Plan Review Details - Project Z17020017
Plan Review Stops For Project Z17020017
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 03-08-2017 Cont ID  
Sent By rbrown Date 03-08-2017 Time 12:29 Rev Time 0.00
Received By tward Date 03-08-2017 Time 12:48 Sent To  
Notes
2017-03-08 12:30:36DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY
 CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE
 HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED
 ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT
 AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE
 PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE
 FOR THE TYPE OF CONSTRUCTION USED.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, GAS SYSTEMS, GENERATORS, FIRE ALARM SYSTEMS,
 FIRE SPRINKLER AND OTHER FIRE SUPPRESSION SYSTEMS,
 GREASE INTERCEPTORS, SITE LIGHTING, SITE LANDSCAPE,
 SITE IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 03-07-2017 Cont ID  
Sent By mkhan Date 03-07-2017 Time 13:36 Rev Time 0.00
Received By mkhan Date 03-07-2017 Time 13:36 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-03-2017 Cont ID  
Sent By pleduc Date 03-03-2017 Time   Rev Time 0.00
Received By pleduc Date 03-03-2017 Time 14:41 Sent To  
Notes
2017-03-03 15:00:41THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE DETAILED
 INFORMATION AS TO IF THE OCCUPANCY WILL REMAIN OPEN
 DURING CONSTRUCTION AND SAFEGUARDS THAT WILL BE PUT IN
 PLACE TO ENSURE LIFE SAFETY AND SAFE EXIT AT ALL TIMES.
  
 7. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
 8. FOR PLAN REVIEW SUBMITTAL, PLEASE REVIEW THE REAR
 EXIT MODIFICATIONS FOR COMPLIANCE WITH THE REQUIREMENTS
 OF NFPA 101, CHAPTER 7 AND 37.
  
 37.2.6 TRAVEL DISTANCE TO EXITS. TRAVEL DISTANCE SHALL
 BE AS SPECIFIED IN 37.2.6.1 AND 37.2.6.2 AND SHALL BE
 MEASURED IN ACCORDANCE WITH SECTION 7.6.
 37.2.6.1 IN BUILDINGS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH 9.7.1.1(1), TRAVEL DISTANCE SHALL NOT
 EXCEED 250 FT (76 M).
 37.2.6.2 IN BUILDINGS NOT COMPLYING WITH 37.2.6.1, THE
 TRAVEL DISTANCE SHALL NOT EXCEED 150 FT (46 M).
  
 37.2.7 DISCHARGE FROM EXITS.
 37.2.7.1 EXIT DISCHARGE SHALL COMPLY WITH SECTION 7.7
 AND 37.2.7.2.
  
 7.7 DISCHARGE FROM EXITS.
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT
 DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH
 7.7.1.4.
 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS
 OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH
 AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO
 A PUBLIC WAY.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.8 FOR EVERY
 BUILDING AND STRUCTURE WHERE REQUIRED IN CHAPTERS 11
 THROUGH 43. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 ACCESS SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE PURPOSES OF THIS REQUIREMENT, EXIT
 DISCHARGE SHALL INCLUDE ONLY DESIGNATED STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS,WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE TIME THAT THE CONDITIONS OF
 OCCUPANCY REQUIRE THAT THE MEANS OF EGRESS BE AVAILABLE
 FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR SUCH PERIODS OF TIME AS ARE NECESSARY
 TO MAINTAIN THE ILLUMINATION TO THE MINIMUM CRITERIA
 VALUES HEREIN SPECIFIED.
  
  
  
 9. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 10. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop L LANDSCAPING
Rev No 3 Status P Date 04-27-2017 Cont ID  
Sent By rcaranci Date 04-27-2017 Time 11:39 Rev Time 0.00
Received By rcaranci Date 04-27-2017 Time 11:39 Sent To  
Notes
2017-04-27 11:39:57FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC 2995 45TH ST. Z17020017
 APRIL 27, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. THE LIVE OAK TREE TO THE WEST OF THE
 EXISTING BUILDING MAY BE CLASSIFIED AS A SPECIMEN TREE
 DUE TO ITS SIZE. THE APPLICANT SHOULD CONSIDER
 DESIGNING THE PATIO AREA IN SUCH A WAY TO AVOID REMOVAL
 OF THE TREE AND TAKE ADVANTAGE OF THE SHADE AND
 BENEFITS THE TREE CAN PROVIDE FOR THE OUTDOOR SEATING
 AREA. AN ARBORIST SHOULD BE CONSULTED ON OPTIONS FOR
 PRUNING OF BRANCHES AND ROOTS TO ACCOMMODATE THE
 BUILDING ADDITION AND USING PAVERS AROUND THE TREE FOR
 THE SEATING AREA.
  
 2. SATISFIED. PLEASE PROVIDE A CHART SHOWING COMPLIANCE
 WITH FLORIDA FRIENDLY LANDSCAPING PER SECTION 94-442
 (G).
  
 3. SATISFIED. PLEASE PROVIDE CALCULATIONS TO SHOW THE
 LANDSCAPING MEETS THE 30% REQUIRED AROUND THE BUILDING
 PER SECTION 94-443(E)(1).
  
 4. SATISFIED. PLEASE PROVIDE BUFFER TREE CALCULATIONS
 AND OVERALL TREE AND FLOWERING TREE REQUIREMENTS TO
 SHOW CODES ARE MET.
  
 5. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 6. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 7. SATISFIED. ALL MISSING LANDSCAPING WILL NEED TO BE
 REPLACED, SO ANY UPDATING OF SPECIES OR MODIFICATIONS
 MUST BE PROPOSED AT THIS TIME.
 ADDITIONAL COMMENTS 4/25/17:
  
 8. SATISFIED. PLEASE CHANGE THE NATIVE LISTING FOR
 CRAPE MYRTLE AND PINK TABEBUIA TO NO.
  
 9. SATISFIED. MODIFY THE FLORIDA FRIENDLY LIST TO
 DOCUMENT GRASS CREDIT AND MOISTURE SENSING CONTROLLER
 CREDIT.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 04-25-2017 Cont ID  
Sent By rcaranci Date 04-25-2017 Time 11:22 Rev Time 0.00
Received By rcaranci Date 04-25-2017 Time 11:22 Sent To  
Notes
2017-04-25 11:24:19MEMO TO FILE
 PROJECT: RACETRAC 2995 45TH ST. Z17020017
 APRIL 25, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. THE LIVE OAK TREE TO THE WEST OF THE
 EXISTING BUILDING MAY BE CLASSIFIED AS A SPECIMEN TREE
 DUE TO ITS SIZE. THE APPLICANT SHOULD CONSIDER
 DESIGNING THE PATIO AREA IN SUCH A WAY TO AVOID REMOVAL
 OF THE TREE AND TAKE ADVANTAGE OF THE SHADE AND
 BENEFITS THE TREE CAN PROVIDE FOR THE OUTDOOR SEATING
 AREA. AN ARBORIST SHOULD BE CONSULTED ON OPTIONS FOR
 PRUNING OF BRANCHES AND ROOTS TO ACCOMMODATE THE
 BUILDING ADDITION AND USING PAVERS AROUND THE TREE FOR
 THE SEATING AREA.
  
 2. SATISFIED. PLEASE PROVIDE A CHART SHOWING COMPLIANCE
 WITH FLORIDA FRIENDLY LANDSCAPING PER SECTION 94-442
 (G).
  
 3. SATISFIED. PLEASE PROVIDE CALCULATIONS TO SHOW THE
 LANDSCAPING MEETS THE 30% REQUIRED AROUND THE BUILDING
 PER SECTION 94-443(E)(1).
  
 4. SATISFIED. PLEASE PROVIDE BUFFER TREE CALCULATIONS
 AND OVERALL TREE AND FLOWERING TREE REQUIREMENTS TO
 SHOW CODES ARE MET.
  
 5. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 6. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 7. SATISFIED. ALL MISSING LANDSCAPING WILL NEED TO BE
 REPLACED, SO ANY UPDATING OF SPECIES OR MODIFICATIONS
 MUST BE PROPOSED AT THIS TIME.
 ADDITIONAL COMMENTS 4/25/17:
  
 8. PLEASE CHANGE THE NATIVE LISTING FOR CRAPE MYRTLE
 AND PINK TABEBUIA TO NO.
  
 9. MODIFY THE FLORIDA FRIENDLY LIST TO DOCUMENT GRASS
 CREDIT AND MOISTURE SENSING CONTROLLER CREDIT.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-07-2017 Cont ID  
Sent By rcaranci Date 03-07-2017 Time 12:43 Rev Time 0.00
Received By rcaranci Date 03-07-2017 Time 12:43 Sent To  
Notes
2017-03-07 12:44:05FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: RACETRAC 2995 45TH ST. Z17020017
 MARCH 7, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. THE LIVE OAK TREE TO THE WEST OF THE EXISTING
 BUILDING MAY BE CLASSIFIED AS A SPECIMEN TREE DUE TO
 ITS SIZE. THE APPLICANT SHOULD CONSIDER DESIGNING THE
 PATIO AREA IN SUCH A WAY TO AVOID REMOVAL OF THE TREE
 AND TAKE ADVANTAGE OF THE SHADE AND BENEFITS THE TREE
 CAN PROVIDE FOR THE OUTDOOR SEATING AREA. AN ARBORIST
 SHOULD BE CONSULTED ON OPTIONS FOR PRUNING OF BRANCHES
 AND ROOTS TO ACCOMMODATE THE BUILDING ADDITION AND
 USING PAVERS AROUND THE TREE FOR THE SEATING AREA.
  
 2. PLEASE PROVIDE A CHART SHOWING COMPLIANCE WITH
 FLORIDA FRIENDLY LANDSCAPING PER SECTION 94-442 (G).
  
 3. PLEASE PROVIDE CALCULATIONS TO SHOW THE LANDSCAPING
 MEETS THE 30% REQUIRED AROUND THE BUILDING PER SECTION
 94-443(E)(1).
  
 4. PLEASE PROVIDE BUFFER TREE CALCULATIONS AND OVERALL
 TREE AND FLOWERING TREE REQUIREMENTS TO SHOW CODES ARE
 MET.
  
 5. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 6. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
 7. ALL MISSING LANDSCAPING WILL NEED TO BE REPLACED, SO
 ANY UPDATING OF SPECIES OR MODIFICATIONS MUST BE
 PROPOSED AT THIS TIME.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status P Date 05-09-2017 Cont ID  
Sent By tward Date 05-09-2017 Time 09:30 Rev Time 0.00
Received By tward Date 05-09-2017 Time 09:32 Sent To  
Notes
2017-05-09 09:32:35ALL COMMENTS FROM FIRST STORM REVIEW SATISFIED.
  
 TRACY L. WARD, P.E.
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120

Review Stop STORM STORMWATER
Rev No 1 Status F Date 03-08-2017 Cont ID  
Sent By tward Date 03-08-2017 Time 12:48 Rev Time 0.00
Received By tward Date 03-08-2017 Time 12:49 Sent To  
Notes
2017-03-08 12:48:47THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE FREEBOARD REQUIREMENT FOR STRUCTURES IN A
 SPECIAL FLOOD HAZARD AREA IS ONE FOOT ABOVE BASE FLOOD
 ELEVATION.
  
 3. 45TH STREET IS MAINTAINED BY FDOT. FDOT APPROVAL
 WILL BE REQUIRED FOR WORK WITHIN THE RIGHT-OF-WAY OF
 45TH ST.
  
 4. REPLACE ANY DRY RETENTION STORAGE IMPACTED BY THE
 BUILDING EXPANSION AND CONCRETE PATIO.
  
 5. DIRECT ROOF DOWNSPOUTS TO DRAIN TO PERVIOUS AREAS OR
 DIRECTLY INTO DRAINAGE SYSTEM INSTEAD ONTO IMPERVIOUS
 SERVICES.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR THE
 PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status P Date 03-03-2017 Cont ID  
Sent By vnoel Date 03-03-2017 Time 11:28 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-03-03 11:28:54NO COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 04-25-2017 Cont ID  
Sent By   Date 04-25-2017 Time   Rev Time 0.00
Received By pgreilic Date 04-25-2017 Time 09:47 Sent To  
Notes
2017-04-25 09:48:07PAUL GREILICH, SENIOR PLANNER
 561-822-1443
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 03-07-2017 Cont ID  
Sent By   Date 03-07-2017 Time   Rev Time 0.00
Received By pgreilic Date 03-07-2017 Time 09:47 Sent To  
Notes
2017-03-07 11:32:15CASE NUMBER: PB862X ? Z17020017
 PROJECT NAME: RACETRAC MARKET
 ADDRESS: 2995 45TH STREET
  
  
 - CONTACT PAUL GREILICH @ (561) 822-1443
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF
 FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 4/7/17, TO BE ELIGIBLE TO BE SCHEDULED FOR THE 5/16/17
 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY
 5/8/17), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED
 IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION
 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS.
  
 1) LABEL DIMENSIONS OF PARKING SPACES, DRIVE AISLES,
 DRIVEWAYS, SIDEWALKS
  
 2) ENSURE ALL PARKING SPACES ARE IN COMPLIANCE WITH
 SEC. 94-485
  
 3) RESTRIPE PARKING SPACES PER SEC. 94-485; REFERENCE
 DETAIL PROVIDED BY STAFF
  
 4) PROVIDE BIKE RACK PER SEC. 94-485(Q)
  
 5) INCLUDE REQUIRED DETAILS ? PARKING, BIKE RACK
  
 6) APPLICANT SHOULD WEIGH THE INDIVIDUAL
 CHARACTERISTICS OF THE SITE AND CONSIDER PRESERVING THE
 MATURE OAK TREE (40? CANOPY) LOCATED TO THE WEST OF THE
 EXISTING BUILDING AS PART OF THE REDESIGN OF THE
 ADDITION AND OUTDOOR SEATING AREA. REVISED PLANS SHOULD
 INTEGRATE THE OAK TREE INTO THE OUTDOOR SEATING AREA OR
 BUILD THE OUTDOOR SEATING AREA AROUND THE TREE
  
 7) TRAFFIC CONCURRENCY LETTER REQUIRED
  
  
  