Plan Review Details - Project Z17030023
Plan Review Stops For Project Z17030023
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 04-11-2017 Cont ID  
Sent By rbrown Date 04-11-2017 Time 18:57 Rev Time 0.00
Received By tward Date 04-12-2017 Time 09:18 Sent To  
Notes
2017-04-11 18:59:42NO COMMENTS ON INFORMAL SITE PLAN REVIEW TO COVERT THE
 EXISTING 6,000 SF TEMPORARY STORAGE BUILDING INTO A
 PERMANENT STORAGE BUILDING.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 04-05-2017 Cont ID  
Sent By mkhan Date 04-05-2017 Time 15:50 Rev Time 0.00
Received By mkhan Date 04-05-2017 Time 15:50 Sent To  
Notes
2017-04-10 10:19:41CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 DATE: 04/10/2017
  
 Z17030023: 6610 N JOG RD - SWA FACILITY (PB CASE NO.
 943K)
  
 AFTER REVIEWING THE SUBMITTED PLANS, WE HAVE THE
 FOLLOWING COMMENT:
  
 1. PER THE 'GENERAL NOTES NO. 3' ON SHEET L-2, ALL
 PROPOSED LANDSCAPED AREAS ARE TO RECEIVE AN AUTOMATIC,
 UNDERGROUND SPRINKLER SYSTEM BUT NO IRRIGATION SYSTEM
 IS NOT SHOWN ON THE PLAN. PLEASE SUBMIT ESTIMATE OF
 IRRIGATION FLOW DEMAND/REQUIREMENT IN GALLONS PER
 MINUTES AND ALSO SHOW ON THE PLANS WHERE AND HOW
 IRRIGATION LINE WILL BE TIED TO AN EXISTING WATER MAIN;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 06-09-2017 Cont ID  
Sent By pleduc Date 06-09-2017 Time   Rev Time 0.00
Received By pleduc Date 06-09-2017 Time 16:37 Sent To  
Notes
2017-06-09 16:39:382ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED MAY
 30, 2017, FROM SONG & ASSOCIATES, INC., TOERIC
 SCHNEIDER, AICP, PRINCIPAL PLANNER, THE PREVIOUSLY
 SUBMITTED FIRE PREVENTION BUREAU COMMENTS HAVE BEEN
 ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 04-05-2017 Cont ID  
Sent By pleduc Date 04-05-2017 Time   Rev Time 0.00
Received By pleduc Date 04-05-2017 Time 16:39 Sent To  
Notes
2017-04-05 16:48:56THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES AT ALL
 TIMES.
  
  
 2. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 3. THE BUILDING OCCUPANCY SHALL COMPLY WITH THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE, INCLUDING
 NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
  
 4. FOR ANY REQUIRED OCCUPANCY CHANGE PLAN REVIEW
 SUBMITTAL, PLEASE INCLUDE THE OCCUPANCY TYPE, PER THE
 FLORIDA FIRE PREVENTION CODE, AND ALL APPLICABLE
 PRODUCT CLASSIFICATION HAZARDS, ANY PROPOSED RACKING
 INCLUDING HEIGHT, SHELVING TYPE, PALLET TYPE, ETC.
  
  
  
 5. ALL EXISTING (OR PROPOSED) HYDRANTS(WATER SUPPLY)
 FOR THIS BUILDING SHALL BE CLEARLY INDICATED AND
 IDENTIFIED.
  
  
  
 6. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 7. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY ACCESS LOCKS, PADLOCKS
 AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
  
 8. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 9. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 08-30-2017 Cont ID  
Sent By rcaranci Date 08-30-2017 Time 11:13 Rev Time 0.00
Received By rcaranci Date 08-30-2017 Time 11:13 Sent To  
Notes
2017-08-30 11:13:59FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SWA WAREHOUSE Z17030023
 AUGUST 30, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A CHART AND ADD THE
 DROUGHT TOLERANCE LEVEL FOR EACH PLANT SPECIES ON THE
 PLANT LIST TO SHOW COMPLIANCE WITH SECTION 94-442(G)
 FLORIDA FRIENDLY LANDSCAPING REQUIREMENTS. ADDING A
 COLUMN IDENTIFYING NATIVE PLANTS IS ALSO SUGGESTED.
 PLEASE INCLUDE THE CHART.
  
 2. SATISFIED. PLEASE SHOW CURBS AT THE LANDSCAPE AREAS
 ADJACENT TO THE PARKING AREA, OR WHEEL STOPS AT THE
 FRONT OF THE SPACES AND CURBS AT THE TERMINAL ISLANDS.
 PLEASE INCLUDE SOME TYPE OF PROTECTION BETWEEN THE
 PARKING AND DRIVEWAY AND THE TERMINAL LANDSCAPE ISLANDS
 AT THE END OF THE PARKING SPACES, AND SHOW THE WHEEL
 STOPS ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 4. SATISFIED. PLEASE INDICATE WHERE IRRIGATION WILL BE
 PROVIDED.
  
 5. SATISFIED. PLEASE CHECK THE APPROVED LANDSCAPE PLANS
 TO VERIFY THE LANDSCAPE BUFFER ALONG JOG ROAD MEETS
 MINIMUM CODE STANDARDS.
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 06-22-2017 Cont ID  
Sent By rcaranci Date 06-22-2017 Time 10:56 Rev Time 0.00
Received By rcaranci Date 06-22-2017 Time 10:56 Sent To  
Notes
2017-06-22 10:57:51FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SWA WAREHOUSE Z17030023
 JUNE 22, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. NOT SATISFIED. PLEASE PROVIDE A CHART AND ADD THE
 DROUGHT TOLERANCE LEVEL FOR EACH PLANT SPECIES ON THE
 PLANT LIST TO SHOW COMPLIANCE WITH SECTION 94-442(G)
 FLORIDA FRIENDLY LANDSCAPING REQUIREMENTS. ADDING A
 COLUMN IDENTIFYING NATIVE PLANTS IS ALSO SUGGESTED.
 PLEASE INCLUDE THE CHART.
  
 2. NOT SATISFIED. PLEASE SHOW CURBS AT THE LANDSCAPE
 AREAS ADJACENT TO THE PARKING AREA, OR WHEEL STOPS AT
 THE FRONT OF THE SPACES AND CURBS AT THE TERMINAL
 ISLANDS.
 PLEASE INCLUDE SOME TYPE OF PROTECTION BETWEEN THE
 PARKING AND DRIVEWAY AND THE TERMINAL LANDSCAPE ISLANDS
 AT THE END OF THE PARKING SPACES, AND SHOW THE WHEEL
 STOPS ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON
 THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 4. SATISFIED. PLEASE INDICATE WHERE IRRIGATION WILL BE
 PROVIDED.
  
 5. SATISFIED. PLEASE CHECK THE APPROVED LANDSCAPE PLANS
 TO VERIFY THE LANDSCAPE BUFFER ALONG JOG ROAD MEETS
 MINIMUM CODE STANDARDS.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 04-10-2017 Cont ID  
Sent By rcaranci Date 04-10-2017 Time 16:37 Rev Time 0.00
Received By rcaranci Date 04-10-2017 Time 16:37 Sent To  
Notes
2017-04-10 16:39:31FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: SWA WAREHOUSE Z17030023
 APRIL 10, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A CHART AND ADD THE DROUGHT TOLERANCE
 LEVEL FOR EACH PLANT SPECIES ON THE PLANT LIST TO SHOW
 COMPLIANCE WITH SECTION 94-442(G) FLORIDA FRIENDLY
 LANDSCAPING REQUIREMENTS. ADDING A COLUMN IDENTIFYING
 NATIVE PLANTS IS ALSO SUGGESTED.
  
 2. PLEASE SHOW CURBS AT THE LANDSCAPE AREAS ADJACENT TO
 THE PARKING AREA, OR WHEEL STOPS AT THE FRONT OF THE
 SPACES AND CURBS AT THE TERMINAL ISLANDS.
  
 3. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE
 LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING.
  
 4. PLEASE INDICATE WHERE IRRIGATION WILL BE PROVIDED.
  
 5. PLEASE CHECK THE APPROVED LANDSCAPE PLANS TO VERIFY
 THE LANDSCAPE BUFFER ALONG JOG ROAD MEETS MINIMUM CODE
 STANDARDS.
  
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 06-20-2017 Cont ID  
Sent By tward Date 06-20-2017 Time 16:46 Rev Time 0.00
Received By tward Date 06-20-2017 Time 17:02 Sent To  
Notes
2017-06-20 17:00:49THE FOLLOWING COMMENTS ARE FROM THE REVIEW OF THE JUNE
 8, 2017 REVIEW PACKAGE:
  
 1. CLARIFY THE FOLLOWING IN THE STORMWATER STATEMENT:
 A. LINE 3.A - USE OF THE 0.9 RUNOFF COEFFICIENT IN THE
 FORMULA 0.9 X 1,200 FT2 X 1 INCH X 1 FT / 12 IN. THE
 VOLUME OF 1 INCH OF RUNOFF IS EQUAL TO 1 INCH TIMES THE
 AREA OF THE SITE.
  
 B. LINE 4.A AND 4.B - INDICATE ON THE SITE PLAN IN
 LOWER RIGHT OF SHEET WHERE THE SWALE DIMENSIONS WERE
 MEASURED. THE LENGTH OF THE FENCE ALONG THE WEST SIDE
 OF THE SITE MEASURES LESS THAN 300 FEET. THE DISTANCE
 BETWEN THE LEFT AND RIGHT TOP OF SLOPE MEASURED BETWEEN
 55 FEET AND 65 FEET. THE WIDTH OF THE BOTTOM OF THE
 SWALE MEASURES BETWEEN 5 FEET AND 7.5 FEET.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop STORM STORMWATER
Rev No 1 Status P Date 04-12-2017 Cont ID  
Sent By tward Date 04-12-2017 Time 09:09 Rev Time 0.00
Received By tward Date 04-12-2017 Time 09:18 Sent To  
Notes
2017-04-12 09:18:01THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE FREEBOARD REQUIREMENT FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA IS ONE FOOT ABOVE BASE FLOOD
 ELEVATION.
  
 3. RUNOFF CALCUILATIONS INCLUDED IN THE STORMWATER
 STATEMENT ON SHEET A-100 NEED TO BE REVISED. "1-INCH
 RUNOFF", BY DEFINITION, HAS TAKEN INTO ACCOUNT THE
 IMPERVIOUS/PERVIOUS AFFECT ON RAINFALL. THE VOLUME OF
 RUNOFF SHOULD BE CALCULATED PER SFWMD CRITERIA: THE
 LARGER OF (A) 1-INCH TIMES TOTAL AREA OR (B) 2.5-INCHES
 TIMES PERCENT IMPERVIOUS TIMES [TOTAL AREA LESS LAKE
 AREA].
  
 4. JOG ROAD IS MAINTAINED BY PALM BEACH COUNTY. ANY
 WORK IN THE RIGHT-OF-WAY OF JOG ROAD WILL REQUIRE A
 PERMIT FROM PALM BEACH COUNTY.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 04-11-2017 Cont ID  
Sent By vnoel Date 04-11-2017 Time 08:14 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-04-11 08:13:061. SURVEY NEEDS TO BE SIGNED AND SEALED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 08-30-2017 Cont ID  
Sent By eschneid Date 08-30-2017 Time 10:22 Rev Time 0.25
Received By eschneid Date 08-30-2017 Time 10:22 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 06-27-2017 Cont ID  
Sent By eschneid Date 06-27-2017 Time 09:35 Rev Time 0.50
Received By eschneid Date 06-27-2017 Time 09:34 Sent To  
Notes
2017-06-27 09:35:50CASE NO. PB 943K
 JUNE 6, 2017 RESUBMITTAL
 SOLID WASTE AUTHORITY EAST LANDFILL STORAGE BUILDING
 6610 N. JOG ROAD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY AUGUST 27, 2017),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($200).
  
 1) REPEAT COMMENT: PROVIDE PARKING STALL DETAILS FOR
 THE PROPOSED PARKING AREA ON THE PLANS. THE PARKING
 STALL DETAIL SHALL MEET CITY STANDARDS. PLEASE SEE
 PARKING DETAIL SENT UNDER SEPARATE COVER.
  

Review Stop Z ZONING
Rev No 1 Status F Date 04-07-2017 Cont ID  
Sent By eschneid Date 04-07-2017 Time 15:01 Rev Time 0.00
Received By eschneid Date 04-07-2017 Time 15:01 Sent To  
Notes
2017-04-07 15:02:10CASE NO. PB 943K
 SOLID WASTE AUTHORITY EAST LANDFILL STORAGE BUILDING
 6610 N. JOG ROAD
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FOUR
 (4) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY JUNE 12, 2017),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($200).
  
 1) PROVIDE WRITTEN VERIFICATION FROM THE CITY'S
 BUILDING DEPARTMENT THAT THE PARKING AREA DOES NOT NEED
 TO CONTAIN AN ADA PARKING SPACE AND AN ACCESSIBLE
 SIDEWALK TO THE JOG ROAD RIGHT-OF-WAY. IF ONE OR BOTH
 ARE REQUIRED, THEN THE PLANS MUST BE UPDATED.
  
 2) THE DRIVE AISLE TO THE PARKING SPACES FROM THE
 EXISTING GATE MUST BE PAVED.
  
 3) PROVIDE PARKING STALL DETAILS FOR THE PROPOSED
 PARKING AREA ON THE PLANS.
  
 4) PROVIDE THE DIMENSION WIDTH OF THE DRIVE TO THE
 BUILDING ON THE SITE PLAN. THIS SHALL BE A MINIMUM OF
 20 FEET WIDE FOR TWO-WAY TRAFFIC AND FIRE DEPARTMENT
 ACCESS.