Plan Review Details - Project Z18020020
Plan Review Stops For Project Z18020020
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-13-2018 Cont ID  
Sent By rbrown Date 03-13-2018 Time 20:29 Rev Time 0.00
Received By rbrown Date 03-13-2018 Time 20:29 Sent To  
Notes
2018-03-13 20:30:51DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-14-2018 Cont ID  
Sent By mgonzale Date 03-14-2018 Time   Rev Time 0.00
Received By mgonzale Date 03-14-2018 Time 13:07 Sent To  
Notes
2018-03-14 13:09:36#1 DEPTH AND LOCATION OF DUMSPTER NEEDS REVIEW.
  
 #2 EXISTING WATERMAIN WILL REQUIRE EASEMENT AND CAUTION
 AS TO ANY PROPOSED LANDSCAPING.
 CITY OF WPB UTILITIES WILL REQUIRE A MEETING TO SEE
 ABOUT THE POSIBILITY AS TO ITS ABANDONMENT.
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-09-2018 Cont ID  
Sent By pleduc Date 03-09-2018 Time 10:01 Rev Time 0.00
Received By pleduc Date 03-09-2018 Time 09:50 Sent To  
Notes
2018-03-09 10:00:54THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND IF APPLICABLE ,WHETHER IT WILL BE MIXED OR
 SEPARATED OCCUPANCY.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND, IF NEEDED, CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. IT IS HIGHLY RECOMMENDED FOR ANY 24 HOUR EMERGENCY
 ACCESS NEEDS THAT A KNOX BOX BE PROVIDED WITH KEYS FOR
 EACH SUITE.
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 04-30-2018 Cont ID  
Sent By rcaranci Date 04-30-2018 Time 17:02 Rev Time 0.00
Received By rcaranci Date 04-30-2018 Time 17:02 Sent To  
Notes
2018-04-30 17:02:55FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 6500 S DIXIE Z18020020
 APRIL 30, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. PLEASE CORRECT THE REQUIRED OPEN SPACE TO
 40 PERCENT OF THE TOTAL SITE, AND RECALCULATE REQUIRED
 TREES AND FLOWERING TREES TO CURRENT CODE OF 1 TREE PER
 1500 SQ FT OF REQUIRED OPEN SPACE OR PORTION THEREOF,
 AND FLOWERING TREES TO ONE PER 6000 SQ FT OR PORTION
 THEREOF PER SECTION 94-442(C)(2)B.
  
 2. SATISFIED. PLEASE SHOW AND LABEL THE REQUIRED 5 FOOT
 LANDSCAPE BUFFER ON ALL SIDES ADJACENT TO THE PROPERTY
 LINES ON THE SITE AND LANDSCAPE PLANS.
  
 3. SATISFIED. PLEASE PROVIDE THE BUFFER REQUIREMENTS
 AND CALCULATIONS ON THE PLAN. ONE TREE PER 30 LF OR
 PORTION THEREOF IS REQUIRED. LARGER TREE SPECIES MUST
 BE USED WHERE POSSIBLE TO PROVIDE BUFFERING TO ADJACENT
 PROPERTIES AND PROVIDE SHADE FOR PARKING AREAS. SOUTH
 LANDSCAPE BUFFER MUST MEET REQUIREMENTS COMPATIBLE WITH
 THE UTILITY EASEMENT.
  
 4. SATISFIED. PLEASE ADD A COLUMN FOR DROUGHT TOLERANCE
 TO THE PLANT LIST AND PROVIDE THE LEVEL FOR EACH
 SPECIES, AND IF THE SPECIES IS NATIVE.
  
 5. SATISFIED. PLEASE PROVIDE A TREE AS REQUIRED IN A
 TERMINAL LANDSCAPE ISLAND AT THE END OF EACH ROW OF
 PARKING SPACES. LARGER TREE SPECIES MUST BE USED WHERE
 POSSIBLE TO PROVIDE BUFFERING TO ADJACENT PROPERTIES
 AND PROVIDE SHADE FOR PARKING AREAS.
  
 6. SATISFIED. PLEASE PROVIDE THE PERVIOUS LANDSCAPE
 AREA SQUARE FOOTAGE ON THE LANDSCAPE PLAN.
  
 7. SATISFIED. PLEASE UPDATE FLORIDA FRIENDLY LANDSCAPE
 POINTS TO SHOW CURRENT APPLICABLE CODE REQUIRES 40
 POINTS.
  
 8. SATISFIED. PLEASE SHOW CALCULATION OF PERCENTAGE OF
 PALMS SUBSTITUTED FOR REQUIRED TREES, NOT TO EXCEED 35
 PERCENT.
  
 9. SATISFIED. PLEASE SHOW CALCULATIONS FOR THE BUILDING
 FOR COMPLIANCE WITH 30 PERCENT PERIMETER LANDSCAPE PER
 SECTION 94-443(E)(1).
  
 10. SATISFIED. PLEASE SHOW ALL WATER, SEWAGE AND
 DRAINAGE LINES ON THE LANDSCAPE PLAN.
  
 11. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS
 TO PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS.
 THIS INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND
 CURBS, AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED
 BY TREE ROOTS.
  
 12. SATISFIED. PLEASE SHOW LOCATIONS OF ANY FPL
 TRANSFORMERS ON THE LANDSCAPE PLAN.
  
 13. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES
 AND FPL TRANSFORMERS MUST HAVE SCREENING HEDGES.
  
 14. SATISFIED. PLEASE PROVIDE THE LOCATIONS OF LIGHTING
 ON THE LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-13-2018 Cont ID  
Sent By rcaranci Date 03-13-2018 Time 11:31 Rev Time 0.00
Received By rcaranci Date 03-13-2018 Time 11:31 Sent To  
Notes
2018-03-13 11:31:52FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 6500 S DIXIE Z18020020
 MARCH 12, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE CORRECT THE REQUIRED OPEN SPACE TO 40 PERCENT
 OF THE TOTAL SITE, AND RECALCULATE REQUIRED TREES AND
 FLOWERING TREES TO CURRENT CODE OF 1 TREE PER 1500 SQ
 FT OF REQUIRED OPEN SPACE OR PORTION THEREOF, AND
 FLOWERING TREES TO ONE PER 6000 SQ FT OR PORTION
 THEREOF PER SECTION 94-442(C)(2)B.
  
 2. PLEASE SHOW AND LABEL THE REQUIRED 5 FOOT LANDSCAPE
 BUFFER ON ALL SIDES ADJACENT TO THE PROPERTY LINES ON
 THE SITE AND LANDSCAPE PLANS.
  
 3. PLEASE PROVIDE THE BUFFER REQUIREMENTS AND
 CALCULATIONS ON THE PLAN. ONE TREE PER 30 LF OR PORTION
 THEREOF IS REQUIRED. LARGER TREE SPECIES MUST BE USED
 WHERE POSSIBLE TO PROVIDE BUFFERING TO ADJACENT
 PROPERTIES AND PROVIDE SHADE FOR PARKING AREAS. SOUTH
 LANDSCAPE BUFFER MUST MEET REQUIREMENTS COMPATIBLE WITH
 THE UTILITY EASEMENT.
  
 4. PLEASE ADD A COLUMN FOR DROUGHT TOLERANCE TO THE
 PLANT LIST AND PROVIDE THE LEVEL FOR EACH SPECIES, AND
 IF THE SPECIES IS NATIVE.
  
 5. PLEASE PROVIDE A TREE AS REQUIRED IN A TERMINAL
 LANDSCAPE ISLAND AT THE END OF EACH ROW OF PARKING
 SPACES. LARGER TREE SPECIES MUST BE USED WHERE POSSIBLE
 TO PROVIDE BUFFERING TO ADJACENT PROPERTIES AND PROVIDE
 SHADE FOR PARKING AREAS.
  
