Plan Review Details - Project Z18020023
Plan Review Stops For Project Z18020023
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-13-2018 Cont ID  
Sent By rbrown Date 03-13-2018 Time 20:01 Rev Time 0.00
Received By rbrown Date 03-13-2018 Time 20:01 Sent To  
Notes
2018-03-13 20:09:08DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. ACCORDING TO THE ADOPTED FLOOD INSURANCE RATE MAPS
 (FIRMS), THE PROPOSED BUILDING IS IN FLOOD ZONE. THE
 FIRST FLOOR OF THE BUILDING AND ALL ASSOCIATED
 MECHANICAL EQUIPMENT (CHILLERS, GENERATORS ETC.) SHALL
 BE 24 INCHES (FREEBOARD) ABOVE THE BASE FLOOD
 ELEVATION.
  
 3. VAN ACCESSIBLE PARKING SPACES. THREE VAN ACCESSIBLE
 PARKING SPACES ARE REQUIRED BUT THE PLANS DO NOT
 CURRENTLY SHOW VAN ACCESSIBLE PARKING SPACES. IF THE
 THREE FIRST FLOOR ACCESSIBLE PARKING SPACES ARE TO BE
 VAN ACCESSIBLE THE PLANS SHOULD BE ANNOTATED TO SHOW
 THAT. PER SECTION 208.2.4 OF FLORIDA ACCESSIBILITY
 CODE, ONE IN EVERY SIX ACCESSIBLE SPACES (AT LEAST ONE)
 IN A PARKING STRUCTURE, SHALL BE ?VAN ACCESSIBLE? AND
 DESIGNED IN ACCORDANCE WITH SECTION OF 502 OF FLORIDA
 ACCESSIBILITY CODE (VERTICAL CLEARANCE NOT LESS THAN 98
 INCHES AT SPACE AND VEHICULAR ACCESS ROUTE)
  
 4. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 5. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 6. ENCLOSED PARKING GARAGES. IF THE PARKING GARAGE DOES
 NOT HAVE SUFFICIENT WALL OPENINGS TO MEET THE
 DEFINITION OF AN OPEN PARKING GARAGE, IT WILL BE
 CONSIDERED AN ENCLOSED PARKING GARAGE AND MUST HAVE
 EXHAUST SYSTEMS. THE EXHAUST SYSTEMS SHALL BE DESIGNED
 TO MINIMIZE NOISE LEVELS USING INLINE FAN SILENCERS OR
 OTHER APPROVED METHODS.
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 8. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 9. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-14-2018 Cont ID  
Sent By mgonzale Date 03-14-2018 Time   Rev Time 1.00
Received By mgonzale Date 03-14-2018 Time   Sent To  
Notes
2018-03-14 12:47:06#1 PROVIDE ESTIMATED FLOWS GPD FOR EACH BUILDING.
  
 #2 BACKFLOW (RPPA AND DCDA) LOCATIONS MUST BE PRE
 APPROVED BY FIRE AND UTILITY CUSTOMER SERVICE FOR EACH
 BUILDING.
  
 #3 PROVIDE TIMELINE AS TO WATERMAIN UPGRADE TO 12" WM.
  
 #4 PROVIDE PRELIMINARY SUMMARY AS TO THE EXISTING SEWER
 CAPACITY WITH CITY OF WPB PUBLIC UTILTIES.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 04-25-2018 Cont ID  
Sent By pleduc Date 04-25-2018 Time   Rev Time 0.00
Received By pleduc Date 04-25-2018 Time 10:11 Sent To  
Notes
2018-04-25 10:14:052ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC INFORMATION PACKET AND
 RESPONSE LETTER DATED MARCH30, 2018, FROM JOSHUA I.
 LONG, AICP, GUNSTER, YOAKLEY & STEWART, TO JOHN P.
 ROACH, AICP, PRINCIPLE PLANNER, THE PREVIOUSLY
 SUBMITTED FIRE PREVENTION BUREAU COMMENTS HAVE BEEN
 ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
 2ND REVIEW RESPONSE
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-09-2018 Cont ID  
Sent By pleduc Date 03-09-2018 Time 09:24 Rev Time 0.00
Received By pleduc Date 03-09-2018 Time 09:05 Sent To  
Notes
2018-03-09 09:24:16THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL PARKING STRUCTURES SHALL COMPLY WITH NFPA 88A,
 PARKING STRUCTURES AND NFPA 101, THE LIFE SAFETY CODE,
 INCLUDING MORE SPECIFICALLY, CHAPTER 42 STORAGE
 OCCUPANCIES (PARKING STRUCTURES)
  
 7. A NFPA 13 COMPLAINT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR THIS
 STRUCTURE. TEMPORARY STANDPIPES ARE REQUIRED WHEN THE
 BUILDING REACHES THREE LEVELS OR THIRTY FEET WHILE
 BEING CONSTRUCTED.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 HIGH RISES SHALL HAVE TWO SEPARATE SOURCES OF WATER
 SUPPLY FEEDING THE FIRE PUMP.
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 18.3 WATER SUPPLIES.
 18.3.1* AN APPROVED WATER SUPPLY CAPABLE OF SUPPLYING
 THE REQUIRED FIRE FLOW FOR FIRE PROTECTION SHALL BE
 PROVIDED TO ALL PREMISES UPON WHICH FACILITIES,
 BUILDINGS, OR PORTIONS OF BUILDINGS ARE HEREAFTER
 CONSTRUCTED OR MOVED INTO THE JURISDICTION. THE
 APPROVED WATER SUPPLY SHALL BE IN ACCORDANCE WITH
 SECTION 18.4.
  
 PER NFPA 14 SECTION 7.12.2, HIGH-RISE BUILDINGS SHALL
 HAVE AT LEAST TWO REMOTELY LOCATED FIRE DEPARTMENT
 CONNECTIONS FOR EACH ZONE.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE
 PRIMARY AND SECONDARY POWER SOURCES?
  
 TWO FIRE PUMP ROOMS ARE INDICATED, WITH EACH HAVING
 THEIR OWN DOOR ACCESS. HOWEVER, ONE DOOR IS FACING THE
 ROADWAY AND THE OTHER FACING THE INSIDE OF THE PARKING
 GARAGE. CAN WE HAVE THEM FACE THE SAME DIRECTION, THE
 OUTSIDE?
  
 8. A CLASS ?A? NFPA 72 COMPLIANT MONITORED FIRE ALARM
 SYSTEM IS REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP
 DRAWINGS, ARE REQUIRED TO BE SUBMITTED, REVIEWED AND
 APPROVED BY THE FIRE PREVENTION BUREAU PRIOR TO ANY
 INSTALLATION.
  
 9. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 PLEASE REVIEW THE EXITING OFF OF THE ROOF DECK POOL
 AREA TO ENSURE IT COMPLIES WITH THE ONE EXIT
 REQUIRMENTS.
  
 11. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 12. COMMAND ROOM
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 A. SHALL BE A MINIMUM OF 200 FT SQUARED WITH A MINIMUM
 DIMENSION OF 10 FT.
 B. THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 C. A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 D. SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS AND THE LOCATION
 OF FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS
 E. A WORK TABLE.
 F. IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 G. THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 H. ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION OF
 THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 I. STATUS INDICATORS AND CONTROLS FOR AIR DISTRIBUTION
 SYSTEMS.
 J. CONTROLS FOR UNLOCKING STAIRWAY DOORS SIMULTANEOUSLY
 K. SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 L. EMERGENCY AND STANDBY POWER STATUS INDICATORS
 M. FIRE PUMP STATUS INDICATORS
 N. GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 O. PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 P. CONTROLS REQUIRED FOR SMOKE CONTROL
 Q. ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1.
 R. ELEVATOR EMERGENCY OR STANDBY POWER SELECTOR
 SWITCH(ES), WHERE EMERGENCY OR STANDBY POWER IS
 PROVIDED
  
 13. RADIO
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
  
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
  
 NFPA 72, 24.5.2* TWO-WAY RADIO COMMUNICATIONS
 ENHANCEMENT SYSTEMS.
  
 24.5.2.2 RADIO COVERAGE. RADIO COVERAGE SHALL BE
 PROVIDED THROUGHOUT THE BUILDING AS A PERCENTAGE OF
 FLOOR AREA AS SPECIFIED IN 24.5.2.2.1 THROUGH
 24.5.2.2.3.
 24.5.2.2.1 CRITICAL AREAS. CRITICAL AREAS, SUCH AS THE
 EMERGENCY COMMAND CENTER(S), THE FIRE PUMP ROOM(S),
 EXIT STAIRS, EXIT PASSAGEWAYS, ELEVATOR LOBBIES,
 STANDPIPE CABINETS, SPRINKLER SECTIONAL VALVE
 LOCATIONS, AND OTHER AREAS DEEMED CRITICAL BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED WITH
 99 PERCENT FLOOR AREA RADIO COVERAGE.
 24.5.2.2.2 GENERAL BUILDING AREAS. GENERAL BUILDING
 AREAS SHALL BE PROVIDED WITH 90 PERCENT FLOOR AREA
 RADIO COVERAGE.
 24.5.2.3 SIGNAL STRENGTH.
 24.5.2.3.1 INBOUND. A MINIMUM INBOUND SIGNAL STRENGTH
 OF -95 DBM, OR OTHER SIGNAL STRENGTH AS REQUIRED BY THE
 AUTHORITY HAVING JURISDICTION, SHALL BE PROVIDED
 THROUGHOUT THE COVERAGE AREA.
 24.5.2.3.2 OUTBOUND. A MINIMUM OUTBOUND SIGNAL STRENGTH
 OF -95 DBM AT THE DONOR SITE, OR OTHER SIGNAL STRENGTH
 AS REQUIRED BY THE AUTHORITY HAVING JURISDICTION, SHALL
 BE PROVIDED FROM THE COVERAGE AREA.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE RESCUE. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
  
 14. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 15. THE SMOKE CONTROL SYSTEM SHALL COMPLY WITH NFPA
 101, CHAPTER 9, BUILDING SERVICE AND FIRE PROTECTION
 EQUIPMENT, INCLUDING:
  
 THE SMOKE CONTROL SYSTEMS SHALL BE INSTALLED,
 INSPECTED, TESTED, AND MAINTAINED IN ACCORDANCE WITH
 NFPA 92, STANDARD FOR SMOKE CONTROL SYSTEMS; NFPA 204,
 STANDARD FOR SMOKE AND HEAT VENTING; OR NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES, AS APPROVED BY THE AUTHORITY
 HAVING JURISDICTION.
  
 THE ENGINEER OF RECORD SHALL CLEARLY IDENTIFY THE
 INTENT OF THE SYSTEM, THE DESIGN METHOD USED, THE
 APPROPRIATENESS OF THE METHOD USED, AND THE REQUIRED
 MEANS OF INSPECTING, TESTING, AND MAINTAINING THE
 SYSTEM.
  
 ACCEPTANCE TESTING SHALL BE PERFORMED BY A SPECIAL
 INSPECTOR IN ACCORDANCE WITH SECTION 9.9.
  
 16. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 17. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 08-10-2020 Cont ID  
Sent By rcaranci Date 08-10-2020 Time 14:33 Rev Time 0.00
Received By rcaranci Date 08-10-2020 Time 14:33 Sent To  
Notes
2020-08-10 14:34:06FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: THE MARINA CMPD Z18020023
 AUGUST 7, 2020
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 LANDSCAPE PERMIT 18110731:
  
  
 1. SATISFIED. SUBMIT THE TREE DISPOSITION PLAN AND
 CHART AND THE LANDSCAPE PLANS FOR REVIEW WITH THE MINOR
 AMENDMENT.
  
 2. SATISFIED. PROVIDE THE ARBORIST REPORT ON THE
 CHANGES FROM RELOCATE TO REMOVAL AS DISCUSSED.
  
  
 3. SATISFIED. UPDATE THE TREE DISPOSITION PLAN SHOWING
 THE CHANGES PROPOSED CLOUDED, AND FILL ALL TO MEET
 CURRENT CODE REQUIREMENTS FOR MITIGATION OF 1:1
 REPLACEMENT FOR TREE CANOPY BELOW 20 FEET DIAMETER, AND
 SQUARE FOOTAGE FOR TREES 20 FEET OR MORE IN DIAMETER.
  
 4. SATISFIED. PROVIDE A MITIGATION CHART SHOWING THE
 APPROVED MITIGATION QUANTITY AND THE TREE MITIGATION
 PROVIDED WITH THE PROPOSED LANDSCAPE PLAN.
  
  
 5. SATISFIED. CORRECT THE NARRATIVE TO REFLECT THAT
 THERE ARE MORE CHANGES PROPOSED TO THE TREE DISPOSITION
 PLAN THAN JUST THE SABAL PALMS.
  
 6. SATISFIED. PROVIDE A LIST OF ANY CHANGES TO THE
 LANDSCAPE PLAN AND CLOUD THEM.
  
  
 7. SATISFIED. SEAGRAPE 76301 AND 76351 ARE PROPOSED TO
 BE REMOVED AND MUST BE INCLUDED IN MITIGATION DUE, ALL
 TREES PROPOSED TO BE REMOVED MUST BE MITIGATED. 76270
 NEEDS CANOPY DIAMETER.
  
 MINOR AMENDMENT:
  
 1. SATISFIED. PLEASE UPDATE THE TREE DISPOSITION PLAN
 SHOWING THE CHANGES PROPOSED WITH THIS PETITION
 BUBBLED, AND AMEND TO MEET CURRENT CODE REQUIREMENTS
 FOR MITIGATION OF 1:1 REPLACEMENT FOR TREE CANOPY BELOW
 20 FEET DIAMETER, AND SQUARE FOOTAGE FOR TREES 20 FEET
 OR MORE IN DIAMETER.
  
 2. SATISFIED. PLEASE PROVIDE A MITIGATION CHART
 SHOWING THE APPROVED MITIGATION QUANTITY AND THE TREE
 MITIGATION PROVIDED WITH THE PROPOSED LANDSCAPE PLAN
 WITH THIS PETITION.
  
 3. SATISFIED. PLEASE SHOW THE OPEN SPACE PERCENTAGE AND
 LANDSCAPE AREA PERCENTAGE FOR PBA#1, #2 AND #3, AND
 SHOW COMPARISON TO WHAT IS CURRENTLY APPROVED.
  
 4. SATISFIED. THE LANDSCAPE PLAN FOR THE FRONTAGE ROAD
 DOES NOT MEET THE DESIGN GUIDELINES CROSS SECTION 6
 UNDER VII C. FRONTAGE ROAD. PLEASE REVISE.
  
 5. SATISFIED. PLEASE PROVIDE REQUIRED SHADE TREE,
 FLOWERING TREE AND SHRUB QUANTITIES FOR THE SITE PER
 CURRENT CODE SECTION 94-442 (B)(2). ADJUST SUBSTITUTION
 OF PALMS TO CURRENT CODE REQUIREMENT OF 3:1 FOR COCONUT
 PALMS FOR REQUIRED TREES, UNLESS AN EXCEPTION PER THE
 DESIGN GUIDELINES.
  
 6. SATISFIED. PLEASE UPDATE THE FLORIDA FRIENDLY
 REQUIREMENTS CHART TO CURRENT CODE AND PROVIDE 40
 POINTS AS REQUIRED.
  
 7. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 INDIVIDUAL LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN, AND
 SHOW COMPLIANCE WITH BUFFER REQUIREMENTS OF SECTION XI-
 D. OF THE DESIGN GUIDELINES. SHOW CALCULATIONS FOR EACH
 BUFFER AND INCLUDE ANY APPLICATION OF PALM SUBSTITUTION
 PER XII G.
  
 8. SATISFIED. PLEASE PROVIDE THE LIST OF SHRUBS BY
 SPECIES, QUANTITY AND SIZE. INCLUDE DROUGHT TOLERANCE
 LEVEL FOR EACH PLANT SPECIES ON THE PLANT LIST AND IF
 NATIVE.
  
 9. SATISFIED. PLEASE PROVIDE THE CALCULATION FOR PBA #2
 AND PBA #3 SEPARATELY FOR XII E. FOUNDATION PLANTING.
  
 10. SATISFIED. THE PROMENADE IS VERY PLAIN. PLEASE
 REVISE THE PLAN TO INCORPORATE MORE INTEREST PER THE
 DESIGN GUIDELINES SUCH AS A MEANDERING WALKWAY WITH
 LANDSCAPING AND RESTING SPACES INTERACTING WITH THE
 WALKWAY.
  
 11. SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW
 PREVENTERS ARE NOT CLEARLY SHOWN IN FINAL LOCATIONS.
  
 12. SATISFIED. PLEASE SHOW LOCATIONS OF ALL WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLANS AND
 RESOLVE ANY CONFLICTS WITH LANDSCAPING.
  
 13. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS
 TO PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS.
 THIS INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND
 CURBS, AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED
 BY TREE ROOTS.
 COMMENTS 11, 12, AND 13. THERE ARE MULTIPLE CONFLICTS
 WITH TREES AND NEW UTILITIES, AND MANY TREES HAVE BEEN
 REMOVED FROM THE PLAN ALONG THE CENTER BUFFER OF THE
 FRONTAGE ROAD TO ACCOMMODATE UTILITY VALVES REDUCING
 THE BUFFERING INTENDED IN THE DESIGN GUIDELINES. THERE
 ARE MULTIPLE TREES THAT DO NOT HAVE ADEQUATE SPACING OR
 ROOT BARRIER TO PROTECT UTILITIES. THE ROOT BARRIER
 PLAN L1-120 AND DETAILS L5-110 ARE FOR SIDEWALKS ONLY,
 NOT UTILITIES.
  
 ADDITIONAL COMMENTS 4/26/18:
 14. SATISFIED. THE ADJUSTMENT TO THE DESIGN GUIDELINES
 REDUCING THE REQUIRED ADDITIONAL TREES PER UNIT FROM
 THE CODE REQUIREMENT MAY NOT BE SUPPORTED BY STAFF.
 SUPPLEMENT 33 TO THE ZLDR?S SECTION 94-443(D) APPROVED
 THROUGH ORDINANCE 4493-13 REQUIRES ONE ADDITIONAL TREE
 PER DWELLING UNIT. THE APPLICANT IS PROPOSING ONE
 ADDITIONAL TREE PER 4 UNITS RESULTING IN 300 LESS TREES
 THAN REQUIRED BY CODE, SO REQUIRES A WAIVER REQUEST.
 THIS WOULD AFFECT ALL FUTURE PBA?S WITH MULTIPLE
 RESIDENTIAL UNITS.
 ADDITIONAL COMMENTS 8/10/20:
 15. SUBMIT THE ARBORIST REPORT ON THE CHANGES FROM
 RELOCATE TO REMOVAL AS DISCUSSED.
  
 16. SUBMIT CLOUDED COPIES OF THE LANDSCAPE PLANS
 MATCHING THE PERMIT SUBMITTALS.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 PROPERTY. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-26-2018 Cont ID  
Sent By rcaranci Date 04-26-2018 Time 15:43 Rev Time 0.00
Received By rcaranci Date 04-26-2018 Time 15:43 Sent To  
Notes
2018-04-26 15:44:55FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: THE MARINA CMPD Z18020023
 APRIL 26, 2018
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE UPDATE THE TREE DISPOSITION PLAN
 SHOWING THE CHANGES PROPOSED WITH THIS PETITION
 BUBBLED, AND AMEND TO MEET CURRENT CODE REQUIREMENTS
 FOR MITIGATION OF 1:1 REPLACEMENT FOR TREE CANOPY BELOW
 20 FEET DIAMETER, AND SQUARE FOOTAGE FOR TREES 20 FEET
 OR MORE IN DIAMETER.
  
 2. SATISFIED. PLEASE PROVIDE A MITIGATION CHART
 SHOWING THE APPROVED MITIGATION QUANTITY AND THE TREE
 MITIGATION PROVIDED WITH THE PROPOSED LANDSCAPE PLAN
 WITH THIS PETITION.
  
 3. SATISFIED. PLEASE SHOW THE OPEN SPACE PERCENTAGE AND
 LANDSCAPE AREA PERCENTAGE FOR PBA#1, #2 AND #3, AND
 SHOW COMPARISON TO WHAT IS CURRENTLY APPROVED.
  
 4. SATISFIED. THE LANDSCAPE PLAN FOR THE FRONTAGE ROAD
 DOES NOT MEET THE DESIGN GUIDELINES CROSS SECTION 6
 UNDER VII C. FRONTAGE ROAD. PLEASE REVISE.
  
 5. SATISFIED. PLEASE PROVIDE REQUIRED SHADE TREE,
 FLOWERING TREE AND SHRUB QUANTITIES FOR THE SITE PER
 CURRENT CODE SECTION 94-442 (B)(2). ADJUST SUBSTITUTION
 OF PALMS TO CURRENT CODE REQUIREMENT OF 3:1 FOR COCONUT
 PALMS FOR REQUIRED TREES, UNLESS AN EXCEPTION PER THE
 DESIGN GUIDELINES.
  
 6. SATISFIED. PLEASE UPDATE THE FLORIDA FRIENDLY
 REQUIREMENTS CHART TO CURRENT CODE AND PROVIDE 40
 POINTS AS REQUIRED.
  
 7. SATISFIED. PLEASE INDICATE THE WIDTH OF ALL
 INDIVIDUAL LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN, AND
 SHOW COMPLIANCE WITH BUFFER REQUIREMENTS OF SECTION XI-
 D. OF THE DESIGN GUIDELINES. SHOW CALCULATIONS FOR EACH
 BUFFER AND INCLUDE ANY APPLICATION OF PALM SUBSTITUTION
 PER XII G.
  
 8. SATISFIED. PLEASE PROVIDE THE LIST OF SHRUBS BY
 SPECIES, QUANTITY AND SIZE. INCLUDE DROUGHT TOLERANCE
 LEVEL FOR EACH PLANT SPECIES ON THE PLANT LIST AND IF
 NATIVE.
  
 9. SATISFIED. PLEASE PROVIDE THE CALCULATION FOR PBA #2
 AND PBA #3 SEPARATELY FOR XII E. FOUNDATION PLANTING.
  
 10. SATISFIED. THE PROMENADE IS VERY PLAIN. PLEASE
 REVISE THE PLAN TO INCORPORATE MORE INTEREST PER THE
 DESIGN GUIDELINES SUCH AS A MEANDERING WALKWAY WITH
 LANDSCAPING AND RESTING SPACES INTERACTING WITH THE
 WALKWAY.
  
 11. NOT SATISFIED. PLEASE SHOW LOCATIONS OF ALL GROUND
 MOUNTED EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C
 UNITS, ETC., AND PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW
 PREVENTERS ARE NOT CLEARLY SHOWN IN FINAL LOCATIONS.
  
 12. NOT SATISFIED. PLEASE SHOW LOCATIONS OF ALL WATER,
 SEWER AND DRAINAGE LINES ON THE LANDSCAPE PLANS AND
 RESOLVE ANY CONFLICTS WITH LANDSCAPING.
  
 13. NOT SATISFIED. PLEASE SHOW LOCATIONS OF ROOT
 BARRIERS TO PROTECT INFRASTRUCTURE AND TREES FROM
 CONFLICTS. THIS INCLUDES WATER, SEWER, DRAINAGE,
 SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT
 COULD BE IMPACTED BY TREE ROOTS.
  
 COMMENTS 11, 12, AND 13. THERE ARE MULTIPLE CONFLICTS
 WITH TREES AND NEW UTILITIES, AND MANY TREES HAVE BEEN
 REMOVED FROM THE PLAN ALONG THE CENTER BUFFER OF THE
 FRONTAGE ROAD TO ACCOMMODATE UTILITY VALVES REDUCING
 THE BUFFERING INTENDED IN THE DESIGN GUIDELINES. THERE
 ARE MULTIPLE TREES THAT DO NOT HAVE ADEQUATE SPACING OR
 ROOT BARRIER TO PROTECT UTILITIES. THE ROOT BARRIER
 PLAN L1-120 AND DETAILS L5-110 ARE FOR SIDEWALKS ONLY,
 NOT UTILITIES.
  
 ADDITIONAL COMMENTS 4/26/18:
 14. THE ADJUSTMENT TO THE DESIGN GUIDELINES REDUCING
 THE REQUIRED ADDITIONAL TREES PER UNIT FROM THE CODE
 REQUIREMENT MAY NOT BE SUPPORTED BY STAFF. SUPPLEMENT
 33 TO THE ZLDR?S SECTION 94-443(D) APPROVED THROUGH
 ORDINANCE 4493-13 REQUIRES ONE ADDITIONAL TREE PER
 DWELLING UNIT. THE APPLICANT IS PROPOSING ONE
 ADDITIONAL TREE PER 4 UNITS RESULTING IN 300 LESS TREES
 THAN REQUIRED BY CODE, SO REQUIRES A WAIVER REQUEST.
 THIS WOULD AFFECT ALL FUTURE PBA?S WITH MULTIPLE
 RESIDENTIAL UNITS.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 PROPERTY. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-13-2018 Cont ID  
Sent By rcaranci Date 03-13-2018 Time 16:34 Rev Time 0.00
Received By rcaranci Date 03-13-2018 Time 16:34 Sent To  
Notes
2018-03-13 16:34:57FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: THE MARINA CMPD Z18020023
 MARCH 13, 2018
  
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE UPDATE THE TREE DISPOSITION PLAN SHOWING THE
 CHANGES PROPOSED WITH THIS PETITION BUBBLED, AND AMEND
 TO MEET CURRENT CODE REQUIREMENTS FOR MITIGATION OF 1:1
 REPLACEMENT FOR TREE CANOPY BELOW 20 FEET DIAMETER, AND
 SQUARE FOOTAGE FOR TREES 20 FEET OR MORE IN DIAMETER.
  
 2. PLEASE PROVIDE A MITIGATION CHART SHOWING THE
 APPROVED MITIGATION QUANTITY AND THE TREE MITIGATION
 PROVIDED WITH THE PROPOSED LANDSCAPE PLAN WITH THIS
 PETITION.
  
 3. PLEASE SHOW THE OPEN SPACE PERCENTAGE AND LANDSCAPE
 AREA PERCENTAGE FOR PBA#1, #2 AND #3, AND SHOW
 COMPARISON TO WHAT IS CURRENTLY APPROVED.
  
 4. THE LANDSCAPE PLAN FOR THE FRONTAGE ROAD DOES NOT
 MEET THE DESIGN GUIDELINES CROSS SECTION 6 UNDER VII C.
 FRONTAGE ROAD. PLEASE REVISE.
  
 5. PLEASE PROVIDE REQUIRED SHADE TREE, FLOWERING TREE
 AND SHRUB QUANTITIES FOR THE SITE PER CURRENT CODE
 SECTION 94-442 (B)(2). ADJUST SUBSTITUTION OF PALMS TO
 CURRENT CODE REQUIREMENT OF 3:1 FOR COCONUT PALMS FOR
 REQUIRED TREES, UNLESS AN EXCEPTION PER THE DESIGN
 GUIDELINES.
  
 6. PLEASE UPDATE THE FLORIDA FRIENDLY REQUIREMENTS
 CHART TO CURRENT CODE AND PROVIDE 40 POINTS AS
 REQUIRED.
  
 7. PLEASE INDICATE THE WIDTH OF ALL INDIVIDUAL
 LANDSCAPE BUFFERS ON THE LANDSCAPE PLAN, AND SHOW
 COMPLIANCE WITH BUFFER REQUIREMENTS OF SECTION XI- D.
 OF THE DESIGN GUIDELINES. SHOW CALCULATIONS FOR EACH
 BUFFER AND INCLUDE ANY APPLICATION OF PALM SUBSTITUTION
 PER XII G.
  
 8. PLEASE PROVIDE THE LIST OF SHRUBS BY SPECIES,
 QUANTITY AND SIZE. INCLUDE DROUGHT TOLERANCE LEVEL FOR
 EACH PLANT SPECIES ON THE PLANT LIST AND IF NATIVE.
  
 9. PLEASE PROVIDE THE CALCULATION FOR PBA #2 AND PBA #3
 SEPARATELY FOR XII E. FOUNDATION PLANTING.
  
 10. THE PROMENADE IS VERY PLAIN. PLEASE REVISE THE PLAN
 TO INCORPORATE MORE INTEREST PER THE DESIGN GUIDELINES
 SUCH AS A MEANDERING WALKWAY WITH LANDSCAPING AND
 RESTING SPACES INTERACTING WITH THE WALKWAY.
  
 11. PLEASE SHOW LOCATIONS OF ALL GROUND MOUNTED
 EQUIPMENT INCLUDING FPL TRANSFORMERS, A/C UNITS, ETC.,
 AND PROVIDE SCREENING FOR ALL GROUND MOUNTED EQUIPMENT
 AND UTILITIES. WATER BACKFLOW PREVENTERS ARE NOT
 CLEARLY SHOWN IN FINAL LOCATIONS.
  
 12. PLEASE SHOW LOCATIONS OF ALL WATER, SEWER AND
 DRAINAGE LINES ON THE LANDSCAPE PLANS AND RESOLVE ANY
 CONFLICTS WITH LANDSCAPING.
  
 13. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 2. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE PERMITTING AND INSTALLATION OF THE
 STREET TREES AND RIGHT OF WAY LANDSCAPING AND
 IRRIGATION APPROVED WITH THIS PETITION.
  
 3. THE APPLICANT, SUCCESSORS AND ASSIGNS SHALL BE
 RESPONSIBLE FOR THE MAINTENANCE OF THE ROAD RIGHT OF
 WAY LANDSCAPING AND IRRIGATION ADJACENT TO THE
 PROPERTY. THIS WILL BE THROUGH A SEPARATE MAINTENANCE
 AGREEMENT WITH THE CITY.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-14 07:11:28BASED ON THE PRINTS IT SHOWS THAT A ROLL OFF COMPACTOR
 SERVICE IS BEING PROPOSED. THE ONLY STIPULATION IS THAT
 THE SERVICE MUST BE FROM ONE OF THE APPROVED FRANCHISE
 ROLL OFF HAULERS.

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-09 13:41:45SEE COMMENTS PROVIDED ON PROJECT Z18020021.
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date 04-25-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-04-25 10:31:05Z18020021 & Z18020023 THE MARINA CMPD
 1ST RESUBMITTAL
  
 TRAFFIC STATEMENT (DATED MARCH 29, 2018) COMMENTS:
  
 - THE TRIP GENERATION CALCULATION APPEARS TO BE CORRECT
 BUT THE RATES INCLUDED IN THE TRAFFIC STATEMENT ARE
 NOT. PER PALM BEACH COUNTY?S TRIP GENERATION RATE
 INFORMATION, DAILY RATE SHOULD BE 152.03 TRIPS PER
 1,000 S.F., AND PM RATE SHOULD BE 12.81 TRIPS PER 1,000
 S.F. FOR 10,000 S.F. OR LESS. RETAIL PASS-BY % SHOULD
 BE 62% FOR 10,000 S.F. OR LESS.
 - INCLUDE DAILY PASS-BY TRIPS AS DAILY DRIVEWAY VOLUMES
 SHOWN IN FIGURE 1. THE DAILY DRIVEWAY VOLUMES SUM UP TO
 THE NET PROPOSED TRIPS ONLY BUT NOT THE TOTAL DRIVEWAY
 VOLUMES SHOWN IN TABLE 2.
 - PROVIDE FINAL SIGNED AND SEALED TRAFFIC STATEMENT.
  
 SITE PLAN (RECEIVED ON APRIL 18, 2018) COMMENTS:
  
 - PURSUANT TO RESOLUTION NO. 20-14, INCLUDE IN THE
 APPLICATION THE STREETSCAPE DESIGN, INCLUDING BUT NOT
 LIMITED TO LANDSCAPING AND SIDEWALKS/BIKE PATHS, ON THE
 EAST AND WEST SIDE OF NORTH FLAGLER DRIVE. PLEASE
 COORDINATE WITH ENGINEERING ON THE STREETSCAPE DESIGN.
 THE STREETSCAPE IMPROVEMENT SHOULD BE INSTALLED PRIOR
 TO THE ISSUANCE OF THE FIRST CERTIFICATE OF OCCUPANCY
 FOR THE PROPOSED PBA DEVELOPMENT. THIS COMMENT WAS
 ACKNOWLEDGED IN THE RESPONSE BUT NO STREETSCAPE DESIGN
 IS PROVIDED FOR THE EAST AND WEST SIDES OF NORTH
 FLAGLER DRIVE.
 - SWAP THE LOCATIONS OF THE TURNAROUND AREA AND THE
 LAST PARKING SPACE PRIOR TO THE RESIDENTIAL ACCESS
 GATE.
 - SOME OF THE DIMENSIONS IN THE CIVIL PLAN ARE
 DIFFERENT THAN THE SITE PLAN, AND THE SIDEWALK DESIGN
 IS SLIGHTLY DIFFERENT BETWEEN THE TWO SETS OF PLANS.
 FOR EXAMPLE, IN SHEETS A1.01 AND C4.00, THE DROP OFF
 AREAS TO THE NORTH AND SOUTH OF THE BUILDING ARE
 INDICATED WITH WIDTHS OF 19?-9? AND 18? RESPECTIVELY IN
 THE SITE PLAN, BUT IS SHOWN AS 18? AND 20? RESPECTIVELY
 IN THE CIVIL PLAN; AND THE INTERNAL ROADWAY WIDTH TO
 THE SOUTH OF THE PROPERTY IS SHOWN AS 25?-2? IN THE
 SITE PLAN BUT IS SHOWN AS 24? IN THE CIVIL PLAN. PLEASE
 REVISE.
 - THE INTERNAL ROADWAY COULD BE REDUCED TO 24? WIDE AND
 THE DROP OFF AREA COULD BE REDUCED TO 18? WIDE TO
 MAXIMIZE THE SIDEWALK WIDTH, WHICH COULD ALLOW A
 MINIMUM OF 6? SIDEWALKS AND PREFERABLY 8? TO 10?
 SIDEWALKS BE PROVIDED. ALSO, INCREASE THE WIDTH OF THE
 SIDEWALKS/PEDESTRIAN PATHWAYS WHICH RUN DIAGONALLY
 ALONG THE SOUTH SIDE OF THE PROPERTY.
 - PROVIDE FINAL SIGNED AND SEALED CIVIL PLAN.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-13 17:30:42Z18020021 & Z18020023
 PPRC MEETING 2018-03-14
  
 THE MARINA TRAFFIC REVIEW GENERAL COMMENTS:
  
 - PURSUANT TO ORDINANCE NO. 4506-14, PROVIDE A TRAFFIC
 STATEMENT, PREPARED BY A LICENSED ENGINEER, TO DOCUMENT
 THE TRIP GENERATION AND VERIFY THAT THE MAXIMUM
 ALLOWABLE TRIP COUNT OF 14,640 AVERAGE DAILY VEHICULAR
 TRIPS IS NOT EXCEEDED. THE TRAFFIC STATEMENT SHALL
 OUTLINE THE NUMBER OF AVERAGE DAILY VEHICULAR TRIPS
 ASSOCIATED WITH THE PROPOSED CONSTRUCTION OR RENOVATION
 ALONG WITH ALL EXISTING DEVELOPMENT PROPOSED TO REMAIN
 ON THE PROPERTY.
 - PURSUANT TO RESOLUTION NO. 20-14, THE DEVELOPER IS
 RESPONSIBLE TO OBTAIN ALL NECESSARY APPROVALS, AND MAKE
 ALL NECESSARY IMPROVEMENTS TO CONVERT 40TH STREET INTO
 A TWO-WAY ROAD BETWEEN NORTH FLAGLER DRIVE AND BROADWAY
 AVENUE PRIOR TO THE ISSUANCE OF THE FIRST BUILDING
 PERMIT.
 - PURSUANT TO RESOLUTION NO. 20-14, PROVIDE PROOF OF
 BOND PAYMENT IN THE AMOUNT OF 110% OF THE COST OF
 INSTALLATION OF A TRAFFIC SIGNAL AT NORTH FLAGLER
 DRIVE/45TH STREET PRIOR TO THE ISSUANCE OF THE FIRST
 BUILDING PERMIT.
 - PURSUANT TO RESOLUTION NO. 20-14, A NORTHBOUND LEFT
 TURN LANE SHALL BE CONSTRUCTED FROM NORTH FLAGLER DRIVE
 ONTO 45TH STREET, AT THE DEVELOPER?S EXPENSE, PRIOR TO
 ISSUANCE OF THE FIRST CERTIFICATE OF OCCUPANCY.
 - PURSUANT TO RESOLUTION NO. 20-14, PRIOR TO ISSUANCE
 OF THE FIRST CERTIFICATE OF OCCUPANCY, SIGNAL TIMING
 PATTERNS SHALL BE OPTIMIZED AT 45TH STREET/BROADWAY
 AVENUE BY THE DEVELOPER TO ENSURE THE MOST EFFICIENT
 TRAFFIC FLOW. ANY COSTS ASSOCIATED WITH THE
 OPTIMIZATION SHALL BE COVERED BY THE DEVELOPER, AND ALL
 WORK SHALL BE DONE IN ACCORDANCE WITH THE CITY AND
 COUNTY?S STANDARDS AND PROCESSES.
 - THE PROPOSED AMENDMENT MODIFIES PBA 2 TO A MAXIMUM OF
 200 RESIDENTIAL UNITS AND PBA 3 TO A MAXIMUM OF 199
 RESIDENTIAL UNITS, BUT THE SITE PLAN, SHEET A0.02
 PROPOSES 199 UNITS IN PBA 2 AND 200 UNITS IN PBA 3.
 PLEASE REVISE.
 - THE REVISED FIGURES ARE MISSING FROM THE REVISED
 DESIGN GUIDELINES, PAGE 21,22,24, AND 26. PLEASE
 REVISE.
  
 SITE PLAN (RECEIVED ON FEBRUARY 13, 2018) COMMENTS:
  
 - PURSUANT TO RESOLUTION NO. 20-14, INCLUDE IN THE
 APPLICATION THE STREETSCAPE DESIGN, INCLUDING BUT NOT
 LIMITED TO LANDSCAPING AND SIDEWALKS/BIKE PATHS, ON THE
 EAST AND WEST SIDE OF NORTH FLAGLER DRIVE. PLEASE
 COORDINATE WITH ENGINEERING ON THE STREETSCAPE DESIGN.
 THE STREETSCAPE IMPROVEMENT SHOULD BE INSTALLED PRIOR
 TO THE ISSUANCE OF THE FIRST CERTIFICATE OF OCCUPANCY
 FOR THE PROPOSED PBA DEVELOPMENT.
 - DIMENSION THE FULL WIDTH OF RIGHT OF WAY AND THE
 WIDTH FROM CENTERLINE.
 - THE GARAGE APPEARS TO BE UNGATED AND UNRESTRICTED.
 PLEASE EXPLAIN THE PARKING MANAGEMENT STRATEGIES FOR
 THE PROPOSED DEVELOPMENT TO MAKE SURE THE PARKING NEEDS
 OF THE VISITORS, RESIDENTS AND THEIR GUESTS ARE
 ACCOMMODATED.
 - PROVIDE A TURNAROUND AREA FOR THE LAST PARKING SPACE
 UNDER RAMP.
 - FOR SOME OF THE ACTIVE USE AND MAINTENANCE FACILITIES
 ON THE WEST SIDE OF THE GARAGE, THE BACKDOORS OPEN INTO
 THE PARKING AISLES UNDER THE RAMP. THIS MAY CREATE
 POTENTIAL CONFLICT WITH VEHICLES. PLEASE PROVIDE A
 BUFFER SPACE BETWEEN THE DOORS AND THE PARKING AISLES,
 REMOVE THE BACKDOORS IF ALTERNATIVE ACCESS EXISTS, AND
 HAVE THE DOORS OPEN TO INSIDE.
 - PROVIDE PEDESTRIAN CONNECTIONS BETWEEN FLAGLER DRIVE
 AND THE PROPERTY NEAR 43RD STREET.
 - CONSIDER PROVIDING WIDER SIDEWALK ALONG THE NORTH AND
 SOUTH BUILDING FRONTAGE BETWEEN FLAGLER DRIVE AND THE
 PROMENADE.
 - THE SOUTHERN DRIVEWAY IS OFFSET TO 42ND STREET. WHEN
 THE PROPERTY TO THE SOUTH REDEVELOPS, THIS DRIVEWAY
 WILL NEED TO BE RELOCATED TO ALIGN WITH 42ND STREET TO
 MINIMIZE POTENTIAL VEHICLE CONFLICTS.
 - PROVIDE AT LEAST 25 FEET OF STORAGE SPACE IN ADVANCE
 OF THE STOP BARS AT THE 2 FLAGLER DRIVE DRIVEWAYS.
 - ALL STOP BARS SHOULD BE PLACED IN ADVANCE OF THE
 CROSSWALKS.
 - ON SHEET C4.11, ALL GARBAGE TRUCK PATHS ARE SHOWN TO
 RUN OVER CURBS. REVISE THE CURB TO ACCOMMODATE GARBAGE
 TRUCKS.
 - CLARIFY IF THE GARBAGE TRUCK NEEDS TO ACCESS THE
 PROMENADE. IF SO, PLEASE MODIFY THE CURBS TO
 ACCOMMODATE.
 - INCLUDE THE AUTOTURN PATHS FOR GARBAGE TRUCKS
 ACCESSING ALL 3 TRASH AREAS.
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  
  

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 03-14-2018 Cont ID  
Sent By jroach Date 03-14-2018 Time 08:48 Rev Time 0.00
Received By jroach Date 03-14-2018 Time 08:48 Sent To  
Notes
2018-03-15 08:48:53PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.14.2018
 PROJECT NO.: Z18020021 & Z18020023
 CASE NO.: PB 1445FF & 1445GG
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. APPROVED SCHOOL CAPACITY AVAILABILITY DETERMINATION
 SHALL BE PROVIDED.
  
 2. SITE PLAN SHALL INCLUDE A NORTH ARROW AND GRAPHIC
 SCALE.
  
 3. THE PROPERTY LINE SHOULD BE CLEARLY IDENTIFIED WITH
 A DIFFERENT LINE TYPE/COLOR/WEIGHT. A PORTION OF THE
 PROPERTY LINE IS SHOWN AS A RED DASHED LINE, WHILE
 OTHER PORTIONS ARE THE SAME LINE WEIGHT/COLOR AS EVERY
 OTHER LINE.
  
 4. DIMENSIONS SHALL BE PROVIDED FOR THE DRIVEWAY AT THE
 SOUTH END OF THE PROJECT, BETWEEN RYBOVICH AND THE TRG
 PROJECT.
  
 5. THERE SHOULD BE A DOOR FROM THE BIKE PARKING SPACE
 TO THE EXTERIOR OF THE BUILDING, WITHOUT HAVING TO GO
 THROUGH THE PARKING GARAGE.
  
 6. THE TRAFFIC ANALYSIS PROVIDED DOES NOT APPEAR TO
 ACCOUNT FOR THE ACTIVE USE SQUARE FOOTAGE THAT IS
 PROPOSED ALONG THE FRONTAGE ROAD.
  
 7. THE SITE PLAN SHOULD INCLUDE LABELS AND DETAILS OF
 ALL FENCING, WALL, ETC.; HEIGHTS SHALL BE IDENTIFIED.
  
 8. DETAIL SHALL BE PROVIDED FOR THE TRASH ENCLOSURE
 SOUTH OF THE OFFICE/OUTDOOR DINING AREA.
  
 9. THE PARKING STALL DETAIL SHOULD MATCH THE CITY?S
 STANDARD DETAIL; PLEASE EMAIL ME FOR A COPY. AN
 ADDITIONAL DETAIL SHALL BE PROVIDED SHOWING HOW THE
 STRIPING WILL BE ACCOMMODATED AROUND OR NEAR THE
 STRUCTURAL COLUMNS IN THE GARAGE.
  
 10. IS THERE A REASON WHY THE GARAGE IS SHOWN AS
 ONE-WAY? THE ARROWS INDICATE ONE-WAY, BUT STOP BARS ARE
 SHOWN ON BOTH SIDES OF THE GARAGE, ETC.
  
 11. PLEASE VERIFY THE LOCATION OF THE STOP BARS,
 PARTICULARLY AT THE EXITS OF THE PARKING GARAGE. I
 BELIEVE THE BAR SHOULD BE RELOCATED, OR A SECOND BAR
 ADDED, BEFORE THE CROSSWALK.
  
 12. THE SITE PLAN SHOULD INCLUDE ALL OF THE PAVEMENT
 MARKINGS THAT ARE SHOWN ON SHEET C4.00.
  
 13. PLEASE PROVIDE TURNING ANALYSIS FOR THE
 LOADING/UNLOADING AND TRASH PICK-UP INSIDE THE GARAGE.
  
 14. BICYCLE PARKING SHALL BE PROVIDED ON THE EXTERIOR
 OF THE BUILDING NEAR EACH OF THE ELEMENTS THAT IS OPEN
 TO THE PUBLIC OR WOULD OTHERWISE BE ACCESSED BY SOMEONE
 WHO DOES NOT HAVE ACCESS TO THE INTERNAL BIKE STORAGE
 AREA.
  
 15. A DETAIL SHALL BE PROVIDED FOR THE PROPOSED BIKE
 RACK, INCLUDING SIZE, STYLE, DIMENSIONS OF THE AREA
 SURROUNDING, ETC.
  
 16. TURN AROUND SPACES SHALL BE PROVIDED AT PARKING
 ROWS THAT HAVE A DEAD END, SUCH AS UNDER THE RAMP ON
 THE GROUND FLOOR AND ON THE TOP LEVEL OF THE GARAGE.
  
 17. DIMENSION ALL PARKING ROWS AND DRIVE AISLES.
  
 18. PEDESTRIAN CONNECTION SHOULD BE MADE FROM THE SOUTH
 LOBBY ENTRANCE TO THE PUBLIC PROMENADE TO THE EAST,
 WITHOUT HAVING TO CROSS LANDSCAPING.
  
 19. POOLS SHALL BE ENCLOSED BY A FENCE OR SIMILAR
 STRUCTURE THAT IS AT LEAST FOUR (4) FEET IN HEIGHT.
 ACCESS TO THE POOL SHOULD BE THROUGH A BUILDING OR
 THROUGH A SELF-CLOSING AND SELF-LATCHING GATE WITH
 LATCHES AT LEAST 54 INCHES ABOVE THE BOTTOM OF THE
 GATE.
  
 20. THE DATA ON SHEET A0.02 INDICATE THAT THERE ARE 199
 DWELLING UNITS IN PBA 2 AND 200 DWELLING UNITS IN PBA
 3; THE DESIGN GUIDELINES HAVE THIS INFORMATION
 REVERSED.
  
 21. PLEASE PROVIDE A DIMENSION FROM THE NORTH PROPERTY
 LINE TO THE NORTHERN ROADWAY; THE MINIMUM BUFFER SHALL
 BE AT LEAST FIVE (5) FEET IN WIDTH.
  
 22. THE MASSING DIAGRAM ON PAGE 18 OF THE DESIGN
 GUIDELINES NEEDS TO BE REVISED TO ACCURATELY REFLECT
 THE NEW MAXIMUM GROSS FLOOR AREAS.
  
 23. PURSUANT TO THE DESIGN GUIDELINES, SHOWER/CHANGING
 FACILITIES SHALL BE PROVIDE FOR EMPLOYEES OF ALL
 NON-RESIDENTIAL USES WITHIN THE CMPD. PLEASE INDICATE
 HOW THIS IS WILL BE PROVIDED FOR THE ACTIVE USES
 PROPOSED ON THE FRONTAGE ROAD.
  
 24. PURSUANT TO THE DESIGN GUIDELINES, A SITE PLAN
 APPLICATION SHALL INCLUDE A PARKING MANAGEMENT PLAN
 THAT DEMONSTRATES THE PROVISION OF SUFFICIENT PARKING
 AND SUFFICIENT VEHICULAR, PEDESTRIAN AND EMERGENCY
 VEHICLE ACCESS FOR ALL CONSTRUCTION TRAFFIC AS WELL AS
 ALL BUILDINGS REMAINING IN OPERATION DURING THE
 DEMOLITION/CONSTRUCTION FOR THE PROPOSED BUILDING.
  
 25. PURSUANT TO THE DESIGN GUIDELINES, THERE IS TO BE A
 MINIMUM OF FIVE (5) FEET OF FOUNDATION PLANTING ALONG
 THE WEST FA?ADE OF THE BUILDING.
  
 26. PURSUANT TO THE DESIGN GUIDELINES THE DESIGN OF THE
 FRONTAGE ROAD IS TO INCLUDE PEDESTRIAN ELEMENTS SUCH AS
 BENCHES, TRASH CAN, FOUNTAINS, PUBLIC ART, ETC.
  
 27. PLEASE PROVIDE INFORMATION PERTAINING OT THE
 PROPOSED GREEN WALLS ON THE GROUND FLOOR, ON THE WEST
 FA?ADE OF THE BUILDING.
  
 28. VERIFICATION FROM THE PROJECT ARCHITECT SHALL BE
 PROVIDED INDICATING THAT THE BUILDING WILL BE AT LEAST
 BRONZE LEVEL ON THE ICC 700 2012 NATIONAL GREEN
 BUILDING STANDARDS IN EFFECT AS OF JANUARY 1, 2014 AND
 INCORPORATE ALL OF THE GREEN INITIATIVES OUTLINED IN
 THE DESIGN GUIDELINES.
  
 29. PARKING FOR THE ACTIVE USES ALONG THE FRONTAGE ROAD
 TO NOT APPEAR TO BE INCLUDED IN THE CALCULATIONS,
 PLEASE CLARIFY. PARKING REQUIREMENTS FOR
 NON-RESIDENTIAL USES ARE OUTLINED IN THE DESIGN
 GUIDELINES.
  
 30. STAFF NEEDS CLARIFICATION REGARDING THE PROPOSED
 NUMBER OF PARKING SPACES AND THE CONFIGURATION OF THE
 GARAGE, ETC. PLEASE CONTACT FOR FURTHER DISCUSSION.
  
 31. PLEASE CLARIFY THE DETAIL OF THE PROPOSED WALKWAY
 EXTENDING INTO THE INTRACOASTAL WATERWAY. IS THE
 DOCKING OF BOATS GOING TO BE PERMITTED? IF SO, ARE THE
 SLIPS FOR RESIDENTS ONLY? ADDITIONAL INFORMATION
 REGARDING THIS ELEMENT MAY GENERATE ADDITIONAL COMMENTS
 DEPENDING UPON THE APPLICABLE SECTIONS OF THE CITY?S
 ZONING AND LAND DEVELOPMENT REGULATIONS.
  
 32. PLEASE PROVIDE THE DIMENSION OF THE METAL PANELS
 (BEHIND THE CABLE RAILS) INSIDE OF THE PARKING GARAGE.
 PURSUANT TO THE DESIGN GUIDELINES, THESE PANELS SHALL
 BE AT LEAST 3 FEET 6 INCHES IN HEIGHT.
  
 33. THERE WAS SOME COMMENTS BY STAFF THAT THE PROPOSED
 DESIGN ELEMENTS FOR THE PARKING GARAGE SEEMED A LITTLE
 OUT OF CONTEXT WITH THE REST OF THE RESIDENTIAL TOWER
 AND THOUGHT THAT THEY COULD BE BETTER INTEGRATED.
  
 34. IS THE GARAGE PROPOSED TO BE GATED? THERE NEEDS TO
 BE DISCUSSIONS WITH STAFF REGARDING OPERATION OF THE
 GARAGE, STACKING, GUEST ACCESS, ACCESS TO PARKING BY
 PATRONS OF THE NON-RESIDENTIAL USES, ETC.
  
 35. IS LIGHTING PROPOSED? A PHOTOMETRIC PLAN SHALL BE
 PROVIDED.
  
 36. IS SIGNAGE PROPOSED AS PART OF THE ACTIVE USES
 ALONG THE FRONTAGE ROAD?
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) IN ORDER TO BE CONSIDERED FOR THE MAY 15, 2018,
 PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE
 SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED
 DOCUMENTS/PLANS NO LATER THAN MARCH 30, 2018.
  
 G) TO BE PLACED ON THE MAY 15, 2018, PLANNING BOARD
 AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO LATER
 THAN APRIL 30, 2018. SIGNAGE SHALL CONFORM AND BE
 INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN
 THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED
 AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED
 ABOVE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION