| 2016-12-07 13:35:16 | CITY OF WEST PALM BEACH |
| | PUBLIC WORKS DEPARTMENT |
| | ENGINEERING DIVISION |
| | |
| | DATE: 12/07/2016 |
| | |
| | Z16110037: 1620 N. CONGRESS AVE. - PRESIDENTIAL STORAGE |
| | |
| | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL |
| | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION |
| | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE |
| | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT |
| | APPLICATION PROCESSES. |
| | |
| | THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR |
| | TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING |
| | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: |
| | |
| | 1. PLEASE PROVIDE AN ALTA/ACSM SURVEY WHICH HAS BEEN |
| | SIGNED AND SEALED BY PROFESSIONAL SURVEY & MAPPER |
| | (PSM). |
| | |
| | 2. PLEASE COORDINATE WITH PALM BEACH COUNTY TO OBTAIN |
| | PERMIT FOR WORK TO BE PERFORMED WITHIN CONGRESS AVENUE |
| | RIGHT-OF-WAY INCLUDING SIDEWALK, CURBING AND CURB RAMPS |
| | ETC. PLEASE SUBMIT A COPY OF THE COUNTY APPROVAL OF THE |
| | DRIVEWAY ENTRANCE ON NORTH CONGRESS PERMIT WITH THE |
| | DEVELOPMENT APPLICATION TO THE CITY?S ENGINEERING |
| | DEPARTMENT; |
| | |
| | 3. PLEASE SHOW THE SIGHT TRIANGLES ON THE PLANS FOR THE |
| | VEHICULAR EXITS. (SECTION 94-305E, CODE OF ORDINANCES). |
| | |
| | 4. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING |
| | THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE |
| | PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH |
| | DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY |
| | SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER |
| | PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A |
| | ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER |
| | FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN |
| | PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE |
| | PLANS; |
| | |
| | 5. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL |
| | BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC |
| | WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION FORMS CAN BE DOWNLOADED AT: |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 6. PLEASE SUBMIT THE LATEST VERSION OF THE ?AUTO-CALC |
| | CERTIFIED COST ESTIMATE FORM? FOR SUBMISSION TO CITY OF |
| | WEST PALM BEACH PUBLIC WORKS DEPARTMENT. THIS FORM CAN |
| | BE DOWNLOADED FROM THE FOLLOWING LINK: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | THE FOLLOWING WATER AND SEWER COMMENTS: |
| | |
| | 7. ADDRESS PREVIOUS PPRC COMMENTS FOR UTILITIES; |
| | |
| | 8. CALL OUT FORCED MAIN (FM) SIZE, MATERIAL ON THE |
| | PLANS; |
| | |
| | 9. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL |
| | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND |
| | SANITARY SEWER CALCULATION (AVERAGE AND PEAK WITH |
| | PEAKING FACTOR). SUBMIT CALCULATIONS TO VALIDATE METER |
| | SIZE SELECTION. SHOW THESE CALCULATIONS ON THE UTILITY |
| | PLAN SHEET AS WELL; |
| | |
| | 10. A FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE |
| | HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL; |
| | |
| | 11. RECORD INFO SHOWS AN EXISTING 6-INCH GAS MAIN |
| | WITHIN THE RIGHT-OF-WAY DEDICATION. SHOW THIS ON THE |
| | PLANS; |
| | |
| | 12. SHOW ALL EXISTING UTILITIES WITHIN THE VICINITY OF |
| | THE PROPOSED SITE AND PROVIDE ALL UTILITY CROSSING |
| | INFORMATION. SHOW CONFLICT INFORMATION (BOTTOM AND TOP |
| | OF CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER, |
| | STORM AND SANITARY SEWER PIPES AS WELL AS OTHER |
| | FRANCHISE UTILITIES; |
| | |
| | 13. IT IS NOT CLEAR FROM THE PLANS WHERE THE PROPOSED |
| | WATER LINE IS CONNECTED TO AS SHOWN ON THE PLAN (AT THE |
| | NORTHWEST PROPERTY LINE). THE LABEL SAYS ?CONNECT TO |
| | EXISTING 8? WATER MAIN? BUT RECORD INFORMATION SHOWS |
| | EXISTING WATER LINE IS FURTHER WEST OF THERE; |
| | |
| | 14. SHOW SIZE AND MATERIAL OF THE PROPOSED WATER LINE; |
| | |
| | 15. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE |
| | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE |
| | DETAILS SHEET. CONTACT THE ENGINEERING SERVICES |
| | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD |
| | FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT) |
| | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR |
| | MS,-PERMITS-APPLICATIONS |
| | |
| | 16. PLACEMENT OF THE PROPOSED METER, BACKFLOW |
| | PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY?S |
| | STANDARD DETAILS. WATER METER SHOULD BE INSIDE AN |
| | 'UTILITY EASEMENT' JUST INSIDE THE PROPERTY NEAR THE |
| | RIGHT-OF-WAY AND ACCESSIBLE; |
| | |
| | 17. SHOW INFORMATION OF THE EXISTING MANHOLES AND |
| | SANITARY SEWER I.E. INVERTS, RIM ELEVATION ETC. ON THE |
| | UTILITY PLANS; |
| | |
| | 18. EXISTING SANITARY SEWER MH TO BE REHABBED PER |
| | CITY?S REQUIREMENTS; |
| | |
| | 19. SHOW SIZE AND MATERIAL OF THE PROPOSED SANITARY |
| | SEWER SERVICE. INCLUDE A PROFILE FOR THE PROPOSED |
| | SERVICE LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE; |
| | |
| | 20. CCTV RECORD (VIDEO AND TV LOG) OF THE EXISTING |
| | SANITARY SEWER (FULL LENGTH FROM MH TO MH) AND NEW |
| | SANITARY SEWER LATERAL WILL BE REQUIRED AS PART OF THE |
| | PROJECT CLOSE-OUT SUBMITTALS; |
| | |
| | 21. PAVEMENT RESTORATION WILL BE REQUIRED FOR THE |
| | PROPOSED SANITARY SEWER CONNECTION TO THE EXISTING |
| | MANHOLE WITHIN THE RIGHT-OF-WAY. REFER TO THE CITY |
| | STANDARD DETAILS FOR RESTORATION GUIDELINES; |
| | |
| | 22. EXISTING WATER SERVICE CONNECTIONS/WATER METERS |
| | SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND |
| | CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES |
| | LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL |
| | PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY |
| | PLANS ACCORDINGLY; |
| | |
| | 23. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY |
| | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS |
| | BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES |
| | MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE |
| | LINK BELOW: |
| | |
| | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI |
| | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | 24. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE |
| | WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN |
| | AN EASEMENT WITHIN THE PROPERTY. LANDSCAPE PLAN SHALL |
| | SHOW LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS, |
| | LIGHT POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE |
| | PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR |
| | POTABLE WATER LINES. |
| | |
| | 25. SUBMITTAL MAINTENANCE OF TRAFFIC (MOT) WILL BE |
| | REQUIRED AT THE PRE-CONSTRUCTION MEETING. |
| | |
| | MOSTAQUE KHAN, P.E. |
| | LAND DEVELOPMENT ENGINEER |
| | [email protected] |
| | 561-494-1024 (OFFICE) |
| | |