Plan Review Details - Project Z17010007
Plan Review Stops For Project Z17010007
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 02-07-2017 Cont ID  
Sent By rbrown Date 02-07-2017 Time 19:32 Rev Time 0.00
Received By rbrown Date 02-07-2017 Time 19:32 Sent To  
Notes
2017-02-07 19:36:27DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. NO GUARD HOUSE PLANS WERE SUBMITTED AT THIS TIME.
 THE GUARD HOUSE PLANS WILL BE REVIEWED WHEN SUBMITTED
 FOR BUILDING PERMIT.
  
 3. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 04-11-2017 Cont ID  
Sent By mkhan Date 04-11-2017 Time 16:19 Rev Time 0.00
Received By mkhan Date 04-11-2017 Time 16:18 Sent To  
Notes
2017-04-11 16:20:39CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 DATE: 04/11/2017
  
 PROJECT NAME: 3200 PRESIDENTIAL WAY (BANYAN CAY GOLF
 COURSE MAINTENANCE FACILITY)
  
 Z17020023
  
 2ND/RE-SUBMITTAL REVIEW RESPONSE: PASSED WITH PROVISO
  
 AFTER REVIEWING THE REVISED PLANS, IT APPEARS THAT SOME
 OF THE COMMENTS HAVE BEEN ADDRESSED AND DEEM SATISFIED.
 WHEREAS, OTHER COMMENTS ARE ACKNOWLEDGED WITH A
 STATEMENT: "THIS WILL BE ADDRESSED AT THE TIME OF
 BUILDING PERMIT SUBMITTAL" IN THE WRITTEN LETTER OF
 RESPONSE TO THE PREVIOUS PPRC COMMENTS DATED MARCH 31,
 2017. THE ACKNOWLEDGED COMMENTS ALONG WITH THE
 FOLLOWING ITEM ARE EXPECTED TO BE ADDRESSED DURING
 "ENGINEERING DEVELOPMENT APPLICATION" PHASE PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 7. IT IS PREFERRED THAT PROPOSED GOLF COURSE
 MAINTENANCE FACILITY HAVE SEPARATE SERVICE CONNECTIONS
 FOR DOMESTIC WATER LINE AND FIRE LINE. FOR THE DOMESTIC
 WATER SERVICE CITY'S POINT-OF-SERVICE WILL BEGIN AT THE
 WATER METER WHEREAS FOR FIRE LINE THE CITY'S
 POINT-OF-SERVICE SHALL BEGIN AT THE TAPPING
 SLEEVE/VALVE I.E. AT THE CONNECTION POINT TO THE
 EXISTING WATER MAIN ON PRESIDENTIAL WAY (PER NFPA 24);
  
 10. COMMENT RELATED TO PLACEMENT OF WATER METER,
 BACKFLOW PREVENTER, DCDA ETC. NEED TO BE ADDRESSED
 DURING "ENGINEERING DEVELOPMENT APPLICATION" PHASE AND
 NOT "AT THE TIME OF CONSTRUCTION". HENCE DETAILS OF
 UTILITY CONNECTION INFORMATION NEED TO BE SHOWN ON THE
 FINAL ENGINEERING PLANS WHICH NEED TO BE APPROVED BY
 THE ENGINEERING SERVICES DEPARTMENT PRIOR TO
 CONSTRUCTION IS AUTHORIZED;
  
 11. SHOW EXTENTS OF PAVEMENT RESTORATION ON THE FINAL
 WATER AND SEWER PLANS FOR UTILITY CONNECTION WORK
 WITHIN THE RIGHT-OF-WAY AND ALSO ATTACH THE LATEST
 CITY'S STANDARD DETAIL TO THE PLAN SET WHICH NEED TO BE
 APPROVED BY THE ENGINEERING SERVICES DEPARTMENT PRIOR
 TO CONSTRUCTION IS AUTHORIZED;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 02-03-2017 Cont ID  
Sent By mkhan Date 02-03-2017 Time 14:24 Rev Time 3.00
Received By mkhan Date 02-03-2017 Time 14:20 Sent To  
Notes
2017-02-03 14:25:50CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 DATE: 02/03/2017
  
 Z17010007: 3100-3200 NORTH CONGRESS AVE - BANYAN CAY
 GUARDHOUSE, ENTRYWAY ROUNDABOUT AND SPINE ROAD
  
 FOLLOWING COMMENT HAS TO BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PLEASE COORDINATE WITH PALM BEACH COUNTY TO OBTAIN
 PERMIT FOR WORK TO BE PERFORMED WITHIN CONGRESS AVENUE
 RIGHT-OF-WAY INCLUDING STREET IMPROVEMENTS, MILLING AND
 OVERLAY, STRIPING, LANDSCAPE MEDIAN SIDEWALK, CURBING
 AND CURB RAMPS ETC. PLEASE SUBMIT A COPY OF THE COUNTY
 APPROVAL/PERMIT FOR ALL WORK TO BE PERFORMED WITHIN
 NORTH CONGRESS RIGHT-OF-WAY;
  
 CONSTRUCTION LEVEL/DETAIL DESIGN/PLANS WILL BE REVIEWED
 AS PART OF THE ENGINEERING DEVELOPMENT APPROVAL AND
 BUILDING PERMIT APPLICATION PROCESSES. THE FOLLOWING
 COMMENTS MUST BE ADDRESSED PRIOR TO ISSUANCE OF
 CONSTRUCTION AUTHORIZATION INCLUDING BUILDING PERMITS
 AND ENGINEERING DEVELOPMENT APPROVAL:
  
 2. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE CITY'S ENGINEERING SERVICES
 DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH ENGINEERING SERVICES DEPARTMENT. THIS
 FORM CAN BE DOWNLOADED FROM THE FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING WATER AND SEWER COMMENTS:
  
 4. PLEASE LABEL PIPE SIZE AND MATERIAL AND ADD NOTES TO
 THE UTILITY PLANS ACCORDINGLY;
  
 5. LANDSCAPE PLAN SHALL SHOW LOCATIONS OF ALL EXISTING
 AND PROPOSED UTILITIES INCLUDING BUT NOT LIMITED TO
 STORM DRAINS, WATER AND SANITARY SEWER PIPES, WATER
 METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC.
  
 6. WEST SIDE OF CONGRESS AVE. SHOWS LANDSCAPE OVER
 PROPOSED WATER MAIN. ROOT BARRIERS SHALL BE REQUIRED
 FOR THAT;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 02-06-2017 Cont ID  
Sent By pleduc Date 02-06-2017 Time   Rev Time 0.00
Received By pleduc Date 02-06-2017 Time 14:03 Sent To  
Notes
2017-02-06 14:19:38THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 4. THE CONSTRUCTION OF ANY BUILDING SHALL COMPLY WITH
 REQUIREMENTS OF THE 5TH EDITION OF THE FLORIDA FIRE
 PREVENTION CODE, INCLUDING NFPA 1 & 101, AND ALL
 ASSOCIATED FIRE CODES.
  
 5. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT AN
 APPLICABLE FIRE EXTINGUISHER IS LOCATED WITHIN THE
 GUARDHOUSE.
  
 6. NO INDICATIONS OF FIRE HYDRANT LOCATIONS COULD BE
 DETERMINED FROM THE SUBMITTAL. ALL EXISTING AND NEW
 FIRE HYDRANTS PLANNED FOR THIS DEVELOPMENT SHALL BE
 CLEARLY INDICATED AND IDENTIFIED ON THE PLAN AND
 CLOSELY COORDINATED WITH THE BUREAU OF FIRE PREVENTION.
  
 7. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS GATES THAT
 THEY BE PROVIDED WITH KNOX KEY SWITCHES FOR 24 HOUR
 EMERGENCY ACCESS. BOTH GATES SHALL OPEN ON ACTIVATION
 OF THE KEY SWITCH OR EXITING WHEN ACTIVATING ANY
 AUTOMATIC OPEN DEVICE. THIS PROVIDES FOR ADAQUATE
 CLEARENCE DISTANCES FOR WIDE EMERGENCY APPARATUS.
  
 8. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 9. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS
 AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 02-07-2017 Cont ID  
Sent By rcaranci Date 02-07-2017 Time 08:59 Rev Time 0.00
Received By rcaranci Date 02-07-2017 Time 08:59 Sent To  
Notes
2017-02-07 08:59:57FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: BANYAN CAY PD AMENDMENT Z17010007
 FEBRUARY 7, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A COMPARISON COUNT FOR TREE AND SHRUB
 QUANTITIES COMPARING THE PROPOSED PLAN TO THE APPROVED
 LANDSCAPE PLAN.
  
 2. SHEETS L-1 AND L-2 GUARDHOUSE DO NOT SHOW WATER,
 SEWER, DRAINAGE LINES OR LIGHTING LOCATIONS. PLEASE
 SHOW THESE SYSTEMS ON THE LANDSCAPE PLAN AND MAKE ANY
 ADJUSTMENTS NECESSARY TO AVOID CONFLICTS.
  
 3. PLEASE PROVIDE WATER NEEDS CATEGORY FOR EACH SPECIES
 ON ALL PLANT LISTS FROM THE SFWMD WATERWISE GUIDE AND
 SHOW COMPLIANCE WITH THE FLORIDA FRIENDLY LANDSCAPE
 CHART SECTION 94-442 (G).
  
 4. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 5. LANDSCAPING FOR LOT 1 WILL BE SEPARATE FROM THE
 COMMON AREA LANDSCAPING. PLEASE CLEARLY SHOW THE LOT
 LINES FOR THE SINGLE FAMILY LOTS AND ADJUST PLAN TO
 AVOID PLACING COMMON AREA LANDSCAPING WITHIN LOT LINES
 ON SHEET L-2 GUARDHOUSE.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status P Date 02-08-2017 Cont ID  
Sent By tward Date 02-08-2017 Time 09:55 Rev Time 0.00
Received By tward Date 02-08-2017 Time 09:57 Sent To  
Notes
2017-02-08 09:56:25THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. CHECK SCALE BAR ON LANDSCAPE PLANS.
  
 2. PROVIDE ROOT BARRIER DETAIL AND SHOW WHERE ROOT
 BARRIER IS TO BE INSTALLED ON THE LANDSCAPE PLANS.
  
 3. CONGRESS AVE. IS MAINTAINED BY PALM BEACH COUNTY.
 COUNTY APPROVAL WILL BE REQUIRED FOR WORK WITHIN THE
 RIGHT-OF-WAY OF CONGRESS AVE.
  
 4. SHOW UTILITIES ON THE GUARDHOUSE LANDSCAPE PLANS.
  
 5. SHOW UTILITIES ON THE LANDSCAPE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE
 MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT
 AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY
 AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 1 Status   Date 02-03-2017 Cont ID  
Sent By vnoel Date 02-03-2017 Time 07:52 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2017-02-03 07:53:551. NO SURVEY PROVIDED.
 2. WILL PLAT BE REQUIRED?
 3.LABEL ALL EXISTING AND PROPOSED UTILITIES WITH
 EASEMENT WIDTHS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 02-08-2017 Cont ID  
Sent By jroach Date 02-08-2017 Time 11:43 Rev Time 0.00
Received By jroach Date 02-08-2017 Time 11:41 Sent To  
Notes
2017-02-08 11:43:17PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 02.08.2017
 PROJECT NO.: Z17010007
 CASE NO.: PB 1624L
 ADDRESS: 3200 NORTH CONGRESS AVENUE
 APPLICANT/CONTACT: JONI BRINKMAN
 TELEPHONE NO.: 561.366.1100
 SCOPE OF REVIEW: GUARDHOUSE, BUFFERS, ENTRY FEATURE,
 ETC.
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. THE CONGRESS AVENUE LANDSCAPE BUFFER AND MEDIAN
 DESIGN NEEDS TO EXTEND TO THE NORTHERN AND SOUTHERN
 LIMITS OF THE DEVELOPMENT; THE PROPOSED PLANS SHOW THE
 PLANTINGS ENDING APPROXIMATELY 150 FEET SHORT.
  
 2. PLEASE PROVIDE DOCUMENTATION FROM PALM BEACH COUNTY
 INDICATING THEIR APPROVAL OF THE PROPOSED MEDIAN
 PLANTINGS. AS CONGRESS AVENUE IS A COUNTY ROAD, ALL
 IMPROVEMENTS IN THE RIGHT-OF-WAY WILL NEED TO BE
 APPROVED AND PERMITTED FROM PALM BEACH COUNTY.
  
 3. THE LANDSCAPE PLAN FOR THE GUARD HOUSE DOES NOT
 MATCH UP WITH WHAT WAS APPROVED FOR THE ENTRY ROAD IN
 2015. THERE NEEDS TO BE COORDINATION BETWEEN ALL OF THE
 PROPOSED PLANS AND THOSE THAT HAVE ALREADY BEEN
 APPROVED.
  
 4. THE LANDSCAPE PLAN FOR THE GUARD HOUSE SHOWS A
 PODOCARPUS HEDGE EXTENDING ALONG THE FRONT OF
 RESIDENTIAL LOTS 1 THROUGH 4 IN POD L1, COMPLETELY
 CUTTING OFF ACCESS TO THE ROAD.
  
 5. THE LANDSCAPE PLAN FOR THE GUARD HOUSE APPEARS TO
 SHOW TREES/PALMS IN THE SIDEWALK IN FRONT OF LOTS 2
 THROUGH 4 IN POD L1.
  
 6. THE SUBMITTED SITE PLAN IS UNCLEAR. VARIOUS ELEMENTS
 (SIDEWALKS, ETC. ) ARE NOT LABELED AND HARD TO
 DIFFERENTIATE FROM OTHER ELEMENTS SHOWN ON THE PLAN.
  
 7. PLEASE PROVIDE AN ENLARGEMENT OF THE GATE HOUSE
 AREA. IT APPEARS THAT THE PARKING FOR THE GUARD HOUSE
 IS INSUFFICIENT. IS THIS PARKING FOR A STANDARD
 VEHICLE, OR IS IT LIMITED TO A GOLF CART? DOES THE
 BUILDING CODE AND/OR ADA REQUIRE ACCESSIBLE PARKING TO
 BE PROVIDED? IF VEHICLES ARE TO BE PARKING THERE, THEN
 THE SPACE AND BACKUP AREA NEEDS TO COMPLY WITH THE
 CITY?S MINIMUM DIMENSIONAL REQUIREMENTS. ADDITIONALLY,
 PLEASE ENSURE SUFFICIENT TURN RADIUS IS PROVIDED FOR
 THIS PARKING SPACE, AS WELL AS GUEST VEHICLES/TRUCKS
 THAT ARE DENIED ENTRY AND ARE REQUIRED TO TURN AROUND.
  
 8. HAS THERE BEEN ANY COORDINATION WITH THE SCHOOL
 DISTRICT ON HOW SCHOOL BUS PICK-UP WILL OCCUR?
  
 9. THE SITE PLAN DOES NOT SHOW THE PROPOSED FEATURES IN
 THE CENTER OF, AND AROUND, THE ROUNDABOUT (FOUNTAIN,
 WALLS, FREESTANDING SIGNS, ETC.).
  
 10. THERE NEEDS TO BE A BUFFER BETWEEN THE EXISTING
 MAINTENANCE FACILITY AND THE RESIDENTIAL CONDOMINIUMS
 LOCATED ALONG CONGRESS AVENUE TO THE SOUTH.
  
 11. THE LANDSCAPE PLANS FOR THE ROUNDABOUT SHOW THE
 FOUNTAIN HAVING SIDEWALK AND PEDESTRIAN CIRCULATION IN
 THE CENTER, HOWEVER, THERE APPEARS TO BE NO SAFE
 CROSSING TO ACCESS THIS AREA. PLEASE ENSURE THAT ALL
 PEDESTRIAN CIRCULATION AREAS CAN BE ACCESSED SAFELY AND
 CONFORM TO ANY REQUIRED ADA STANDARDS.
  
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 6 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved