Plan Review Details - Project Z17120011
| Plan Review Stops For Project Z17120011 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
01-09-2018 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
01-09-2018 |
Time |
23:43 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
01-09-2018 |
Time |
23:43 |
Sent To |
|
|
| Notes |
| 2018-01-09 23:50:25 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR THE BUILDING PERMIT APPLICATION. | | | | | | 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE. | | | | | | 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS, | | | FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS, | | | GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE, | | | SITE IRRIGATION, ETC. | | | | | | 5. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE | | | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, | | | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
01-08-2018 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
01-08-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
01-02-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-08 16:52:51 | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | DATE: 01/08/2018 | | | PROJECT: CARP | | | ADDRESS: 1626 OLD OKEECHOBEE RD | | | STATUS: FAILED | | | | | | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. FOLLOWING COMMENTS NEED TO BE | | | ADDRESSED PRIOR TO SITE PLAN APPROVAL: | | | | | | 1. SHOW ALL EXISTING UTILITIES WITHIN THE VICINITY OF | | | THE PROPOSED SITE AS WELL AS PROPOSED UTILITIES TO | | | SERVE THE DEVELOPMENT (LABEL SIZE AND MATERIAL OF ALL | | | PIPES AND CONDUITS ETC.); | | | | | | 2. RELOCATE DCDA AND METER FROM PARKING LOT AREA; | | | | | | 3. UPDATE TITLE BLOCK FROM 'BLVD' TO 'RD'; | | | | | | 4. EXISTING SANITARY SEWER LATERAL FROM ALPHA STREET | | | MUST BE CUT AND CAPPED AT THE MANHOLE. MANHOLE MUST BE | | | REHAB; | | | | | | 5. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH | | | AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT | | | ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED | | | DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN | | | SHEET; | | | | | | 6. ON THE LANDSCAPING PLAN, WHEN SUBMITTED IN THE NEXT | | | REVIEW PHASE, SHOW LOCATIONS OF ALL WATER METERS, | | | VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT BARRIERS MAY | | | BE REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND | | | STORMWATER, SANITARY, OR POTABLE WATER LINES. ALSO | | | CLEARLY INDICATE ALL EXISTING AND PROPOSED EASEMENTS ON | | | THE LANDSCAPE PLAN; | | | | | | 7. PLEASE ALSO SHOW ON THE LANDSCAPE PLAN, WHEN | | | SUBMITTED IN THE NEXT REVIEW PHASE, SHOW THE SIGHT | | | TRIANGLES FOR THE ALL VEHICULAR EXITS FROM THE SITE. | | | (SECTION 94-305E, CODE OF ORDINANCES); | | | | | | AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE | | | FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC | | | CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF | | | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL | | | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE | | | FOLLOWING LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND | | | SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND | | | PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO | | | VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS | | | ON THE UTILITY PLAN SHEET AS WELL; | | | | | | 4. CCTV MUST BE PROVIDED FROM MANHOLE TO MANHOLE WHERE | | | THE PROPOSED SANITARY SEWER WILL BE LOCATED. CONTACT ME | | | FOR THE MANHOLE NUMBER AND SUBMIT CD WITH THE | | | ENGINEERING DEVELOPMENT APPROVAL APPLICATION. | | | COORDINATE WITH UTILITIES O&M SANITARY SEWER | | | SUPERINTENDENT CHARLES PHOENIX PROVIDE 48-HOUR NOTICE | | | AND OBTAIN A RIGHT-OF-WAY PERMIT; | | | | | | 5. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE | | | WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN | | | AN EASEMENT WITHIN THE PROPERTY; | | | | | | 6. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE | | | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE | | | DETAIL SHEET/S DURING SUBMISSION OF THE FINAL | | | ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD | | | FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT) | | | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O | | | RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS- | | | APPLICATIONS | | | | | | 7. PLACEMENT OF THE ANY PROPOSED METER, BACKFLOW | | | PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY?S | | | STANDARD DETAILS. WATER METER SHOULD BE WITHIN THE | | | RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' JUST | | | INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND | | | ACCESSIBLE; | | | | | | 8. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT | | | TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE | | | CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER | | | PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING | | | UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL | | | ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY | | | CROSSING INFORMATION; | | | | | | 9. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE | | | EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION | | | POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE | | | LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE; | | | | | | 10. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR | | | UTILITY CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE | | | WITH 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE | | | MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL | | | LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A | | | TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH. | | | PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE | | | MILLING AND RESURFACING; | | | | | | 11. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL | | | EXISTING UTILITIES ON OLD OKEECHOBEE ROAD AND ALPHA | | | STREET INCLUDING BUT NOT LIMITED TO WATER, SEWER, GAS, | | | UNDERGROUND ELECTRIC CONDUITS, VALVES, ETC. PLEASE | | | IDENTIFY THE SOURCE OF THE AS-BUILT INFORMATION | | | UTILIZED FOR THE POTABLE WATER, SANITARY SEWER, AND | | | STORM SEWER DESIGN; | | | | | | 12. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE | | | THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM | | | BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT | | | TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA | | | TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33402 | | | (MAILING ADDRESS: PO BOX 3366) | | | P: 561.494.1108 | | | C: 561.459.6518 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
05-21-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-21-2018 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-21-2018 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2018-05-21 11:25:36 | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM PAUL | | | GREILICH, SENIOR PLANNER, DATED MAY 11, 2018, AND THE | | | DRAWING DOCUMENTS, THE PREVIOUSLY SUBMITTED FIRE | | | PREVENTION BUREAU COMMENTS APPEAR TO HAVE BEEN | | | ADDRESSED. | | | | | | HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED | | | PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR | | | APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
01-05-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
01-05-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
01-05-2018 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2018-01-05 16:10:01 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 6TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE. | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT AN | | | ADEQUATE WATER SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | THE NEW FIRE HYDRANT(S) AND FDC'S PLANNED FOR THIS | | | DEVELOPMENT ARE ACCEPTABLE. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT | | | THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS | | | AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
