Plan Review Details - Project Z18040013
Plan Review Stops For Project Z18040013
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 05-08-2018 Cont ID  
Sent By rbrown Date 05-08-2018 Time 18:45 Rev Time 0.00
Received By rbrown Date 05-08-2018 Time 18:44 Sent To  
Notes
2018-05-08 18:53:54DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCORDING TO THE ADOPTED FLOOD INSURANCE RATE MAPS
 (FIRMS), THE PROPOSED BUILDING IS IN FLOOD ZONE AE WITH
 A BASE FLOOD ELEVATION OF 12.1 FT NAVD. THE FIRST FLOOR
 OF THE BUILDING AND ALL ASSOCIATED MECHANICAL EQUIPMENT
 (CHILLERS, GENERATORS ETC.) SHALL BE 24 INCHES
 (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION.
  
 3. PEDESTRIAN/WHEELCHAIR ACCESSIBLE ROUTE. THE PLANS
 ONLY SHOW VEHICLULAR DRIVEWAY ACCESS AND DO NOT SHOW
 ANY PEDESTRIAN ACCESS TO THE FACILITY. WHEN SUBMITTED
 FOR PERMIT, THE PLANS SHALL SHOW AT LEAST ONE
 ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS 206.2 AND
 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC
 RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES.
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING, AND UNIT WITH AN INDEPENDENT
 ENTRANCE FROM THE STREET, SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 05-09-2018 Cont ID  
Sent By mgonzale Date 05-09-2018 Time   Rev Time 1.00
Received By mgonzale Date 05-09-2018 Time   Sent To I
Notes
2018-05-09 11:17:22PLEASE RESPOND TO COMMENTS IN WRITING:
  
 1. PROPOSED DRIVEWAY APRON SHALL BE PER CITY OF WPB
 STANDARD
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 2. CONDITION OF APPROVAL - TO REMOVE EXISTING DRIVEWAY
 APRON AND RESTORE SIDEWALK WHERE NOT NEEDED.
 THIS WILL REQUIRE CONTRACTOR TO OBTAIN A RIGHT-OF-WAY
 PERMIT.
  
 3. METER AND METER BOX TO BE LOCATED JUST BEHIND THE
 SIDEWALK IN EASEMENT. (5'X5' EASEMENT)
  
 4. SHOW SANITARY SEWER SERVICE LINE WITH CLEAN/OUT.
  
 5. SHOW POWER POLE LOCATION ON ALL PLANS. (POWER POLE
 LOCATED SW CORNER OF SITE ON SIDEWALK)
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 05-08-2018 Cont ID  
Sent By pleduc Date 05-08-2018 Time   Rev Time 0.00
Received By pleduc Date 05-08-2018 Time 16:16 Sent To  
Notes
2018-05-08 16:18:11THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND, IF REQUIRED, NEW FIRE HYDRANTS
 PLANNED FOR THIS DEVELOPMENT SHALL BE CLEARLY INDICATED
 AND IDENTIFIED ON THE PLAN AND CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. IF REQUIRED, PROVIDE FOR A FIRE SPRINKLER AND/OR
 FIRE ALARM PER THE APPLICABLE OCCUPANCY CODE. FOR ANY
 LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND
 FIRE ALARM, ENSURE THEY COMPLY WITH THE REQUIREMENTS OF
 FS 61G AND SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT
 ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON
 PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS,
 EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE
 EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES
 AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE
 SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY
 DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 05-03-2018 Cont ID  
Sent By rcaranci Date 05-03-2018 Time 14:43 Rev Time 0.00
Received By rcaranci Date 05-03-2018 Time 14:43 Sent To  
Notes
2018-05-03 14:43:58FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 1156 CLARE AVE Z18040013
 MAY 3, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A LANDSCAPE PLAN PREPARED, SIGNED AND
 SEALED BY A LANDSCAPE ARCHITECT PER THE CODE
 REQUIREMENT.
  
 2. PLEASE INDICATE THE REQUIRED OPEN SPACE TO 40
 PERCENT OF THE TOTAL SITE, AND RECALCULATE REQUIRED
 TREES AND FLOWERING TREES TO CURRENT CODE OF 1 TREE PER
 1500 SQ FT OF REQUIRED OPEN SPACE OR PORTION THEREOF,
 AND FLOWERING TREES TO ONE PER 6000 SQ FT OR PORTION
 THEREOF PER SECTION 94-442(C)(2)B.
  
 3. PLEASE PROVIDE CALCULATIONS FOR BUFFER REQUIREMENTS
 FOR ALL PROPERTY LINES, AND PROVIDE THE REQUIRED TREES
 OR NUMBER OF SUBSTITUTE PALMS PER CURRENT CODE
 REQUIREMENTS OF SECTION 94-443(D).
  
 4. PLEASE PROVIDE A TREE AS REQUIRED AND A TERMINAL
 LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING
 SPACES.
  
 5. PLEASE PROVIDE THE PERVIOUS LANDSCAPE AREA SQUARE
 FOOTAGE ON THE LANDSCAPE PLAN.
  
  
 6. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 7. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
  
 8. PLEASE REVISE PLANT LIST TO SHOW 12 FOOT MINIMUM
 TREE SIZES REQUIRED.
  
 9. PLEASE COMPLETE THE COLUMN FOR DROUGHT TOLERANCE ON
 THE PLANT LIST TO PROVIDE THE LEVEL FOR EACH SPECIES.
  
 10. PLEASE SHOW CALCULATIONS FOR THE BUILDING FOR
 COMPLIANCE WITH 30 PERCENT PERIMETER LANDSCAPE PER
 SECTION 94-443(E)(1).
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-05-08 19:23:40PLEASE NOTE THAT IF YOU INTEND ON HAVING A TRAH SERVICE
 AT THIS FACILITY YOU MUST PROVIDE THE DETAILS ON THIS.

Review Stop STORM STORMWATER
Rev No 1 Status F Date 05-09-2018 Cont ID  
Sent By tward Date 05-09-2018 Time 12:53 Rev Time 0.00
Received By tward Date 05-09-2018 Time 12:54 Sent To  
Notes
2018-05-09 12:54:29THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. NO ENGINEERING PLANS PROVIDED FOR THE INFORMAL SITE
 PLAN REVIEW REQUEST.
  
 2. DIRECT ROOFING GUTTER DOWN SPOUTS TO PERVIOUS AREAS
 IF POSSIBLE. OTHERWISE ATTEMPT TO CONNECT DIRECTLY TO
 THE DRAINAGE SYSTEM INSTEAD OF DISCHARGING TO
 IMPERVIOUS AREAS.
  
 3. DRAINAGE SYSTEM TO PROVIDE WATER QUALITY TREATMENT
 AND PEAK FLOW LIMITATIONS PER SFWMD CRITERIA.
  
 4. PROVIDE SCALE BAR ON THE SURVEY.
  
 5. 2017 FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE
 AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP APPROVAL PRIOR TO
 STARTING CONSTRUCTION.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 05-07-2018 Cont ID  
Sent By vnoel Date 05-07-2018 Time 09:03 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-05-07 09:08:551. UNITY OF TITLE HAS BEEN RECORDED.
 2. POWER POLE IN NW CORNER MAY INTERFERE WITH DRIVEWAY.
 3. APRON CANNOT EXTEND INTO ADJOINING PROPERTY.
 4. NO PRELIMINARY ENGINEERING PLANS INCLUDED. IF WATER
 MAIN/METER BOX SHOWN IN LANDSCAPE AREA, THEN EASEMENT
 WILL BE REQUIRED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 05-08-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-05-08 16:57:15- PROVIDE TRAFFIC IMPACT STUDY IN ACCORDANCE WITH CITY
 CODE SECTION 94-311 OR DOCUMENTATION DEMONSTRATING THAT
 CITY CODE SECTION 94-311(C) TRAFFIC IMPACT STUDY
 REQUIRED IS NOT APPLICABLE.
 - PROVIDE TRIP GENERATION LETTER DEMONSTRATING THAT
 DRIVEWAY VOLUME IS LOW ENOUGH TO WARRANT TWO WAY YIELD
 OPERATION
 - PARKING SPACE WIDTH SHOULD BE INCREASED TO 9?-6? TO
 ALLOW FOR CAR DOOR OPENING NEXT TO WALL. STANDARD
 PARKING SPACE IN CITY CODE DOES NOT ASSUME A WALL IS
 ADJACENT TO THE PARKING SPACE.
 - 15?-5? STACKING DISTANCE TO GATE IS INSUFFICIENT.
 PROVIDE 20? STACKING DISTANCE. IT IS ILLEGAL UNDER
 FLORIDA STATUTES FOR A VEHICLE TO STAND ON THE
 SIDEWALK.
 - SHOW ADA RAMPS IN DRIVEWAY
 - REVIEW IS PRELIMINARY BASED ON LIMITED INFORMATION
 PROVIDED ON SITE PLAN. DETAILED ENGINEERING PLANS WILL
 BE REQUIRED.
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 05-08-2018 Cont ID  
Sent By   Date 05-08-2018 Time   Rev Time 0.00
Received By pgreilic Date 05-08-2018 Time 15:32 Sent To  
Notes
2018-05-08 15:34:491156 CLARE AVE
 ISPR 18-08
 Z18040013
  
 1.) APPLICANT SHOULD CONSIDER JOINING SUBJECT PROPERTY
 TO THE PROPERTY DIRECTLY ADJACENT TO THE NORTH. THIS
 WOULD ALLOW FOR GREATER FLEXIBILITY OF DESIGN (PARKING,
 LANDSCAPE REQUIREMENTS, INGRESS/EGRESS) AND INCREASE
 THE OVERALL FUNCTIONALITY OF THE SITE
 2.) PROPOSED DRIVEWAY DOES NOT MEET CRITERIA OUTLINED
 IN SEC. 94-485
 3.) PROPOSED DRIVEWAY APRON CANNOT ENCROACH ONTO
 ADJACENT PROPERTY
 4.) WEST ELEVATION OF BUILDING 1 (A 2.0) SHOWS
 ELECTRICAL METERS AND PANELS ALONG CLARE AVE FRONTAGE.
 PLEASE RELOCATE TO LOCATION NOT VISIBLE FROM CLARE AVE.
 5.) CONSIDER ADDING FENESTRATION/ARCHITECTURAL
 TREATMENT TO BUILDING FACADES
 6.) PROVIDE BIKE RACK ON SITE WITH CURRENT CITY DETAIL
 7.) WHAT IS THE PROPOSED USE OF THE STRUCTURES?
 DIFFERENT USES ARE INDICATED IN JUSTIFICATION AND SITE
 PLAN. PLEASE CLARIFY
 8.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW
 CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN
 EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS
 ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE
 ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78,
 ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT
 SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR
 ADDITIONAL INFORMATION
 9.) SHOW ALL UTILITIES ON SITE PLAN
  
 ?PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN
 FORMAT
 ?WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 11
 PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11
 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND AN
 ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON
 THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS.
 ?PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE.
 ?CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443
 IF THERE ARE ANY QUESTIONS
  