Plan Review Details - Project Z17030035
Plan Review Stops For Project Z17030035
Review Stop L LANDSCAPING
Rev No 2 Status P Date 05-25-2017 Cont ID  
Sent By rcaranci Date 05-25-2017 Time 16:24 Rev Time 0.00
Received By rcaranci Date 05-25-2017 Time 16:24 Sent To  
Notes
2017-05-25 16:24:30FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: BRAMAN MOTORCARS Z17030035
 MAY 25, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A HEDGE ON THE NORTH SIDE
 OF THE GENERATOR.
  
 2. SATISFIED. PLEASE ADD A HEDGE ADJACENT TO THE
 BACKFLOW PREVENTER PARALLEL TO THE FENCE IN THE
 LANDSCAPE ISLAND, AND PROVIDE A SCREENING HEDGE FOR THE
 FPL TRANSFORMER. THIS IS LOCATED ALONG THE NORTH
 PROPERTY LINE NORTH OF BUILDING C.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-18-2017 Cont ID  
Sent By rcaranci Date 04-18-2017 Time 17:05 Rev Time 0.00
Received By rcaranci Date 04-18-2017 Time 17:05 Sent To  
Notes
2017-04-18 17:05:23FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: BRAMAN MOTORCARS Z17030035
 APRIL 18, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A HEDGE ON THE NORTH SIDE OF THE
 GENERATOR.
  
 2. PLEASE ADD A HEDGE ADJACENT TO THE BACKFLOW
 PREVENTER PARALLEL TO THE FENCE IN THE LANDSCAPE
 ISLAND, AND PROVIDE A SCREENING HEDGE FOR THE FPL
 TRANSFORMER. THIS IS LOCATED ALONG THE NORTH PROPERTY
 LINE NORTH OF BUILDING C.
  

Review Stop Z ZONING
Rev No 4 Status P Date 08-22-2017 Cont ID  
Sent By eschneid Date 08-22-2017 Time 10:39 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 06-16-2017 Cont ID  
Sent By eschneid Date 06-16-2017 Time 10:37 Rev Time 0.00
Received By eschneid Date 06-16-2017 Time 15:00 Sent To  
Notes
2017-06-16 15:00:49VERIFY GAS LINES AND METERS DO NOT CONFLICT WITH THE
 LANDSCAPE NORTH OF THE GENERATOR.

Review Stop Z ZONING
Rev No 2 Status F Date 06-01-2017 Cont ID  
Sent By eschneid Date 06-01-2017 Time 08:56 Rev Time 0.75
Received By eschneid Date 06-01-2017 Time 08:56 Sent To  
Notes
2017-06-01 08:56:19CASE NO. PB 1222O
 BRAMAN GENERATOR MINOR - MAY 11, 2017 RESUB
 2901 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THESE COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY AUGUST 1, 2017),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) TWO ELECTRIC CAR SERVICE BAYS WERE ADDED AS PART OF
 PERMIT REVISION 16120004. THESE ARE LOCATED TO THE EAST
 OF THE INTERIOR LOADING ZONE AND REPLACED SQUARE
 FOOTAGE ALLOCATED TO SERVICE PARTS/STORAGE ON THE SITE
 PLAN. THE SITE PLAN AND DATA TABLES (INCLUDING PARKING
 REQUIREMENTS) MUST BE UPDATED TO SHOW ACCURATE
 CONDITIONS. THIS AREA WAS SHOWN PREVIOUSLY AS A DETAIL
 AREA, WHICH STAFF WAS NOT REQUIRING TO BE COUNTED AS A
 SERVICE BAY, ON THE ARCHITECTURAL SITE PLAN BUT NOT
 REFLECTED ON THE SITE PLAN.
  
 2) PROVIDE THE MOST RECENT OVERALL GROUND FLOOR PLAN,
 SHEET 1.1.1, WHICH SHOWS THE CONVERSION OF THE TWO
 DETAIL SPACES TO THE ELECTRIC CAR SERVICE BAYS AS WELL
 AS THE OTHER INTERNAL GROUND FLOOR CHANGES WHICH HAVE
 OCCURRED THROUGH THE BUILDING PERMIT REVISION PROCESS.
  
 3) PROVIDE SHEETS A1.2.1, A1.3.1, A1.5.1, A1.6.1 AND
 A1.7.1 THE OVERALL FLOOR AND ROOF PLANS FOR THE GARAGE
 LEVELS.
  
 4) EXPLAIN WHY SHEET 1.2.1C SHOWS A TIRE CAROUSEL
 ACROSS FROM THE ADA PARKING SPACES, YET THE RECENT
 SUBMITTED BUILDING PERMIT REVISION SHOWS THIS AREA AS
 OPEN TO BELOW? IF THIS IS NOT THE TIRE CAROUSEL, THEN
 YOU NEED TO REMOVE THE NOMENCLATURE FROM THE MINOR
 AMENDMENT PLANS; OTHERWISE, THE PERMIT PLANS NEED TO BE
 CORRECTED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 04-10-2017 Cont ID  
Sent By eschneid Date 04-10-2017 Time 15:43 Rev Time 0.00
Received By eschneid Date 04-10-2017 Time 15:43 Sent To  
Notes
2017-04-10 15:44:01CASE NO. PB 1222O
 BRAMAN GENERATOR MINOR
 2901 OKEECHOBEE BOULEVARD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THESE COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY JUNE 10, 2017), THE
 CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER ACTION
 SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) PLEASE SUBMIT PLANS WITH THE EXISTING CONDITION BASE
 LAYER TURNED OFF.
  
 2) THE JUSTIFICATION LETTER STATES THAT AN ENCLOSED
 DROP-OFF SERVICE AREA HAS BEEN REMOVED FROM THE PLANS.
 STAFF IS UNABLE TO LOCATE WHERE THIS HAS BEEN REMOVED.
 PLEASE PROVIDE A MARKED UP PLAN TO SHOW WHERE THIS AREA
 IS.
  
 3) PROVIDE THE DEPTH DIMENSION AND A DETAIL FOR THE
 COMPACT SPACES ON THE PLANS.
  
 4) THE COMPACT PARKING SPACE ON THE SECOND FLOOR
 ADJACENT TO STAIR 4 DOES NOT MEET THE REQUIRED MINIMUM
 EIGHT (8) FOOT STALL WIDTH AT THE ENTRANCE TO THE
 PARKING SPACE.
  
 5) WHY ARE THERE TWO BACKFLOW PREVENTERS SHOWN ALONG
 EXCHANGE COURT? IT IS STATED THAT THE ONE BEHIND
 BUILDING C IS RELOCATED. DOES THIS MEAN THAT THERE IS
 NO LONGER ONE BEHIND BUILDING E (NORTHWEST CORNER OF
 THE SITE)?
  
  
  