Plan Review Details - Project Z18050045
Plan Review Stops For Project Z18050045
Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 06-07-2018 Cont ID  
Sent By mgonzale Date 06-07-2018 Time   Rev Time 0.50
Received By rcaranci Date 06-07-2018 Time   Sent To I
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 3 Status P Date 08-01-2018 Cont ID  
Sent By rcaranci Date 08-01-2018 Time 14:59 Rev Time 0.00
Received By rcaranci Date 08-01-2018 Time 14:57 Sent To  
Notes
2018-08-01 14:59:40ADDRESS COMMENTS IN ZONING FOR CORRECTIONS TO
 CALCULATIONS

Review Stop L LANDSCAPING
Rev No 2 Status F Date 07-19-2018 Cont ID  
Sent By rcaranci Date 07-19-2018 Time 17:05 Rev Time 0.00
Received By rcaranci Date 07-19-2018 Time 17:05 Sent To  
Notes
2018-07-19 17:06:02LANDSCAPE COMMENTS INCLUDED IN ZONING COMMENTS MUST BE
 SATISFIED.
 LANDSCAPE AREA MUST MEET THE 15 % REQUIRED.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-07-2018 Cont ID  
Sent By rcaranci Date 06-07-2018 Time 15:57 Rev Time 0.00
Received By rcaranci Date 06-07-2018 Time 15:57 Sent To  
Notes
2018-06-07 15:59:02LANDSCAPE COMMENTS INCLUDED IN ZONING COMMENTS MUST BE
 SATISFIED.
 ADDITIONALLY, CONSIDER USING A FLORIDA NATIVE SPECIES
 FOR THE HEDGE SURROUNDING THE GENERATOR ENCLOSURE.
  

Review Stop STORM STORMWATER
Rev No 1 Status P Date 06-01-2018 Cont ID  
Sent By tward Date 06-01-2018 Time 16:29 Rev Time 0.00
Received By tward Date 06-01-2018 Time 16:29 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 08-02-2018 Cont ID  
Sent By eschneid Date 08-02-2018 Time 10:16 Rev Time 0.00
Received By eschneid Date 08-02-2018 Time 10:16 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 07-13-2018 Cont ID  
Sent By eschneid Date 07-13-2018 Time 12:15 Rev Time 0.50
Received By eschneid Date 07-13-2018 Time 11:55 Sent To  
Notes
2018-07-13 12:15:16CASE NO. PB 1577E
 BRAMAN AUDI GENERATOR
 2101 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE COMMENTS WITHIN 60 DAYS FROM
 THE DATE OF THESE COMMENTS (BY SEPTEMBER 13, 2018), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ASSESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) REVISED COMMENT: THE SITE CURRENTLY HAS 15%
 PERVIOUS/LANDSCAPE AREA, WHICH IS THE MINIMUM,
 PERMITTED BY THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. THE PROPOSED GENERATOR PAD WILL REDUCE
 THIS BELOW 15%; THEREFORE, IT IS NOT PERMITTED UNLESS
 AN EQUAL AMOUNT OF PERVIOUS/LANDSCAPE AREA IS REPLACED
 ELSEWHERE ON THE SITE. WHILE THE USE OF PERVIOUS
 PAVEMENT MEETS THE MINIMUM 15% PERVIOUS AREA
 REQUIREMENT, IT DOES NOT COUNT TOWARD MEETING THE
 MINIMUM 15% LANDSCAPE AREA. THE PROPOSED SITE HAS A
 LANDSCAPE AREA DEFICIENCY OF 424.25 SQUARE FEET. PLEASE
 NOTE THAT MEETING THE LANDSCAPE MINIMUM WILL HAVE THE
 SITE COMPLY WITH THE PERVIOUS MINIMUM AND THERE WOULD
 BE NO NEED TO REPLACE THE ASPHALT WITH PERVIOUS
 PAVEMENT.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-06-2018 Cont ID  
Sent By eschneid Date 06-06-2018 Time 16:01 Rev Time 2.00
Received By eschneid Date 06-06-2018 Time 11:44 Sent To  
Notes
2018-06-06 16:01:46CASE NO. PB 1577E
 BRAMAN AUDI GENERATOR
 2101 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 AUGUST 6, 2018), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) THIS APPLICATION REQUIRED AN ENGINEERING SERVICES
 REVIEW. PLEASE SUBMIT THE ENGINEERING SERVICES REVIEW
 FEE IN THE AMOUNT OF $424 TO THE PLANNING DIVISION WITH
 THE RESUBMITTAL.
  
 2) THE SITE PLAN IS A MARKUP OF THE PREVIOUSLY SIGNED
 AND SEALED PLAN BY DOUG SNYDER CREATED AND COPYWRITED
 BY FSMY ARCHITECTS. PROVIDE A LETTER FROM FSMY GRANTING
 PERMISSION TO WGI TO REPRODUCE AND CHANGE THE SITE
 PLAN.
  
 3) THE MODIFIED SITE PLAN THAT WAS SUBMITTED IS NOT THE
 AS BUILT CONDITION AS SHOWN ON THE CURRENT APPROVED DSI
 SITE PLAN OR BUILDING PERMIT PLAN. THE ACCURATE SITE
 PLAN IS REQUIRED.
  
 4) THE SITE, CIVIL AND LANDSCAPE PLANS (CURRENT OR
 PREVIOUSLY SUBMITTED FOR SITE PLAN REVIEW OR BUILDING
 PERMIT REVIEW) DO NOT ACCURATELY SHOW THE LOCATION OF
 THE HARVEY BLOWERS, TO INCLUDE THE UNITS THEMSELVES,
 THE PAD THEY ARE LOCATED ON, OR THE SCREEN WALL AROUND
 THEM. THE CORRECT PLANS NEED TO BE SUBMITTED. NOTE: THE
 REQUIRED TREE IN THE SAME ISLAND NEEDS TO BE
 REINSTALLED AS SHOWN ON THE LANDSCAPE PLAN.
  
 5) THE SITE CURRENTLY HAS 15% PERVIOUS/LANDSCAPE AREA,
 WHICH IS THE MINIMUM, PERMITTED BY THE ZONING AND LAND
 DEVELOPMENT REGULATIONS. THE PROPOSED GENERATOR PAD
 WILL REDUCE THIS BELOW 15%; THEREFORE, IT IS NOT
 PERMITTED UNLESS AN EQUAL AMOUNT OF PERVIOUS/LANDSCAPE
 AREA IS REPLACED ELSEWHERE ON THE SITE. ANOTHER
 SOLUTION IS TO PUT THE GENERATOR ON A CURRENTLY PAVED
 PORTION OF THE SITE.
  
 6) PROVIDE DETAILS OF BOTH THE GENERATOR AND THE
 ENCLOSURE. THE ENCLOSURE HEIGHT MUST SCREEN THE FULL
 HEIGHT OF THE GENERATOR, TO INCLUDE ANY EXHAUST STACKS,
 FUEL TANKS ETC.
  
 7) THE LANDSCAPE PLAN SHOWS A HEDGE AROUND THE ENTIRE
 GENERATOR PAD. TYPICALLY, THERE NEEDS TO BE A GAP IN
 THE HEDGE TO PERMIT ACCESS TO THE GENERATOR FOR
 MAINTENANCE. PLEASE ADJUST THE PLAN TO CONFORM TO THE
 ACTUAL GENERATOR LAYOUT.
  
 8) PLEASE NOTE THAT THERE ARE A NUMBER OF TREES THAT
 ARE REQUIRED AND SHOWN ON THE LANDSCAPE PLAN THAT ARE
 MISSING FROM THE SITE. ALL THESE TREES MUST BE
 RE-INSTALLED.