05-22-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-22-2018 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-22-2018 |
Time |
11:56 |
Sent To |
|
|
| Notes |
| 2018-05-22 11:56:40 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 1626 OKEECHOBEE RD Z17120011 | | | MAY 22, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE UPDATE PLAN TO CURRENT LANDSCAPE | | | CODE AS OF APRIL 21, 2017. THESE UPDATES INCLUDE TREE | | | AND FLOWERING TREE REQUIREMENTS, FLORIDA FRIENDLY | | | LANDSCAPE REQUIREMENTS, AND SUBSTITUTION OF PALM TREES. | | | | | | 2. SATISFIED. PLEASE COMPLETE THE TREE DISPOSITIONS ON | | | THE TREE INVENTORY CHART. | | | | | | 3. SATISFIED. PLEASE PROVIDE A DETAILED EXPLANATION OF | | | WHY THE LIVE OAK #20 ON SITE CANNOT BE RELOCATED. | | | | | | 4. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 5. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER | | | LINES ON THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | | | | 6. SATISFIED. REVISE CALCULATIONS OF REQUIRED TREES AND | | | SHRUBS TO CURRENT CODE, AND ADD THE REQUIRED TREES (2 | | | PER UNIT) PER SECTION 94-443(D). | | | | | | 7. SATISFIED. PLEASE CORRECT CALCULATIONS FOR BUFFER | | | TREE REQUIREMENTS FOR WEST PROPERTY LINE TO 7, AND | | | PROVIDE THE REQUIRED TREES OR NUMBER OF SUBSTITUTE | | | PALMS PER CURRENT CODE REQUIREMENTS (3:1). | | | | | | 8. SATISFIED. PLEASE SHOW THE REQUIRED HEDGE FOR THE | | | DUMPSTER ENCLOSURE. | | | | | | 9. SATISFIED. PLEASE REMOVE THE CHART LABELED DESIGN | | | OPTIONS, AS IT IS NO LONGER APPLICABLE, AND UPDATE THE | | | FLORIDA FRIENDLY LANDSCAPE OPTIONS CHART. | | | | | | 10. SATISFIED. IF THE PARKING IS TO REMAIN IN THE | | | PROPOSED LOCATION, THE TERMINAL ISLAND LANDSCAPE MUST | | | MEET CODE REQUIREMENTS. | | | | | | 11. SATISFIED. THREE ILEX CASSINE ARE SHOWN ON THE | | | PLAN, BUT NOT ON THE PLANT LIST. PLEASE REVISE. | | | 12. SATISFIED. PLEASE REVISE LANDSCAPE REQUIREMENT LIST | | | #8 LIST TO SHOW CURRENT 12 FOOT MINIMUM TREE SIZES | | | REQUIRED. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
01-08-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
01-08-2018 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
01-08-2018 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2018-01-08 11:57:39 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 1626 OKEECHOBEE RD Z17120011 | | | JANUARY 8, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE UPDATE PLAN TO CURRENT LANDSCAPE CODE AS OF | | | APRIL 21, 2017. THESE UPDATES INCLUDE TREE AND | | | FLOWERING TREE REQUIREMENTS, FLORIDA FRIENDLY LANDSCAPE | | | REQUIREMENTS, AND SUBSTITUTION OF PALM TREES. | | | | | | 2. PLEAS COMPLETE THE TREE DISPOSITIONS ON THE TREE | | | INVENTORY CHART. | | | | | | 3. PLEASE PROVIDE A DETAILED EXPLANATION OF WHY THE | | | LIVE OAK #20 ON SITE CANNOT BE RELOCATED. | | | | | | 4. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 5. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES ON | | | THE LANDSCAPE PLAN AND RESOLVE CONFLICTS WITH | | | LANDSCAPING. | | | | | | 6. REVISE CALCULATIONS OF REQUIRED TREES AND SHRUBS TO | | | CURRENT CODE, AND ADD THE REQUIRED TREES (2 PER UNIT) | | | PER SECTION 94-44 | | | | | | 7. PLEASE CORRECT CALCULATIONS FOR BUFFER TREE | | | REQUIREMENTS FOR WEST PROPERTY LINE TO 7, AND PROVIDE | | | THE REQUIRED TREES OR NUMBER OF SUBSTITUTE PALMS PER | | | CURRENT CODE REQUIREMENTS (3:1). | | | | | | 8. PLEASE SHOW THE REQUIRED HEDGE FOR THE DUMPSTER | | | ENCLOSURE. | | | | | | 9. PLEASE REMOVE THE CHART LABELED DESIGN OPTIONS, AS | | | IT IS NO LONGER APPLICABLE, AND UPDATE THE FLORIDA | | | FRIENDLY LANDSCAPE OPTIONS CHART. | | | | | | 10. IF THE PARKING IS TO REMAIN IN THE PROPOSED | | | LOCATION, THE TERMINAL ISLAND LANDSCAPE MUST MEET CODE | | | REQUIREMENTS. | | | | | | 11. THREE ILEX CASSINE ARE SHOWN ON THE PLAN, BUT NOT | | | ON THE PLANT LIST. PLEASE REVISE. | | | 12. PLEASE REVISE LANDSCAPE REQUIREMENT LIST #8 LIST TO | | | SHOW CURRENT 12 FOOT MINIMUM TREE SIZES REQUIRED. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
P |
Date |
01-09-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-09-2018 |
Time |
|
Rev Time |
1.00 |
| Received By |
|
Date |
01-08-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-09 08:34:50 | THE ENCLOSURE NEEDS TO HAVE PIN HOLES TO HOLD THE GATES | | | OPEN WHILE SERVICEING THE CONTAINER. |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
05-17-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-17-2018 |
Time |
12:44 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-17-2018 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2018-05-17 13:02:43 | THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE MAY | | | 13, 2018 SUBMITTAL PACKAGE. COMMENTS # 1- 10 REFER TO | | | WHETHER OR NOT THE COMMENTS FROM THE INITIAL STORM | | | REVIEW WERE ADDRESSED IN THIS SUBMITTAL. | | | | | | 1. SURVEY IDENTIFIES THE PROJECT BEING WITHIN FEMA | | | FLOOD ZONE 'X', WHICH IS NOT A SPECIAL FLOOD HAZARD | | | AREA. | | | | | | 2. COMMENT SATISFIED. | | | | | | 3. VERTICAL DATUM IS LISTED AS NAVD 1988. THE CITY'S | | | VERTICAL DATUM IS NGVD 1929. THE CITY WILL ALLOW THE | | | USE OF NAVD 1988 PROVIDED A CONVERSION TO NGVD 19219 IS | | | SHOWN ON THE PLANS AND SURVEY. | | | | | | 4. COMMENT NOT ADDRESSED. ONLY SHEET C-1 OF SIX CIVIL | | | ENGINEERING SHEETS WAS PROVIDED. | | | | | | 5. COMMENT SATISFIED. | | | | | | 6. ADD "MIN. 3 FEET' HORIZONTAL DIMENSION NOTES BETWEEN | | | WATER MAINS AND DRAINAGE STRUCTURES / PIPES. | | | | | | 7. NO CALCULATIONS PROVIDED. THESE CAN BE SUBMITTED | | | WITH THE ENGINEERING PERMIT APPLICATION. | | | | | | 8. PROVIDE GRADING ARROWS TO THE PLAN SHEET TO INDICATE | | | SWALE DOES NOT DRAIN TO ADJACENT PROPERTY. | | | | | | 9. PROVIDE A TYPICAL CROSS SECTION EXTENDING FROM THE | | | CENTERLINE OF OKEECHOBEE TO THE BACK OF WALK SHOWING | | | PROPOSED GRADE BREAKS, DIMENSIONS, SLOPES. | | | | | | 10. NO LIMITS OR NOTES REGARDING MILLING AND OVERLAY | | | PROVIDED ON THE ENGINEERING PLAN SHEET. | | | | | | 11. THE SEWER LATERAL ON ALPHA ROAD IS TO BE REMOVED | | | AND CAPPED AT THE MAIN BY THE CONTRACTOR. REVISE THE | | | NOTE ON SHEET C-1 TO INDICATE THIS. ALPHA ROAD TO BE | | | MILLED AND OVERLAID PER THE CITY DETAIL. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
01-09-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
01-09-2018 |
Time |
14:38 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
01-09-2018 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2018-01-09 14:39:56 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE | | | BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD | | | HAZARD AREA ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE | | | AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX? | | | | | | 2. UPDATE THE FLOOD INFORMATION ON THE BOUNDARY AND | | | TOPOGRAPHIC SURVEY AND POSSIBLY ON THE SITE PLAN (SHEET | | | A-1). | | | | | | 3. LABEL THE VERTICAL DATUM ON THE ENGINEERING PLANS. | | | | | | 4. USE THE CITY?S TRENCH-BACKFILL-PAVEMENT RESTORATION | | | DETAIL (GC-9) IN LIEU OF THE PAVEMENT REPAIR DETAIL ON | | | SHEET C-5. | | | | | | 5. SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | 6. PROVIDE MORE HORIZONTAL CLEARANCE BETWEEN THE | | | PROPOSED CATCH BASINS AND FIRE LINE / WATER SERVICE | | | LINE. | | | | | | 7. STORMWATER MANAGEMENT SYSTEM TO BE DESIGNED TO MEET | | | SFWMD CRITERIA INCLUDING WATER QUALITY TREATMENT AND | | | PEAK DISCHARGE. | | | | | | 8. PROVIDE A SWALE ALONG THE EAST PROPERTY LINE TO | | | COLLECT THE STORMWATER RUNOFF BEFORE IT FLOWS ONTO THE | | | ADJACENT PROPERTY. | | | | | | 9. PARKING ALONG OKEECHOBEE ROAD MAY REQUIRE A ?DEEPER? | | | SWALE TO COLLECT THE STORMWATER RUNOFF AND DIRECT IT TO | | | THE INTERNAL CATCH BASINS BEFORE IT FLOWS INTO THE | | | OKEECHOBEE ROAD R/W. | | | | | | 10. SHOW ON THE ENGINEERING PLANS THE MILL AND | | | RESURFACE LIMITS FOR THE TRENCH REPAIR IN THE RIGHT-OF | | | WAY PER CITY DETAIL GC-9. | | | | | | | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
05-30-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
05-30-2018 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
01-05-2018 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
01-05-2018 |
Time |
08:00 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-05 08:18:23 | 1. DUMPSTER DETAIL NOT CITY STANDARD. APPROVAL OF | | | DETAIL AND LOCATION WILL BE REQUIRED BY PUBLIC WORKS. | | | 2. NOTE #7 SAYS SURVEY IS NOT VALID FOR DESIGN? | | | 3. NO VERTICAL DATUM SPECIFIED ON ENG. PLANS. | | | 4. SURVEY SHOULD BE ABSTRACTED FOR EASEMENTS; APPEARS | | | TO BE POLE LINE ALONG EAST PROPERTY LINE. | | | 5. SITE/CIVIL PLANS WILL NEED TO BE SUBMITTED THRU | | | ENGINEERING. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
05-25-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-25 17:05:22 | - APPLICANT'S MAY 13 LETTER STATES THAT BACK OUT | | | PARKING HAS BEEN APPROVED. THE TRAFFIC DIVISION HAS NOT | | | APPROVED BACK OUT PARKING INTO THE PUBLIC RIGHT OF WAY. | | | - SIDEWALK ON OLD OKEECHOBEE ROAD NEEDS TO CONNECT TO | | | PUBLIC RIGHT OF WAY. | | | | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER | | | 561-494-1092 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
01-10-2018 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-01-10 09:06:42 | 1) BACK OUT PARKING INTO THE RIGHT OF WAY IS NOT | | | ALLOWED. | | | 2) PROPOSED SIDEWALK ALONG OKEECHOBEE IS OUTSIDE OF THE | | | RIGHT OF WAY. WHO WILL MAINTAIN THE SIDEWALK? SIDEWALK | | | NEEDS TO BE ACCESIBLE TO THE PUBLIC. | | | 3) SIDEWALK ALONG OKEECHOBEE NEEDS TO BE RUN ALONG THE | | | ENTIRE FRONTAGE. | | | 4) TRAFFIC IMPACT STATEMENT WASN'T INCLUDED IN PACKET | | | SENT TO ENGINEERING. | | | | | | ERIK D. FERGUSON, P.E. | | | CITY TRANSPORTATION ENGINEER | | | [email protected] | | | 561-494-1092 | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
05-18-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
05-18-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
05-18-2018 |
Time |
09:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
01-09-2018 |
|
|
Cont ID |
|
| Sent By |
|
Date |
01-09-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pgreilic |
Date |
01-09-2018 |
Time |
12:35 |
Sent To |
|
|
| Notes |
| 2018-01-09 12:37:30 | Z17120011 | | | FSPR 17-12 | | | 1626 OKEECHOBEE ROAD | | | | | | 1.) PARKING SPACES CANNOT ENTER AND EXIT DIRECTLY ONTO | | | ADJACENT ROW. CONSIDER RELOCATING PARKING SPACES TO | | | FRONT OF THE SITE (NARROWEST LOT LINE ABUTTING ROW, IN | | | THIS CASE OFF OF ALPHA ROAD) WITH INGRESS/EGRESS OFF OF | | | ALPHA ROAD. CONSIDER REDUCED PARKING SPACES OR ANGLED | | | PARKING TO MAXIMIZE THIS PORTION OF THE SITE. | | | | | | 2.) LABEL DISTANCE BETWEEN PRIMARY STRUCTURE AND | | | ACCESSORY BUILDING | | | | | | 3.) PLEASE INCLUDE ACCURATE AND UP TO DATE CITY | | | APPROVED DETAILS FOR BIKE RACK, DUMPSTER, AND STRIPING | | | FOR PARKING STALLS | | | | | | 4.) PROVIDE SIDEWALK TO ENABLE PEDESTRIAN ACCESS | | | | | | -WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN | | | (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF | | | FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE | | | RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS | | | TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL | | | COMMENTS. | | | | | | -PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUTE TO NOT BE SUFFIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGNAL APPLICATION FEE. | | | | | | -PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THE PPRC MEETING, THE CASE SHALL BE | | | CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE | | | A NEW DEVELOPMENT APPLICATION. | | | | | | | | | PAUL GREILICH, AICP, SENIOR PLANNER | | | 561-822-1443 | | | [email protected] | | | | | | |
|
|
| |