2016-12-14 10:32:58DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 3. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 5. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 6. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status P Date 01-17-2017 Cont ID  
Sent By mkhan Date 01-17-2017 Time 16:30 Rev Time 0.00
Received By mkhan Date 01-17-2017 Time 16:31 Sent To  
Notes
2017-01-17 16:32:58CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: HOME DEPOT CPD - 1560 PALM BEACH LAKES
 BLVD. - Z16110014
  
 2ND REVIEW RESPONSE: PASSED WITH CONDITION
  
 DATE: JANUARY 17, 2017
  
 AFTER A REVIEWING THE REVISED PLANS AND THE RESPONSES
 TO THE PREVIOUS PPRC COMMENTS (RECEIVED ON 12/15/2016),
 IT APPEARS THAT SOME OF THE COMMENTS HAVE BEEN
 ACKNOWLEDGED. HOWEVER, THESE ACKNOWLEDGED COMMENTS
 ALONG WITH THE FOLLOWING ITEMS (CRITICAL UTILITY ITEMS)
 ARE EXPECTED TO BE ADDRESSED DURING 'ENGINEERING
 DEVELOPMENT APPLICATION' PHASE PRIOR TO ISSUANCE OF
 CONSTRUCTION AUTHORIZATION INCLUDING BUILDING PERMITS
 AND ENGINEERING DEVELOPMENT APPROVAL:
  
 5. ANGLE THE DUMPSTERS MORE SO THAT GARBAGE TRUCKS CAN
 PULL UP STRAIGHT. ALSO THERE ARE LOW HANGING OVERHEAD
 CABLE LINES BETWEEN THE POLES AT THE LOCATION OF THE
 PROPOSED DUMPSTERS. CITY?S FRONT LOADING DUMP TRUCKS
 NEEDS TO HAVE NO LESS THAN 14' HIGH VERTICAL CLEARANCE
 AND 12' HORIZONTAL CLEARANCES FOR THE TRUCK TO DRIVE
 THROUGH. PLEASE VERIFY THE CLEARANCES;
  
 6. CITY'S STANDARD DETAIL FOR DUMPSTER ENCLOSURE SHOWN
 ON SHEET C5.10 (NOT ON MSP-2). ON SHEET C4.00 SHOW
 DUMPSTER ENCLOSURE DIMENSION INSTEAD OF PAD DIMENSION;
  
 10. PROPOSED 4-INCH FIRE LINE TO THE BUILDING IS SHOWN
 TO BE COMING FROM THE EXISTING 10-INCH WATER MAIN TO
 THE EAST SIDE OF THE UNIT A-2 (RESTAURANT). THIS IS A
 PRIVATE FIRE LINE AND FROM. LIKE THE 2-INCH DOMESTIC
 WATER CONNECTIONS FOR EACH UNIT, FIRE LINE FOR THE
 BUILDING NEED TO BE CHANGED TO SHOW FEEDING OFF THE
 20-INCH WATER MAIN LOCATED ON PALM BEACH LAKES
 RIGHT-OF-WAY. AT THE NEXT STAGE I.E. DETAIL ENGINEERING
 DESIGN PLANS SHOULD SHOW THE CHANGE;
  
 16. PROPOSED 4-INCH SANITARY SERVICE TO THE SITE IS
 SHOWING TO HAVE CONFLICT WITH EXISTING WATER LINE TO
 THE WESTERN BOUNDARY OF THE LOT. AT THE NEXT STAGE I.E.
 DETAIL ENGINEERING DESIGN PLANS SHOULD SHOW THE CHANGE;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1124 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 12-12-2016 Cont ID  
Sent By mkhan Date 12-12-2016 Time 20:35 Rev Time 0.00
Received By mkhan Date 12-12-2016 Time 09:05 Sent To  
Notes
2016-12-11 20:38:21CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 DATE: 12/12/2016
  
 Z16110014: 1560 PALM BEACH LAKES BLVD. - HOME DEPOT CPD
  
 THIS IS AN INITIAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS, AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES.
  
 THE FOLLOWING GENERAL COMMENTS MUST BE ADDRESSED PRIOR
 TO ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. PLEASE SUBMIT THE LATEST VERSION OF THE 'AUTO-CALC
 CERTIFIED COST ESTIMATE FORM' FOR SUBMISSION TO CITY OF
 WEST PALM BEACH PUBLIC WORKS DEPARTMENT. THIS FORM CAN
 BE DOWNLOADED FROM THE FOLLOWING LINK:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 3. SOLID WASTE YARDAGE CALCULATION WILL NEED TO BE
 SUBMITTED AS PART OF THE FINAL DESIGN TO VERIFY THAT
 THE DESIGN INCLUDES APPROPRIATE NUMBER AND SIZE OF
 DUMPSTERS/GARBAGE RECEPTACLES. PLEASE SHOW ON THE PLAN
 IF A COMPACTOR IS PROPOSED TO REDUCE THE YARDAGE OF
 WASTE THAT WILL NEED TO BE COLLECTED;
  
 4. PROVIDE STATEMENT OR DOCUMENTATION THAT THE PROPOSED
 SANITATION FACILITY/DUMPSTER CAN BE PLACED AND ACCESSED
 AT THE SPECIFIED LOCATION AS SHOWN ON THE PLANS;
  
 5. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A
 ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER
 FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN
 PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE
 PLANS;
  
 6. PLEASE INCLUDE THE CITY OF WEST PALM BEACH STANDARD
 DETAIL FOR THE DUMPSTER ENCLOSURE ON THE PLANS. MINIMUM
 DIMENSIONAL (E.G. THE GATE WIDTH MUST BE A MINIMUM OF
 12.5 FEET) REQUIREMENTS FOR THE ENCLOSURE ARE LISTED IN
 CODE OF ORDINANCES, SECTION 94-444(B) OF THE CODE OF
 ORDINANCES. CITY STANDARD DETAIL GC-8 MAY BE DOWNLOADED
 AT:
  
 HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE
 RING-STANDARDS/
  
 7. IF ROLL OUT TYPE DUMPSTER IS PROPOSED, PLEASE NOTE
 ON THE PLANS THAT: 'OWNER IS RESPONSIBLE TO ROLL OUT
 THE DUMPSTER OUTSIDE THE ENCLOSURE PRIOR TO CITY'S
 SANITATION CREW PICK UP GARBAGE'.
  
 THE FOLLOWING WATER AND SEWER COMMENTS:
  
 8. SUBMIT WITH THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION SIGNED & SEALED ENGINEER/MEP WATER AND
 SANITARY SEWER CALCULATION (AVERAGE AND PEAK WITH
 PEAKING FACTOR). SUBMIT CALCULATIONS TO VALIDATE METER
 SIZE SELECTION. SHOW THESE CALCULATIONS ON THE UTILITY
 PLAN SHEET AS WELL;
  
 9. FIRE HYDRANT FLOW TEST DATA FROM EXISTING FIRE
 HYDRANT WILL BE REQUIRED PART OF THE PLAN SUBMITTAL;
  
 10. PROPOSED WATER CONNECTION TO THE RESTAURANT 'A-2'
 IS SHOWN ON THE UTILITY PLAN TO BE FROM A PRIVATE FIRE
 LINE. WATER SERVICE IS AVAILABLE FROM PALM BEACH LAKES
 BLVD;
  
 11. PROPOSED WATER CONNECTION TO THE RETAIL SPACE 'A-1'
 IS SHOWN ON THE UTILITY PLAN TO BE FROM A WATERLINE
 THAT IS DEDICATED TO THE ADJACENT BUSINESS. WATER
 SERVICE IS AVAILABLE FROM PALM BEACH LAKES BLVD;
  
 12. PLEASE NOTE ON THE PLAN THAT ?WATERLINE THAT HAS
 NOT BEEN USED FOR A WHILE SHALL REQUIRE BAC-T TESTING
 PRIOR TO CONNECTION FOR NEW SERVICE?;
  
 13. SHOW ON THE PLANS LOCATION OF FIRE DEPARTMENT
 CONNECTIONS (FDC). PROPOSED FIRE DEPARTMENT CONNECTION
 SHALL BE WITHIN 150 FEET OF A FIRE HYDRANT AND SHALL BE
 WITHIN AN EASEMENT WITHIN THE PROPERTY;
  
 14. PLEASE INCLUDE THE LATEST VERSION OF THE APPLICABLE
 CITY OF WEST PALM BEACH STANDARD UTILITY DETAILS TO THE
 DETAILS SHEET. CONTACT THE ENGINEERING SERVICES
 DEPARTMENT FOR THE LATEST REVISED DETAILS IN CAD
 FORMAT. CITY'S STANDARD DETAILS (IN PDF FILE FORMAT)
 CAN BE DOWNLOADED FROM THE FOLLOWING SITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 15. PLACEMENT OF THE PROPOSED METER, BACKFLOW
 PREVENTER, DCDA ETC. SHALL BE INSTALLED PER THE CITY'S
 STANDARD DETAILS. WATER METER SHOULD BE INSIDE AN
 'UTILITY EASEMENT' JUST INSIDE THE PROPERTY NEAR THE
 RIGHT-OF-WAY AND ACCESSIBLE;
  
 16. SHOW CONFLICT INFORMATION (BOTTOM AND TOP OF
 CROSSING PIPES) AT THE CONFLICT POINTS OF ALL WATER,
 STORM AND SANITARY SEWER PIPES AS WELL AS OTHER
 FRANCHISE UTILITIES;
  
 17. THERE IS AN EXISTING SANITARY SEWER LATERAL STUB
 (LOCATED JUST NORTH OF THE EXISTING SANITARY MANHOLE)
 AVAILABLE NEAR THE NORTHWEST PROPERTY CORNER. IS THERE
 A REASON WHY PROPOSED SANITARY SEWER SERVICE CONNECTION
 IS NOT UTILIZING THIS EXISTING SUB?
  
 18. SHOW DIRECTION OF FLOW FOR THE EXISTING SANITARY
 SEWER. INCLUDE A PROFILE FOR PROPOSED SERVICE LATERAL
 WITH GROUND ELEVATIONS ABOVE THE PIPE;
  
 19. CCTV RECORD (VIDEO AND TV LOG) OF THE EXISTING
 SANITARY SEWER (FULL LENGTH FROM MH TO MH) AND NEW
 SANITARY SEWER LATERAL WILL BE REQUIRED AS PART OF THE
 PROJECT CLOSE-OUT SUBMITTALS;
  
 20. PAVEMENT RESTORATION WILL BE REQUIRED FOR PROPOSED
 WATER AND SEWER CONNECTION IF PERFORMED WITHIN CITY'S
 RIGHT-OF-WAY AND SHALL BE SHOWN ON THE UTILITY PLAN.
 REFER TO THE CITY'S LATEST STANDARD DETAIL FOR THE
 PAVEMENT RESTORATION GUIDELINES;
  
 21. EXISTING WATER SERVICE CONNECTIONS/WATER METERS
 SERVING THE PROPERTY, IF NOT USED, ARE TO BE CUT AND
 CAPPED AT THE MAIN. DE-ACTIVATED/INACTIVE PIPELINES
 LARGER THAN 2" DIAMETER WILL BE REMOVED. PLEASE LABEL
 PIPE SIZE AND MATERIAL AND ADD NOTES TO THE UTILITY
 PLANS ACCORDINGLY;
  
 22. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES
 MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 23. LANDSCAPE PLAN SHALL SHOW LOCATIONS OF ALL WATER
 METERS, VALVES, CLEAN-OUTS, LIGHT POLES, ETC. ROOT
 BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE NEAR
 UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER
 LINES.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1024 (OFFICE)
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 01-24-2017 Cont ID  
Sent By pleduc Date 01-24-2017 Time   Rev Time 0.00
Received By pleduc Date 01-24-2017 Time 08:12 Sent To  
Notes
2017-01-24 08:35:142ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE LETTER DATED
 DECEMBER 15, 2016, AND ASSOCIATED FILES FROM KIMBERLY
 HORN SUBMITTED TO JOHN P. ROACH, PRINCIPAL PLANNER, THE
 PREVIOUSLY SUBMITTED FIRE PREVENTION BUREAU COMMENTS
 HAVE BEEN ADDRESSED.
  
 THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT DOES
 NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 12-09-2016 Cont ID  
Sent By pleduc Date 12-09-2016 Time   Rev Time 0.00
Received By pleduc Date 12-09-2016 Time 08:37 Sent To  
Notes
2016-12-09 08:47:30THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER
 PROTECTION.
  
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
  
 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM
 ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION.
 ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND
 AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT
 WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
  
 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
  
 6. FOR PLAN REVIEW SUBMITTAL, PLEASE INCLUDE THE
 OCCUPANCY TYPE, PER THE FLORIDA FIRE PREVENTION CODE,
 AND WHETHER IT IS MIXED OR SEPARATED OCCUPANCY.
  
  
 7. FOR PLAN REVIEW SUBMITTAL, PLEASE ENSURE THAT A FIRE
 LOAD CALCULATION IS INCLUDED AND THAT ADEQUATE WATER
 SUPPLY IS EXISTING OR WILL BE PROVIDED.
  
  
 8. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
 ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE
 BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND
 FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET
 OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER
 ARRIVING EMERGENCY VEHICLES.
  
  
 9. PROVIDE FOR A FIRE SPRINKLER AND/OR FIRE ALARM PER
 THE APPLICABLE OCCUPANCY CODE. FOR ANY LIFE SAFETY
 ENGINEERED SYSTEM, I.E FIRE SPRINKLER AND FIRE ALARM,
 ENSURE THEY COMPLY WITH THE REQUIREMENTS OF FS 61G AND
 SUBMITTED WITH THE MASTER PLAN.
  
  
 10. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 11. PER FLORIDA 69A-60.0081; NOTICE SIGNAGE IS REQUIRED
 FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
  
  
 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 01-13-2017 Cont ID  
Sent By rcaranci Date 01-13-2017 Time 16:03 Rev Time 0.00
Received By rcaranci Date 01-13-2017 Time 16:03 Sent To  
Notes
2017-01-13 16:04:11FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: HOME DEPOT CPD MAJOR Z16110014
 JANUARY 13, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. SATISFIED. PLEASE ADD THE REQUIRED TERMINAL
 LANDSCAPE ISLAND AND TREE AT THE END OF THE ROW OF
 PARKING ADJACENT TO THE SEATING AREA.
  
 2. NOT SATISFIED. PLEASE SHOW LOCATIONS OF ROOT
 BARRIERS TO PROTECT INFRASTRUCTURE AND TREES FROM
 CONFLICTS. THIS INCLUDES WATER, SEWER, DRAINAGE,
 SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES THAT
 COULD BE IMPACTED BY TREE ROOTS.
  
 THREE MONTGOMERY PALMS ARE SHOWN DIRECTLY ON TOP OF
 WATER SERVICE ON THE FRONT OF THE BUILDING. ONE
 MONTGOMERY PALM BETWEEN THE PATIO AND LOADING ZONE IS
 SHOWN CLOSE TO THE SEWER LINE. PLEASE REVISE TO ADJUST
 LOCATIONS TO AVOID CONFLICTS AND ADD ROOT BARRIER WHERE
 NEEDED.
  
 3. SATISFIED. THERE APPEARS TO BE A MISSING ROYAL PALM
 IN THE RIGHT OF WAY ADJACENT TO THE FRONT OF THE NEW
 BUILDING THAT MUST BE REPLACED.
  
 4. NOT SATISFIED. ALL MISSING LANDSCAPING, PARTICULARLY
 REQUIRED TREES MUST BE REPLACED, AND ANY CHANGE IN
 SPECIES MAY BE ESTABLISHED AT THIS TIME.
  
 PLEASE REVISE THE PLAN SHEET MSP-3 TO SHOW REQUIRED
 TREES FOR THE LANDSCAPE ISLANDS IMMEDIATELY ADJACENT TO
 THE PROPOSED PARKING AREA. THE TREES SHOULD ALSO BE
 SHADOWED IN ON L1.00.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 12-12-2016 Cont ID  
Sent By rcaranci Date 12-12-2016 Time 17:31 Rev Time 0.00
Received By rcaranci Date 12-12-2016 Time 17:31 Sent To  
Notes
2016-12-12 17:32:09FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462
 PROJECT: HOME DEPOT CPD MAJOR Z16110014
 DECEMBER 12, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
  
 1. PLEASE ADD THE REQUIRED TERMINAL LANDSCAPE ISLAND
 AND TREE AT THE END OF THE ROW OF PARKING ADJACENT TO
 THE SEATING AREA.
  
 2. PLEASE SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 3. THERE APPEARS TO BE A MISSING ROYAL PALM IN THE
 RIGHT OF WAY ADJACENT TO THE FRONT OF THE NEW BUILDING
 THAT MUST BE REPLACED.
  
 4. ALL MISSING LANDSCAPING, PARTICULARLY REQUIRED TREES
 MUST BE REPLACED, AND ANY CHANGE IN SPECIES MAY BE
 ESTABLISHED AT THIS TIME.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 12-14-2016 Cont ID  
Sent By tward Date 12-14-2016 Time 01:18 Rev Time 0.00
Received By tward Date 12-14-2016 Time 01:45 Sent To  
Notes
2016-12-14 01:45:48THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION
 INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD
 HAZARD AREA.
  
 3. THE PLANS SHOW AN EXISTING DRAINAGE PIPE HEADING IN
 THE NW DIRECTION OUT OF THE PARKING LOT CATCH BASIN.
 SHOW WHERE THE PIPE ENDS.
  
 4. CHECK THE GRADING OF THE INTERFACES BETWEEN NEW AND
 EXISTING PARKING LOT DRIVE AISLES. THERE APPEARS TO BE
 AN EXISTING SPOT GRADE FOR THE EASTERN DRIVE AISLE THAT
 DOES NOT AGREE WITH THE PROPOSED M.E. ELEVATION.
  
 5. IDENTIFY THE ENTITY RESPONSIBLE TO MAINTAIN THE
 ONSITE AND MASTER DRAINAGE SYSTEMS.
  
 6. THE PROFILE OF THE EXISTING SIDEWALK ALONG THE SOUTH
 RIGHT-OF-WAY OF PALM BEACH LAKES BLVD MAY NEED TO BE
 REVISED. AT THE EAST END, THE EXISTING SIDEWALK IS
 HIGHER THAN THE PROPOSED FFE ELEVATION OF THE BUILDING.
 AT THE WEST END, THE SLOPE OF THE SIDEWALK CONNECTIONS
 BETWEEN THE PROPOSED BUILDING AND EXISTING SIDEWALK
 WILL EXCEED ADA CRITERIA. NOTE PALM BEACH LAKES BLVD IS
 MAINTAINED BY PALM BEACH COUNTY.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE
 MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT
 AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY
 AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 12-13-2016 Cont ID  
Sent By vnoel Date 12-13-2016 Time 11:00 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2016-12-13 11:15:481. CROSS ACCESS/UTILITY/DRAINAGE AGREEMENT WILL BE
 REQUIRED. ALSO FOR OFF-SITE DUMPSTERS.
 2. UTILITY DEPT. WILL ADDRESS CONNECTION POINTS FOR
 WATER AND SEWER.
 3. AS PARCEL WAS REPLATTED, 6 FOOT UE FROM PREVIOUS
 PLAT MAY NOT NEED TO BE ABANDONED.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 12-14-2016 Cont ID  
Sent By jroach Date 12-14-2016 Time 11:40 Rev Time 0.00
Received By jroach Date 12-14-2016 Time 11:40 Sent To  
Notes
2016-12-14 11:41:10PLANS AND PLATS REVIEW COMMITTEE (PPRC) ZONING REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 12.14.2016
 PROJECT NO.: Z16110014
 CASE NO.: PB1171KK
 ADDRESS: 1560 PALM BEACH LAKES BOULEVARD
 APPLICANT/CONTACT: MARK RICKARDS
 TELEPHONE NO.: 561.404.7244
 SCOPE OF REVIEW: NEW RETAIL/RESTAURANT
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS:
  
 1. IMPERVIOUS SURFACE AREA SHALL NOT EXCEED 85%.
 PERVIOUS/LANDSCAPE AREA SHALL BE AT LEAST 15%.
  
 2. PARKING FOR RESTAURANTS SHALL BE CALCULATED AT 1
 SPACE PER 100 SQUARE FEET (OUTDOOR SEATING SHALL BE
 INCLUDED IN THIS CALCULATION).
  
 3. IT WAS SUGGESTED AT AN INTERNAL STAFF MEETING THAT
 AN OPTION BE EXPLORED OF PUTTING THE OUTDOOR PATIO ON
 THE NORTH SIDE OF THE BUILDING (ALONG PALM BEACH LAKES
 BLVD).
  
 4. THERE SHALL BE A LANDSCAPE ISLAND OF AT LEAST FIVE
 (5) FEET IN WIDTH NORTH OF THE LOADING ZONE.
  
 5. THE FIVE (5) ROWS OF PARKING THAT ARE SHOWN WITHOUT
 WHEEL STOPS SHOULD CONSIST OF 16 FEET OF ASPHALT (NOT
 18 FEET), AS THE TWO (2) FOOT OVERHANG WILL OCCUR FROM
 THE INTO THE LANDSCAPE AREA.
  
 6. PHOTOMETRIC PLAN SHALL BE PROVIDED. PHOTOMETRIC
 LEVELS SHALL NOT EXCEED 1.0 FOOTCANDLES AT THE PROPERTY
 LINE.
  
 7. PARKING STALL STRIPING DETAIL SHALL CONFORM TO THE
 CITY?S MINIMUM STANDARDS. CONTACT ME FOR A DIGITAL COPY
 OF THE DETAIL.
  
 8. OVERHANGS PROPOSED SHALL BE SHOWN AND DIMENSIONED ON
 THE SITE PLAN. OVERHANGS SHALL NOT ENCROACH MORE THAN
 THREE (3) FEET INTO THE REQUIRED SETBACK.
  
 9. FREESTANDING SIGNS DO NOT CONFORM TO THE MINIMUM
 SETBACK REQUIREMENTS FROM THE INTERNAL LOT LINES, ARE
 LOCATED IN THE VISIBILITY TRIANGLES OF THE ACCESS
 DRIVES, AND DON?T SEEM TO BE EFFECTIVE IN THEIR
 PROPOSED LOCATIONS.
  
 10. UPDATED MASTER LANDSCAPE PLAN SHALL BE PROVIDED.
  
 11. PARKING SPACES ARE ONLY REQUIRED TO BE 8.5 FEET IN
 WIDTH; THE PROPOSED STRIPING MAY BE ADJUSTED
 ACCORDINGLY.
  
 12. PLEASE DIMENSION THE BUILDING HEIGHTS ON THE
 ELEVATIONS. BUILDING HEIGHT SHOULD BE FROM GRADE TO THE
 ROOF DECK OF THE FLAT ROOF. ADDITIONAL DIMENSIONS
 SHOULD BE SHOWN FOR THE PARAPET.
  
 13. ADDITIONAL GLAZING NEEDS TO BE PROVIDED AT ON THE
 EAST AND WEST ELEVATIONS, AT THE NORTHERN CORNERS OF
 THE BUILDING.
 ___________________________________________
  
 PLEASE NOTE THE FOLLOWING WHEN RESUBMITTING:
  
 A) WRITTEN RESPONSES TO COMMENTS MADE BY ALL
 DEPARTMENTS SHALL BE PROVIDED UPON RESUBMISSION.
  
 B) 15 SETS OF REVISED PLANS AND/OR DOCUMENTS SHALL BE
 PROVIDED, ALONG WITH ONE (1) REDUCED COPY (11IN X
 17IN), AND AN ELECTRONIC COPY OF ALL PLANS.
  
 C) PLEASE NOTE THAT RE-SUBMITTALS MAY BE SUBJECT TO
 ADDITIONAL COMMENTS.
  
 D) IF NO RESPONSE IS RECEIVED WITHIN 60 DAYS OF THE
 ISSUANCE OF THESE COMMENTS, THE APPLICATION WILL BE
 CONSIDERED WITHDRAWN AND ANY FURTHER ACTION WILL
 REQUIRE SUBMISSION OF A NEW DEVELOPMENT APPLICATION.
  
 E) PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE.
  
 F) IN ORDER TO BE CONSIDERED FOR THE FEBRUARY 22, 2017,
 PLANNING BOARD AGENDA, ALL COMMENTS SHALL BE
 SATISFACTORILY ADDRESSED. PLEASE SUBMIT ALL REVISED
 DOCUMENTS/PLANS NO LATER THAN FRIDAY, DECEMBER 30,
 2016.
  
 G) TO BE PLACED ON THE FEBRUARY 22, 2017, PLANNING
 BOARD AGENDA, SIGNS SHALL BE POSTED ON THE PROPERTY NO
 LATER THAN FEBRUARY 7, 2017. SIGNAGE SHALL CONFORM AND
 BE INSTALLED WITH THE REQUIREMENTS OF THE CITY?S ZONING
 AND LAND DEVELOPMENT REGULATIONS, AS ALSO PROVIDED IN
 THE DEVELOPMENT APPLICATION. A SIGNED AND NOTARIZED
 AFFIDAVIT SHALL BE PROVIDED BY THE DEADLINE REFERENCED
 ABOVE.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN P. ROACH, AICP, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 P: 561.822.1448
 F: 561.822.1460
  
 E: [email protected]
  
 W: WPB.ORG
  

  Print


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved