Plan Review Details - Project Z16110015
| Plan Review Stops For Project Z16110015 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
12-14-2016 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
12-14-2016 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
03-27-2017 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2016-12-14 11:06:04 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. FOR ANY BUILDING CROSSING A PROPERTY LINE, EITHER A | | | RECORDED UNITY OF TITLE, OR SOME OTHER APPROVED LEGAL | | | INSTRUMENT, SHALL BE INCLUDED WITH THE PERMIT | | | APPLICATION, OR THE BUILDING MUST HAVE A FIRE WALL | | | ALONG THE PROPERTY LINE, PER SECTION 202 OF FLORIDA | | | BUILDING CODE, BUILDING, FIRE SEPARATION DISTANCE. | | | | | | 3. ON FIRST FLOOR PLAN SHEET A1.1A, IT APPEARS THAT THE | | | EGRESS FROM THE EXISTING AND PROPOSED BUILDINGS IS | | | THROUGH THE SPACE LABELED AS "CONNECTION TO THE OLD | | | SCHOOL" AND THOUGH DOUBLE DOORS INTO THE COURTYARD. THE | | | DOOUBLE DOORS MAY NEED TO BE RELOCATED BECAUSE THEY ARE | | | SHOWN RIGHT UP AGAINST THE LIBRARY AND WILL BE AT RISK | | | FROM FIRE OR SMOKE COMING FROM ANY WINDOWS THAT ARE IN | | | THE EXTERIOR WALL OF THE LIBRARY. | | | | | | 3. WHEN SUBMITTED FOR PERMIT, THE PLANS SHALL SHOW AT | | | LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH SECTIONS | | | 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, FROM THE | | | PUBLIC RIGHT-OF-WAY TO ALL ACCESSIBLE BUILDING OR | | | FACILITY ENTRANCES. | | | | | | 4. SHOW AT LEAST ONE ACCESSIBLE ROUTE, COMPLYING WITH | | | SECTIONS 206.2 AND 402.2 OF FLORIDA ACCESSIBILITY CODE, | | | CONNECTING ACCESSIBLE BUILDING OR FACILITY ENTRANCES | | | WITH ALL ACCESSIBLE SPACES AND ELEMENTS WITHIN THE | | | BUILDING OR FACILITY | | | | | | 5. ANY PART OF AN ACCESSIBLE ROUTE WITH A SLOPE GREATER | | | THAN 1:20 SHALL BE CONSIDERED A RAMP AND SHALL COMPLY | | | WITH SECTION 405 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 6. ACCESSIBLE PARKING LOCATION IS NOT SHOWN. THE SITE | | | DATA TABLE ON SHEET SP-1 STATES THAT 2 ACCIESSIBLE | | | PARKING SPACES ARE BEING PROVIDED. THE LOCATION OF THE | | | PROPOSED ACCESSIBLE PARKING SPACES DOES NOT APPEAR TO | | | BE SHOWN ON THE PLANS. PER SECTION 208.3 OF FLORIDA | | | ACCESSIBILITY CODE, ACCESSIBLE PARKING SPACES ARE TO BE | | | LOCATED ON THE SHORTEST POSSIBLE ROUTE OF TRAVEL FROM | | | ADJACENT PARKING TO AN ACCESSIBLE ENTRANCE FOR EACH | | | BUILDING. THE DESIGN OF ACCESSIBLE PARKING SPACES SHALL | | | COMPLY WITH SECTION 502 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 7. WHEN SELECTING LOCATIONS FOR ACCESSIBLE PARKING | | | SPACES, PLEASE NOTE THAT ACCESSIBLE PARKING SPACE | | | ACCESS AISLES SHALL BE LOCATED SO THAT THE USER IS NOT | | | COMPELLED TO WALK OR WHEEL BEHIND ANOTHER PARKED | | | VEHICLE OR IN THE TRAVEL LANE. THE ACCESS AISLES SHALL | | | ALSO COMPLY WITH THE OTHER PROVISIONS OF SECTION OF | | | 502.3 OF FLORIDA ACCESSIBILITY CODE. | | | | | | 8. THE ADDITION TO THE EXISTING BUILDING IS COVERED BY | | | CHAPTER 11 OF THE FLORIDA EXISTING BUILDING CODE. THE | | | HEIGHT AND/OR AREA INCREASE DUE TO THE PROPOSED | | | ADDITION SHALL NOT INCREASE THE TOTAL BUILDING HEIGHT | | | AND/OR AREA BEYOND THAT ALLOWED UNDER THE APPLICABLE | | | PROVISIONS OF CHAPTER 5 OF THE FLORIDA BUILDING CODE | | | FOR THE TYPE OF CONSTRUCTION USED. | | | | | | 9. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH | | | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND | | | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF | | | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. | | | | | | 10. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 11. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC | | | PLACES (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION | | | OF PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, | | | CONTACT SYBILLE WELTER, ART IN PUBLIC PLACES | | | COORDINATOR, AT (561) 822-1521, OR BY EMAIL: | | | [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
03-24-2017 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
03-24-2017 |
Time |
16:22 |
Rev Time |
0.00 |
| Received By |
mkhan |
Date |
03-24-2017 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2017-03-24 16:23:21 | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | | | | PROJECT NAME: GREEN SCHOOL EXPANSION RESUBMITTAL - ISPR | | | 16-01B - Z16110015 | | | | | | 2ND REVIEW RESPONSE: PASSED WITH CONDITION | | | | | | DATE: MARCH 24, 2017 | | | | | | AFTER A REVIEWING THE REVISED PLAN (RECEIVED ON | | | 03/14/2017) AND THE RESPONSES TO THE PREVIOUS PPRC | | | COMMENTS, IT APPEARS THAT SOME OF THE COMMENTS HAVE | | | BEEN ACKNOWLEDGED AND OTHER REQUESTED INFORMATION ARE | | | NOT YET SHOWN ON THE ?PHASE II CONCEPTUAL PLAN?. THESE | | | ACKNOWLEDGED COMMENTS NEED TO BE ADDRESSED AND ?MORE | | | DETAILS? NEED TO BE SHOWN ON THE FINAL PLANS AS AGREED | | | UPON ON THE RESPONSE DURING DETAIL DESIGN AT | | | ?ENGINEERING DEVELOPMENT APPLICATION? PHASE PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1124 (OFFICE) | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
12-12-2016 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
12-12-2016 |
Time |
12:14 |
Rev Time |
4.00 |
| Received By |
mkhan |
Date |
12-12-2016 |
Time |
12:14 |
Sent To |
|
|
| Notes |
| 2016-12-12 12:16:47 | CITY OF WEST PALM BEACH | | | PUBLIC WORKS DEPARTMENT | | | ENGINEERING DIVISION | | | | | | DATE: 12/12/2016 | | | | | | Z16110015: 2001 S. DIXIE HWY. - GREEN SCHOOL | | | | | | THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. | | | | | | THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR | | | TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 1. PLAN REVIEW FOR ADDITIONAL IMPROVEMENT WILL REQUIRE | | | A SEPARATE ENGINEERING DEVELOPMENT APPROVAL APPLICATION | | | FROM THE ENGINEERING DIVISION OF THE PUBLIC WORKS | | | DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION FORMS CAN BE DOWNLOADED AT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC | | | CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF | | | WEST PALM BEACH PUBLIC WORKS DEPARTMENT FOR ADDITIONAL | | | WORK PROPOSED. THIS FORM CAN BE DOWNLOADED FROM THE | | | FOLLOWING LINK: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | THE FOLLOWING WATER AND SEWER COMMENTS: | | | | | | 3. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND | | | SANITARY SEWER CALCULATION (AVERAGE AND PEAK WITH | | | PEAKING FACTOR) FOR THE PROPOSED BUILDING/GYMNASIUM. | | | SUBMIT CALCULATIONS TO VALIDATE METER SIZE SELECTION. | | | SHOW THESE CALCULATIONS ON THE UTILITY PLAN SHEET AS | | | WELL; | | | | | | 4. PLAN DOES NOT CLEARLY SHOW WHAT ARE THE UTILITY | | | SERVICES TO THE PROPOSED GYMNASIUM BUILDING; | | | | | | 5. HOW DO YOU PROPOSE TO ISOLATE THE EXISTING WATER | | | MAIN IN THE ALLEY WAY BETWEEN BISCAYNE DRIVE AND | | | FLAMINGO DRIVE? REVIEW WATERLINE CONFIGURATION ON | | | BISCAYNE DRIVE; | | | | | | 6. A FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE | | | HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL; | | | | | | 7. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE | | | CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE | | | DETAILS SHEET. CONTACT THE ENGINEERING SERVICES | | | DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD | | | FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT) | | | CAN BE DOWNLOADED FROM THE FOLLOWING SITE: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR | | | MS,-PERMITS-APPLICATIONS | | | | | | 8. PLACEMENT OF THE PROPOSED METER, BACKFLOW PREVENTER, | | | DCDA ETC. SHALL BE INSTALLED PER THE CITY'S STANDARD | | | DETAILS. WATER METER SHOULD BE INSIDE AN 'UTILITY | | | EASEMENT' JUST INSIDE THE PROPERTY NEAR THE | | | RIGHT-OF-WAY AND ACCESSIBLE; | | | | | | 9. PROVIDE ALL UTILITY CROSSING INFORMATION. SHOW | | | CONFLICT INFORMATION (BOTTOM AND TOP OF CROSSING PIPES) | | | AT THE CONFLICT POINTS OF ALL WATER, STORM AND SANITARY | | | SEWER PIPES AS WELL AS OTHER FRANCHISE UTILITIES; | | | | | | 10. PAVEMENT RESTORATION WILL BE REQUIRED FOR THE | | | PROPOSED SANITARY SEWER CONNECTION TO THE EXISTING | | | MANHOLE WITHIN THE RIGHT-OF-WAY. REFER TO THE CITY | | | STANDARD DETAILS FOR RESTORATION GUIDELINES AND SHOW | | | THE EXTENT OF PAVEMENT RESTORATION ON THE PLANS; | | | | | | 11. EXISTING WATER SERVICE CONNECTIONS/WATER METERS | | | SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND | | | CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES | | | LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL | | | PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY | | | PLANS ACCORDINGLY; | | | | | | 12. EXISTING SEWER SERVICE CONNECTIONS SERVING THE | | | PROPERTY, IF NOT USED, ARE TO BE CUT AND CAPPED AT THE | | | MAIN; | | | | | | 13. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY | | | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS | | | BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES | | | MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE | | | LINK BELOW: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI | | | CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL | | | | | | 14. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE | | | WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE WITHIN | | | AN EASEMENT WITHIN THE PROPERTY. LANDSCAPE PLAN SHALL | | | SHOW LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS, | | | LIGHT POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE | | | PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR | | | POTABLE WATER LINES. | | | | | | 15. SUBMITTAL MAINTENANCE OF TRAFFIC (MOT) WILL BE | | | REQUIRED AT THE PRE-CONSTRUCTION MEETING. | | | | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1024 (OFFICE) | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
12-09-2016 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
12-09-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
12-09-2016 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2016-12-09 09:18:29 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES, | | | INCLUDING BUT NOT LIMITED TO, CHAPTER 14, NEW | | | EDUCATIONAL OCCUPANCIES. | | | | | | | | | 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE | | | OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE, | | | AND WHETHER IT WILL BE MIXED OR SEPARATED OCCUPANCIES. | | | | | | | | | 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE | | | LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER | | | SUPPLY IS EXISTING OR WILL BE PROVIDED. | | | | | | | | | 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | | | | 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER | | | THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY | | | ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM, | | | ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND | | | SUBMITTED WITH THE MASTER PLAN. | | | | | | | | | 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | | | | 11. IT IS HIGHLY RECOMMENDED FOR ANY SITE AND/OR | | | BUILDING ACCESS POINTS THAT THEY BE PROVIDED WITH KNOX | | | KEY BOXES, ACCESS LOCKS, PADLOCKS AND/OR SWITCHES FOR | | | 24 HOUR EMERGENCY ACCESS. | | | | | | | | | 12. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED | | | FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE | | | CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY | | | MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE | | | WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME | | | TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED | | | WITH A MALTESE CROSS SIGN MEASURING 8 INCHES | | | HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED | | | REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED | | | WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR. | | | | | | | | | 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | | | | 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
4 |
Status |
P |
Date |
06-27-2017 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
06-27-2017 |
Time |
16:56 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
06-27-2017 |
Time |
16:56 |
Sent To |
|
|
| Notes |
| 2017-06-27 16:57:28 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16110015 | | | JUNE 27, 2017 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. SATISFIED. PLEASE PROVIDE INFORMATION ON THE | | | INSTALLATION AND COMPLETION OF THE APPROVED AND | | | PERMITTED LANDSCAPING FOR THE CO OF THE EXISTING | | | BUILDING, AND HOW THE TIMING OF THE CONSTRUCTION OF | | | THIS ADDITION WOULD BE COORDINATED. | | | | | | THE CURRENT BUILDING IS OPERATING UNDER A TCO. IF THE | | | LANDSCAPING IS COMPLETED TO PERMIT PLAN, AND | | | CERTIFICATION FROM THE LANDSCAPE ARCHITECT CAN BE | | | ISSUED, A FINAL INSPECTION SHOULD BE SCHEDULED AND THE | | | LANDSCAPE PERMIT CLOSED OUT. | | | | | | LANDSCAPE INSPECTION WAS CONDUCTED ON 5/30/17, A PUNCH | | | LIST OF ITEMS WAS EMAILED. | | | | | | 2. SATISFIED. PLEASE SHOW THE BUFFER PLANTINGS ALONG | | | THE WEST PROPERTY LINE AS PREVIOUSLY APPROVED, AND | | | LABEL ALL LANDSCAPE BUFFERS. | | | | | | 3. SATISFIED. PLEASE CORRECT THE FOUNDATION PLANTING | | | CALCULATION TO REFLECT THE PERCENTAGE OF THE ENTIRE | | | BUILDING FOR REQUIRED AND PROVIDED LINEAR FOOTAGE TO | | | MEET THE REQUIREMENTS OF SECTION 94-443(E)(1). | | | THE PROPOSED BUILDING MEETS THE REQUIREMENT, BUT THE | | | EXISTING BUILDING SHOWS ONLY 60 LINEAR FEET PROVIDED, | | | NOT THE 100 INDICATED ON THE PLAN, AND SHORT OF THE 75 | | | FEET REQUIRED. | | | | | | 4. SATISFIED. PLEASE PROVIDE A STATUS UPDATE ON | | | CONDITION #2 OF THE CURRENT APPROVAL REGARDING STREET | | | TREES ON DIXIE. | | | | | | PER THE PLANNING AND ZONING ADMINISTRATOR, PLEASE | | | PROVIDE ANY INFORMATION FROM FDOT TO SHOW THIS CANNOT | | | BE ACCOMPLISHED. | | | | | | COMMENT WAS NOT SATISFIED FROM THE LAST REVIEW. (ALSO | | | SEE COMMENT #9) | | | | | | 5. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | MAY NEED TO BE ADJUSTED IF REQUIRED TREES FOR PARKING | | | ARE ADDED IN THE NORTH DROP OFF AREA PARKING. | | | | | | 6. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 7. SATISFIED. PLEASE REMOVE THE REFERENCE TO THE OAK | | | TREE IN THE RIGHT OF WAY AT THE SOUTH SIDE OF BISCAYNE | | | DRIVE, AS IT HAS BEEN REMOVED. | | | TREE IS STILL SHOWN ON SHEETS LP-1 AND LI-1. PLEASE | | | REVISE. | | | ADDITIONAL COMMENTS 4/3/17: | | | 8. SATISFIED. PLEASE PROVIDE THE REQUIRED TREE AND | | | TERMINAL LANDSCAPE ISLAND ADJACENT TO EACH END OF THE | | | ROW OF PARKING IN THE NORTH DROP OFF AREA. | | | | | | 9. SATISFIED. PLEASE INDICATE CURBED BULB OUTS ADJACENT | | | TO THE PARKING SPACES PROPOSED IN THE FLAMINGO DRIVE | | | RIGHT OF WAY AND PROVIDE LANDSCAPING AND STREET TREES. | | | | | | THE REQUIRED NUMBER OF BUFFER TREES CANNOT BE INSTALLED | | | WHERE EFFECTIVE DUE TO THE NONCONFORMING SETBACK OF THE | | | EXISTING BUILDING, THEREFORE THE LOGICAL WAY TO MEET | | | THE INTENT OF THE CODE AND PROVIDE FOR SCREENING AND | | | SUPPLY NECESSARY SHADE FOR THE SIDEWALKS AND PARKING | | | SPACES IS TO PROVIDE TREES IN THE RIGHT OF WAY. | | | RECENTLY AMENDED LANDSCAPE CODE REQUIRES THIS IN FUTURE | | | PROJECTS, AND THE CITY IS REQUESTING THAT THIS PROJECT | | | PROVIDE THE TREES WHERE POSSIBLE TO BENEFIT THE PUBLIC. | | | | | | 10. SATISFIED. PLEASE INDICATE WHERE THE FPL | | | TRANSFORMER IS PROPOSED IF IT IS NOT GOING TO REMAIN IN | | | THE CURRENT LOCATION. | | | | | | ADDITIONAL COMMENTS 5/31/17: | | | 11. SATISFIED. PLEASE PROVIDE A TREE DISPOSITION PLAN | | | TO SHOW WHAT IS PROPOSED FOR THE EXISTING TREES ON SITE | | | THAT WILL NEED TO BE RELOCATED OR REMOVED. TREES MAY BE | | | RELOCATED TO ANY LOCATION WITHIN THE CITY. A SEPARATE | | | PLAN WILL BE REQUIRED TO BE SUBMITTED AND REVIEWED IF | | | ADDING TREES TO EXISTING DEVELOPMENTS. | | | | | | 12. SATISFIED. PLEASE CORRECT THE LANDSCAPE | | | REQUIREMENTS CHART TO SHOW THE NUMBER OF FLOWERING | | | TREES PROVIDED TO MATCH THE PLANT LIST (SHOWS 9), | | | LANDSCAPE PLAN (SHOWS 8) AND CURRENT CONDITIONS (7, | | | LOCATION IN SOUTH PARKING LOT HAS A SILVER BUTTONWOOD | | | EXISTING INSTEAD OF TABEBUIA). | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | 2. A SEPARATE LANDSCAPE PERMIT SHALL BE REQUIRED FOR | | | ANY RELOCATION OF TREES OR PALMS ONTO OTHER PROPERTIES | | | TO ALLOW REVIEW OF LOCATIONS, RECORD FINAL LOCATIONS, | | | AND ALLOW FOR INSPECTIONS. | | | | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
3 |
Status |
F |
Date |
05-31-2017 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
05-31-2017 |
Time |
14:23 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
05-24-2017 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2017-05-31 14:26:13 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16110015 | | | MAY 31, 2017 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. ONGOING. PLEASE PROVIDE INFORMATION ON THE | | | INSTALLATION AND COMPLETION OF THE APPROVED AND | | | PERMITTED LANDSCAPING FOR THE CO OF THE EXISTING | | | BUILDING, AND HOW THE TIMING OF THE CONSTRUCTION OF | | | THIS ADDITION WOULD BE COORDINATED. | | | | | | THE CURRENT BUILDING IS OPERATING UNDER A TCO. IF THE | | | LANDSCAPING IS COMPLETED TO PERMIT PLAN, AND | | | CERTIFICATION FROM THE LANDSCAPE ARCHITECT CAN BE | | | ISSUED, A FINAL INSPECTION SHOULD BE SCHEDULED AND THE | | | LANDSCAPE PERMIT CLOSED OUT. | | | | | | LANDSCAPE INSPECTION WAS CONDUCTED ON 5/30/17, A PUNCH | | | LIST OF ITEMS WAS EMAILED. | | | | | | 2. SATISFIED. PLEASE SHOW THE BUFFER PLANTINGS ALONG | | | THE WEST PROPERTY LINE AS PREVIOUSLY APPROVED, AND | | | LABEL ALL LANDSCAPE BUFFERS. | | | | | | 3. SATISFIED. PLEASE CORRECT THE FOUNDATION PLANTING | | | CALCULATION TO REFLECT THE PERCENTAGE OF THE ENTIRE | | | BUILDING FOR REQUIRED AND PROVIDED LINEAR FOOTAGE TO | | | MEET THE REQUIREMENTS OF SECTION 94-443(E)(1). | | | THE PROPOSED BUILDING MEETS THE REQUIREMENT, BUT THE | | | EXISTING BUILDING SHOWS ONLY 60 LINEAR FEET PROVIDED, | | | NOT THE 100 INDICATED ON THE PLAN, AND SHORT OF THE 75 | | | FEET REQUIRED. | | | | | | 4. NOT SATISFIED. PLEASE PROVIDE A STATUS UPDATE ON | | | CONDITION #2 OF THE CURRENT APPROVAL REGARDING STREET | | | TREES ON DIXIE. | | | | | | PER THE PLANNING AND ZONING ADMINISTRATOR, PLEASE | | | PROVIDE ANY INFORMATION FROM FDOT TO SHOW THIS CANNOT | | | BE ACCOMPLISHED. | | | | | | COMMENT WAS NOT SATISFIED FROM THE LAST REVIEW. (ALSO | | | SEE COMMENT #9) | | | | | | 5. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | MAY NEED TO BE ADJUSTED IF REQUIRED TREES FOR PARKING | | | ARE ADDED IN THE NORTH DROP OFF AREA PARKING. | | | | | | 6. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 7. NOT SATISFIED. PLEASE REMOVE THE REFERENCE TO THE | | | OAK TREE IN THE RIGHT OF WAY AT THE SOUTH SIDE OF | | | BISCAYNE DRIVE, AS IT HAS BEEN REMOVED. | | | TREE IS STILL SHOWN ON SHEETS LP-1 AND LI-1. PLEASE | | | REVISE. | | | | | | ADDITIONAL COMMENTS 4/3/17: | | | 8. SATISFIED. PLEASE PROVIDE THE REQUIRED TREE AND | | | TERMINAL LANDSCAPE ISLAND ADJACENT TO EACH END OF THE | | | ROW OF PARKING IN THE NORTH DROP OFF AREA. | | | | | | 9. NOT SATISFIED. PLEASE INDICATE CURBED BULB OUTS | | | ADJACENT TO THE PARKING SPACES PROPOSED IN THE FLAMINGO | | | DRIVE RIGHT OF WAY AND PROVIDE LANDSCAPING AND STREET | | | TREES. | | | | | | THE REQUIRED NUMBER OF BUFFER TREES CANNOT BE INSTALLED | | | WHERE EFFECTIVE DUE TO THE NONCONFORMING SETBACK OF THE | | | EXISTING BUILDING, THEREFORE THE LOGICAL WAY TO MEET | | | THE INTENT OF THE CODE AND PROVIDE FOR SCREENING AND | | | SUPPLY NECESSARY SHADE FOR THE SIDEWALKS AND PARKING | | | SPACES IS TO PROVIDE TREES IN THE RIGHT OF WAY. | | | RECENTLY AMENDED LANDSCAPE CODE REQUIRES THIS IN FUTURE | | | PROJECTS, AND THE CITY IS REQUESTING THAT THIS PROJECT | | | PROVIDE THE TREES WHERE POSSIBLE TO BENEFIT THE PUBLIC. | | | | | | 10. SATISFIED. PLEASE INDICATE WHERE THE FPL | | | TRANSFORMER IS PROPOSED IF IT IS NOT GOING TO REMAIN IN | | | THE CURRENT LOCATION. | | | | | | ADDITIONAL COMMENTS 5/31/17: | | | 11. PLEASE PROVIDE A TREE DISPOSITION PLAN TO SHOW WHAT | | | IS PROPOSED FOR THE EXISTING TREES ON SITE THAT WILL | | | NEED TO BE RELOCATED OR REMOVED. TREES MAY BE RELOCATED | | | TO ANY LOCATION WITHIN THE CITY. A SEPARATE PLAN WILL | | | BE REQUIRED TO BE SUBMITTED AND REVIEWED IF ADDING | | | TREES TO EXISTING DEVELOPMENTS. | | | | | | 12. PLEASE CORRECT THE LANDSCAPE REQUIREMENTS CHART TO | | | SHOW THE NUMBER OF FLOWERING TREES PROVIDED TO MATCH | | | THE PLANT LIST (SHOWS 9), LANDSCAPE PLAN (SHOWS 8) AND | | | CURRENT CONDITIONS (7, LOCATION IN SOUTH PARKING LOT | | | HAS A SILVER BUTTONWOOD EXISTING INSTEAD OF TABEBUIA). | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
F |
Date |
04-03-2017 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
04-03-2017 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
04-03-2017 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2017-04-03 16:35:11 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16110015 | | | APRIL 3, 2017 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. NOT SATISFIED. PLEASE PROVIDE INFORMATION ON THE | | | INSTALLATION AND COMPLETION OF THE APPROVED AND | | | PERMITTED LANDSCAPING FOR THE CO OF THE EXISTING | | | BUILDING, AND HOW THE TIMING OF THE CONSTRUCTION OF | | | THIS ADDITION WOULD BE COORDINATED. | | | | | | THE CURRENT BUILDING IS OPERATING UNDER A TCO. IF THE | | | LANDSCAPING IS COMPLETED TO PERMIT PLAN, AND | | | CERTIFICATION FROM THE LANDSCAPE ARCHITECT CAN BE | | | ISSUED, A FINAL INSPECTION SHOULD BE SCHEDULED AND THE | | | LANDSCAPE PERMIT CLOSED OUT. | | | | | | 2. SATISFIED. PLEASE SHOW THE BUFFER PLANTINGS ALONG | | | THE WEST PROPERTY LINE AS PREVIOUSLY APPROVED, AND | | | LABEL ALL LANDSCAPE BUFFERS. | | | | | | 3. PARTIALLY SATISFIED. PLEASE CORRECT THE FOUNDATION | | | PLANTING CALCULATION TO REFLECT THE PERCENTAGE OF THE | | | ENTIRE BUILDING FOR REQUIRED AND PROVIDED LINEAR | | | FOOTAGE TO MEET THE REQUIREMENTS OF SECTION | | | 94-443(E)(1). | | | THE PROPOSED BUILDING MEETS THE REQUIREMENT, BUT THE | | | EXISTING BUILDING SHOWS ONLY 60 LINEAR FEET PROVIDED, | | | NOT THE 100 INDICATED ON THE PLAN, AND SHORT OF THE 75 | | | FEET REQUIRED. | | | | | | 4. NOT SATISFIED. PLEASE PROVIDE A STATUS UPDATE ON | | | CONDITION #2 OF THE CURRENT APPROVAL REGARDING STREET | | | TREES ON DIXIE. | | | | | | PER THE PLANNING AND ZONING ADMINISTRATOR, PLEASE | | | PROVIDE ANY INFORMATION FROM FDOT TO SHOW THIS CANNOT | | | BE ACCOMPLISHED. | | | | | | 5. SATISFIED. PLEASE PROVIDE LOCATIONS OF LIGHTING ON | | | THE LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | MAY NEED TO BE ADJUSTED IF REQUIRED TREES FOR PARKING | | | ARE ADDED IN THE NORTH DROP OFF AREA PARKING. | | | | | | 6. SATISFIED. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO | | | PROTECT INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS | | | INCLUDES WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, | | | AND ANY FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE | | | ROOTS. | | | | | | 7. SATISFIED. PLEASE REMOVE THE REFERENCE TO THE OAK | | | TREE IN THE RIGHT OF WAY AT THE SOUTH SIDE OF BISCAYNE | | | DRIVE, AS IT HAS BEEN REMOVED. | | | ADDITIONAL COMMENTS 4/3/17: | | | 8. PLEASE PROVIDE THE REQUIRED TREE AND TERMINAL | | | LANDSCAPE ISLAND ADJACENT TO EACH END OF THE ROW OF | | | PARKING IN THE NORTH DROP OFF AREA. | | | | | | 9. PLEASE INDICATE CURBED BULB OUTS ADJACENT TO THE | | | PARKING SPACES PROPOSED IN THE FLAMINGO DRIVE RIGHT OF | | | WAY AND PROVIDE LANDSCAPING AND STREET TREES. | | | | | | 10. PLEASE INDICATE WHERE THE FPL TRANSFORMER IS | | | PROPOSED IF IT IS NOT GOING TO REMAIN IN THE CURRENT | | | LOCATION. | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
12-13-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
12-13-2016 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
12-13-2016 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2016-12-13 12:44:25 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 2001 S DIXIE Z16110015 | | | DECEMBER 13, 2016 | | | I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND | | | PROVIDE THE FOLLOWING COMMENTS: | | | | | | 1. PLEASE PROVIDE INFORMATION ON THE INSTALLATION AND | | | COMPLETION OF THE APPROVED AND PERMITTED LANDSCAPING | | | FOR THE CO OF THE EXISTING BUILDING, AND HOW THE TIMING | | | OF THE CONSTRUCTION OF THIS ADDITION WOULD BE | | | COORDINATED. | | | | | | 2. PLEASE SHOW THE BUFFER PLANTINGS ALONG THE WEST | | | PROPERTY LINE AS PREVIOUSLY APPROVED, AND LABEL ALL | | | LANDSCAPE BUFFERS. | | | | | | 3. PLEASE CORRECT THE FOUNDATION PLANTING CALCULATION | | | TO REFLECT THE PERCENTAGE OF THE ENTIRE BUILDING FOR | | | REQUIRED AND PROVIDED LINEAR FOOTAGE TO MEET THE | | | REQUIREMENTS OF SECTION 94-443(E)(1). | | | | | | 4. PLEASE PROVIDE A STATUS UPDATE ON CONDITION #2 OF | | | THE CURRENT APPROVAL REGARDING STREET TREES ON DIXIE. | | | | | | 5. PLEASE PROVIDE LOCATIONS OF LIGHTING ON THE | | | LANDSCAPE PLAN TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 6. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT | | | INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES | | | WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY | | | FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS. | | | | | | 7. PLEASE REMOVE THE REFERENCE TO THE OAK TREE IN THE | | | RIGHT OF WAY AT THE SOUTH SIDE OF BISCAYNE DRIVE, AS IT | | | HAS BEEN REMOVED. | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
4 |
Status |
P |
Date |
06-27-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
06-27-2017 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
06-27-2017 |
Time |
14:07 |
Sent To |
|
|
| Notes |
| 2017-06-27 14:04:57 | COMMENT(S) BELOW BASED CONCEPTUAL LEVEL REVIEW OF | | | 6/27/2017 EMAILED SET OF PLANS FROM R. REIKENIS: | | | 1. CONSTRUCTION PLANS NEED TO INCLUDE CITY'S STANDARD | | | DETAILS FOR DRAINAGE STRUCTURE S-102. | | | | | | 2. S&S DRAINAGE CALCS SUBMITTED 6/27/17 DEMONSTRATE | | | PROJECT DRAINAGE SYSTEM MEETS WATER QUALITY AND | | | DISCHARGE REQUIREMENTS. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
3 |
Status |
F |
Date |
05-25-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
05-25-2017 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
05-25-2017 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2017-05-25 16:53:02 | COMMENTS BELOW ARE FROM THE CONCEPTUAL LEVEL REVIEW OF | | | THE MAY 23, 2017 REVIEW PACKAGE. | | | | | | 1. WEIR BOX DETAIL ON SHEET 5 OF 8 CALLS OUT PLACING | | | THE WEIR IN STRUCTURE S-102. THE WEIR NEEDS TO BE | | | INSTALLED ON THE PRIVATE SYSTEM, OUTSIDE OF THE | | | RIGHT-OF-WAY. | | | | | | 2. CONSIDER MOVING THE STORM PIPE ALONG THE WEST SIDE | | | OF THE BUILDING FURTHER TO THE WEST AWAY FROM THE | | | BUILDING SO THAT IF THE PIPE NEEDS TO BE REPLACED IN | | | THE FUTURE, IT CAN BE EXCAVATED WITHOUT UNDERMINING THE | | | BUILDING FOUNDATION. | | | | | | 3. CONSIDER ADDING MORE EXFILTRATION TRENCH AT THE | | | SOUTH END OF THE DRAINAGE SYSTEM (WEST OF THE BUILDING | | | AND/OR ACROSS THE WEST END OF THE SOCCER FIELD. THE | | | EXISTING EXFILTRATION TRENCH IS AT THE UP STREAM END OF | | | THE DRAINAGE SYSTEM AND ONLY THE PARKING LOT RUNOFF | | | WILL BE FLOW TO THE EXFILTRATION TRENCH. THE PIPE | | | SYSTEM SLOPES FROM NORTH TO SOUTH. | | | | | | 4. CONFIRM DIAMETER OF THE EXISTING STORM PIPE ON | | | BISCAYNE DRIVE WHERE STRUCTURE S-102 WILL BE | | | CONSTRUCTED. | | | | | | 5. LANDSCAPING ALONG THE SOUTH SIDE OF NEW BUILDING | | | WILL BE IN CONFLICT WITH THE PROPOSED STORM PIPES. | | | | | | 6. CONSIDER USING 45-DEGREE BEND INSTEAD OF 90-DEGREE | | | BEND AFTER THE 4" X 8" REDUCER FOR THE WATER MAIN | | | CONNECTION ON BISCAYNE DRIVE. | | | | | | 7. PROVIDE UPDATED DRAINAGE CALCULATIONS FOR PHASE 2 | | | IMPROVEMENTS. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
F |
Date |
03-27-2017 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
03-27-2017 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
03-27-2017 |
Time |
11:07 |
Sent To |
|
|
| Notes |
| 2017-03-27 11:06:56 | COMMENTS ON MARCH 23, 2017 REVIEW PACKAGE: | | | | | | 1. LANDSCAPE PLAN SHOWS TREES PROPOSED OVER OR NEAR THE | | | ON-SITE DRAINAGE SYSTEMS INCLUDING ALONG THE SOUTH AND | | | WEST PROPERTY LINES AND ALONG THE ONSITE EXFILTRATION | | | TRENCH SOUTH OF FLAMINGO DRIVE. HOW WILL THE DRAINAGE | | | SYSTEM BE PROTECTED FROM ROOT INTRUSION AND FUTURE | | | MAINTENANCE NEEDS OF THE DRAINAGE SYSTEMS? | | | | | | 2. PHASE II CONCEPTUAL PLAN SHOWS EXISTING DRAINAGE | | | (EXDN) UNDER THE PROPOSED BUILDING. IS THIS DRAINAGE TO | | | REMAIN? | | | | | | 3. LABEL THE CIRCULAR SYMBOL SHOWN TO THE WEST OF THE | | | RELOCATED CONTROL STRUCTURE ON THE CONCEPTUAL PLAN. IS | | | THIS A STORM MANHOLE? | | | | | | 4. WHAT ARE THE LONG NARROW HATCHING AREAS ON SOUTH AND | | | EAST SIDES OF PROPOSED BUILDING SHOWN ON THE CONCEPTUAL | | | PLAN SHEET? | | | | | | 5. THERE APPEARS TO BE AN EXISTING WATER MAIN ADJACENT | | | TO THE STORM PIPE BETWEEN THE RELOCATED CONTROL | | | STRUCTURE AND MANHOLE IN BISCAYNE DRIVE. THERE NEEDS TO | | | BE A MINIMUM FIVE FEET HORIZONTAL CLEARANCE BETWEEN THE | | | WATER AND STORM PIPE. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMNWATER ENGINEER | | | [email protected] | | | 561-494-1120 | | | |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
12-14-2016 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
12-14-2016 |
Time |
01:47 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
12-14-2016 |
Time |
01:48 |
Sent To |
|
|
| Notes |
| 2016-12-14 01:48:44 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | | | | 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE | | | AVAILABLE AT | | | HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?. | | | PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS | | | WILL NOT IMPACT THE PROPOSED PROJECT. | | | | | | 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION | | | INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE | | | BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD | | | HAZARD AREA. | | | | | | 3. SHOW UTILITIES ON THE LANDSCAPE PLANS. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED | | | BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE | | | MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT | | | AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY | | | AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA. | | | | | | 3. PROVIDE A COPY OF THE SFWMD ERP OR ERP MODIFICATION | | | FOR THIS PROPOSED DEVELOPMENT. | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
04-11-2017 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
04-11-2017 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2017-04-11 09:01:27 | PASSED WITH CONDITION OF REPLAT AND UTILITY EASEMENT | | | ABANDONMENT PRIOR TO C.O. |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
12-13-2016 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
12-13-2016 |
Time |
11:20 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-12-13 11:29:12 | 1. ENTIRE PROPERTY WILL NEED TO BE REPLATTED. | | | 2. EXISTING 2 FOOT UE NEEDS TO BE ABANDONED. | | | 3. ENTIRE ALLEY SHOULD BE SHOWN AS CITY-OWNED. |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
06-30-2017 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
06-30-2017 |
Time |
10:08 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
06-30-2017 |
Time |
10:08 |
Sent To |
|
|
| Notes |
| 2017-06-30 10:11:07 | CONDITIONS OF APPROVAL: | | | | | | 1.) A REPLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY (C.O.) FOR | | | THE EXPANSION. | | | | | | 2.) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT - PLANNING DIVISION. | | | | | | 3.) A SEPARATE LANDSCAPE PERMIT HALL BE REQUIRED FOR | | | ANY RELOCATION OF TREES OR PALMS ONTO OTHER PROPERTIES | | | TO ALLOW REVIEW OF LOCATIONS, RECORD FINAL LOCATIONS, | | | AND ALLOW FOR INSPECTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
05-23-2017 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
05-23-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
05-23-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-05-23 15:32:16 | GENERAL COMMENTS: | | | | | | 1.) PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT WITH | | | ANY CHANGES MADE TO THE PLANS. | | | | | | 2.) A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF THE C.O. FOR THE EXPANSION. | | | | | | 3.) CROSSWALK STRIPING ON BISCAYNE DRIVE WILL REQUIRE A | | | PERMIT FROM THE ENGINEERING SERVICES DEPARTMENT. | | | | | | | | | SITE PLAN COMMENTS: | | | | | | 1.) IS THERE AN ALTERNATIVE LOCATION FOR THE DUMPSTER | | | ENCLOSURE SHOULD IT BE REMOVED FROM THE 20 FT. UTILITY | | | EASEMENT? | | | | | | 2.) DUMPSTER DETAIL IS MISSING FROM THE REGULATING PLAN | | | (SHEET SP-2). | | | | | | 3.) BICYCLE RACK DETAIL DOES NOT MATCH THE SITE PLAN. | | | THE APPLICANT MAY ALSO WANT TO ORIENTATE THE RACK SO | | | THAT IT IS PARALLEL WITH THE STREET FOR EASE OF USE. | | | | | | 4.) BICYCLE RACK DETAIL IN THE REGULATING PLAN (SHEET | | | SP-2) DOES NOT HAVE ALL THE DIMENSIONS TO DEMONSTRATE | | | THAT THE PAD AND RACK IS CONSISTENT WITH THE CITY'S | | | BICYCLE DESIGN STANDARDS. | | | | | | 5.) THE REGULATING PLAN (SHEET SP-2) SHOWS A DETAIL FOR | | | A 6 FT. HIGH DECORATIVE FENCE; HOWEVER, THIS FENCE | | | CANNOT BE LOCATED IN THE SITE PLAN. PLEASE SHOW WHERE | | | THE FENCE IS LOCATED OR REMOVE THE DETAIL FROM THE | | | REGULATING PLAN. | | | | | | 6.) THE PROPOSED FAR IN THE SITE DATA TABULAR IS | | | INCONSISTENT WITH THE PROPOSED FAR IN THE DEVELOPMENT | | | REGULATIONS TABLE. PLEASE ADDRESS FOR CONSISTENCY (THE | | | CORRECT PROPOSED FAR IS 0.61) | | | | | | 7.) BASED ON STAFF'S CALCULATION, THE PROPOSED BUILDING | | | COVERAGE IS 46 PERCENT (WITHOUT THE 1,600 SQ. FT. | | | CANOPY). PLEASE CORRECT IN THE SITE DATA AND | | | DEVELOPMENT REGULATIONS TABLES FOR CONSISTENCY. ALSO, | | | PLEASE SHOW WHERE THE 1,600 SQ. FT. CANOPY IS LOCATED | | | IN THE SITE PLAN. | | | | | | 8.) PHOTOMETRIC PLAN STILL DOES NOT SHOW LIGHT | | | SPILLOVER BEYOND THE PROPERTY LINE. PLEASE ADDRESS. | | | | | | 9.) CLARIFY AND CORRECT IN THE REGULATING PLAN IF THE | | | DETAIL FOR THE LIGHT POLE LOCATION DETAIL (EAST PARKING | | | LOT) IS FOR THE TWO SOUTH END PARKING LOTS. | | | | | | 10.) WILL THE EXISTING GREASE TRAPS, LOCATED IN THE | | | STUDENT DROP OFF/PICK UP AREA BE REMOVED? PLEASE | | | PROVIDE ADDITIONAL INFORMATION AND/OR NOTATE IF THE | | | INTENT IS TO LEAVE THE GREASE TRAPS. | | | | | | 11.) NORTH ARROW IS MISSING FROM THE PHOTOMETRIC PLAN. | | | | | | 12.) REVISE THE HEIGHT OF THE PROPOSED BUILDING TO THE | | | TOP OF THE PARAPET WALL (LOCATED ON THE ROOFTOP OF THE | | | BUILDING). PLEASE ENSURE THE CHANGE TO THE HEIGHT IS | | | REFLECTED IN ALL PLANS. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX | | | (6) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND | | | AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT | | | CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE | | | ($200.00). | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
04-13-2017 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
04-13-2017 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
04-13-2017 |
Time |
|
Sent To |
|
|
| Notes |
| 2017-04-13 16:40:43 | GENERAL COMMENTS: | | | | | | 1.) ANY REFERENCE TO THE "ALLEY" SHOULD BE REMOVED FROM | | | THE PLANS UPON THE APPROVAL OF ORD. 4702-17 AND RESO. | | | 106-17. | | | | | | 2.) PLEASE ENSURE THAT ALL PLANS ARE CONSISTENT WITH | | | ANY CHANGES MADE TO THE PLANS. | | | | | | 3.) A RE-PLAT OF THE PROPERTY WILL BE REQUIRED PRIOR TO | | | THE ISSUANCE OF THE C.O. FOR THE EXPANSION. | | | | | | | | | SITE PLAN COMMENTS: | | | | | | 1.) REVISED COMMENT #2: RELOCATE THE DUMPSTER ENCLOSURE | | | FROM THE 20 FT. UTILITY EASEMENT ALONG THE WEST | | | PROPERTY LINE OR PROVIDE WRITTEN CONSENT FROM THE | | | UTILITY PROVIDER(S) THAT THE DUMPSTER ENCLOSURE CAN BE | | | LOCATED WITHIN THE EASEMENT. | | | | | | 2.) REVISED COMMENT #4: THE CANOPIED PRE-K PLAY AREA | | | HAS BEEN RELOCATED FROM THE PREVIOUS SUBMITTAL. IS | | | THERE STILL A 4 FT. HIGH DECORATIVE FENCE AROUND THE | | | PLAY AREA? IF SO, PLEASE ILLUSTRATE. THE PLANS INDICATE | | | THAT THERE IS NO FENCE AROUND THE PLAY AREA. | | | | | | 3.) REVISED COMMENT #6: BICYCLE RACK DETAIL STILL DOES | | | NOT MATCH THE PLANS. PLEASE ADDRESS FOR CONSISTENCY. | | | | | | 4.) REVISED COMMENT #8: PROPOSED HEIGHT OF THE BUILDING | | | IS STILL MISSING FROM THE SITE DATA TABULAR. | | | | | | 5.) CHECK CALCULATIONS FOR THE TOTAL SITE AREA AND | | | TOTAL GROSS FLOOR AREA. CALCULATIONS DO NOT SEEM TO ADD | | | UP. | | | | | | 6.) TEN (10) VISITOR PARKING SPACES ARE REQUIRED (ONLY | | | 4 VISITOR PARKING SPACES PROVIDED). [ZLDR S.94-486] | | | | | | 7.) PURSUANT TO ZLDR S.94-486 TABLE XV-6, THE MINIMUM | | | NUMBER OF PARKING SPACES REQUIRED FOR THE USE IS 34 | | | PARKING SPACES (1 SPACE/STAFF MEMBER + 10 GUEST PARKING | | | SPACES). THE PROJECT DOES NOT MEET THE MINIMUM PARKING | | | REQUIREMENT FOR THE PROJECT. PLEASE ADDRESS. | | | | | | 8.) PROVIDE DETAIL (I.E. HEIGHT) ON THE PROPOSED | | | TRELLIS. | | | | | | 9.) THERE SEEMS TO BE AN OUTDOOR KITCHEN INCLUDED IN | | | THE LATEST SUBMITTAL. PLEASE PROVIDE ADDITIONAL | | | INFORMATION AND DETAILS ON THE PROPOSED OUTDOOR | | | KITCHEN. | | | | | | 10.) SHOW LIGHT SPILLOVER JUST BEYOND THE PROPERTY LINE | | | IN THE PHOTOMETRIC PLAN. | | | | | | | | | ARCHITECTURAL PLANS (FLOOR PLAN AND ELEVATIONS) | | | | | | 1.) CHECK THE BUILDING HEIGHT PROVIDED IN THE | | | ELEVATIONS. INCLUDE THE HEIGHT OF THE ROOFTOP WALL. THE | | | ELEVATIONS SEEM TO INDICATE THAT THE BUILDING IS | | | APPROXIMATELY 133 FT. TALL? PLEASE CLARIFY. | | | | | | 2.) FINAL ARCHITECTURAL PLANS SHALL BE DESIGNED, DATED | | | AND SEALED BY A FLORIDA REGISTERED ARCHITECT. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF SIX | | | (6) PAPER COPIES, ONE (1) REDUCED COPY IN 8.5 INCHES X | | | 11 INCHES AND ONE (1) SET IN 11 INCHES X 17 INCHES, AND | | | AN ELECTRONIC COPY OF ALL PLANS. PLEASE NOTE THAT | | | CHANGES ON THE RESUBMITTED PLANS MAY RESULT IN | | | ADDITIONAL COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ASSESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20 PERCENT OF THE ORIGINAL APPLICATION FEE | | | ($200.00). | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
12-09-2016 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
12-09-2016 |
Time |
09:49 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
12-09-2016 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2016-12-09 09:56:44 | GENERAL COMMENTS: | | | | | | 1.) THE PROPOSED EXPANSION IS CONTINGENT ON THE | | | APPROVAL OF THE ALLEYWAY ABANDONMENT BETWEEN FLAMINGO | | | DRIVE AND BISCAYNE DRIVE. THE APPLICATION FOR THE | | | ABANDONMENT IS CURRENTLY PENDING WITH THE PLANNING | | | DIVISION (REFERENCE CASE NO. PB 1720). | | | | | | | | | SITE PLAN COMMENTS: | | | | | | 1.) THE PROPOSED PLAN NOW SHOWS TANDEM PARKING IN THE | | | SOUTHWEST PARKING LOT. TANDEM PARKING IS NOT PERMITTED | | | OUTSIDE THE DOWNTOWN MASTER PLAN (DMP) AREA. PLEASE | | | ADDRESS. | | | | | | 2.) SHOW THE 10 FT. WIDE FPL UTILITY EASEMENT IN THE | | | PLAN. | | | | | | 3.) WHERE ARE THE A/C UNITS LOCATED? IF LOCATED ON THE | | | GROUND LEVEL, THE A/C UNITS WILL NEED TO COMPLY WITH | | | THE SETBACK REQUIREMENTS OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDRS). COMPLETE SCREENING OF | | | THE EQUIPMENT WILL NEED TO BE PROVIDED IF THE UNITS ARE | | | LOCATED ON THE ROOFTOP OF THE BUILDING (I.E. USE OF | | | PARAPETS TO SCREEN THE A/C UNITS FROM VIEW). | | | | | | 4.) CLEARLY SHOW THE LOCATION OF THE PROPOSED 4 FT. | | | HIGH DECORATIVE FENCE AROUND THE PRE-K CANOPIED PLAY | | | AREA. IT IS NOT CLEAR TO HOW FAR THE FENCE EXTENDS. | | | | | | 5.) RELOCATE THE BICYCLE PARKING TO A MORE VISIBLE, | | | EASILY ACCESSIBLE LOCATION ON THE SCHOOL SITE (I.E. | | | NEAR THE ENTRANCE ON FLAMINGO DRIVE IN THE DROP-OFF AND | | | PICK-UP AREA). | | | | | | 6.) THE BICYCLE RACK DETAIL ON SHEET SP-2 SHOWS A HEDGE | | | AROUND THE PAD; HOWEVER, THIS IS NOT ILLUSTRATED IN THE | | | LANDSCAPE PLAN. THE DETAIL MUST MATCH ALL PLANS. PLEASE | | | ADDRESS. | | | | | | 7.) THE TWO (2) ACCESSIBLE PARKING SPACES LOCATED NEXT | | | TO THE DUMPSTER ENCLOSURE SHALL BE RELOCATED CLOSER TO | | | THE ENTRANCE OF THE SCHOOL BUILDING. [ZLDR S.94-485(O)] | | | | | | 8.) PLEASE MAKE THE FOLLOWING CORRECTIONS TO THE SITE | | | DATA TABULAR: PROJECT NO.: ISPR 16-01B/Z16110015; | | | BUILDING HEIGHT (MAX. 50'): PLEASE PROVIDE THE OVERALL | | | HEIGHT OF THE SCHOOL STRUCTURE; BICYCLE PARKING | | | PROPOSED: 2 (NOT 6 ACCORDING TO THE SITE PLAN) | | | | | | 9.) PLEASE MAKE THE FOLLOWING CORRECTIONS IN THE | | | DEVELOPMENT REGULATIONS TABULAR: MINIMUM OPEN SPACE | | | REQUIREMENT IS 40% (NOT 32%) | | | | | | 10.) REVIEW THE PARKING COUNT FOR THE PROJECT. THE | | | PARKING PROVIDED IN THE SITE DATA TABULAR DOES NOT | | | MATCH THE NUMBER OF PARKING SPACES PROVIDED IN THE SITE | | | PLAN. | | | | | | | | | ARCHITECTURAL PLANS (FLOOR PLAN AND ELEVATIONS): | | | | | | 1.) CONSIDER ADDING ARCHITECTURAL ELEMENTS ON THE | | | BUILDING FACADES TO BREAK UP THE BLANK WALLS. | | | | | | 2.) PLEASE PROVIDE COLORED ELEVATIONS. | | | | | | 3.) FINAL ARCHITECTURAL PLANS SHALL BE SIGNED, DATED | | | AND SEALED BY A FLORIDA LICENSED ARCHITECT. | | | | | | | | | LIGHTING/PHOTOMETRICS: | | | | | | 1.) PROVIDE AN UPDATED PHOTOMETRIC PLAN FOR THE | | | PROJECT. | | | | | | 2.) HOW TALL ARE THE PARKING LOT LIGHT FIXTURES? | | | PROVIDE A DETAIL. | | | | | | | | | INSTRUCTIONS FOR RESUBMITTAL: | | | | | | * PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | * WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF TEN | | | (10) COPIES, ONE (1) REDUCED COPY (8.5 BY 11), AND AN | | | ELECTRONIC COPY IN .PNG FORMAT OF ALL PLANS. PLEASE | | | NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO ADDITIONAL | | | COMMENTS. | | | | | | * PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% ($200) OF THE ORIGINAL APPLICATION FEE. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. |
|
|
| |
Print |
|