Plan Review Details - Project Z18040013
| Plan Review Stops For Project Z18040013 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
05-08-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
05-08-2018 |
Time |
18:45 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
05-08-2018 |
Time |
18:44 |
Sent To |
|
|
| Notes |
| 2018-05-08 18:53:54 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. ACCORDING TO THE ADOPTED FLOOD INSURANCE RATE MAPS | | | (FIRMS), THE PROPOSED BUILDING IS IN FLOOD ZONE AE WITH | | | A BASE FLOOD ELEVATION OF 12.1 FT NAVD. THE FIRST FLOOR | | | OF THE BUILDING AND ALL ASSOCIATED MECHANICAL EQUIPMENT | | | (CHILLERS, GENERATORS ETC.) SHALL BE 24 INCHES | | | (FREEBOARD) ABOVE THE BASE FLOOD ELEVATION. | | | | | | 3. PEDESTRIAN/WHEELCHAIR ACCESSIBLE ROUTE. THE PLANS | | | ONLY SHOW VEHICLULAR DRIVEWAY ACCESS AND DO NOT SHOW | | | ANY PEDESTRIAN ACCESS TO THE FACILITY. WHEN SUBMITTED | | | FOR PERMIT, THE PLANS SHALL SHOW AT LEAST ONE | | | ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS 206.2 AND | | | 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC | | | RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY | | | ENTRANCES. | | | | | | 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 7. EACH SEPARATE BUILDING, AND UNIT WITH AN INDEPENDENT | | | ENTRANCE FROM THE STREET, SHALL HAVE A SEPARATE | | | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, | | | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
05-09-2018 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
05-09-2018 |
Time |
|
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
05-09-2018 |
Time |
|
Sent To |
I |
|
| Notes |
| 2018-05-09 11:17:22 | PLEASE RESPOND TO COMMENTS IN WRITING: | | | | | | 1. PROPOSED DRIVEWAY APRON SHALL BE PER CITY OF WPB | | | STANDARD | | | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | 2. CONDITION OF APPROVAL - TO REMOVE EXISTING DRIVEWAY | | | APRON AND RESTORE SIDEWALK WHERE NOT NEEDED. | | | THIS WILL REQUIRE CONTRACTOR TO OBTAIN A RIGHT-OF-WAY | | | PERMIT. | | | | | | 3. METER AND METER BOX TO BE LOCATED JUST BEHIND THE | | | SIDEWALK IN EASEMENT. (5'X5' EASEMENT) | | | | | | 4. SHOW SANITARY SEWER SERVICE LINE WITH CLEAN/OUT. | | | | | | 5. SHOW POWER POLE LOCATION ON ALL PLANS. (POWER POLE | | | LOCATED SW CORNER OF SITE ON SIDEWALK) | | | | | | MANNY GONZALEZ | | | SENIOR ENGINEERING PROJECT COORDINATOR | | | PUBLIC WORKS DEPARTMENT | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33401 | | | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) | | | MAIN PHONE: (561) 822-1200 | | | DIRECT: (561) 494-1085 | | | FAX: (561) 494-1116 | | | EMAIL: [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
05-08-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-08-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-08-2018 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2018-05-08 16:18:11 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND, IF REQUIRED, NEW FIRE HYDRANTS | | | PLANNED FOR THIS DEVELOPMENT SHALL BE CLEARLY INDICATED | | | AND IDENTIFIED ON THE PLAN AND CLOSELY COORDINATED WITH | | | THE BUREAU OF FIRE PREVENTION. | | | | | | 9. IF REQUIRED, PROVIDE FOR A FIRE SPRINKLER AND/OR | | | FIRE ALARM PER THE APPLICABLE OCCUPANCY CODE. FOR ANY | | | LIFE SAFETY ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND | | | FIRE ALARM, ENSURE THEY COMPLY WITH THE REQUIREMENTS OF | | | FS 61G AND SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS SHALL BE PROVIDED THAT | | | ILLUSTRATE OCCUPANT LOADS, TRAVEL DISTANCES, COMMON | | | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, | | | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE | | | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES | | | AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED (REQUIRED WITH FIRE | | | SPRINKLER SYSTEM) THAT A KNOX BOX WITH KEYS FOR ENTRY | | | DOOR LOCKS BE PROVIDED FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE ITS FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
05-03-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-03-2018 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-03-2018 |
Time |
14:43 |
Sent To |
|
|
| Notes |
| 2018-05-03 14:43:58 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 1156 CLARE AVE Z18040013 | | | MAY 3, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE PROVIDE A LANDSCAPE PLAN PREPARED, SIGNED AND | | | SEALED BY A LANDSCAPE ARCHITECT PER THE CODE | | | REQUIREMENT. | | | | | | 2. PLEASE INDICATE THE REQUIRED OPEN SPACE TO 40 | | | PERCENT OF THE TOTAL SITE, AND RECALCULATE REQUIRED | | | TREES AND FLOWERING TREES TO CURRENT CODE OF 1 TREE PER | | | 1500 SQ FT OF REQUIRED OPEN SPACE OR PORTION THEREOF, | | | AND FLOWERING TREES TO ONE PER 6000 SQ FT OR PORTION | | | THEREOF PER SECTION 94-442(C)(2)B. | | | | | | 3. PLEASE PROVIDE CALCULATIONS FOR BUFFER REQUIREMENTS | | | FOR ALL PROPERTY LINES, AND PROVIDE THE REQUIRED TREES | | | OR NUMBER OF SUBSTITUTE PALMS PER CURRENT CODE | | | REQUIREMENTS OF SECTION 94-443(D). | | | | | | 4. PLEASE PROVIDE A TREE AS REQUIRED AND A TERMINAL | | | LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING | | | SPACES. | | | | | | 5. PLEASE PROVIDE THE PERVIOUS LANDSCAPE AREA SQUARE | | | FOOTAGE ON THE LANDSCAPE PLAN. | | | | | | | | | 6. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 7. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | | | | 8. PLEASE REVISE PLANT LIST TO SHOW 12 FOOT MINIMUM | | | TREE SIZES REQUIRED. | | | | | | 9. PLEASE COMPLETE THE COLUMN FOR DROUGHT TOLERANCE ON | | | THE PLANT LIST TO PROVIDE THE LEVEL FOR EACH SPECIES. | | | | | | 10. PLEASE SHOW CALCULATIONS FOR THE BUILDING FOR | | | COMPLIANCE WITH 30 PERCENT PERIMETER LANDSCAPE PER | | | SECTION 94-443(E)(1). | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-08 19:23:40 | PLEASE NOTE THAT IF YOU INTEND ON HAVING A TRAH SERVICE | | | AT THIS FACILITY YOU MUST PROVIDE THE DETAILS ON THIS. |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
05-09-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-09-2018 |
Time |
12:53 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-09-2018 |
Time |
12:54 |
Sent To |
|
|
| Notes |
| 2018-05-09 12:54:29 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. NO ENGINEERING PLANS PROVIDED FOR THE INFORMAL SITE | | | PLAN REVIEW REQUEST. | | | | | | 2. DIRECT ROOFING GUTTER DOWN SPOUTS TO PERVIOUS AREAS | | | IF POSSIBLE. OTHERWISE ATTEMPT TO CONNECT DIRECTLY TO | | | THE DRAINAGE SYSTEM INSTEAD OF DISCHARGING TO | | | IMPERVIOUS AREAS. | | | | | | 3. DRAINAGE SYSTEM TO PROVIDE WATER QUALITY TREATMENT | | | AND PEAK FLOW LIMITATIONS PER SFWMD CRITERIA. | | | | | | 4. PROVIDE SCALE BAR ON THE SURVEY. | | | | | | 5. 2017 FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE | | | BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD | | | HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE | | | AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX? | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP APPROVAL PRIOR TO | | | STARTING CONSTRUCTION. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
05-07-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
05-07-2018 |
Time |
09:03 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-07 09:08:55 | 1. UNITY OF TITLE HAS BEEN RECORDED. | | | 2. POWER POLE IN NW CORNER MAY INTERFERE WITH DRIVEWAY. | | | 3. APRON CANNOT EXTEND INTO ADJOINING PROPERTY. | | | 4. NO PRELIMINARY ENGINEERING PLANS INCLUDED. IF WATER | | | MAIN/METER BOX SHOWN IN LANDSCAPE AREA, THEN EASEMENT | | | WILL BE REQUIRED. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
05-08-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-08 16:57:15 | - PROVIDE TRAFFIC IMPACT STUDY IN ACCORDANCE WITH CITY | | | CODE SECTION 94-311 OR DOCUMENTATION DEMONSTRATING THAT | | | CITY CODE SECTION 94-311(C) TRAFFIC IMPACT STUDY | | | REQUIRED IS NOT APPLICABLE. | | | - PROVIDE TRIP GENERATION LETTER DEMONSTRATING THAT | | | DRIVEWAY VOLUME IS LOW ENOUGH TO WARRANT TWO WAY YIELD | | | OPERATION | | | - PARKING SPACE WIDTH SHOULD BE INCREASED TO 9?-6? TO | | | ALLOW FOR CAR DOOR OPENING NEXT TO WALL. STANDARD | | | PARKING SPACE IN CITY CODE DOES NOT ASSUME A WALL IS | | | ADJACENT TO THE PARKING SPACE. | | | - 15?-5? STACKING DISTANCE TO GATE IS INSUFFICIENT. | | | PROVIDE 20? STACKING DISTANCE. IT IS ILLEGAL UNDER | | | FLORIDA STATUTES FOR A VEHICLE TO STAND ON THE | | | SIDEWALK. | | | - SHOW ADA RAMPS IN DRIVEWAY | | | - REVIEW IS PRELIMINARY BASED ON LIMITED INFORMATION | | | PROVIDED ON SITE PLAN. DETAILED ENGINEERING PLANS WILL | | | BE REQUIRED. | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
05-08-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
05-08-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
05-08-2018 |
Time |
15:32 |
Sent To |
|
|
| Notes |
| 2018-05-08 15:34:49 | 1156 CLARE AVE | | | ISPR 18-08 | | | Z18040013 | | | | | | 1.) APPLICANT SHOULD CONSIDER JOINING SUBJECT PROPERTY | | | TO THE PROPERTY DIRECTLY ADJACENT TO THE NORTH. THIS | | | WOULD ALLOW FOR GREATER FLEXIBILITY OF DESIGN (PARKING, | | | LANDSCAPE REQUIREMENTS, INGRESS/EGRESS) AND INCREASE | | | THE OVERALL FUNCTIONALITY OF THE SITE | | | 2.) PROPOSED DRIVEWAY DOES NOT MEET CRITERIA OUTLINED | | | IN SEC. 94-485 | | | 3.) PROPOSED DRIVEWAY APRON CANNOT ENCROACH ONTO | | | ADJACENT PROPERTY | | | 4.) WEST ELEVATION OF BUILDING 1 (A 2.0) SHOWS | | | ELECTRICAL METERS AND PANELS ALONG CLARE AVE FRONTAGE. | | | PLEASE RELOCATE TO LOCATION NOT VISIBLE FROM CLARE AVE. | | | 5.) CONSIDER ADDING FENESTRATION/ARCHITECTURAL | | | TREATMENT TO BUILDING FACADES | | | 6.) PROVIDE BIKE RACK ON SITE WITH CURRENT CITY DETAIL | | | 7.) WHAT IS THE PROPOSED USE OF THE STRUCTURES? | | | DIFFERENT USES ARE INDICATED IN JUSTIFICATION AND SITE | | | PLAN. PLEASE CLARIFY | | | 8.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL OR GREATER THAN $750,000 IS SUBJECT TO THE | | | ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY?S CODE OF ORDINANCES. CONTACT | | | SYBILLE WELTER @ 561-822-1521 OR [email protected] FOR | | | ADDITIONAL INFORMATION | | | 9.) SHOW ALL UTILITIES ON SITE PLAN | | | | | | ?PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN WRITTEN | | | FORMAT | | | ?WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF 11 | | | PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X 11 | | | INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND AN | | | ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE CHANGES ON | | | THE RESUBMITTED PLAN MAY RESULT IN ADDITIONAL COMMENTS. | | | ?PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE. | | | ?CONTACT PAUL GREILICH, SENIOR PLANNER @ 561-822-1443 | | | IF THERE ARE ANY QUESTIONS | | | |
|
|
| |
Print |
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |