEMENT (ORB 2327 PG
 31) CONFLICTS WITH THE LOCATION OF THE PROPOSED
 BUILDING. PLEASE EXPLAIN HOW THIS WILL BE RECTIFIED AND
 PROVIDE WRITTEN APPROVAL FROM FPL. ? THE LETTER
 PROVIDED BY FPL DOES NOT SPECIFICALLY MENTION OR
 ADDRESS THE EASEMENT ISSUE AND APPEARS TO BE ONLY A
 SERVICE AVAILABILITY LETTER.
  
 3. SETBACKS ON THE SITE PLAN SHALL BE MEASURED FROM THE
 PROPERTY LINE TO THE CLOSEST POINT OF THE BUILDING. ?
 THE MEASUREMENT SHOWN FROM THE SOUTH DIXIE HIGHWAY
 RIGHT-OF-WAY STILL DOES NOT APPEAR TO BE THE CLOSEST
 POINT.
  
 4. GENERATORS SHALL BE SCREENED IN ACCORDANCE WITH SEC.
 94-315 OF THE CITY?S ZLDRS. A DETAIL SHALL BE PROVIDED
 SHOWING COMPLIANCE.
  
 5. A BIKE RACK DETAIL SHALL BE PROVIDED SHOWING THAT
 THE PROPOSED RACK COMPLIES WITH THE CITY?S MINIMUM
 REQUIREMENTS. THE STYLE OF THE RACK AS WELL AS
 DIMENSIONS REGARDING PLACEMENT SHALL BE INDICATED.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) IN ORDER TO BE CONSIDERED FOR THE NOVEMBER 28, 2018,
 PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE
 SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED
 DOCUMENTS/PLANS NO LATER THAN FRIDAY, NOVEMBER 2, 2018.
  
 G) TO BE PLACED ON THE NOVEMBER 28, 2018, PLANNING
 BOARD AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO
 LATER THAN NOVEMBER 13, 2018. SIGNAGE SHALL CONFORM AND
 BE INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN
 THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED
 AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED
 ABOVE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 09-18-2018 Cont ID  
Sent By jroach Date 09-18-2018 Time 14:06 Rev Time 0.00
Received By jroach Date 09-18-2018 Time 14:06 Sent To  
Notes
2018-09-18 14:06:37PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 09.18.2018
 PROJECT NO.: Z18080015
 CASE NO.: PB 1111UU
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. AN APPROVED TRAFFIC CONCURRENCY STATEMENT SHALL BE
 PROVIDED FROM THE PALM BEACH COUNTY TRAFFIC DIVISION.
  
 2. EXISTING 6 FOOT FPL UTILITY EASEMENT (ORB 2327 PG
 31) CONFLICTS WITH THE LOCATION OF THE PROPOSED
 BUILDING. PLEASE EXPLAIN HOW THIS WILL BE RECTIFIED AND
 PROVIDE WRITTEN APPROVAL FROM FPL.
  
 3. UTILITY LETTERS SHALL BE PROVIDED INDICATING NO
 OBJECTION TO THE PROPOSED DEVELOPMENT.
  
 4. AS THE NUMBER OF PARKING SPACES IS BEING REDUCED,
 DETAILED JUSTIFICATION SHALL BE PROVIDED. STAFF HAS NOT
 BEEN ABLE TO DETERMINE WHEN A WAIVER WAS GRANTED TO THE
 CITY?S ZONING AND LAND DEVELOPMENT REGULATIONS OTHER
 THAN ADOPTION OF A MASTER PLAN THAT INDICATING 1150
 SPACE PROVIDED. THIS IS SIGNIFICANTLY LESS THAN THAT
 WHICH IS REQUIRED BY THE CITY?S ZLDR. AS SUCH, TO
 PROPOSED A FURTHER REDUCTION, IT SHOULD BE TREATED AS A
 WAIVER AND COMPLY WITH THE PROVISIONS OF SEC.
 94-207(B)(13) OF THE CITY?S ZLDR.
  
 5. SETBACKS ON THE SITE PLAN SHALL BE MEASURED FROM THE
 PROPERTY LINE TO THE CLOSEST POINT OF THE BUILDING.
  
 6. THE ANGLE OF THE PROPOSED HANDICAP PARKING SPACES
 SHALL BE PROVIDED.
  
 7. THE CONFIGURATION OF THE PROPOSED HANDICAP PARKING
 SPACES RESULTS IN THE SPACES BEING TOO SHORT, CAUSING
 VEHICLES TO OVERHANG INTO THE DRIVE AISLE.
  
 8. THE FLOOR PLAN OF THE BUILDING SHOULD BE ADJUSTED TO
 ALLOW THE STAIRWELLS AT THE ENDS OF THE CORRIDORS TO BE
 ON THE BACK SIDE OF THE BUILDING (AWAY FROM THE STREET)
 SO AS TO ALLOW ARCHITECTURAL ELEMENTS AND WINDOWS ON
 THE PROMINENT CORNERS.
  
 9. PARKING STALL STRIPING DETAIL SHALL BE PROVIDED.
  
 10. BIKE RACKS SHALL BE PROVIDED AT BOTH ENTRANCES INTO
 THE BUILDING, OR OTHERWISE PROVIDE BICYCLE STORAGE
 FACILITIES WITHIN THE BUILDING. OPTIONS SHOULD BE
 CONSIDERED FOR BICYCLE STORAGE THAT WOULD ALLOW
 STUDENTS TO STORE THEIR BICYCLE OUTSIDE OF THE ELEMENTS
 FOR EXTENDED PERIODS OF TIME.
  
 11. PLEASE LABEL THE ROOMS, ETC. ON THE VARIOUS FLOOR
 PLANS.
  
 12. STAFF (INCLUDING THE CITY?S URBAN DESIGN DIVISION)
 WOULD LIKE TO COORDINATE A MEETING WITH THE ARCHITECT
 AND DESIGN TEAM TO DISCUSS ARCHITECTURAL STYLE OPTIONS
 FOR THE PROPOSED BUILDING TO ENSURE COMPATIBILITY, BUT
 MORE IMPORTANTLY PROVIDE AN ARCHITECTURAL STYLE THAT IS
 APPROPRIATELY EXECUTED ACROSS ALL ELEMENTS OF THE
 BUILDING.
  
 13. HAS THERE BEEN ANY CONSIDERATION OF ADDING STREET
 STREETS TO THE FDOT RIGHT-OF-WAY?
  
 14. ARCHITECTURAL DRAWINGS SHALL PROVIDE THE BUILDING
 HEIGHT AS MEASURED FROM THE MEAN GRADE TO THE MEAN
 POINT OF THE PITCHED ROOF, OR TO THE ROOF DECK OF A
 FLAT ROOF.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) IN ORDER TO BE CONSIDERED FOR THE NOVEMBER 20, 2018,
 PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE
 SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED
 DOCUMENTS/PLANS NO LATER THAN FRIDAY, SEPTEMBER 28,
 2018.
  
 G) TO BE PLACED ON THE NOVEMBER 20, 2018, PLANNING
 BOARD AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO
 LATER THAN NOVEMBER 5, 2018. SIGNAGE SHALL CONFORM AND
 BE INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN
 THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED
 AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED
 ABOVE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print