Plan Review Details - Project Z17060017
Plan Review Stops For Project Z17060017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 07-11-2017 Cont ID  
Sent By rbrown Date 07-11-2017 Time 19:49 Rev Time 0.00
Received By rbrown Date 07-11-2017 Time 19:49 Sent To  
Notes
2017-07-11 19:52:12DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. NEW FLOOD INSURANCE RATE MAPS (FIRMS) WILL BE
 ADOPTED BEFORE OCTOBER 2017. THE PROPOSED BUILDING MAY
 BE IN FLOOD ZONE. THE CURRENT REQUIREMENT IS FOR THE
 ELEVATION OF THE FIRST FLOOR OF THE BUILDING AND ALL
 ASSOCIATED MECHANICAL EQUIPMENT (CHILLERS, GENERATORS
 ETC.) SHALL BE 12 INCHES (FREEBOARD) ABOVE THAT BASE
 FLOOD ELEVATION. PLEASE NOTE THAT THERE IS A PROPOSAL
 TO INCREASE THE FREEBOARD TO 24 INCHES SOMETIME AFTER
 THE MIDDLE OF MAY 2017.
  
 3. BUILDING SIZE. WHEN SUBMITTED FOR BUILDING PERMIT,
 THE PLANS SHALL SHOW THAT THE TYPE OF CONSTRUCTION FOR
 THE BUILDINGS WILL BE IN ACCORDANCE WITH THE HEIGHT,
 AREA AND OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE
 FLORIDA BUILDING CODE
  
 4. BUILDING LOCATION RELATIVE TO THE PROPERTY LINE AND
 OTHER STRUCTURES. WHEN SUBMITTED FOR BUILDING PERMIT,
 COMPLIANCE WITH ALL BUILDING SEPARATION, PERCENTAGE OF
 OPENINGS AND OPENING PROTECTIVE REQUIREMENTS OF
 CHAPTERS 6 AND 7 OF THE FLORIDA BUILDING CODE SHALL BE
 VERIFIED.
  
 5. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 6. GREASE INTERCEPTOR. A GREASE INTERCEPTOR WILL BE
 REQUIRED. PLEASE CONTACT JEFFREY ODOMS, UTILITIES O&M
 SUPERINTENDENT, PUBLIC UTILITIES DEPARTMENT, FATS OILS
 AND GREASE DIVISION, AT (561) 822-2172, OR BY EMAIL:
 [email protected]
  
 7. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
 8. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 07-11-2017 Cont ID  
Sent By mkhan Date 07-07-2017 Time 16:58 Rev Time 0.00
Received By mkhan Date 07-07-2017 Time 16:58 Sent To  
Notes
2017-07-07 16:59:30CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: PALM BEACH TOUR & TRANSPORTATION - 1422
 OKEECHOBEE RD. - Z17060017
  
 RESPONSE: PASSED WITH CONDITION
  
 DATE: JULY 11, 2017
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR
 TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED FROM THE FOLLOWING WEBSITE LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE "AUTO-CALC
 CERTIFIED COST ESTIMATE FORM" FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL
 WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE
 FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. WHAT IS THE PLAN FOR WATER AND SANITARY SEWER
 SERVICE FOR THE PROPOSED WASH AREA/BAY (AS SHOWN IN THE
 'BUILDING FLOOR PLANS - 3.1')? SUBMIT UTILITY PLAN FOR
 WATER AND SEWER WITH THE FINAL PLANS;
  
 4. WHAT IS THE PLAN FOR FIRE PROTECTION FOR THE
 PROPOSED "BUILDING B"? SHOW PROPOSED FIRE LINE AND
 BACKFLOW PREVENTER, METER ASSEMBLY ETC. IN THE UTILITY
 PLAN DURING FINAL PLANS SUBMITTALS;
  
 5. SHOW ON THE FINAL PLANS ADA ACCESSIBLE RAMP ON THE
 SIDEWALK FOR THE PROPOSED DRIVE/ACCESS AND ADD A DETAIL
 FOR THE SPECIFIC RAMP TYPE;
  
 6. EXISTING WATER SERVICE CONNECTIONS/WATER METERS
 SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND
 CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES
 LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL
 PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY
 PLANS ACCORDINGLY;
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 07-07-2017 Cont ID  
Sent By pleduc Date 07-07-2017 Time 11:19 Rev Time 0.00
Received By pleduc Date 07-07-2017 Time 11:15 Sent To  
Notes
2017-07-07 11:18:48THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN SUBMITTAL PURPOSES, THE PARKING GARAGE
 FALLS UNDER NFPA 88A AND MEET THE APPLICABLE
 REQUIREMENTS.
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS
 AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 09-29-2017 Cont ID  
Sent By rcaranci Date 09-29-2017 Time 17:01 Rev Time 0.00
Received By rcaranci Date 09-29-2017 Time 17:01 Sent To  
Notes
2017-09-29 17:01:32TO: PAUL GRIELICH, SENIOR PLANNER
 FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 1422 OKEECHOBEE ROAD Z17060017
 SEPTEMBER 29, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. CONDITIONALLY SATISFIED. PLEASE UPDATE PLAN TO
 CURRENT LANDSCAPE CODE AS OF APRIL 21, 2017. THESE
 UPDATES INCLUDE TREE AND FLOWERING TREE REQUIREMENTS,
 FLORIDA FRIENDLY LANDSCAPE REQUIREMENTS, AND
 SUBSTITUTION OF PALM TREES.
 40 POINTS ARE REQUIRED FOR FLORIDA FRIENDLY LANDSCAPE
 POINTS.
  
 2. CONDITIONALLY SATISFIED. PLEASE PROVIDE LOCATIONS OF
 LIGHTING ON THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH
 LANDSCAPING.
  
 3. SATISFIED. PLEASE SHOW CALCULATIONS FOR BUFFER TREE
 REQUIREMENTS. THE EAST BUFFER DOES NOT MEET THE CODE
 REQUIREMENTS AS SHOWN.
  
 4. SATISFIED. SOME LANDSCAPE AREA CAN BE GAINED IF THE
 CURB IS LOCATED IN PLACE OF WHEEL STOPS, ALLOWING THE
 OVERHANG TO BE GRASS OR GROUNDCOVER.
  
 5. SATISFIED. DOORS ARE SHOWN ON THE EAST AND SOUTH
 SIDES OF THE NEW BUILDING EXITING INTO LANDSCAPE
 BUFFERS. REQUIRED LANDSCAPING CANNOT BE ELIMINATED TO
 PROVIDE ACCESS. PLEASE REVISE.
  
 6. CONDITIONALLY SATISFIED. THE ADA SPACE NEEDS A TREE
 OR PALMS TO THE EAST TO SATISFY THE TERMINAL ISLAND
 REQUIREMENT. PLEASE REVISE.
 CHANGE TO A TRIPLE ALEXANDER TO MEET CODE.
  
 7. SATISFIED. PLEASE SHOW CALCULATIONS AND LANDSCAPE
 AREAS PROVIDED TO MEET THE PARKING AREA LANDSCAPE
 REQUIREMENTS OF SECTION 94-44(C)(3) AND (4).
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
 2. PRIOR TO ISSUANCE OF A LANDSCAPE PERMIT FOR THE
 PROJECT THE APPLICANT SHALL REVISE THE LANDSCAPE PLAN
 TO MEET CURRENT FLORIDA FRIENDLY LANDSCAPE CODE
 REQUIREMENTS OF 40 POINTS.
 3. PRIOR TO ISSUANCE OF A LANDSCAPE PERMIT FOR THE
 PROJECT THE APPLICANT SHALL REVISE THE LANDSCAPE PLAN
 TO CHANGE THE ALEXANDER PALM FROM A DOUBLE TO A TRIPLE
 TRUNK TO MEET CODE REQUIREMENTS.
 4. PRIOR TO ISSUANCE OF A LANDSCAPE PERMIT FOR THE
 PROJECT THE APPLICANT SHALL REVISE THE LANDSCAPE PLAN
 TO SHOW THE LOCATIONS OF LIGHTING TO AVOID CONFLICTS
 WITH LANDSCAPING.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 07-10-2017 Cont ID  
Sent By rcaranci Date 07-10-2017 Time 17:24 Rev Time 0.00
Received By rcaranci Date 07-10-2017 Time 17:24 Sent To  
Notes
2017-07-10 17:24:24FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: 1422 OKEECHOBEE ROAD Z17060017
 JULY 10, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE UPDATE PLAN TO CURRENT LANDSCAPE CODE AS OF
 APRIL 21, 2017. THESE UPDATES INCLUDE TREE AND
 FLOWERING TREE REQUIREMENTS, FLORIDA FRIENDLY LANDSCAPE
 REQUIREMENTS, AND SUBSTITUTION OF PALM TREES.
  
 2. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 3. PLEASE SHOW CALCULATIONS FOR BUFFER TREE
 REQUIREMENTS. THE EAST BUFFER DOES NOT MEET THE CODE
 REQUIREMENTS AS SHOWN.
  
 4. SOME LANDSCAPE AREA CAN BE GAINED IF THE CURB IS
 LOCATED IN PLACE OF WHEEL STOPS, ALLOWING THE OVERHANG
 TO BE GRASS OR GROUNDCOVER.
  
 5. DOORS ARE SHOWN ON THE EAST AND SOUTH SIDES OF THE
 NEW BUILDING EXITING INTO LANDSCAPE BUFFERS. REQUIRED
 LANDSCAPING CANNOT BE ELIMINATED TO PROVIDE ACCESS.
 PLEASE REVISE.
  
 6. THE ADA SPACE NEEDS A TREE OR PALMS TO THE EAST TO
 SATISFY THE TERMINAL ISLAND REQUIREMENT. PLEASE REVISE.
  
 7. PLEASE SHOW CALCULATIONS AND LANDSCAPE AREAS
 PROVIDED TO MEET THE PARKING AREA LANDSCAPE
 REQUIREMENTS OF SECTION 94-44(C)(3) AND (4).
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By tward Date 10-16-2017 Time 17:20 Sent To  
Notes
2017-10-16 17:20:23THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS, FROM THE REVIEW OF THE
 9/26/2017 SUBMITTAL PACKAGE, MUST BE ADDRESSED PRIOR TO
 SITE PLAN APPROVAL:
  
 1. NEW FEMA FIRM MAPS AND TWO FEET OF FREEBOARD ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN SPECIAL FLOOD
 HAZARD AREAS ARE NOW IN EFFECT. THE MAPS ARE AVAILABLE
 AT HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?
  
 2. LABEL VERTICAL DATUM ON SHEET 1 OF 2 OF THE
 PRELIMINARY ENGINEERING PLAN.
  
 3. PROVIDE GRADING PLAN SHOWING WHERE SURFACE RUNOFF
 WILL DRAIN TO.
  
 4. CONSIDER ADDING PIPES BETWEEN CB#1/MH#4 AND BETWEEN
 MH#3/MH#6 TO CREATE A MANIFOLD SYSTEM.
  
 5. SHOW MILL AND OVERLAY LIMITS FOR TRENCH CUT(S) IN
 RIGHT-OF-WAY.
  
 6. REPLACE SIDEWALK AND CURB ALONG PROPERTY FRONTAGE.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE A COPY OF THE SFWMD ERP PERMIT AND SIGNED
 AND SEALED DRAINAGE CALCULATIONS. GIVEN THE PROPOSED
 LAYOUT OF THE EXFILTRATION TRENCH, THE SFWMD ALTERNATE
 EXFILTRATION TRENCH EQUATION FOR WHEN THE TRENCH WIDTH
 IS GREATER THAN TWO TIMES THE TOTAL TRENCH DEPTH SHOULD
 BE USED.
  
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 10-16-2017 Cont ID  
Sent By vnoel Date 10-16-2017 Time 08:06 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-07-12 08:37:021. UNITY OF TITLE WILL BE REQUIRED. APPLICATION IS MADE
 THROUGH THIS DEPT.
 2. ARE THE 2 WATER METERS AT THE WEST ENTRANCE TO
 REMAIN? IF SO, THEY WILL NEED TO BE RELOCATED OR CAPPED
 BACK TO THE MAIN.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 2 Status P Date   Cont ID  
Sent By   Date 10-05-2017 Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status F Date 07-11-2017 Cont ID  
Sent By   Date 07-11-2017 Time   Rev Time  
Received By   Date 07-11-2017 Time   Sent To  
Notes
2017-07-11 18:13:54THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
 THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR
 TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1 - PROVIDE TOPOGRAPHIC SURVEY SO THAT WE CAN VERIFY IF
 EXISTING SIDEWALK IS ADA ACCESIBLE AND MEETS CURRENT
 WIDTH REQUIREMENTS.
 2 - PROVIDE ONE DRIVEWAY ON OLD OKEECHOBEE.
 3 - SHOW CLEAR SIGHT LINE TRIANGLE.
  
 ERIK D. FERGUSON, PE
 SENIOR PROJECT ENGINEER
 [email protected]
 561-494-1092

Review Stop Z ZONING
Rev No 1 Status F Date 07-11-2017 Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By pgreilic Date 07-11-2017 Time 15:50 Sent To  
Notes
2017-07-11 15:54:14ZBA 3357
 CLASS B SPECIAL USE PERMIT
 1422 OKEECHOBEE ROAD
  
  
 1.) CONSTRUCTION OF PROPOSED BUILDING B WILL REQUIRE
 RELOCATION OF EXISTING UTILITIES AND ABANDONMENT OF
 EXISTING 6 FOOT UTILITY EASEMENT
  
 2.) ONLY 8.5 FEET REQUIRED WIDTH INSTEAD OF 9 FOR
 PARKING SPACE, CONSIDER REVISION
  
 3.) SHOW PROPOSED LOCATION OF PARKING SPACES IN
 PROPOSED BUILDING B ON SITE PLAN
  
 4.) PROVIDE DETAILS FOR PROPOSED PARKING SPACES AND
 DUMPSTER
  
 5.) REVISE LOCATION OF BUILDING ENTRANCE/EXIT TO AVOID
 PROPOSED LANDSCAPE BUFFER
  
 6.) PROVIDE REQUIRED TRAFFIC CONCURRENCY LETTER
  
 7.) PROVIDE REQUIRED UTILITY LETTERS
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF
 FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING, THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
  
 PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]
  