Plan Review Details - Project Z18050029
| Plan Review Stops For Project Z18050029 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
06-12-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
06-12-2018 |
Time |
19:05 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
06-12-2018 |
Time |
19:05 |
Sent To |
|
|
| Notes |
| 2018-06-12 19:07:10 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. UNITY OF TITLE. FOR ANY BUILDING CROSSING A PROPERTY | | | LINE, EITHER A RECORDED UNITY OF TITLE, OR SOME OTHER | | | APPROVED LEGAL INSTRUMENT, SHALL BE INCLUDED WITH THE | | | PERMIT APPLICATION, OR THE BUILDING MUST HAVE A FIRE | | | WALL ALONG THE PROPERTY LINE, PER SECTION 202 OF | | | FLORIDA BUILDING CODE, BUILDING, FIRE SEPARATION | | | DISTANCE. | | | | | | 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 5. BUILDING ADDRESS. EACH SEPARATE BUILDING, AND UNIT | | | WITH AN INDEPENDENT ENTRANCE FROM THE STREET, SHALL | | | HAVE A SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT | | | MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494 | | | 1080, OR BY EMAIL: [email protected] | | | | | | 6. ART IN PUBLIC PLACES. THIS PROJECT WILL BE SUBJECT | | | TO ART IN PUBLIC PLACES (AIPP) ASSESSMENT. FOR ADVICE | | | ON THE PROVISION OF PUBLIC ARTWORK IN LIEU OF THE AIPP | | | ASSESSMENT, CONTACT SYBILLE WELTER, ART IN PUBLIC | | | PLACES COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
06-13-2018 |
|
|
Cont ID |
|
| Sent By |
Mgonzale |
Date |
06-13-2018 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
06-13-2018 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-06-13 13:08:45 | #1 DISCUSS DOWNSTREAM SEWER CAPCAITY WITH CITY OF WPB | | | PUBLIC UTILITY ENGINEER. | | | | | | #2 SEND IN THE GPD REQUESTING CONNECTION TO WATER AND | | | SEWER TO CITY OF WPB PUBLIC UTILITY ENGINEER. | | | | | | #3 NEW MAHOLE WILL BE REQUIRED AT THE POINT OF SERVICE | | | FOR SANITARY SEWER CONNECTION TO EXECUTIVE DR. | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF | | | WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." | | | FOR MORE INFORMATION REFER TO THE LINK BELOW: | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
06-08-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
06-08-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
06-08-2018 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2018-06-08 16:50:50 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA | | | 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE | | | BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE | | | BEING CONSTRUCTED. | | | | | | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | | PRIOR TO ANY INSTALLATION. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE | | | PRIMARY AND SECONDARY POWER SOURCES? | | | | | | 7. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | IS A GENERATOR BEING PROPOSED TO PROVIDE FOR LIFE | | | SAFETY? IT SHALL COMPLY WITH NFPA 110. | | | | | | 8. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 | | | KEYWAY SYSTEM. | | | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S | | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | | B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 9. COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT | | | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON | | | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, | | | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 10. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 11. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
P |
Date |
02-25-2019 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
02-25-2019 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
02-25-2019 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2019-02-25 15:45:35 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: CLEAR LAKE ESTATES RESIDENTIAL Z18050029 | | | FEBRUARY 21, 2019 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PROVIDE A TREE SURVEY, PROVIDE A PLAN | | | WITH LOCATIONS OF EXISTING TREES, AND PROVIDE A TREE | | | DISPOSITION CHART TO SHOW IF THEY WILL BE PRESERVED IN | | | PLACE, RELOCATED OR REMOVED. | | | TREE SURVEY NOT FOUND. | | | CORRECTIONS TO TREE DISPOSITION PLAN ARE LISTED IN NEW | | | COMMENTS. | | | | | | 2. SATISFIED. PROVIDE THE LANDSCAPE PLAN IN A MINIMUM | | | SCALE OF 1:20. | | | PLAN WAS SUBMITTED IN 1:30 SCALE AND IS STILL DIFFICULT | | | TO DISCERN DETAILS. 1:20 WILL EXPAND THE NUMBER OF | | | SHEETS BUT WILL BE EASIER TO READ DETAILS. | | | | | | 3. SATISFIED. PROVIDE THE AMOUNT OF PROVIDED OPEN SPACE | | | AND LANDSCAPE AREA ON THE LANDSCAPE PLAN. | | | | | | 4. SATISFIED. SHOW THE CALCULATIONS FOR MINIMUM SHADE | | | TREE AND FLOWERING TREE REQUIREMENTS PER SECTION | | | 94-443(C)(2)B. AND ADD REQUIRED TREES PER UNIT TO | | | ESTABLISH THE MINIMUM TREES REQUIRED FOR THE SITE. OPEN | | | SPACE REQUIRED FOR RESIDENTIAL ZONING INCLUDES | | | SETBACKS, PARKING, SIDEWALKS, LANDSCAPE ISLANDS AND | | | BUILDING PERIMETER PLANTINGS. | | | | | | 5. SATISFIED. SUBSTITUTION OF PALMS REQUIRES 3:1 RATIO | | | FOR COCONUT PALMS, REVISE ON CHART. PALMS SUBSTITUTION | | | IS 102 NOT 132, REVISE ON CHART. | | | PALMS ARE 3:1 OR 1:1. ADD UP ALL TRUNKS AT 3:1 AND THEN | | | DIVIDE BY 3 TO GET TREE COUNT AND ADD 1:1 PALMS. IN MY | | | REVIEW, THE COUNT CAME OUT TO PALMS SUBSTITUTED FOR 180 | | | TREES. | | | | | | 6. SATISFIED. LIGUSTRUM DOES NOT QUALIFY AS A SHADE | | | TREE. REVISE SHADE TREE COUNT. | | | | | | 7. SATISFIED. PROVIDE THE REQUIRED 5 FOOT LANDSCAPE | | | BUFFER PLANTINGS ALONG THE EAST PROPERTY LINE ADJACENT | | | TO THE LAKE WITH THE REQUIRED TREES OR NUMBER OF | | | SUBSTITUTE PALMS PER CURRENT CODE REQUIREMENTS OF | | | SECTION 94-443(D). | | | | | | 8. SATISFIED. PLEASE INCLUDE ALL CALCULATIONS FOR THE | | | EAST BUFFER AND NORTH BUFFER SEGMENTS ADJACENT TO THE | | | ENTRANCE ON THE PERIMETER BUFFER REQUIREMENT CHART SO | | | THAT LINEAR FOOTAGE OF ALL PROPERTY LINE SEGMENTS ARE | | | INCLUDED. | | | BUFFER SEGMENT ADJACENT TO THE ROAD NEEDS TO BE LISTED | | | SEPARATELY, AS THIS HAS A REQUIRED 10 FOOT BUFFER, | | | DIFFERENT FROM THE 5 FOOT REQUIRED BUFFER ON ALL OTHER | | | SEGMENTS AND NEEDS TO INCLUDE REQUIRED TREES. | | | | | | 9. SATISFIED. PLEASE PROVIDE THE TREE AS REQUIRED IN | | | THE TERMINAL LANDSCAPE ISLAND AT THE ENDS OF THE ROWS | | | OF PARKING SPACES ADJACENT TO THE ENTRANCE TO BUILDING | | | 4. | | | TERMINAL ISLAND TREE IS REQUIRED AT THE SOUTH SIDE OF | | | THE BUILDING, CANNOT BE DISPLACED BY A FIRE HYDRANT. | | | | | | 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY | | | LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT | | | COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT | | | TOLERANT, AND CORRECT THE POINTS AWARDED FOR MULCH TO | | | 5. PROVIDE THE MINIMUM 50 POINTS. | | | | | | 11. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 12. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER | | | LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | THERE APPEAR TO BE CONFLICTS IN MULTIPLE LOCATIONS. | | | EXPLAIN HOW THE 12 FOOT UTILITY EASEMENT ALONG THE WEST | | | AND SOUTH PROPERTY LINE WILL ALLOW THE PLANTING OF | | | BUFFER TREES AS PROPOSED. | | | 13. SATISFIED. PROVIDE LOCATIONS AND SCREENING FOR ALL | | | ABOVE GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C | | | UNITS, ETC. | | | HEDGE SCREENING NOT SHOWN FOR BACKFLOWS AND VALVES, FPL | | | TRANSFORMER LOCATIONS NOT SHOWN. | | | | | | 14. SATISFIED. SHOW LOCATIONS OF ANY ROOT BARRIERS | | | REQUIRED TO PROTECT UTILITY LINES. | | | SOME ROOT BARRIER LOCATIONS ARE SHOWN, BUT OTHERS | | | APPEAR TO REQUIRE ROOT BARRIER DUE TO PROXIMITY. | | | | | | 15. SATISFIED. PLEASE SHOW CALCULATIONS FOR EACH | | | RESIDENTIAL BUILDING FOR COMPLIANCE WITH 40 PERCENT | | | PERIMETER LANDSCAPE PER SECTION 94-443(E), AND 30 | | | PERCENT REQUIREMENT FOR THE PARKING DECK. | | | | | | 16. SATISFIED. PLEASE SHOW COMPLIANCE WITH SECTION | | | 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF | | | PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | ADDITIONAL COMMENTS 12/14/18: | | | 17. SATISFIED. THE FOLLOWING CORRECTIONS NEED TO BE | | | MADE TO THE TREE DISPOSITION PLAN: | | | ? 1:1 REPLACEMENT FOR SABAL PALMS IS CATEGORY 3 AT 100 | | | SQ FT. FOR EACH PALM TRUNK. | | | ? #21 FICUS IS CATEGORY 1 AT 300 SQ FT. | | | ? STAFF REVIEW OF CHART SHOWS TOTAL MITIGATION DUE IS | | | 9130 SQ FT. | | | ? GIVE THE CONDITION OF SEAGRAPE TREE #31, AS ALL | | | NATIVE TREES IN GOOD CONDITION MUST BE PRESERVED OR | | | RELOCATED. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
12-14-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-14-2018 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-11-2018 |
Time |
16:57 |
Sent To |
|
|
| Notes |
| 2018-12-14 16:10:21 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: CLEAR LAKE ESTATES RESIDENTIAL Z18050029 | | | DECEMBER 14, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PARTIALLY SATISFIED. PROVIDE A TREE SURVEY, PROVIDE | | | A PLAN WITH LOCATIONS OF EXISTING TREES, AND PROVIDE A | | | TREE DISPOSITION CHART TO SHOW IF THEY WILL BE | | | PRESERVED IN PLACE, RELOCATED OR REMOVED. | | | TREE SURVEY NOT FOUND. | | | CORRECTIONS TO TREE DISPOSITION PLAN ARE LISTED IN NEW | | | COMMENTS. | | | | | | 2. PARTIALLY SATISFIED. PROVIDE THE LANDSCAPE PLAN IN A | | | MINIMUM SCALE OF 1:20. | | | PLAN WAS SUBMITTED IN 1:30 SCALE AND IS STILL DIFFICULT | | | TO DISCERN DETAILS. 1:20 WILL EXPAND THE NUMBER OF | | | SHEETS BUT WILL BE EASIER TO READ DETAILS. | | | | | | 3. SATISFIED. PROVIDE THE AMOUNT OF PROVIDED OPEN SPACE | | | AND LANDSCAPE AREA ON THE LANDSCAPE PLAN. | | | | | | 4. SATISFIED. SHOW THE CALCULATIONS FOR MINIMUM SHADE | | | TREE AND FLOWERING TREE REQUIREMENTS PER SECTION | | | 94-443(C)(2)B. AND ADD REQUIRED TREES PER UNIT TO | | | ESTABLISH THE MINIMUM TREES REQUIRED FOR THE SITE. OPEN | | | SPACE REQUIRED FOR RESIDENTIAL ZONING INCLUDES | | | SETBACKS, PARKING, SIDEWALKS, LANDSCAPE ISLANDS AND | | | BUILDING PERIMETER PLANTINGS. | | | | | | 5. PARTIALLY SATISFIED. SUBSTITUTION OF PALMS REQUIRES | | | 3:1 RATIO FOR COCONUT PALMS, REVISE ON CHART. PALMS | | | SUBSTITUTION IS 102 NOT 132, REVISE ON CHART. | | | PALMS ARE 3:1 OR 1:1. ADD UP ALL TRUNKS AT 3:1 AND THEN | | | DIVIDE BY 3 TO GET TREE COUNT AND ADD 1:1 PALMS. IN MY | | | REVIEW, THE COUNT CAME OUT TO PALMS SUBSTITUTED FOR 180 | | | TREES. | | | | | | 6. SATISFIED. LIGUSTRUM DOES NOT QUALIFY AS A SHADE | | | TREE. REVISE SHADE TREE COUNT. | | | | | | 7. SATISFIED. PROVIDE THE REQUIRED 5 FOOT LANDSCAPE | | | BUFFER PLANTINGS ALONG THE EAST PROPERTY LINE ADJACENT | | | TO THE LAKE WITH THE REQUIRED TREES OR NUMBER OF | | | SUBSTITUTE PALMS PER CURRENT CODE REQUIREMENTS OF | | | SECTION 94-443(D). | | | | | | 8. PARTIALLY SATISFIED. PLEASE INCLUDE ALL CALCULATIONS | | | FOR THE EAST BUFFER AND NORTH BUFFER SEGMENTS ADJACENT | | | TO THE ENTRANCE ON THE PERIMETER BUFFER REQUIREMENT | | | CHART SO THAT LINEAR FOOTAGE OF ALL PROPERTY LINE | | | SEGMENTS ARE INCLUDED. | | | BUFFER SEGMENT ADJACENT TO THE ROAD NEEDS TO BE LISTED | | | SEPARATELY, AS THIS HAS A REQUIRED 10 FOOT BUFFER, | | | DIFFERENT FROM THE 5 FOOT REQUIRED BUFFER ON ALL OTHER | | | SEGMENTS AND NEEDS TO INCLUDE REQUIRED TREES. | | | | | | 9. PARTIALLY SATISFIED. PLEASE PROVIDE THE TREE AS | | | REQUIRED IN THE TERMINAL LANDSCAPE ISLAND AT THE ENDS | | | OF THE ROWS OF PARKING SPACES ADJACENT TO THE ENTRANCE | | | TO BUILDING 4. | | | TERMINAL ISLAND TREE IS REQUIRED AT THE SOUTH SIDE OF | | | THE BUILDING, CANNOT BE DISPLACED BY A FIRE HYDRANT. | | | | | | 10. SATISFIED. PLEASE CORRECT THE FLORIDA FRIENDLY | | | LANDSCAPE CHART SO THAT TREES AND SHRUBS ARE NOT | | | COUNTED TWICE FOR EACH CATEGORY OF NATIVE AND DROUGHT | | | TOLERANT, AND CORRECT THE POINTS AWARDED FOR MULCH TO | | | 5. PROVIDE THE MINIMUM 50 POINTS. | | | | | | 11. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 12. PARTIALLY SATISFIED. PLEASE SHOW LOCATIONS OF WATER | | | AND SEWER LINES ON THE LANDSCAPE PLAN AND RESOLVE | | | CONFLICTS WITH LANDSCAPING. | | | THERE APPEAR TO BE CONFLICTS IN MULTIPLE LOCATIONS. | | | EXPLAIN HOW THE 12 FOOT UTILITY EASEMENT ALONG THE WEST | | | AND SOUTH PROPERTY LINE WILL ALLOW THE PLANTING OF | | | BUFFER TREES AS PROPOSED. | | | 13. PARTIALLY SATISFIED. PROVIDE LOCATIONS AND | | | SCREENING FOR ALL ABOVE GROUND UTILITY VALVES, BACKFLOW | | | PREVENTERS, A/C UNITS, ETC. | | | HEDGE SCREENING NOT SHOWN FOR BACKFLOWS AND VALVES, FPL | | | TRANSFORMER LOCATIONS NOT SHOWN. | | | | | | 14. PARTIALLY SATISFIED. SHOW LOCATIONS OF ANY ROOT | | | BARRIERS REQUIRED TO PROTECT UTILITY LINES. | | | SOME ROOT BARRIER LOCATIONS ARE SHOWN, BUT OTHERS | | | APPEAR TO REQUIRE ROOT BARRIER DUE TO PROXIMITY. | | | | | | 15. SATISFIED. PLEASE SHOW CALCULATIONS FOR EACH | | | RESIDENTIAL BUILDING FOR COMPLIANCE WITH 40 PERCENT | | | PERIMETER LANDSCAPE PER SECTION 94-443(E), AND 30 | | | PERCENT REQUIREMENT FOR THE PARKING DECK. | | | | | | 16. SATISFIED. PLEASE SHOW COMPLIANCE WITH SECTION | | | 94-445 L. PLANT SPECIES. A MINIMUM OF 60 PERCENT OF | | | PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE OR DROUGHT | | | TOLERANT SPECIES SELECTED FROM THE CITY LIST OR THE | | | LIST OF SPECIES IN THE MOST RECENT EDITION OF SOUTH | | | FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH | | | FLORIDA LANDSCAPES. | | | ADDITIONAL COMMENTS 12/14/18: | | | 17. THE FOLLOWING CORRECTIONS NEED TO BE MADE TO THE | | | TREE DISPOSITION PLAN: | | | ? 1:1 REPLACEMENT FOR SABAL PALMS IS CATEGORY 3 AT 100 | | | SQ FT. FOR EACH PALM TRUNK. | | | ? #21 FICUS IS CATEGORY 1 AT 300 SQ FT. | | | ? STAFF REVIEW OF CHART SHOWS TOTAL MITIGATION DUE IS | | | 9130 SQ FT. | | | ? GIVE THE CONDITION OF SEAGRAPE TREE #31, AS ALL | | | NATIVE TREES IN GOOD CONDITION MUST BE PRESERVED OR | | | RELOCATED. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
06-12-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-12-2018 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-12-2018 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2018-06-12 16:22:10 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: SAIL CLUB RESIDENTIAL Z18050029 | | | JUNE 12, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PROVIDE A TREE SURVEY, PROVIDE A PLAN WITH LOCATIONS | | | OF EXISTING TREES, AND PROVIDE A TREE DISPOSITION CHART | | | TO SHOW IF THEY WILL BE PRESERVED IN PLACE, RELOCATED | | | OR REMOVED. | | | | | | 2. PROVIDE THE LANDSCAPE PLAN IN A MINIMUM SCALE OF | | | 1:20. | | | | | | 3. PROVIDE THE AMOUNT OF PROVIDED OPEN SPACE AND | | | LANDSCAPE AREA ON THE LANDSCAPE PLAN. | | | | | | 4. SHOW THE CALCULATIONS FOR MINIMUM SHADE TREE AND | | | FLOWERING TREE REQUIREMENTS PER SECTION 94-443(C)(2)B. | | | AND ADD REQUIRED TREES PER UNIT TO ESTABLISH THE | | | MINIMUM TREES REQUIRED FOR THE SITE. OPEN SPACE | | | REQUIRED FOR RESIDENTIAL ZONING INCLUDES SETBACKS, | | | PARKING, SIDEWALKS, LANDSCAPE ISLANDS AND BUILDING | | | PERIMETER PLANTINGS. | | | | | | 5. SUBSTITUTION OF PALMS REQUIRES 3:1 RATIO FOR COCONUT | | | PALMS, REVISE ON CHART. PALMS SUBSTITUTION IS 102 NOT | | | 132, REVISE ON CHART. | | | | | | 6. LIGUSTRUM DOES NOT QUALIFY AS A SHADE TREE. REVISE | | | SHADE TREE COUNT. | | | | | | 7. PROVIDE THE REQUIRED 5 FOOT LANDSCAPE BUFFER | | | PLANTINGS ALONG THE EAST PROPERTY LINE ADJACENT TO THE | | | LAKE WITH THE REQUIRED TREES OR NUMBER OF SUBSTITUTE | | | PALMS PER CURRENT CODE REQUIREMENTS OF SECTION | | | 94-443(D). | | | | | | 8. PLEASE INCLUDE ALL CALCULATIONS FOR THE EAST BUFFER | | | AND NORTH BUFFER SEGMENTS ADJACENT TO THE ENTRANCE ON | | | THE PERIMETER BUFFER REQUIREMENT CHART SO THAT LINEAR | | | FOOTAGE OF ALL PROPERTY LINE SEGMENTS ARE INCLUDED. | | | | | | 9. PLEASE PROVIDE THE TREE AS REQUIRED IN THE TERMINAL | | | LANDSCAPE ISLAND AT THE ENDS OF THE ROWS OF PARKING | | | SPACES ADJACENT TO THE ENTRANCE TO BUILDING 4. | | | | | | 10. PLEASE CORRECT THE FLORIDA FRIENDLY LANDSCAPE CHART | | | SO THAT TREES AND SHRUBS ARE NOT COUNTED TWICE FOR EACH | | | CATEGORY OF NATIVE AND DROUGHT TOLERANT, AND CORRECT | | | THE POINTS AWARDED FOR MULCH TO 5. PROVIDE THE MINIMUM | | | 50 POINTS. | | | | | | 11. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 12. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | 13. PROVIDE LOCATIONS AND SCREENING FOR ALL ABOVE | | | GROUND UTILITY VALVES, BACKFLOW PREVENTERS, A/C UNITS, | | | ETC. | | | 14. SHOW LOCATIONS OF ANY ROOT BARRIERS REQUIRED TO | | | PROTECT UTILITY LINES. | | | | | | 15. PLEASE SHOW CALCULATIONS FOR EACH RESIDENTIAL | | | BUILDING FOR COMPLIANCE WITH 40 PERCENT PERIMETER | | | LANDSCAPE PER SECTION 94-443(E), AND 30 PERCENT | | | REQUIREMENT FOR THE PARKING DECK. | | | 16. PLEASE SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT | | | SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL | | | ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT | | | SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF | | | SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA | | | WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA | | | LANDSCAPES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
2 |
Status |
P |
Date |
11-29-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
11-29-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-29-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-11-29 12:54:25 | PLAN IS APPROVED FOR LOCATIONS OF PICK UP. MAINTENANCE | | | STAFF MUST HAVE DUMPSTERS AT THE ROADWAY FOR PICK UP ON | | | SCHEDULED DAYS OF SERVICE AT APPROPRIATE TIMES. |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
F |
Date |
06-11-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-11-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
06-11-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-11 14:33:35 | THE PLANS SHOW INDIVIDUAL TRASH ROOM WITH NO STREET | | | ACCESS. NEED TO PROVIDE A DIRECT ACCESS LOCATION FOR | | | DUMPSTER SERVICE. MUST PROVIDE ADEQUATE SANITATION | | | PLAN. |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
06-13-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-13-2018 |
Time |
07:19 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-13-2018 |
Time |
07:20 |
Sent To |
|
|
| Notes |
| 2018-06-13 07:20:16 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. UPDATE THE FLOOD ZONE INFORMATION ON THE BOUNDARY | | | SURVEY. NEW FIRMS WERE ISSUED IN OCTOBER 2017. | | | | | | 2. THE CITY VERTICAL DATUM IS NGVD 1929. LABEL THE | | | VERTICAL DATUM ON THE CONCEPTUAL PAVING, DRAINAGE, | | | PLAN. SHOW THE DATUM CONVERSION TO NGVD1929 IF NGVD1929 | | | IS NOT USED. NOTE THE OCTOBER 20, 2015 BOUNDARY SURVEY | | | USES NGVD1929. | | | | | | 3. SHOW THE DATUM CONVERSION TO NGVD1929 ON THE | | | CONCEPTUAL WATER AND WASTEWATER PLAN. | | | | | | 4. OUTFALL CULVERT CONNECTION TO EXISTING CATCH BASIN | | | IS NEAR AN EXISTING 10-INCH WATER MAIN. | | | | | | 5. CONSIDER REDUCING THE LENGTH OF THE PARKING SPACES | | | AND PROVIDE TWO FEET OF OVERHANG IN THE LANDSCAPE | | | AREAS. THIS WILL REDUCE THE AMOUNT OF ASPHALT AND | | | INCREASE THE PERVIOUS AREA. | | | | | | 6. CONSIDER INCORPORATING LOW IMPACT DESIGN (LID) FOR | | | THE PROJECT. | | | | | | 7. CONSIDER ADDING STORMWATER DETENTION AREAS IN THE | | | LARGE LANDSCAPE AREAS SUCH AS TO THE NE OF THE ENTRANCE | | | ROAD, WEST OF THE ROUNDABOUT OR BETWEEN/BEHIND THE | | | BUILDINGS 2 AND 3. | | | | | | 8. SHOW AND LABEL UTILITIES ON THE LANDSCAPE PLANS. | | | | | | 9. DIRECT ROOFING GUTTER DOWN SPOUTS TO PERVIOUS AREAS | | | IF POSSIBLE. OTHERWISE ATTEMPT TO CONNECT DIRECTLY TO | | | THE DRAINAGE SYSTEM INSTEAD OF DISCHARGING TO | | | IMPERVIOUS AREAS. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. PROVIDE SFWMD ERP FOR THE DEVELOPMENT. | | | | | | 3. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
06-11-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
06-11-2018 |
Time |
09:21 |
Rev Time |
|
| Received By |
vnoel |
Date |
06-11-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-11 09:37:02 | 1. SURVEY IS OUT OF DATE. | | | 2. UNITY OF TITLE WILL BE REQUIRED. | | | 3. ENGINEERING DEVELOPMENT APPLICATION WILL BE | | | REQUIRED. | | | 4. DETAIL AND AGREEMENT WILL BE REQUIRED FOR WALKWAY | | | ALONG CLEAR LAKE. | | | 5. VEHICULAR ACCESS TO CLEAR LAKE MAY BE REQUIRED. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
4 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
02-20-2019 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2019-02-20 09:52:59 | 1. IS THE COMMUNITY GATED FROM PEDESTRIAN ACCESS TOO? | | | IF SO, PLEASE SHOW THE WALL OR FENCE AROUND THE SITE | | | PERIMETER IF PROPOSED. | | | 2. TRANSPORTATION DIVISION REQUESTS THAT THE PEDESTRIAN | | | CONNECTION FROM EXECUTIVE CENTER DRIVE TO THE LAKE PATH | | | REMAIN OPEN 24 HOURS A DAY AND ALLOWS PUBLIC ACCESS. | | | 3. INCLUDE PLAN SHEETS FOR BOTH FLOORS OF THE PARKING | | | GARAGES | | | 4. INCLUDE THE PEDESTRIAN CONNECTION FROM EXECUTIVE | | | CENTER DRIVE TO THE LAKE PATH IN THE PHOTOMETRIC | | | ANALYSIS. | | | 5. COORDINATE WITH PALM TRAN FOR BUS SHELTER | | | REQUIREMENTS. PROVIDE BUS SHELTER TO THE NEAREST BUS | | | STOP ON EXECUTIVE CENTER OR RELOCATE THE EXISTING BUS | | | STOP TO ACCOMMODATE A BUS SHELTER ALONG THE SITE | | | FRONTAGE IF NECESSARY. | | | 6. PROVIDE EASEMENT FOR THE PORTION OF SIDEWALK AND | | | PEDESTRIAN CONNECTION FROM EXECUTIVE CENTER DRIVE TO | | | THE LAKE PATH WHICH ARE OUTSIDE PUBLIC RIGHT-OF-WAY OR | | | EXISTING ACCESS EASEMENT. | | | 7. PLANNED DEVELOPMENT IS INTENDED TO CREATE A MORE | | | DESIRABLE AND ATTRACTIVE DEVELOPMENT IN THE CITY, AND | | | THE REQUEST FOR PARKING WAIVER SHALL CONFORM TO THE | | | CONCEPTS OF NEW URBANISM. THE EXISTING PALMTRAN BUS | | | ROUTE 49, WHILE MEETS THE BASIC TRAVEL NEEDS, DOES NOT | | | PROVIDE DESIRABLE SERVICE DUE TO LONG HEADWAYS. PLEASE | | | CONSTRUCT PROTECTED BIKE LANE ALONG EXECUTIVE CENTER | | | DRIVE BETWEEN CONGRESS AVENUE AND THE SITE, WITH | | | REDUCED TRAVEL LANE WIDTH OF 10 FEET AND GREEN BIKE | | | LANES AT CONFLICT AREAS. THE PROTECTED BIKE LANES WILL | | | PROVIDE A SAFE AND COMFORTABLE CONNECTION FOR RESIDENTS | | | TO ACCESS, BY BICYCLE, ADDITIONAL TRANSIT OPTIONS AND | | | THE PLANNED TROLLEY ON PALM BEACH LAKES BOULEVARD. | | | | | | SHING TSOI | | | CITY IN-HOUSE TRAFFIC CONSULTANT | | | 561-494-1141 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
F |
Date |
12-10-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
12-10-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
12-10-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-12-10 17:54:53 | 719 EXECUTIVE CENTER DRIVE 11/29/2018 RESUBMITTAL - | | | Z18050029 | | | 1. PROVIDE SIDEWALK ON SOUTH SIDE OF ACCESS ROAD. | | | 2. REDUCE THE WIDTH OF THE 24? INBOUND ACCESS ROAD. | | | 3. CAN OUTBOUND ACCESS ROAD WIDTH BE REDUCED FROM 20?? | | | IT APPEARS THAT ONLY ONE LANE IS NEEDED. | | | 4. CONSIDER ELIMINATING THE MEDIAN AT THE EXECUTIVE | | | CENTER ENTRANCE, THIS WOULD ELIMINATE ANY CONCERNS | | | ABOUT PASSING A STALLED VEHICLE, ALLOW REDUCED LANE | | | WIDTHS, AND SHORTEN PEDESTRIAN CROSSING DISTANCES. | | | 5. SUGGEST PROVIDING SIDEWALK CONNECTION FROM WEST SIDE | | | OF BUILDING FOUR TO ACCESS ROAD. | | | 6. TRANSPORTATION DIVISION REQUESTS THAT THE PEDESTRIAN | | | CONNECTION FROM EXECUTIVE CENTER DRIVE TO THE LAKE PATH | | | REMAIN OPEN 24 HOURS A DAY. THE INTENT OF THE PATH, | | | UPON COMPLETION IS TO PROVIDE A MODAL SHIFT. THE PATH | | | MUST REMAIN OPEN AS LONG AS POSSIBLE IN ORDER FOR IT TO | | | BE A DESIRABLE FACILITY FOR A MODE SHIFT TO NON-SINGLE | | | OCCUPANCY VEHICULAR MODES. | | | 7. PROVIDE PEDESTRIAN SCALE LIGHTING FOR THE PEDESTRIAN | | | CONNECTION FROM EXECUTIVE CENTER DRIVE TO THE LAKE | | | PATH. | | | 8. COORDINATE WITH PALM TRAN FOR BUS SHELTER | | | REQUIREMENTS. SINCE THE APPLICANT IS SEEKING A PARKING | | | REDUCTION DUE TO TRANSIT SERVICE, CONSIDER PROVIDING A | | | HIGH QUALITY TRANSIT SHELTER ON SITE. | | | 9. CONSIDER PROVIDING A PICKUP / DROP OFF AREA FOR UBER | | | AND LYFT PICKUP OUTSIDE OF THE GATE. THE WAITING AREA | | | FOR UBER AND LYFT COULD BE COMBINED WITH A TRANSIT | | | SHELTER. | | | 10. PROVIDE VEHICULAR QUEUING ANALYSIS FOR GUESTS. | | | 11. SHOW LOCATION OF CALL BOX FOR GATE. | | | 12. THE ENTRANCE DESIGN DOES NOT PROVIDE MUCH REACTION | | | TIME FOR DRIVERS TO DETERMINE IF THEY SHOULD BE IN THE | | | GUEST OR RESIDENT TRAVEL LANE. | | | | | | | | | | | | ERIK D. FERGUSON, P.E. | | | CITY TRANSPORTATION ENGINEER | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
06-13-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-13-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
06-13-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-13 15:31:56 | NOTES GIVEN AT 6/13/18 PPRC MEETING TO APPLICANT | | | | | | - APPLICANT PROVIDED WITH PORTION OF DRAFT CITY BICYCLE | | | MASTER PLAN. APPLICANT INFORMED THAT PLANS SHOWS CLEAR | | | LAKE TRAIL, PUBLIC CONNECTION FROM EXECUTIVE DRIVE TO | | | TRAIL, BICYCLE LANES ON EXECUTIVE DRIVE | | | - INCORRECT BUS ROUTE WAS LISTED IN JUSTIFICATION | | | STATEMENT. CORRECT BUS ROUTE IS #49 | | | - BUS ONLY RUNS ON ONE HOUR HEADWAY. CHANCE OF MODE | | | SHIFT TO TRANSIT LOW GIVEN ONE HOUR BUS FREQUENCY. | | | - PRELIMINARY REVIEW OF TRAFFIC STATEMENT WAS | | | PERFORMED. OUR OPINION IS THAT THE COUNTY COASTAL | | | CONCURRENCY EXCEPTION ARREA ONLY APPLIES TO IMPACTS TO | | | COUNTY ROADS AND THAT CITY CODE DOES NOT CONTAIN AN | | | EXCEPTION TO IMPACT TO IMPACT TO CITY ROADS. | | | - COUNTY EXCEPTION DOES NOT ELIMINATE REQUIREMENT TO | | | ANALYZE AND MITIGATION SITE RELATED TRAFFIC IMPACTS. | | | | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
06-12-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
06-12-2018 |
Time |
|
Rev Time |
1.00 |
| Received By |
|
Date |
06-12-2018 |
Time |
|
Sent To |
TRAFFIC |
|
| Notes |
| 2018-06-12 09:58:37 | SAIL CLUB RESIDENTIAL | | | | | | - CONTACT UYEN DANG @ (561) 494-1087 | | | | | | 1) NO SITE REVIEW UNTIL A TRAFFIC STUDY IS SUBMITTED. | | | SCHEDULE A MEETING WITH DEB GRAYSON AT 494-1062 AND | | | REQUEST TO MEET WITH UYEN DANG, ERIK FERGUSON AND JOHN | | | ROACH. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
02-26-2019 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
02-26-2019 |
Time |
10:35 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
02-26-2019 |
Time |
10:34 |
Sent To |
|
|
| Notes |
| 2019-02-26 10:39:56 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.30.2019 | | | PROJECT NO.: Z18050029 | | | CASE NO.: PB 1242G | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. [ PREVIOUS COMMENT PARTIALLY SATISIFED - MAY BE | | | ADDRESSED AS A CONDITION OF APPROVAL ] - ALL | | | OUTSTANDING PUBLIC UTILITY LETTERS SHALL BE PROVIDED; | | | COMCAST LETTER SHALL BE PROVIDED PRIOR TO ISSUANCE OF | | | ANY PERMITS. | | | | | | 2. [ PREVIOUS COMMENT NOT SATISFIED - MAY BE ADDREESED | | | AS A CONDITION OF APPROVAL ] - PHOTOMETRIC LEVELS SHALL | | | BE PROVIDED AT ALL PROPERTY LINES AND SHALL NOT EXCEED | | | 0.5 FOOTCANDLES. THE PHOTOMETRIC PLANS PROVIDED DO NOT | | | SHOW LEVELS AT THE NORTHWEST PROPERTY LINE, AND THE | | | LEVELS APPEAR TO EXCEED 0.5 FOOTCANDLES ALONG THE | | | EXECUTIVE CENTER DRIVE RIGHT-OF-WAY. | | | | | | 3. REGARDING THE PROPOSED ENTRY SIGNS: | | | | | | 3.1 THE AREA OF THE ENTRY SIGNAGE SHALL NOT EXCEED 48 | | | SQUARE FEET PER SIGN. DIMENSIONS WERE NOT PROVIDED ON | | | THE CONCEPTS. EITHER THE SIGNS NEED TO COMPLY WITH SUCH | | | PROVISION, OR A WAIVER IS REQUIRED. | | | | | | 3.2 PER THE CITY'S ZLDRS, ONLY ONE (1) SIGN IS | | | PERMITTED PER ENTRANCE AND NO TWO SIGNS SHALL BE WITHIN | | | 500 FEET OF ONE ANOTHER. EITHER THE PROPOSAL SHALL BE | | | LIMITED TO ONE (1) SIGN, OR A WAIVER IS REQUIRED. | | | ___________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE | | | PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X | | | 17IN), AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
01-30-2019 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
01-30-2019 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
01-30-2019 |
Time |
14:15 |
Sent To |
|
|
| Notes |
| 2019-01-30 14:22:32 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 01.30.2019 | | | PROJECT NO.: Z18050029 | | | CASE NO.: PB 1242G | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. REGARDING THE PARKING WAIVER, THE TABLE IN THE | | | JUSTFICATION STATEMENT INDICATES THAT THE WAIVER IS FOR | | | 15%, BUT THE TEXT INDICATES THAT THE WAIVER IS FOR 10%. | | | ENSURE THAT ALL PLANS AND DOCUMENTS ARE CONSISTENT AND | | | ACCURATE. ADDITIONALLY, THE JUSTIFICATION STATEMENT | | | INDCATES THAT A PARKING STUDY IS BEING PROVIDED, BUT | | | NONE HAS BEEN RECEIVED TO DATE. | | | | | | 2. ALL OUTSTANDING PUBLIC UTILITY LETTERS SHALL BE | | | PROVIDED. NO LETTERS WERE RECEIVED WITH THE NOV. 20, | | | 2018, RESUBMITTAL. | | | | | | 3. AS IT APPEARS STRUCTURAL ELEMENTS OF THE BUILDINGS | | | ARE ENCROACHING INTO THE REQUIRED SIDE AND REAR | | | SETBACKS, PLEASE PROVIDE THE DIMENSIONS OF SUCH | | | ENCROACHMENT. PURSUANT TO SEC. 94-305, SUCH ELEMENTS | | | SHALL NOT EXTEND MORE THAN THREE (3) FEET INTO THE | | | REQUIRED SETBACK. DIMENSIONS WERE NOT PROVIDED FOR | | | BALCONIES, ROOF OVERHANGS, ETC. THAT APPEAR TO BE | | | ENCROACHING INTO THE SETBACK. | | | | | | 4. PHOTOMETRIC LEVELS SHALL BE PROVIDED AT ALL PROPERTY | | | LINES AND SHALL NOT EXCEED 0.5 FOOTCANDLES. THE | | | PHOTOMETRIC PLANS PROVIDED DO NOT SHOW LEVELS AT THE | | | PROPERTY LINES. | | | | | | 5. PDFS WERE NOT PROVIDED OF THE REVISED ARCHITECTURAL | | | PLAN, NOR THE PHOTOMETRIC PLANS. ALL RESUBMITTAL | | | PLANS/DOCUMENTS SHALL BE PROVIDED IN PDF FORMAT IN | | | ADDITION TO THE HARD-COPIES. | | | ___________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE | | | PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X | | | 17IN), AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | | | | F) IN ORDER TO BE CONSIDERED FOR THE MARCH 19, 2019, | | | PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE | | | SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED | | | DOCUMENTS/PLANS NO LATER THAN FRIDAY, FEBRUARY 15, 2019 | | | . | | | | | | G) TO BE PLACED ON THE MARCH 19, 2019, PLANNING BOARD | | | AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO LATER | | | THAN MARCH 4, 2019. SIGNAGE SHALL CONFORM AND BE | | | INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING | | | AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN | | | THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED | | | AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED | | | ABOVE. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
06-13-2018 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
06-13-2018 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
06-13-2018 |
Time |
12:09 |
Sent To |
|
|
| Notes |
| 2018-06-13 12:09:39 | PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW | | | ___________________________________________ | | | | | | DATE OF REVIEW: 06.13.2018 | | | PROJECT NO.: Z18050029 | | | CASE NO.: PB 1242G | | | ___________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING | | | REVIEW COMMENTS: | | | | | | 1. AN UPDATED TRAFFIC CONCURRENCY APPROVAL SHALL BE | | | PROVIDED FROM PALM BEACH COUNTY. | | | | | | 2. AN APPROVED SCHOOL CAPACITY AVAILABILITY | | | DETERMINATION SHALL BE PROVIDED FROM THE SCHOOL | | | DISTRICT OF PALM BEACH COUNTY. | | | | | | 3. AS CURRENTLY WRITTEN, THE JUSTIFICATION FOR THE | | | PARKING WAIVER DOES NOT MEET THE REQUIRED MINIMUM | | | NUMBER OF STANDARDS. | | | | | | 4. ALL OUTSTANDING PUBLIC UTILITY LETTERS SHALL BE | | | PROVIDED. | | | | | | 5. IT IS RECOMMENDED THAT ANY PARKING ROWS FRONTING | | | ONTO A LANDSCAPE BUFFER/AREA BE REDUCED TO 16 FEET IN | | | LENGTH, ALLOWING FOR 2 FEET OF OVERHANG INTO THE | | | LANDSCAPE AREA. THIS REDUCES THE AMOUNT OF IMPERVIOUS | | | AREA, THE NEED FOR WHEEL STOPS, ETC. NOTE THAT THE | | | OVERHANG CANNOT EXTEND INTO THE MINIMUM REQUIRED BUFFER | | | WIDTH. | | | | | | 6. PLEASE EXPLAIN THE LOCATION OF THE PARKING GARAGE | | | AND THE NEED FOR THE SETBACK WAIVER, GIVEN THE SIZE OF | | | THE PROPERTY AND ALTERNATIVE LOCATIONS AVAILABLE. | | | | | | 7. THE DEVELOPER WILL BE RESPONSIBLE FOR THE | | | CONSTRUCTION OF THAT PORTION OF THE LAKE PATH THAT IS | | | IMMEDIATELY ADJACENT TO THE PROPOSED DEVELOPMENT. STAFF | | | WILL BE DEVELOPING LANGUAGE REGARDING THE TIMING, | | | OBLIGATIONS, ETC. AS WELL AS A CROSS SECTION OF THE | | | REQUIRED DESIGN. | | | | | | 8. A DIRECT, OPEN AND PUBLIC PEDESTRIAN CONNECTION | | | SHALL BE PROVIDED FROM EXECUTIVE CENTER DRIVE TO THE | | | LAKE PATH. THE CONNECTION SHALL REMAIN UNLOCKED AND | | | OPEN TO THE GENERAL PUBLIC FROM DAWN UNTIL DUSK. | | | | | | 9. PLEASE PROVIDE JUSTIFICATION AS TO HOW THE PROPOSED | | | DEVELOPMENT MEETS THAT ZONING AND LAND DEVELOPMENT | | | REGULATIONS REQUIREMENT THAT PLANNED DEVELOPMENTS | | | IMPLEMENT ?INNOVATIVE LAND PLANNING AND DEVELOPMENT | | | TECHNIQUES TO CREATE A MORE DESIRABLE AND ATTRACTIVE | | | DEVELOPMENT.? IT IS STRONGLY ENCOURAGED THAT THE | | | APPLICANT COORDINATE A STAND-ALONE MEETING WITH STAFF | | | TO DISCUSS THE PROPOSED DESIGN OF THE SITE, AS THERE | | | ARE SEVERAL CONCERNS. | | | | | | 10. AS IT APPEARS STRUCTURAL ELEMENTS OF THE BUILDINGS | | | ARE ENCROACHING INTO THE REQUIRED SIDE AND REAR | | | SETBACKS, PLEASE PROVIDE THE DIMENSIONS OF SUCH | | | ENCROACHMENT. PURSUANT TO SEC. 94-305, SUCH ELEMENTS | | | SHALL NOT EXTEND MORE THAN THREE (3) FEET INTO THE | | | REQUIRED SETBACK. | | | | | | 11. PHOTOMETRIC LEVELS SHALL BE PROVIDED AT ALL | | | PROPERTY LINES AND SHALL NOT EXCEED 0.5 FOOTCANDLES. | | | | | | 12. SITE PLAN SHALL IDENTIFY THE NUMBER OF BICYCLE | | | PARKING SPACES REQUIRED/PROVIDED; ONE (1) BICYCLE SPACE | | | SHALL BE PROVIDED FOR EVERY 20 VEHICULAR PARKING | | | SPACES. | | | | | | 13. A UNITY OF TITLE WILL BE REQUIRED PRIOR TO THE | | | ISSUANCE OF ANY BUILDING PERMITS. | | | ___________________________________________ | | | | | | PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING: | | | | | | A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL | | | DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION. | | | | | | B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE | | | PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X | | | 17IN), AND AN ELECTRONIC COPY OF ALL PLANS. | | | | | | C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO | | | ADDITIONAL COMMENTS. | | | | | | D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE | | | ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE | | | CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL | | | REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION. | | | | | | E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | | | | F) IN ORDER TO BE CONSIDERED FOR THE AUGUST 21, 2018, | | | PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE | | | SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED | | | DOCUMENTS/PLANS NO LATER THAN FRIDAY, JUNE 29, 2018. | | | | | | G) TO BE PLACED ON THE AUGUST 21, 2018, PLANNING BOARD | | | AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO LATER | | | THAN AUGUST 6, 2018. SIGNAGE SHALL CONFORM AND BE | | | INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING | | | AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN | | | THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED | | | AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED | | | ABOVE. | | | ___________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | F: 561.822.1460 | | | | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| |