Plan Review Details - Project Z17070016
Plan Review Stops For Project Z17070016
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 08-09-2017 Cont ID  
Sent By rbrown Date 08-09-2017 Time 12:18 Rev Time 0.00
Received By rbrown Date 08-09-2017 Time 12:18 Sent To  
Notes
2017-08-09 12:20:24DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. NEW FLOOD INSURANCE RATE MAPS (FIRMS) WILL BE
 ADOPTED BEFORE OCTOBER 2017. THE PROPOSED BUILDING MAY
 BE IN FLOOD ZONE. THE CURRENT REQUIREMENT IS FOR THE
 ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL
 ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS
 ETC.) SHALL BE 12 INCHES (FREEBOARD) ABOVE THAT BASE
 FLOOD ELEVATION. PLEASE NOTE THAT THERE IS A PROPOSAL
 TO INCREASE THE FREEBOARD TO 24 INCHES SOMETIME AFTER
 THE MIDDLE OF MAY 2017.
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE
  
 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 5. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 8. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 08-03-2017 Cont ID  
Sent By squinone Date 08-03-2017 Time   Rev Time 8.00
Received By squinone Date 08-03-2017 Time   Sent To  
Notes
2017-08-03 13:45:15CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 PROJECT NAME: DRIVE SHACK
 RESPONSE: PASSED
 DATE: AUGUST 8, 2017
  
 NO COMMENTS, CONNECTING TO PBC UTILITIES.
  
 SINCERELY,
 SOFIA QUINONES, E.I.
 PROJECT ENGINEER
 [email protected]
 561-494-1108 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 08-01-2017 Cont ID  
Sent By pleduc Date 08-01-2017 Time 12:47 Rev Time 0.00
Received By pleduc Date 08-01-2017 Time 11:40 Sent To  
Notes
2017-08-01 12:47:01THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE(S), PER THE FLORIDA FIRE PREVENTION
 CODE, AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED. A FIRE PUMP
 ROOM IS INDICATED. A REVIEW OF THE AVAILABLE WATER
 SUPPLY MAY PROVE THAT A FIRE PUMP MAY NOT BE REQUIRED.
  
  
 8. FOR PLAN REVIEW AND CONSTRUCTION PURPOSES, NEW FIRE
 HYDRANTS PLANNED FOR THIS DEVELOPMENT SHALL BE
 INSTALLED PER THE REQUIREMENTS OF NFPA 24, STANDARD FOR
 THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND
 THEIR APPURTENANCES.
  
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM(S), I.E FIRE SPRINKLER AND FIRE
 ALARM, ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS
 61G AND SUBMITTED WITH THE MASTER PLAN.
  
 PLEASE REVIEW ALL RELATED CODES AND ENSURE THAT IF THE
 STAIRWELLS REQUIRE STANDPIPES, THAT THEY ARE DESIGNED
 AS PART OF THE LIFE SAFETY SYSTEM.
  
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 THE EXIT STAIRWAYS APPEAR THAT THEY ARE OPEN. PLEASE
 ENSURE THAT THE EXIT STAIRWAYS, PER THE APPLICABLE LIFE
 SAFETY CODE, ARE NOT REQUIRED TO PROTECTED PER THE EXIT
 TRAVEL DISTANCES.
  
  
 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES BE
 PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS AND/OR
 SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 10-06-2017 Cont ID  
Sent By rcaranci Date 10-06-2017 Time 17:00 Rev Time 0.00
Received By rcaranci Date 10-06-2017 Time 17:00 Sent To  
Notes
2017-10-06 17:00:34FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 MEMO TO FILE
 PROJECT: DRIVE SHACK Z17070016
 OCTOBER 6, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. PLEASE CORRECT THE PERVIOUS AND
 IMPERVIOUS CALCULATIONS AND LIST AREAS OF ARTIFICIAL
 TURF THAT ARE TO BE COUNTED AS IMPERVIOUS. SHEETS PSP-1
 AND ALL LANDSCAPE SHEETS NEED CORRECTION.
  
 2. SATISFIED. BUFFER PLANTINGS NEED TO BE ADEQUATE TO
 ENSURE THE ARTIFICIAL TURF IS NOT VISIBLE FROM THE
 PUBLIC THOROUGHFARE.
 ADDITIONAL BUFFERING ALONG THE CORNER AS DESCRIBED IN
 THE CONDITION BELOW WILL FULLY ADDRESS THIS COMMENT.
  
 3. SATISFIED. PLEASE PROVIDE THE INFORMATION ON THE
 ARTIFICIAL TURF CONSTRUCTION AND INSTALLATION TO
 DEMONSTRATE CODE REQUIREMENTS ARE MET.
  
 4. SATISFIED. PLEASE PROVIDE ADDITIONAL LANDSCAPE
 BUFFERING TO MITIGATE THE IMPACT OF THE NETTING AND
 LARGE POLES BY ADDING SHADE TREES AND PALMS TO THE
 BUFFERS ON THE NORTH, EAST AND SOUTHEAST SIDES. ALSO
 INCLUDE PLANTINGS IN THE DETENTION AREAS. BELVEDERE
 ROAD BUFFER SHOULD BE CONSISTENT WITH THE REST OF THE
 AIRPORT PROPERTY THAT INCLUDES BERMED AREAS, LARGE LIVE
 OAKS, AND LAYERED SHRUB PLANTINGS. BUFFER FOR THE
 PARKING AREA ADJACENT TO FLORIDA MANGO SHOULD BE
 CONSISTENT WITH THE BUFFER FOR THE GAS STATION ON THE
 OPPOSITE SIDE.
  
  
 5. SATISFIED. PLEASE PROVIDE A PLAN FOR ROADWAY
 BEAUTIFICATION PER SECTION 94-452. SHRUBS AND
 GROUNDCOVER MAY BE USED TO EXTEND THE PLANTED AREAS OF
 THE BUFFER INTO THE ROAD SHOULDER LANDSCAPING.
 THERE IS AN OPPORTUNITY TO INCREASE THE BUFFER THROUGH
 THE ADDITION OF ROAD SHOULDER LANDSCAPING AT THE CORNER
 OF BELVEDERE AND AUSTRALIAN. THE BUFFER WITHIN THE
 PROPERTY LINE IS EXTREMELY NARROW AT THIS POINT, AND
 DOES NOT SCREEN AS WELL AS THE REST OF THE PROJECT. THE
 ADDITION OF LARGE CATEGORY TREES SUCH AS OAKS, AND
 ADDITIONAL HEDGES WOULD CONTINUE THE SAME PATTERN AS
 ALONG BELVEDERE ROAD ADJACENT TO THE SIDEWALK.
 ADDITIONAL BUFFERING ALONG THE CORNER AS DESCRIBED IN
 THE CONDITION BELOW WILL FULLY ADDRESS THIS COMMENT.
  
  
 6. SATISFIED. PLEASE PROVIDE TYPICAL BUFFER CROSS
 SECTIONS FOR ALL BUFFERS INCLUDING PLANT PLACEMENT,
 FENCING AND CHANGES IN ELEVATION.
  
 7. SATISFIED. PLEASE PROVIDE AN UPDATED CHART SHOWING
 COMPLIANCE WITH FLORIDA FRIENDLY LANDSCAPING PER
 SECTION 94-442 (G). THIS INCLUDES SHOWING DROUGHT
 TOLERANCE LEVEL AND NATIVE SPECIES ON THE PLANT LIST
 AND PROVIDING THE REQUIRED 40 POINTS.
  
 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 9. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES
 AND FPL TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE
 PROVIDE MORE SCREENING FOR THE SERVICE AREA ALONG THE
 PARKING LOT.
  
 10. SATISFIED. STAFF RECOMMENDS THE HIGH RISE OAKS BE
 CHANGED TO CATHEDRAL OR SPECIES LIVE OAKS.
  
 11. SATISFIED. PLEASE PROVIDE ONE PLANT LIST OR MAKE
 ALL LISTS CONSISTENT ON ALL SHEETS. PLEASE MAKE THE
 FOLLOWING CORRECTIONS:
 ? ADD A COLUMN TO IDENTIFY NATIVE PLANT SPECIES.
 ? INCLUDE THE WATER USAGE LEVEL FOR NATCHEZ CRAPE
 MYRTLE.
 ? REMOVE SYNTHETIC TURF FROM PLANT LIST AND SHOW
 SEPARATELY.
 ? SHOW WATER USAGE FOR ALPINIA.
  
 12. SATISFIED. TREE HEIGHTS NEED TO MEET THE REQUIRED
 12 FEET HEIGHT SPECIFIED IN SECTION 94-445(4).
  
 13. SATISFIED. PARKING LOT LANDSCAPE AREAS MUST MEET
 THE REQUIREMENTS OF SECTION 94-443(C)(3) AND (4).
 PLEASE SHOW ALL CALCULATIONS AND PROVIDE A DIAGRAM
 SHOWING THE AREAS COUNTED TOWARD THIS REQUIREMENT.
  
 14. SATISFIED. THE LIGHTING PLAN PROVIDE FOR THE
 PARKING LOT IS NOT COMPATIBLE WITH ESTABLISHING A TREE
 CANOPY FOR SHADING THE PARKING SPACES. PLEASE DESIGN
 THE LIGHTING AT A LOWER LEVEL TO WORK IN HARMONY WITH
 THE TREE CANOPY.
  
 15. SATISFIED. PLEASE CONSIDER A DESIGN OF LOCATING
 LANDSCAPE ISLANDS WITHIN THE PARKING FIELD TO PROVIDE
 THE MAXIMUM LANDSCAPE AREAS TO SUPPORT LARGE CANOPY
 SHADE TREES TO MAXIMIZE THE SHADE CANOPY. STAFF WOULD
 SUPPORT CREATIVE VARIATIONS TO ACCOMPLISH THIS GOAL,
 INCLUDING MORE SPACES IN A ROW IF WIDTHS OF LANDSCAPE
 AREAS ARE INCREASED.
  
 CONDITIONS OF APPROVAL
  
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 09-13-2017 Cont ID  
Sent By rcaranci Date 09-13-2017 Time 17:20 Rev Time 0.00
Received By rcaranci Date 09-13-2017 Time 17:20 Sent To  
Notes
2017-09-13 17:21:30FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 MEMO TO FILE
 PROJECT: DRIVE SHACK Z17070016
 SEPTEMBER 6, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. PLEASE CORRECT THE PERVIOUS AND
 IMPERVIOUS CALCULATIONS AND LIST AREAS OF ARTIFICIAL
 TURF THAT ARE TO BE COUNTED AS IMPERVIOUS. SHEETS PSP-1
 AND ALL LANDSCAPE SHEETS NEED CORRECTION.
  
 2. CONDITIONALLY SATISFIED. BUFFER PLANTINGS NEED TO BE
 ADEQUATE TO ENSURE THE ARTIFICIAL TURF IS NOT VISIBLE
 FROM THE PUBLIC THOROUGHFARE.
 ADDITIONAL BUFFERING ALONG THE CORNER AS DESCRIBED IN
 THE CONDITION BELOW WILL FULLY ADDRESS THIS COMMENT.
  
 3. SATISFIED. PLEASE PROVIDE THE INFORMATION ON THE
 ARTIFICIAL TURF CONSTRUCTION AND INSTALLATION TO
 DEMONSTRATE CODE REQUIREMENTS ARE MET.
  
 4. CONDITIONALLY SATISFIED. PLEASE PROVIDE ADDITIONAL
 LANDSCAPE BUFFERING TO MITIGATE THE IMPACT OF THE
 NETTING AND LARGE POLES BY ADDING SHADE TREES AND PALMS
 TO THE BUFFERS ON THE NORTH, EAST AND SOUTHEAST SIDES.
 ALSO INCLUDE PLANTINGS IN THE DETENTION AREAS.
 BELVEDERE ROAD BUFFER SHOULD BE CONSISTENT WITH THE
 REST OF THE AIRPORT PROPERTY THAT INCLUDES BERMED
 AREAS, LARGE LIVE OAKS, AND LAYERED SHRUB PLANTINGS.
 BUFFER FOR THE PARKING AREA ADJACENT TO FLORIDA MANGO
 SHOULD BE CONSISTENT WITH THE BUFFER FOR THE GAS
 STATION ON THE OPPOSITE SIDE.
 ADDITIONAL BUFFERING ALONG THE CORNER AS DESCRIBED IN
 THE CONDITION BELOW WILL FULLY ADDRESS THIS COMMENT.
  
  
 5. CONDITIONALLY SATISFIED. PLEASE PROVIDE A PLAN FOR
 ROADWAY BEAUTIFICATION PER SECTION 94-452. SHRUBS AND
 GROUNDCOVER MAY BE USED TO EXTEND THE PLANTED AREAS OF
 THE BUFFER INTO THE ROAD SHOULDER LANDSCAPING.
 THERE IS AN OPPORTUNITY TO INCREASE THE BUFFER THROUGH
 THE ADDITION OF ROAD SHOULDER LANDSCAPING AT THE CORNER
 OF BELVEDERE AND AUSTRALIAN. THE BUFFER WITHIN THE
 PROPERTY LINE IS EXTREMELY NARROW AT THIS POINT, AND
 DOES NOT SCREEN AS WELL AS THE REST OF THE PROJECT. THE
 ADDITION OF LARGE CATEGORY TREES SUCH AS OAKS, AND
 ADDITIONAL HEDGES WOULD CONTINUE THE SAME PATTERN AS
 ALONG BELVEDERE ROAD ADJACENT TO THE SIDEWALK.
 ADDITIONAL BUFFERING ALONG THE CORNER AS DESCRIBED IN
 THE CONDITION BELOW WILL FULLY ADDRESS THIS COMMENT.
  
  
 6. CONDITIONALLY SATISFIED. PLEASE PROVIDE TYPICAL
 BUFFER CROSS SECTIONS FOR ALL BUFFERS INCLUDING PLANT
 PLACEMENT, FENCING AND CHANGES IN ELEVATION.
 SEE INCLUDED CONDITION BELOW.
  
 7. SATISFIED. PLEASE PROVIDE AN UPDATED CHART SHOWING
 COMPLIANCE WITH FLORIDA FRIENDLY LANDSCAPING PER
 SECTION 94-442 (G). THIS INCLUDES SHOWING DROUGHT
 TOLERANCE LEVEL AND NATIVE SPECIES ON THE PLANT LIST
 AND PROVIDING THE REQUIRED 40 POINTS.
  
 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 9. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES
 AND FPL TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE
 PROVIDE MORE SCREENING FOR THE SERVICE AREA ALONG THE
 PARKING LOT.
  
 10. SATISFIED. STAFF RECOMMENDS THE HIGH RISE OAKS BE
 CHANGED TO CATHEDRAL OR SPECIES LIVE OAKS.
  
 11. SATISFIED. PLEASE PROVIDE ONE PLANT LIST OR MAKE
 ALL LISTS CONSISTENT ON ALL SHEETS. PLEASE MAKE THE
 FOLLOWING CORRECTIONS:
 ? ADD A COLUMN TO IDENTIFY NATIVE PLANT SPECIES.
 ? INCLUDE THE WATER USAGE LEVEL FOR NATCHEZ CRAPE
 MYRTLE.
 ? REMOVE SYNTHETIC TURF FROM PLANT LIST AND SHOW
 SEPARATELY.
 ? SHOW WATER USAGE FOR ALPINIA.
  
 12. SATISFIED. TREE HEIGHTS NEED TO MEET THE REQUIRED
 12 FEET HEIGHT SPECIFIED IN SECTION 94-445(4).
  
 13. SATISFIED. PARKING LOT LANDSCAPE AREAS MUST MEET
 THE REQUIREMENTS OF SECTION 94-443(C)(3) AND (4).
 PLEASE SHOW ALL CALCULATIONS AND PROVIDE A DIAGRAM
 SHOWING THE AREAS COUNTED TOWARD THIS REQUIREMENT.
  
 14. SATISFIED. THE LIGHTING PLAN PROVIDE FOR THE
 PARKING LOT IS NOT COMPATIBLE WITH ESTABLISHING A TREE
 CANOPY FOR SHADING THE PARKING SPACES. PLEASE DESIGN
 THE LIGHTING AT A LOWER LEVEL TO WORK IN HARMONY WITH
 THE TREE CANOPY.
  
 15. SATISFIED. PLEASE CONSIDER A DESIGN OF LOCATING
 LANDSCAPE ISLANDS WITHIN THE PARKING FIELD TO PROVIDE
 THE MAXIMUM LANDSCAPE AREAS TO SUPPORT LARGE CANOPY
 SHADE TREES TO MAXIMIZE THE SHADE CANOPY. STAFF WOULD
 SUPPORT CREATIVE VARIATIONS TO ACCOMPLISH THIS GOAL,
 INCLUDING MORE SPACES IN A ROW IF WIDTHS OF LANDSCAPE
 AREAS ARE INCREASED.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE PUBLIC HEARING FOR PLANNING BOARD, THE
 LANDSCAPE PLAN SHALL BE REVISED TO SHOW THE VEITCHIA
 PALMS ALONG THE SIDEWALK IN THE NORTH BUFFER INCREASED
 TO TRIPLE STEMS IN ORDER TO PROVIDE SHADE CANOPY FOR
 THE SIDEWALK.
  
 2. PRIOR TO THE PUBLIC HEARING FOR PLANNING BOARD, THE
 LANDSCAPE PLAN SHALL BE REVISED TO SHOW THE PLANT
 IDENTIFICATION TAGS MISSING FROM SHEET LP-4 TOWARDS THE
 TOP OF THE SHEET.
  
 3. PRIOR TO THE PUBLIC HEARING FOR PLANNING BOARD, THE
 APPLICANT SHALL REVISE THE LANDSCAPE PLAN TO INCLUDE
 ADDITIONAL LANDSCAPE MATERIAL WITHIN THE ROAD RIGHT OF
 WAY AT THE CORNER OF BELVEDERE ROAD AND AUSTRALIAN
 AVENUE TO SUPPLEMENT THE LANDSCAPE BUFFER IN THAT AREA
 AND MAKE IT COMPARABLE IN ACTUAL WIDTH AND DENSITY TO
 THE LANDSCAPE BUFFERS ALONG BELVEDERE ROAD AND
 AUSTRALIAN AVENUE.
  
 4. PRIOR TO THE PUBLIC HEARING FOR PLANNING BOARD, THE
 APPLICANT SHALL SUBMIT TYPICAL CROSS SECTIONS OF ALL
 LANDSCAPE BUFFERS.
  
 5. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 08-04-2017 Cont ID  
Sent By rcaranci Date 08-04-2017 Time 15:35 Rev Time 0.00
Received By rcaranci Date 08-04-2017 Time 15:35 Sent To  
Notes
2017-08-04 15:36:09PROJECT: DRIVE SHACK Z17070016
 AUGUST 4, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE CORRECT THE PERVIOUS AND IMPERVIOUS
 CALCULATIONS AND LIST AREAS OF ARTIFICIAL TURF THAT ARE
 TO BE COUNTED AS IMPERVIOUS. SHEETS PSP-1 AND ALL
 LANDSCAPE SHEETS NEED CORRECTION.
  
 2. BUFFER PLANTINGS NEED TO BE ADEQUATE TO ENSURE THE
 ARTIFICIAL TURF IS NOT VISIBLE FROM THE PUBLIC
 THOROUGHFARE.
  
 3. PLEASE PROVIDE THE INFORMATION ON THE ARTIFICIAL
 TURF CONSTRUCTION AND INSTALLATION TO DEMONSTRATE CODE
 REQUIREMENTS ARE MET.
  
 4. PLEASE PROVIDE ADDITIONAL LANDSCAPE BUFFERING TO
 MITIGATE THE IMPACT OF THE NETTING AND LARGE POLES BY
 ADDING SHADE TREES AND PALMS TO THE BUFFERS ON THE
 NORTH, EAST AND SOUTHEAST SIDES. ALSO INCLUDE PLANTINGS
 IN THE DETENTION AREAS. BELVEDERE ROAD BUFFER SHOULD BE
 CONSISTENT WITH THE REST OF THE AIRPORT PROPERTY THAT
 INCLUDES BERMED AREAS, LARGE LIVE OAKS, AND LAYERED
 SHRUB PLANTINGS. BUFFER FOR THE PARKING AREA ADJACENT
 TO FLORIDA MANGO SHOULD BE CONSISTENT WITH THE BUFFER
 FOR THE GAS STATION ON THE OPPOSITE SIDE.
  
 5. PLEASE PROVIDE A PLAN FOR ROADWAY BEAUTIFICATION PER
 SECTION 94-452. SHRUBS AND GROUNDCOVER MAY BE USED TO
 EXTEND THE PLANTED AREAS OF THE BUFFER INTO THE ROAD
 SHOULDER LANDSCAPING.
  
 6. PLEASE PROVIDE TYPICAL BUFFER CROSS SECTIONS FOR ALL
 BUFFERS INCLUDING PLANT PLACEMENT, FENCING AND CHANGES
 IN ELEVATION.
  
 7. PLEASE PROVIDE AN UPDATED CHART SHOWING COMPLIANCE
 WITH FLORIDA FRIENDLY LANDSCAPING PER SECTION 94-442
 (G). THIS INCLUDES SHOWING DROUGHT TOLERANCE LEVEL AND
 NATIVE SPECIES ON THE PLANT LIST AND PROVIDING THE
 REQUIRED 40 POINTS.
  
 8. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 9. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES. WATER BACKFLOW VALVES AND FPL
 TRANSFORMERS MUST HAVE SCREENING HEDGES. PLEASE PROVIDE
 MORE SCREENING FOR THE SERVICE AREA ALONG THE PARKING
 LOT.
  
 10. STAFF RECOMMENDS THE HIGH RISE OAKS BE CHANGED TO
 CATHEDRAL OR SPECIES LIVE OAKS.
  
 11. PLEASE PROVIDE ONE PLANT LIST OR MAKE ALL LISTS
 CONSISTENT ON ALL SHEETS. PLEASE MAKE THE FOLLOWING
 CORRECTIONS:
 ? ADD A COLUMN TO IDENTIFY NATIVE PLANT SPECIES.
 ? INCLUDE THE WATER USAGE LEVEL FOR NATCHEZ CRAPE
 MYRTLE.
 ? REMOVE SYNTHETIC TURF FROM PLANT LIST AND SHOW
 SEPARATELY.
 ? SHOW WATER USAGE FOR ALPINIA.
  
 12. TREE HEIGHTS NEED TO MEET THE REQUIRED 12 FEET
 HEIGHT SPECIFIED IN SECTION 94-445(4).
  
 13. PARKING LOT LANDSCAPE AREAS MUST MEET THE
 REQUIREMENTS OF SECTION 94-443(C)(3) AND (4).
 PLEASE SHOW ALL CALCULATIONS AND PROVIDE A DIAGRAM
 SHOWING THE AREAS COUNTED TOWARD THIS REQUIREMENT.
  
 14. THE LIGHTING PLAN PROVIDE FOR THE PARKING LOT IS
 NOT COMPATIBLE WITH ESTABLISHING A TREE CANOPY FOR
 SHADING THE PARKING SPACES. PLEASE DESIGN THE LIGHTING
 AT A LOWER LEVEL TO WORK IN HARMONY WITH THE TREE
 CANOPY.
  
 15. PLEASE CONSIDER A DESIGN OF LOCATING LANDSCAPE
 ISLANDS WITHIN THE PARKING FIELD TO PROVIDE THE MAXIMUM
 LANDSCAPE AREAS TO SUPPORT LARGE CANOPY SHADE TREES TO
 MAXIMIZE THE SHADE CANOPY. STAFF WOULD SUPPORT CREATIVE
 VARIATIONS TO ACCOMPLISH THIS GOAL, INCLUDING MORE
 SPACES IN A ROW IF WIDTHS OF LANDSCAPE AREAS ARE
 INCREASED.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 RAY CARANCI, LANDSCPE PLANNER 561-822-1462

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 08-08-2017 Cont ID  
Sent By tward Date 08-08-2017 Time 11:22 Rev Time 0.00
Received By tward Date 08-08-2017 Time 11:22 Sent To  
Notes
2017-08-08 11:22:12THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE FREEBOARD REQUIREMENT FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA IS TWO FEET ABOVE BASE FLOOD
 ELEVATION.
  
 3. INDICATE ON THE PLANS HOW MUCH OF EXISTING STORM
 PIPES IN SOUTHEAST CORNER OF THE SITE WILL BE REMOVED.
  
 4. SHOW THE FULL EXTENT OF THE FORCE MAIN WITHIN THE
 PROPERTY ON THE LANDSCAPE PLANS. THE LINEWORK IS
 MISSING AT THE SOUTHEAST CORNER OF THE SITE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 09-14-2017 Cont ID  
Sent By vnoel Date 09-14-2017 Time 09:07 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2017-09-14 09:08:25DUMPSTER ENCLOSURE STILL REQUIRES SANITATION DEPT.
 APPROVAL.

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date 08-07-2017 Cont ID  
Sent By vnoel Date 08-07-2017 Time 09:53 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-08-07 10:04:411. BOUNDARY APPEARS CHANGED FROM PREVIOUS RE-ZONING
 APPLICATION.
 2. WATER AND SEWER WILL BE PROVIDED BY PB COUNTY.
 3. APPEARS THAT THE DUMPSTER ENCLOSURE WILL CONTAIN
 MORE THAN ONE RECEPTACLE. WILL NEED APPROVAL FROM PETER
 BIENIEK, PUBLIC WORKS DIRECTOR (561-494-1099) AS TO
 LOCATION AND SIZE.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 3 Status P Date   Cont ID  
Sent By   Date 10-06-2017 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2017-10-06 16:07:37PROJECT IS PASSED WITH CONDITIONAL APPROVAL THAT
 APPLICANT PROVIDE PALM BEACH COUNTY TRAFFIC CONCURRENCY
 LETTER PRIOR TO CITY COMMISSION MEETING.
  
 ERIK D. FERGUSON, P.E.
 SENIOR PROJECT ENGINEER

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status F Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2017-09-14 09:46:401 - PROVIDE COUNTY TRAFFIC PERFORMANCE STANDARDS
 CONCURRENCY APPROVAL LETTER FOR PROPOSED USE. THE
 LATEST LETTER INCLUDED IN THE SUBMITTAL, DATED FEBRUARY
 13, 2017, IS FOR A DIFFERENT USE AND REFERENCES A
 JANUARY 9, 2017 STUDY BY PINDER TROUTMAN.
  
 2. FIGURE 2 KIMLEY HORN - DRIVEWAY VOLUMES. TRIP
 DISTRIBUTION IS ILLOGICAL. THERE ARE NO EASTBOUND RIGHT
 TURNS PROPOSED AT THE INTERSECTION OF BELVERDERE ROAD
 AND FLORIDA MANGO. THERE WILL BE SOME EASTBOUND (IN)
 TRIPS THAT WILL DIVERT OFF OF BELVEDERE AT FLORIDA
 MANGO TO ACCESS THE SITE AND NOT CONTINUE FURTHER EAST
 TO SECOND DRIVEWAY. REVISE DRIVEWAY VOLUME FIGURE.
  
 3. IS AN EAST BOUND RIGHT TURN LANE NEEDED AT FLORIDA
 MANGO / BELVEDERE?
  
 ERIK D. FERGUSON, P.E.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date   Cont ID  
Sent By   Date 08-08-2017 Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
2017-08-08 08:54:091. VERIFY NUMBER OF GOLF DRIVING BAYS. ARTECH PLANS
 SHOW 48 BAYS, BUT SCHMIDT AND NICOLS JUSTIFICATION
 STATEMENT STATES 90 BAYS.
 2. IS A PARKING STUDY AVAILABLE FOR SIMILAR FACILITIES?
 PARKING APPEARS EXCESSIVE.
 3. PROVIDE SIDEWALK ALONG BELVEDERE ROAD. SIDEWALK
 SHOULD PREFERABLY BE BUFFERED BY TREES.
 4. SHEET PSP-1. 10? SAFE SIGHT TRIANGLE ON BELVEDERE
 ROAD DOES NOT MEET FLORIDA GREENBOOK STANDARDS.
 5. HAS COUNTY APPROVED SPLIT PHASE (SHARED LEFT / THRU)
 SIGNAL PHASING AT INTERSECTION OF BELVEDERE / FLORIDA
 MANGO? SPLIT PHASE MAY OPERATE WORSE THAN A SINGLE LEFT
 TURN LANE.
 6. PROVIDE TRAFFIC STUDY.
  
 ERIK D. FERGUSON

Review Stop Z ZONING
Rev No 2 Status P Date 09-15-2017 Cont ID  
Sent By hmtribou Date 09-15-2017 Time 10:10 Rev Time 0.00
Received By hmtribou Date 09-15-2017 Time 10:09 Sent To  
Notes
2017-09-15 10:22:37-PRIOR TO PUBLIC HEARING PLEASE REVISE PLANS AND
 JUSTIFICATION STATEMENT FOR FURTHER CLARIFICATION OF
 PROPERTY BOUNDARY LINE FOR REZONING AND BOUNDARY LINE
 FOR DRIVEWAY PROJECT TO BE COMPLETED BY THE DEPARTMENT
 OF AIRPORTS. CLARIFY DESCRIPTIONS ON ALL DOCUMENTATION
 TO BE THE SAME INCLUDING LABELS ON THE SITE PLAN, NOTES
 ON THE SITE PLAN AND DESCRIPTIONS IN THE JUSTIFICATION
 STATEMENT.
 -PRIOR TO PUBLIC HEARING REVISE SIGN DETAIL ON
 REGULATING PLAN.
 -PRIOR TO PUBLIC HEARING REVISE ENGINEERING PLANS TO
 MATCH SITE PLAN PAVERS AT SERVICE AREA ENTRY.
 -PRIOR TO PERMITTING REVISE DOORS ON DUMPSTER FOR
 ACCESS.
  

Review Stop Z ZONING
Rev No 1 Status F Date 08-04-2017 Cont ID  
Sent By hmtribou Date 08-04-2017 Time 15:20 Rev Time 8.00
Received By hmtribou Date 08-04-2017 Time 15:10 Sent To  
Notes
2017-08-04 15:11:50CASE NUMBER: PB 1752
 PROJECT NAME: DRIVE SHACK
  
 ZONING CONTACT: HEATHER M. TRIBOU
  (561) 822-1562
  [email protected]
  
 PROCESS COMMENTS
  
 - PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) AND AN ELECTRONIC COPIES IN PDF FORMAT OF ALL
 PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED
 PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS
 THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 AUGUST 25, 2017, TO BE SCHEDULED FOR THE OCTOBER 17,
 2017 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 OCTOBER 12, 2017), THE CASE SHALL BE CONSIDERED
 WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW
 DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 GENERAL COMMENTS
  
 --UPDATE ALL SHEETS TO REFLECT ANY CHANGES.
  
 -- SURVEY AND LEGAL DESCRIPTION DIFFERS FROM 2016
 FUTURE LAND USE AMENDMENT AND REZONING. IT IS UNCLEAR
 IF THE NEW SOUTH WEST CORNER CLIP WILL BE FOR A
 DEDICATED ROW OR FOR A DRIVEWAY. IF IT IS THE LATTER,
 THE ENTIRE PROPERTY MUST BE REZONED TO AVOID AN
 UNDEVELOPABLE SLIVER OF THE PROPERTY REMAINING GENERAL
 COMMERCIAL.
  
 -- AN EXISTING GATEWAY/ WAYFINDING SIGN IS LOCATED ON
 THE SUBJECT SITE ALONG BELVEDERE WHICH IS PROPOSED TO
 BE RELOCATED ON THE ENGINEERING PLANS. COORDINATE WITH
 THE CITY FOR DESIRED LOCATION, NEW APPROVED SIGNAGE
 DETAIL AND PROVIDE EASEMENT OR ANOTHER FORM OF
 ACCEPTABLE AGREEMENT FOR THE SIGN BEFORE CERTIFICATE OF
 OCCUPANCY.
  
  
 --TO ADDRESS REVIEW STANDARD SECTION 94-35(C)
 (3):SCREENING AND BUFFERING: TO PROTECT UNDESIRABLE
 VIEWS OF NETTING AND POLES ALONG BOTH BELVEDERE RD. AND
 AUSTRALIAN AVE. PROVIDE ENHANCED LANDSCAPING FOR
 SCREENING AND BUFFERING. PROVIDE SECTIONS ALONG BOTH
 BELVEDERE AND AUSTRALIAN TO VISUALIZE A PROPER BUFFER
 AT EYE LEVEL OF BOTH VEHICLES AND PEDESTRIANS.
  
 -- SECTION 94-35 (C)(1)HARMONIOUS AND EFFICIENT
 ORGANIZATION. IN RESPONSE TO SOLAR ORIENTATION THE
 BUILDING HAS BEEN LAID OUT ON THE REAR OF THE SITE WITH
 THE BUILDING FACING THE REAR OF THE SITE PER ARTICLE
 XIX: DEFINITIONS THE FRONT OF THE LOT WOULD BE
 AUSTRALIAN AVE. PROVIDE JUSTIFICATION ON HOW THE FRONT
 OF THE LOT WILL BE ADDRESSED.
  
 -- THIS PROJECT REQUIRES FOR THE PUBLIC ART ASSESSMENT
 (SEC. 98-129 OF CHAPTER 28 OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES). IT IS ENCOURAGED THAT THE
 ART BE INTEGRATED INTO THE SITE PLAN NOW TO ASSIST WITH
 MITIGATION OF THE FENCE HEIGHT WAIVER AND THE FA?ADE
 ORIENTATION.
  
 --THE TRAFFIC EQUIVALENCY STATEMENT SHALL BE SUBMITTED
 TO THE PALM BEACH COUNTY TRAFFIC DIVISION FOR APPROVAL.
  
 -- CONDITION OF APPROVAL- FAA APPROVAL MUST BE PROVIDED
 AT BUILDING PERMIT SUBMITTAL.
  
 --CONDITION OF APPROVAL- ALL DRIVEWAYS MUST HAVE
 COMPLETED CONSTRUCTION BEFORE FINAL INSPECTIONS
  
 ---THE INTENT OF A PLANNED DEVELOPMENT DISTRICT (94-207
 (1)) IS TO ENCOURAGE INNOVATIVE LAND PLANNING AND
 DEVELOPMENT TECHNIQUES TO CREATE MORE DESIRABLE AND
 ATTRACTIVE DEVELOPMENT IN THE CITY.
  
 SPECIFIC COMMENTS
  
 --ARCHITECTURE- THE BUILDING IS ORIENTED SO THAT THE
 MOST PROMINENT ARCHITECTURAL FEATURE UPON ENTRY IS AN
 EXTERIOR STAIRCASE. PLEASE REVISE ARCHITECTURE ON THE
 NORTH SIDE OF THE BUILDING TO ADDRESS THE ENTRY TO THE
 SITE.
  
 --ARCHITECTURE- PLEASE PROVIDE DETAILS DESCRIPTIONS OF
 MATERIALS TO BE PROVIDED ON BUILDING EXTERIOR.
  
 --ARCHITECTURE- STAIRWAY #4 WILL BE IN VIEW OF THE
 PUBLIC AND SHOULD BE SCREENED.
  
 --ARCHITECTURE- A COVER IS RECOMMENDED AT THE DROP-OFF
 AREA TO PROTECT VISITORS FROM SUMMER RAINS
  
 --ARCHITECTURE-PROVIDE SCREENING TO THE SERVICE AREA.
  
 --TRAFFIC STATEMENT- PLEASE COORDINATE COVER PAGE, NET
 NEW EXTERNAL PM PEAK HOURS, WITH TABLES WITHIN THE
 STUDY.
  
 --TRAFFIC- PROVIDE PRELIMINARY CURB CUT APPROVAL FROM
 PALM BEACH COUNTY
  
 --TRAFFIC- PROVIDE PROOF OF PRELIMINARY PERMIT FOR
 INTERNAL DRIVE FROM PALM BEACH COUNTY DEPARTMENT OF
 AIRPORTS.
  
 --TO ADDRESS SECTION 94-35 (C)(7) PEDESTRIAN
 CIRCULATION. ADD A DIRECT SIDEWALK THROUGH THE PROPOSED
 PARKING LOT TO THE WEST FOR SAFE PEDESTRIAN PASSAGE TO
 THE NEW CONVENIENCE STORE.
  
 --IN CONFORMANCE WITH THE CITY OF WEST PALM BEACH?S
 COMPLETE STREETS POLICY, PROVIDE A MID-BLOCK PEDESTRIAN
 CROSSING ON PERIMETER ROAD TO ALIGN WITH THE PEDESTRIAN
 PATHWAY WITH ENHANCED PAVEMENT AT THE TRAVEL PLAZA SITE
 TO THE WEST.
  
 --TO ADDRESS SEC. 78-7: PROVIDE SIDEWALKS CONNECTING
 THE EXISTING SIDEWALKS ON THE EAST SIDE OF THE PROPERTY
 ALONG AUSTRALIAN AVE. TO THE NEW SIDEWALK ALONG
 BELVEDERE RD. TO THE WEST.
  
 -- TO ADDRESS SEC. 78-7: PROVIDE A CROSSWALK AT THE
 INTERSECTION OF PERIMETER ROAD CONNECTING THE NEW
 SIDEWALK AT THE TRAVEL PLAZA TO THE SITE.
  
 --TO ADDRESS SECTION 94-35 (C)(9) COORDINATION OF
 ON-SITE CIRCULATION WITH OFF-SITE CIRCULATION. THE SITE
 PLAN INDICATES PARKING ALONG THE DRIVE AISLE AT THE
 RADIUS OF THE PROPOSED TRAFFIC CIRCLE MEETING MINIMUM 5
 FOOT LANDSCAPE REQUIREMENTS. THIS IS INCONSISTENT WITH
 THE SURROUNDING CONTEXT OF THE TRAVEL PLAZA AND A LOST
 OPPORTUNITY OF PROVIDING IDENTITY AS AIRPORT PASSENGERS
 ENTER WEST PALM BEACH. PLEASE REMOVE THE TEN PARKING
 SPACES, WHICH IS EXCESS PARKING, TO PROVIDE ENHANCED
 LANDSCAPE AT THIS CORNER TO COORDINATE WITH THE PATTERN
 OF THE ROUGHLY TWENTY-FOUR FOOT SETBACK FROM PARKING TO
 PAVEMENT THAT EXISTS ON THE TRAVEL PLAZA TO THE WEST OF
 THE SITE.
  
 -- TURNING VOLUMES ON THE SITE PLAN TO MATCH TRAFFIC
 EQUIVALENCY STATEMENT
  
 -- JUSTIFICATION STATEMENT INDICATES PARKING
 CALCULATIONS ARE BASED OFF THE REQUIREMENTS OF THE CITY
 OF ORLANDO. AFTER FURTHER REVIEW, THE CITY OF ORLANDO
 REQUIRES A MINIMUM AND MAXIMUM. CONSISTENT WITH THE
 CITY OF WEST PALM?S BEACH PARKING SEC. 94-486 FOR
 INDOOR/OUTDOOR RECREATION CALCULATE PARKING AS 3 SPACES
 PER BAY AND ONE SPACE PER EMPLOYEE ON BUSIEST SHIFT.
  
 --150 FOOT POLES WILL REQUIRE A WAIVER FROM
 94-302(C)(1), JUSTIFICATION MUST BE PROVIDED INCLUDING
 BUT NOT LIMITED TO PAINT COLORS.
  
 --SITE PLAN- PLEASE PROVIDE DUMPSTER DETAIL TO MATCH
 SITE PLAN
  
 --SITE PLAN- PLEASE INDICATE IN SITE DATA THAT
 ARTIFICIAL TURF IS INCLUDE IN IMPERVIOUS SURFACE
 CALCULATION.
  
 --SITE PLAN- ACCORDING TO SECTION 94-485 TABLE XV-3
 NINE HANDICAPPED PARKING SPACES ARE REQUIRED FOR 400
 PARKING SPACES, EIGHT HAVE BEEN PROVIDED.
  
 --SITE PLAN- ACCORDING TO SECTION 94-485 TABLE XV -4
 TWO LOADING SPACES ARE REQUIRED, ONE HAS BEEN PROVIDED.
  
 --SITE PLAN- ACCORDING TO SECTION 94-485 TABLE XV -5
 ONE BIKE PARKING SPACE IS REQUIRED PER TEN PARKING
 SPACES, TEN HAVE BEEN PROVIDED.
  
 --SITE PLAN- CORRECT BIKE DETAIL TO SHOW THE NUMBER OF
 SPACES REQUIRED TO BE PROVIDED.
  
 --SIGNS- PROVIDE SIGNAGE DETAILS OF ALL SIGNS WITH
 HEIGHT AND WIDTH CALCULATIONS TO PROVIDE PROOF OF
 COMPLIANCE WITH 94-408.
  
 --SIGNS- THE DRIVING RANGE GAME SIGN IS DESCRIBED IN
 THE JUSTIFICATION STATEMENT AS AN INTERNAL SIGN. BASED
 ON SUBMITTED DRAWINGS THE SIGN IS INTERNAL TO A
 TRANSPARENT MESH THEREFORE WILL BE SEEN FROM THE ROW
 AND IS NOT EXEMPT FROM REGULATION PURSUANT SEC. 94-402
 (A) (1). INCLUDE ELEVATIONS AND DIMENSIONS FOR THE
 DRIVING RANGE GAME SIGN.
  
 --LIGHTING PLAN- THE LIGHTING PLAN FOR THE DRIVING
 RANGES NEED TO INDICATE THE FIXTURE TYPE, MOUNTING
 HEIGHT AND LOCATIONS. IN ADDITION THE EXTRAPOLATION OF
 THE LUMENS TO GET TO ZERO AT THE PROPERTY LINE IS
 UNCLEAR ESPECIALLY AT THE SOUTH WEST CORNER OF THE
 DRIVING RANGE.
  