Plan Review Details - Project Z18080012
| Plan Review Stops For Project Z18080012 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
09-11-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
09-11-2018 |
Time |
13:21 |
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
09-11-2018 |
Time |
13:21 |
Sent To |
|
|
| Notes |
| 2018-09-11 13:29:12 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. LOCATION OF ACCESSIBLE PARKING SPACES. NO THAT A | | | BUILDING IS PROPSED CLOSE TO THE NORTH-EAST PARKING | | | LOT, ACCESSIBLE PARKING IS REQUIRED IN THAT PARKING | | | LOT. THE ACCESSIBLE PARKING SHALL BE THE CLOSEST | | | PARKING SPACES TO THE BUILDING ENTRANCE. PER SECTION | | | 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE PARKING | | | SPACES ARE TO BE LOCATED ON THE SHORTEST POSSIBLE ROUTE | | | OF TRAVEL FROM ADJACENT PARKING TO AN ACCESSIBLE | | | ENTRANCE. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE | | | REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M | | | SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS | | | AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL: | | | [email protected] | | | | | | 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 6. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT | | | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 | | | 1080, OR BY EMAIL: [email protected] | | | | | | 7. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
10-04-2018 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
10-04-2018 |
Time |
|
Rev Time |
1.00 |
| Received By |
rrossano |
Date |
10-04-2018 |
Time |
|
Sent To |
I |
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
09-17-2018 |
|
|
Cont ID |
|
| Sent By |
RRossano |
Date |
09-18-2018 |
Time |
|
Rev Time |
2.00 |
| Received By |
rrossano |
Date |
09-18-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-18 15:52:30 | THE CITY OF WEST PALM BEACH HAS A NUMBER OF REGULATIONS | | | AND PERMIT REQUIREMENTS WHICH DIRECTLY AFFECT THE | | | DEVELOPMENT AND INSTALLATION OF WATER AND WASTEWATER | | | UTILITIES WITHIN THE CITY. PLEASE SEE DEVELOPMENT | | | PERMIT SUBMITTAL REQUIREMENTS AT THE LINK BELOW: | | | HTTP://WPB.ORG/CMSPAGES/GETAMAZONFILE.ASPX?PATH=~\WPB_W | | | EBSITE\MEDIA\ENGINEERING\DEVELOPMENT-APPLICATION-FULL-P | | | ACKAGE_2016.PDF&HASH=7BD4DD7EB6115181D8C5977BCC02A97B19 | | | 60045731D3658206F27451722716EF | | | THIS AND OTHER RELATED ENGINEERING DOCUMENTS CAN BE | | | FOUND HERE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | CODE OF ORDINANCES, CITY OF WEST PALM BEACH, FLORIDA, | | | CODIFIED THROUGH ORD. NO. 4183-08, ADOPTED SEPT. 22, | | | 2008. (SUPPLEMENT NO. 18) | | | CHAPTER 90 UTILITIES, ARTICLE I. IN GENERAL, | | | SEC. 90-7. POLICY REGARDING EXTENSION OF WATER OR SEWER | | | SERVICE FACILITIES OF THE CITY. | | | | | | THE WATER AND WASTEWATER SERVICE AGREEMENTS AND THE | | | CONSTRUCTION PERMITS ADDRESS RESERVATION OF CAPACITY | | | BASED ON USAGE, METER SIZE AND FEES, DESIGN STANDARDS, | | | BACKFLOW PREVENTION, FIRE SERVICE AND IRRIGATION. | | | | | | PROVIDE PEAK FLOWS AND WATER & SEWER CALCULATIONS. | | | | | | AS OF DECEMBER 20, 2015, THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | STATING "ALL BACKFLOW DEVICES MUST BE LEAD-FREE". FOR | | | MORE INFORMATION, REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | EXISTING UTILITY LINES SHALL BE SHOWN AND LABELED ON | | | PLAN VIEW BY DASHED LINES. PROPOSED UTILITY LINES SHALL | | | BE SHOWN BY SOLID LINES. | | | | | | PLANS SHALL SHOW PROPOSED LOCATIONS AND DIMENSIONS OF | | | ALL WATER, STORMWATER, AND SANITARY AND SEWER LINES, | | | INCLUDING STUBS TO EACH PROPERTY LINE FOR WATER AND | | | SANITARY SEWERS, THE MAKE AND MODEL OF ALL VALVES, | | | METERS, AND OTHERS DEVICES TO BE INSTALLED ON THE | | | SYSTEM, CATCH BASINS, CULVERTS, DITCHES INCLUDING | | | GRADES, PIPES SIZES, MATERIALS, ELEVATIONS, | | | ASSUMPTIONS, CALCULATIONS, INVERT ELEVATIONS FOR ALL | | | INLETS AND MANHOLES AND PROFILES OF SANITARY SEWER | | | LINES. ALL AVAILABLE ELEVATION SHALL BE SHOWN ON THE | | | PROFILE VIEW. DIRECTION OF FLOW SHALL BE SHOWN ON PLAN | | | VIEW ON PLAN VIEW FOR ALL SANITARY AND STORM SEWERS. | | | | | | PLAN VIEW SHALL SHOW ALL EXISTING AND PROPOSED | | | UNDERGROUND UTILITY LAYOUT, INCLUDING FIBER OPTIC, | | | ELECTRIC, GAS, AND CABLEVISION & TELECOMMUNICATION | | | FACILITIES LOCATED ON THE RIGHT-OF-WAY. | | | | | | PROVIDE DETAILS AND PROFILE VIEW OF ALL UTILITY | | | CONFLICTS. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | | | | RICK ROSSANO | | | PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1098 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 246-9525 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | ENGINEERING SERVICES DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | MOBILE: (561) 644-7301 | | | EMAIL: [email protected] | | | WWW.WPB.ORG/ENGINEERING |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
11-02-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
11-02-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
11-02-2018 |
Time |
10:03 |
Sent To |
|
|
| Notes |
| 2018-11-02 10:06:10 | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM PAUL | | | GREILICH, SENIOR PLANNER, THE LETTER ATTACHMENT DATED | | | SEPTEMBER 28, 2018, FROM URBAN DESIGN KILDAY STUDIOS | | | AND DRAWING DOCUMENTS, THE PREVIOUSLY SUBMITTED FIRE | | | PREVENTION BUREAU COMMENTS APPEAR TO HAVE BEEN | | | ADDRESSED. | | | | | | HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED | | | PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR | | | APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
09-06-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
09-06-2018 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
09-06-2018 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2018-09-06 11:30:48 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY CLASSIFICATION, PER THE FLORIDA FIRE | | | PREVENTION CODE, AND WHETHER IT IS MIXED OR SEPARATED | | | OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | AN EXISTING FIRE HYDRANT IS INDICATED IN CLOSE | | | PROXIMITY OF THE PROPOSED FDC AND BOTH LOCATIONS ARE | | | ACCEPTABLE. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. THERE IS AN INDICATION | | | OF A FDC FOR THIS STRUCTURE AND THAT IS WILL SUPPORT A | | | FIRE SPRINKLER SYSTEM. | | | | | | FOR ANY LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE | | | SPRINKLER AND FIRE ALARM, ENSURE THEY COMPLY WITH THE | | | REQUIREMENTS OF FS 61G AND SUBMITTED WITH THE MASTER | | | PLAN. | | | | | | THE FIRE SPRINKLER SYSTEM SHALL BE MONITORED. | | | | | | PER THE PROPOSED OCCUPANCY CLASSIFICATION A FULL FIRE | | | ALARM SYSTEM MAY BE REQUIRED AND SHALL BE SUBMITTED | | | UNDER SEPARATE SHOP DRAWINGS. IT WAS INDICATED THAT | | | THERE WILL BE PERSONS SLEEPING ON COTS, AND IT SO, A | | | FULL FIRE ALARM SHALL BE REQUIRED. | | | | | | | | | 10. ALL PROPOSED KITCHEN COOKING EQUIPMENT SHALL COMPLY | | | WITH NFPA 96 AND SHALL BE SUBMITTED UNDER SEPARATE SHOP | | | DRAWINGS. | | | | | | | | | 11. A GENERATOR IS INDICATED AND SHALLCIMPLY WITH NFPA | | | 37 AND BE SUBMITTED UNDER A SEPARATE PERMIT. IF THIS | | | GENERATOR PROVIDES EMERGENCY POWER TO THE LIFE SAFETY | | | SYSTEMS IT SHALL COMPLY WITH THE REQUIREMENTS OF NFPA | | | 110. | | | | | | 12. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 13. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 14. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 15. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
10-12-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-12-2018 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-12-2018 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2018-10-12 11:02:29 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: FPL DSI Z18080012 | | | OCTOBER 12, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L. | | | PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT | | | MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | | | | 2. SATISFIED. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE | | | CHART AND SHOW POINTS (50). | | | | | | | | | 3. SATISFIED. THE FOUNDATION LANDSCAPE LACKS ANY TREES | | | OR PALMS. STAFF SUGGESTS INCLUDING SOME SABAL PALMS. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
09-17-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-17-2018 |
Time |
17:19 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-17-2018 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2018-09-17 17:19:30 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: FPL DSI Z18080012 | | | SEPTEMBER 17, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | 2. PROVIDE THE FLORIDA FRIENDLY LANDSCAPE CHART AND | | | SHOW POINTS (50). | | | | | | | | | 3. THE FOUNDATION LANDSCAPE LACKS ANY TREES OR PALMS. | | | STAFF SUGGESTS INCLUDING SOME SABAL PALMS. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
11-09-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
11-09-2018 |
Time |
15:54 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
11-09-2018 |
Time |
15:56 |
Sent To |
|
|
| Notes |
| 2018-11-09 15:55:38 | THE FOLLOWING COMMENT IS FROM THE REVIEW OF THE | | | 10/1/2018 SUBMITTAL PACKAGE: | | | | | | 1. REVISE THE FLOOD ZONES ON THE LANDSCAPE PLAN, LP-1. | | | (REPEAT COMMENT). | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
09-12-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-12-2018 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-12-2018 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2018-09-12 07:58:55 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. REVISE THE FLOOD ZONES ON THE LANDSCAPE PLAN, LP-1, | | | AND OVERALL SITE PLAN, A-100. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE SFWMD ERP MODIFICATION FOR THE PROJECT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
10-18-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-18-2018 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
09-12-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-12-2018 |
Time |
10:22 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-12 10:30:37 | 1. ADD CONVERSION TO NGVD-29 | | | 2. CORNER INFORMATION MISSING AT NE AND SE CORNERS. | | | 3. EAST PROPERTY LINE MISSING LINEWEIGHT. | | | 4. ADD BEARING BASE. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
10-10-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
09-06-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-09-06 15:46:25 | Z18080012 FPL DISTRIBUTION CENTER DSI (AUGUST 14, 2018 | | | SUBMITTAL) | | | 1. PROVIDE TPS LETTER FROM PALM BEACH COUNTY. | | | 2. THE JUSTIFICATION STATEMENT INDICATES THAT A TRAFFIC | | | STATEMENT IS INCLUDED FOR REVIEW, BUT IS NOT PROVIDED. | | | 3. THE SITE PLAN AND ARCHITECTURAL PLAN NEED TO BE | | | SIGNED AND SEALED. | | | 4. PROVIDE AUTOTURN PATH TO SHOW TRUCK ACCESS TO THE | | | LOADING ZONE EAST OF THE COMMISSARY BUILDING. | | | 5. PROVIDE PEDESTRIAN CONNECTION TO THE COMMISSARY | | | BUILDING OR TO THE ENTRANCE OF THE PROTECTED WALKWAY. | | | | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
10-02-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
10-02-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
10-02-2018 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2018-10-02 14:17:12 | 1.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE | | | ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT | | | SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR | | | ADDITIONAL INFORMATION | | | | | | *WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15 (15) | | | PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11 | | | INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN | | | ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON | | | THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | *PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | *CONTACT PAUL GREILICH, SENIOR PLANNER @ | | | [email protected] OR 561-822-1443 FOR ANY QUESTIONS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
09-17-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
09-17-2018 |
Time |
16:00 |
Sent To |
|
|
| Notes |
| 2018-09-17 16:04:14 | 1.) PROVIDE HANDICAP PARKING SPACE TO THE EAST OF THE | | | PROPOSED COMMISSARY BUILDING WITH A DIRECT ACCESSIBLE | | | ROUTE TO THE EAST ENTRANCE OF THE PROPOSED BUILDING. | | | COULD ALSO BE USED TO PROVIDE WALKWAY TO FUTURE | | | GENERATOR LOCATION | | | 2.) STRIPE OR DELINEATE LOADING ZONE TO DIFFERENTIATE | | | THIS SPACE FROM THE DRIVE AISLE | | | 3.) CONSIDER WIDENING DRIVE AISLE TO THE WEST OF THE | | | COMMISSARY NEAR WESTERN PROPERTY LINE (SHOWN AS 14 FEET | | | WIDE ON SITE PLAN) | | | 4.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE | | | ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT | | | SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR | | | ADDITIONAL INFORMATION | | | | | | *WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 15 (15) | | | PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11 | | | INCHES AND ONE (1) SET IN 11 X 17 INCHES, AND AN | | | ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON | | | THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | *PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | | | | *CONTACT PAUL GREILICH, SENIOR PLANNER @ | | | [email protected] OR 561-822-1443 FOR ANY QUESTIONS | | | |
|
|
| |