Plan Review Details - Project Z17020016
Plan Review Stops For Project Z17020016
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 03-08-2017 Cont ID  
Sent By rbrown Date 03-08-2017 Time 08:46 Rev Time 0.00
Received By rbrown Date 03-08-2017 Time 08:46 Sent To  
Notes
2017-03-08 08:52:37DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. SITE PLAN SHEET 1 OF 2 SHOWS THE WALL AT THE EDGE OF
 THE RAMP LOCATED SUCH THAT THERE IS WHEELCHAIR ACCESS
 FROM THE ACCESSIBLE PARKING SPACES BUT NO WHEELCHAIR
 ACCESS FOR PERSONS APPROACHING ON THE CONCRETE WALKWAY
 THAT COMES FROM COLUMBIA DRIVE. WHEN SUBMITTED FOR
 PERMIT, THE PLANS SHALL SHOW AT LEAST ONE ACCESSIBLE
 ROUTE, COMPLYING WITH SECTIONS 206.2 AND 402.2 OF
 FLORIDA ACCESSIBILITY CODE, FROM THE PUBLIC
 RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR FACILITY
 ENTRANCES.
  
 3. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SITE LIGHTING, SITE LANDSCAPE, SITE
 IRRIGATION, ETC.
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status P Date 03-07-2017 Cont ID  
Sent By mkhan Date 03-07-2017 Time 14:27 Rev Time 0.00
Received By mkhan Date 03-07-2017 Time 14:27 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 05-02-2017 Cont ID  
Sent By pleduc Date 05-02-2017 Time   Rev Time 0.00
Received By pleduc Date 05-02-2017 Time 12:23 Sent To  
Notes
2017-05-02 12:40:572ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED APRIL
 24, 2017, FROM JOHNSTON GROUP, DEVELOPMENT & DESIGN, TO
 JOHN ROACH, PRINCIPAL PLANNER, THE PREVIOUSLY SUBMITTED
 FIRE PREVENTION BUREAU COMMENTS HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 03-03-2017 Cont ID  
Sent By pleduc Date 03-03-2017 Time   Rev Time 0.00
Received By pleduc Date 03-03-2017 Time 11:16 Sent To  
Notes
2017-03-03 11:29:44THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3.DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 4. THE PROPSED CONSTRUCTION SHALL COMPLY WITH THE 5TH
 EDITION OF THE FLORIDA FIRE PREVENTION CODE, INCLUDING
 NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 5. THE INSTALLATION OF PAVERS ALONG THE VEHICLE TRAVEL
 LANE SHALL COMPLY WITH ALL DOT STANDARDS FOR VEHILCE
 TRAVEL.
  
  
 6. THE PROPOSED GATES SHALL BE PROVIDED WITH KNOX KEY
 ACCESS LOCKS, PADLOCKS AND/OR SWITCHES FOR 24 HOUR
 EMERGENCY ACCESS.
  
  
 7. ENSURE A FIRE EXTINGUISHERS IS PROVIDED FOR THE
 ATTENDANT BUILDING.
  
  
 8. ENSURE THE SMALL PATIO WITH ARBOR AREA IS NOT AN
 AREA LEADING FROM A REQUIRED EXIT. IF SO, THE GATE
 ALONG THE FENCE WILL BE REQUIRED TO MEET THE EXIT WIDTH
 AND HAVE EXIT HARDWARE.
  
  
 9. THE PROPOSED STORAGE BUILDING SHALL MEET THE
 REQUIREMENTS OF THE FLORIDA FIRE PREVENTION CODE, 5TH
 EDITION. IT IS RECOMMENDED TO HAVE A KNOX BOX INSTALLED
 AT THIS BUILDING FOR EMERGECNY FIRE DEPARTMENT 24 HR
 EMERGENCY ACCESS.
  
 ENSURE THE PROPOSED CANOPY IS FIRE RETARDENT CERTIFIED.
  
  
 10. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 11. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 05-10-2017 Cont ID  
Sent By rcaranci Date 05-10-2017 Time 09:24 Rev Time 0.00
Received By rcaranci Date 05-10-2017 Time 09:24 Sent To  
Notes
2017-05-10 09:24:45FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: JEWISH FEDERATION Z17020016
 MAY 9, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE THE FOLLOWING CORRECTIONS
 TO THE TREE MITIGATION CHART IDENTIFYING EXISTING TREES
 ON THE PROPERTY THAT WILL BE REMOVED AND MITIGATION
 PROVIDED PER SECTION 94-448:
 ? CASSIA SHOULD BE CATEGORY 2 AT 150
 ? PROVIDE TOTAL OF ALL CANOPY REMOVAL
 ? CORRECT THE REPLACEMENT CHART TO SHOW 600 CREDIT FOR
 2 NEW OAK TREES
 ? SHOW ALL NEW TREES ADDED AND TOTAL CANOPY CREDITS
 PROVIDED
  
 2. SATISFIED. PLEASE PROVIDE A COLUMN ON THE PLANT LIST
 SHOWING DROUGHT TOLERANCE LEVELS INDICATED IN
 WATERWISE, THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 PLANT AND LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN
 SECTION 94-446(G). PLEASE REVISE AND RECALCULATE TO
 CONFIRM PERCENTAGES FOR POINTS CLAIMED.
  
 3. SATISFIED. PLEASE PROVIDE A NOTE ON THE PLANS TO
 SUBSTANTIATE THE TYPE OF MOISTURE SENSING CONTROLLER
 PROVIDED TO MEET THE POINTS TAKEN ON FLORIDA FRIENDLY
 LANDSCAPE REQUIREMENTS CHART. ALSO PLEASE RENAME THE
 CHART TO REFLECT THE REQUIRED NAME AND CODE SECTION.
  
 4. SATISFIED. PLEASE PROVIDE A REQUIRED SHADE TREE FOR
 EACH ROW OF PARKING IN ALL TERMINAL ISLANDS IN PARKING
 AREAS PER SECTION 94-443 (C)(3)A, OR EXPLAIN WHY PALMS
 ARE SUBSTITUTED. SPECIFICALLY AT THE SOUTH ENTRANCE,
 ALSO EXPLAIN THE NEED TO REMOVE THE EXISTING OAK TREES.
  
 5. SATISFIED. PLEASE PROVIDE DETAILS ON HOW THE
 GUARDRAIL SYSTEM WILL BE INSTALLED WITHOUT DAMAGING THE
 EXISTING MATURE TREE ROOTS.
  
 6. SATISFIED. PLEASE PROVIDE CALCULATIONS TO SHOW THE
 LANDSCAPING MEETS THE 30% REQUIRED AROUND THE NEW
 STORAGE BUILDING PER SECTION 94-443(E)(1).
  
 7. SATISFIED. PLEASE SHOW ALL UTILITIES INCLUDING
 WATER, SEWER, AND FPL TRANSFORMERS ON THE LANDSCAPE
 PLAN. ADJUST UTILITY LOCATIONS TO AVOID TREES.
  
 8. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 9. SATISFIED. PLEASE PROVIDE SCREENING FOR ALL GROUND
 MOUNTED EQUIPMENT AND UTILITIES.
  
 10. SATISFIED. PLEASE PROVIDE A COMPLETE HEDGE AROUND
 THE THREE NON-ACCESS SIDES OF THE DUMPSTER ENCLOSURE AS
 REQUIRED.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 03-06-2017 Cont ID  
Sent By rcaranci Date 03-06-2017 Time 11:02 Rev Time 0.00
Received By rcaranci Date 03-06-2017 Time 11:02 Sent To  
Notes
2017-03-06 11:02:36FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: JEWISH FEDERATION Z17020016
 MARCH 7, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE THE FOLLOWING CORRECTIONS TO THE TREE
 MITIGATION CHART IDENTIFYING EXISTING TREES ON THE
 PROPERTY THAT WILL BE REMOVED AND MITIGATION PROVIDED
 PER SECTION 94-448:
 ? CASSIA SHOULD BE CATEGORY 2 AT 150
 ? PROVIDE TOTAL OF ALL CANOPY REMOVAL
 ? CORRECT THE REPLACEMENT CHART TO SHOW 600 CREDIT FOR
 2 NEW OAK TREES
 ? SHOW ALL NEW TREES ADDED AND TOTAL CANOPY CREDITS
 PROVIDED
  
 2. PLEASE PROVIDE A COLUMN ON THE PLANT LIST SHOWING
 DROUGHT TOLERANCE LEVELS INDICATED IN WATERWISE, THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT PLANT AND
 LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN SECTION
 94-446(G). PLEASE REVISE AND RECALCULATE TO CONFIRM
 PERCENTAGES FOR POINTS CLAIMED.
  
 3. PLEASE PROVIDE A NOTE ON THE PLANS TO SUBSTANTIATE
 THE TYPE OF MOISTURE SENSING CONTROLLER PROVIDED TO
 MEET THE POINTS TAKEN ON FLORIDA FRIENDLY LANDSCAPE
 REQUIREMENTS CHART. ALSO PLEASE RENAME THE CHART TO
 REFLECT THE REQUIRED NAME AND CODE SECTION.
  
 4. PLEASE PROVIDE A REQUIRED SHADE TREE FOR EACH ROW OF
 PARKING IN ALL TERMINAL ISLANDS IN PARKING AREAS PER
 SECTION 94-443 (C)(3)A, OR EXPLAIN WHY PALMS ARE
 SUBSTITUTED. SPECIFICALLY AT THE SOUTH ENTRANCE, ALSO
 EXPLAIN THE NEED TO REMOVE THE EXISTING OAK TREES.
  
 5. PLEASE PROVIDE DETAILS ON HOW THE GUARDRAIL SYSTEM
 WILL BE INSTALLED WITHOUT DAMAGING THE EXISTING MATURE
 TREE ROOTS.
  
 6. PLEASE PROVIDE CALCULATIONS TO SHOW THE LANDSCAPING
 MEETS THE 30% REQUIRED AROUND THE NEW STORAGE BUILDING
 PER SECTION 94-443(E)(1).
  
 7. PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER,
 AND FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST
 UTILITY LOCATIONS TO AVOID TREES.
  
 8. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 9. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES.
  
 10. PLEASE PROVIDE A COMPLETE HEDGE AROUND THE THREE
 NON-ACCESS SIDES OF THE DUMPSTER ENCLOSURE AS REQUIRED.
  
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 03-08-2017 Cont ID  
Sent By tward Date 03-08-2017 Time 04:56 Rev Time 0.00
Received By tward Date 03-08-2017 Time 05:02 Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 03-03-2017 Cont ID  
Sent By vnoel Date 03-03-2017 Time 08:56 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-03-03 09:21:181. APPROVAL OF FENCE IN 25' DRAINAGE EASEMENT WILL
 REQUIRE NPBCOID APPROVAL.
 2. APPROVAL OF FENCE IN 12' UTILITY EASEMENT WILL
 REQUIRE ALL UTILITY COMPANIES APPROVAL.
 3. QUEUE LENGTH FOR NEW ENTRY GATE MY NOT BE
 SUFFICIENT. DETAIL OF ATTENDANT BUILDING IS UNREADABLE.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 05-12-2017 Cont ID  
Sent By jroach Date 05-12-2017 Time 08:50 Rev Time 0.00
Received By jroach Date 05-12-2017 Time 08:50 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 05-02-2017 Cont ID  
Sent By jroach Date 05-02-2017 Time 11:32 Rev Time 0.00
Received By jroach Date 05-02-2017 Time 11:32 Sent To  
Notes
2017-05-02 11:34:38PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 05.02.2017
 PROJECT NO.: Z17020016
 CASE NO.: PB 813J
 ADDRESS: 1 HARVARD CIRCLE
 APPLICANT/CONTACT: RYAN JOHNSTON
 TELEPHONE NO.: 561.691.4552
 SCOPE OF REVIEW: ADDITION OF STORAGE BUILDING AND SITE
 IMPROVEMENTS.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. IN YOUR RESPONSE TO ZONING COMMENT #8 YOU STATE
 THAT... "THE APPLICANT IS PROPOSING TO MAINTAIN TWO-WAY
 INGRESS AND EGRESS AT THE MAIN DRIVEWAY ENTRANCE FROM
 HARVARD CIRCLE DURING DAYTIME OPERATING HOURS WITH THE
 GATE IN A PERMANENT OPEN POSITION. AFTER HOURS THE GATE
 WILL BE IN USE WITH KEY CARD ENTRY AND THE DRIVEWAY ON
 COLUMBIA WILL BE AN ENTRANCE ONLY. THE GATE ON HARVARD
 CIRCLE WILL ALWAYS BE IN USE AND IS AN EXIT ONLY." I
 BELIEVE THIS RESPONSE IS INCORRECT. BASED UPON YOUR
 SITE PLAN, IT APPEARS THAT COLUMBIA DRIVE WILL MAINTAIN
 TWO-WAY INGRESS AND EGRESS, AND HARVARD CIRCLE WILL BE
 AN EXIT ONLY. IF THE RESPONSE YOU PROVIDED IS
 INCORRECT, PLEASE UPDATE ACCORDINGLY.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

Review Stop Z ZONING
Rev No 1 Status F Date 03-08-2017 Cont ID  
Sent By jroach Date 03-08-2017 Time 08:58 Rev Time 0.00
Received By jroach Date 03-08-2017 Time 08:58 Sent To  
Notes
2017-03-08 08:59:02PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 03.08.2017
 PROJECT NO.: Z17020016
 CASE NO.: PB 813J
 ADDRESS: 1 HARVARD CIRCLE
 APPLICANT/CONTACT: RYAN JOHNSTON
 TELEPHONE NO.: 561.691.4552
 SCOPE OF REVIEW: ADDITION OF STORAGE BUILDING AND SITE
 IMPROVEMENTS.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. PUBLIC UTILITY LETTERS SHALL BE PROVIDED FROM ALL
 UTILITY COMPANIES INDICATING THAT THEY HAVE NO
 OBJECTION TO THE PROPOSED IMPROVEMENTS.
  
 2. HAS THERE BEEN ANY DISCUSSION AS TO WHETHER TRAFFIC
 CONCURRENCY IS REQUIRED FOR THE ADDITIONAL SQUARE
 FOOTAGE?
  
 3. PLEASE PROVIDE THE STATUS OF REVIEW BY THE VILLAGE
 COMMERCE CENTER ARCHITECTURAL REVIEW BOARD.
  
 4. IMPROVEMENTS ARE SHOWN IN THE EXISTING UTILITY
 EASEMENT?EASEMENT CONSENT SHALL BE PROVIDED FROM ALL
 UTILITY COMPANIES.
  
 5. STAFF WOULD LIKE TO HAVE MORE DISCUSSION REGARDING
 THE PROPOSED GUARDRAIL. IF THE BARRIER IS TO BE
 VISIBLE, A MORE AESTHETIC ALTERNATIVE WOULD BE
 ENCOURAGED. IF THE BARRIER IS GOING TO BE HIDDEN
 COMPLETELY AMONGST THE LANDSCAPING, THEN WHAT IS
 PROPOSED MAY BE ACCEPTABLE. REGARDLESS, ADDITIONAL
 INFORMATION NEEDS TO BE PROVIDED REGARDING HOW THE
 GUARDRAIL IS TO BE INSTALLED AS IT COULD HAVE IMPACT ON
 EXISTING MATURE TREES, ETC.
  
 6. PLEASE DIMENSION THE DISTANCE BETWEEN THE FRONT OF
 THE PARKING STALL AND THE PROPOSED GUARDRAIL. THERE
 NEEDS TO BE A MINIMUM OF TWO (2) FEET OF CLEAR OVERHANG
 FOR THE PARKING.
  
 7. PLEASE IDENTIFY THE HEIGHT OF THE PROPOSED GATES.
  
 8. PLEASE CLARIFY THE PROPOSED TRAFFIC PATTERN WITHIN
 THE SITE, SPECIFICALLY RELATING TO THE GATE OPERATIONS,
 DIRECTION OF TRAFFIC FLOW (ENTRANCES AND EXISTS). IS
 THE ACCESS POINT ON COLUMBIA DRIVE AN ENTRANCE ONLY? IF
 NOT, THE EXIT GATE IS SWINGING IN THE WRONG DIRECTION.
 IF THE ACCESS POINTS ARE GOING TO BE DESIGNATED AS
 SEPARATE ENTRANCE AND EXIT, THEN SIGNAGE MAY BE
 REQUIRED WITHIN THE PARKING LOT TO DIRECT TRAFFIC FLOW.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved