Plan Review Details - Project Z18020018
Plan Review Stops For Project Z18020018
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-13-2018 Cont ID  
Sent By rbrown Date 03-13-2018 Time 20:19 Rev Time 0.00
Received By rbrown Date 03-13-2018 Time 20:19 Sent To  
Notes
2018-03-13 20:22:01DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 03-14-2018 Cont ID  
Sent By mgonzale Date 03-14-2018 Time   Rev Time  
Received By mgonzale Date 03-14-2018 Time   Sent To  
Notes
2018-03-14 13:13:00#1 PROVIDE VIDEO OF EXISTING SEWER MAIN BEFORE CWPB
 UTILITIES AGREES TO SERVE PROJECT.
  
 #2 SIDEWALK IN THE ROW WILL REQUIRE REPLACEMENT.
  
 #3 ADA PARKING DETAIL HAS SOME DEFICIENCIES WITH
 DIMENSIONS.
  
 #4. PROPOSED WATER SERVICE ENTERING SITE CONFLICTS WITH
 PROPOSED LANDSCAPING/TREE.
  
  
 MANNY GONZALEZ
 SENIOR ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 IMPORTANT MESSAGE: AS OF DECEMBER 20, 2015 THE CITY OF
 WEST PALM BEACH
 CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE."
 FOR MORE INFORMATION REFER TO THE LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-09-2018 Cont ID  
Sent By pleduc Date 03-09-2018 Time 09:49 Rev Time 0.00
Received By pleduc Date 03-09-2018 Time 09:25 Sent To  
Notes
2018-03-09 09:49:37THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE AND PROPOSED HAZARD CLASSIFICATION PER
 THE FLORIDA FIRE PREVENTION CODE, NFPA 101, CHAPTER 42,
 STORAGE OCCUPANCIES.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND/OR CLOSELY COORDINATED WITH THE BUREAU
 OF FIRE PREVENTION.
  
 IF REQUIRED, ALL NEW FIRE HYDRANTS AND FDC?S PLANNED
 FOR THIS DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH
 THE BUREAU OF FIRE PREVENTION.
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 10. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS
 AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 11. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 12. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-13-2018 Cont ID  
Sent By rcaranci Date 03-13-2018 Time 10:25 Rev Time 0.00
Received By rcaranci Date 03-13-2018 Time 10:25 Sent To  
Notes
2018-03-13 10:26:03FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 1125 OKEECHOBEE RD. Z18020018
 MARCH 12, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE SHOW LOCATIONS OF ADJACENT BUILDINGS, HEDGES
 AND TREES ON THE LANDSCAPE PLAN.
  
 2. PLEASE SHOW AND LABEL THE REQUIRED 5 FOOT LANDSCAPE
 BUFFER ON SIDES AND REAR PROPERTY LINES, AND 10 FOOT
 LANDSCAPE BUFFER ADJACENT TO THE STREET.
  
 3. SHOW CALCULATIONS TO MEET REQUIRED TREE COUNT FOR
 EACH BUFFER LENGTH.
  
 4. PLEASE SHOW COMPLIANCE WITH THE 20 PERCENT BUILDING
 PERIMETER LANDSCAPING REQUIREMENT.
  
 5. THE CIVIL ENGINEERING PLAN SUBMITTED SHOWS LANDSCAPE
 SYMBOLS, PROPOSED LANDSCAPING SHOULD ONLY BE SHOWN ON
 THE LANDSCAPE PLAN.
  
 6. PLEASE CORRECT THE REQUIRED OPEN SPACE TO 40 PERCENT
 OF THE TOTAL SITE, AND RECALCULATE REQUIRED TREES AND
 FLOWERING TREES.
  
 7. PROVIDE CURBS FOR ALL VEHICULAR USE AREAS ADJACENT
 TO LANDSCAPING.
  
 8. PLEASE PROVIDE THE BUFFER REQUIREMENTS AND
 CALCULATIONS ON THE PLAN.
  
 9. PLEASE UPDATE FLORIDA FRIENDLY LANDSCAPE POINTS FOR
 THE FOLLOWING ITEMS:
 - APPLICABLE CODE REQUIRES 40 POINTS.
 -PROVIDE AN AREA PLAN SHOWING HIGH, MEDIUM AND LOW
 WATER USE ZONES IF POINTS ARE CLAIMED.
 -PROVIDE INFORMATION ON MOISTURE SENSOR OR EFFICIENT
 CONTROLLER IF POINTS ARE CLAIMED.
  
 10. PLEASE ADD A COLUMN FOR DROUGHT TOLERANCE TO THE
 PLANT LIST AND PROVIDE THE LEVEL FOR EACH SPECIES.
  
 11. PLEASE PROVIDE A TREE AS REQUIRED IN THE TERMINAL
 LANDSCAPE ISLAND ON BOTH SIDES OF PARKING SPACES.
  
 12. PLEASE SHOW LOCATIONS OF ANY FPL TRANSFORMERS ON
 THE LANDSCAPE PLAN.
  
 13. PLEASE SHOW ALL WATER, SEWAGE AND DRAINAGE LINES ON
 THE LANDSCAPE PLAN.
  
 14. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 15. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL
 TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE PROVIDE
 LANDSCAPE HEDGE ON THREE SIDES OF DUMPSTER ENCLOSURE AS
 REQUIRED.
  
 16. PLEASE PROVIDE THE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date 03-14-2018 Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-15 08:04:43PREVIOUS NOTE WAS A MISTAKE FOR THE PROPERTY. SPOKE
 WITH OWNER AT PPRC THEY WILL USE A 96 GALLON SERVICE
 BUT MUST PROVIDE A PERMIT REQUIRED ENCLOSURE IF IT IS
 KEPT OUTSIDE.
2018-03-15 08:01:32SPKE WITH PROPERTY OWNER AT PPRC MEETING. THE PLAN IS
 THEY WILL USE 96 GALLON CARTS AND WILL BE RESPONSIBLE
 TO TAKE THEM TO THE CURB. THIS DECISION WAS MADE IN THE
 PUBLIC WORKS OFFICE IN COLLABORATION WITH THE OWNER
 PREVIOUS TO PPRC MEETING.
2018-03-14 07:12:44WHAT IS YOUR PLAN FOR SANITATION PICK UP?

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-09-2018 Cont ID  
Sent By tward Date 03-09-2018 Time 13:42 Rev Time 0.00
Received By tward Date 03-09-2018 Time 13:43 Sent To  
Notes
2018-03-09 13:43:34THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 2. THE CITY VERTICAL DATUM IS NGVD 1929. THE CITY HAS
 ALLOWED THE USE OF NAVD 1988 PROVIDED THE CONVERSION
 EQUATION TO NGVD 1929 IS PROVIDED. SHOW THE DATUM
 CONVERSION ON THE BOUNDARY SURVEY.
  
 3. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE
 AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?
 UPDATE THE FLOOD ZONE INFORMATION ON THE BOUNDARY
 SURVEY.
  
 4. NO STORMWATER DRAINAGE SYSTEM IS SHOWN ON THE CIVIL
 ENGINEERING PLANS. THE SYSTEM SHALL BE DESIGNED TO
 PROVIDE WATER QUALITY TREATMENT PER SFWMD CRITERIA AND
 LIMIT DISCHARGE TO EXISTING CONDITIONS.
  
 5. THE SIDEWALK ALONG OKEECHOBEE ROAD IS MEET ADA SLOP
 REQUIREMENTS INCLUDING THE DRIVEWAY APRON.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. EROSION CONTROL PLAN AND DETAILS TO BE SUBMITTED
 WITH THE ENGINEERING PERMIT APPLICATION.
  
 3. PROVIDE A COPY OF THE SFWMD ERP PERMIT FOR THE
 PROJECT.
  
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 03-12-2018 Cont ID  
Sent By vnoel Date 03-12-2018 Time 10:03 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-03-12 10:20:361. PROPOSED SERVICES APPEAR TO CONFLICT WITH PROPOSED
 LANDSCAPING.
 2. NEED CONVERSION FROM NGVD-29 TO NAVD 88 SHOWN ON
 SURVEY.
 3.DRILL HOLE IS NOT ACCEPTABLE CORNER MONUMENTATION.
 4. NEED DESCRIPTION OF PARENT BENCHMARK.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 03-06-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-03-13 17:35:411 - PROJECT MAY BE EXEMPT FROM A TRAFFIC IMPACT
 STATEMENT. IF PROJECT IS EXEMPT THEN PROVIDE A TRIP
 GENERATION LETTER DEMONSTRATING THE EXEMPTION FROM
 SECTION 94-311 OF THE TRAFFIC PERFORMANCE STANDARDS
 2- PROVIDE PALM BEACH COUNTY TRAFFIC CONCURRENCY
 LETTER.
 3- IS DRIVE AISLE OF PARKING SPACES SUFFICIENT TO BACK
 OUT?
 4 - DRIVEWAY WIDTH ISN?T WIDE ENOUGH FOR TWO CARS. IF A
 SINGLE LANE BI-DIRECTIONAL DRIVEWAY IS PROPOSED THEN
 THE WIDTH COULD BE REDUCED. FIRE MAY REQUIRE THE
 DRIVEWAY TO 20? WIDE FOR FIRE ACCESS.
 5 - IS ON STREET PARALLEL PARKING AN OPTION TO PROVIDE
 REQUIRED PARKING SPACES?
  
 ERIK D. FERGUSON, PE
 CITY TRANSPORTATION ENGINEER
 561-494-1092
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 03-13-2018 Cont ID  
Sent By eschneid Date 03-13-2018 Time 11:05 Rev Time 2.00
Received By eschneid Date 03-13-2018 Time 11:05 Sent To  
Notes
2018-03-13 11:13:32CASE NO. ISPR 18-03
 1125 OKEECHOBEE RD. WAREHOUSE
 1125 OKEECHOBEE RD.
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY MAY 15, 2018),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($200).
  
 1) THE VARIOUS PLANS PROVIDED SHOW DIFFERING DIMENSIONS
 FOR VARIOUS PLAN ELEMENTS. ALL PLANS MUST SHOW THE SAME
 CONDITIONS.
  
 A. THE ARCHITECTURAL SITE PLAN (2,177 SF) AND THE CIVIL
 PLAN (2,138 SF) LIST DIFFERING SQUARE FOOTAGES FOR THE
 BUILDING. NOTE: THE PALM BEACH COUNTY TRAFFIC APPROVAL
 LETTER IS FOR 2,138 SF. IF THE BUILDING IS 2,177 SF,
 THE TRAFFIC LETTER NEEDS TO BE REVISED.
  
 B. THE ARCHITECTURAL SITE PLAN (9.5 FEET) AND THE CIVIL
 AND LANDSCAPE PLANS (9 FEET) SHOW DIFFERING PARKING
 SPACE WIDTHS.
  
 C. THE ARCHITECTURAL SITE PLAN (39 FEET) AND THE CIVIL
 PLAN (38.08 FEET) SHOW DIFFERING FRONT SETBACK
 DIMENSIONS.
  
 2) DUE TO THE NEIGHBORING BUILDINGS NOT BEING
 CONSTRUCTED WITH A ZERO FOOT SETBACK (ON THE PROPERTY
 LINE), THE PROPOSED BUILDING IS REQUIRED TO PROVIDE THE
 SIDE AND REAR LANDSCAPE BUFFER MINIMUM OF FIVE (5)
 FEET. THE INDUSTRIAL ZONING DISTRICT ONLY PERMITS A
 ZERO FOOT SETBACK WHEN AN ADJACENT EXISTING BUILDING
 HAS A ZERO FOOT SETBACK.
  
 3) THE SITE DATA TABLE INCORRECTLY LISTS THE AMOUNT OF
 OPEN SPACE. THE OPEN SPACE IS THE SITE AREA NOT
 CONTAINING BUILDINGS.
  
 4) THE SITE DATA TABLE DOES NOT INCLUDE THE REQUIRED
 PARKING, BICYCLE AND LOADING REQUIREMENTS.
  
 5) NINETY DEGREE PARKING SPACES REQUIRE A 24 FOOT DRIVE
 AISLE. THE PLANS DO NOT SHOW THIS STANDARD BEING MET.
  
 6) NO PARKING DETAIL WAS PROVIDED FOR THE REGULAR
 PARKING SPACE. THE ADA PARKING DETAIL DOES NOT COMPLY
 WITH CITY STANDARDS AND DOES NOT MATCH THE SIZE OF THE
 PROPOSED PARKING SPACE.
  
 7) THE SITE REQUIRES ONE 10 FOOT BY 25 FOOT LOADING
 SPACE. NO LOADING SPACE IS SHOWN ON THE PLANS.
  
 8) THE SITE REQUIRES BICYCLE PARKING. PLEASE PROVIDE
 THE RACK LOCATION AND DETAIL IN CONFORMANCE WITH CITY
 REQUIREMENTS.
  
 9) NO DUMPSTER LOCATION IS SHOWN ON THE SITE. PROVIDE
 THE LOCATION AND DETAILS.
  
 10) THE A/C UNIT AND PAD ARE NOT SHOWN ON THE CIVIL OR
 LANDSCAPE PLANS. ALL PLANS MUST SHOW THE SAME
 CONDITIONS.
  
 11) PLEASE CONSIDER PROVIDING ARCHITECTURAL DETAILS
 SUCH AS SCORING OR OTHER ELEMENTS TO IMPROVE THE
 APPEARANCE OF THE BUILDING.
  
 12) ALL LANDSCAPE SHALL BE PROTECTED FROM VEHICULAR
 ENCROACHMENT BY A TYPE D CURB. THIS IS NOT CLEARLY
 INDICATED ON THE PLANS.
  
 13) THE SURVEY MUST BE ABSTRACTED TO SHOW ALL
 EASEMENTS.
  
  