Plan Review Details - Project Z17120016
Plan Review Stops For Project Z17120016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 01-09-2018 Cont ID  
Sent By rbrown Date 01-09-2018 Time 22:43 Rev Time 0.00
Received By rbrown Date 01-09-2018 Time 22:43 Sent To  
Notes
2018-01-09 22:48:27DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR THE BUILDING PERMIT APPLICATION.
  
 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE.
  
 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED. THE EQUIVALENT REQUIREMENTS FOR ONE AND TWO
 FAMILY DWELLINGS, AND TOWNHOUSES ARE IN SECTION R302 OF
 FLORIDA BUILDING CODE (RESIDENTIAL).
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 5. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 01-08-2018 Cont ID  
Sent By squinone Date 01-08-2018 Time   Rev Time 0.00
Received By squinone Date 01-02-2018 Time   Sent To  
Notes
2018-01-08 09:23:19CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 DATE: 01/08/2018
 PROJECT: GULFSTREAM GOODWILL
 ADDRESS: 2100 NORTH TAMARIND AVENUE
 STATUS: FAILED
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 NO CIVIL ENGINEERING PLANS WERE SUBMITTED IN THE
 INITIAL SITE PLAN PACKAGE INDICATING STORMWATER CONTROL
 AND PLANS FOR WATER AND SEWER SERVICES/CONNECTIONS FOR
 THE PROPOSED DEVELOPMENT. FOLLOWING COMMENTS NEED TO BE
 ADDRESSED PRIOR TO SITE PLAN APPROVAL:
  
 1. PLEASE SHOW ON THE PLANS, HOW WILL THE SITE/BUILDING
 BE SERVED FOR WATER, SEWER AND FIRE PROTECTION. SHOW
 ALL EXISTING UTILITIES WITHIN THE VICINITY OF THE
 PROPOSED SITE AS WELL AS PROPOSED UTILITIES TO SERVE
 THE DEVELOPMENT (LABEL SIZE AND MATERIAL OF ALL PIPES
 AND CONDUITS ETC.);
  
 2. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH
 AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT
 ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED
 DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN
 SHEET;
  
 3. CCTV MUST BE PROVIDED FROM MANHOLE TO MANHOLE IN THE
 LOCATION OF THE PROPOSED SANITARY SEWER LATERAL.
 CONTACT ME FOR THE MANHOLE NUMBERS AND SUBMIT CD WITH
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION;
  
 4. WILL THE EXISTING WOOD POWER POLES IN THE MIDDLE OF
 THE 5-FOOT SIDEWALK BE RELOCATED?
  
 5. ON THE LANDSCAPING PLAN, WHEN SUBMITTED IN THE NEXT
 REVIEW PHASE, SHOW LOCATIONS OF ALL WATER METERS,
 VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT BARRIERS MAY
 BE REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND
 STORMWATER, SANITARY, OR POTABLE WATER LINES. ALSO
 CLEARLY INDICATE ALL EXISTING AND PROPOSED EASEMENTS ON
 THE LANDSCAPE PLAN;
  
 6. PLEASE ALSO SHOW ON THE LANDSCAPE PLAN, WHEN
 SUBMITTED IN THE NEXT REVIEW PHASE, SHOW THE SIGHT
 TRIANGLES FOR THE ALL VEHICULAR EXITS FROM THE SITE.
 (SECTION 94-305E, CODE OF ORDINANCES);
  
 7. SHOW ON THE SITE PLANS ADA ACCESSIBLE RAMPS ON THE
 SIDEWALK AT EACH ENTRANCE AND EXIT /DRIVEWAY APPROACH;
  
 8. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS AND
 MANEUVER WITHIN THE PROPOSED DEVELOPMENT;
  
 AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE
 FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND
 PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO
 VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS
 ON THE UTILITY PLAN SHEET AS WELL;
  
 4. SHOW ON THE FINAL PLANS WHERE ARE THE PROPOSED WATER
 AND SANITARY SEWER LINES ARE CONNECTED TO EXISTING
 WATER AND SEWER MAINS;
  
 5. SHOW THE NEAREST FIRE HYDRANT TO THIS SITE ON THE
 FINAL UTILITY PLAN. FIRE HYDRANT FLOW TEST DATA FROM
 EXISTING FIRE HYDRANT WILL BE REQUIRED PART OF THE PLAN
 SUBMITTAL. SHOW HYDRANT FLOW TEST DATA RESULT ON THE
 PLANS;
  
 6. FIRE HYDRANT TEST CAN BE REQUESTED AT (561)804-4700;
  
 7. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE
 WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN
 AN EASEMENT WITHIN THE PROPERTY;
  
 8. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAIL SHEET/S DURING SUBMISSION OF THE FINAL
 ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O
 RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-
 APPLICATIONS
  
 9. PLACEMENT OF THE ANY PROPOSED METER, BACKFLOW
 PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY'S
 STANDARD DETAILS. WATER METER SHOULD BE WITHIN THE
 RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' JUST
 INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND
 ACCESSIBLE;
  
 10. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT
 TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE
 CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER
 PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING
 UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL
 ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY
 CROSSING INFORMATION;
  
 11. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE
 EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION
 POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE
 LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE;
  
 12. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR
 UTILITY CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE
 WITH 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE
 MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL
 LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A
 TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH.
 PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE
 MILLING AND RESURFACING;
  
 13. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL
 EXISTING UTILITIES ON N. TAMARIND AVE, 20TH CT. AND
 21ST ST. INCLUDING BUT NOT LIMITED TO WATER, SEWER,
 GAS, UNDERGROUND ELECTRIC CONDUITS ETC. PLEASE IDENTIFY
 THE SOURCE OF THE AS-BUILT INFORMATION UTILIZED FOR THE
 POTABLE WATER, SANITARY SEWER, AND STORM SEWER DESIGN;
  
 14. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE
 THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM
 BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED,
 MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD
 FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT
 TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA
 TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 SOFIA QUINONES-BENEJAM, EI
 PROJECT ENGINEER
 CITY OF WEST PALM BEACH
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33402
 (MAILING ADDRESS: PO BOX 3366)
 P: 561.494.1108
 C: 561.459.6518
 F: 561.494.1116
 EMAIL: [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 04-09-2018 Cont ID  
Sent By pleduc Date 04-09-2018 Time 13:15 Rev Time 0.00
Received By pleduc Date 04-09-2018 Time 13:13 Sent To  
Notes
2018-04-09 13:15:16AFTER A REVIEW OF THE PPRC RESPONSE INFORMATION PACKET
 RECEIVED FROM JOHN P. ROACH, PRINCIPLE PLANNER, DATED
 APRIL 5, 2018, THE PREVIOUSLY SUBMITTED FIRE PREVENTION
 BUREAU COMMENTS APPEAR TO HAVE BEEN ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 01-05-2018 Cont ID  
Sent By pleduc Date 01-05-2018 Time   Rev Time 0.00
Received By pleduc Date 01-05-2018 Time 08:39 Sent To  
Notes
2018-01-05 08:45:29THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION SHALL TO COMPLY WITH NFPA 241. EXTRA
 ATTENTION SHALL BE GIVEN TO THE PERMITTING AND LOCATION
 OF CONSTRUCTION TRAILERS. A PERMIT IS REQUIRED FOR ANY
 CONSTRUCTION TRAILER RELATED TO THIS PROJECT.
 SEPARATION DISTANCES FROM MAIN STRUCTURES AS WELL AS
 OTHER TRAILERS SHALL BE CLOSELY MONITORED FOR THE
 REQUIREMENTS OF FIRE SPRINKLER PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. ALL EXISTING AND/OR NEW FIRE HYDRANTS PLANNED FOR
 THIS DEVELOPMENT SHALL BE CLEARLY INDICATED AND
 IDENTIFIED ON THE PLAN AND CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 7. THE 4 UNIT STRUCTURE IS DEFINED AS AN APARTMENT
 BUILDING PER NFPA 101, WHICH REQUIRES FIRE SPRINKLER
 PROTECTION.
 PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER THE
 APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 THE FIRE SPRINKLER SYSTEM IS REQUIRED TO BE MONITORED.
  
 8. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 06-07-2018 Cont ID  
Sent By rcaranci Date 06-07-2018 Time 16:24 Rev Time 0.00
Received By rcaranci Date 06-07-2018 Time 16:24 Sent To  
Notes
2018-06-07 16:24:36FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GULFSTREAM GOODWILL Z17120016
 JUNE 7, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE CALCULATIONS FOR BUFFER
 REQUIREMENTS FOR ALL PROPERTY LINES, AND PROVIDE THE
 REQUIRED TREES OR NUMBER OF SUBSTITUTE PALMS PER
 CURRENT CODE REQUIREMENTS OF SECTION 94-443(D).
 PLEASE PROVIDE CALCULATIONS FOR ALL PROPERTY LINES,
 ONLY TAMARIND SIDE WAS SUBMITTED.
  
 2. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 3. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER
 LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
  
 4. SATISFIED. PLEASE REVISE PLANT LIST TO SHOW CURRENT
 12 FOOT MINIMUM TREE SIZES REQUIRED.
 SILVER BUTTONWOOD IS STILL SHOWN AT 10 FEET. USED AS
 REQUIRED BUFFER TREES, SO MUST MEET MINIMUM CODE
 REQUIREMENT.
  
 5. SATISFIED. LANDSCAPE DATA CHART SHOWS 20 TREES TOTAL
 REQUIRED, BUT PLANT LIST ONLY SHOWS 18 TREES, PLEASE
 INDICATE NUMBER OF PALMS SUBSTITUTED FOR REQUIRED
 TREES.
 29 TREES AND 6 PALMS (2 TREES), PROVIDED TOTAL IS 31.
 ADDITIONAL COMMENTS 4/13/18:
 6. SATISFIED. PLEASE PROVIDE SCREENING HEDGE FOR
 BACKFLOW PREVENTERS.
  
 7. SATISFIED. PLEASE PROVIDE LARGER TREE SPECIES FOR
 THE SOUTH BUFFER. THIS LOCATION WILL PROVIDE SHADE FOR
 THE UNITS, PROVIDING ENERGY SAVINGS. DRAINAGE LINE
 LOCATION CAN BE ADJUSTED TO ALLOW MORE ROOT AREA FOR
 LARGER TREES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-13-2018 Cont ID  
Sent By rcaranci Date 04-13-2018 Time 16:29 Rev Time 0.00
Received By rcaranci Date 04-13-2018 Time 16:29 Sent To  
Notes
2018-04-13 16:30:13FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GULFSTREAM GOODWILL Z17120016
 APRIL 13, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PARTIALLY SATISFIED. PLEASE PROVIDE CALCULATIONS FOR
 BUFFER REQUIREMENTS FOR ALL PROPERTY LINES, AND PROVIDE
 THE REQUIRED TREES OR NUMBER OF SUBSTITUTE PALMS PER
 CURRENT CODE REQUIREMENTS OF SECTION 94-443(D).
 PLEASE PROVIDE CALCULATIONS FOR ALL PROPERTY LINES,
 ONLY TAMARIND SIDE WAS SUBMITTED.
  
 2. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 3. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER
 LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
  
 4. PARTIALLY SATISFIED. PLEASE REVISE PLANT LIST TO
 SHOW CURRENT 12 FOOT MINIMUM TREE SIZES REQUIRED.
 SILVER BUTTONWOOD IS STILL SHOWN AT 10 FEET. USED AS
 REQUIRED BUFFER TREES, SO MUST MEET MINIMUM CODE
 REQUIREMENT.
  
 5. PARTIALLY SATISFIED. LANDSCAPE DATA CHART SHOWS 20
 TREES TOTAL REQUIRED, BUT PLANT LIST ONLY SHOWS 18
 TREES, PLEASE INDICATE NUMBER OF PALMS SUBSTITUTED FOR
 REQUIRED TREES.
 29 TREES AND 6 PALMS (2 TREES), PROVIDED TOTAL IS 31.
 ADDITIONAL COMMENTS 4/13/18:
 6. PLEASE PROVIDE SCREENING HEDGE FOR BACKFLOW
 PREVENTERS.
  
 7. PLEASE PROVIDE LARGER TREE SPECIES FOR THE SOUTH
 BUFFER. THIS LOCATION WILL PROVIDE SHADE FOR THE UNITS,
 PROVIDING ENERGY SAVINGS. DRAINAGE LINE LOCATION CAN BE
 ADJUSTED TO ALLOW MORE ROOT AREA FOR LARGER TREES.
  
 8. PLEASE SHOW COMPLIANCE WITH SECTION 94-445 L. PLANT
 SPECIES. A MINIMUM OF 60 PERCENT OF PLANT MATERIAL
 ADDED SHALL BE FLORIDA NATIVE OR DROUGHT TOLERANT
 SPECIES SELECTED FROM THE CITY LIST OR THE LIST OF
 SPECIES IN THE MOST RECENT EDITION OF SOUTH FLORIDA
 WATER MANAGEMENT DISTRICT WATERWISE SOUTH FLORIDA
 LANDSCAPES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 01-08-2018 Cont ID  
Sent By rcaranci Date 01-08-2018 Time 15:48 Rev Time 0.00
Received By rcaranci Date 01-08-2018 Time 15:47 Sent To  
Notes
2018-01-08 15:48:42FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: GULFSTREAM GOODWILL Z17120016
 JANUARY 8, 2018
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE CALCULATIONS FOR BUFFER REQUIREMENTS
 FOR ALL PROPERTY LINES, AND PROVIDE THE REQUIRED TREES
 OR NUMBER OF SUBSTITUTE PALMS PER CURRENT CODE
 REQUIREMENTS OF SECTION 94-443(D).
  
 2. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 3. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES ON
 THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH
 LANDSCAPING.
  
 4. PLEASE REVISE PLANT LIST TO SHOW CURRENT 12 FOOT
 MINIMUM TREE SIZES REQUIRED.
  
 5. LANDSCAPE DATA CHART SHOWS 20 TREES TOTAL REQUIRED,
 BUT PLANT LIST ONLY SHOWS 18 TREES, PLEASE INDICATE
 NUMBER OF PALMS SUBSTITUTED FOR REQUIRED TREES.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.25
Received By pbieniek Date 01-09-2018 Time 08:08 Sent To  
Notes
2018-01-09 08:10:51THE SOLID WASTE COLLECTION IS APPROVED BUT RESIDENTS
 MUST PLACE CANS AT CURB.

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 01-09-2018 Cont ID  
Sent By tward Date 01-09-2018 Time 14:26 Rev Time 0.00
Received By tward Date 01-09-2018 Time 14:27 Sent To  
Notes
2018-01-09 14:27:33THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. NO ENGINEERING PLANS WERE PROVIDED.
  
 2. LABEL VERTICAL DATUM ON THE SITE PLAN.
  
 3. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 4. PROVIDE DRAINAGE IMPROVEMENTS FOR THE CURB RAMP AT
 THE NE CORNER OF TAMARIND AVE AND 20TH ST.
  
 5. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE
 AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?
  
 6. UPDATE FLOOD ZONE INFORMATION (NOTE NO. 9) ON THE
 BOUNDARY AND TOPOGRAPHIC SURVEY.
  
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION MAY
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 01-05-2018 Cont ID  
Sent By vnoel Date 01-05-2018 Time 07:05 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2018-01-05 07:18:371. NO PRELIMINARY ENGINEERING DRAWINGS.
 2. NO VERTICAL DATUM SPECIFIED.
 3. UNUSED WATER AND SEWER SERVICES WILL NEED TO BE CUT
 BACK TO MAIN.
 4. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THRU ENGINEERING SERVICES.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 01-09-2018 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2018-01-09 17:23:551) THE PROPOSED SIDEWALK ON TAMARIND IS SHOWN OUTSIDE
 OF THE RIGHT OF WAY. WHO WILL MAINTAIN THE SIDEWALK? IF
 THE CITY WILL MAINTAIN THE SIDEWALK THEN A RIGHT OF WAY
 DEDICATION IS REQUIRED.
 2) LABEL RIGHT OF WAY ON SITE PLAN.
 3) SECTION 94-305 SETBACKS TABLE X-1 CONTAINS A 40'
 ROADWAY ROADWAY RIGHT OF WAY SETBACK FROM CENTERLINE OF
 ROADWAY.
  
 ERIK D. FERGUSON, P.E.
 CITY TRANSPORTATION ENGINEER
 [email protected]
 561-494-1092

Review Stop Z ZONING
Rev No 2 Status F Date 04-16-2018 Cont ID  
Sent By jroach Date 04-16-2018 Time 14:59 Rev Time 0.00
Received By jroach Date 04-16-2018 Time 14:59 Sent To  
Notes
2018-04-16 15:05:53PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.16.2018
 PROJECT NO.: Z17120016
 CASE NO.: ISPR 17-05
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 7. THE SITE DATA TABLE SHOULD BE CORRECTED TO REFLECT
 THE FOLLOWING:
  
  A. OPEN SPACE SHOULD BE THE LOT AREA MINUS BUILDING
 COVERAGE.
  
  B. LANDSCAPING SHOULD BE ALL PERVIOUS AREA.
  
  C. IMPERVIOUS SURFACE AREA SHOULD BE ALL BUILDING
 COVERAGE, SIDEWALKS, ETC.
  
  D. BUILDING COVERAGE + OPEN SPACE = 100%
  LANDSCAPE AREA + IMPERVIOUS SURFACE AREA = 100%
  
 9. ARCHITECTURAL PLANS SHALL INCLUDE THE FOLLOWING TO
 ENSURE COMPLIANCE WITH SEC. 94-222(H) OF THE CITY?S
 ZLDRS:
  
  B. WINDOW DETAIL SHOWING THAT WINDOWS ARE RECESSED A
 MINIMUM OF TWO (2) INCHES FROM THE EXTERIOR FACE OF THE
 FACE.
  
  C. WINDOW DETAIL OR NOTE INDICATING THAT ALL WINDOWS
 WILL BE OPERABLE.
  
 12. DIMENSIONS SHALL BE PROVIDED INDICATING THE OVERALL
 HEIGHT OF THE BUILDING, AS DEFINED BY THE CITY?S ZLDRS.
  
 14. DIMENSIONS SHALL BE PROVIDED FOR THE ROOF OVERHANG
 TO ENSURE COMPLIANCE WITH SEC. 94-305(B)(2) OF THE
 CITY?S ZLDRS.
  
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 01-10-2018 Cont ID  
Sent By jroach Date 01-10-2018 Time 10:43 Rev Time 0.00
Received By jroach Date 01-10-2018 Time 10:42 Sent To  
Notes
2018-01-10 10:43:31PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 01.10.2018
 PROJECT NO.: Z17120016
 CASE NO.: ISPR 17-05
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. AN APPROVED SCHOOL CAPACITY AVAILABILITY
 DETERMINATION (SCAD) SHALL BE PROVIDED FROM THE SCHOOL
 DISTRICT OF PALM BEACH COUNTY.
  
 2. PLEASE PROVIDE A COPY OF THE TITLE ABSTRACT UTILIZED
 AND REFERENCED ON THE SURVEY.
  
 3. PLEASE PROVIDE OUTSTANDING UTILITY LETTERS (AT&T).
  
 4. WRITTEN CONFIRMATION FROM THE CITY?S PUBLIC WORKS
 DEPARTMENT SHALL BE PROVIDED INDICATING NO OBJECTION TO
 THE USE OF CAN PICK-UP AND THAT A DUMPSTER/ENCLOSURE IS
 NOT REQUIRED FOR THE PROPOSED DEVELOPMENT.
  
 5. WRITTEN CONFIRMATION FROM THE CITY?S TRAFFIC
 ENGINEER / ENGINEERING DEPARTMENT SHALL BE PROVIDED
 INDICATING APPROVAL OF THE PROPOSED ON-STREET PARKING
 CONFIGURATION AND IMPROVEMENTS. IT APPEARS THAT THE
 SIZE OF THE PARKING STALLS ARE INCORRECT AND ENCROACH
 INTO THE TRAVEL LANE ON NORTH TAMARIND AVENUE.
  
 6. DISCUSSION WITH THE CITY?S ENGINEERING DEPARTMENT
 NEEDS TO OCCUR REGARDING THE EXISTING POWER POLES AND
 THEIR ENCROACHMENT INTO THE PROPOSED SIDEWALK.
  
 7. THE SITE DATA TABLE SHOULD BE CORRECTED TO REFLECT
 THE FOLLOWING:
  
  A. OPEN SPACE SHOULD BE THE LOT AREA MINUS BUILDING
 COVERAGE.
  
  B. LANDSCAPING SHOULD BE ALL PERVIOUS AREA.
  
  C. IMPERVIOUS SURFACE AREA SHOULD BE ALL BUILDING
 COVERAGE, SIDEWALKS, ETC.
  
  D. BUILDING COVERAGE + OPEN SPACE = 100%
  LANDSCAPE AREA + IMPERVIOUS SURFACE AREA = 100%
  
 8. ELEVATIONS SHALL BE PROVIDED FOR ALL SIDES OF THE
 BUILDINGS.
  
 9. ARCHITECTURAL PLANS SHALL INCLUDE THE FOLLOWING TO
 ENSURE COMPLIANCE WITH SEC. 94-222(H) OF THE CITY?S
 ZLDRS:
  
  A. EXTERIOR FINISH MATERIAL
  
  B. WINDOW DETAIL SHOWING THAT WINDOWS ARE RECESSED A
 MINIMUM OF TWO (2) INCHES FROM THE EXTERIOR FACE OF THE
 FACE.
  
  C. WINDOW DETAIL OR NOTE INDICATING THAT ALL WINDOWS
 WILL BE OPERABLE.
  
 10. PURSUANT TO SEC. 94-222(H) OF THE CITY?S ZLDRS, IF
 SHUTTERS ARE PROPOSED, THEY ARE TO BE OPERABLE, SIZED
 TO MATCH THE OPENING, AND PROVIDED FOR ALL WINDOWS ON A
 GIVEN WALL.
  
 11. THERE SHOULD BE CONSISTENCY IN ARCHITECTURAL
 TREATMENT OF THE WINDOWS. AS PROPOSED, SOME WINDOWS
 HAVE SILL, OTHERS DO NOT; SOME HAVE SHUTTERS, OTHERS DO
 NOT.
  
 12. DIMENSIONS SHALL BE PROVIDED INDICATING THE OVERALL
 HEIGHT OF THE BUILDING, AS DEFINED BY THE CITY?S ZLDRS.
  
 13. DIMENSIONS SHALL BE PROVIDED INDICATING THE AMOUNT
 OF ENCROACHMENT OF THE MECHANICAL EQUIPMENT INTO THE
 SETBACK. PURSUANT TO SEC. 94-305(B)(4), MECHANICAL
 EQUIPMENT SHALL NOT ENCROACH MORE THAN FOUR (4) FEET
 INTO THE SETBACK.
  
 14. DIMENSIONS SHALL BE PROVIDED FOR THE ROOF OVERHANG
 TO ENSURE COMPLIANCE WITH SEC. 94-305(B)(2) OF THE
 CITY?S ZLDRS.
  
 15. WAS CONSIDERATION MADE OF THE FOLLOWING PREVIOUS
 RECOMMENDATIONS:
  
  A. DEEPER EAVES WITH RAFTER TAILS OR BRACKETS
  
  B. BALUSTERS/RAILINGS BETWEEN THE COLUMNS ON THE FRONT
 ENTRY INTO EACH BUILDING
  
 16. IS THERE ANY WAY TO AVOID THE NEED FOR A RAILING ON
 TOP OF THE RETAINING WALL, IN FRONT OF THE NORTHERNMOST
 BUILDING?
  
 17. ANY RAILINGS THAT ARE NECESSARY SHOULD BE
 DECORATIVE IN NATURE.
  
 18. ACCESSIBLE RAMPS WILL LIKELY NEED TO BE
 CONSTRUCTED/MAINTAINED AT THE 20TH STREET AND 21ST
 STREET INTERSECTIONS. PLEASE CONFIRM WITH THE CITY?S
 ENGINEERING DEPARTMENT.
  
 19. ACCESS BY THE RESIDENTS SHOULD BE CONSIDERED AS
 PART OF THE PLACEMENT OF THE TRASH RECEPTACLES.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  