Plan Review Details - Project Z17080018
| Plan Review Stops For Project Z17080018 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
09-19-2017 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
09-19-2017 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
09-19-2017 |
Time |
19:19 |
Sent To |
|
|
| Notes |
| 2017-09-19 19:23:26 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT, | | | THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR | | | THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT, | | | AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE | | | FLORIDA BUILDING CODE | | | | | | 3. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND | | | OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT, | | | COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF | | | OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF | | | CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE | | | VERIFIED. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 5. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE | | | ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO, | | | GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL: | | | [email protected] | | | | | | 6. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES | | | (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF | | | PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT | | | SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT | | | (561) 822-1521, OR BY EMAIL: [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
3 |
Status |
P |
Date |
10-27-2017 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
10-27-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
10-27-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-27 11:32:46 | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | DATE: 10/27/2017 | | | PROJECT: GEORGIAN GARDENS APARTMENT | | | ADDRESS: 4330 COMMUNITY DRIVE | | | STATUS: PASSED WITH CONDITIONS | | | | | | IN THE NEXT PHASE, THE FOLLOWING GENERAL COMMENTS MUST | | | BE ADDRESSED PRIOR TO ISSUANCE OF CONSTRUCTION | | | AUTHORIZATION INCLUDING BUILDING PERMITS AND | | | ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC | | | CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF | | | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL | | | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE | | | FOLLOWING LINK: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING- | | | PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 3. PLACEMENT OF ANY PROPOSED METER, BACKFLOW PREVENTER, | | | DCDA, CITY'S POINT OF SERVICE, ETC. SHALL BE INSTALLED | | | PER THE CITY'S STANDARD DETAILS. WATER METER SHOULD BE | | | WITHIN THE RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' | | | JUST INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND | | | ACCESSIBLE; | | | | | | 4. RELOCATE THE WEST FIRE HYDRANT AND FIRE LINE WITHIN | | | ADJACENT PROPERTY LIMITS; | | | | | | 5. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND | | | SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND | | | PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO | | | VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS | | | ON THE UTILITY PLAN SHEET AS WELL; | | | | | | 6. SHOW ON THE FINAL PLANS WHERE ARE THE PROPOSED WATER | | | AND SANITARY SEWER LINES ARE CONNECTED TO EXISTING | | | WATER AND SEWER MAINS; | | | | | | 7. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE | | | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE | | | DETAIL SHEET/S DURING SUBMISSION OF THE FINAL | | | ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD | | | FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT) | | | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O | | | RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS- | | | APPLICATIONS | | | | | | 8. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT | | | TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE | | | CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER | | | PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING | | | UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL | | | ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY | | | CROSSING INFORMATION; | | | | | | 9. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE | | | EXISTING SANITARY SEWER; | | | | | | 10. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR | | | UTILITY CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE | | | WITH 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE | | | MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL | | | LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A | | | TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH. | | | PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE | | | MILLING AND RESURFACING; | | | | | | 11. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL | | | EXISTING UTILITIES ON COMMUNITY DRIVE INCLUDING BUT NOT | | | LIMITED TO WATER, SEWER, GAS, UNDERGROUND ELECTRIC | | | CONDUITS ETC. PLEASE IDENTIFY THE SOURCE OF THE | | | AS-BUILT INFORMATION UTILIZED FOR THE POTABLE WATER, | | | SANITARY SEWER, AND STORM SEWER DESIGN; | | | | | | 12. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE | | | THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM | | | BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT | | | TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA | | | TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | 13. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE | | | WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN | | | AN EASEMENT WITHIN THE PROPERTY; | | | | | | 14. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH | | | AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT | | | ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED | | | DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN | | | SHEET; | | | | | | 15. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE | | | CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN | | | THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY | | | BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY | | | DESIGN; | | | | | | 16. ON THE LANDSCAPING PLAN, ROOT BARRIERS MAY BE | | | REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND | | | STORMWATER, SANITARY, OR POTABLE WATER LINES; | | | | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33402 | | | (MAILING ADDRESS: PO BOX 3366) | | | P: 561.494.1108 | | | C: 561.459.6518 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
F |
Date |
10-06-2017 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
10-06-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
10-05-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-06 14:25:21 | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | DATE: 10/06/2017 | | | PROJECT: GEORGIAN GARDENS APARTMENT | | | ADDRESS: 4330 COMMUNITY DRIVE | | | STATUS: FAILED | | | | | | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. FOLLOWING COMMENTS NEED TO BE | | | ADDRESSED PRIOR TO SITE PLAN APPROVAL: | | | | | | 1. NOTE NO. 2 SHOULD SAY, 'ALL WATER AND WASTEWATER | | | CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE CITY OF | | | WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT...' | | | | | | 2. PLACEMENT OF ANY PROPOSED METER, BACKFLOW PREVENTER, | | | DCDA, CITY?S POINT OF SERVICE, ETC. SHALL BE INSTALLED | | | PER THE CITY?S STANDARD DETAILS. WATER METER SHOULD BE | | | WITHIN THE RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' | | | JUST INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND | | | ACCESSIBLE; | | | | | | 3. AS-BUILTS SHOWS ANOTHER 8-INCH SANITARY SEWER PIPE | | | WITH A MANHOLE ON THE SOUTH SIDE OF THE PROPERTY | | | CONNECTING TO THE ADJACENT PROPERTY'S LIFT STATION. | | | NEEDS TO BE VERIFIED AND FOR AS-BUILT INFORMATION | | | CONTACT JANICE TARBILL AT [email protected]; | | | | | | 4. CHANGE DDCV TO DCDA AND RPZ TO RPPA; | | | | | | 5. CITY DOES NOT ALLOW DIRECTIONAL BORE OF UTILITIES | | | WILL NEED TO REFER TO CITY STANDARD DETAIL P-4 | | | TRENCH-BACKFILL-PAVEMENT RESTORATION; | | | | | | 6. THE CITY WILL NEED A COPY OF THE AGREEMENT WHICH | | | ALLOWS GEORGIAN GARDENS TO CONNECT TO THE ADJACENT | | | PROPERTY'S FIRE LINE AND DRIVEWAY; | | | | | | 7. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH | | | AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT | | | ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED | | | DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN | | | SHEET; | | | | | | 8. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE | | | CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN | | | THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY | | | BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY | | | DESIGN; | | | | | | 9. ON THE LANDSCAPING PLAN, ROOT BARRIERS MAY BE | | | REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND | | | STORMWATER, SANITARY, OR POTABLE WATER LINES; | | | | | | AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE | | | FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC | | | CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF | | | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL | | | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE | | | FOLLOWING LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND | | | SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND | | | PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO | | | VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS | | | ON THE UTILITY PLAN SHEET AS WELL; | | | | | | 4. SHOW ON THE FINAL PLANS WHERE ARE THE PROPOSED WATER | | | AND SANITARY SEWER LINES ARE CONNECTED TO EXISTING | | | WATER AND SEWER MAINS; | | | | | | 5. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE | | | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE | | | DETAIL SHEET/S DURING SUBMISSION OF THE FINAL | | | ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD | | | FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT) | | | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: HTTP://WPB.O | | | RG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS- | | | APPLICATIONS | | | | | | 6. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT | | | TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE | | | CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER | | | PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING | | | UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL | | | ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY | | | CROSSING INFORMATION; | | | | | | 7. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE | | | EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION | | | POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE | | | LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE; | | | | | | 8. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR UTILITY | | | CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE WITH | | | 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE | | | MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL | | | LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A | | | TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH. | | | PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE | | | MILLING AND RESURFACING; | | | | | | 9. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL | | | EXISTING UTILITIES ON COMMUNITY DRIVE INCLUDING BUT NOT | | | LIMITED TO WATER, SEWER, GAS, UNDERGROUND ELECTRIC | | | CONDUITS ETC. PLEASE IDENTIFY THE SOURCE OF THE | | | AS-BUILT INFORMATION UTILIZED FOR THE POTABLE WATER, | | | SANITARY SEWER, AND STORM SEWER DESIGN; | | | | | | 10. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE | | | THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM | | | BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT | | | TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA | | | TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | 11. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE | | | WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN | | | AN EASEMENT WITHIN THE PROPERTY. | | | | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33402 | | | (MAILING ADDRESS: PO BOX 3366) | | | P: 561.494.1108 | | | C: 561.459.6518 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
09-14-2017 |
|
|
Cont ID |
|
| Sent By |
squinone |
Date |
09-14-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
squinone |
Date |
09-14-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-09-14 14:10:51 | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | DATE: 09/20/2017 | | | PROJECT: GEORGIAN GARDENS APARTMENT | | | ADDRESS: 4330 COMMUNITY DRIVE | | | STATUS: FAILED | | | | | | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | NO CIVIL ENGINEERING PLANS WERE SUBMITTED IN THE | | | INITIAL SITE PLAN PACKAGE INDICATING STORMWATER CONTROL | | | AND PLANS FOR WATER AND SEWER SERVICES/CONNECTIONS FOR | | | THE PROPOSED DEVELOPMENT. FOLLOWING COMMENTS NEED TO BE | | | ADDRESSED PRIOR TO SITE PLAN APPROVAL: | | | | | | 1. PLEASE SHOW ON THE PLANS, IN THE NEXT REVIEW LEVEL, | | | HOW WILL THE SITE/BUILDING BE SERVED FOR WATER, SEWER | | | AND FIRE PROTECTION. SHOW ALL EXISTING UTILITIES WITHIN | | | THE VICINITY OF THE PROPOSED SITE AS WELL AS PROPOSED | | | UTILITIES TO SERVE THE DEVELOPMENT (LABEL SIZE AND | | | MATERIAL OF ALL PIPES AND CONDUITS ETC.); | | | | | | 2. SUBMIT ESTIMATES FOR WATER AND FIRE DEMAND, BOTH | | | AVERAGE AND PEAK FLOW WITH PEAKING FACTOR. ALSO SUBMIT | | | ESTIMATES OF SANITARY SEWER FLOW FOR THE PROPOSED | | | DEVELOPMENT. SHOW PROJECTED DEMANDS ON THE UTILITY PLAN | | | SHEET; | | | | | | 3. THE AVAILABLE WATER PRESSURE IN THIS PORTION OF THE | | | CITY MAY NOT BE ACCEPTABLE AT ELEVATIONS HIGHER THAN | | | THE 2ND FLOOR. WE RECOMMEND A LONG-TERM PRESSURE STUDY | | | BE PERFORMED PRIOR TO FINALIZATION OF THE UTILITY | | | DESIGN; | | | | | | 4. ON THE LANDSCAPING PLAN, WHEN SUBMITTED IN THE NEXT | | | REVIEW PHASE, SHOW LOCATIONS OF ALL WATER METERS, | | | VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT BARRIERS MAY | | | BE REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND | | | STORMWATER, SANITARY, OR POTABLE WATER LINES. ALSO | | | CLEARLY INDICATE ALL EXISTING AND PROPOSED EASEMENTS ON | | | THE LANDSCAPE PLAN; | | | | | | 5. PLEASE ALSO SHOW ON THE LANDSCAPE PLAN, WHEN | | | SUBMITTED IN THE NEXT REVIEW PHASE, SHOW THE SIGHT | | | TRIANGLES DIMENSIONS FOR THE ALL VEHICULAR EXITS FROM | | | THE SITE. (SECTION 94-305E, CODE OF ORDINANCES); | | | | | | 6. SHOW ON THE SITE PLANS ADA ACCESSIBLE RAMPS ON THE | | | SIDEWALK AT EACH ENTRANCE AND EXIT /DRIVEWAY APPROACH; | | | | | | 7. PLEASE SUBMIT ESTIMATES FOR THE SOLID WASTE | | | COLLECTION YARDAGE AT THE CONCEPTUAL STAGE. AS PART OF | | | THE FINAL DESIGN, THIS SOLID WASTE ESTIMATE WILL NEED | | | TO BE VERIFIED TO VALIDATE APPROPRIATE NUMBER AND SIZE | | | OF DUMPSTERS/GARBAGE RECEPTACLES. PLEASE SHOW ON THE | | | PLAN IF A COMPACTOR IS PROPOSED TO REDUCE THE YARDAGE | | | OF WASTE THAT WILL NEED TO BE COLLECTED; | | | | | | 8. FOR SANITATION/GARBAGE COLLECTION CONTACT THE CITY?S | | | PUBLIC WORKS DEPARTMENT. FINAL APPROVED SITE PLANS NEED | | | TO SHOW PROPOSED SANITATION COLLECTION PLANS AND | | | DETAILS; AND WILL NEED APPROVAL FROM PETER BIENIEK, | | | PUBLIC WORKS DIRECTOR. IF A SEPARATE ON-SITE LOCATION | | | IS CHOSEN FOR STANDARD DUMPSTER, PLEASE INCLUDE THE | | | CITY OF WEST PALM BEACH STANDARD DETAIL FOR THE | | | DUMPSTER ENCLOSURE ON THE PLANS. MINIMUM DIMENSIONAL | | | (E.G. THE GATE WIDTH MUST BE A MINIMUM OF 12.5 FEET) | | | REQUIREMENTS FOR THE ENCLOSURE ARE LISTED IN CODE OF | | | ORDINANCES, SECTION 94-444(B) OF THE CODE OF | | | ORDINANCES. CITY STANDARD DETAIL GC-8 MAY BE DOWNLOADED | | | AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS | | | /FORMS,-PERMITS-APPLICATIONS | | | | | | 9. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING | | | THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS AND | | | MANEUVER WITHIN THE PROPOSED DEVELOPMENT. | | | | | | AFTER THE SITE PLAN IS APPROVED, IN THE NEXT PHASE, THE | | | FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 2. PLEASE SUBMIT THE LATEST VERSION OF THE ?AUTO-CALC | | | CERTIFIED COST ESTIMATE FORM? FOR SUBMISSION TO CITY OF | | | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL | | | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE | | | FOLLOWING LINK: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND | | | SANITARY SEWER CALCULATION (IN DETAIL I.E. AVERAGE AND | | | PEAK WITH PEAKING FACTOR). SUBMIT CALCULATIONS TO | | | VALIDATE METER SIZE SELECTION. SHOW THESE CALCULATIONS | | | ON THE UTILITY PLAN SHEET AS WELL; | | | | | | 4. SHOW ON THE FINAL PLANS WHERE ARE THE PROPOSED WATER | | | AND SANITARY SEWER LINES ARE CONNECTED TO EXISTING | | | WATER AND SEWER MAINS; | | | | | | 5. SHOW THE NEAREST FIRE HYDRANT TO THIS SITE ON THE | | | FINAL UTILITY PLAN. FIRE HYDRANT FLOW TEST DATA FROM | | | EXISTING FIRE HYDRANT WILL BE REQUIRED PART OF THE PLAN | | | SUBMITTAL. SHOW HYDRANT FLOW TEST DATA RESULT ON THE | | | PLANS; | | | | | | 6. FIRE HYDRANT TEST CAN BE REQUESTED AT (561)804-4700 | | | | | | 7. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE | | | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE | | | DETAIL SHEET/S DURING SUBMISSION OF THE FINAL | | | ENGINEERING PLANS. CONTACT THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD | | | FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT) | | | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 8. PLACEMENT OF THE ANY PROPOSED METER, BACKFLOW | | | PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY?S | | | STANDARD DETAILS. WATER METER SHOULD BE WITHIN THE | | | RIGHT-OF-WAY OR INSIDE AN 'UTILITY EASEMENT' JUST | | | INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND | | | ACCESSIBLE; | | | | | | 9. IN THE FINAL PLANS, MUST PROVIDE UTILITY CONFLICT | | | TABLE (BOTTOM AND TOP OF CROSSING PIPES) AT THE | | | CONFLICT POINTS OF ALL WATER, STORM AND SANITARY SEWER | | | PIPES AS WELL AS OTHER FRANCHISE UTILITIES. EXISTING | | | UTILITIES WITHIN THE PROPOSED SANITARY SEWER LATERAL | | | ARE TO BE VERIFIED VIA SOFTDIGS, PROVIDE ALL UTILITY | | | CROSSING INFORMATION; | | | | | | 10. IN THE FINAL PLANS, SHOW DIRECTION OF FLOW FOR THE | | | EXISTING SANITARY SEWER. SHOW INVERT AT CONNECTION | | | POINTS AND INCLUDE A PROFILE FOR THE PROPOSED SERVICE | | | LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE; | | | | | | 11. PAVEMENT RESTORATION FOR OPEN CUT/TRENCH FOR | | | UTILITY CONNECTION WORKS WILL NEED TO BE IN ACCORDANCE | | | WITH 2016 CITY STANDARD DETAIL GC-9. THE ROAD SHALL BE | | | MILLED/RESURFACED FOR FULL LANE WIDTH OF THE TRAVEL | | | LANE(S) ENCROACHED BY THE TRENCH AREA, INCLUDING A | | | TRANSITION AREA OF 50 FEET ON EACH SIDE OF THE TRENCH. | | | PLEASE SHOW ON THE FINAL PLANS THE EXTENT OF THE | | | MILLING AND RESURFACING; | | | | | | 12. SHOW ON THE FINAL PLANS SIZE AND MATERIAL OF ALL | | | EXISTING UTILITIES ON COMMUNITY DRIVE INCLUDING BUT NOT | | | LIMITED TO WATER, SEWER, GAS, UNDERGROUND ELECTRIC | | | CONDUITS ETC. PLEASE IDENTIFY THE SOURCE OF THE | | | AS-BUILT INFORMATION UTILIZED FOR THE POTABLE WATER, | | | SANITARY SEWER, AND STORM SEWER DESIGN; | | | | | | 13. FOR THE FINAL WATER AND SEWER PLANS, INCLUDE A NOTE | | | THAT: AS OF DECEMBER 20, 2015 THE CITY OF WEST PALM | | | BEACH CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED, | | | MAKING KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD | | | FREE." FOR MORE INFORMATION REFER TO THE LINK BELOW: HT | | | TP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICA | | | TIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | 14. ALL PROPOSED FIRE DEPARTMENT CONNECTIONS SHALL BE | | | WITHIN 100 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN | | | AN EASEMENT WITHIN THE PROPERTY. | | | | | | SOFIA QUINONES-BENEJAM, EI | | | PROJECT ENGINEER | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS STREET, 4TH FLOOR | | | WEST PALM BEACH, FL 33402 | | | (MAILING ADDRESS: PO BOX 3366) | | | P: 561.494.1108 | | | C: 561.459.6518 | | | F: 561.494.1116 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
05-08-2018 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
05-08-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
05-08-2018 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2018-05-08 16:42:55 | 3RD REVIEW RESPONSE | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM LINDA | | | LOUIE, PLANNER, AND THE ATTACHMENT DATED MAY 2, 2018, | | | THE PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU | | | COMMENTS APPEAR TO HAVE BEEN ADDRESSED. | | | | | | HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED | | | PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR | | | APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
10-05-2017 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
10-05-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
10-05-2017 |
Time |
16:21 |
Sent To |
|
|
| Notes |
| 2017-10-05 16:32:06 | 2ND REVIEW RESPONSE | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED | | | OCTOBER 4, 2017, FROM GUNSTER, YOAKLEY & STEWARD, P.A., | | | TO LINDA LOUIE, PLANNER, THE PREVIOUSLY SUBMITTED FIRE | | | PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED. | | | | | | THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES | | | NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
09-13-2017 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
09-13-2017 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
09-13-2017 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2017-09-13 14:13:06 | THE FOLLOWING COMMENTS WERE SUBMITTED BY SUE ELLEN | | | CALDERON, ASST. FIRE MARSHAL, BUREAU OF FIRE | | | PREVENTION, WEST PALM BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | 7. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | 8. ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | 10. PER FLORIDA ADMINISTRATIVE CODE SECTION | | | 61G15-32.004, FIRE PROTECTION ENGINEERING DOCUMENTS | | | SHALL INCLUDE THE POINT OF SERVICE FOR THE WATER | | | SUPPLY, A LIST OF APPLICABLE NFPA STANDARDS APPLICABLE | | | TO THE PROJECT, CLASSIFICATION OF HAZARD OCCUPANCY FOR | | | EACH ROOM OR AREA, SUPPRESSION SYSTEM TYPE, DESIGN | | | DENSITIES, WATER SUPPLY DATA (FIRE PUMP DATA, HYDRANT | | | FLOW TEST DATA) AND ANY PERFORMANCE BASED INFORMATION | | | SUCH AS PRE-ENGINEERED SYSTEMS. | | | | | | 11. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | SUE ELLEN CALDERON | | | ASST. FIRE MARSHAL | | | [email protected] | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
06-14-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-14-2018 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-14-2018 |
Time |
15:20 |
Sent To |
|
|
| Notes |
| 2018-06-14 15:21:24 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: GEORGIAN GARDENS Z17080018 | | | JUNE 14, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | 1. COMMENTS 1 THROUGH 9 PREVIOUSLY SATISFIED. | | | 2. SATISFIED. | | | 3. SATISFIED. | | | 4. SATISFIED. | | | 5. SATISFIED. | | | 6. SATISFIED. | | | 7. SATISFIED. | | | 8. SATISFIED. | | | 9. SATISFIED. | | | ADDITIONAL COMMENT 5/21/18: | | | 10. SATISFIED. PLEASE RESTORE THE SHADE TREES AS | | | REQUIRED IN THE PARKING AREA LANDSCAPE ISLANDS. | | | LIGUSTRUM DOES NOT QUALIFY AS A SHADE TREE PER CITY | | | CODE. UTILITY LINES ARE SPACED FAR ENOUGH AWAY TO ALLOW | | | ROOT BARRIER PLACEMENT TO BE SHOWN ON THE LANDSCAPE | | | PLAN. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
05-21-2018 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-21-2018 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-21-2018 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2018-05-21 11:01:53 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | MEMO TO FILE | | | PROJECT: GEORGIAN GARDENS Z17080018 | | | MAY 21, 2018 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | 1. COMMENTS 1 THROUGH 9 PREVIOUSLY SATISFIED. | | | 2. SATISFIED. | | | 3. SATISFIED. | | | 4. SATISFIED. | | | 5. SATISFIED. | | | 6. SATISFIED. | | | 7. SATISFIED. | | | 8. SATISFIED. | | | 9. SATISFIED. | | | ADDITIONAL COMMENT 5/21/18: | | | 10. PLEASE RESTORE THE SHADE TREES AS REQUIRED IN THE | | | PARKING AREA LANDSCAPE ISLANDS. LIGUSTRUM DOES NOT | | | QUALIFY AS A SHADE TREE PER CITY CODE. UTILITY LINES | | | ARE SPACED FAR ENOUGH AWAY TO ALLOW ROOT BARRIER | | | PLACEMENT TO BE SHOWN ON THE LANDSCAPE PLAN. | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
10-27-2017 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
10-27-2017 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
10-27-2017 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2017-10-27 15:09:19 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | MEMO TO FILE | | | PROJECT: GEORGIAN GARDENS Z17080018 | | | OCTOBER 27, 2017 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. PLEASE PROVIDE A TREE SURVEY AND A TREE | | | DISPOSITION LIST IDENTIFYING SPECIES AND TREE CANOPY | | | DIAMETER OF TREES AND PALMS, AND INDICATE WHETHER THEY | | | WILL REMAIN, BE RELOCATED OR REMOVED. ALL CALCULATIONS | | | AND DATA NEEDS TO BE UPDATED WHEN THE LOCATIONS AND | | | SPECIES OF TREES TO REMAIN ARE DETERMINED. | | | | | | 2. SATISFIED. PLEASE SHOW THE BUFFER REQUIREMENTS OF | | | SECTION 94-443(D)(1) ARE MET, WITH CALCULATIONS SHOWN | | | ON THE PLAN. | | | | | | 3. SATISFIED. PLEASE SHOW THE REQUIREMENTS OF ONE | | | ADDITIONAL TREE PER UNIT IS PROVIDED PER SECTION | | | 94-443(D)(2)A. | | | | | | 4. SATISFIED. PLEASE SHOW THE REQUIRED AND PROVIDED | | | PERIMETER LANDSCAPE FOR THE BUILDING PERIMETER PER | | | SECTION 94-443(D)(2)B. | | | | | | 5. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER | | | LINES AND FPL TRANSFORMERS ON THE LANDSCAPE PLAN. | | | | | | 6. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 7. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES | | | AND FPL TRANSFORMERS MUST HAVE SCREENING HEDGES. | | | | | | 8. SATISFIED. PARKING LOT LANDSCAPE AREAS MUST MEET THE | | | REQUIREMENTS OF SECTION 94-443(C)(3) AND (4). PLEASE | | | SHOW ALL CALCULATIONS AND PROVIDE A DIAGRAM SHOWING THE | | | AREAS COUNTED TOWARD THIS REQUIREMENT. | | | | | | 9. SATISFIED. PLEASE PROVIDE THE LOCATIONS OF LIGHTING | | | ON THE LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
09-06-2017 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-06-2017 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-06-2017 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2017-09-06 16:42:24 | PROJECT: GEORGIAN GARDENS Z17080018 | | | SEPTEMBER 6, 2017 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | | | | 1. PLEASE PROVIDE A TREE SURVEY AND A TREE DISPOSITION | | | LIST IDENTIFYING SPECIES AND TREE CANOPY DIAMETER OF | | | TREES AND PALMS, AND INDICATE WHETHER THEY WILL REMAIN, | | | BE RELOCATED OR REMOVED. ALL CALCULATIONS AND DATA | | | NEEDS TO BE UPDATED WHEN THE LOCATIONS AND SPECIES OF | | | TREES TO REMAIN ARE DETERMINED. | | | | | | 2. PLEASE SHOW THE BUFFER REQUIREMENTS OF SECTION | | | 94-444(D)(1) ARE MET, WITH CALCULATIONS SHOWN ON THE | | | PLAN. | | | | | | 3. PLEASE SHOW THE REQUIREMENTS OF ONE ADDITIONAL TREE | | | PER UNIT IS PROVIDED PER SECTION 94-444(D)(2)A. | | | | | | 4. PLEASE SHOW THE REQUIRED AND PROVIDED PERIMETER | | | LANDSCAPE FOR THE BUILDING PERIMETER PER SECTION | | | 94-444(D)(2)B. | | | | | | 5. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES AND | | | FPL TRANSFORMERS ON THE LANDSCAPE PLAN. | | | | | | 6. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT | | | INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES | | | WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY | | | FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS. | | | | | | 7. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED | | | EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL | | | TRANSFORMERS MUST HAVE SCREENING HEDGES. | | | | | | 8. PARKING LOT LANDSCAPE AREAS MUST MEET THE | | | REQUIREMENTS OF SECTION 94-443(C)(3) AND (4). PLEASE | | | SHOW ALL CALCULATIONS AND PROVIDE A DIAGRAM SHOWING THE | | | AREAS COUNTED TOWARD THIS REQUIREMENT. | | | | | | 9. PLEASE PROVIDE THE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO PREVENT CONFLICTS WITH TREES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
5 |
Status |
P |
Date |
06-18-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-18-2018 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-18-2018 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
F |
Date |
05-10-2018 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-10-2018 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-10-2018 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2018-05-10 18:03:24 | THE FOILLOWING COMMENTS ARE FROM THE REVIEW OF THE MAY | | | 7, 2018 SUBMITTAL PACKAGE. | | | | | | 1. THE LANDSCAPE PLANS ARE NOT SHOWING THE LATEST | | | PROPOSED UTILITIES SHOWN ON THE CIVIL PLANS. INCLUDE | | | THE ROOF DRAINAGE PIPING ON THE PLUMBING SITE PLAN . | | | | | | 2. LABEL VERTICAL DATUM ON DRAINAGE PLAN AND WATER AND | | | SEWER PLANS. PROVIDE CONVERSION EQUATION TO NGVD 1929. | | | | | | 3. IDENTIFY WHICH DRAINAGE STRUCTURE(S) WILL BE CONTROL | | | STRUCTURES FOR RESTRICTING RUNOFF DISCHARGE FROM THE | | | SITE. | | | | | | 4. DDA NEEDED AFTER THE 8" GATE VALVE ON THE WATER MAIN | | | AT THE NORTHEAST CORNER OF THE PROPERTY. THE WATER MAIN | | | AFTER THE VALVE WILL BE A PRIVATE WATER MAIN. | | | | | | TRACY WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
P |
Date |
12-13-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-13-2017 |
Time |
14:47 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-13-2017 |
Time |
15:00 |
Sent To |
|
|
| Notes |
| 2017-12-13 14:59:49 | THE COOMENTS BELOW ARE FROM THE SET OF PLANS | | | DISTRIBUTED THE WEEK OF 12/11/17: | | | | | | 1. THE SITE PLAN STILL SHOWS RETENTION POND WITH BLUE | | | COLOR FOR WATER. THE CONCEPTUAL ENGINEERING PLAN SHOWS | | | THE FEATURE AS A DRY DETENTION AREA. THE SITE PLAN WILL | | | BE CHANGED TO LABEL THE AREA AS DRY DETENTION AND THE | | | BLUE COLOR CHANGED. | | | | | | 2. THE CONCEPTUAL ENGINEERING PLAN IS NOT SHOWING THE | | | LIMITS OF THE: | | | A. UTILITY EASEMENT / RIGHT OF WAY EASEMENT ALONG THE | | | NORTH PROPERTY LINE | | | B. RIGHT OF WAY EASEMENT ALONG THE EAST PROPERTY LINE. | | | | | | THE ENGINEER HAS EMAILED TO SAY THE CONCEPTUAL | | | ENGINEERING PLAN WILL BE RESUBMITTED WITH THE EASEMENT | | | LINES SHOWN. | | | | | | 3. A FIRE HYDRANT IS SHOWN NEAR THE NORTHEAST CORNER OF | | | THE PROPERTY. THE FIRE MARSHALL HAS REQUESTED THE FIRE | | | DEPARTMENT CONNECTION BE MOVED TO BE NEAR THE FIRE | | | HYDRANT NEAR THE ENTRANCE ROAD AT THE SOUTHWEST CORNER | | | OF THE SITE. THIS CHANGE IN FDC LOCATION WILL BE MADE | | | DURING ENGINEERING PERMIT APPLICATION SUBMITTAL. THE FH | | | AT THE NORTHEAST CORNER OF THE SITE WILL NOT BE NEEDED. | | | THIS FH WILL NOT BE ON THE PLANS FOR ENGINEERING PERMIT | | | APPLICATION. | | | | | | 4. THE CONCEPTUAL ENGINEERING PLAN SHOWS THE EXISTING | | | SANITARY SEWER GOING OUTSIDE OF THE 12' EASEMENT ALONG | | | THE SOUTH PROPERTY LINE. THE SEWER SYSTEM ACTUALLY | | | TURNS SOUTH BEFORE THE END OF THE EASEMENT AND CONNECTS | | | TO THE OFFSITE SEWER MANHOLE SHOWN ON THE DRAWING. THIS | | | CAN BE CORRECTED ON THE PLANS SUBMITTED FOR ENGINEERING | | | PERMIT. | | | | | | 5. THE CONCEPTUAL ENGINEERING PLAN SHOWS A UTILITY | | | EASEMENT AROUND THE PROPOSED FIRE HYDRANT AND WATER | | | METER NEAR THE NORTHEAST CORNER OF THE PROPERTY. IF THE | | | EXISTING 10-UTILITY EASEMENT ALONG THE NORTH PROPERTY | | | LINE IS REMAINING THEN ANOTHER UTILITY EASEMENT IS NOT | | | NEEDED. THE FIRE HYDRANT AND WATER METER APPEAR TO BE | | | WITHIN THE EXISTING UTILITY EASEMENT. THE ENGINEERING | | | EMAILED TO SAY THE REVISED ENGINEERING PLAN DRAWING | | | WILL NOT SHOW THE PROPOSED UTILITY EASEMENT AROUND THE | | | WATER METER AND FIRE HYDRANT. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
10-16-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-16-2017 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
10-16-2017 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2017-10-16 16:54:46 | THE FOLLOWING COMMENTS ARE BASED UPON THE REVIEW OF THE | | | OCTOBER 5, 2017 SUBMITTAL PACKAGE. | | | | | | 1. LABEL THE VERTICAL DATUM ON THE CONCEPTUAL PAVING, | | | DRAINAGE, WATER AND WASTEWATER PLAN. IF DIFFERENT THAN | | | CITY'S VERTICAL DATUM, NGVD1929, THEN PROVIDE | | | CONVERSION FACTOR TO OBTAIN NGVD 1929. | | | | | | 2. SHOW ALL UTILITIES ON THE LANDSCAPE PLANS. THE | | | CONCEPTUAL ENGINEERING PLAN SHOWS STORM WATER PIPES | | | INTO THE DRY DETENTION AREA THAT ARE NOT SHOWN ON THE | | | LANDSCAPE PLANS. | | | | | | 3. CONCEPTUAL ENGINEERING PLAN LABELS THE OPEN FEATURE | | | IN THE SOUTHWEST CORNER OF THE SITE AS A PROPOSED DRY | | | DETENTION AREA. THE ARCHITECTURAL PLANS LABEL THE AREA | | | AS RETENTION POND. POND INDICATES PERMANENT WATERBODY | | | WHICH IS NOT THE SAME AS DRY DETENTION AREA. RETENTION | | | AND DETENTION ARE NOT THE SAME EITHER. | | | | | | 4. SFWMD HAS MINIMUM DIMENSIONAL REQUIREMENTS FOR WET | | | PONDS USED FOR WATER QUALITY TREATMENT. | | | | | | 5. SFWMD PERMIT TO BE SUBMITTED WITH ENGINEERING PERMIT | | | APPLICATION. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
09-07-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
09-07-2017 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
09-07-2017 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2017-09-07 13:20:23 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE | | | BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD | | | HAZARD AREAS WILL BE EFFECTIVE ON OCTOBER 5, 2017 IF | | | RESOLUTION PASSES AT SECOND READING BEFORE CITY | | | COMMISSION. THE MAPS ARE AVAILABLE AT | | | HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?. | | | | | | 2. NO ENGINEERING PLANS WERE PROVIDED. | | | | | | 3. DEVELOPMENT IS LOCATED IN THE C-17 DRAINAGE BASIN. | | | | | | 4. SHOW UTILITIES ON THE LANDSCAPE PLANS AND LIGHTING | | | PLANS. | | | | | | 5. CITY?S VERTICAL DATUM IS NATIONAL GEODETIC VERTICAL | | | DATUM OF 1929 (NGVD29). THE VERTICAL DATUM ON THE | | | ALTA/NSPS LAND TITLE BOUNDARY SURVEY IS NORTH AMERICAN | | | VERTICAL DATUM OF 1988 (NAVD88). PROVIDE A CONVERSION | | | FACTOR BETWEEN NAVD88 AND NGVD29 ON THE SURVEY. | | | | | | 6. PROVIDE ?NORTH? ARROW ON SHEET A0.02. | | | | | | 7. IT APPEARS THE DRIVEWAY TO THE PROPOSED DEVELOPMENT | | | IS ON A SEPARATE PARCEL OF LAND THAT IS OWNED BY | | | OTHERS. IS THERE AN ACCESS EASEMENT/AGREEMENT TO USE | | | THE DRIVEWAY. | | | | | | 8. THE SFWMD ERP PERMIT FOUND ON SFWMD?S WEBSITE | | | DOESN?T APPEAR TO MATCH WHAT WAS BUILT. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR | | | THIS PROPOSED DEVELOPMENT. | | | | | | 3. PROVIDE A COPY OF THE NPBCID PERMIT MODIFICATION FOR | | | THIS DEVELOPMENT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
3 |
Status |
P |
Date |
10-30-2017 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-30-2017 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-30 07:39:42 | PASSED WITH CONDITION OF EITHER AGREEMENT FOR | | | CONNECTION TO PRIVATE LIFT STATION OR NEW ON-SITE LIFT | | | STATION AND CONNECTION TO CITY SANITARY. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
F |
Date |
10-16-2017 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-16-2017 |
Time |
07:35 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-16 07:44:02 | 1. THIS PROPERTY FALLS WITHIN THE CITY'S SERVICE AREA | | | FOR WATER AND SEWER. THE ABILITY TO CONNECT TO THE | | | COUNTY'S FACILITIES IS NOT AN OPTION. PLEASE REVIEW AND | | | REVISE ACCORDINGLY. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
09-15-2017 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
09-15-2017 |
Time |
08:26 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-09-15 08:39:47 | 1. NO ENGINEERING PLANS PROVIDED. NEED TO REVIEW THE | | | ADJOINING PRIVATE LIFT STATION. | | | 2. NEED DUMPSTER LOCATION APPROVED BY PETER BIENIEK, | | | PUBLIC WORKS DIRECTOR. | | | 3. NEED CONVERSION FROM NAVD 88 TO NGVD 29. | | | 4. NEED COUNTY APPROVAL FOR LANDSCAPING IN UTILITY | | | EASEMENTS. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
3 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
05-14-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-14 17:04:46 | PASSED WITH CONDITION. A PALM BEACH COUNTY RIGHT OF WAY | | | PERMIT IS REQUIRED FOR MODIFICATION TO THE ENTRANCE ON | | | COMMUNITY DRIVE. | | | | | | ERIK D. FERGUSON, PE | | | CITY TRANSPORTATION ENGINEER |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
2 |
Status |
P |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
10-12-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-10-12 16:10:45 | PASSED WITH CONDITIONS: | | | 1) APPLICANT WILL WORK WITH OWNER OF ADJACENT PROPERTY | | | TO MODIFY SHARED ACCESS ENTRACE ON COMMUNITY DRIVE FOR | | | A.D.A. COMPLIANCE. NOTE THAT THE MODIFICATIONS TO THE | | | ENTRANCE WILL MOST LIKELY REQUIRE A PALM BEACH COUNTY | | | PERMIT AS COMMUNITY DRIVE IS A COUNTY ROADWAY. | | | | | | ERIK D. FERGUSON, P.E. | | | SENIOR PROJECT ENGINEER | | | 561-494-1092 | | | [email protected] |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-09-18 09:40:48 | THIS REVIEW IS PRELIMINARY AS DETAILED ENGINEERING | | | PLANS WERE NOT PROVIED. THE COMMENTS ARE AS FOLLOWS: | | | 1) PROVIDE PALM BEACH COUNTY TRAFFIC CONCURRENC LETTER. | | | 2) THE EXISTING SIDEWALK AT THE DRIVEWAY ENTRANCE DOES | | | NOT APPEAR TO BE A.D.A. COMPLIANT. PROVIDE DRIVEWAY | | | PROFILE AND CURB RAMP DETAILS WITH RESUBMITTAL. | | | | | | ERIK D. FERGUSON, P.E. | | | SENIOR PROJECT ENGINEER | | | 561-494-1092 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
06-20-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
06-20-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
06-20-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-20 15:25:12 | APPROVED WITH THE FOLLOWING CONDITIONS: | | | | | | 1.) THE DEVELOPER SHALL WORK WITH THE OWNER OF THE | | | ADJACENT PROPERTY TO MODIFY THE SHARED ACCESS ENTRANCE | | | ON COMMUNITY DRIVE FOR A.D.A. COMPLIANCE. MODIFICATION | | | TO THE ENTRANCE WILL REQUIRE A RIGHT-OF-WAY PERMIT FROM | | | PALM BEACH COUNTY, AS COMMUNITY DRIVE IS A COUNTY | | | ROADWAY. THE DEVELOPER SHALL BE REQUIRED TO OBTAIN THE | | | COUNTY RIGHT-OF-WAY PERMIT PRIOR TO THE ISSUANCE OF A | | | BUILDING PERMIT. | | | | | | 2.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 3.) PRIOR TO THE SUBMISSION OF A BUILDING PERMIT, AN | | | ENGINEERING DEVELOPMENT APPROVAL APPLICATION SHALL BE | | | REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
F |
Date |
06-11-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
06-11-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
06-11-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-06-11 14:04:17 | BELOW ARE OUTSTANDING SITE PLAN COMMENTS (PLANS REVISED | | | 6/1/18 AND SUBMITTED TO THE CITY ON 6/5/18 IN | | | ASSOCIATION WITH THE REQUEST FOR THE MAJOR PLANNED | | | DEVELOPMENT (PD) AMENDMENT, APPROVED BY THE CITY | | | COMMISSION ON 1/29/18 (ORDINANCE NO. 4757-17). | | | | | | 1.) PLEASE ADDRESS THE FOLLOWING IN THE PROJECT | | | INFORMATION TABULAR ON SHEET A0.03: THE BUILDING HEIGHT | | | INFORMATION DOES NOT MATCH THE HEIGHT PROVIDED IN THE | | | BUILDING ELEVATIONS (SHEETS A2.01 AND A2.02). THE | | | HEIGHT SHOULD READ 53'-0" TO THE TOP, AS SPECIFIED IN | | | THE ELEVATION DRAWINGS. [5/10/18 REPEAT COMMENT] | | | | | | 2.) ADD NOTE TO SEE DETAIL ON SHEET A0.05 AT THE | | | LOCATION OF THE MONUMENT SIGN ON SHEET A1.01 (SITE | | | PLAN). [5/10/18 REPEAT COMMENT] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
05-10-2018 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
05-10-2018 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
05-10-2018 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-05-10 12:27:54 | BELOW ARE OUTSTANDING SITE PLAN COMMENTS (PLANS REVISED | | | AND SUBMITTED TO CITY ON 5/3/18) IN ASSOCIATION WITH | | | THE REQUEST FOR THE MAJOR PLANNED DEVELOPMENT (PD) | | | AMENDMENT, APPROVED BY THE CITY COMMISSION ON 1/29/18 | | | (ORDINANCE NO. 4757-17). | | | | | | 1.) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE COVER | | | SHEET: LIFE SAFETY PLAN-GROUND LEVEL IS SHEET A1.06 | | | (NOT A1.07); LIFE SAFETY PLAN-TYPICAL LEVEL IS SHEET | | | A1.07 (NOT A1.05); LIFE SAFETY PLAN-ROOF LEVEL IS SHEET | | | A1.08 (NOT A1.05); TREE DISPOSITION PLAN IS SHEETS TD-1 | | | AND TD-2 (NOT TDP-1 AND TDP-2); PLUMBING SITE PLAN IS | | | SHEET P-100 (NOT MECHANICAL SITE PLAN);. | | | | | | 2.) SHEET A0.02 IS INCONSISTENT WITH THE LATEST CHANGES | | | MADE TO THE SITE PLAN (I.E. LOCATION OF THE LIGHT | | | FIXTURES, TREES IN THE MIDDLE OF THE PARKING AREA | | | PEDESTRIAN CROSSWALK, PAVED SURFACE IS SHADED GREEN | | | WITHIN THE CROSSWALK, ETC.). PLEASE ADDRESS. | | | | | | 3.) PLEASE ADDRESS THE FOLLOWING IN THE PROJECT | | | INFORMATION TABULAR ON SHEET A0.03: THE BUILDING | | | HEIGHT INFORMATION DOES NOT MATCH THE HEIGHT PROVIDED | | | IN THE BUILDING ELEVATIONS (SHEETS A2.01 AND A2.02); | | | SIDE SETBACK (WEST) IS 43'-9" (NOT 43'-9""); PLEASE | | | MODIFY THE FOOTNOTE REGARDING THE 40% REDUCTION TO | | | REFERENCE THE ZONING CODE SECTION OR ORDINANCE NO. | | | 4758-17 (THE CITY-INITIATED TEXT AMENDMENT HAS ALREADY | | | BEEN ADOPTED). | | | | | | 4.) THE BICYCLE RACK DETAIL ON SHEET A0.04 HAS BEEN | | | MODIFIED SO THAT IT IS NO LONGER CONSISTENT WITH THE | | | CITY'S BICYCLE PARKING GUIDELINES. PLEASE ADDRESS AS | | | THE WAVE RACK IS NOT PERMITTED IN THE CITY. | | | | | | 5.) PLEASE CORRECT THE PROPERTY NAME AND PROPERTY | | | ADDRESS FOR DETAIL 0.6 ON SHEET A0.05 (MONUMENT SIGN | | | DETAILS). | | | | | | 6.) ADD NOTE TO SEE DETAIL ON SHEET A0.05 AT THE | | | LOCATION OF THE MONUMENT SIGN ON SHEET A1.01 (SITE | | | PLAN). | | | | | | 7.) GENERAL SITE PLAN NOTE #5 ON SHEET A1.01 (SITE | | | PLAN), STATES THAT THE SANITARY LINE WILL BE CONNECTED | | | TO THE ADJACENT PROPERTY LIFT STATION. PER CONDITION OF | | | APPROVAL IN ORDINANCE NO. 4757-17, THE DEVELOPER SHALL | | | PROVIDE AN AGREEMENT FOR THE CONNECTION. PLEASE | | | ADDRESS. | | | | | | 8.) GENERAL SITE PLAN NOTE #12 SHOULD STATE THAT THERE | | | SHALL NOT BE ANY LANDSCAPE MATERIAL WITHIN 5 FT. OF | | | UNDERGROUND UTILITIES (NOT LOCATED WITHIN 5 FT. OF | | | UNDERGROUND UTILITIES). PLEASE CORRECT. | | | | | | 9.) ALL EXTERIOR LIGHTING SHALL BE SHIELDED TO REDUCE | | | GLARE AND SHALL BE ARRANGED TO REFLECT LIGHT OR GLARE | | | AWAY FROM ALL ADJACENT RESIDENTIAL DISTRICTS, ADJACENT | | | RESIDENCES OR PUBLIC THOROUGHFARES. PLEASE REVIEW | | | PHOTOMETRIC PLAN AND ENSURE THE PLAN DEMONSTRATES | | | COMPLIANCE. PLEASE ADD NOTE IN THE PHOTOMETRIC PLAN IF | | | CONSISTENT WITH THE ZLDR FOR EXTERIOR LIGHTING. [ZLDR | | | S.94-309(A)] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
11-21-2017 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
11-21-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
11-21-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2018-02-12 11:40:55 | CONDITIONS OF APPROVAL: | | | | | | 1.) PRIOR TO CITY COMMISION, THE APPLICANT SHALL BE | | | REQUIRED TO COMPLETE THE FOLLOWING: A) REVISE THE SITE | | | PLAN AND LANDSCAPE PLAN TO MATCH THE ENGINEERING PLAN; | | | B) ANY EXISTING AND/OR PROPOSED LANDSCAPE MATERIAL | | | WITHIN FIVE (5) FEET OF UNDERGROUND UTILITIES SHALL BE | | | RELOCATED IN THE LANDSCAPE PLAN. C) REVISE THE DETAIL | | | OF THE PERMANENT FREESTANDING IDENTIFICATION SIGN | | | LOCATED AT THE NORTHWEST CORNER OF THE PROPERTY, TO | | | COMPLY WITH THE DIMENSIONAL STANDARDS OF SECTION 94-407 | | | OF THE ZONING AND LAND DEVELOPMENT REGULATIONS (ZLDRS). | | | | | | 2.) THE SITE PLAN SHALL BE CONTINGENT ON THE APPROVAL | | | OF A CITY-INITIATED TEXT AMENDMENT TO THE ZONING AND | | | LAND DEVELOPMENT REGULATIONS (ZLDRS) TO ALLOW FOR A | | | PARKING REDUCTION OF UP TO 50 PERCENT FOR ELDERLY | | | HOUSING. FAILURE TO ADOPT THE PARKING REDUCTION INTO | | | THE ZLDRS THAT IS CONSISTENT WITH THE PROJECT (ELDERLY | | | HOUSING CONSISERED 55+) WILL TERMINATE THE APPROVAL OF | | | THE SITE PLAN. | | | | | | 3.) PRIOR TO THE SUBMISSION OF A BUILDING PERMIT, THE | | | DEVELOPER SHALL PROVIDE EITHER AN AGREEMENT FOR A | | | CONNECTION TO A PRIVATE LIFT STATION OFF-SITE, OR | | | DESIGN A NEW ON-SITE LIFT STATION AND CONNECTION TO THE | | | CITY'S SANITARY SEWER SERVICE. | | | | | | 4.) THE DEVELOPER SHALL WORK WITH THE PROPERTY OWNER OF | | | THE ADJACENT PROPERTY TO MODIFY THE SHARED ACCESS | | | ENTRANCE ON COMMUNITY DRIVE FOR A.D.A. COMPLIANCE. | | | MIODIFICATION TO THE ENTRANCE WILL REQUIRE A | | | RIGHT-OF-WAY PERMIT FROM PALM BEACH COUNTY, AS | | | COMMUNITY DRIVE IS A COUNTY ROADWAY. THE DEVELOPER | | | SHALL BE REQUIRED TO OBTAIN THE COUNTY RIGHT-OF-WAY | | | PERMIT PRIOR TO THE ISSUANCE OF A BUILDING PERMIT. | | | | | | 5.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 6.) PRIOR TO THE SUBMISSION OF A BUILDING PERMIT, AN | | | ENGINEERING DEVELOPMENT APPROVAL APPLICATION SHALL BE | | | REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
09-07-2017 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
09-07-2017 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
09-07-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-09-07 08:29:02 | GENERAL COMMENTS: | | | | | | 1.) THE APPLICATION IS SEEKING A 40 PERCENT PARKING | | | REDUCTION FROM THE CITYWIDE PARKING STANDARDS FOR | | | MULTIFAMILY RESIDENTIAL. CURRENTLY, THE PLANNING | | | DIVISION IS IN THE PROCESS OF PROCESSING A ZLDR TEXT | | | AMENDMENT THAT WOULD REDUCE THE PARKING REQUIREMENT (UP | | | TO 40%) FOR SENIOR HOUSING PROJECTS. THE SCHEDULE FOR | | | PROCESSING THE ZLDR TEXT AMENDMENT IS UNCERTAIN AT THIS | | | TIME. ACCORDING TO THE JUSTIFICATION STATEMENT, IT IS | | | THE APPLICANT?S INTENT TO PROCESS THE APPLICATION | | | ALONGSIDE WITH THE CITY-INITIATE ZLDR TEXT AMENDMENT. | | | THE APPLICANT ALSO UNDERSTANDS THAT THE SITE PLAN WILL | | | NOT BE APPROVED UNTIL THE TEXT AMENDMENT IS FORMALLY | | | ADOPTED BY THE CITY. | | | | | | 2.) PROVIDE A TRAFFIC LETTER FROM THE PALM BEACH COUNTY | | | TRAFFIC DIVISION STATING THAT THE PROPOSED PROJECT | | | MEETS THE TRAFFIC PERFORMANCE STANDARDS (TPS) OF THE | | | COUNTY. THE COUNTY LETTER APPROVING THE TPS STANDARDS | | | OF THE COUNTY SHALL BE RECEIVED BY STAFF PRIOR TO | | | SCHEDULING THE APPLICATION FOR A PUBLIC HEARING. | | | | | | 3.) PROVIDE A SCHOOL CAPACITY AVAILABILITY | | | DETERMINATION (SCAD) LETTER FROM THE SCHOOL DISTRICT OF | | | PALM BEACH COUNTY STATING THAT THE PROPOSED PROJECT | | | MEETS THE SCHOOL CONCURRENCY REQUIREMENTS OF THE | | | COUNTY. THE SCAD LETTER APPROVING SCHOOL CONCURRENCY | | | SHALL BE SUBMITTED TO STAFF PRIOR TO SCHEDULING THE | | | APPLICATION FOR A PUBLIC HEARING. | | | | | | 4.) THE SURVEY SHOWS A 10 FT. WIDE UTILITY AND ROW | | | EASEMENT ALONG THE NORTH AND EAST PROPERTY LINES. | | | ACCORDING TO ORB RECORDS, FDOT MAY HAVE AN INTEREST IN | | | THE ROW EASEMENT. THE APPLICANT WILL BE REQUIRED TO | | | OBTAIN WRITTEN DOCUMENTATION FROM FDOT AND PALM BEACH | | | COUNTY TRAFFIC (COMMUNITY DRIVE IS A COUNTY ROADWAY), | | | STATING THAT THE ROW EASEMENT IS NOT NEEDED, AS THIS | | | MAY IMPLICATE THE BUILDING SETBACK LINE ALONG THE NORTH | | | AND EAST SIDES OF THE PROPERTY. | | | | | | 5.) THE APPLICANT WILL BE RESPONSIBLE FOR THE ENVELOPES | | | AND ADDRESSED LABELS FOR THE PUBLIC NOTICE MAILERS. A | | | SIGNED AND NOTARIZED PUBLIC NOTICE MAILER AFFIDAVIT | | | WILL BE REQUIRED PRIOR TO EACH PUBLIC HEARING. | | | | | | 6.) ALL PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW | | | CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN | | | EXISTING BUILDING, WHERE THE TOTAL CONSTRUCTION COSTS | | | ARE EQUAL TO OR GREATER THAN $750,000.00 IS SUBJECT TO | | | THE ART IN PUBLIC PLACES REQUIREMENTS OF CHAPTER 78, | | | ARTICLE V, OF THE CITY'S CODE OF ORDINANCES. | | | | | | | | | SITE PLAN COMMENTS: | | | | | | 1.) PROVIDE DETAILS AND DIMENSIONS ON THE PROPOSED | | | MONUMENT SIGN AT THE NORTHWEST CORNER OF THE PROPERTY. | | | INCLUDE ANY SETBACK DIMENSIONS FROM THE PROPERTY | | | LINE(S). PLEASE NOTE THAT THE PROPOSED MONUMENT SIGN | | | SHALL COMPLY WITH THE SIGNAGE REQUIREMENTS OF ZLDR | | | S.94-407. | | | | | | 2.) ADD DIMENSIONS TO THE LANDSCAPE ISLANDS (I.E. | | | WIDTH). | | | | | | 3.) THERE ARE TWO (2) EXISTING TRANSFORMER PADS LOCATED | | | ALONG THE NORTH PROPERTY LINE, WHICH SEEMS TO BE | | | MISSING FROM THE SITE PLAN. PLEASE INCLUDE THE | | | TRANSFORMERS IN THE SITE PLAN FOR CONSISTENCY. | | | | | | 4.) WHERE IS THE LOCATION OF A/C UNITS/MECHANICAL | | | EQUIPMENT (I.E. GROUND LEVEL OR ROOFTOP)? PLEASE NOTE | | | THAT MECHANICAL EQUIPMENT SHALL BE SCREENED FROM VIEW | | | BY EITHER LANDSCAPING OR THE BUILDING PARAPET. | | | | | | 5.) PHOTOMETRIC PLAN INDICATES THE USE OF POLE | | | FIXTURES. PLEASE ILLUSTRATE THE LOCATION OF THESE | | | FIXTURES IN THE SITE PLAN AND PROVIDE SETBACK | | | DIMENSIONS FROM THE PROPERTY LINE. PLEASE NOTE THAT THE | | | POLES MUST BE LOCATED A MINIMUM OF 5 FT. FROM THE | | | PROPERTY LINE(S). ALSO, INCLUDE A DETAIL OF THE POLE | | | FIXTURE IN THE PLAN. | | | | | | 6.) HOW BIG ARE THE 1 BR AND 2BR UNITS? | | | | | | 7.) ADD OUTDOOR/PEDESTRIAN AMENITIES (I.E. BENCHES, | | | GAZEBO, WALKING PATH AROUND THE LAKE, ETC.) FOR THE | | | RESIDENTS OF THE PROPOSED DEVELOPMENT. | | | | | | 8.) ADD TRAFFIC CALMING/CROSSWALKS LEADING FROM THE | | | PARKING LOT TO THE BUILDING. | | | | | | 9.) THE PROPOSED BICYCLE RACKS MUST DEMONSTRATE THAT | | | ALL THE MINIMUM DIMENSIONS HAVE BEEN MET PER THE CITY'S | | | BICYCLE PARKING STANDARDS (I.E. DISTANCE FROM EACH THE | | | END OF THE RACK TO THE BUILDING/PAVEMENT. THIS IS TO | | | ENSURE THAT THERE IS SUFFICIENT SPACE FOR BICYCLE | | | PARKING AND THAT THE BICYCLE WILL NOT ENCROACH UPON ANY | | | SIDEWALK/WALKING PATH). PLEASE ILLUSTRATE COMPLIANCE | | | WITH DIMENSIONS. | | | | | | 10.) THE BICYCLE RACK LOCATED FURTHEST EAST SEEMS TO | | | ENCROACH UPON LANDSCAPE. THIS IS NOT PERMITTED. PLEASE | | | ADDRESS. | | | | | | 11.) THERE SEEMS TO BE A DOOR LOCATED ON THE NORTH SIDE | | | OF THE BUILDING; HOWEVER, THERE DOES NOT SEEM TO BE A | | | WALKING PATH LEADING FROM THE DOOR TO THE PARKING AREA | | | AND/OR SIDEWALK. PLEASE ADDRESS. | | | | | | 12.) THERE IS A PROPOSED T-TURNAROUND LOCATED AT THE | | | NORTHEAST CORNER OF THE PROPERTY. HOWEVER, IT DOES NOT | | | SEEM TO BE A PRACTICAL TURNAROUND FOR LARGER VEHICLES. | | | WAS A CURB CUT CONSIDERED AT THIS LOCATION? THIS | | | PROPOSED T-TURNAROUND MAY ALSO REQUIRE ADDITIONAL | | | FEEDBACK FROM THE FIRE, ENGINEERING AND PUBLIC WORKS | | | DEPT. | | | | | | | | | LANDSCAPE COMMENTS: | | | | | | 1.) THERE ARE TWO (2) EXISTING TRANSFORMER PADS LOCATED | | | ALONG THE NORTH PROPERTY LINE WHICH SEEMS TO BE MISSING | | | FROM THE LANDSCAPE PLAN. PLEASE SHOW THE EXISTING | | | TRANSFORMER PADS IN THE LANDSCAPE PLAN TO DEMONSTRATE | | | THAT THE PADS WILL NOT CONFLICT WITH THE PROPOSED | | | LANDSCAPING. | | | | | | 2.) SHOW LIGHT POLE FIXTURES IN THE LANDSCAPE PLAN TO | | | DEMONSTRATE THAT THE FIXTURES WILL NOT INTERFERE WITH | | | THE PROPOSED LANDSCAPE FOR THE PROJECT. | | | | | | 3.) A TREE ALTERATION PERMIT WILL BE REQUIRED PRIOR TO | | | THE REMOVAL OF ANY TREES ON THE PROPERTY. | | | | | | 4.) PLEASE ADDRESS ANY ADDITIONAL LANDSCAPE COMMENTS | | | PROVIDED BY THE CITY'S LANDSCAPE PLANNER, RAY CARANCI @ | | | (561) 822-1462. ALL LANDSCAPE COMMENTS SHALL BE | | | SATISFIED PRIOR TO THE SCHEDULING OF THE APPLICATION | | | FOR A PUBLIC HEARING. | | | | | | | | | ARCHITECTURAL FLOOR PLANS AND ELEVATIONS: | | | | | | 1.) FINAL ARCHITECTURAL PLANS SHALL BE SIGNED, DATED | | | AND SEALED BY A FLORIDA REGISTERED ARCHITECT. | | | | | | 2.) PLEASE ENSURE THAT ANY CHANGES TO THE SITE | | | PLAN/LANDSCAPE AND PHOTOMETRIC PLAN ARE REFLECTED IN | | | THE ARCHITECTURAL DRAWINGS FOR CONSISTENCY. | | | | | | | | | LIGHTING PLAN: | | | | | | 1.) THE PHOTOMETRIC PLAN SHALL BE SIGNED AND SEALED BY | | | A FLORIDA REGISTERED PROFESSIONAL ENGINEER. | | | | | | 2.) PROVIDE A DETAIL (INCLUDING DIMENSIONS) OF THE | | | PROPOSED POLE FIXTURES. | | | | | | 3.) THERE SEEMS TO BE AN EXISTING TRANSFORMER ALONG THE | | | NORTH PROPERTY LINE THAT IS MISSING FROM THE | | | PHOTOMETRIC PLAN. PLEASE INCLUDE THE PAD IN THE PLAN | | | FOR CONSISTENCY. | | | | | | 4.) PER ZLDR S.94-309(A), ALL OUTDOOR LIGHTING SHALL BE | | | SHIELDED TO REDUCE GLARE AND SHALL BE ARRANGED TO | | | REFLECT LIGHT OR GLARE AWAY FROM ALL ADJACENT | | | RESIDENTIAL DISTRICTS, ADJACENT RESIDENCES, OR PUBLIC | | | THROUGHFARES. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF | | | FIFTEEN (15) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 | | | INCHES X 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 | | | INCHES, AND AN ELECTRONIC COPY OF ALL PLANS. PLEASE | | | NOTE THAT CHANGES ON THE RESUBMITTED PLANS MAY RESULT | | | IN ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE | | | ($600.00). | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| |