 6. PLEASE PROVIDE THE PERVIOUS LANDSCAPE AREA SQUARE
 FOOTAGE ON THE LANDSCAPE PLAN.
  
 7. PLEASE UPDATE FLORIDA FRIENDLY LANDSCAPE POINTS TO
 SHOW CURRENT APPLICABLE CODE REQUIRES 40 POINTS.
  
 8. PLEASE SHOW CALCULATION OF PERCENTAGE OF PALMS
 SUBSTITUTED FOR REQUIRED TREES, NOT TO EXCEED 35
 PERCENT.
  
 9. PLEASE SHOW CALCULATIONS FOR THE BUILDING FOR
 COMPLIANCE WITH 30 PERCENT PERIMETER LANDSCAPE PER
 SECTION 94-443(E)(1).
  
 10. PLEASE SHOW ALL WATER, SEWAGE AND DRAINAGE LINES ON
 THE LANDSCAPE PLAN.
  
 11. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 12. PLEASE SHOW LOCATIONS OF ANY FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN.
  
 13. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL
 TRANSFORMERS MUST HAVE SCREENING HEDGES.
  
 14. PLEASE PROVIDE THE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 03-15-2018 Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-15 08:07:29SPOKE WITH OWNERS AT PPRC MEETING AND PER A PREVIOUS
 DISCUSSION AT THE DPW OFFICE IT IS AGREED THEY WILL USE
 96 GALLON CARTS FOR THEIR SERVICE AND THE TENENT OR
 TENENTS WILL BE RESPONSIBLE TO BRING THE CARTS TO THE
 CURB FOR PICK UP.
2018-03-14 07:15:23BASED ON THE PLAN IT APPEARS TO SHOW THAT THE
 SANITATION SERVICE PROPOSED IS 96 GALLON CARTS. IF THAT
 IS TRUE THEN EITHER THE PROPERTY OWNERS/MANAGERS WOULD
 BE RESPONSIBLE TO PLACE THEM CURBSIDE FOR PICK UP ON
 SERVICE DAYS.
  
 IF YOU INTEND TO USE A DUMPSTER SERVICE THE ENCLOSRE
 WOULD HAVE TO BE RELOCATED TO PREVENT OUR SERVICE TRUCK
 FROM BACKING UP MORE THEN 30'.

Review Stop STORM STORMWATER
Rev No 2 Status P Date 05-10-2018 Cont ID  
Sent By tward Date 05-10-2018 Time 17:02 Rev Time 0.00
Received By tward Date 05-10-2018 Time 17:07 Sent To  
Notes
2018-05-10 17:06:02COMMENTS BELOW ARE FROM THE REVIEW OF THE APRIL 25,
 2018 SUBMITTAL PACKAGE.
  
 1. THOUGH NOT REQUIRED, SUGGESTION IS MADE TO INCLUDE
 POLLUTANT RETARDANT BAFFLES (PRB'S) IN FRONT OF THE
 EXFILTRATION TRENCHES TO PROLONG THE EFFECTIVENESS OF
 THE EXFILTRATION TRENCH. THE SUMP IN THE CATCH BASINS
 SHOULD BE INCREASED TO 18 INCHES OR 24 INCHES FROM 12
 INCHES IF PRB'S ARE INTALLED.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-09-2018 Cont ID  
Sent By tward Date 03-09-2018 Time 13:44 Rev Time 0.00
Received By tward Date 03-09-2018 Time 13:46 Sent To  
Notes
2018-03-09 13:45:43THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. THE CITY?S VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED. SHOW THE DATUM
 CONVERSION ON THE BOUNDARY SURVEY.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE SFWMD ERP FOR THE DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 05-02-2018 Cont ID  
Sent By vnoel Date 05-02-2018 Time 09:41 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2018-05-02 09:42:31UNITY OF TITLE HAS BEEN RECORDED.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 03-12-2018 Cont ID  
Sent By vnoel Date 03-12-2018 Time 13:30 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-03-12 13:46:291. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH ENGINEERING SERVICES.
 2. CHECK DIXIE HWY RIGHT-OF-WAY VS. FDOT MAINTENANCE
 MAP
 3. PROPERTY CORNERS ON SHEET C.01 DOES NOT MATCH
 SURVEY.
 4. WATER SERVICE RECORDS INDICATE PROPERTY BEING SERVED
 BY METER IN 6' EASEMENT.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 05-21-2018 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2018-05-21 09:18:11PASSED
 ERIK D. FERGUSON P.E.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 03-08-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-08 17:32:58- PROVIDE TRAFFIC IMPACT STUDY IN ACCORDANCE WITH CITY
 CODE SECTION 94-311 OR A TRIP GENERATION LETTER AND
 DOCUMENTATION DEMONSTRATING THAT CITY CODE SECTION
 94-311(C) TRAFFIC IMPACT STUDY REQUIRED IS NOT
 APPLICABLE.
 - PROVIDE COUNTY TRAFFIC CONCURRENCY LETTER
 - IT MAY BE POSSIBLE TO ADD ONE ADDITIONAL ON-STREET
 PARKING SPACE ON S. DIXIE WITH ELIMINATION OF EXISTING
 CURB CUT ON SOUTH DIXIE.
 - GENERAL COMMENT IS IT POSSIBLE TO PROVIDE LANDSCAPING
 BEHIND THE CURB ON SOUTH DIXIE IN THE EXISTING PAVER
 STRIP INSTEAD OF LANDSCAPING BETWEEN BACK OF SIDEWALK
 AND BUILDING? LANDSCAPING IN THIS LOCATION WOULD
 PROVIDE MORE BENEFIT TO PEDESTRIAN THAN THE LANDSCAPING
 BETWEEN THE BACK OF SIDEWALK AND BUILDING. NOT SURE IF
 THIS IS CONSISTENT WITH CODE.
 - CITY HAS NOT COMPLETED A DETAILED REVIEW DUE TO THE
 INCOMPLETE INFORMATION PROVIDED.
 - REDUCE DRIVEWAY WIDTH ON HUNTER TO 20'.
 - FDOT PERMIT WILL BE REQUIRED TO REMOVE EXISTING
 DRIVEWAY ON S. DIXIE.
 - CAN LANDSCAPING BE INSTALLED INSTEAD OF PROPOSED
 PAVER BLOCKS AT THE LOCATION WHERE THE EXISTING S.
 DIXIE DRIVEWAY IS BEING REMOVED?
 - CONSIDER PLACING DUMPSTER IN DIFFERENT LOCATION TO
 ALLOW PARKING AISLE TO ALLOW A FUTURE CONNECTION TO
 ADJACENT PROPERTY. THIS WOULD ALLOW THE PARKING AISLE
 TO FUNCTION IN THE FUTURE AS AN ALLEY.
  
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER
 (561) 494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 05-07-2018 Cont ID  
Sent By awooten Date 05-07-2018 Time 15:18 Rev Time 0.00
Received By awooten Date 05-07-2018 Time 15:17 Sent To  
Notes
2018-05-07 15:17:19****************************************CONDITIONAL
 ZONING APPROVAL***********************************
  
 THE FOLLOWING IS A CONDITION OF SITE PLAN APPROVAL:
  
 REPLACE THE ENTIRE EXISTING SIDEWALK ON SOUTH DIXIE
 HIGHWAY WITH CONCRETE.
  
 ALANA WOOTEN
 ASSOCIATE PLANNER
 561-822-1449
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 03-13-2018 Cont ID  
Sent By ajones Date 03-13-2018 Time 16:25 Rev Time 0.00
Received By ajones Date 03-13-2018 Time 13:14 Sent To  
Notes
2018-03-13 16:31:38CASE NO. ISPR 18-04
 PROJECT NAME STATE FARM BUILDING
 ADDRESS 6500 S. DIXIE HIGHWAY
  
 - CONTACT ALANA WOOTEN @ (561) 822-1449
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11)/FIVE (5) PAPER COPIES AND AN ELECTRONIC COPY IN
 .PNG/.PDF FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES
 ON THE RESUBMITTED PLANS OR THE SUBMITTAL OF
 INFORMATION/PLANS TO ADDRESS THE COMMENTS MAY RESULT IN
 ADDITIONAL COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING, THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 1. THE BICYCLE PARKING SHALL BE MOVED TO THE FRONT OF
 THE BUILDING.
 2. PLEASE VERTIFY THE ON STREET PARKING COUNT.
 3. WHEN REFORMING THE SIDEWALK ON DIXIE, REPLACE THE
 PAVERS BRICKS WITH CONCRETE.
  
  
  