Plan Review Details - Project Z18050030
Plan Review Stops For Project Z18050030
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 06-12-2018 Cont ID  
Sent By elevesqu Date 06-12-2018 Time 19:17 Rev Time 0.00
Received By mgonzale Date 06-12-2018 Time 19:17 Sent To  
Notes
2018-06-12 19:20:31DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY
 LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER
 APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE
 PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE
 WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF
 FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION
 DISTANCE.
  
 3. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 4. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 5. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 6. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT
 TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE
 ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP
 ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC
 PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 02-13-2019 Cont ID  
Sent By Mgonzale Date 02-13-2019 Time   Rev Time 1.00
Received By   Date 02-13-2019 Time   Sent To I
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 04-10-2019 Cont ID  
Sent By rrossano Date 04-10-2019 Time   Rev Time 0.00
Received By rrossano Date 04-10-2019 Time   Sent To  
Notes
2019-04-10 06:44:04PASSED WITH PROVISO: DECORATIVE PATTERN PAVER DESIGN
 EXTENDING INTO 8TH STREET SHALL BE EVALUATED AT TIME OF
 FORMAL SUBMITTAL BY CITY OF WEST PALM BEACH ENGINEERING
 SERVICES TRAFFIC SECTION. THE CITY RESERVES THE RIGHT
 TO INSURE COMPLIANCE WITH ADA AND MANUAL OF UNIFORM
 TRAFFIC CONTROL DEVICES (MUTCD) STANDARDS.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
  
 RICK ROSSANO
 PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1098
 FAX: (561) 494-1116
 MOBILE: (561) 246-9525
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 ENGINEERING SERVICES DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 MOBILE: (561) 644-7301
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING
  
 CENTRAL OPERATIONS CENTER (DISPATCH):
 24-HOUR EMERGENCY RESPONSE SERVICES TO PUBLIC
 UTILITIES, PUBLIC WORKS, PARKS, ETC. 561-822-2210

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 06-13-2018 Cont ID  
Sent By Mgonzale Date 06-13-2018 Time   Rev Time 1.00
Received By mgonzale Date 06-13-2018 Time   Sent To I
Notes
2018-06-13 13:14:40#1 DISCUSS CONNECTIONS FOR WATER AND SEWER WITH CITY OF
 WPB PUBLIC UTILITIES ENGINEER.
  
 #2 PROVIDE GPD CALCULATIONS FOR WATER AND SEWER
 DEMANDS.
  
 #3 NEW TREE CONFLICTS WITH THE 8" SANITARY SEWER IN THE
 ALLEY/EASEMENT. AND ROSEMARY.
  
 #4 DISCUSS REPLACEMENT OF MAIN IN LUE OF CUTTING THE
 WATER SERVICES AT MAIN ON 8TH ST. - CITY OF WPB PUBLIC
 UTILITIES ENGINEER.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 02-08-2019 Cont ID  
Sent By pleduc Date 02-08-2019 Time   Rev Time 0.00
Received By pleduc Date 02-07-2019 Time 10:32 Sent To  
Notes
2019-02-08 08:59:07AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM LIZ
 LEVESQUE, URBAN DESIGN PLANNER, THE LETTER ATTACHMENT
 DATED FEBRUARY 4, 2019, FROM REG ARCHITECTS, INC., AND
 DRAWING DOCUMENTS, THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS APPEAR TO HAVE BEEN
 ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 06-08-2018 Cont ID  
Sent By pleduc Date 06-08-2018 Time   Rev Time 0.00
Received By pleduc Date 06-08-2018 Time 16:57 Sent To  
Notes
2018-06-08 17:11:44THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PERMIT PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS OCCUPANCY SHALL BE
 PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 PLEASE REVIEW THE REAR EXTERIOR STAIR AS IT APPEARS TO
 HAVE UNPROTECTED WINDOW OPENINGS DURING THE EGRESS PATH
 THAT DO NOT MEET THE CODE REQUIREMENTS.
  
 PLEASE REVIEW THE EGRESS PATHS FROM THE 3RD FLOOR TO
 THE 2ND AND EXIT PATHS ON THE 2ND FLOOR. IT APPEAR THAT
 THERE ARE DOORS THAT OPEN AGAINST THE PATH OF TRAVEL
 AND A DOOR IN AREA 203 THAT OPENS INTO A STAIR TRAVEL
 PATH. ADDITIONALLY, IT APPEARS THAT SETS OF DOUBLE DOOR
 ALLOW FOR EGRESS FROM THE MEZZANINE BUT THEN SINGLE
 DOORS MAY PROVIDE FOR A PINCH POINT THAT REDUCES FLOW
 ADN RESTRICT EGRESS.
  
 11. A KNOX BOX WITH KEYS IS REQUIRED FOR ENTRY DOOR
 LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 4 Status P Date 06-04-2019 Cont ID  
Sent By rcaranci Date 06-04-2019 Time 16:06 Rev Time 0.00
Received By rcaranci Date 06-04-2019 Time 16:06 Sent To  
Notes
2019-06-04 16:06:57FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SUNSET LOUNGE Z18050030
 JUNE 4, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. COMMENTS 1-13 PREVIOUSLY SATISFIED
 2. SATISFIED.
 3. SATISFIED.
 4. SATISFIED.
 5. SATISFIED.
 6. SATISFIED.
 7. SATISFIED.
 8. SATISFIED.
 9. SATISFIED.
 10. SATISFIED.
 11. SATISFIED.
 12. SATISFIED.
 13. SATISFIED.
  
 14. SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445 L.
 PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 THE INFORMATION PROVIDED DOES NOT MEET THE CODE
 REQUIREMENT. ALL ADDED PLANT MATERIAL FROM THE PLANT
 LIST NEEDS TO BE INCLUDED, AND PERCENTAGE OF PLANTS
 THAT ARE DROUGHT TOLERANT OR NATIVE MUST MEET OR EXCEED
 60% OF THE TOTAL PLANTS.
  
 15. SATISFIED.
 ADDITIONAL COMMENTS 2/20/19:
 16. SATISFIED. THE OPEN SPACE ADJACENT TO THE BUILDING
 BEING COUNTED TOWARD THE PRIVATE OPEN SPACE IS BEING
 CLASSIFIED AS SEMI-PUBLIC COURTYARD. PROVIDE THE
 CALCULATIONS FOR 25% MIN. VEGETATED AREA AND 30% MIN.
 TREE CANOPY.
  
 17. SATISFIED. SHOW LOCATIONS OF WATER AND SEWER LINES
 ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE
 PLAN. CIVIL ENGINEERING PLANS ALREADY SHOW CONFLICTS.
 SHOW ROOT BARRIER LOCATIONS.
 18. SATISFIED. CORRECT THE PLANT LIST TO SHOW SHELL
 GINGER AS NON-NATIVE.
  
 19. SATISFIED. ADD WHEEL STOPS PARKING SPACES IN THE
 CENTER WITH OVERHANGS ADJACENT TO THE CENTER SIDEWALK.
 THE OVERHANG CANNOT BE OVER THE SIDEWALK.
  
 20. SATISFIED. PROVIDE SCREENING HEDGES FOR ABOVE
 GROUND UTILITY VALVES AS SHOWN ON THE CIVIL PLANS.
 21. SATISFIED. LANDSCAPE PLAN AND SITE PLAN HAVE
 DIFFERENCES THAT NEED TO BE CORRECTED TO BE CONSISTENT.
 22. SATISFIED. LANDSCAPE ISLAND MID ROW WHERE THE SEA
 GRAPE WAS LOCATED SHOULD BE MOVED TO PROVIDE THE AREA
 ADJACENT TO THE DUMPSTER NOW THAT THE SEAGRAPE IS NOT
 BEING PRESERVED.
 23. SATISFIED. THE 5 FOOT LANDSCAPE ISLAND ALONG THE
 NORTH ROW OF PARKING SHOULD ALSO BE SHIFTED TO THE
 TERMINAL ISLAND.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 05-01-2019 Cont ID  
Sent By rcaranci Date 05-01-2019 Time 12:59 Rev Time 0.00
Received By rcaranci Date 05-01-2019 Time 12:59 Sent To  
Notes
2019-05-01 13:02:10FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SUNSET LOUNGE Z18050030
 MAY 1, 2019
 RESUBMITTAL OF 4/5/19 REVISION
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. COMMENTS 1-13 PREVIOUSLY SATISFIED
 2. SATISFIED.
 3. SATISFIED.
 4. SATISFIED.
 5. SATISFIED.
 6. SATISFIED.
 7. SATISFIED.
 8. SATISFIED.
 9. SATISFIED.
 10. SATISFIED.
 11. SATISFIED.
 12. SATISFIED.
 13. SATISFIED.
  
 14. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445
 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 THE INFORMATION PROVIDED DOES NOT MEET THE CODE
 REQUIREMENT. ALL ADDED PLANT MATERIAL FROM THE PLANT
 LIST NEEDS TO BE INCLUDED, AND PERCENTAGE OF PLANTS
 THAT ARE DROUGHT TOLERANT OR NATIVE MUST MEET OR EXCEED
 60% OF THE TOTAL PLANTS.
  
 15. SATISFIED.
 ADDITIONAL COMMENTS 2/20/19:
 16. NOT SATISFIED. THE OPEN SPACE ADJACENT TO THE
 BUILDING BEING COUNTED TOWARD THE PRIVATE OPEN SPACE IS
 BEING CLASSIFIED AS SEMI-PUBLIC COURTYARD. PROVIDE THE
 CALCULATIONS FOR 25% MIN. VEGETATED AREA AND 30% MIN.
 TREE CANOPY.
  
 17. PARTIALLY SATISFIED. SHOW LOCATIONS OF WATER AND
 SEWER LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS
 WITH LANDSCAPING. SHOW LOCATIONS OF ANY ROOT BARRIERS
 REQUIRED TO PROTECT UTILITY LINES AND LABEL THEM ON THE
 PLAN. CIVIL ENGINEERING PLANS ALREADY SHOW CONFLICTS.
 SHOW ROOT BARRIER LOCATIONS.
 18. NOT SATISFIED. CORRECT THE PLANT LIST TO SHOW SHELL
 GINGER AS NON-NATIVE.
  
 19. SATISFIED. ADD WHEEL STOPS PARKING SPACES IN THE
 CENTER WITH OVERHANGS ADJACENT TO THE CENTER SIDEWALK.
 THE OVERHANG CANNOT BE OVER THE SIDEWALK.
  
 20. SATISFIED. PROVIDE SCREENING HEDGES FOR ABOVE
 GROUND UTILITY VALVES AS SHOWN ON THE CIVIL PLANS.
 21. SATISFIED. LANDSCAPE PLAN AND SITE PLAN HAVE
 DIFFERENCES THAT NEED TO BE CORRECTED TO BE CONSISTENT.
 22. SATISFIED. LANDSCAPE ISLAND MID ROW WHERE THE SEA
 GRAPE WAS LOCATED SHOULD BE MOVED TO PROVIDE THE AREA
 ADJACENT TO THE DUMPSTER NOW THAT THE SEAGRAPE IS NOT
 BEING PRESERVED.
 23. SATISFIED. THE 5 FOOT LANDSCAPE ISLAND ALONG THE
 NORTH ROW OF PARKING SHOULD ALSO BE SHIFTED TO THE
 TERMINAL ISLAND.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 02-21-2019 Cont ID  
Sent By rcaranci Date 02-21-2019 Time 14:02 Rev Time 0.00
Received By rcaranci Date 02-21-2019 Time 14:02 Sent To  
Notes
2019-02-21 14:03:56FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SUNSET LOUNGE Z18050030
 FEBRUARY 21, 2019
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. STAFF WILL MEET WITH THE APPLICANT TO
 DISCUSS CORRECTIONS TO THE TREE DISPOSITION LIST.
 A SITE VISIT IS NECESSARY TO POSITIVELY IDENTIFY THE
 TREE SPECIES. ALL INVASIVE EXOTIC PLANTS SUCH AS JAVA
 PLUM MUST BE IDENTIFIED TO BE REMOVED. THE SEAGRAPE
 TREE #13 IS IN AN AWKWARD LOCATION FOR THE PROPOSED
 SITE PLAN AND SHOULD BE RELOCATED. SABAL PALMS THAT ARE
 IN A POOR LOCATION THAT ARE LESS THAN 10 FOOT CLEAR
 TRUNK SHOULD BE REMOVED AND MITIGATED.
  
 2. SATISFIED. SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE SECTION 94-446 (G) AND PROVIDE 50 POINTS FROM
 THE DESIGN OPTIONS CHART.
  
 3. SATISFIED. PROVIDE A COLUMN FOR NATIVE PLANT SPECIES
 IDENTIFICATION IN THE PLANT LIST.
  
 4. SATISFIED. MONTGOMERY PALM IS LISTED AS MEDIUM WATER
 USAGE, PLEASE CORRECT.
  
 5. SATISFIED. THE ROSEMARY STREETSCAPE DESIGN NEEDS TO
 BE LOOKED AT MORE CLOSELY TO ASSURE THE TREES HAVE
 ADEQUATE ROOT SPACE WITH STRUCTURAL SOIL OR LARGER
 PLANTING AREAS.
  
 6. SATISFIED. PLEASE PROVIDE THE CALCULATIONS FOR THE
 REQUIRED AND PROVIDED TREES THE LANDSCAPE BUFFERS
 ADJACENT TO PARKING AREAS, AND THE STREET TREES ALONG
 AREAS NOT ADJACENT TO PARKING.
  
 7. SATISFIED. PROVIDE CALCULATIONS FOR PROVIDED TOTAL
 OPEN SPACE AND REQUIRED TREE COUNTS.
  
 8. SATISFIED. THE OAK TREES PROPOSED FOR THE ROSEMARY
 LANDSCAPE BUFFER ARE NOT POSSIBLE WITH THE OVERHEAD
 POWER LINES. PLEASE INDICATE IF THE POWER LINES WILL BE
 MOVED OR RELOCATED UNDERGROUND.
  
 9. SATISFIED. ON THE SITE PLAN AND LANDSCAPE PLAN, SHOW
 LOCATIONS OF STRUCTURAL SOIL UNDER SIDEWALK AREAS
 ADJACENT TO TREE PLANTING AREAS, PROVIDING A MINIMUM14
 BY 9 FOOT ROOT ZONE FOR ALL STREET TREES AND PROVIDE A
 TYPICAL DETAIL FOR STRUCTURAL SOIL.
  
 10. SATISFIED. IDENTIFY THE TYPE OF PRIVATE OPEN SPACE
 PROVIDED, AND SUPPLY CALCULATIONS FOR ANY REQUIRED
 VEGETATED AREA AND TREE CANOPY.
  
 11. SATISFIED. ALL TERMINAL LANDSCAPE ISLANDS FOR ROWS
 OF PARKING MUST BE THE FULL LENGTH OF THE ADJACENT
 PARKING SPACE.
  
 12. SATISFIED. PROVIDE MORE SUBSTANTIAL PLANTINGS
 INCLUDING HEDGES AND MID-RANGE TREES FOR THE REAR OF
 THE BUILDING.
  
 13. SATISFIED. THE GREEN ISLAND FICUS PLANTING ALONG
 THE CURB ON 9TH ST. MUST CONTAIN BREAKS ADJACENT TO THE
 PARKING SPACES TO ALLOW ACCESS.
  
 14. NOT SATISFIED. SHOW COMPLIANCE WITH SECTION 94-445
 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF PLANT
 MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT
 TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE
 LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH
 FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
 THE INFORMATION PROVIDED DOES NOT MEET THE CODE
 REQUIREMENT. ALL ADDED PLANT MATERIAL FROM THE PLANT
 LIST NEEDS TO BE INCLUDED, AND PERCENTAGE OF PLANTS
 THAT ARE DROUGHT TOLERANT OR NATIVE MUST MEET OR EXCEED
 60% OF THE TOTAL PLANTS.
  
 15. SATISFIED. CORRECT THE CAD OVERLAY EXTENDING INTO
 THE TOP OF THE PLANT LIST ON SHEET LP-1.
 ADDITIONAL COMMENTS 2/20/19:
 16. THE OPEN SPACE ADJACENT TO THE BUILDING BEING
 COUNTED TOWARD THE PRIVATE OPEN SPACE IS BEING
 CLASSIFIED AS SEMI-PUBLIC COURTYARD. PROVIDE THE
 CALCULATIONS FOR 25% MIN. VEGETATED AREA AND 30% MIN.
 TREE CANOPY.
  
 17. SHOW LOCATIONS OF WATER AND SEWER LINES ON THE
 LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH LANDSCAPING.
 SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO PROTECT
 UTILITY LINES AND LABEL THEM ON THE PLAN. CIVIL
 ENGINEERING PLANS ALREADY SHOW CONFLICTS.
  
 18. CORRECT THE PLANT LIST TO SHOW SHELL GINGER AS
 NON-NATIVE.
  
 19. ADD WHEEL STOPS PARKING SPACES IN THE CENTER WITH
 OVERHANGS ADJACENT TO THE CENTER SIDEWALK. THE OVERHANG
 CANNOT BE OVER THE SIDEWALK.
  
 20. PROVIDE SCREENING HEDGES FOR ABOVE GROUND UTILITY
 VALVES AS SHOWN ON THE CIVIL PLANS.
 21. LANDSCAPE PLAN AND SITE PLAN HAVE DIFFERENCES THAT
 NEED TO BE CORRECTED TO BE CONSISTENT.
 22. LANDSCAPE ISLAND MID ROW WHERE THE SEA GRAPE WAS
 LOCATED SHOULD BE MOVED TO PROVIDE THE AREA ADJACENT TO
 THE DUMPSTER NOW THAT THE SEAGRAPE IS NOT BEING
 PRESERVED.
 23. THE 5 FOOT LANDSCAPE ISLAND ALONG THE NORTH ROW OF
 PARKING SHOULD ALSO BE SHIFTED TO THE TERMINAL ISLAND.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 06-11-2018 Cont ID  
Sent By rcaranci Date 06-11-2018 Time 14:39 Rev Time 0.00
Received By rcaranci Date 06-11-2018 Time 14:39 Sent To  
Notes
2018-06-11 14:39:54FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SUNSET LOUNGE Z18050030
 JUNE11, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. STAFF WILL MEET WITH THE APPLICANT TO DISCUSS
 CORRECTIONS TO THE TREE DISPOSITION LIST.
 A SITE VISIT IS NECESSARY TO POSITIVELY IDENTIFY THE
 TREE SPECIES. ALL INVASIVE EXOTIC PLANTS SUCH AS JAVA
 PLUM MUST BE IDENTIFIED TO BE REMOVED. THE SEAGRAPE
 TREE #13 IS IN AN AWKWARD LOCATION FOR THE PROPOSED
 SITE PLAN AND SHOULD BE RELOCATED. SABAL PALMS THAT ARE
 IN A POOR LOCATION THAT ARE LESS THAN 10 FOOT CLEAR
 TRUNK SHOULD BE REMOVED AND MITIGATED.
  
 2. SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY LANDSCAPE
 SECTION 94-446 (G) AND PROVIDE 50 POINTS FROM THE
 DESIGN OPTIONS CHART.
  
 3. PROVIDE A COLUMN FOR NATIVE PLANT SPECIES
 IDENTIFICATION IN THE PLANT LIST.
  
 4. MONTGOMERY PALM IS LISTED AS MEDIUM WATER USAGE,
 PLEASE CORRECT.
  
 5. THE ROSEMARY STREETSCAPE DESIGN NEEDS TO BE LOOKED
 AT MORE CLOSELY TO ASSURE THE TREES HAVE ADEQUATE ROOT
 SPACE WITH STRUCTURAL SOIL OR LARGER PLANTING AREAS.
  
 6. PLEASE PROVIDE THE CALCULATIONS FOR THE REQUIRED AND
 PROVIDED TREES THE LANDSCAPE BUFFERS ADJACENT TO
 PARKING AREAS, AND THE STREET TREES ALONG AREAS NOT
 ADJACENT TO PARKING.
  
 7. PROVIDE CALCULATIONS FOR PROVIDED TOTAL OPEN SPACE
 AND REQUIRED TREE COUNTS.
  
 8. THE OAK TREES PROPOSED FOR THE ROSEMARY LANDSCAPE
 BUFFER ARE NOT POSSIBLE WITH THE OVERHEAD POWER LINES.
 PLEASE INDICATE IF THE POWER LINES WILL BE MOVED OR
 RELOCATED UNDERGROUND.
  
 9. ON THE SITE PLAN AND LANDSCAPE PLAN, SHOW LOCATIONS
 OF STRUCTURAL SOIL UNDER SIDEWALK AREAS ADJACENT TO
 TREE PLANTING AREAS, PROVIDING A MINIMUM14 BY 9 FOOT
 ROOT ZONE FOR ALL STREET TREES AND PROVIDE A TYPICAL
 DETAIL FOR STRUCTURAL SOIL.
  
 10. IDENTIFY THE TYPE OF PRIVATE OPEN SPACE PROVIDED,
 AND SUPPLY CALCULATIONS FOR ANY REQUIRED VEGETATED AREA
 AND TREE CANOPY.
  
 11. ALL TERMINAL LANDSCAPE ISLANDS FOR ROWS OF PARKING
 MUST BE THE FULL LENGTH OF THE ADJACENT PARKING SPACE.
  
 12. PROVIDE MORE SUBSTANTIAL PLANTINGS INCLUDING HEDGES
 AND MID-RANGE TREES FOR THE REAR OF THE BUILDING.
  
 13. THE GREEN ISLAND FICUS PLANTING ALONG THE CURB ON
 9TH ST. MUST CONTAIN BREAKS ADJACENT TO THE PARKING
 SPACES TO ALLOW ACCESS.
  
 14. SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 15. CORRECT THE CAD OVERLAY EXTENDING INTO THE TOP OF
 THE PLANT LIST ON SHEET LP-1.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS MAY BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 02-09-2019 Cont ID  
Sent By   Date 02-09-2019 Time   Rev Time  
Received By   Date 02-09-2019 Time   Sent To  
Notes
2019-02-09 19:19:27BASED ON RESUBMITTAL THE PLANS PASS. PLEASE NOTE IT
 LOOKS AS THOUGH YOU ARE PLANNING TO HAVE TWO DUMPSTERS
 IN THIS LOCATION. THEY WOULD NEED TO BE ON WHEELS TO
 WORK AS PROPOSED.
2018-07-23 14:16:00BASED ON A REVIEW OF THE PROJECT THE ENCLOSURE WILL
 NEED TO MEET ALL CITY GUIDELINES. THE PAD CAN BE BUILT
 TO HOLD A DUMPSTER THAT IS WHEELED OUT BY SANITATION
 STAFF. THE ENCLOSURE SHOULD BE SET FURTHER FORWARD FROM
 ITS LOCATION TOWARDS THE ENTRANCE. THIS WILL ALLOW THE
 DRIVERS TO PICK UP THE DUMPSTER ON THE STREET. PLEASE
 BE AWARE THAT THE CITY WILL ONLY BE ABLE TO PROVIDE UP
 TO A 6 CUBIC YARD DUMPSTER ON WHEELS. THE AMOUNT OF USE
 WILL BE BASED ON THE PRODUCTION BY THE OCCUPANTS WHICH
 WILL DICTATE THE SIZE OF THE DUMPSTER SERVICE NEEDED.
2018-06-11 14:35:25NEED TO PROVIDE DIRECT ACCESS FOR COMMERCIAL TRUCK TO
 SERVICE CONTAINERS. PLEASE PROVIDE AUTO TURN ANALYSIS
 AND DESIGN PROPER APPROACH ACCORDINGLY.

Review Stop STORM STORMWATER
Rev No 5 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 4 Status P Date 07-31-2019 Cont ID  
Sent By tward Date 07-31-2019 Time 15:29 Rev Time 0.00
Received By tward Date 07-31-2019 Time 15:41 Sent To  
Notes
2019-07-31 15:41:26THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JULY
 17, 2019 REVIEW PACKAGE. THEY CAN BE PROVISO FOR SITE
 PLAN APPROVAL.
  
 1.. PROVIDE CONDITION ASSESSMENT OF THE EXISTING
 DRAINAGE SYSTEM ON N. ROSEMARY AVE. [REPEAT COMMENT]
  
 2.. THERE SHOULD NOT BE DIRECT SHEETFLOW RUNOFF ACROSS
 THE SIDEWALK ALONG THE NORTH SIDE OF 8TH STREET.GRADE
 THE PARCEL NORTH OF 8TH STREET TO FLOW INTO THE
 PERVIOUS BANDS TO OBTAIN SOME STORMWATER TREATMENT.YARD
 DRAIN(S) CAN BE CONSTRUCTED TO COLLECT EXCESS
 STORMWATER AND PIPE IT TO THE EXISTING DRAIANGE
 STRUCTURE AT THE NW CORNER OF 8TH ST AND N. ROSEMARY
 AVE.
  
 3. PRIOR TO C.O., THE PROPOSED EASEMENTS SHALL BE
 RECORDED IN THE COUNTY CLERK'S OFFICE.
  
 4. LANDSCAPE PLAN DOES NOT MATCH THE SITE/HARDSCAPE
 PLAN. THE ONSITE CIRCULAR BANDS NORTH OF 8TH STREET
 MEASURE 5 FEET WIDE ON THE LANDSCAPE PLAN. THE BANDS
 ARE DIMENSIONED AS 4 FEET WIDE ON THE HARDSCAPE PLAN.
  
 5. 8TH STREET IMPROVEMENTS SHOULD BE COORDINATED WITH
 THE HEART AND SOUL PROJECT.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 3 Status F Date 06-06-2019 Cont ID  
Sent By tward Date 06-06-2019 Time 09:24 Rev Time 0.00
Received By tward Date 06-06-2019 Time 09:26 Sent To  
Notes
2019-06-06 09:26:28THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE MAY
 22, 2019 REVIEW PACKAGE:
 1. V. NOEL WAS PROVIDED WITH A SIGNED AND SEALED
 BOUNDARY AND TOPOGRAPHIC SURVEY. THE RELATIONSHIP
 BETWEEN THE NAVD 1988 AND NGVD 1929 VERTICAL DATUMS AT
 THIS LOCATION NEEDS TO BE LISTED ON THE SURVEY. [REPEAT
 COMMENT]
  
 2. SHOW FLOW AREAS FOR THE CROSS SECTION D AS SHOWN FOR
 THE OTHER SECTIONS ON SHEET C3.2.
  
 3. THE ELEVATIONS FOR THE CROSS SECTIONS ON SHEET C3.2
 DO NOT MATCH THE GRADING SHOWN ON SHEET C2.1. SUGGEST
 SHOWING THE CROSS SECTIONS WITHOUT THE ELEVATION GRID.
  
 4. PROVIDE CONDITION ASSESSMENT OF THE EXISTING
 DRAINAGE SYSTEM ON N. ROSEMARY AVE. [REPEAT COMMENT]
  
 5. STORMWATER SYSTEM FOR THE PARCEL NORTH OF 8TH STREET
 TO PROVIDE WATER QUALITY TREATMENT AND PEAK FLOW
 ATTENUATION PER SFWMD CRITERIA.
  
 6. DRAINAGE EASEMENT (MINIMUM 5 FEET FROM CENTERLINE OF
 PIPE) WILL BE NEEDED FOR THE PIPE BETWEEN S-303 AND THE
 EXISTING CATCH BASIN.
  
 7. SHEET C6.1 IS MISLABELED. SHEET INDEX SHOWS IT
 SHOULD BE LABELED SITE DEMOLITION AND EROSON CONTROL
 PLAN.
  
 8. ON THE DEMOLITION PLAN SHOW THE DEMOLITION OF 8TH
 STREET FOR THE HARDSCAPE ITEMS.
  
 9. WHO IS DESIGNING THE RAISED INTERSECTIONS ON 8TH
 STREET? HOW WILL IT AFFECT THE EXISTING DRAINAGE
 PATTERNS AT THESE INTERSECTIONS?
  
 10. ROOT BARRIERS WILL BE NEEDED FOR THE OAK TREE NEXT
 TO EXISTING INLET AT THE NORTHWEST CORNER OF 8TH STREET
 AND N. ROSEMARY AVE.
  
 11. SEVERAL CONFLICTS BETWEEN PROPOSED STORM PIPE ON
 HENRIETTA AVE AND EXISTING/PROPOSED TREES.
  
 12. SEVERAL CONFLICTS BETWEEN PROPOSED STORM PIPE ON N.
 ROSEMARY AVE AND PROPOSED TREES.
  
 13. HOW IS THIS PROJECT BEING COORDINATED WITH THE
 PROPOSED IMPROVEMENTS ON THE SOUTH SIDE OF 8TH STREET?
  
 14. STORMWATER RUNOFF FROM THE PROPOSED ALLEY R/W
 ABANDONMENT SHOULD FLOW TO THE ONSITE DRAINAGE SYSTEM.
  
 15. SHOW AND LABEL THE PROPOSED PROPERTY LINES AT EACH
 END OF THE ALLEY TO BE ABANDONED AND SHOW PROPOSED
 EASEMENTS ON THE CIVIL PLANS.
  
 16. THE WIDTH OF THE TRAVEL LANES CANNOT INCLUDE THE
 GUTTER. (P&Z SITE PLAN SHEET A0.04)
  
 17. CORRECT THE LABELING AND DIMENSIONING OF THE
 HENRIETTA AVE RIGHT-OF-WAY ON SHEET A0.04. THE 50.0
 DIMENSION AT THE SOUTH END OF THE STREET IS SHOWN FROM
 BACK OF SIDEWALK TO BACK OF SIDEWALK. THE DIMENSION AT
 THE NORTH END OF THE STREET READS ?40.0 R.O.W. (WAS
 30.0 R.O.W.)? AND IS SHOWN FROM FRONT OF SIDEWALK TO
 FRONT OF SIDEWALK. RIGHT OF WAY LINES SHOULD MATCH THE
 BOUNDARY SURVEY.
  
 TRACY WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 2 Status F Date 02-20-2019 Cont ID  
Sent By tward Date 02-20-2019 Time 08:38 Rev Time 0.00
Received By tward Date 02-20-2019 Time 09:01 Sent To  
Notes
2019-02-20 09:01:15THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE
 FEBRUARY 5, 2019 REVIEW PACKAGE:
  
 1. SHOW THE VERTICAL DATUM RELATIONSHIP BETWEEN NAVD
 1988 AND NGVD 1929 ON THE SURVEY (SHEET A.SI) [REPEAT
 COMMENT].
  
 2. ADD THE VERTICAL DATUM CONVERSION EQUATION TO NOTE 7
 ON SHEET C1.0.
  
 3. LABEL THE VERTICAL DATUM AND SHOW THE VERTICAL DATUM
 CONVERSION EQUATION ON EACH SHEET WITH ELEVATION DATA
 (SHEETS C2.1, C2.2, C3.1, C3.2, C4.1, C6.1).
  
 4. SURVEY (SHEET A.SI) IS NOT SIGNED AND SEALED.
  
 5. PROVIDE A CROSS SECTION FOR 8TH STREET SHOWING HOW
 THE VALET DROP OFF AREA WILL BE GRADED.
  
 6. SURVEY NOTE ON SHEET A.SI STATES THERE IS A LATER
 CERTIFIED SURVEY. PROVIDE A COPY OF THIS SURVEY.
 [REPEAT COMMENT]
  
 7. PROVIDE A CONDITION ASSESSMENT OF THE EXISTING
 DRAINAGE SYSTEM ON N. ROSEMARY AVE. [REPEAT COMMENT]
  
 8. NEED WHEEL STOP OR CURB FOR THE FOUR FULL DEPTH
 PARKING SPACES.
  
 9. HARDSCAPE WITHIN THE PUBLIC RIGHT OF WAY WILL
 REQUIRE MAINTENANCE AGREEMENT WITH THE CITY.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 06-13-2018 Cont ID  
Sent By tward Date 06-13-2018 Time 07:21 Rev Time 0.00
Received By tward Date 06-13-2018 Time 07:22 Sent To  
Notes
2018-06-13 07:22:04THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED. LABEL THE VERTICAL
 DATUM ON THE CONCEPTUAL PAVING, GRADING & DRAINAGE PLAN
 AND THE WATER & WASTEWATER PLAN. SHOW THE DATUM
 CONVERSION IF NAVD 1988 IS USED. SHOW THE DATUM
 CONVERSION ON THE SURVEY.
  
 2. UPDATE THE FLOOD ZONE INFORMATION ON SHEET A.SI.
 FEMA ISSUED NEW FIRMS IN OCTOBER 2017.
  
 3. ONSITE STORMWATER MANAGEMENT SYSTEM IS TO PROVIDE
 WATER QUALITY TREATMENT AND PEAK FLOW ATTENUATION PER
 SFWMD CRITERIA.
  
 4. EXPLAIN HOW STORMWATER MANAGEMENT IS BEING PROVIDED
 IN THE PARCEL NORTH OF 8TH STREET.
  
 5. IT APPEARS THE CURB IS BEING RELOCATED AT THE NE
 CORNER OF 8TH STREET AND N. ROSEMARY AVE. HOW WILL THIS
 AFFECT THE EXISTING ROADWAY DRAINAGE SYSTEM.
  
 6. PROVIDE ADDITIONAL EXISTING GRADES ALONG N. ROSEMARY
 AVE AND HENRIETTA AVE.
  
 7. SURVEY NOTE ON SHEET A.SI STATES THERE IS A LATER
 CERTIFIED SURVEY. PROVIDE A COPY OF THIS SURVEY.
  
 8. PROVIDE A CONDITION ASSESSMENT OF THE EXISTING
 DRAINAGE SYSTEM ON N. ROSEMARY AVE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE SFWMD ERP FOR THE DEVELOPMENT.
  
 3. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 05-28-2019 Cont ID  
Sent By vnoel Date 05-28-2019 Time 11:38 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 06-11-2018 Cont ID  
Sent By vnoel Date 06-11-2018 Time 09:38 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-06-11 09:43:411. NO SURVEY PROVIDED.
 2. ALLEY WILL REQUIRE ABANDONMENT THRU PLANNING.
 EASEMENT FOR SANITARY WILL BE RESERVED.
 3. ALL EXISTING SERVICES TO BE ABANDONED WILL BE
 REQUIRED TO CUT BACK TO MAIN.
 4. ENGINEERING DEVELOPMENT APPLICATION WILL BE
 REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 4 Status P Date 06-04-2019 Cont ID  
Sent By   Date 06-12-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-06-04 13:55:35**REVISED JUNE 12, 2019**
  
 PASSED WITH THE FOLLOWING CONDITIONS OF APPROVAL.
  
 1. THE APPLICANT SHOULD REVISE THE SITE PLAN DURING
 PERMITTING TO SHOW NORTH CURB LINE AND ANY CURB CUTS ON
 NORTH SIDE OF NINTH STREET.
 2. THE APPLICANT SHOULD REVISE THE SITE PLAN DURING
 PERMITTING TO PROVIDE ADEQUATE SIGHT DISTANCE ON THE
 SOUTHBOUND APPROACH FROM THE PARKING LOT ADJACENT TO
 THE DUMPSTER, PER FDOT GREENBOOK/AASHTO REQUIREMENTS.
 3. THE APPLICANT SHOULD COORDINATE WITH THE CITY ON THE
 ROSEMARY CROSS-SECTION ALONG THE SITE FRONTAGE DURING
 PERMITTING, AND THE APPLICANT MAY BE REQUIRED TO
 ELIMINATE PARALLEL PARKING ALONG ROSEMARY AVENUE IF
 NECESSARY.
 4. THE APPLICANT SHOULD COORDINATE WITH THE CITY ON THE
 STREET LIGHTING REQUIREMENT DURING PERMITTING.
  
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status F Date   Cont ID  
Sent By   Date 04-23-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-04-23 10:27:20***PREVIOUS COMMENTS WERE NOT ADDRESSED AND ARE
 REPEATED HERE. PLEASE PROVIDE RESPONSE TO COMMENTS.***
  
 1. A TRAFFIC STATEMENT WAS NEVER PROVIDED WITH THE
 SUBMITTAL. PLEASE PROVIDE EVENT DATA ON THE EXISTING
 DEVELOPMENT, AND DISCUSS THE ACTIVITIES WHICH WILL BE
 HELD ON SITE, INCLUDING INFORMATION ON THE HOURS OF
 OPERATIONS, DURATION, PROJECTED NUMBER OF ATTENDEES,
 ETC. PLEASE VERIFY WHETHER THE PROVIDED PARKING SPACES
 WOULD BE SUFFICIENT FOR THE PLANNED ACTIVITIES.
 2. LABEL RADIUSES OF CURB RETURNS.
 3. PROVIDE TYPICAL SECTIONS FOR PUBLIC STREETS
 INCLUDING 8TH STREET AND THE ALLEY WITH DIMENSIONS
 4. PROVIDE SIGNED AND SEALED SURVEY AS REQUIRED IN THE
 CITY?S DEVELOPMENT APPLICATION FORM.
 5. REVISE SITE PLAN TO SHOW NORTH CURB LINE AND ANY
 CURB CUTS ON NORTH SIDE OF NINTH STREET
 6. LIVE OAKS ARE PROPOSED UNDER POWER LINE ON NORTH
 ROSEMARY AVE. CHECK FPL REQUIREMENTS.
 7. EIGHT-FOOT WIDE SIDEWALKS ARE REQUIRED FOR
 NON-RESIDENTIAL IN THE DOWNTOWN MASTER PLAN.
 8. ON-SITE, PROVIDE SIGHT TRIANGLE EXHIBIT FOR SIGHT
 LINE WITH DUMPSTER.
 9. THE 20-FOOT VISIBILITY TRIANGLE SHOULD BE DRAWN
 ALONG THE CORNER OF PROPERTY LINES. PLEASE REVISE.
 10. SHEET A0.04 EIGHT ST. IS NOTED AS 60? ROW, BUT 50?
 PLOTTED. CLARIFY WHY THERE ARE TWO RIGHT OF WAY WIDTHS.
 11. WE DON?T SUPPORT SHIFTING OF ROSEMARY TO PROVIDE
 PARALLEL PARKING ON ONE SIDE AS THIS WILL MAKE IT
 DIFFICULT FOR THE OTHER SIDE OF THE STREET TO PROVIDE
 PARALLEL PARKING IN THE FUTURE. THIS WILL ALSO CAUSE
 ROSEMARY AVENUE TO SHIFT THROUGH INTERSECTIONS AT NINTH
 STREET AND EIGHT STREET. PLEASE HOLD ROADWAY CENTERLINE
 AND WIDEN ONSITE FOR PARALLEL PARKING.
 12. THE PEDESTRIAN CONNECTION AT MIDBLOCK ON 8TH STREET
 GOES THROUGH THE MIDDLE OF THE VALET/DROPOFF LANE.
 PROVIDE A BULB OUT AT THIS LOCATION FOR THE MIDBLOCK
 CONNECTION. ALSO, THE CIVIL PLAN DOES NOT SHOW THIS
 MIDBLOCK CONNECTION. PLEASE REVISE.
 13. ARE STREET LIGHTS BEING PROPOSED? WHO WILL MAINTAIN
 THE STREET LIGHTS?
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]
 (IN-HOUSE ON TUESDAYS AND WEDNESDAYS)

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 02-13-2019 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2019-02-13 15:20:54NOTE: QUITE A NUMBER OF PREVIOUS COMMENTS WERE NOT
 ADDRESSED AND ARE REPEATED HERE.
 1. A TRAFFIC STATEMENT WAS NEVER PROVIDED WITH THE
 SUBMITTAL. PLEASE PROVIDE EVENT DATA ON THE EXISTING
 DEVELOPMENT, AND DISCUSS THE ACTIVITIES WHICH WILL BE
 HELD ON SITE, INCLUDING INFORMATION ON THE HOURS OF
 OPERATIONS, DURATION, PROJECTED NUMBER OF ATTENDEES,
 ETC. PLEASE VERIFY WHETHER THE PROVIDED PARKING SPACES
 WOULD BE SUFFICIENT FOR THE PLANNED ACTIVITIES.
 2. LABEL RADIUSES OF CURB RETURNS.
 3. PROVIDE TYPICAL SECTIONS FOR PUBLIC STREETS
 INCLUDING 8TH STREET AND THE ALLEY WITH DIMENSIONS
 4. PROVIDE SIGNED AND SEALED SURVEY AS REQUIRED IN THE
 CITY'S DEVELOPMENT APPLICATION FORM.
 5. REVISE SITE PLAN TO SHOW NORTH CURB LINE AND ANY
 CURB CUTS ON NORTH SIDE OF NINTH STREET
 6. LIVE OAKS ARE PROPOSED UNDER POWER LINE ON NORTH
 ROSEMARY AVE. CHECK FPL REQUIREMENTS.
 7. EIGHT-FOOT WIDE SIDEWALKS ARE REQUIRED FOR
 NON-RESIDENTIAL IN THE DOWNTOWN MASTER PLAN.
 8. ON-SITE, PROVIDE SIGHT TRIANGLE EXHIBIT FOR SIGHT
 LINE WITH DUMPSTER.
 9. THE 20-FOOT VISIBILITY TRIANGLE SHOULD BE DRAWN
 ALONG THE CORNER OF PROPERTY LINES. PLEASE REVISE.
 10. SHEET A0.04 EIGHT ST. IS NOTED AS 60' ROW, BUT 50'
 PLOTTED. CLARIFY WHY THERE ARE TWO RIGHT OF WAY WIDTHS.
 11. WE DON'T SUPPORT SHIFTING OF ROSEMARY TO PROVIDE
 PARALLEL PARKING ON ONE SIDE AS THIS WILL MAKE IT
 DIFFICULT FOR THE OTHER SIDE OF THE STREET TO PROVIDE
 PARALLEL PARKING IN THE FUTURE. THIS WILL ALSO CAUSE
 ROSEMARY AVENUE TO SHIFT THROUGH INTERSECTIONS AT NINTH
 STREET AND EIGHT STREET. PLEASE HOLD ROADWAY CENTERLINE
 AND WIDEN ONSITE FOR PARALLEL PARKING.
 12. THE PEDESTRIAN CONNECTION AT MIDBLOCK ON 8TH STREET
 GOES THROUGH THE MIDDLE OF THE VALET/DROPOFF LANE.
 PROVIDE A BULB OUT AT THIS LOCATION FOR THE MIDBLOCK
 CONNECTION. ALSO, THE CIVIL PLAN DOES NOT SHOW THIS
 MIDBLOCK CONNECTION. PLEASE REVISE.
 13. ARE STREET LIGHTS BEING PROPOSED? WHO WILL MAINTAIN
 THE STREET LIGHTS?
  
 SHING TSOI
 CITY IN-HOUSE TRAFFIC CONSULTANT
 561-494-1141
 [email protected]

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 06-12-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-06-12 11:01:51SUNSET LOUNGE SITE PLAN (DATED 5-30-18)
 - THE COMMENTS ARE PRELIMINARY AS THE PLANS ARE MISSING
 KEY DIMENSIONS SUCH AS RADIUSES OF CURB RETURNS AND
 WIDTHS OF LANES ON STREETS.
 - LABEL RADIUSES OF CURB RETURNS.
 - PROVIDE TYPICAL SECTIONS FOR PUBLIC STREETS WITH
 DIMENSIONS
 - PROVIDE SIGNED AND SEALED SURVEY
 - REVISE SITE PLAN TO SHOW NORTH CURB LINE AND ANY CURB
 CUTS ON NORTH SIDE OF NINTH STREET
 - ON SITE ANGLE PARKING APPEARS TO BE 60 DEGREES. AISLE
 WIDTH IS TOO NARROW FOR 60 DEGREES.
 - LABEL ANGLE OF ANGLE PARKING WITH RESUBMITTAL
 - LIVE OAKS ARE PROPOSED UNDER POWER LINE ON NORTH
 ROSEMARY AVE. CHECK FPL REQUIREMENTS.
 - INTERNAL PARKING LOT. AISLE WIDTH DOESN?T MEET CITY
 STANDARD 24 FOOT.
 - INTERNAL PARKING LOT, SPACES ARE 9? WIDE. CITY CODE
 IS 8.5 FOOT WIDE.
 - EIGHT FOOT WIDE SIDEWALKS ARE REQUIRED FOR
 NON-RESIDENTIAL IN THE DOWNTOWN MASTER PLAN.
 - SHEET A0.04 COUNT OF ON-STREET PARALLEL PARKING
 SPACES IN PLAN VIEW IS INCORRECT.
 - ON-SITE, PROVIDE SIGHT TRIANGLE EXHIBIT FOR SIGHT
 LINE WITH DUMPSTER.
 - NINTH STREET. ON STREET PARKING SPACE IS TOO CLOSE TO
 FIRE HYDRANT. FLORIDA STATUTES 15? NO PARKING FROM
 HYDRANT.
 - SHEET A0.04 EIGHT ST. IS NOTED AS 60? ROW, BUT 50?
 PLOTTED. CLARIFY WHY THERE ARE TWO RIGHT OF WAY WIDTHS.
 - WHY ARE BIKE LANES PROPOSED ON 8TH STREET?
 - APPEARS ROSEMARY AVENUE IS SHIFTING THROUGH
 INTERSECTION OF EIGHT STREET TO ALLOW FOR PARALLEL
 PARKING ON WEST SIDE OF ROSEMARY AVE. PROVIDE DETAILS
 FOR ROADWAY TRANSITION.
 - ROSEMARY AVE. ON STREET PARKING SPACE IS 8? 8 INCHES
 WIDE. IT CAN BE REDUCED TO 8?.
 - ROSEMARY IS SHOWN WITH NINE FOOT LANES. PROVIDE 10
 FOOT WIDE LANES.
 - WE DON'T SUPPORT SHIFTING OF ROSEMARY TO PROVIDE
 PARALLEL PARKING ON ONE SIDE AS THIS WILL MAKE IT
 DIFFICULT FOR THE OTHER SIDE OF THE STREET TO PROVIDE
 PARALLEL PARKING IN THE FUTURE. SUGGEST HOLDING ROADWAY
 CENTERLINE AND WIDEN ONSITE FOR PARALLEL PARKING.
 - WHO IS THE ENGINEER OF RECORD FOR THE ROADWAY
 IMPROVEMENTS?
 - CONSIDER ON-STREET ANGLED PARKING AROUND BUILDING AND
 PARK TO PROVIDE ADDITIONAL PARKING
 - SUGGEST ELIMINATING SOME ON-STREET PARKING ON 8TH
 STREET TO PROVIDE A PEDESTRIAN CONNECTION AT MIDBLOCK
 FROM THE SUNSET TO THE PARK
 - ARE STREET LIGHTS BEING PROPOSED? WHO WILL MAINTAIN
 THE STREET LIGHTS?
 - CODE OF ORDINANCES 94-305, TABLE X-1 ROSEMARY IS A
 THOROUGHFARE WITH A 30 FOOT RIGHT OF WAY SETBACK AND IS
 REQUIRED TO HAVE FOUR LANES.
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 4 Status P Date 05-28-2019 Cont ID  
Sent By elevesqu Date 05-28-2019 Time 10:22 Rev Time 0.00
Received By elevesqu Date 05-28-2019 Time 10:18 Sent To  
Notes
2019-05-28 10:22:41PROVISOS:
 APPLICATION FOR ALLEY ABANDONMENT ONGOING.
 APPLICANT SHALL SUBMIT FOR REPLAT AND UNIFY PROPERTIES.
 PHOTOMETRICS AND STREET LIGHT DETAIL FOR STREET
 LIGHTING SHALL BE PROVIDED AT TIME OF PERMIT.
 APPLICANT SHALL SUBMIT SEPARATE LANDSCAPE PERMIT.
 A SEPARATE FENCE PERMIT WILL BE REQUIRED FOR THE
 PROPOSED METAL FENCE.
 ANY SIGNAGE SHALL REQUIRE SEPARATE PERMIT.
 ALL ABOVE GROUND UTILITIES, INCLUDING THE BACKFLOW
 PREVENTER SHALL BE LANDSCAPED.
 EXACT LOCATION OF BACKFLOW PREVENTER, TRANSFORMER, AND
 FDC SHALL BE REVIEWED IN THE FIELD DURING CONSTRUCTION
 WITH ENGINEERING DEPARTMENT, LANDSCAPE PLANNER, AND
 ZONING DEPARTMENT.
 THE SIDEWALK ALONG ROSEMARY AVENUE CROSS INTO THE
 PROPERTY LINE. AN EASEMENT WILL BE REQUIRED.
 APPLICANT SHALL MOVE DUMPSTER ENCLOSURE OUT OF SIGHT
 TRIANGLE LINE. THIS MAY BE ACCOMPLISHED BY REMOVING
 TRAFFIC ISLAND AND SHIFTING PARKING SPACES AND
 ENCLOSURE TO THE NORTH.
  

Review Stop Z ZONING
Rev No 3 Status F Date 05-03-2019 Cont ID  
Sent By elevesqu Date 05-03-2019 Time 16:03 Rev Time 0.00
Received By elevesqu Date 05-03-2019 Time 16:03 Sent To  
Notes
2019-05-03 16:03:05 
 PER SECTION 94-54, THE ALLEY ABANDONMENT IS REQUIRED TO
 HAVE DAC REVIEW AS PART OF THE FORMAL SITE PLAN REVIEW
 PROCESS. DAC REVIEW FOR ALLEY ABANDONMENT REQUIRED
 PRIOR TO SITE PLAN APPROVAL. DAC REVIEW OF ALLEY
 ABANDONMENT SCHEDULED FOR 5/8/2019.
  
 1. SATISFIED.
 2. SATISFIED.
 3. SATISFIED.
 4. SATISFIED.
 5. SATISFIED.
 6. SATISFIED.
 7. SATISFIED.
 8. SATISFIED.
 9. SATISFIED.
 10. SATISFIED.
 11. SATISFIED.
 12. SATISFIED.
 13. SATISFIED.
 14. ONGOING. PLEASE NOTE, THE PROPERTIES WILL NEED TO
 BE UNIFIED.
 15. ONGOING. PLEASE NOTE, THIS SITE WILL BE REQUIRED TO
 BE REPLATTED.
 16. SATISFIED.
 17. SATISFIED.
 18. SATISFIED.
 19. SATISFIED.
 20. SATISFIED.
 21. SATISFIED.
 22. SATISFIED.
 23. SATISFIED.
 24. SATISFIED.
 25. SATISFIED.
 26. SATISFIED.
 27. SATISFIED.
 28. SATISFIED.
 29. SATISFIED.
 30. SATISFIED.
 31. SATISFIED.
 32. SATISFIED.
 33. SATISFIED.
 34. SATISFIED.
 35. SATISFIED.
 36. SATISFIED.
 37. ONGOING. PROVISO: PHOTOMETRICS AND STREET LIGHT
 DETAIL FOR STREET LIGHTING SHALL BE PROVIDED AT TIME OF
 PERMIT.
 38. SATISFIED.
 39. SATISFIED.
 40. ONGOING. PARKING SHALL COMPLY WITH SECTION
 94-113(F) FOR LANDSCAPING REQUIREMENTS.
 LANDSCAPE REQUIREMENTS SHALL BE REVIEWED THROUGH
 SEPARATE LANDSCAPE PERMIT. SEE COMMENT #45.
 41. SATISFIED.
 42. SATISFIED.
 43. SATISFIED.
 44. SATISFIED.
 NEW COMMENTS FEBRUARY 22, 2019
 45. ONGOING. PLEASE NOTE, A SEPARATE LANDSCAPE PERMIT
 WILL BE REQUIRED.
 46. ONGOING. PLEASE NOTE, A SEPARATE FENCE PERMIT WILL
 BE REQUIRED FOR THE PROPOSED METAL FENCE.
 47. SATISFIED.
 48. SATISFIED.
 49. SATISFIED.
 50. ONGOING. PROVISO: ALL ABOVE GROUND UTILITIES,
 INCLUDING THE BACKFLOW PREVENTER SHALL BE LANDSCAPED.
 PLEASE ADDRESS AT TIME OF LANDSCAPE PERMIT. EXACT
 LOCATION OF BACKFLOW PREVENTER, TRANSFORMER, AND FDC
 SHALL BE REVIEWED IN THE FIELD DURING CONSTRUCTION WITH
 ENGINEERING DEPARTMENT, LANDSCAPE PLANNER, AND ZONING
 DEPARTMENT.
 51. SATISFIED.
 52. SATISFIED.
 53. SATISFIED.
 54. SATISFIED.
 55. SATISFIED.
 56. SATISFIED.
 57. SATISFIED.
 58. ONGOING. PLEASE UPDATE ALL CIVIL PLANS TO MATCH THE
 SITE PLAN. COORDINATE WITH TRAFFIC REVIEW COMMENTS.
 59. SATISFIED.
 60. SATISFIED.
 61. SATISFIED.
 62. ONGOING.
 63. SATISFIED.
  
 PROVISOS:
 THE SIDEWALK ALONG ROSEMARY AVENUE CROSS INTO THE
 PROPERTY LINE. AN EASEMENT WILL BE REQUIRED.
  

Review Stop Z ZONING
Rev No 2 Status F Date 02-22-2019 Cont ID  
Sent By elevesqu Date 02-22-2019 Time 14:51 Rev Time 0.00
Received By elevesqu Date 02-22-2019 Time 14:50 Sent To  
Notes
2019-02-22 14:51:131. SATISFIED. PLEASE CONSIDER OPEN AIR STRUCTURES UNDER
 THE HALLWAY AND AREAS CONNECTING TO THE EXISTING
 STRUCTURE ON THE ROOFTOP TERRACE LEVEL TO MEET THE
 DISTRICT HEIGHT REQUIREMENTS.
 2. SATISFIED. PLEASE PROVIDE MORE DETAIL AND HEIGHT OF
 THE STRUCTURES ON THE ROOFTOP TERRACE.
 3. SATISFIED. CONSIDER THE USE OF PERMEABLE SURFACE,
 ESPECIALLY IN THE PROPOSED SURFACE PARKING LOT.
 4. SATISFIED. THE COLORED RENDERING AND THE PROPOSED
 ELEVATIONS DO NOT APPEAR TO MATCH. PLEASE REVISE
 ACCORDINGLY.
 5. SATISFIED. PLEASE NOTE, PER TABLE IV-38, THE CORRECT
 STREET DESIGNATIONS AND SETBACKS ARE AS FOLLOWS:
 A. FRONT (8TH STREET): RESIDENTIAL- 17'
 B. SIDE (9TH STREET): RESIDENTIAL - 17'
 C. SIDE (HENRIETTA AVE): RESIDENTIAL- 17'
 D. SIDE (ROSEMARY AVE): SECONDARY - 12'
 6. SATISFIED. PLEASE CORRECT THE SITE DATA TABLE, AND
 INCLUDE THE SETBACK DIMENSIONS OF THE PROPOSED ADDITION
 AND PARKING LOTS ON THE SITE PLAN (SHEET A0.04, SHEET
 A1.00).
 7. SATISFIED. PLEASE SHOW EXISTING CURBS AND
 CENTERLINES OF ALL ROADWAYS AND INDICATE WHERE THE
 CURBS WILL BE MODIFIED.
 8. SATISFIED. PLEASE NOTE, IN THE DOWNTOWN MASTER PLAN
 AREA, SETBACKS ARE MEASURED FROM BACK OF CURB, AS
 DEFINED IN SECTION 94-109. WHERE THE CURB LOCATION
 VARIES ALONG A PROPERTY, THE BACK OF CURB SHALL BE
 DEFINED AS THE PREDOMINANT BACK OF CURB LINE FURTHEST
 FROM THE CENTER LINE OF THE ROAD (CURB LOCATION ALONG
 50% OF STREET FRONTAGE). PLEASE AMEND THE SETBACK
 MEASUREMENTS AS NECESSARY.
 9. SATISFIED. PLEASE NOTE, THE MINIMUM REQUIRED
 LANDSCAPE BUFFER FOR PARKING CANNOT BE INCLUDED AS PART
 OF THE REQUIRED SETBACK. PLEASE REVISE ACCORDINGLY.
 10. SATISFIED. PLEASE NOTE, THE MAXIMUM BUILDING
 FOOTPRINT FOR GROUND LEVEL IS 87% AND FOR THE PODIUM IS
 90%. PLEASE PROVIDE DETAIL IN THE TABLE ON THE PERCENT
 BUILDING FOOTPRINT FOR EACH PROPOSED NEW LEVEL. PLEASE
 AMEND THE LABEL FROM "LOT COVERAGE" TO "BUILDING
 FOOTPRINT."
 11. PARTIALLY SATISFIED. PARKING CALCULATIONS IS BASED
 ON NET INTERIOR AREA, NOT GROSS AREA. PLEASE INCLUDE
 THE NET INTERIOR AREA AND CALCULATE ACCORDINGLY. PLEASE
 BREAK DOWN THE TABLE INTO REQUIRED AND PROVIDED
 PARKING.
 THE MINIMUM PARKING FOR THIS SITE IS 1/1000 AND THE
 MAXIMUM IS 2/1000. PLEASE ADJUST TABLE ACCORDINGLY.
 12. PARTIALLY SATISFIED. PLEASE SUBMIT AN ILLUSTRATION
 AND TABLE OF THE F.A.R. BREAKDOWN BY EACH SEPARATE
 FLOOR, INCLUDING THE ADDITIONAL PARKING. PLEASE
 SEPARATE THE SQUARE FOOTAGE BY ALLEY, NORTH PROPERTY
 AND SOUTH PROPERTY. PER SECTION 94-79 (HISTORIC
 RESIDENTIAL DESIGN STANDARDS), FAR INCLUDES INTERIOR
 AND ROOFED EXTERIOR STAIRWAYS, ELEVATORS, ESCALATORS
 AND SIMILAR FEATURES. PLEASE REVISE ACCORDINGLY.
 THE PROVIDED PLAN IS DIFFICULT TO INTERPRET. PLEASE
 PROVIDE A FAR BREAKDOWN BY EACH FLOOR USING THE FLOOR
 PLAN. AN EXAMPLE CAN BE SENT IF REQUESTED.
 13. NOT SATISFIED. THE APPLICANT SHALL SUBMIT A
 SEPARATE ALLEY ABANDONMENT APPLICATION.
 14. ONGOING. PLEASE NOTE, THE PROPERTIES WILL NEED TO
 BE UNIFIED.
 15. ONGOING. PLEASE NOTE, THIS SITE WILL BE REQUIRED TO
 BE REPLATTED.
 16. SATISFIED. PLEASE INCLUDE ILLUSTRATIONS AND A DATA
 TABLE DEMONSTRATING COMPLIANCE WITH THE ACTIVE USE
 REQUIREMENTS FOR NWD-2, AS REQUIRED BY TABLE IV-38.
 PLEASE NOTE, THE STREET DESIGNATIONS ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 17. SATISFIED. PLEASE INCLUDE ILLUSTRATIONS AND A DATA
 TABLE DEMONSTRATING COMPLIANCE WITH THE TRANSPARENCY
 REQUIREMENTS FOR THE GROUND FLOOR IN NWD-2, AS REQUIRED
 BY TABLE IV-38. PLEASE NOTE, THE STREET DESIGNATIONS
 ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 18. NOT SATISFIED. THE PROPOSED AISLE WIDTHS IN SOME
 SECTIONS OF THE PROPOSED PARKING AREAS APPEAR TO BE TOO
 SMALL. PLEASE LOOK AT SECTION 94-485, FIGURE XV-2 AND
 REVISE ACCORDINGLY.
 ALTHOUGH THE TERMINAL ISLAND WAS REDUCED BUT THE 24?
 DIMENSION INCLUDES 2 FEET OF THE TERMINAL ISLAND.
 PLEASE REVISE. THE TERMINAL ISLAND CAN BE REDUCED TO 5
 FEET WITH A MINIMUM RADIUS OF TWO AND ONE-HALF FEET AT
 ITS END TO MEET THIS REQUIREMENT.
 19. SATISFIED. THE PROPOSED NUMBER OF ADA PARKING
 SPACES DOES NOT MEET THE REQUIREMENT AS ESTABLISHED BY
 SECTION 94-485, TABLE XV-3. PLEASE REVISE.
 20. SATISFIED. IF PROPOSED ADA PARKING SPACES ARE
 DIAGONAL, THE REQUIRED LENGTH IS 18' AND WIDTH IS 12',
 PER SECTION 94-485 (O)(2). THE PROPOSED DIAGONAL
 PARKING SPACE AREA TO THE EAST OF THE BUILDING ADDITION
 DOES NOT WORK WITH REQUIRED PARKING DEPTHS AND DRIVE
 AISLE WIDTHS. PLEASE CONSIDER ALTERNATIVES.
 21. SATISFIED. THE NUMBER OF ON STREET PARKING ALONG
 HENRIETTA AVENUE IS LABELED AS 5 SPACES BUT THERE
 APPEAR TO ONLY BE 4 SPACES. PLEASE CONFIRM LABELS AND
 TOTAL NUMBERS IN THE SITE DATA TABLE.
 22. SATISFIED. THE EXISTING ON SITE POWER POLES APPEAR
 TO CREATE PROBLEMS WITH PROPOSED SIDEWALKS, ON STREET
 PARKING AND PROPOSED STREET TREES. PLEASE PROVIDE THE
 LOCATION OF EXISTING POLES, AND PROVIDE DETAIL OF POLES
 BEING REMOVED OR NEWLY PROPOSED POLES. PLEASE CONTACT
 STAFF TO HOLD A SEPARATE MEETING TO DISCUSS THE
 MULTIPLE ISSUES.
 23. SATISFIED. THE PROPOSED BUS PARKING DOES NOT WORK
 WITH TURNING RADIUS REQUIREMENTS. PLEASE CONSIDER A BUS
 PULL-OFF OR OTHER ALTERNATIVE.
 24. PARTIALLY SATISFIED. THE REQUIRED BICYCLE PARKING
 FOR COMMERCIAL DEVELOPMENTS IS 1 PER 15 REQUIRED
 PARKING SPACES WITHIN A SECURED STORAGE AREA. THE
 REQUIREMENT FOR PUBLIC USE IS ONE SPACE PER EVERY 100
 FEET OF STREET FRONTAGE. PLEASE INCLUDE THE DIMENSIONS
 OF THE STREET FRONTAGES AND DEMONSTRATE COMPLIANCE OF
 THE SEPARATE BICYCLE PARKING REQUIREMENTS IN THE SITE
 DATA TABLE. THE BICYCLE PARKING NUMBER IN THE SITE DATA
 TABLE DOES NOT APPEAR TO MATCH WHAT IS ON THE SITE
 PLAN. PLEASE UPDATE WITH RESUBMITTAL MEETING THE CITY
 REQUIREMENTS.
 PLEASE PROVIDE SOME PUBLIC BICYCLE RACKS IN THE
 PROPOSED PLAZA, CLOSER TO THE SIDEWALK. PLEASE BREAK
 DOWN BICYCLE PARKING REQUIREMENT INTO PUBLIC
 REQUIREMENT AND PRIVATE REQUIREMENT.
 25. SATISFIED. PLEASE REVISE FROM WALL-MOUNTED BIKE
 RACKS TO GROUND MOUNTED BIKE RACKS ALONG THE NORTH SIDE
 OF THE BUILDING.
 26. NOT SATISFIED. PLEASE INCLUDE BICYCLE RACK DETAIL,
 MEETING CITY STANDARDS. STAFF WILL PROVIDE DETAIL.
 PLEASE SHOW EXACT LOCATION OF PROPOSED BICYCLE RACKS
 AND DIMENSIONS ON THE SITE PLAN.
 PLEASE PROVIDE BICYBLE RACK DETAIL. THE BICYCLE RACK IN
 THE FRONT ALONG 8TH STREET DOES NOT APPEAR TO FIT WITH
 THE REQUIRED DIMENSIONS, PLEASE REVISE ACCORDINGLY.
 27. NOT SATISFIED. PLEASE PROVIDE ADDITIONAL
 FENESTRATION ALONG THE NORTH FACADE OF THE PROPOSED NEW
 ADDITION, AS IT IS FACING THE PRIMARY PARKING LOT FOR
 THE BUILDING USE. BLANK WALLS CANNOT BE VISIBLE BY THE
 GENERAL PUBLIC. BLANK WALL MEANS ANY PORTION OF A
 FA?ADE THAT HAS AN AREA GREATER THAN 20 PERCENT OF THE
 ENTIRE FA?ADE ELEVATION THAT IS ABSENT OF FENESTRATION
 AND IS ABSENT OF A PLANAR BREAK OF AT LEAST TWO FEET IN
 DEPTH. PLEASE ILLUSTRATE COMPLIANCE WITH BLANK WALL
 REGULATIONS.
 28. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, ON
 FACADES ENCLOSING ACTIVE USES (E.G., THE KITCHEN,
 BATHROOMS), FENESTRATION MUST COVER A MINIMUM OF 15% OF
 THE FACADE AREA. PLEASE PROVIDE ADDITIONAL FENESTRATION
 ALONG THE EAST FACADE OF THE PROPOSED BUILDING
 ADDITION.
 29. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, ON
 FACADES ENCLOSING NON-ACTIVE USES, ARCHITECTURAL
 TREATMENT SHALL BE PROVIDED. SEE SECTION 94-109,
 DEFINITIONS AND MINIMUM REQUIREMENTS FOR ARCHITECTURAL
 TREATMENT REQUIREMENTS, SPECIFICALLY FOR THE EAST
 FACADE OF THE PROPOSED ADDITION. PLEASE ADD MORE
 ARCHITECTURAL TREATMENT TO THE PROPOSED ADDITION.
 30. NOT SATISFIED. PER SECTION 94-109, TABLE IV-4, AT
 THE GROUND FLOOR, HORIZONTAL PROJECTIONS WITH A MINIMUM
 CUMULATIVE HORIZONTAL LENGTH OF 50% OF THE BUILDING
 FRONTAGE SHALL BE PROVIDED. IT APPEARS THAT THE
 FRONTAGES, ESPECIALLY THE NORTH AND EAST ELEVATION MAY
 NOT MEET THIS REQUIREMENT. PLEASE REVISE AND PROVIDE
 ILLUSTRATIONS SHOWING THE LENGTH OF HORIZONTAL
 PROJECTIONS ALONG THE GROUND FLOOR FRONTAGES TO SATISFY
 THIS REQUIREMENT.
 31. SATISFIED. PLEASE PROVIDE DIMENSIONS AND DETAIL OF
 PROPOSED AWNINGS AND CANOPIES. SEE TABLE IV-5:
 PROJECTION STANDARDS FOR REGULATIONS.
 32. NOT SATISFIED. PLEASE SEE SECTION 94-110(D) FOR
 SIGNAGE REQUIREMENTS FOR COMMERCIAL AND MIXED-USES
 WITHIN RESIDENTIAL ENCLAVE PLANNING AREAS. PLEASE
 PROVIDE DETAIL OF ANY NEWLY PROPOSED SIGNS, AND ADD A
 NOTE SAYING "SIGNAGE WILL BE REVIEWED SEPARATELY AT
 TIME OF SIGN PERMITTING" TO THE PLANS.
 33. PARTIALLY SATISFIED. PLEASE INCLUDE A SEPARATE OPEN
 SPACE PLAN AND TABLE MEETING THE REQUIREMENTS OF
 SECTION 94-109 TABLE IV-6 AND TABLE IV-7. PLEASE NOTE,
 REQUIRED LANDSCAPE BUFFERS CANNOT BE INCLUDED IN OPEN
 SPACE CALCULATIONS.
 THE PRIVATE OPEN SPACE SHALL INCLUDE THE GATHERING
 PLAZA AND THE ROOFTOP GARDEN. THE GATHERING PLAZA SHALL
 MEET THE REQUIREMENTS OF SEMI-PUBLIC COURTYARD, AS
 OUTLINED IN SECTION 94-109 TABLE IV-7.
 34. SATISFIED. PLEASE CONSIDER AN OPEN SPACE
 AMENITY/SEATING AREA IN THE REAR OF THE BUILDING FOR
 KITCHEN STAFF/EMPLOYEES, WHICH COULD THEN BE CONSIDERED
 IN THE OPEN SPACE CALCULATIONS.
 35. SATISFIED. PLEASE INCLUDE PLANTING ON THE ROOFTOP
 TERRACE TO PROVIDE A ROOFTOP GARDEN AREA. PLEASE
 INCLUDE DETAIL OF PROPOSAL AND AMENITIES.
 36. NOT SATISFIED. PER SECTION 94-113(E), CURBS AND
 WHEEL STOPS, ALL LANDSCAPED AREAS AND PLANT MATERIALS
 WITHIN OR ADJACENT TO VEHICULAR USE AREAS SHALL BE
 PROTECTED FROM VEHICULAR ENCROACHMENT BY WHEEL STOPS,
 CURBS, OR OTHER SIMILAR DEVICES. PLEASE DEMONSTRATE
 COMPLIANCE.
 PLEASE ADD WHEEL STOPS TO FOUR MIDDLE PARKING SPACES ON
 BOTH SITE PLAN AND LANDSCAPE PLAN.
 37. NOT SATISFIED. PER SECTION 94-113(D), STREET
 LIGHTS, STREET LIGHTING SHALL BE PROVIDED TO ATTAIN THE
 APPROPRIATE FOOTCANDLE MEASUREMENT NECESSARY FOR SAFE
 PEDESTRIAN AND VEHICULAR MOVEMENT. LIGHT FIXTURE AND
 POLES SHALL MEET THE CITY APPROVED STANDARD. PLEASE
 PROVIDE LOCATION AND DETAIL OF LIGHT FIXTURES.
 PLEASE SUBMIT PHOTOMETRIC PLANS AND LIGHT FIXTURE
 DETAILS.
 38. SATISFIED. PER SECTION 94-113(D), SIDEWALKS, A
 SIDEWALK WITH A MINIMUM OF EIGHT FEET CLEAR WIDTH SHALL
 BE PROVIDED ALONG THE BUILDING FRONTAGE. PLEASE REVISE
 ACCORDINGLY.
 39. SATISFIED. PER SECTION 94-113(F), SURFACE PARKING
 LOTS SHALL MEET THE MINIMUM GROUND FLOOR SETBACK
 REQUIREMENTS AS PROVIDED IN THE SUBDISTRICT BUILDING
 REQUIREMENTS TABLE. A FIVE-FOOT LANDSCAPE BUFFER SHALL
 BE PROVIDED AROUND THE ENTIRE PERIMETER OF THE SURFACE
 LOT IN ADDITION TO THE GROUND FLOOR SETBACK TO VISUALLY
 SCREEN PARKING AREAS.
 40. ONGOING. PARKING SHALL COMPLY WITH SECTION
 94-113(F) FOR LANDSCAPING REQUIREMENTS.
 LANDSCAPE REQUIREMENTS SHALL BE REVIEWED THROUGH
 SEPARATE LANDSCAPE PERMIT. SEE COMMENT #45.
 41. PARTIALLY SATISFIED. PLEASE INCLUDE DETAIL AND
 DIMENSIONS OF THE PROPOSED DUMPSTER ENCLOSURE AREA,
 MEETING THE REGULATIONS OF SECTION 94-315.
 PLEASE INCLUDE DETAIL OF TRASH RECEPTACLE ENCLOSURE,
 INCLUDING MATERIAL AND HEIGHT, MEETING THE
 SPECIFICATIONS OF SECTION 94-315(A).
 42. SATISFIED. CAN VISITORS ENTER THROUGH THE BACK OF
 THE BUILDING? PLEASE PROVIDE DETAIL INTO BUILDING
 ENTRANCES FROM EIGHTH STREET AND FROM THE PARKING LOT.
 PLEASE CONSIDER PEDESTRIAN CONNECTIVITY INCLUDING
 CROSSWALKS, AND DISTINGUISHED PRIMARY ENTRANCES.
 43. SATISFIED. PLEASE CLEAN UP LABELS ON THE PLAN THAT
 ARE REMAINING FROM THE FIRST SUBMITTAL OR OTHERWISE
 MISPLACED.
 44. SATISFIED. PLEASE REMOVE THE LABEL READING
 "PROPOSED 3RD FLOOR-PLAN" FROM SHEET A1.03 AND RELABEL
 AS "PROPOSED ROOFTOP TERRACE" OR SOMETHING SIMILAR.
 NEW COMMENTS FEBRUARY 22, 2019
 45. PLEASE NOTE, A SEPARATE LANDSCAPE PERMIT WILL BE
 REQUIRED.
 46. PLEASE NOTE, A SEPARATE FENCE PERMIT WILL BE
 REQUIRED FOR THE PROPOSED METAL FENCE. IN THIS
 DISTRICT, FENCES SHALL BE A MAXIMUM HEIGHT OF FOUR
 FEET. PLEASE REVISE HEIGHT ON PLANS.
 47. THE LANDSCAPE AND HARDSCAPE PLANS DO NOT MATCH THE
 NEW BUILDING FOOTPRINT AND ON STREET PARKING SPACE
 LAYOUT AND HAVE DISCREPANCIES IN PROPOSED LANDSCAPING.
 PLEASE ADJUST ACCORDINGLY.
 48. PLEASE INCLUDE A TREE REMOVAL/RELOCATION PLAN WITH
 RESUBMITTAL.
 49. ARE GATES PROPOSED TO ACCESS THE PARKING LOT?
 PLEASE NOTE, A QUEUING DISTANCE OF AT LEAST 20 FEET IS
 REQUIRED PER SECTION 94-111(P).
 50. PLEASE SHOW ANY ABOVE GROUND UTILITIES,
 TRANSFORMERS, BACKFLOW PREVENTERS, ETC. ON THE SITE
 PLAN. THESE SHALL NOT BE LOCATED WITHIN THE MINIMUM
 SETBACK. PLEASE CONSIDER A DIFFERENT LOCATION FOR THE
 BACKFLOW PREVENT AND WATER METER, FURTHER FROM THE
 SIDEWALK.
 51. PLEASE ENLARGE THE INTERNAL SIDEWALK WITHIN THE
 PLAZA THAT LEADS FROM THE ADA PARKING TO THE 8TH STREET
 ENTRANCE TO ALLOW FOR BETTER PEDESTRIAN ACCESS.
 52. PLEASE ADD SIDEWALK AND SETBACK DIMENSIONS ON THE
 HARDSCAPE PLAN SHEET HP-1.
 53. THE PROPOSED LOCATION OF THE WALL/FENCE ON THE
 HARDSCAPE PLAN DOES NOT MATCH THE PROPOSED LOCATION ON
 THE LANDSCAPE PLAN. PLEASE CLARIFY AND REVISE
 ACCORDINGLY.
 54. PLEASE SUBMIT A GROUND FLOOR PLAN WITH RESUBMITTAL.
 55. PLEASE UPDATE THE INDICATED PARKING NEAR THE HEART
 AND SOUL PARK ALONG 8TH STREET, AS THE CURRENT PARK
 PLAN DOES NOT HAVE PARKING ON 8TH STREET.
 56. PLEASE UPDATE THE BICYLE RACKS ON THE HARDSCAPE
 PLAN TO MATCH THE SITE PLAN.
 57. PLEASE UPDATE THE CIVIL PLANS TO SHOW THE PROPOSED
 PEDESTAL AT THE FRONT OF THE BUILDING ON 8TH STREET.
 PLEASE ENSURE THAT THERE IS AT LEAST 8 FEET MINIMUM
 SIDEWALK BETWEEN THE BACK OF CURB AND THE PEDESTAL.
 58. PLEASE UPDATE ALL CIVIL PLANS TO MATCH THE SITE
 PLAN.
 59. PLEASE SHOW THE PROPOSED GENERATOR ON THE LANDSCAPE
 PLAN WITH SUFFICIENT PROPOSED SCREENING.
 60. PLEASE ADD BOLLARDS OR PEDESTRIAN PROTECTION ALONG
 8TH STREET WITH THE CURBLESS DESIGN.
 61. PLEASE ADD A DETECTABLE WARNING RAMP AT THE
 MID-BLOCK CROSSING FROM SUNSET LOUNGE TO THE HEART AND
 SOUL PARK.
 62. PLEASE CHECK WITH THE ENGINEERING DEPARTMENT
 REGARDING THE SHIFTING OF THE CENTERLINE.
 63. PLEASE SUBMIT PLANS CONFIRMING THERE WILL BE
 SCREENING AS HIGH AS ANY PROPOSED ROOFTOP MECHANICAL
 EQUIPMENT.
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 06-12-2018 Cont ID  
Sent By elevesqu Date 06-12-2018 Time 15:15 Rev Time 0.00
Received By elevesqu Date 06-12-2018 Time 15:14 Sent To  
Notes
2018-06-12 15:15:121. PLEASE CONSIDER OPEN AIR STRUCTURES UNDER THE
 HALLWAY AND AREAS CONNECTING TO THE EXISTING STRUCTURE
 ON THE ROOFTOP TERRACE LEVEL TO MEET THE DISTRICT
 HEIGHT REQUIREMENTS.
 2. PLEASE PROVIDE MORE DETAIL AND HEIGHT OF THE
 STRUCTURES ON THE ROOFTOP TERRACE.
 3. CONSIDER THE USE OF IMPERMEABLE SURFACE, ESPECIALLY
 IN THE PROPOSED SURFACE PARKING LOT.
 4. THE COLORED RENDERING AND THE PROPOSED ELEVATIONS DO
 NOT APPEAR TO MATCH. PLEASE REVISE ACCORDINGLY.
 5. PLEASE NOTE, PER TABLE IV-38, THE CORRECT STREET
 DESIGNATIONS AND SETBACKS ARE AS FOLLOWS:
 A. FRONT (8TH STREET): RESIDENTIAL- 17'
 B. SIDE (9TH STREET): RESIDENTIAL - 17'
 C. SIDE (HENRIETTA AVE): RESIDENTIAL- 17'
 D. SIDE (ROSEMARY AVE): SECONDARY - 12'
 PLEASE CORRECT THE SITE DATA TABLE, AND INCLUDE THE
 SETBACK DIMENSIONS OF THE PROPOSED ADDITION AND PARKING
 LOTS ON THE SITE PLAN (SHEET A0.04, SHEET A1.00).
 6. PLEASE SHOW EXISTING CURBS AND CENTERLINES OF ALL
 ROADWAYS AND INDICATE WHERE THE CURBS WILL BE MODIFIED.
 7. PLEASE NOTE, IN THE DOWNTOWN MASTER PLAN AREA,
 SETBACKS ARE MEASURED FROM BACK OF CURB, AS DEFINED IN
 SECTION 94-109. WHERE THE CURB LOCATION VARIES ALONG A
 PROPERTY, THE BACK OF CURB SHALL BE DEFINED AS THE
 PREDOMINANT BACK OF CURB LINE FURTHEST FROM THE CENTER
 LINE OF THE ROAD (CURB LOCATION ALONG 50% OF STREET
 FRONTAGE). PLEASE AMEND THE SETBACK MEASUREMENTS AS
 NECESSARY.
 8. PLEASE NOTE, THE MINIMUM REQUIRED LANDSCAPE BUFFER
 FOR PARKING CANNOT BE INCLUDED AS PART OF THE REQUIRED
 SETBACK. PLEASE REVISE ACCORDINGLY.
 9. PLEASE NOTE, THE MAXIMUM BUILDING FOOTPRINT FOR
 GROUND LEVEL IS 87% AND FOR THE PODIUM IS 90%. PLEASE
 PROVIDE DETAIL IN THE TABLE ON THE PERCENT BUILDING
 FOOTPRINT FOR EACH PROPOSED NEW LEVEL. PLEASE AMEND THE
 LABEL FROM "LOT COVERAGE" TO "BUILDING FOOTPRINT."
 10. PARKING CALCULATIONS IS BASED ON NET INTERIOR AREA,
 NOT GROSS AREA. PLEASE INCLUDE THE NET INTERIOR AREA
 AND CALCULATE ACCORDINGLY. PLEASE NOTE, ANY PARKING
 ABOVE THE MAXIMUM REQUIREMENT IS COUNTED AS FAR. PLEASE
 BREAKDOWN THE TABLE INTO REQUIRED AND PROVIDED PARKING.
 11. PLEASE SUBMIT AN ILLUSTRATION AND TABLE OF THE
 F.A.R. BREAKDOWN BY EACH SEPARATE FLOOR, INCLUDING THE
 ADDITIONAL PARKING. PLEASE SEPARATE THE SQUARE FOOTAGE
 BY ALLEY, NORTH PROPERTY AND SOUTH PROPERTY.
 12. THE APPLICANT SHALL SUBMIT A SEPARATE ALLEY
 ABANDONMENT APPLICATION.
 13. PLEASE NOTE, THE PROPERTIES WILL NEED TO BE
 UNIFIED.
 14. PLEASE NOTE, THIS SITE WILL BE REQUIRED TO BE
 REPLATTED.
 15. PLEASE INCLUDE ILLUSTRATIONS AND A DATA TABLE
 DEMONSTRATING COMPLIANCE WITH THE ACTIVE USE
 REQUIREMENTS FOR NWD-2, AS REQUIRED BY TABLE IV-38.
 PLEASE NOTE, THE STREET DESIGNATIONS ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 16. PLEASE INCLUDE ILLUSTRATIONS AND A DATA TABLE
 DEMONSTRATING COMPLIANCE WITH THE TRANSPARENCY
 REQUIREMENTS FOR THE GROUND FLOOR IN NWD-2, AS REQUIRED
 BY TABLE IV-38. PLEASE NOTE, THE STREET DESIGNATIONS
 ARE AS FOLLOWS:
 A. 8TH AVENUE: RESIDENTIAL
 B. HENRIETTA AVENUE: RESIDENTIAL
 C. ROSEMARY AVENUE: SECONDARY
 D. 9TH STREET: RESIDENTIAL
 17. THE PROPOSED AISLE WIDTHS IN SOME SECTIONS OF THE
 PROPOSED PARKING AREAS APPEAR TO BE TOO SMALL. PLEASE
 LOOK AT SECTION 94-485, FIGURE XV-2 AND REVISE
 ACCORDINGLY.
 18. THE PROPOSED NUMBER OF ADA PARKING SPACES DOES NOT
 MEET THE REQUIREMENT AS ESTABLISHED BY SECTION 94-485,
 TABLE XV-3. PLEASE REVISE.
 19. IF PROPOSED ADA PARKING SPACES ARE DIAGONAL, THE
 REQUIRED LENGTH IS 18' AND WIDTH IS 12', PER SECTION
 94-485 (O)(2). THE PROPOSED DIAGONAL PARKING SPACE AREA
 TO THE EAST OF THE BUILDING ADDITION DOES NOT WORK WITH
 REQUIRED PARKING DEPTHS AND DRIVE AISLE WIDTHS. PLEASE
 CONSIDER ALTERNATIVES.
 20. THE NUMBER OF ON STREET PARKING ALONG HENRIETTA
 AVENUE IS LABELED AS 5 SPACES BUT THERE APPEAR TO ONLY
 BE 4 SPACES. PLEASE CONFIRM LABELS AND TOTAL NUMBERS IN
 THE SITE DATA TABLE.
 21. THE EXISTING ON SITE POWER POLES APPEAR TO CREATE
 PROBLEMS WITH PROPOSED SIDEWALKS, ON STREET PARKING AND
 PROPOSED STREET TREES. PLEASE PROVIDE THE LOCATION OF
 EXISTING POLES, AND PROVIDE DETAIL OF POLES BEING
 REMOVED OR NEWLY PROPOSED POLES. PLEASE CONTACT STAFF
 TO HOLD A SEPARATE MEETING TO DISCUSS THE MULTIPLE
 ISSUES.
 22. THE PROPOSED BUS PARKING DOES NOT WORK WITH TURNING
 RADIUS REQUIREMENTS. PLEASE CONSIDER A BUS PULL-OFF OR
 OTHER ALTERNATIVE.
 23. THE REQUIRED BICYCLE PARKING FOR COMMERCIAL
 DEVELOPMENTS IS 1 PER 15 REQUIRED PARKING SPACES WITHIN
 A SECURED STORAGE AREA. THE REQUIREMENT FOR PUBLIC USE
 IS ONE SPACE PER EVERY 100 FEET OF STREET FRONTAGE.
 PLEASE INCLUDE THE DIMENSIONS OF THE STREET FRONTAGES
 AND DEMONSTRATE COMPLIANCE OF THE SEPARATE BICYCLE
 PARKING REQUIREMENTS IN THE SITE DATA TABLE. THE
 BICYCLE PARKING NUMBER IN THE SITE DATA TABLE DOES NOT
 APPEAR TO MATCH WHAT IS ON THE SITE PLAN. PLEASE UPDATE
 WITH RESUBMITTAL MEETING THE CITY REQUIREMENTS.
 24. PLEASE REVISE FROM WALL-MOUNTED BIKE RACKS TO
 GROUND MOUNTED BIKE RACKS ALONG THE NORTH SIDE OF THE
 BUILDING.
 25. PLEASE INCLUDE BICYCLE RACK DETAIL, MEETING CITY
 STANDARDS. STAFF WILL PROVIDE DETAIL. PLEASE SHOW EXACT
 LOCATION OF PROPOSED BICYCLE RACKS AND DIMENSIONS ON
 THE SITE PLAN.
 26. PLEASE PROVIDE ADDITIONAL FENESTRATION ALONG THE
 NORTH FA?ADE OF THE PROPOSED NEW ADDITION, AS IT IS
 FACING THE PRIMARY PARKING LOT FOR THE BUILDING USE.
 27. PER SECTION 94-109, TABLE IV-4, ON FACADES
 ENCLOSING ACTIVE USES (E.G., THE KITCHEN, BATHROOMS),
 FENESTRATION MUST COVER A MINIMUM OF 15% OF THE FA?ADE
 AREA. PLEASE PROVIDE ADDITIONAL FENESTRATION ALONG THE
 EAST FA?ADE OF THE PROPOSED BUILDING ADDITION.
 28. PER SECTION 94-109, TABLE IV-4, ON FACADES
 ENCLOSING NON-ACTIVE USES, ARCHITECTURAL TREATMENT
 SHALL BE PROVIDED. SEE SECTION 94-109, DEFINITIONS AND
 MINIMUM REQUIREMENTS FOR ARCHITECTURAL TREATMENT
 REQUIREMENTS, SPECIFICALLY FOR THE EAST FA?ADE OF THE
 PROPOSED ADDITION. PLEASE ADD MORE ARCHITECTURAL
 TREATMENT TO THE PROPOSED ADDITION.
 29. PER SECTION 94-109, TABLE IV-4, AT THE GROUND
 FLOOR, HORIZONTAL PROJECTIONS WITH A MINIMUM CUMULATIVE
 HORIZONTAL LENGTH OF 50% OF THE BUILDING FRONTAGE SHALL
 BE PROVIDED. IT APPEARS THAT THE FRONTAGES, ESPECIALLY
 THE NORTH AND EAST ELEVATION MAY NOT MEET THIS
 REQUIREMENT. PLEASE REVISE AND PROVIDE ILLUSTRATIONS
 SHOWING THE LENGTH OF HORIZONTAL PROJECTIONS ALONG THE
 GROUND FLOOR FRONTAGES TO SATISFY THIS REQUIREMENT.
 30. PLEASE PROVIDE DIMENSIONS AND DETAIL OF PROPOSED
 AWNINGS AND CANOPIES. SEE TABLE IV-5: PROJECTION
 STANDARDS FOR REGULATIONS.
 31. PLEASE SEE SECTION 94-110(D) FOR SIGNAGE
 REQUIREMENTS FOR COMMERCIAL AND MIXED-USES WITHIN
 RESIDENTIAL ENCLAVE PLANNING AREAS. THE PROPOSAL SEEMS
 TO EXCEED THE MAXIMUM NUMBER OF SIGNS PERMITTED. PLEASE
 PROVIDE DETAIL OF THE SIGNS, AND ADD A NOTE SAYING
 "SIGNAGE WILL BE REVIEWED SEPARATELY AT TIME OF SIGN
 PERMITTING" TO THE PLANS.
 32. PLEASE INCLUDE A SEPARATE OPEN SPACE PLAN AND TABLE
 MEETING THE REQUIREMENTS OF SECTION 94-109 TABLE IV-6
 AND TABLE IV-7. PLEASE NOTE, REQUIRED LANDSCAPE BUFFERS
 CANNOT BE INCLUDED IN OPEN SPACE CALCULATIONS.
 33. PLEASE CONSIDER AN OPEN SPACE AMENITY/SEATING AREA
 IN THE REAR OF THE BUILDING FOR KITCHEN
 STAFF/EMPLOYEES, WHICH COULD THEN BE CONSIDERED IN THE
 OPEN SPACE CALCULATIONS.
 34. PLEASE INCLUDE PLANTING ON THE ROOFTOP TERRACE TO
 PROVIDE A ROOFTOP GARDEN AREA. PLEASE INCLUDE DETAIL OF
 PROPOSAL AND AMENITIES.
 35. PER SECTION 94-113(E), CURBS AND WHEEL STOPS, ALL
 LANDSCAPED AREAS AND PLANT MATERIALS WITHIN OR ADJACENT
 TO VEHICULAR USE AREAS SHALL BE PROTECTED FROM
 VEHICULAR ENCROACHMENT BY WHEEL STOPS, CURBS, OR OTHER
 SIMILAR DEVICES. PLEASE DEMONSTRATE COMPLIANCE.
 36. PER SECTION 94-113(D), STREET LIGHTS, STREET
 LIGHTING SHALL BE PROVIDED TO ATTAIN THE APPROPRIATE
 FOOTCANDLE MEASUREMENT NECESSARY FOR SAFE PEDESTRIAN
 AND VEHICULAR MOVEMENT. LIGHT FIXTURE AND POLES SHALL
 MEET THE CITY APPROVED STANDARD. PLEASE PROVIDE
 LOCATION AND DETAIL OF LIGHT FIXTURES.
 37. PER SECTION 94-113(D), SIDEWALKS, A SIDEWALK WITH A
 MINIMUM OF EIGHT FEET CLEAR WIDTH SHALL BE PROVIDED
 ALONG THE BUILDING FRONTAGE. PLEASE REVISE ACCORDINGLY.
 38. PER SECTION 94-113(F), SURFACE PARKING LOTS SHALL
 MEET THE MINIMUM GROUND FLOOR SETBACK REQUIREMENTS AS
 PROVIDED IN THE SUBDISTRICT BUILDING REQUIREMENTS
 TABLE. A FIVE-FOOT LANDSCAPE BUFFER SHALL BE PROVIDED
 AROUND THE ENTIRE PERIMETER OF THE SURFACE LOT IN
 ADDITION TO THE GROUND FLOOR SETBACK TO VISUALLY SCREEN
 PARKING AREAS.
 39. PARKING SHALL COMPLY WITH SECTION 94-113(F) FOR
 LANDSCAPING REQUIREMENTS.
 40. PLEASE INCLUDE DETAIL AND DIMENSIONS OF THE
 PROPOSED DUMPSTER ENCLOSURE AREA, MEETING THE
 REGULATIONS OF SECTION 94-315.
 41. CAN VISITORS ENTER THROUGH THE BACK OF THE
 BUILDING? PLEASE PROVIDE DETAIL INTO BUILDING ENTRANCES
 FROM EIGHTH STREET AND FROM THE PARKING LOT. PLEASE
 CONSIDER PEDESTRIAN CONNECTIVITY INCLUDING CROSSWALKS,
 AND DISTINGUISHED PRIMARY ENTRANCES.
 42. PLEASE CLEAN UP LABELS ON THE PLAN THAT ARE
 REMAINING FROM THE FIRST SUBMITTAL OR OTHERWISE
 MISPLACED.
 43. PLEASE REMOVE THE LABEL READING "PROPOSED 3RD
 FLOOR-PLAN" FROM SHEET A1.03 AND RELABEL AS "PROPOSED
 ROOFTOP TERRACE" OR SOMETHING SIMILAR.
  