Plan Review Details - Project Z16110037
Plan Review Stops For Project Z16110037
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 12-14-2016 Cont ID  
Sent By rbrown Date 12-14-2016 Time 12:33 Rev Time 0.00
Received By rbrown Date 12-14-2016 Time 12:33 Sent To  
Notes
2016-12-14 12:35:19DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 NO COMMENTS ON THE PROPOSED MINOR AMENDMENT TO AMEND
 THE LANDSCAPE PLANS AND INCREASE THE SQUARE FOOTAGE OF
 THE BUILDING FROM THE APPROVED SITE PLAN.
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 01-17-2017 Cont ID  
Sent By mkhan Date 01-17-2017 Time 12:07 Rev Time 4.00
Received By mkhan Date 01-17-2017 Time 12:06 Sent To  
Notes
2017-01-17 12:20:29CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: PRESIDENTIAL STORAGE CPD - 1620 N.
 CONGRESS AVE. - Z16110037
  
 2ND REVIEW RESPONSE: PASSED WITH CONDITION
  
 DATE: JANUARY 17, 2017
  
 AFTER A REVIEWING THE REVISED PLANS AND THE RESPONSES
 TO THE PREVIOUS PPRC COMMENTS (RECEIVED ON 12/22/2016),
 IT APPEARS THAT MOST OF THE COMMENTS HAVE BEEN
 ACKNOWLEDGED. HOWEVER, THESE ACKNOWLEDGED COMMENTS ARE
 EXPECTED TO BE ADDRESSED DURING 'ENGINEERING
 DEVELOPMENT APPLICATION' PHASE PRIOR TO ISSUANCE OF
 CONSTRUCTION AUTHORIZATION INCLUDING BUILDING PERMITS
 AND ENGINEERING DEVELOPMENT APPROVAL.
  
 SO I AM PASSING IT AT THIS STAGE WITH A CONDITION THAT
 AT THE NEXT LEVEL I.E. ACKNOWLEDGED COMMENTS WILL BE
 ADDRESSED IN THE DETAIL PLANS SUBMITTED AT THE
 "ENGINEERING DEVELOPMENT APPLICANT" PHASE.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-07-2016 Cont ID  
Sent By mkhan Date 12-07-2016 Time 13:30 Rev Time 4.00
Received By mkhan Date 12-07-2016 Time 08:46 Sent To  
Notes
2016-12-07 13:35:16CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 DATE: 12/07/2016
  
 Z16110037: 1620 N. CONGRESS AVE. - PRESIDENTIAL STORAGE
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR
 TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. PLEASE PROVIDE AN ALTA/ACSM SURVEY WHICH HAS BEEN
 SIGNED AND SEALED BY PROFESSIONAL SURVEY & MAPPER
 (PSM).
  
 2. PLEASE COORDINATE WITH PALM BEACH COUNTY TO OBTAIN
 PERMIT FOR WORK TO BE PERFORMED WITHIN CONGRESS AVENUE
 RIGHT-OF-WAY INCLUDING SIDEWALK, CURBING AND CURB RAMPS
 ETC. PLEASE SUBMIT A COPY OF THE COUNTY APPROVAL OF THE
 DRIVEWAY ENTRANCE ON NORTH CONGRESS PERMIT WITH THE
 DEVELOPMENT APPLICATION TO THE CITY?S ENGINEERING
 DEPARTMENT;
  
 3. PLEASE SHOW THE SIGHT TRIANGLES ON THE PLANS FOR THE
 VEHICULAR EXITS. (SECTION 94-305E, CODE OF ORDINANCES).
  
 4. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A
 ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER
 FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN
 PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE
 PLANS;
  
 5. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 6. PLEASE SUBMIT THE LATEST VERSION OF THE ?AUTO-CALC
 CERTIFIED COST ESTIMATE FORM? FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT. THIS FORM CAN
 BE DOWNLOADED FROM THE FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 THE FOLLOWING WATER AND SEWER COMMENTS:
  
 7. ADDRESS PREVIOUS PPRC COMMENTS FOR UTILITIES;
  
 8. CALL OUT FORCED MAIN (FM) SIZE, MATERIAL ON THE
 PLANS;
  
 9. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (AVERAGE AND PEAK WITH
 PEAKING FACTOR). SUBMIT CALCULATIONS TO VALIDATE METER
 SIZE SELECTION. SHOW THESE CALCULATIONS ON THE UTILITY
 PLAN SHEET AS WELL;
  
 10. A FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE
 HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL;
  
 11. RECORD INFO SHOWS AN EXISTING 6-INCH GAS MAIN
 WITHIN THE RIGHT-OF-WAY DEDICATION. SHOW THIS ON THE
 PLANS;
  
 12. SHOW ALL EXISTING UTILITIES WITHIN THE VICINITY OF
 THE PROPOSED SITE AND PROVIDE ALL UTILITY CROSSING
 INFORMATION. SHOW CONFLICT INFORMATION (BOTTOM AND TOP
 OF CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER,
 STORM AND SANITARY SEWER PIPES AS WELL AS OTHER
 FRANCHISE UTILITIES;
  
 13. IT IS NOT CLEAR FROM THE PLANS WHERE THE PROPOSED
 WATER LINE IS CONNECTED TO AS SHOWN ON THE PLAN (AT THE
 NORTHWEST PROPERTY LINE). THE LABEL SAYS ?CONNECT TO
 EXISTING 8? WATER MAIN? BUT RECORD INFORMATION SHOWS
 EXISTING WATER LINE IS FURTHER WEST OF THERE;
  
 14. SHOW SIZE AND MATERIAL OF THE PROPOSED WATER LINE;
  
 15. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAILS SHEET. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY?S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 16. PLACEMENT OF THE PROPOSED METER, BACKFLOW
 PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY?S
 STANDARD DETAILS. WATER METER SHOULD BE INSIDE AN
 'UTILITY EASEMENT' JUST INSIDE THE PROPERTY NEAR THE
 RIGHT-OF-WAY AND ACCESSIBLE;
  
 17. SHOW INFORMATION OF THE EXISTING MANHOLES AND
 SANITARY SEWER I.E. INVERTS, RIM ELEVATION ETC. ON THE
 UTILITY PLANS;
  
 18. EXISTING SANITARY SEWER MH TO BE REHABBED PER
 CITY?S REQUIREMENTS;
  
 19. SHOW SIZE AND MATERIAL OF THE PROPOSED SANITARY
 SEWER SERVICE. INCLUDE A PROFILE FOR THE PROPOSED
 SERVICE LATERAL WITH GROUND ELEVATIONS ABOVE THE PIPE;
  
 20. CCTV RECORD (VIDEO AND TV LOG) OF THE EXISTING
 SANITARY SEWER (FULL LENGTH FROM MH TO MH) AND NEW
 SANITARY SEWER LATERAL WILL BE REQUIRED AS PART OF THE
 PROJECT CLOSE-OUT SUBMITTALS;
  
 21. PAVEMENT RESTORATION WILL BE REQUIRED FOR THE
 PROPOSED SANITARY SEWER CONNECTION TO THE EXISTING
 MANHOLE WITHIN THE RIGHT-OF-WAY. REFER TO THE CITY
 STANDARD DETAILS FOR RESTORATION GUIDELINES;
  
 22. EXISTING WATER SERVICE CONNECTIONS/WATER METERS
 SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND
 CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES
 LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL
 PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY
 PLANS ACCORDINGLY;
  
 23. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES
 MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
  
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 24. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE
 WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN
 AN EASEMENT WITHIN THE PROPERTY. LANDSCAPE PLAN SHALL
 SHOW LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS,
 LIGHT POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE
 PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR
 POTABLE WATER LINES.
  
 25. SUBMITTAL MAINTENANCE OF TRAFFIC (MOT) WILL BE
 REQUIRED AT THE PRE-CONSTRUCTION MEETING.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1024 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 12-09-2016 Cont ID  
Sent By pleduc Date 12-09-2016 Time   Rev Time 0.00
Received By pleduc Date 12-09-2016 Time 09:22 Sent To  
Notes
2016-12-09 09:40:09THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT WILL BE MIXED OR SEPARATED OCCUPANCIES.
  
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 11. IT IS HIGHLY RECOMMENDED FOR ANY ACCESS POINTS OR
 GATES THAT THEY BE PROVIDED WITH KNOX KEY BOX ACCESS
 LOCKS, PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY
 ACCESS.
  
  
 12. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
  
  
 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 2 Status P Date 01-11-2017 Cont ID  
Sent By rcaranci Date 01-11-2017 Time 15:55 Rev Time 0.00
Received By rcaranci Date 01-11-2017 Time 15:55 Sent To  
Notes
2017-01-11 15:55:41FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PRESIDENTIAL STORAGE CPD MINOR Z16110037
 JANUARY 11, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE ADJUST ALL CALCULATIONS ON THE
 SITE PLAN AND LANDSCAPE PLAN FOR AREAS AND QUANTITIES.
  
 2. SATISFIED. THE TREE COUNT HAS BEEN REDUCED BY 5
 TREES. PLEASE ADD TREES TO BRING THE TOTALS TO THE
 NUMBER APPROVED WITH THE PD.
  
 3. SATISFIED. THE WATER SUPPLY LINE CONFIGURATION
 DISRUPTS THE BUFFER TREES AND THE REQUIRED TREE IN THE
 TERMINAL ISLAND OF THE NORTH PARKING. PLEASE
 RECONFIGURE TO MEET REQUIREMENTS AND SHOW LOCATIONS OF
 BACKFLOW PREVENTERS.
  
 4. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO
 PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS
 INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS,
 AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE
 ROOTS.
  
 5. SATISFIED. PLEASE UPDATE CALCULATIONS FOR PARKING
 LOT LANDSCAPE AREA REQUIREMENTS PER SECTION 94-443 (C)
 3 AND 4.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-12-2016 Cont ID  
Sent By rcaranci Date 12-12-2016 Time 16:23 Rev Time 0.00
Received By rcaranci Date 12-12-2016 Time 16:23 Sent To  
Notes
2016-12-12 16:23:40FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: PRESIDENTIAL STORAGE CPD MINOR Z16110037
 DECEMBER 12, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE ADJUST ALL CALCULATIONS ON THE SITE PLAN AND
 LANDSCAPE PLAN FOR AREAS AND QUANTITIES.
  
 2. THE TREE COUNT HAS BEEN REDUCED BY 5 TREES. PLEASE
 ADD TREES TO BRING THE TOTALS TO THE NUMBER APPROVED
 WITH THE PD.
  
 3. THE WATER SUPPLY LINE CONFIGURATION DISRUPTS THE
 BUFFER TREES AND THE REQUIRED TREE IN THE TERMINAL
 ISLAND OF THE NORTH PARKING. PLEASE RECONFIGURE TO MEET
 REQUIREMENTS AND SHOW LOCATIONS OF BACKFLOW PREVENTERS.
  
 4. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 5. PLEASE UPDATE CALCULATIONS FOR PARKING LOT LANDSCAPE
 AREA REQUIREMENTS PER SECTION 94-443 (C) 3 AND 4.
  

Review Stop STORM STORMWATER
Rev No 2 Status P Date 01-18-2017 Cont ID  
Sent By tward Date 01-18-2017 Time 16:04 Rev Time 0.00
Received By tward Date   Time   Sent To  
Notes
2017-01-18 16:19:33COMMENTS ON THE 12/22/2016 RE-SUBMITTAL PACKAGE.
 1. SOME OF THE RESPONSES TO THE PPRC COMMENTS INDICATED
 THE COMMENTS WILL BE ADDRESSED AT BUILDING PERMIT
 SUBMITTAL.
  
 2. COORDINATE WITH PALM BEACH COUNTY THE PROPOSED
 IMPROVEMENTS IN THE CONGRESS AVE RIGHT-OF-WAY. SHOULD
 THERE BE VALLEY GUTTER ACROSS THE DRIVEWAYS? WILL
 EXISTING LIGHT POLE NORTH OF THE SOUTH DRIVEWAY NEED TO
 BE RELCATED BECAUSE OF PROPOSED DRAINAGE STRUCTURE #1?
 WHO WILL BE RESPONSIBLE TO MAINTAIN THE EXFILTRATION
 TRENCH CONNECTED TO STRUCTURE #1?
  
 3. CONNECTION OF PROPOSED 8" WATER MAIN TO THE EXISTING
 18" WATER MAIN SHOULD NOT OCCUR UNDER THE DRAINAGE
 STRUCTURE TOP.
  
 4. LABEL THE VERTICAL DATUM FOR THE FINISHED FLOOR
 ELEVATION ON THE SITE PLAN.
  
 5. THE PAVING, DRAINAGE, WATER AND SEWER PLAN LISTS THE
 FFE AS 17.50 NGVD. THE SITE PLAN LISTS THE FFE AS
 16.50. THIS NEEDS TO BE COORDINATED.
  
 6. WILL FILL BE BROUGHT IN FOR THE AREAS NORTHWEST AND
 SOUTHEAST OF THE PARKING LOTS. PROVIDE A CROSS SECTION
 ACROSS THESE AREAS FROM THE PROPERTY LINE TO THE
 CURBING OF THE PARKING AREAS.
  
 TRACY L. WARD, P.E.
 ENGINEERING SERVICES DEPARTMENT
 [email protected]
 561-494-1120
  

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-14-2016 Cont ID  
Sent By tward Date 12-14-2016 Time 01:49 Rev Time 0.00
Received By tward Date 12-14-2016 Time 01:51 Sent To  
Notes
2016-12-14 01:51:06THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION
 INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD
 HAZARD AREA.
  
 3. TREES ARE PROPOSED OVER OR NEAR THE EXFILTRATION
 TRENCH.
  
 4. PROVIDE A COPY OF THE AGREEMENT TO CONNECT TO AND
 DISCHARGE STORMWATER RUNOFF TO THE PRIVATE LAKE ON THE
 ADJACENT PROPERTY.
  
 5. IT APPEARS DRAINAGE STRUCTURES ON CONGRESS AVE WILL
 BE IMPACTED BY THE DRIVEWAY CONSTRUCTION. A PERMIT WILL
 BE REQUIRED FROM PALM BEACH COUNTY.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE
 MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT
 AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY
 AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP OR ERP MODIFICATION
 FOR THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop Z ZONING
Rev No 3 Status P Date 01-23-2017 Cont ID  
Sent By eschneid Date 01-23-2017 Time 10:40 Rev Time 0.25
Received By eschneid Date 01-23-2017 Time 10:40 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 01-10-2017 Cont ID  
Sent By eschneid Date 01-10-2017 Time 15:31 Rev Time 0.25
Received By eschneid Date 01-10-2017 Time 13:26 Sent To  
Notes
2017-01-10 15:32:08CASE NO. PB 1697D ? 1ST RESUBMITTAL
 PRESIDENTIAL STORAGE CPD
 1620 NORTH CONGRESS AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THESE COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THESE COMMENTS (BY MARCH 10, 2017),
 THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY FURTHER
 ACTION SHALL REQUIRE A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 ADDITIONAL RESUBMITTAL AT NO ADDITIONAL COST. IF
 PREVIOUSLY-ISSUED COMMENTS CONTINUE TO NOT BE
 SUFFICIENTLY ADDRESSED, THE APPLICANT WILL BE ACCESSED
 A RESUBMITTAL FEE. SUCH FEE WILL BE 20% OF THE ORIGINAL
 APPLICATION FEE ($60).
  
 1) REVISED COMMENT: THE BUILDING DIMENSIONS SHOWN ON
 THE LANDSCAPE PLAN WERE NOT UPDATED.
  

Review Stop Z ZONING
Rev No 1 Status F Date 12-09-2016 Cont ID  
Sent By eschneid Date 12-09-2016 Time 16:46 Rev Time 2.00
Received By eschneid Date 12-09-2016 Time 16:46 Sent To  
Notes
2016-12-09 16:48:20CASE NO. PB 1697D
 PRESIDENTIAL STORAGE CPD
 1620 NORTH CONGRESS AVENUE
  
 - CONTACT ERIC SCHNEIDER @ (561) 822-1446
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF FIVE
 (5) PAPER COPIES AND AN ELECTRONIC COPY IN .PDF FORMAT
 OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE DATE OF THE PPRC MEETING (BY FEBRUARY 14,
 2017), THE CASE SHALL BE CONSIDERED WITHDRAWN. ANY
 FURTHER ACTION SHALL REQUIRE A NEW DEVELOPMENT
 APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($60).
  
 1) PLEASE CHANGE THE "PROPOSED ZONING" AND "PROPOSED
 LAND USE" LINE ITEMS ON THE SITE DATA TABLE TO REFLECT
 THEM AS THE CURRENT ZONING AND LAND USE.
  
 2) THE PARKING IS INCORRECTLY CALCULATED. RETAIL USES
 ONLY REQUIRE 1 PARKING SPACE PER 250 SQUARE FEET.
 PLEASE UPDATE THE TABLE TO SHOW ONLY 35 REQUIRED
 PARKING SPACES.
  
 3) THE BUILDING INCREASED IN SIZE; HOWEVER THE LOT
 COVERAGE AND NET FLOOR AREA RATIO NUMBERS DID NOT
 CHANGE. PLEASE VERIFY ALL NUMBERS BASED ON THE NEW
 SQUARE FOOTAGE.
  
 4) THE FRONT SETBACK ON THE TABLE IS LISTED STILL
 LISTED AS 7 FEET; HOWEVER, THE PLANS SHOW 8 FOOT
 SETBACK DIMENSIONS ON THE TAG LINES. PLEASE CLARIFY.
  
 5) THE BUILDING SQUARE FOOTAGE AND DIMENSIONS SHOWN ON
 THE LANDSCAPE PLAN WERE NOT UPDATED.
  
 6) THE JUSTIFICATION STATEMENT NEEDS TO BE REVISED TO
 STATE THAT THERE ARE NOW 13, INSTEAD OF 12 PARKING
 SPACES IN THE SOUTH LOT.
  
 7) ON THE SITE PLAN, THERE IS AN ARROW INDICATING A "NO
 PARKING - FIRE LANE" SIGN WHICH POINTS TO THE DUMPSTER
 ENCLOSURE. PLEASE CORRECT THE DRAWING.
  
 8) PLEASE VERIFY THAT THE GRASSPAVE WILL BE ABLE TO
 SUPPORT A FIRE TRUCK WHERE THE EXFILTRATION TRENCH RUNS
 UNDER IT.
  