Plan Review Details - Project Z18030013
Plan Review Stops For Project Z18030013
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 04-10-2018 Cont ID  
Sent By rbrown Date 04-10-2018 Time 19:36 Rev Time 0.00
Received By rbrown Date 04-10-2018 Time 19:36 Sent To  
Notes
2018-04-10 20:44:56DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A
 RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL
 INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT
 APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL
 ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA
 BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE.
  
 3. NUMBER OF ACCESSIBLE PARKING SPACES SERVING THE
 OFFICE SPACE. THERE ARE NOT SUFFICIENT ACCESSIBLE
 PARKING SPACES DIRECTLY SERVING THE OFFICE SPACE. THE
 PARKING TABLE ON SITE AND PROJECT DATA SHEET A0.01
 STATES THAT 562 PARKING SPACES ARE PROPOSED FOR THE
 OFFICE USE. THEREFORE 13 ACCESSIBLE PARKING SPACES ARE
 REQUIRED FOR OFFICE USE PER SECTION 208.2 OF FLORIDA
 ACCESSIBILITY CODE. OFFICE LEVEL PLAN SHEETS A1.09,
 A1.10, AND A1.11 FOR LEVELS 9 THROUGH 18 ALL SHOW THAT
 ONLY ELEVATORS 1 THROUGH 5 SERVE THE OFFICE LEVELS.
 ONLY 4 OF THE PROVIDED ACCESSIBLE PARKING SPACES ARE
 LOCATED AS THE CLOSEST PARKING SPACES TO THOSE
 ELEVATORS. OF THOSE 4 ACCESSIBLE PARKING SPACES, 2 ARE
 ON LEVEL 7 PLAN SHEET A1.07 AND 2 ARE ON LEVEL 8 PLAN
 SHEET A1.08. THE REMAINDER OF THE ACCESSIBLE PARKING
 SPACES ARE SHOWN ON PLAN SHEETS A1.02 THOUGH A1.06, FOR
 LEVELS 2 THROUGH 6, AND NONE OF THOSE ARE THE CLOSEST
 PARKING SPACES TO ELEVATORS 1 THROUGH 5. SO, THERE ARE
 NOT ENOUGH ACCESSIBLE PARKING SPACES SERVING THE OFFICE
 SPACE. IT IS NOTED THAT ELEVATORS 1 THROUGH DO NOT STOP
 AT LEVELS 2 THROUGH 6 BUT THAT DOES NOT AFFECT THIS
 ISSUE. PER SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE,
 ACCESSIBLE PARKING SPACES ARE TO BE LOCATED ON THE
 SHORTEST POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING
 TO AN ACCESSIBLE ENTRANCE. THE DESIGN OF ACCESSIBLE
 PARKING SPACES SHALL COMPLY WITH SECTION 502 OF FLORIDA
 ACCESSIBILITY CODE
  
 4. VAN ACCESSIBLE PARKING SPACES. A TOTAL OF 3 VAN
 ACCESSIBLE PARKING SPACES ARE REQUIRED BUT ONLY 2 ARE
 SHOWN. LEVEL 2 PLAN SHEET A1.02 SHOWS 2 VAN ACCESSIBLE
 PARKING SPACES AND THERE DOES NOT APPEAR TO BE ANY
 OTHERS SHOWN ON THE PLANS, SO AN ADDITIONAL VAN
 ACCESSIBLE PARKIG SPACE IS REQUIREDPER SECTION 208.2.4
 OF FLORIDA ACCESSIBILITY CODE, ONE IN EVERY SIX
 REQUIRED ACCESSIBLE SPACES (AT LEAST ONE) IN A PARKING
 STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND DESIGNED IN
 ACCORDANCE WITH SECTION OF 502 OF FLORIDA ACCESSIBILITY
 CODE (VERTICAL CLEARANCE NOT LESS THAN 98 INCHES AT
 SPACE AND VEHICULAR ACCESS ROUTE).
  
 5. EGRESS FROM THE SOUTH OFFICE SPACE ON LEVEL 2 AND
 LEVEL 4. EGRESS FROM THE OFFICE SPACE SHALL NOT PASS
 THROUGH THE PARKING GARAGE. LEVEL 2 PLAN SHEET A1.02
 AND LEVEL 4 PLAN SHEET A1.04 SHOW ONE OF THE EGRESS
 PATHS FROM THE SOUTH (FERN ST) OFICE SPACE GOING
 THROUGH THE PARKING GARAGE. SECTION 1016.2(2) OF
 FLORIDA BUILDING CODE STATES THAT EGRESS FROM A SPACE
 SHALL NOT PASS THROUGH AN ADJOINING AREA UNLESS SUCH
 ADJOINING AREA AND THE SPACE SERVED ARE ACCESSORY TO
 ONE OR THE OTHER.
  
 6. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 7. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 8. ENCLOSED PARKING GARAGES. THE PARKING GARAGE APPEARS
 TO BE ENCLOSED AND MECHANICALLY VENTILATED. IF THE
 PARKING GARAGE DOES NOT HAVE WALL OPENINGS, OR
 SUFFICIENT WALL OPENINGS TO MEET THE DEFINITION OF AN
 OPEN PARKING GARAGE, IT WILL BE CONSIDERED AN ENCLOSED
 PARKING GARAGE AND MUST HAVE EXHAUST SYSTEMS. THE
 EXHAUST SYSTEMS SHALL BE DESIGNED TO MINIMIZE NOISE
 LEVELS USING INLINE FAN SILENCERS OR OTHER APPROVED
 METHODS.
  
 9. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 10. EACH SEPARATE BUILDING, AND UNIT WITH AN
 INDEPENDENT ENTRANCE FROM THE STREET, SHALL HAVE A
 SEPARATE ADDRESS. FOR STREET ADDRESSING, CONTACT
 MICHAEL ORIO, GIS SUPPORT SPECIALIST, AT (561) 494
 1080, OR BY EMAIL: [email protected]
  
 11. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC
 PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION
 OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT,
 CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES
 COORDINATOR, AT (561) 822-1521, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 04-11-2018 Cont ID  
Sent By Mgonzale Date 04-11-2018 Time   Rev Time 1.00
Received By mgonzale Date 04-11-2018 Time   Sent To I
Notes
2018-04-11 10:56:10PLEASE RESPOND TO COMMENTS IN WRITING:
  
 #1 UTILITY AND TOPOGRAPHIC INFORMATION SHOWN IN THE ROW
 APPEARS TO BE INCORRECT. PLEASE REQUEST LATEST
 AS-BUILTS FROM OUR CAD GROUP TO UPDATE PLAN.
 NEW SEWER MAIN WAS REPLACED IN EVERNIA.
  
 #2 LARGE DOMESTIC METER AND VAULT SHOWN IN THE ROW
 NEEDS TO MOVE ON-SITE IN AN EASEMENT JUST INSIDE THE
 PROPERTY, AS FUTURE ROAD ROW WILL NOT ALLOW SPACE FOR
 THIS METER.
 THIS METER MAY BE INSTALLED IN A FIRE RATED ROOM,
 INSTALLED ABOVE GROUND FOR CONVENIENCE.
  
 #3 WATER DEMANDS AS SHOWN ON SHEET C-6 WILL BE PROVIDED
 FOR EACH METER SERVING THE PROPERTY. INCLUDING ANY
 IRRIGATION AND/OR SMALLER WATER SERVICES SERVING THE
 BUILDING FOR ANY OTHER PURPOSE.
  
 #4 ALL EXISTING SERVICES SHALL BE SHOWN AND BE CUT BACK
 TO MAIN.
  
 #5 IF YOU DECIDE SERVICE OFF AN OLDER SANITARY SEWER
 MAIN, THEN A VIDEO ASSESMENT OF THE SEWER WILL BE
 REQUIRED TO SATISFY THIS SUBMITTAL.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 05-08-2018 Cont ID  
Sent By pleduc Date 05-08-2018 Time   Rev Time 0.00
Received By pleduc Date 05-08-2018 Time 16:56 Sent To  
Notes
2018-05-08 16:58:242ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM ANA MARIA
 APONTE, CITY URBAN DESIGNER, THE ATTACHED LETTER DATED
 APRIL 27, 2018, FROM LEO A DALY, AND INFORMATIONAL
 DOCUMENTS, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 04-05-2018 Cont ID  
Sent By pleduc Date 04-05-2018 Time   Rev Time 0.00
Received By pleduc Date 04-05-2018 Time 13:38 Sent To  
Notes
2018-04-05 14:11:56THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED. SEPARATE SHOP DRAWINGS, ARE REQUIRED
 TO BE SUBMITTED, REVIEWED AND APPROVED BY THE FIRE
 PREVENTION BUREAU PRIOR TO ANY INSTALLATION.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. PLEASE
 PROVIDE THE DIMENSION TO THE FIRE HYDRANT CLOSEST TO
 THE SOUTHERN LOCATED FDC AND ENSURE COMPLIANCE.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS
 OPERATIONAL AND WILL ACCOMMODATE AN AMBULANCE STRETCHER
 76 INCHES LONG AND 24 INCHES WIDE IN THE HORIZONTAL
 POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. COMMAND ROOM
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 13. RADIO
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ONE KNOX BOX WITH KEYS SHOULD BE PROVIDED AT EACH FDC
 LOCATION.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 05-18-2018 Cont ID  
Sent By rcaranci Date 05-18-2018 Time 14:45 Rev Time 0.00
Received By rcaranci Date 05-18-2018 Time 14:45 Sent To  
Notes
2018-05-18 14:45:37FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CITY PLACE OFFICE Z18030013
 MAY 18, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE INCLUDE ALL STREET TREES AFFECTED
 BY CONSTRUCTION ON THE TREE DISPOSITION LIST.
  
 2. SATISFIED. PLEASE ADJUST THE CALCULATIONS FOR TREE
 MITIGATION FOR ANY CHANGES TO THE LANDSCAPE PLAN.
  
 3. PARTIALLY SATISFIED. PLEASE CONSOLIDATE PLANT LISTS
 AND PROVIDE ONLY ONE LIST THAT INCLUDES THE TERRACE
 PLANTINGS. PROVIDE WATER NEEDS CATEGORY FOR EACH
 SPECIES ON THE PLANT LIST FROM THE SFWMD WATERWISE
 GUIDE TO SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY
 LANDSCAPE CHART SECTION 94-446 (G). LOW, MEDIUM OR HIGH
 DROUGHT TOLERANCE IS REQUIRED FOR EACH LISTING.
 LABEL EACH SPECIES AS LOW MEDIUM OR HIGH DROUGHT
 TOLERANCE IN PLANT LIST COLUMN.
  
 4. PARTIALLY SATISFIED. PLEASE UPDATE THE FLORIDA
 FRIENDLY LANDSCAPE CHART SECTION 94-446 (G) TO CURRENT
 CODE REQUIREMENTS OF 50 POINTS AND UPDATE POINT VALUES.
  
 THE DESIGN OPTIONS CHART LIST HAS CHANGED WORDING AND
 POINT VALUES, UPDATE TO CURRENT VERSION IN MUNICODE.
  
 5. SATISFIED. THE ROSEMARY STREETSCAPE SHALL MATCH THE
 DESIGN CURRENTLY IN PROGRESS.
 (MINIMUM STREET TREE HEIGHT IS 20 FEET, THE
 LAGERSTROEMIA DO NOT MEET THIS REQUIREMENT.)
  
 6. SATISFIED. PLEASE ADD AN OAK STREET TREE AT THE
 MIDPOINT OF THE DROP OFF AREA ALONG EVERNIA ST. THE
 UTILITY LOCATIONS MAY HAVE TO BE ADJUSTED TO AVOID
 CONFLICT.
  
 7. SATISFIED. PLEASE SHOW LOCATIONS OF STRUCTURAL SOIL
 ON SHEET L2.00 UNDER SIDEWALK AREAS ADJACENT TO TREE
 PLANTING AREAS, PROVIDING A MINIMUM14 BY 9 FOOT ROOT
 ZONE FOR ALL STREET TREES AND PROVIDE A TYPICAL DETAIL
 FOR STRUCTURAL SOIL.
  
 8. SATISFIED. FERN ST. STREET TREES SHALL BE ADJUSTED
 TO PROVIDE AN OAK IN THE PLANTING BULB OUT ON THE WEST
 SIDE OF THE ENTRANCE DRIVE INSTEAD OF THE PIGEON PLUM,
 AND THE REMAINING THREE STREET TREES SHOWN AS PIGEON
 PLUMS SHALL BE 4 BY 8 FT. BIOSWALES WITH LIVE OAK TREES
 TO MATCH THE STREET TREE INSTALLATIONS TO THE EAST OF
 THE PROPERTY.
  
 9. SATISFIED. THE PLANT SYMBOL TA/374 IS NOT INCLUDED
 OR IDENTIFIED ON THE PLANT LIST, PLEASE REVISE.
  
 10. SATISFIED. REMOVE PLAZA TREE REQUIREMENT REFERENCES
 FROM THE CODE COMPLIANCE TABLE, AS THESE DO NOT APPLY.
 TREE REQUIREMENTS ARE ADDRESSED IN THE PUBLIC OPEN
 SPACE REQUIREMENTS.
 ADDITIONAL COMMENTS 5/18/18:
 11. SECTION 94-448(D)(3) REQUIRES ALL NATIVE TREES AND
 PALMS IN GOOD CONDITION TO BE RELOCATED RATHER THAN
 DESTROYED. EVEN THOUGH THEY MAY NOT BE USED DIRECTLY ON
 THIS PROJECT, THERE ARE OTHER AREAS WITHIN CITY PLACE
 THAT MAY BE POSSIBLE, AND THE CITY HAS PUBLIC SITES
 THAT ARE IN NEED OF TREES AND PALMS.
  
 12. THERE ARE MISIDENTIFIED SPECIES ON THE TREE
 DISPOSITION LIST. PALMS 68 AND 69 ARE COCONUT PALMS,
 PLEASE CORRECT.
  
 13. PLEASE CORRECT ALL CANOPY CALCULATIONS FOR TREES
 LESS THAN 20 FEET DIAMETER (1:1 REPLACEMENT MITIGATION)
 TO SHOW THEIR CANOPY CATEGORY BY SPECIES. CATEGORY 1 IS
 300 SQ FT CANOPY CREDIT, CATEGORY 2 IS 150 SQ FT CANOPY
 CREDIT, CATEGORY 3 IS 100 SQ FT CANOPY CREDIT, AND
 CATEGORY 4 IS 50 SQ FT CANOPY CREDIT.
  
 14. FOR THE FINAL PLANT LIST, PLEASE SHOW COMPLIANCE
 WITH SECTION 94-445 L. PLANT SPECIES. A MINIMUM OF 60
 PERCENT OF PLANT MATERIAL ADDED SHALL BE FLORIDA NATIVE
 OR DROUGHT TOLERANT SPECIES SELECTED FROM THE CITY LIST
 OR THE LIST OF SPECIES IN THE MOST RECENT EDITION OF
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT WATERWISE SOUTH
 FLORIDA LANDSCAPES.
  
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-10-2018 Cont ID  
Sent By rcaranci Date 04-10-2018 Time 17:22 Rev Time 0.00
Received By rcaranci Date 04-10-2018 Time 17:22 Sent To  
Notes
2018-04-10 17:23:05FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: CITY PLACE OFFICE Z18030013
 APRIL 10, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE INCLUDE ALL STREET TREES AFFECTED BY
 CONSTRUCTION ON THE TREE DISPOSITION LIST.
  
 2. PLEASE ADJUST THE CALCULATIONS FOR TREE MITIGATION
 FOR ANY CHANGES TO THE LANDSCAPE PLAN.
  
 3. PLEASE CONSOLIDATE PLANT LISTS AND PROVIDE ONLY ONE
 LIST THAT INCLUDES THE TERRACE PLANTINGS. PROVIDE WATER
 NEEDS CATEGORY FOR EACH SPECIES ON THE PLANT LIST FROM
 THE SFWMD WATERWISE GUIDE TO SHOW COMPLIANCE WITH THE
 FLORIDA FRIENDLY LANDSCAPE CHART SECTION 94-446 (G).
 LOW, MEDIUM OR HIGH DROUGHT TOLERANCE IS REQUIRED FOR
 EACH LISTING.
  
 4. PLEASE UPDATE THE FLORIDA FRIENDLY LANDSCAPE CHART
 SECTION 94-446 (G) TO CURRENT CODE REQUIREMENTS OF 50
 POINTS AND UPDATE POINT VALUES.
  
 5. THE ROSEMARY STREETSCAPE SHALL MATCH THE DESIGN
 CURRENTLY IN PROGRESS.
 (MINIMUM STREET TREE HEIGHT IS 20 FEET, THE
 LAGERSTROEMIA DO NOT MEET THIS REQUIREMENT.)
  
 6. PLEASE ADD AN OAK STREET TREE AT THE MIDPOINT OF THE
 DROP OFF AREA ALONG EVERNIA ST. THE UTILITY LOCATIONS
 MAY HAVE TO BE ADJUSTED TO AVOID CONFLICT.
  
 7. PLEASE SHOW LOCATIONS OF STRUCTURAL SOIL ON SHEET
 L2.00 UNDER SIDEWALK AREAS ADJACENT TO TREE PLANTING
 AREAS, PROVIDING A MINIMUM14 BY 9 FOOT ROOT ZONE FOR
 ALL STREET TREES AND PROVIDE A TYPICAL DETAIL FOR
 STRUCTURAL SOIL.
  
 8. FERN ST. STREET TREES SHALL BE ADJUSTED TO PROVIDE
 AN OAK IN THE PLANTING BULB OUT ON THE WEST SIDE OF THE
 ENTRANCE DRIVE INSTEAD OF THE PIGEON PLUM, AND THE
 REMAINING THREE STREET TREES SHOWN AS PIGEON PLUMS
 SHALL BE 4 BY 8 FT. BIOSWALES WITH LIVE OAK TREES TO
 MATCH THE STREET TREE INSTALLATIONS TO THE EAST OF THE
 PROPERTY.
  
 9. THE PLANT SYMBOL TA/374 IS NOT INCLUDED OR
 IDENTIFIED ON THE PLANT LIST, PLEASE REVISE.
  
 10. REMOVE PLAZA TREE REQUIREMENT REFERENCES FROM THE
 CODE COMPLIANCE TABLE, AS THESE DO NOT APPLY. TREE
 REQUIREMENTS ARE ADDRESSED IN THE PUBLIC OPEN SPACE
 REQUIREMENTS.
  
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION. THIS WILL BE THROUGH A
 SEPARATE MAINTENANCE AGREEMENT WITH THE CITY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 04-12-2018 Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-04-12 13:45:35PLEASE ENSURE THAT WHEN YOU CONTRACT FOR ROLL OFF
 SERVICE YOU ARE USING ONE OF THE FRACHISE AUTHORIZED
 COMPANIES.
2018-04-10 15:03:38BASED ON THE PRINTS PROVIDED I WAS NOT ABLE TO SEE WHAT
 THE SANITATION PLAN IS. HOW DO YOU PLAN ON HANDLING THE
 TRASH FOR THE RESIDENTS OF THIS BUILDING? PLEASE
 PROVIDE THOSE SPECIFICATIONS FOR REVIEW.

Review Stop STORM STORMWATER
Rev No 1 Status F Date 04-10-2018 Cont ID  
Sent By tward Date 04-10-2018 Time 14:28 Rev Time 0.00
Received By tward Date 04-10-2018 Time 14:45 Sent To  
Notes
2018-04-10 14:44:57THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. THIS REVIEW DOES NOT INCLUDE THE ADJACENT
 RIGHTS-OF-WAY DESIGN FEATURES.
  
 2. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE
 AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?
 UPDATE THE FEMA FLOOD MAP INFORMATION ON THE SURVEY.
  
 3. ONSITE STORMATER MANAGEMENT SYSTEM TO BE DESIGNED TO
 PROVIDE WATER QUALITY TREATMENT AND PEAK FLOW
 ATTENUATION IN ACCORDANCE WITH SFWMD AND CWPB CRITERIA.
  
 4. COMBINE ROOF LEADERS TO MINIMIMZE THE NUMBER OF
 DRAINAGE CONNECTIONS TO THE OFSITE DRAINAGE SYSTEMS.
  
 5. MAINTAIN HISTORIC RUNOFF (DRAINAGE BASIN) PATTERNS.
  
 6. DRANAGE PIPES WITHIN PUBLIC RIGHT-OF-WAY TO BE
 MINIMUM 15" RCP.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION PERMIT
 FOR THE PROJECT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 04-09-2018 Cont ID  
Sent By vnoel Date 04-09-2018 Time 09:14 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-04-09 09:44:131. REPLAT WILL BE REQUIRED.
 2. AERIAL ENCROACHMENT WILL BE REQUIRED FOR
 AWNINGS/BALCONY'S INTO RIGHT-OF-WAY.
 3. ACCESS/UTILITY EASEMENT WILL BE REQUIRED OVER
 DRIVEWAY TO ALLEY.
 4. PLEASE NOTE ROSEMARY AVE. MAINTENANCE MAP IN RPB 8,
 P 82.
 5. ADDITIONAL ACCESS EASEMENT FROM ADJACENT OWNER WILL
 BE REQUIRED FOR ALLEY ACCESS.
 6. CITY WILL OBTAIN QUOTE FOR APPRAISAL TO BE PAID FOR
 BY DEVELOPER.
 7. MAINTENANCE AGREEMENT WILL BE REQUIRED FOR
 PLANTERS/LANDSCAPING, ETC. IN RIGHT-OF-WAY.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 04-10-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-04-10 17:57:59 
 ROSEMARY TOWER (370 SOUTH ROSEMARY AVENUE) TRAFFIC
 ANALYSIS (DATED MARCH 8, 2018) COMMENTS:
 - CLARIFY THE PROPOSED OFFICE AND RETAIL SQUARE
 FOOTAGE. VARIOUS SQUARE-FOOTAGES FOR THE OFFICE ARE
 INDICATED IN THE TRAFFIC STUDY INCLUDING 227,321 SQ.
 FT., 249,902 SQ. FT., AND 205,118 SQ. FT. THE RETAIL
 SQUARE FOOTAGE OF 22,581 SQ. FT. IS ASSUMED IN THE
 TRAFFIC STUDY. THESE ARE DIFFERENT THAN THE SQUARE
 FOOTAGES SHOWN ON THE SUBMITTED SITE PLAN.
 - CONSIDER REMOVING THE EXCESS PARKING SPACES. THE
 EXCESS PARKING SPACES APPEAR TO BE CONTRADICTORY OF THE
 ASSUMPTION FOR MULTI-MODAL TRIPS. THE TRIP GENERATION
 ASSUMES 20% REDUCTION IN VEHICULAR TRIPS TO ACCOUNT FOR
 MULTIMODAL TRIPS AND INTERNALIZATION WITH ADJACENT
 DOWNTOWN DEVELOPMENTS. HOWEVER, THE PROPOSED
 DEVELOPMENT PROVIDES 562 OFFICE ORIENTED PARKING
 SPACES, WHICH IS APPROXIMATELY 10% MORE THAN THE CODE
 REQUIREMENT OF 513 SPACES.
 - IF VEHICULAR TRIP REDUCTION IS ASSUMED AND EXCESS
 PARKING SPACES ARE PROPOSED, PLEASE PROVIDE A PARKING
 STUDY TO SHOW THAT THE EXCESS PARKING SPACES ARE NEEDED
 EVEN WITH THE VEHICULAR TRIP REDUCTION.
 - PROVIDE SUPPORTING DOCUMENTATION FOR THE 20%
 REDUCTION FOR MULTI-MODAL TRIPS. 20% REDUCTION FOR
 MULTI-MODAL TRIPS IS VERY HIGH.
 - INTERNALIZATION OF TRIPS WITH ADJACENT DOWNTOWN
 DEVELOPMENTS SHOULD BE ACCOUNTED FOR IN THE TRIP
 DISTRIBUTION, BUT NOT AS A REDUCTION IN TRIP
 GENERATION.
 - CLARIFY IF THE ITE RATES WITH ?GENERAL URBAN/SUBURBAN
 CHARACTERISTICS? FROM THE 10TH EDITION OF ITE TRIP
 GENERATION MANUAL ALREADY ACCOUNT FOR PERSON-BASED
 TRIPS. THE TOTAL PEAK HOUR TRIPS IN TABLES 6 AND 7 ARE
 35% LOWER THAN THE TRIPS ESTIMATED BASED ON THE TRIP
 GENERATION RATES FROM PALM BEACH COUNTY OR ITE TRIP
 GENERATION 9TH EDITION (398 AM TRIPS AND 372 PM TRIPS).
 THE 10TH EDITION OF ITE TRIP GENERATION MANUAL HAS
 ADDED DATA FOR URBAN LAND USES, AND THE PUBLISHED RATES
 MAY HAVE ACCOUNTED FOR MULTI-MODAL TRIPS. THEREFORE,
 INCLUDING AN ADDITIONAL 20% REDUCTION IN TRIPS MAY HAVE
 DOUBLE-DISCOUNTED FOR THE MULTI-MODAL TRIPS.
 - INCLUDE THE RETAIL LAND USES IN THE TRIP GENERATION
 ESTIMATES.
 - PROVIDE TRIP INFORMATION AND SUPPORTING DOCUMENT FOR
 EACH COMMITTED DEVELOPMENT ASSUMED IN THE REPORT.
 - COLLECT UPDATED COUNTS. TRAFFIC COUNTS WERE COLLECTED
 IN 2016. TRAFFIC PATTERN AND VOLUMES IN DOWNTOWN MIGHT
 HAVE CHANGED SIGNIFICANTLY SINCE THEN.
 - INCLUDE THE INTERSECTION ANALYSIS AT AUSTRALIAN
 AVENUE/CLEARWATER PLACE FOR THE FERN STREET EXTENSION
 SCENARIO.
 - PROVIDE WARRANT ANALYSIS FOR THE PROPOSED 4-WAY STOP
 AT ROSEMARY AVENUE/EVERNIA STREET PER GUIDANCE IN MUTCD
 - THE PROPOSED DEVELOPMENT RELIES HEAVILY ON FERN
 STREET, TAMARIND AVENUE, AND OKEECHOBEE BOULEVARD FOR
 VEHICULAR ACCESS TO THE SITE. 70% OF THE TRAFFIC IS
 ASSIGNED TO THE OKEECHOBEE BOULEVARD/TAMARIND AVENUE
 INTERSECTION, WHICH CURRENTLY OPERATES AT LOS E AND IS
 PROJECTED TO OPERATE AT LOS F WHEN BUILT-OUT. OVERALL
 INTERSECTION DELAY IS PROJECTED TO INCREASE BY 16% OVER
 THE BACKGROUND CONDITION DURING PM PEAK HOUR, BUT NO
 MITIGATION MEASURES ARE PROPOSED TO ADDRESS THE TRAFFIC
 ISSUES AT THIS INTERSECTION. PER CITY?S COMP PLAN,
 PLEASE IDENTIFY ADDITIONAL TRANSPORTATION SYSTEM
 MANAGEMENT (TSM) AND TRANSPORTATION DEMAND MANAGEMENT
 (TDM) MEASURES AS MITIGATION, OR PROVIDE PROPORTIONATE
 SHARE CONTRIBUTION TOWARDS CITY?S TSM, TDM OR
 MULTI-MODEL IMPROVEMENTS, INCLUDING:
 O CONTRIBUTE FUNDING TOWARDS FERN STREET EXTENSION
 O CONTRIBUTE FUNDING TOWARDS DOWNTOWN TROLLEY
 OPERATIONS
 O CONTRIBUTE FUNDING TOWARDS THE PROPOSED IMPROVEMENT
 AT OKEECHOBEE BOULEVARD/TAMARIND AVENUE IN THE CITY?S
 DRAFT DOWNTOWN MOBILITY PLAN
 O RECONSTRUCT BOTH SIDES OF ROSEMARY STREET TO SHARED
 STREET ALONG THE SOUTHERN HALF OF THE PROPERTY FRONTAGE
 TO BE CONSISTENT WITH THE CITY?S DRAFT DOWNTOWN
 MOBILITY PLAN
 O PROVIDE PARKING MANAGEMENT AND PRICING STRATEGIES TO
 DISCOURAGE VEHICULAR TRIPS
 O REQUIRE TENANTS TO PROVIDE SUBSIDIES TO TRANSIT
 PASSES FOR EMPLOYEES CONTINUOUSLY
 O PROVIDE CAR SHARING AND BIKE SHARING SERVICES
 O DEDICATE PARKING SPACES FOR CARPOOLS
 O OTHER TDM MEASURES AS APPROPRIATE
 THE EXACT AMOUNT OF CONTRIBUTION WILL BE DETERMINED
 WHEN THE TRIP GENERATION AND TRAFFIC ANALYSES ARE
 FINALIZED
 - SOME OF THE LOS AND DELAY RESULTS REPORTED IN TABLES
 3 AND 4 ARE NOT CONSISTENT WITH THE SYNCHRO RESULTS IN
 THE APPENDICES. REPORT HCM 2010 RESULTS INSTEAD OF
 SYNCHRO RESULTS, AND INCLUDE THE APPROPRIATE OUTPUTS IN
 THE APPENDICES. IN ADDITION, SOME OF THE INFORMATION
 REPRESENTED IN TABLES 3 AND 4 ARE MISLEADING, AND
 DETAILED REVIEW CANNOT BE COMPLETED UNTIL THE TABLES
 ARE CORRECTED. FOR EXAMPLE:
 O SIGNAL TIMING ASSUMED FOR THE AM PEAK HOUR BACKGROUND
 CONDITION AT OKEECHOBEE BOULEVARD/TAMARIND AVENUE IS
 UNREASONABLE. WB LEFT-TURN IS ASSIGNED 67 SECONDS OF
 SPLIT TIME FOR 78 VEHICLES PER HOUR. THIS HAS RESULTED
 IN VERY HIGH DELAY FOR OTHER MOVEMENTS, RESULTING IN
 THE BACKGROUND CONDITION BEING A LOT WORSE THAN THE
 TOTAL CONDITION.
 O THE REPORTED LOS AND DELAY FOR THE PM PEAK HOUR AT
 OKEECHOBEE BOULEVARD/TAMARIND AVENUE ARE NOT CONSISTENT
 WITH THE SYNCHRO OUTPUTS. TABLE 4 SHOWS THAT TOTAL
 CONDITION OPERATES BETTER THAN BACKGROUND CONDITION,
 BUT THE SYNCHRO OUTPUTS SHOW A 16% INCREASE IN DELAY IN
 THE TOTAL CONDITION OVER BACKGROUND CONDITION. ALSO,
 DELAY OF 92.6 SECONDS PER VEHICLE IS LOS F BUT NOT LOS
 E AS REPORTED IN TABLE 4.
 O THE LANE CONFIGURATIONS USED FOR THE TRAFFIC ANALYSIS
 AT OKEECHOBEE BOULEVARD/TAMARIND AVENUE ARE NOT
 CONSISTENT WITH EXISTING LANE CONFIGURATIONS.
 O 10-MINUTE DELAY AND 40-MINUTE DELAY ARE REPORTED FOR
 THE SB LEFT-TURN MOVEMENT AT OKEECHOBEE
 BOULEVARD/QUADRILLE BOULEVARD DURING AM AND PM PEAK
 HOUR EVEN UNDER EXISTING CONDITIONS. CLARIFY IF THIS IS
 REASONABLE.
 SITE PLAN COMMENTS (RECEIVED ON MARCH 13, 2018):
 - DIMENSION ALL DRIVEWAY WIDTHS
 - DIMENSION THE RIGHT-OF-WAY WIDTHS ON ALL FRONTAGE
 ROADWAYS
 - IN ADDITION TO SETBACKS FROM PROPERTY LINE, DIMENSION
 SETBACKS FROM CENTERLINE OF THE ROADWAY PER CITY CODE
 94-305(D) AND COMPREHENSIVE PLAN TRANSPORTATION ELEMENT
 APPENDIX A
 - CLARIFY WHERE THE EXISTING SKYBIKE STATION ON
 ROSEMARY AVENUE WOULD BE RELOCATED
 - PROVIDE SECURE BIKE RACKS AND/OR BIKE STORAGE PER
 CITY CODE 94-111(I)(1). THE PROPOSED BIKE RACKS ARE
 LOCATED ON THE SERVICE VEHICLE ALLEY WHICH IS GATED.
 PLEASE CLARIFY IF TENANTS ARE ABLE TO ACCESS THE BIKE
 RACKS.
 - PROVIDE SHOWER AND CHANGING FACILITIES AVAILABLE FOR
 ALL TENANTS PER CITY CODE 94-111(I)(1)
 - THE EXISTING LIVE OAK TREES ON ROSEMARY AVENUE DEFINE
 EACH PARKING SPACE WHICH HAS DIFFERENT PAVER PATTERN
 THAN THE SIDEWALK. REVISE THE HARDSCAPE FOR PARKING
 SPACES TO MATCH ROSEMARY AVENUE STREETSCAPE
 - PROVIDE TYPE III PAVER DETAILS WHICH IS MISSING FROM
 THE HARDSCAPE PLAN
 - SOME PLAN SHEETS SHOW THE EXISTING PARKING SPACES
 OUTSIDE THE PUBLIX BUILDING, WHILE SOME DO NOT. CLARIFY
 IF THE PROPOSED DEVELOPMENT WILL RECONSTRUCT THE WEST
 SIDE OF ROSEMARY AVENUE TO SHARED STREET MATCHING THE
 REST OF ROSEMARY AVENUE. IF NOT, PLEASE INCLUDE THIS IN
 THE RECONSTRUCTION.
 - IF THE 4-WAY STOP CONTROL IS PROPOSED AND WARRANTED
 AT ROSEMARY AVENUE/EVERNIA STREET, PLEASE PROVIDE
 PAVEMENT MARKING AND SIGNAGE AT THIS INTERSECTION.
 - THE AUTOTURN TRUCK PATHS ARE SHOWN TO TRACK OVER THE
 CONCRETE SIDEWALK ALONG THE ALLEY. PLEASE REVISE.
 - NARROW THE SERVICE VEHICLE EXIT. THE SERVICE VEHICLE
 EXIT IS WIDER THAN REQUIRED PER THE AUTOTURN TRUCK
 PATHS.
 - CLARIFY IF THE SERVICE VEHICLE ENTRANCE IS GATED MOST
 OF THE TIME, AND IF SO, CLARIFY HOW THE UTILITY SERVICE
 VEHICLES ARE ABLE TO ACCESS THE ALLEY WAY.
 - PROVIDE AUTOTURN TEMPLATE FOR UTILITY SERVICE
 VEHICLES ALONG THE ALLEY WAY INCLUDING THE 90-DEGREE
 TURN TO ADJACENT PROPERTIES.
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 04-11-2018 Cont ID  
Sent By aaponte Date 04-11-2018 Time 12:29 Rev Time 0.00
Received By aaponte Date 03-13-2018 Time 12:29 Sent To  
Notes
2018-04-11 12:32:57GENERAL COMMENTS
 1.PLEASE INSERT PROPOSED BUILDING IN THE CONTEXT
 (SURVEY WITH EXISTING AND UNDER CONSTRUCTION
 SURROUNDINGS) INCLUDE ALL THE ADJACENT STREETS AND
 BUILDINGS AND INCLUDE PROPOSED CHANGES ON CURB LINES.
 2. PLEASE PREPARE CONTEXT ELEVATIONS, IN COLOR.
 3. PLEASE CHECK THE DIMENSIONS OF ROSEMARY AVENUE
 INCLUDED IN THE SITE PLAN. TROLLEY DROP-OFF AREA SEEMS
 WIDER THAN TRAVEL LANES.
 4. INCLUDE THE LOCATION OF THE EXISTING CURB LINE IN
 SITE PLAN DRAWINGS TO INDICATE THE PROPOSED CHANGES
 FROM CURRENT SECTION.
 5. ROSEMARY STREET STREETSCAPE DESIGN SHALL MATCH THE
 STREETSCAPE DESIGN CURRENTLY IN PROGRESS, DETAILS STILL
 TO BE DETERMINED.
 6. FERN STREET STREETSCAPE SHALL MATCH THE DESIGN
 RECENTLY INSTALLED (BIO-SWALES WITH OAK TREES). THE
 PLANTING AREA WEST OF DRIVEWAY CAN BE EXPANDED TO MATCH
 THE BIO-SWALE ALIGNMENT.
 7. ANY EXISTING ON-STREET PARKING PROPOSED FOR REMOVAL
 WILL REQUIRE A PAYMENT OF REMOVAL FEE.
 8. EAST ELEVATION (GARAGE FACING SINGLE FAMILY HOUSE)
 SHALL BE ENHANCED TO MINIMIZE THE IMPACT OF THE BLANK
 WALL (POSSIBLE ARCHITECTURAL SCREEN AS PROPOSED ON
 OTHER NON-ACTIVE USE FACADES). THE EASTERN MOST WALL IS
 ALSO 21% EXCEEDING THE MAXIMUM ALLOWED FOR A BLANK
 WALL.
 9. EVERNIA STREET FA?ADE IS NOT IN COMPLIANCE WITH THE
 PLANAR BREAK REQUIREMENT. BREAK SHALL OCCUR FOR THE
 FULL HEIGHT OF THE PODIUM (PLANAR BREAK DEFINITION).
 10. SOUTH ELEVATION (SHEET A0.01.2) INDICATES SPANDREL
 GLASS ON GARAGE AREAS, BUT IT LOOKS LIKE ARCHITECTURAL
 SCREEN, PLEASE CLARIFY.
 11. SKYBIKE FACILITY REMOVED FROM ROW. PROJECT SHALL
 RELOCATE FACILITY ON-SITE.
 12. PLEASE INCLUDE EXACT AMOUNT OF TDRS NEEDED IN
 PROJECT DATE (SHEET A0.01).
 13. PLEASE INDICATE THE LOCATION OF THE SHOWERS AND
 CHANGING FACILITIES REQUIRED FOR THE TENANTS.
 14. WHAT IS THE TREATMENT PROPOSED AT THE GROUND FLOOR
 NON-ACTIVE FA?ADE ON EVERNIA STREET? ?PAINTED ALUMINUM
 PANEL?? WHY NOT SPANDREL GLASS?
 15. PLEASE CONFIRM THE NET INTERIOR AREA CALCULATION
 USED FOR PARKING UTILIZES THE DEFINITION OF NET
 INTERIOR AREA FROM THE DMP.
 16. ONLY 2 10 X 50 LOADING SPACES REQUIRED FOR THIS
 PROJECT.
 17. BIKE PARKING FOR TENANTS SHALL BE IN AN ENCLOSED
 SECURED AREA (38 SPACES).
 18. PLEASE INDICATE THE LOCATION OF REQUIRED PUBLIC
 BIKE PARKING 1/100 FEET OF STREET FRONTAGE (8 SPACES
 REQUIRED).
 19. PROJECT IS PROPOSING 606 PARKING SPACES, MORE THAN
 THE MINIMUM REQUIRED PARKING FOR THE PROJECT. STAFF IS
 SUGGESTING THE PARKING PROVIDED ON SITE BE REDUCED TO
 NO MORE THAN THE MINIMUM REQUIRED FOR THE PROJECT.
 20. BULB OUT ON THE EAST SIDE OF ROSEMARY AVENUE AND
 FERN STREET SHALL BE MODIFIED TO FULLY ACCOMMODATE THE
 BIKE LANE UP TO THE INTERSECTION.
 21. PLEASE ENSURE THE RENDERINGS PRESENTED ARE FULLY
 ACCURATE WITH THE CONTEXT AND PROPOSED MATERIALS AND
 LANDSCAPE.
 22. STREET LIGHT FIXTURE SPECIFIED IS NOT CONSISTENT
 WITH DOWNTOWN LIGHT FIXTURE STANDARD. LIGHT FIXTURES
 ALONG FERN STREET AND EVERNIA STREET SHALL FOLLOW DMP
 STANDARD. ROSEMARY FIXTURE WILL BE DETERMINED BY THE
 CURRENT STREETSCAPE REDESIGN PROJECT.
 23. PROPOSED PAVERS ON SIDEWALK SHALL MATCH ROSEMARY
 AVENUE.
 24. PLEASE INDICATE ANY SEATING ON PRIVATE OPEN SPACE
 AREAS.
 25. SEATING AREAS ON PUBLIC OPEN SPACE SHALL BE OF
 HIGHER FINISH AND INCLUDE ELEMENTS TO DETER
 SKATEBOARDERS.
 26. ADDITIONAL BASE PLANTING IS SUGGESTED ALONG
 BUILDING FA?ADE FOR AT LEAST SOME PORTIONS OF THE
 PUBLIC OPEN SPACE EDGE.
 27. PLEASE INDICATE THAT THE EXPOSED PARKING DECK WILL
 INCLUDE A FULL PAINTED APPLICATION BY AN ARTIST.
 ADDITIONAL INFORMATION:
 - THE PROJECT IS REQUIRED TO OBTAIN APPROVAL FROM THE
 DAC FOR SPECIAL REVIEW AND TDR TRANSFER. PLEASE FOLLOW
 DAC SUBMITTAL DEADLINES.
  
  