Plan Review Details - Project Z16100012
Plan Review Stops For Project Z16100012
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 11-08-2016 Cont ID  
Sent By rbrown Date 11-08-2016 Time 19:31 Rev Time 0.00
Received By rbrown Date 11-08-2016 Time 19:31 Sent To  
Notes
2016-11-08 19:38:25DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION,
 COMMENTS:
  
 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE
 SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH
 FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE
 ADDRESSED FOR PERMITTING.
  
 2. ACCESSIBLE PARKING SPACES. SHEET SP-1 SHOWS REGULAR
 PARKING SPACES WHICH ARE CLOSER THAN THE ACCESS PARKING
 SPACES TO THE ENTRANCE OF BUILDINGS A, B, C, AND D. PER
 SECTION 208.3 OF FLORIDA ACCESSIBILITY CODE, ACCESSIBLE
 PARKING SPACES ARE TO BE LOCATED ON THE SHORTEST
 POSSIBLE ROUTE OF TRAVEL FROM ADJACENT PARKING TO AN
 ACCESSIBLE ENTRANCE FOR EACH BUILDING. THE DESIGN OF
 ACCESSIBLE PARKING SPACES SHALL COMPLY WITH SECTION 502
 OF FLORIDA ACCESSIBILITY CODE
  
 3. GENERAL NOTES ON SHEET SP-6 MAKE NUMEROUS REFERENCES
 TO CITY OF LAKE WORTH. THE CORRECT MUNICPALITY NAME IS
 CITY OF WEST PALM BEACH.
  
 4. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL
 SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS
 WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND
 OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA
 BUILDING CODE
  
 5. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH
 ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND
 OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF
 THE FLORIDA BUILDING CODE SHALL BE VERIFIED.
  
 6. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS
 AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE
 WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED
 FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS,
 GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND
 OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS,
 SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC.
  
 7. EACH SEPARATE BUILDING SHALL HAVE A SEPARATE
 ADDRESS. FOR STREET ADDRESSING, CONTACT MICHAEL ORIO,
 GIS SUPPORT SPECIALIST, AT (561) 494 1080, OR BY EMAIL:
 [email protected]
  
 8. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES
 (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF
 PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT
 SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT
 (561) 822-1521, OR BY EMAIL: [email protected]
  
 ROBERT BROWN
 BUILDING OFFICIAL
 TEL: 561 805 6652
 EMAIL: [email protected]
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 3 Status P Date 03-09-2017 Cont ID  
Sent By mkhan Date 03-09-2017 Time 13:33 Rev Time 0.00
Received By mkhan Date 01-24-2017 Time 08:34 Sent To  
Notes
2017-03-09 16:34:54CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: VILLAGE OF MANGONIA LAKES - Z16100012
  
 DATE: MARCH 09, 2017
  
 3RD REVIEW RESPONSE: PASSED WITH CONDITION (SEE BELOW):
  
 THIRD SUBMITTALS HAVE BEEN RECEIVED ON 02/27/2017, ALL
 PREVOUS COMMENTS THOSE HAVE BEEN ACKNOWLEDGED AND
 OTHERS THOSE HAVE NOT YET BEEN SATISFIED ARE EXPECTED
 TO BE ADDRESSED DURING 'ENGINEERING DEVELOPMENT
 APPLICATION' PHASE PRIOR TO ISSUANCE OF CONSTRUCTION
 AUTHORIZATION INCLUDING BUILDING PERMITS AND
 ENGINEERING DEVELOPMENT APPROVAL.

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 2 Status F Date 12-27-2016 Cont ID  
Sent By mkhan Date 12-22-2016 Time 08:50 Rev Time 4.00
Received By mkhan Date 12-22-2016 Time 08:49 Sent To  
Notes
2016-12-27 08:53:44CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
  
 PROJECT NAME: VILLAGE OF MANGONIA LAKES - Z16100012
 2ND REVIEW RESPONSE: PASSED WITH CONDITION
 DATE: DECEMBER 30, 2016
  
 AFTER A REVIEWING THE REVISED PLANS AND THE RESPONSES
 TO THE PREVIOUS PPRC COMMENTS (RECEIVED ON 11/30/2016),
 IT APPEARS THAT SOME OF THE COMMENTS HAVE BEEN
 ACKNOWLEDGED. HOWEVER, THESE ACKNOWLEDGED COMMENTS
 ALONG WITH THE FOLLOWING ITEMS ARE EXPECTED TO BE
 ADDRESSED DURING 'ENGINEERING DEVELOPMENT APPLICATION'
 PHASE PRIOR TO ISSUANCE OF CONSTRUCTION AUTHORIZATION
 INCLUDING BUILDING PERMITS AND ENGINEERING DEVELOPMENT
 APPROVAL:
  
 2. SUBMITTED 'TRAFFIC STUDY' IS BEING REVIEWED;
  
 3. SUBMITTED 'CONSENT OF ADJOINING PROPERTY FOR
 DRAINAGE' IS BEING REVIEWED;
  
 6. CAUTION! FROM THE SUBMITTED 'AUTOTURN ANALYSIS' I.E.
 'DUMPSTER AUTOTURN EXHIBIT' IT SEEMS LIKE THAT THE
 FRONTEND LOADER GARBAGE TRUCK MAY HAVE DIFFICULTY TO
 MANEUVER TO GET TO THE DUMPSTERS LOCATED TO THE SOUTH
 OF THE BLDG. NO. 2170 AND NEXT TO THE BLDG. 2180. MAY
 BE THEY WILL REQUIRE TO BE PLACED AT A DIFFERENT ANGLE
 WHICH MAY CAUSE TO LOSE THE PARKING SPACE/S NEXT TO
 THEM. THE DUMPSTER LOCATED JUST NORTH OF THE BLDG. NO.
 2200 (SIX-STORY) MAY NEED TO BE SHIFTED TO FURTHER
 NORTH. PLEASE REVIEW AND REVISE PLAN AS NECESSARY PRIOR
 TO SITE PLAN APPROVAL;
  
 7. SANITARY SEWER MANHOLE CALLED OUT AS 'CITY'S POINT
 OF SERVICE' IS NEITHER LOCATED WITHIN THE RIGHT-OF-WAY
 NOR AT THE PROPERTY LINE INSTEAD IT IS SHOWN TO BE
 INSIDE THE PRIVATE PROPERTY. PLEASE REVISE;
  
 8. LANDSCAPE PLAN HAS NOT BEEN REVISED TO SHOW
 LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS,
 LIGHT POLES, ETC. NOTE ON THE PLANS: 'ROOT BARRIERS MAY
 BE REQUIRED WHERE PLANTINGS ARE NEAR UNDERGROUND
 STORMWATER, SANITARY, OR POTABLE WATER LINES';
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 3. SUBMIT A COPY OF THE STORMWATER PERMIT ISSUED BY THE
 SFWMD (#50-03247) AT THE TIME OF SUBMITTING THE
 ENGINEERING DEVELOPMENT APPLICATION;
  
 5. SHOW DISTANCE TO THE CLOSEST FIRE HYDRANT ON
 AUSTRALIAN AVENUE ON THE 'WATER AND SEWER PLANS'. NOW
 IT IS SHOWN ON THE SITE PLAN ONLY;
  
 6. CALCULATIONS FOR WATER AND SANITARY SEWER DEMANDS
 (AVERAGE AND PEAK) HAVE BEEN PROVIDED BUT MORE DETAILED
 INFORMATION IS NEEDED WITH THE FINAL PLANS. WHILE
 SUBMITTING THE ?ENGINEERING DEVELOPMENT APPLICATION?,
 SUBMIT SIGNED & SEALED ENGINEER/MEP WATER CALCULATIONS
 (AVERAGE AND PEAK) WITH PEAKING FACTOR TO VALIDATE
 METER SIZING/SELECTION AND SERVICE SIZING. SHOW THESE
 CALCULATIONS ON THE PLAN SHEET AS WELL;
  
 10. DIRECTION OF FLOW FOR THE EXISTING SANITARY SEWER
 IS NOT SHOWN ON THE REVISED WATER AND SEWER PLANS;
  
 11. RIGHT-OF-WAY LINES ARE NOT SHOWN OR LABELED ON THE
 REVISED WATER AND SEWER PLANS;
  
 12. PROPOSED MANHOLE SHOWN AS THE ?CITY'S
 POINT-OF-SERVICE? FOR SANITARY SEWER IS INSIDE THE
 PROPERTY NOT WITHIN THE WITHIN THE RIGHT-OF-WAY. ALSO
 ALL PROPOSED ONSITE SANITARY SERVICE NEED TO BE SHOWN
 AS PRIVATE;
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1024 (OFFICE)
  

Review Stop ENG - PPRC ENGINEERING - PPRC
Rev No 1 Status F Date 11-07-2016 Cont ID  
Sent By mkhan Date 11-07-2016 Time 10:23 Rev Time 4.00
Received By mkhan Date 11-07-2016 Time 10:22 Sent To  
Notes
2016-11-07 10:26:19CITY OF WEST PALM BEACH
 PUBLIC WORKS DEPARTMENT
 ENGINEERING DIVISION
  
 THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT:
  
 HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PALM BEACH COUNTY APPROVAL OF THE PROPOSED DRIVEWAYS
 WILL BE REQUIRED PRIOR TO FINAL SITE PLAN APPROVAL;
  
 2. A TRAFFIC STUDY WILL BE REQUIRED FOR THIS PROJECT
 SHOWING HOW THE PROPOSED DEVELOPMENT WILL AFFECT THE
 TRAFFIC VOLUME AND SURROUNDING LOCAL ROADWAYS. INCLUDE
 TRAFFIC ACCIDENT DATA FOR AFFECTED STREET CORRIDORS.
 ESTIMATE INCREASED OR DECREASED POTENTIAL. SAFETY
 IMPROVEMENTS SHALL BE RECOMMENDED WHERE NECESSARY;
  
 3. CONSENT OF ADJOINING PROPERTY IS REQUIRED FOR
 DRAINAGE;
  
 4. SEE COMMENTS ON DRAINAGE FROM CITY'S STORMWATER
 ENGINEER;
  
 5. SOLID WASTE YARDAGE CALCULATION WILL NEED TO BE
 SUBMITTED AS PART OF THE FINAL DESIGN TO VERIFY THAT
 THE DESIGN INCLUDES APPROPRIATE NUMBER AND SIZE OF
 DUMPSTERS/GARBAGE RECEPTACLES. PLEASE SHOW ON THE PLAN
 IF A COMPACTOR IS PROPOSED TO REDUCE THE YARDAGE OF
 WASTE THAT WILL NEED TO BE COLLECTED;
  
 6. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING
 THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE
 PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH
 DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY
 SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER
 PER SECTION 74-35(A)(5) OF THE CODE OF ORDINANCES. IF A
 ROLL-OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A LETTER
 FROM THE PRIVATE PROVIDER VERIFYING THAT THEY CAN
 PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE
 PLANS;
  
 7. WATER TO BE MASTER-METERED. SANITARY SEWER WILL
 REQUIRE A POINT OF CONNECTION AT RIGHT-OF-WAY;
  
 8. PLEASE REVISE THE LANDSCAPE PLAN TO SHOW LOCATIONS
 OF ALL WATER METERS, VALVES, CLEAN-OUTS, LIGHT POLES,
 ETC. ROOT BARRIERS MAY BE REQUIRED WHERE PLANTINGS ARE
 NEAR UNDERGROUND STORMWATER, SANITARY, OR POTABLE WATER
 LINES;
  
 9. REVISE THE NORTH ARROW ON THE PLANS.
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL:
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC
 WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL
 APPLICATION FORMS CAN BE DOWNLOADED AT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 2. CONTACT THE PALM BEACH COUNTY FOR WORK WITHIN THE
 AUSTRALIAN AVENUE RIGHT-OF-WAY TO OBTAIN A PERMIT.
 PLEASE SUBMIT A COPY OF THE PERMIT WITH THE DEVELOPMENT
 APPLICATION TO THE CITY?S ENGINEERING DEPARTMENT;
  
 3. PLEASE IDENTIFY THE SOURCE OF THE AS-BUILT
 INFORMATION UTILIZED FOR THE POTABLE WATER, SANITARY
 SEWER, AND STORM SEWER DESIGN;
  
 4. 8-FEET PATHWAY ALONG THE LAKE MANGONIA WILL BE
 REVIEWED BY THE CITY'S PUBLIC UTILITIES;
  
 5. SHOW DISTANCE TO THE CLOSEST FIRE HYDRANT ON
 AUSTRALIAN AVENUE;
  
 6. PLEASE SUBMIT THE CALCULATIONS FOR WATER AND
 SANITARY SEWER DEMANDS (AVERAGE AND PEAK); AND FIRE
 DEMAND. SUBMIT CALCULATIONS TO VALIDATE METER SIZE
 SELECTION.
  
 7. PLEASE INCLUDE APPLICABLE CITY OF WEST PALM BEACH
 STANDARD DETAILS TO THE DETAILS SHEET. CONTACT THE
 ENGINEERING SERVICES DEPARTMENT FOR THE LATEST REVISED
 DETAILS IN CAD FORMAT. CITY?S STANDARD DETAILS (IN PDF
 FILE FORMAT) CAN BE DOWNLOADED FROM THE FOLLOWING SITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
  
 8. PLACEMENT OF THE PROPOSED METER, BACKFLOW PREVENTER,
 DCDA ETC. SHALL BE INSTALLED PER THE CITY?S STANDARD
 DETAILS. REVISE THE LOCATION OF THE FIRE HYDRANT. WATER
 METER SHOULD BE INSIDE AN 'UTILITY EASEMENT' JUST
 INSIDE THE PROPERTY NEAR THE RIGHT-OF-WAY AND
 ACCESSIBLE;
  
 9. PROVIDE SOFT DIG INFORMATION FOR THE EXISTING
 UTILITIES;
  
 10. SHOW DIRECTION OF FLOW FOR THE EXISTING SANITARY
 SEWER;
  
 11. SHOW RIGHT-OF-WAY LINES (LABEL THEM) ON THE
 UTILITY/WATER AND SEWER PLANS;
  
 12. CONSTRUCT A MANHOLE WITHIN THE RIGHT-OF-WAY AS
 POINT-OF-SERVICE FOR SANITARY SEWER AND SHOW ALL
 PROPOSED ONSITE SANITARY SERVICE AS PRIVATE;
  
 13. PAVEMENT RESTORATION WILL BE REQUIRED FOR THE
 PROPOSED SANITARY SEWER CONNECTION TO THE EXISTING
 MANHOLE WITHIN THE RIGHT-OF-WAY;
  
 14. EXISTING WATER SERVICE CONNECTIONS SERVING THE
 PROPERTY, IF NOT USED, ARE TO BE CUT AND CAPPED AT THE
 MAIN. DE-ACTIVATED/INACTIVE PIPELINES LARGER THAN 2"
 DIAMETER WILL BE REMOVED. PLEASE LABEL PIPE SIZE AND
 MATERIAL AND ADD NOTES TO THE UTILITY PLANS
 ACCORDINGLY;
  
 15. ADD AN ON-LINE VALVE FOR WATER LINE;
  
 16. PROVIDE PROFILE FOR WATER AND SEWER LINES;
  
 17. PLEASE INCLUDE THE CITY OF WEST PALM BEACH STANDARD
 DETAIL FOR THE DUMPSTER ENCLOSURE ON THE PLANS. MINIMUM
 DIMENSIONAL (E.G. THE GATE WIDTH MUST BE A MINIMUM OF
 12.5 FEET) REQUIREMENTS FOR THE ENCLOSURE ARE LISTED IN
 CODE OF ORDINANCES, SECTION 94-444(B) OF THE CODE OF
 ORDINANCES. CITY STANDARD DETAIL GC-8 MAY BE DOWNLOADED
 AT:
  
 HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE
 RING-STANDARDS/
  
 18. CITY'S GARBAGE COLLECTOR TRUCK NEEDS TO HAVE NO
 LESS THAN 14' HIGH VERTICAL CLEARANCE AND 12'
 HORIZONTAL CLEARANCES FOR THE TRUCK TO DRIVE THROUGH;
  
 19. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY
 OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS
 BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES
 MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE
 LINK BELOW:
  
 HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLI
 CATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL
  
 20. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE
 WITHIN 150 FEET OF A FIRE HYDRANT. LANDSCAPE PLAN SHALL
 SHOW LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS,
 LIGHT POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE
 PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR
 POTABLE WATER LINES.
  
 MOSTAQUE KHAN, P.E.
 LAND DEVELOPMENT ENGINEER
 [email protected]
 561-494-1024 (OFFICE)
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 12-07-2016 Cont ID  
Sent By pleduc Date 12-07-2016 Time   Rev Time 0.00
Received By pleduc Date 12-07-2016 Time 17:24 Sent To  
Notes
2016-12-07 17:26:572ND REVIEW RESPONSE
  
 AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM PAUL
 GREILICH, SENIOR PLANNER, AND ATTACHMENT SOUTH EAST
 ARCHITECT SERVICES, INC., THE PREVIOUSLY SUBMITTED FIRE
 PREVENTION BUREAU COMMENTS APPEAR TO HAVE BEEN
 ADDRESSED.
  
 HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED
 PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR
 APPROVAL.
  
 THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT
 THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE
 REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
 PETER LEDUC
 FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 561-804-4709
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 10-31-2016 Cont ID  
Sent By pleduc Date 10-31-2016 Time   Rev Time 0.00
Received By pleduc Date 10-31-2016 Time 11:08 Sent To  
Notes
2016-10-31 11:52:44THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC,
 FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM
 BEACH FIRE RESCUE.
  
 THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE
 DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE.
 ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS
 ARE SUBMITTED FOR PERMIT.
  
 THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE
 PROPOSED PROJECT.
  
 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY
 WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE
 PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A
 PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED
 TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN
 STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY
 MONITORED FOR THE POTENTIAL REQUIREMENT OF FIRE
 SPRINKLER PROTECTION.
  
 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY
 IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING
 ALL CONSTRUCTION ACTIVITIES.
  
 3. THE BUILDINGS ADDRESSES SHALL BE CLEARLY VISIBLE
 FROM ALL ACCESS ROADWAYS, INCLUDING DURING
 CONSTRUCTION. ADDRESS NUMBERS SHALL CONTRAST WITH THEIR
 BACKGROUND AND SHALL NOT BE LESS THAN SIX (6) INCHES IN
 HEIGHT WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS.
  
 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE
 REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 5. THE CONSTRUCTION OF THE BUILDINGS SHALL COMPLY WITH
 THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 6. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND NFPA
 14 COMPLIANT WET STANDPIPE SYSTEM ARE REQUIRED FOR
 THESE STRUCTURES. TEMPORARY STANDPIPES ARE REQUIRED
 WHEN THE BUILDING REACHES THREE LEVELS OR THIRTY FEET
 WHILE BEING CONSTRUCTED.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
  
 7. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS
 REQUIRED FOR THESE STRUCTURES.
  
 SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED,
 REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU
 PRIOR TO ANY INSTALLATION.
  
  
 8. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7
 KEYWAY SYSTEM.
  
 ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER'S
 EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA
 B44, SAFETY CODE FOR ELEVATORS.
  
 ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN
 WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL
 LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET
 MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER
 ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN
 AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE
 IN THE HORIZONTAL POSITION.
  
  
 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL
 BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL
 DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS,
 EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A
 PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE
 SAFETY FEATURES AND EQUIPMENT.
  
  
 10. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS
 DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED
 ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF
 FIRE PREVENTION.
  
 THE PROPOSED FIRE HYDRANT LOCATIONS AND FDC'S ARE ON
 OPPOSITE SIDE OF THE TRAVEL LANE. FOR FIRE OPERATIONAL
 PURPOSES PLEASE RELOCATE THEM TO THE SAME SIDE OF THE
 TRAVEL LANE.
  
 THE PROPOSED FDC'S ARE INDICATED ON PARKING ISLANDS
 WHERE THEY CAN BE DAMAGED BY VEHICLE TRAFFIC. IT IS
 STRONGLY RECOMMENDED THAT THEY BE MOVED TO INTERIOR
 LOCATIONS BEYOND THE SIDEWALKS.
  
  
 11. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS
 BUILDING.
  
 ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS,
 PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS.
  
 ACTIVATION OF THE KNOX KEY SWITCH AT THE ENTRY POINTS
 SHALL OPEN BOTH GATES.
  
  
 12. THE CANOPY PROTECTING THE GATE ENTRY PAD PROJECTS
 INTO THE FIRE LANE
  
 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED
 VERTICAL CLEARANCE OF NOT LESS THAN 13 FT 6 IN. (4.1
 M).
  
 VERTICAL CLEARANCE SHALL BE PERMITTED TO BE REDUCED,
 PROVIDED SUCH REDUCTION DOES NOT IMPAIR ACCESS BY FIRE
 APPARATUS, AND APPROVED SIGNS ARE INSTALLED AND
 MAINTAINED INDICATING THE ESTABLISHED VERTICAL
 CLEARANCE WHEN APPROVED.
  
 PLEASE PROVIDE DETAILS OF HOW THE LOW CLEARENCE HEIGHT
 WILL BE INDICATED AND FIRE APPARATUS APPROACH WILL BE
 PROTECTED.
  
  
 13. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT
 DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL.
  
  
 14. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING
 PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH
 THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop L LANDSCAPING
Rev No 4 Status F Date 03-10-2017 Cont ID  
Sent By rcaranci Date 03-10-2017 Time 11:50 Rev Time 0.00
Received By rcaranci Date 02-27-2017 Time 11:49 Sent To  
Notes
2017-03-10 11:54:00FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: VILLAGE AT MANGONIA LAKES Z16100012
 MARCH 10, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A CHART IDENTIFYING
 EXISTING TREES ON THE PROPERTY AND INDICATE THE
 SPECIES, CANOPY SIZE, AND IF THEY WILL BE REMOVED,
 RELOCATED, OR REMAIN. INVASIVE EXOTICS ARE REQUIRED TO
 BE REMOVED PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY
 PER SECTION 94-448(F)(11).
 PLEASE PROVIDE A MITIGATION CHART FOR THE EXISTING
 TREES ON THE PROPERTY BASED ON THE TREE SURVEY.
  
 2. SATISFIED. PLEASE PROVIDE A 10 FOOT LANDSCAPE BUFFER
 ADJACENT TO AUSTRALIAN AVENUE PER SECTION 94-443(D).
 PROVIDE A 5 FOOT LANDSCAPE BUFFER ON ALL OTHER NON
 RIGHT OF WAY SIDES. INDICATE AND LABEL THE LANDSCAPE
 BUFFERS ON THE LANDSCAPE AND SITE PLAN.
  
 PLEASE INDICATE AND LABEL ALL LANDSCAPE BUFFERS WIDTHS
 ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE A COLUMN ON THE PLANT LIST
 SHOWING DROUGHT TOLERANCE LEVELS INDICATED IN
 WATERWISE, THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 PLANT AND LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN
 SECTION 94-446(G). PLEASE REVISE AND RECALCULATE TO
 CONFIRM PERCENTAGES FOR POINTS CLAIMED.
  
 4. SATISFIED. PLEASE SHOW THE TOTAL NUMBER OF PARKING
 SPACES PROVIDED ON THE SITE PLAN DATA CHART AND USE
 THIS NUMBER FOR THE CALCULATION OF LANDSCAPE AREA
 REQUIRED PER SECTION 94-443(C)(3).
 SITE PLAN SHOWS 384 SPACES, LANDSCAPE PLAN DATA SHOWS
 378. PLEASE REVISE.
  
 5. SATISFIED. PLEASE DEMONSTRATE COMPLIANCE WITH
 SECTION 94-443 (C)(4) FOR THE AMOUNT OF LANDSCAPE AREA
 REQUIRED IN THE LANDSCAPE ISLANDS PROVIDING 4 SQUARE
 FEET FOR EACH 100 SQUARE FEET OF OTHER PAVED AREAS
 ADDITIONAL TO PARKING SPACES.
 PLEASE PROVIDE A PLAN SHOWING THE LANDSCAPE AREAS
 PROVIDED WITHIN THE PARKING FIELD PER CODE TO MEET
 THESE REQUIREMENTS.
  
 6. SATISFIED. PLEASE PROVIDE A COMPREHENSIVE LIST OF
 TREES SHOWING THE QUANTITIES TO MEET THE REQUIREMENTS
 OF THE SITE AND ADDITIONAL TREES REQUIRED FOR
 MULTIFAMILY BUILDINGS PER SECTION 94-443(D)(2)A.
  
 7. SATISFIED. PLEASE PROVIDE CALCULATIONS FOR THE
 CLUBHOUSE AND 12 UNIT BUILDING SHOWING COMPLIANCE WITH
 SECTION 94-443(D)(2)B. PROVIDING 40 PERCENT OF THE
 LINEAR FEET AROUND THE BUILDING AS LANDSCAPED.
 PLEASE PROVIDE THE CALCULATIONS FOR REQUIRED AND
 PROVIDED LINEAR FEET FOR EACH BUILDING AN SHEET L-4.
  
 8. SATISFIED. PLEASE CORRECT THE APPLICATION COLUMN
 CALCULATION FOR REQUIRED SHRUBS TO 1/500 SQ FT OF
 REQUIRED OPEN SPACE.
  
 9. SATISFIED. PLEASE CORRECT THE LANDSCAPE CODE
 REQUIREMENT CHART TO REFLECT THE CORRECT NUMBER OF
 BUFFER TREES FOR EACH BUFFER SECTION, AND PROVIDE THE
 PLACEMENT OF THE BUFFER TREES EVERY 30 FEET ON THE
 LANDSCAPE PLAN ACCORDINGLY.
  
 10. SATISFIED. PLEASE PROVIDE TREES IN ALL TERMINAL
 ISLANDS IN PARKING AREAS PER SECTION 94-443 (C)(3)A.
  
 11. SATISFIED. THE MINIMUM WIDTH OF DIVIDER ISLANDS OF
 5 FOOT LANDSCAPE AREAS, AND LANDSCAPE BUFFER STRIPS
 CANNOT INCLUDE VEHICLE OVERHANG AREAS.
  
 12. WITHDRAWN. IMPROVEMENTS WITHIN THE LAKE MAINTENANCE
 AREA WILL BE EXPLORED TO INCLUDE PLANTING OF TREES.
  
 13. NOT SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL
 AND SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES. PLEASE INCREASE PLAN
 SCALE TO 1:20.
  
 14. NOT SATISFIED. PLEASE PROVIDE SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT AND UTILITIES. PROVIDE
 LANDSCAPE SCREENING AND LOCATION FOR ANY LIFT STATION.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES. PLEASE INCREASE PLAN
 SCALE TO 1:20.
  
  
 15. SATISFIED. PLEASE PROVIDE A COMPLETE HEDGE AROUND
 THE THREE NON-ACCESS SIDES OF THE DUMPSTER/COMPACTOR
 ENCLOSURE.
  
 16. WITHDRAWN. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE
 PROPOSED PARK AREA MEETING THE LANDSCAPE CODE
 REQUIREMENTS.
 ADDITIONAL COMMENTS 12/8/16:
 17. NOT SATISFIED. ADJUST LOCATIONS OF REQUIRED TREES
 NEAR DUMPSTERS, OR PROVIDE EQUIVALENT PALM SUBSTITUTE
 TO AVOID CONFLICT WITH THE FUNCTIONALITY OF THE GARBAGE
 TRUCK EMPTYING THE DUMPSTERS.
 ADDITIONAL COMMENTS 1/20/17:
 18. PLEASE PROVIDE CALCULATIONS TO SHOW EACH BUILDING
 MEETS THE REQUIREMENTS OF SECTION 94-443(D)(2)B, AT
 LEAST 40 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR
 OF ALL STRUCTURES SHALL BE PLANTED WITH TREES, SHRUBS
 OR HEDGES.
  
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 3 Status F Date 01-23-2017 Cont ID  
Sent By rcaranci Date 01-23-2017 Time 17:08 Rev Time 0.00
Received By rcaranci Date 01-23-2017 Time 17:08 Sent To  
Notes
2017-01-23 17:08:20FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: VILLAGE AT MANGONIA LAKES Z16100012
 JANUARY 20, 2017
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. SATISFIED. PLEASE PROVIDE A CHART IDENTIFYING
 EXISTING TREES ON THE PROPERTY AND INDICATE THE
 SPECIES, CANOPY SIZE, AND IF THEY WILL BE REMOVED,
 RELOCATED, OR REMAIN. INVASIVE EXOTICS ARE REQUIRED TO
 BE REMOVED PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY
 PER SECTION 94-448(F)(11).
 PLEASE PROVIDE A MITIGATION CHART FOR THE EXISTING
 TREES ON THE PROPERTY BASED ON THE TREE SURVEY.
  
 2. SATISFIED. PLEASE PROVIDE A 10 FOOT LANDSCAPE BUFFER
 ADJACENT TO AUSTRALIAN AVENUE PER SECTION 94-443(D).
 PROVIDE A 5 FOOT LANDSCAPE BUFFER ON ALL OTHER NON
 RIGHT OF WAY SIDES. INDICATE AND LABEL THE LANDSCAPE
 BUFFERS ON THE LANDSCAPE AND SITE PLAN.
  
 PLEASE INDICATE AND LABEL ALL LANDSCAPE BUFFERS WIDTHS
 ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE A COLUMN ON THE PLANT LIST
 SHOWING DROUGHT TOLERANCE LEVELS INDICATED IN
 WATERWISE, THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 PLANT AND LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN
 SECTION 94-446(G). PLEASE REVISE AND RECALCULATE TO
 CONFIRM PERCENTAGES FOR POINTS CLAIMED.
  
 4. SATISFIED. PLEASE SHOW THE TOTAL NUMBER OF PARKING
 SPACES PROVIDED ON THE SITE PLAN DATA CHART AND USE
 THIS NUMBER FOR THE CALCULATION OF LANDSCAPE AREA
 REQUIRED PER SECTION 94-443(C)(3).
 SITE PLAN SHOWS 384 SPACES, LANDSCAPE PLAN DATA SHOWS
 378. PLEASE REVISE.
  
 5. SATISFIED. PLEASE DEMONSTRATE COMPLIANCE WITH
 SECTION 94-443 (C)(4) FOR THE AMOUNT OF LANDSCAPE AREA
 REQUIRED IN THE LANDSCAPE ISLANDS PROVIDING 4 SQUARE
 FEET FOR EACH 100 SQUARE FEET OF OTHER PAVED AREAS
 ADDITIONAL TO PARKING SPACES.
 PLEASE PROVIDE A PLAN SHOWING THE LANDSCAPE AREAS
 PROVIDED WITHIN THE PARKING FIELD PER CODE TO MEET
 THESE REQUIREMENTS.
  
 6. SATISFIED. PLEASE PROVIDE A COMPREHENSIVE LIST OF
 TREES SHOWING THE QUANTITIES TO MEET THE REQUIREMENTS
 OF THE SITE AND ADDITIONAL TREES REQUIRED FOR
 MULTIFAMILY BUILDINGS PER SECTION 94-443(D)(2)A.
  
 7. SATISFIED. PLEASE PROVIDE CALCULATIONS FOR THE
 CLUBHOUSE AND 12 UNIT BUILDING SHOWING COMPLIANCE WITH
 SECTION 94-443(D)(2)B. PROVIDING 40 PERCENT OF THE
 LINEAR FEET AROUND THE BUILDING AS LANDSCAPED.
 PLEASE PROVIDE THE CALCULATIONS FOR REQUIRED AND
 PROVIDED LINEAR FEET FOR EACH BUILDING AN SHEET L-4.
  
 8. SATISFIED. PLEASE CORRECT THE APPLICATION COLUMN
 CALCULATION FOR REQUIRED SHRUBS TO 1/500 SQ FT OF
 REQUIRED OPEN SPACE.
  
 9. SATISFIED. PLEASE CORRECT THE LANDSCAPE CODE
 REQUIREMENT CHART TO REFLECT THE CORRECT NUMBER OF
 BUFFER TREES FOR EACH BUFFER SECTION, AND PROVIDE THE
 PLACEMENT OF THE BUFFER TREES EVERY 30 FEET ON THE
 LANDSCAPE PLAN ACCORDINGLY.
  
 10. SATISFIED. PLEASE PROVIDE TREES IN ALL TERMINAL
 ISLANDS IN PARKING AREAS PER SECTION 94-443 (C)(3)A.
  
 11. SATISFIED. THE MINIMUM WIDTH OF DIVIDER ISLANDS OF
 5 FOOT LANDSCAPE AREAS, AND LANDSCAPE BUFFER STRIPS
 CANNOT INCLUDE VEHICLE OVERHANG AREAS.
  
 12. WITHDRAWN. IMPROVEMENTS WITHIN THE LAKE MAINTENANCE
 AREA WILL BE EXPLORED TO INCLUDE PLANTING OF TREES.
  
 13. NOT SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL
 AND SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES.
  
 14. NOT SATISFIED. PLEASE PROVIDE SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT AND UTILITIES. PROVIDE
 LANDSCAPE SCREENING AND LOCATION FOR ANY LIFT STATION.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES.
  
  
 15. SATISFIED. PLEASE PROVIDE A COMPLETE HEDGE AROUND
 THE THREE NON-ACCESS SIDES OF THE DUMPSTER/COMPACTOR
 ENCLOSURE.
  
 16. WITHDRAWN. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE
 PROPOSED PARK AREA MEETING THE LANDSCAPE CODE
 REQUIREMENTS.
 ADDITIONAL COMMENTS 12/8/16:
 17. NOT SATISFIED. ADJUST LOCATIONS OF REQUIRED TREES
 NEAR DUMPSTERS, OR PROVIDE EQUIVALENT PALM SUBSTITUTE
 TO AVOID CONFLICT WITH THE FUNCTIONALITY OF THE GARBAGE
 TRUCK EMPTYING THE DUMPSTERS.
 ADDITIONAL COMMENTS 1/20/17:
 18. PLEASE PROVIDE CALCULATIONS TO SHOW EACH BUILDING
 MEETS THE REQUIREMENTS OF SECTION 94-443(D)(2)B, AT
 LEAST 40 PERCENT OF THE LINEAR FEET AROUND THE EXTERIOR
 OF ALL STRUCTURES SHALL BE PLANTED WITH TREES, SHRUBS
 OR HEDGES.
  
 PLEASE NOTE RESPONSES TO LANDSCAPE COMMENTS WERE NOT
 RECEIVED WITH THE REVIEW PACKET.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 2 Status F Date 12-08-2016 Cont ID  
Sent By rcaranci Date 12-08-2016 Time 11:37 Rev Time 0.00
Received By rcaranci Date 12-08-2016 Time 11:37 Sent To  
Notes
2016-12-08 11:38:07FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: VILLAGE AT MANGONIA LAKES Z16100012
 DECEMBER 8, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. NOT SATISFIED. PLEASE PROVIDE A CHART IDENTIFYING
 EXISTING TREES ON THE PROPERTY AND INDICATE THE
 SPECIES, CANOPY SIZE, AND IF THEY WILL BE REMOVED,
 RELOCATED, OR REMAIN. INVASIVE EXOTICS ARE REQUIRED TO
 BE REMOVED PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY
 PER SECTION 94-448(F)(11).
 PLEASE PROVIDE A MITIGATION CHART FOR THE EXISTING
 TREES ON THE PROPERTY BASED ON THE TREE SURVEY.
  
 2. NOT SATISFIED. PLEASE PROVIDE A 10 FOOT LANDSCAPE
 BUFFER ADJACENT TO AUSTRALIAN AVENUE PER SECTION
 94-443(D). PROVIDE A 5 FOOT LANDSCAPE BUFFER ON ALL
 OTHER NON RIGHT OF WAY SIDES. INDICATE AND LABEL THE
 LANDSCAPE BUFFERS ON THE LANDSCAPE AND SITE PLAN.
  
 PLEASE INDICATE AND LABEL ALL LANDSCAPE BUFFERS WIDTHS
 ON THE LANDSCAPE PLAN.
  
 3. SATISFIED. PLEASE PROVIDE A COLUMN ON THE PLANT LIST
 SHOWING DROUGHT TOLERANCE LEVELS INDICATED IN
 WATERWISE, THE SOUTH FLORIDA WATER MANAGEMENT DISTRICT
 PLANT AND LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN
 SECTION 94-446(G). PLEASE REVISE AND RECALCULATE TO
 CONFIRM PERCENTAGES FOR POINTS CLAIMED.
  
 4. NOT SATISFIED. PLEASE SHOW THE TOTAL NUMBER OF
 PARKING SPACES PROVIDED ON THE SITE PLAN DATA CHART AND
 USE THIS NUMBER FOR THE CALCULATION OF LANDSCAPE AREA
 REQUIRED PER SECTION 94-443(C)(3).
 SITE PLAN SHOWS 384 SPACES, LANDSCAPE PLAN DATA SHOWS
 378. PLEASE REVISE.
  
 5. NOT SATISFIED. PLEASE DEMONSTRATE COMPLIANCE WITH
 SECTION 94-443 (C)(4) FOR THE AMOUNT OF LANDSCAPE AREA
 REQUIRED IN THE LANDSCAPE ISLANDS PROVIDING 4 SQUARE
 FEET FOR EACH 100 SQUARE FEET OF OTHER PAVED AREAS
 ADDITIONAL TO PARKING SPACES.
 PLEASE PROVIDE A PLAN SHOWING THE LANDSCAPE AREAS
 PROVIDED WITHIN THE PARKING FIELD PER CODE TO MEET
 THESE REQUIREMENTS.
  
 6. SATISFIED. PLEASE PROVIDE A COMPREHENSIVE LIST OF
 TREES SHOWING THE QUANTITIES TO MEET THE REQUIREMENTS
 OF THE SITE AND ADDITIONAL TREES REQUIRED FOR
 MULTIFAMILY BUILDINGS PER SECTION 94-443(D)(2)A.
  
 7. NOT SATISFIED. PLEASE PROVIDE CALCULATIONS FOR THE
 CLUBHOUSE AND 12 UNIT BUILDING SHOWING COMPLIANCE WITH
 SECTION 94-443(D)(2)B. PROVIDING 40 PERCENT OF THE
 LINEAR FEET AROUND THE BUILDING AS LANDSCAPED.
 PLEASE PROVIDE THE CALCULATIONS FOR REQUIRED AND
 PROVIDED LINEAR FEET FOR EACH BUILDING AN SHEET L-4.
  
 8. SATISFIED. PLEASE CORRECT THE APPLICATION COLUMN
 CALCULATION FOR REQUIRED SHRUBS TO 1/500 SQ FT OF
 REQUIRED OPEN SPACE.
  
 9. SATISFIED. PLEASE CORRECT THE LANDSCAPE CODE
 REQUIREMENT CHART TO REFLECT THE CORRECT NUMBER OF
 BUFFER TREES FOR EACH BUFFER SECTION, AND PROVIDE THE
 PLACEMENT OF THE BUFFER TREES EVERY 30 FEET ON THE
 LANDSCAPE PLAN ACCORDINGLY.
  
 10. SATISFIED. PLEASE PROVIDE TREES IN ALL TERMINAL
 ISLANDS IN PARKING AREAS PER SECTION 94-443 (C)(3)A.
  
 11. SATISFIED. THE MINIMUM WIDTH OF DIVIDER ISLANDS OF
 5 FOOT LANDSCAPE AREAS, AND LANDSCAPE BUFFER STRIPS
 CANNOT INCLUDE VEHICLE OVERHANG AREAS.
  
 12. WITHDRAWN. IMPROVEMENTS WITHIN THE LAKE MAINTENANCE
 AREA WILL BE EXPLORED TO INCLUDE PLANTING OF TREES.
  
 13. NOT SATISFIED. PLEASE INCLUDE A ROOT BARRIER DETAIL
 AND SHOW LOCATIONS OF ROOT BARRIERS TO PROTECT
 INFRASTRUCTURE AND TREES FROM CONFLICTS. THIS INCLUDES
 WATER, SEWER, DRAINAGE, SIDEWALKS AND CURBS, AND ANY
 FIELD STRUCTURES THAT COULD BE IMPACTED BY TREE ROOTS.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES.
  
 14. NOT SATISFIED. PLEASE PROVIDE SCREENING FOR ALL
 GROUND MOUNTED EQUIPMENT AND UTILITIES. PROVIDE
 LANDSCAPE SCREENING AND LOCATION FOR ANY LIFT STATION.
  
 PLEASE SHOW ALL UTILITIES INCLUDING WATER, SEWER, AND
 FPL TRANSFORMERS ON THE LANDSCAPE PLAN. ADJUST UTILITY
 LOCATIONS TO AVOID REQUIRED TREES.
  
  
 15. SATISFIED. PLEASE PROVIDE A COMPLETE HEDGE AROUND
 THE THREE NON-ACCESS SIDES OF THE DUMPSTER/COMPACTOR
 ENCLOSURE.
  
 16. WITHDRAWN. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE
 PROPOSED PARK AREA MEETING THE LANDSCAPE CODE
 REQUIREMENTS.
 ADDITIONAL COMMENTS 12/8/16:
 17. ADJUST LOCATIONS OF REQUIRED TREES NEAR DUMPSTERS,
 OR PROVIDE EQUIVALENT PALM SUBSTITUTE TO AVOID CONFLICT
 WITH THE FUNCTIONALITY OF THE GARBAGE TRUCK EMPTYING
 THE DUMPSTERS.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop L LANDSCAPING
Rev No 1 Status F Date 11-07-2016 Cont ID  
Sent By rcaranci Date 11-07-2016 Time 12:49 Rev Time 0.00
Received By rcaranci Date 11-07-2016 Time 12:49 Sent To  
Notes
2016-11-07 12:49:59FROM: RAY CARANCI, LANDSCAPE PLANNER
 PROJECT: VILLAGE AT MANGONIA LAKES Z16100012
 NOVEMBER 7, 2016
 I HAVE REVIEWED THE ABOVE REFERENCED PETITION, AND
 PROVIDE THE FOLLOWING COMMENTS:
  
 1. PLEASE PROVIDE A CHART IDENTIFYING EXISTING TREES ON
 THE PROPERTY AND INDICATE THE SPECIES, CANOPY SIZE, AND
 IF THEY WILL BE REMOVED, RELOCATED, OR REMAIN. INVASIVE
 EXOTICS ARE REQUIRED TO BE REMOVED PRIOR TO THE FIRST
 CERTIFICATE OF OCCUPANCY PER SECTION 94-448(F)(11).
  
 2. PLEASE PROVIDE A 10 FOOT LANDSCAPE BUFFER ADJACENT
 TO AUSTRALIAN AVENUE PER SECTION 94-443(D). PROVIDE A 5
 FOOT LANDSCAPE BUFFER ON ALL OTHER NON RIGHT OF WAY
 SIDES. INDICATE AND LABEL THE LANDSCAPE BUFFERS ON THE
 LANDSCAPE AND SITE PLAN.
  
 3. PLEASE PROVIDE A COLUMN ON THE PLANT LIST SHOWING
 DROUGHT TOLERANCE LEVELS INDICATED IN WATERWISE, THE
 SOUTH FLORIDA WATER MANAGEMENT DISTRICT PLANT AND
 LANDSCAPE PRACTICES GUIDE AS SPECIFIED IN SECTION
 94-446(G). PLEASE REVISE AND RECALCULATE TO CONFIRM
 PERCENTAGES FOR POINTS CLAIMED.
  
 4. PLEASE SHOW THE TOTAL NUMBER OF PARKING SPACES
 PROVIDED ON THE SITE PLAN DATA CHART AND USE THIS
 NUMBER FOR THE CALCULATION OF LANDSCAPE AREA REQUIRED
 PER SECTION 94-443(C)(3).
  
 5. PLEASE DEMONSTRATE COMPLIANCE WITH SECTION 94-443
 (C)(4) FOR THE AMOUNT OF LANDSCAPE AREA REQUIRED IN THE
 LANDSCAPE ISLANDS PROVIDING 4 SQUARE FEET FOR EACH 100
 SQUARE FEET OF OTHER PAVED AREAS ADDITIONAL TO PARKING
 SPACES.
  
 6. PLEASE PROVIDE A COMPREHENSIVE LIST OF TREES SHOWING
 THE QUANTITIES TO MEET THE REQUIREMENTS OF THE SITE AND
 ADDITIONAL TREES REQUIRED FOR MULTIFAMILY BUILDINGS PER
 SECTION 94-443(D)(2)A.
  
 7. PLEASE PROVIDE CALCULATIONS FOR THE CLUBHOUSE AND 12
 UNIT BUILDING SHOWING COMPLIANCE WITH SECTION
 94-443(D)(2)B. PROVIDING 40 PERCENT OF THE LINEAR FEET
 AROUND THE BUILDING AS LANDSCAPED.
  
 8. PLEASE CORRECT THE APPLICATION COLUMN CALCULATION
 FOR REQUIRED SHRUBS TO 1/500 SQ FT OF REQUIRED OPEN
 SPACE.
 9. PLEASE CORRECT THE LANDSCAPE CODE REQUIREMENT CHART
 TO REFLECT THE CORRECT NUMBER OF BUFFER TREES FOR EACH
 BUFFER SECTION, AND PROVIDE THE PLACEMENT OF THE BUFFER
 TREES EVERY 30 FEET ON THE LANDSCAPE PLAN ACCORDINGLY.
  
 10. PLEASE PROVIDE TREES IN ALL TERMINAL ISLANDS IN
 PARKING AREAS PER SECTION 94-443 (C)(3)A.
  
 11. THE MINIMUM WIDTH OF DIVIDER ISLANDS OF 5 FOOT
 LANDSCAPE AREAS, AND LANDSCAPE BUFFER STRIPS CANNOT
 INCLUDE VEHICLE OVERHANG AREAS.
  
 12. IMPROVEMENTS WITHIN THE LAKE MAINTENANCE AREA WILL
 BE EXPLORED TO INCLUDE PLANTING OF TREES.
  
 13. PLEASE INCLUDE A ROOT BARRIER DETAIL AND SHOW
 LOCATIONS OF ROOT BARRIERS TO PROTECT INFRASTRUCTURE
 AND TREES FROM CONFLICTS. THIS INCLUDES WATER, SEWER,
 DRAINAGE, SIDEWALKS AND CURBS, AND ANY FIELD STRUCTURES
 THAT COULD BE IMPACTED BY TREE ROOTS.
  
 14. PLEASE PROVIDE SCREENING FOR ALL GROUND MOUNTED
 EQUIPMENT AND UTILITIES. PROVIDE LANDSCAPE SCREENING
 AND LOCATION FOR ANY LIFT STATION.
  
 15. PLEASE PROVIDE A COMPLETE HEDGE AROUND THE THREE
 NON-ACCESS SIDES OF THE DUMPSTER/COMPACTOR ENCLOSURE.
  
 16. PLEASE PROVIDE A LANDSCAPE PLAN FOR THE PROPOSED
 PARK AREA MEETING THE LANDSCAPE CODE REQUIREMENTS.
 CONDITIONS OF APPROVAL
 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  

Review Stop PARK PARKING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop PW PUBLIC WORKS
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop STORM STORMWATER
Rev No 1 Status F Date 11-04-2016 Cont ID  
Sent By tward Date 11-04-2016 Time 13:14 Rev Time  
Received By tward Date   Time   Sent To  
Notes
2016-11-04 13:14:11THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL
 DETAILS, DESIGN CALCULATIONS AND THE POLLUTION
 PREVENTION PLAN WILL BE REVIEWED AS PART OF THE
 ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT
 APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT
 APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP://
 WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER
 MITS-APPLICATIONS
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE
 PLAN APPROVAL:
  
 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE
 AVAILABLE AT
 HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?.
 PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS
 WILL NOT IMPACT THE PROPOSED PROJECT.
  
 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION
 INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE
 BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD
 HAZARD AREA.
  
 3. SURVEY AND ENGINEERING PLANS REFERENCE THE NORTH
 AMERICAN VERTICAL DATUM OF 1988. THE CITY?S VERTICAL
 DATUM IS NATIONAL GEODETIC VERTICAL DATUM OF 1929.
 PROVIDE ON THE SURVEY AND ENGINEERING PLANS THE
 RELATIONSHIP BETWEEN THESE TWO VERTICAL DATUMS AT THIS
 SITE.
  
 4. SITE PLAN INDICATES THE PLATTED DRAINAGE EASEMENT IS
 TO BE VACATED. INDICATE IF THE OUTFALL CONNECTION TO
 AUSTRALIAN AVENUE DRAINAGE SYSTEM WILL BE NEEDED. IF
 NOT, REMOVE CONTROL STRUCTURE AND PIPE CONNECTION TO
 THE AUSTRALIAN AVENUE DRAINAGE SYSTEM IN THE NORTHEAST
 CORNER OF THE SITE.
  
 5. THE PUBLIC UTILITIES DEPARTMENT WILL NEED TO APPROVE
 THE 5? WIDE CONCRETE WALKING PATH ALONG LAKE MANGONIA.
 PROVIDE A CROSS SECTION OF THE PATH AND INDICATE THE
 CROSS SLOPE SLOPES AWAY FROM THE LAKE.
  
 6. STATE THE NEED FOR THE 8? WIDE MAINTENANCE ACCESS
 GATES TO THE CITY?S PROPERTY AROUND THE LAKE.
  
 7. PROVIDE COPY OF AGREEMENT WITH OWNER OF PARCEL 1 TO
 DISCHARGE STORMWATER RUNOFF INTO THE LAKE ON PARCEL 1.
  
 8. INDICATE ON THE PRB DETAIL THAT THE BAFFLE SHOULD
 EXTEND A MINIMUM OF 6 INCHES BELOW THE PIPE INVERT.
 WHICH STRUCTURES WILL HAVE PRBS?
  
 9. NORTH ARROW ON ENGINEERING PLANS APPEARS TO BE
 POINTING SOUTH.
  
 10. INDICATE PAVEMENT RESTORATION AT SEWER CONNECTION
 TO EXISTING MANHOLE ON AUSTRALIAN AVE.
  
 11. AUSTRALIAN AVE. RIGHT-OF-WAY IS MAINTAINED BY PALM
 BEACH COUNTY. A COUNTY LAND DEVELOPMENT RIGHT-OF-WAY
 PERMIT MAY BE REQUIRED.
  
 12. SHOW EXISTING AND PROPOSED UTILITIES AND EASEMENTS
 ON THE LANDSCAPE PLANS.
  
 13. ARE THE PROPOSED FACILITIES SHOWN ON THE PROPERTY
 OWNED BY THE CITY PART OF THE SITE PLAN APPROVAL
 REQUEST?
  
 THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO
 ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING
 BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL.
  
 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL
 BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT.
 THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS
 CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE
 ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 2. PROVIDE ENGINEERING CALCULATIONS SIGNED AND SEALED
 BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER FOR THE
 MINIMUM REQUIRED STORM RUNOFF WATER QUALITY TREATMENT
 AND PEAK FLOOD STAGES FOR 5-YEAR 1-DAY, 25-YEAR 3-DAY
 AND 100-YEAR 3-DAY DESIGN STORMS PER SFWMD CRITERIA.
  
 3. PROVIDE A COPY OF THE SFWMD ERP MODIFICATION FOR
 THIS PROPOSED DEVELOPMENT.
  
 TRACY WARD, PE
 SENIOR STORMWATER ENGINEER
 ENGINEERING SERVICES DEPARTMENT
 561-494-1120
 [email protected]
  

Review Stop SURVEY SURVEYING
Rev No 2 Status P Date 01-09-2017 Cont ID  
Sent By vnoel Date 01-09-2017 Time 11:04 Rev Time 0.00
Received By vnoel Date   Time   Sent To  
Notes
2017-01-09 11:10:22PASSED WITH THE FOLLOWING CONDITIONS:
  
 1. APPROVAL OF SALE/LEASE OF CITY-OWNED PROPERTY.
 2. APPROVAL FROM PUBLIC UTILITIES FOR WALKWAY ALONG
 LAKE MANGONIA.

Review Stop SURVEY SURVEYING
Rev No 1 Status F Date 11-08-2016 Cont ID  
Sent By vnoel Date 11-08-2016 Time 06:55 Rev Time  
Received By vnoel Date   Time   Sent To  
Notes
2016-11-08 07:02:041. HAS USE OF CITY OWNED PROPERTY BEEN APPROVED? NEED
 AGREEMENT OR LEASE.
 2. DRAINAGE EASEMENT WILL NEED TO BE TERMINATED AND
 APPROVAL FROM PARCEL NO. 1 FOR OUTFALL INTO LAKE.
 3. WATER AND SEWER WILL NEED TO BE REDESIGNED AS A
 PRIVATE SYSTEM.
 4, SEE ENGINEERING AND STORMWATER FOR FURTHER COMMENTS.

Review Stop TRAFFIC TRAFFIC ENGINEERING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status F Date 02-16-2017 Cont ID  
Sent By   Date 02-16-2017 Time   Rev Time 0.00
Received By   Date 02-16-2017 Time   Sent To  
Notes
2017-02-16 11:14:30PAUL GREILICH SENIOR PLANNER
 561-822-1443
 [email protected]
  
  
 1.) NORTHERNMOST BUILDING NEEDS TO MEET SETBACK SET
 FORTH IN SEC. 94-77(3) (MAXIMUM BUILDING HEIGHT. THE
 MAXIMUM BUILDING HEIGHT SHALL BE THE GREATER OF 40 FEET
 OR TWO FEET IN HEIGH FOR EACH ONE FOOT IN SETBACK FROM
 SIDE AND REAR LOT LINES.)

Review Stop Z ZONING
Rev No 2 Status F Date 12-16-2016 Cont ID  
Sent By   Date 12-16-2016 Time   Rev Time 0.00
Received By pgreilic Date 12-16-2016 Time 10:59 Sent To  
Notes
2016-12-16 10:59:06VILLAGE AT MANGONIA LAKE MANGONIA
 Z16100012
 12/15/16
  
 1.) NORTHERNMOST BUILDING NEEDS TO MEET SETBACK SET
 FORTH IN 94-77(3) (MAXIMUM BUILDING HEIGHT. THE MAXIMUM
 BUILDING HEIGHT SHALL BE THE GREATER OF 40 FEET OR TWO
 FEET IN HEIGHT FOR EACH ONE FOOT IN SETBACK FROM SIDE
 AND REAR LOT LINES.)
  
 2.) PROVIDE REQUIRED UTILITY LETTERS INDICATING
 PROPOSED DEVELOPMENT DOES NOT INTERFERE WITH SERVICE
  
 3.) CONSIDER REMOVING 2 PARKING SPACES NEAREST TO THE
 PROPOSED FOUNTAIN AND ADDING ADDITIONAL LANDSCAPING
  
 4.) SHOW PROPOSED LOCATION(S) OF ART IN PUBLIC PLACES
  
 5.) A NORTHBOUND LEFT TURN LANE WITH A MINIMUM 280 FEET
 STORAGE LENGTH PLUS 50 FEET TAPER SHALL BE CONSTRUCTED
 CONCURRENTLY WITH THE DEVELOPMENT AT THE PROJECT
 DRIVEWAY ON N. AUSTRALIAN AVENUE
  
  
 PAUL GREILICH, SENIOR PLANNER
 (561)-822-1443
 [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status F Date 11-07-2016 Cont ID  
Sent By   Date 11-07-2016 Time   Rev Time 0.00
Received By pgreilic Date 11-07-2016 Time 16:08 Sent To  
Notes
2016-11-07 16:09:00VILLAGE AT MANGONIA LAKE MAJOR PD AMENDMENT (Z16100012)
 2101 N. AUSTRALIAN AVE
 NOVEMBER 7, 2016
 PAUL GREILICH, SENIOR PLANNER
  
  
 1. A PEDESTRIAN ACCESS EASEMENT SHALL BE RECORDED PRIOR
 TO THE ISSUANCE OF ANY BUILDING PERMIT TO ENSURE THAT
 THE SIDEWALK CONNECTION BETWEEN AUSTRALIAN AVENUE AND
 THE LAKE PATH ALONG LAKE MANGONIA SHALL REMAIN OPEN TO
 THE GENERAL PUBLIC FROM DAWN UNTIL DUSK
  
 2. AN 8-FOOT WIDE LAKE PATH SHALL BE SHOWN ON THE PLANS
 AND CONSTRUCTED PRIOR TO THE ISSUANCE OF ANY BUILDING
 PERMIT
  
 3. PARKING WAIVER SUBJECT TO ADDITIONAL REQUIREMENTS;
 APPLICANT HAS MET 2 OF THE 3 REQUIREMENTS FOR A PARKING
 WAIVER (SEC. 94-207(13))
  
 4. PROVIDE PEDESTRIAN CONNECTIONS FROM PARKING SPACES
 FRONTING AUSTRALIAN AVE TO APARTMENT BUILDINGS
  
 5. ENHANCE INTERNAL PEDESTRIAN CIRCULATION AND
 CONNECTIVITY THROUGHOUT THE SITE. CONSIDER AN IMPROVED
 DESIGN THAT BETTER INTEGRATES PARKING AREAS, GREEN
 SPACE, PEDESTRIAN PATHS, AND APARTMENT BUILDINGS
  
 6. RELOCATE HANDICAP SPACES TO MINIMIZE DISTANCE TO
 BUILDING ENTRANCES
  
 7. PROVIDE REQUIRED TRAFFIC LETTER FROM THE PALM BEACH
 COUNTY TRAFFIC DIVISION (SEE DEVELOPMENT APPLICATION)
  
 8. PROVIDE REQUIRED PUBLIC UTILITY LETTERS CONFIRMING
 THAT THE PROPOSED PROJECT DOES NOT ENCROACH INTO THEIR
 EASEMENTS OR OTHERWISE INTERFERE WITH THE PROVISIONS OF
 THEIR SERVICES (SEE DEVELOPMENT APPLICATION)
  
 9. REMOVE ALL AUSTRALIAN PINES ON SITE AND REPLACE WITH
 NON-INVASIVE NON-EXOTIC SPECIES
  
 10. WITHIN 24 MONTHS FOLLOWING THE ISSUANCE OF THE LAST
 CERTIFICATE OF OCCUPANCY, IF A TRAFFIC WARRANT STUDY
 DETERMINES THAT A TRAFFIC LIGHT IS WARRANTED AT THE
 INTERSECTION OF AUSTRALIAN AVENUE AND THE PRIMARY
 INGRESS/EGRESS LOCATION FOR REDEMPTIVE LIFE, SUCH A
 LIGHT SHALL BE INSTALLED AT THE EXPENSE OF THE
 DEVELOPER
  
 11. PROVIDE LARGER SCALE LOCATION MAP WITH NORTH ARROW
 AND INCLUDE SURROUNDING STREET NAMES, LABEL SITE AREA
  
 12. SHOW PROPERTY LINE AS BOLDER/MORE DISCERNABLE LINE
 (SP-1, SP-1.1)
  
 13. MEET MINIMUM DIMENSIONS OF DUMPSTERS (SEC. 94-444)
  
 14. PROVIDE ACCURATE DUMPSTER DETAIL (SEC. 94-444)
  
 15. LABEL ALL BUILDING OVERHANGS/AWNINGS
  
 16. MAXIMUM SIGN AREA LIMITED TO 48 SQUARE FEET (SEC.
 94-407)
  
 17. MINIMUM SIGN SETBACK IS 15 FT. FROM PUBLIC
 RIGHTS-OF-WAY IF PLACED PARALLEL TO THE STREET AND 20
 FT. IF ONE OF MORE SIGN FACES NOT PLACED PARALLEL TO
 THE STREET (SEC. 94-407)
  
 18. SHOW VISIBILITY TRIANGLES (SEC. 94-207(6))
  
 19. LABEL PROPOSED RETENTION AREA ON SITE PLAN(S)
  
  
 - PLEASE PROVIDE RESPONSES TO REVIEW COMMENTS IN
 WRITTEN FORMAT.
  
 - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN
 (11) PAPER COPIES AND AN ELECTRONIC COPY IN .PNG/.PDF
 FORMAT OF ALL PLANS. PLEASE NOTE THAT CHANGES ON THE
 RESUBMITTED PLANS OR THE SUBMITTAL OF INFORMATION/PLANS
 TO ADDRESS THE COMMENTS MAY RESULT IN ADDITIONAL
 COMMENTS.
  
 - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND
 SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY,
 NOVEMBER 25, 2016 TO BE ELIGIBLE TO BE SCHEDULED FOR
 THE JANUARY 18, 2017 PLANNING BOARD MEETING.
  
 - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT
 RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS
 FROM THE PPRC MEETING (BY 1/9/17), THE CASE SHALL BE
 CONSIDERED WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE
 A NEW DEVELOPMENT APPLICATION.
  
 - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1)
 RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED
 COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE
 APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE
 WILL BE 20% OF THE ORIGINAL APPLICATION FEE ($600).
  
 - CONTACT PAUL GREILICH @ 561-822-1443 OR
 [email protected]
  