Plan Review Details - Project Z16090010
| Plan Review Stops For Project Z16090010 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
10-12-2016 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
10-12-2016 |
Time |
09:54 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
10-12-2016 |
Time |
09:54 |
Sent To |
|
|
| Notes |
| 2016-10-12 09:57:03 | DEVELOPMENT SERVICES DEPARTMENT, BUILDING DIVISION, | | | COMMENTS: | | | | | | 1. THIS REVIEW IS A CURSORY REVIEW AS IT RELATES TO THE | | | SITE. IT IS NOT A REVIEW FOR FULL COMPLIANCE WITH | | | FLORIDA BUILDING CODE. THE FOLLOWING COMMENTS ARE TO BE | | | ADDRESSED FOR PERMITTING. | | | | | | 2. WHEN SUBMITTED FOR BUILDING PERMIT, THE PLANS SHALL | | | SHOW THAT THE TYPE OF CONSTRUCTION FOR THE BUILDINGS | | | WILL BE IN ACCORDANCE WITH THE HEIGHT, AREA AND | | | OCCUPANCY LIMITATIONS IN CHAPTER 5 OF THE FLORIDA | | | BUILDING CODE | | | | | | 3. WHEN SUBMITTED FOR BUILDING PERMIT, COMPLIANCE WITH | | | ALL BUILDING SEPARATION, PERCENTAGE OF OPENINGS AND | | | OPENING PROTECTIVE REQUIREMENTS OF CHAPTERS 6 AND 7 OF | | | THE FLORIDA BUILDING CODE SHALL BE VERIFIED. | | | | | | 4. SEPARATE PERMITS REQUIRED. ALL APPLICABLE PERMITS | | | AND SUB-PERMITS MUST BE OBTAINED BEFORE COMMENCING THE | | | WORK. SEPARATE PERMITS, PLANS AND FEES, ARE REQUIRED | | | FOR SIGNS, SWIMMING POOLS AND SPAS, GAS SYSTEMS, | | | GENERATORS, FIRE ALARM SYSTEMS, FIRE SPRINKLER AND | | | OTHER FIRE SUPPRESSION SYSTEMS, GREASE INTERCEPTORS, | | | SITE LIGHTING, SITE LANDSCAPE, SITE IRRIGATION, ETC. | | | | | | 5. THIS PROJECT WILL BE SUBJECT TO ART IN PUBLIC PLACES | | | (AIPP) ASSESSMENT. FOR ADVICE ON THE PROVISION OF | | | PUBLIC ARTWORK IN LIEU OF THE AIPP ASSESSMENT, CONTACT | | | SYBILLE WELTER, ART IN PUBLIC PLACES COORDINATOR, AT | | | (561) 822-1521, OR BY EMAIL: [email protected] | | | | | | ROBERT BROWN | | | BUILDING OFFICIAL | | | TEL: 561 805 6652 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
2 |
Status |
P |
Date |
11-22-2016 |
|
|
Cont ID |
|
| Sent By |
mkhan |
Date |
11-22-2016 |
Time |
14:19 |
Rev Time |
1.00 |
| Received By |
mkhan |
Date |
11-22-2016 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2016-11-22 14:49:40 | 2ND REVIEW RESPONSE: PASSED WITH CONDITION | | | DATE: 11/22/2016: | | | | | | PROJECT NAME: 45TH STREET HOTEL | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM HEATHER | | | TRIBOU, PLANNER, AND ATTACHMENT DATED OCTOBER 28, 2016, | | | FROM JON E. SCHMIDT AND ASSOCIATES, SOME OF THE | | | PREVIOUSLY SUBMITTED COMMENTS APPEAR TO HAVE BEEN | | | ACKNOWLEDGED I.E. THEY ARE EXPECTED TO BE ADDRESSED | | | DURING ?ENGINEERING DEVELOPMENT APPLICATION? SUBMITTAL. | | | HOWEVER, WE HAVE FURTHER COMMENT TO THE RESPONSE | | | PROVIDED IN THAT MEMO FOR ITEM NO. 9 (REGARDING | | | SANITARY SEWER CONNECTION) WHICH WILL HAVE TO BE | | | CONSIDERED PRIOR TO ISSUANCE OF CONSTRUCTION | | | AUTHORIZATION INCLUDING BUILDING PERMITS AND | | | ENGINEERING DEVELOPMENT APPROVAL: | | | | | | 9. THE CITY IS REVIEWING THE NEED TO UPSIZE THE 6-INCH | | | SEWER LATERAL THAT'S CITY-OWNED AND MAINTAINED WITHIN | | | THE NORTHPOINT PARKWAY R/W. THE 6-INCH PIPE WILL BE A | | | SEWER MAIN AS IT WILL BE RECEIVING FLOWS FROM BOTH | | | HARLEY DAVIDSON AND THE PROPOSED 160-ROOM HOTEL. | | | IMPROVEMENTS TO THE SEWER LATERAL, IF NEEDED AS | | | DETERMINED BY THE CITY, WILL BE ADDRESSED AS PART OF | | | THE ENGINEERING DEVELOPMENT SUBMITTAL. | | | | | | ENGINEERING DEPARTMENT CONTACT: | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1024 (OFFICE) | | | |
|
|
| Review Stop |
ENG - PPRC |
ENGINEERING - PPRC |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
10-11-2016 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
10-11-2016 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-10-11 12:36:06 | CITY OF WEST PALM BEACH | | | PUBLIC WORKS DEPARTMENT | | | ENGINEERING DIVISION | | | | | | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING DIVISION OF THE PUBLIC | | | WORKS DEPARTMENT. THE ENGINEERING DEVELOPMENT APPROVAL | | | APPLICATION FORMS CAN BE DOWNLOADED AT: HTTP://WPB.ORG/ | | | DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PERMITS-APP | | | LICATIONS | | | | | | 2. PLEASE SUBMIT THE CALCULATIONS FOR WATER AND | | | SANITARY SEWER DEMANDS (AVERAGE AND PEAK); AND FIRE | | | DEMAND. SUBMIT CALCULATIONS TO VALIDATE METER SIZE | | | SELECTION. | | | | | | 3. AFTER NEW WATER AND SEWER SERVICES ARE ACTIVATED, | | | EXISTING WATER AND SEWER SERVICE CONNECTIONS SERVING | | | THE PROPERTY, IF NOT USED, ARE TO BE CUT AND CAPPED AT | | | THE MAIN. PLEASE ADD NOTES ON THE UTILITY PLAN | | | ACCORDINGLY. | | | | | | 4. PLEASE INCLUDE APPLICABLE CITY OF WEST PALM BEACH | | | STANDARD WATER AND SEWER DETAILS TO THE DETAILS SHEET. | | | CONTACT THE ENGINEERING SERVICES DEPARTMENT (561) | | | 494-1040 FOR THE LATEST REVISED DETAILS. | | | | | | 5. PLEASE PROVIDE THE DETAILS TO SHOW HOW THE PROPOSED | | | 5-FEET CONCRETE SIDEWALK WILL BE TYING INTO THE | | | EXISTING SIDEWALK WITHIN THE RIGHT-OF-WAY TO MEET THE | | | CITY?S ENGINEERING DESIGN STANDARDS. | | | HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGINEE | | | RING-STANDARDS/ | | | | | | 6. PLEASE INCLUDE THE CITY OF WEST PALM BEACH STANDARD | | | DETAIL FOR THE DUMPSTER ENCLOSURE ON THE PLANS. MINIMUM | | | DIMENSIONAL (E.G. THE GATE WIDTH MUST BE A MINIMUM OF | | | 12.5 FEET) REQUIREMENTS FOR THE ENCLOSURE ARE LISTED IN | | | CODE OF ORDINANCES, SECTION 94-444(B) OF THE CODE OF | | | ORDINANCES. CITY STANDARD DETAIL GC-8 MAY BE DOWNLOADED | | | AT HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SERVICES/ENGI | | | NEERING-STANDARDS/ | | | | | | | | | 7. PLEASE PROVIDE AN AUTOTURN ANALYSIS DEMONSTRATING | | | THE SOLID WASTE COLLECTION VEHICLE CAN ACCESS THE | | | PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. THE TRASH | | | DUMPSTER/COMPACTORS MUST LOCATED IN AREAS EASILY | | | SERVICED BY THE CITY SANITATION EQUIPMENT AND MANPOWER | | | PER SECTION 74-35(A) (5) OF THE CODE OF ORDINANCES. IF | | | A ROLL?OFF COMPACTOR IS PROPOSED, PLEASE PROVIDE A | | | LETTER FROM THE PRIVATE PROVIDER VERIFYING THAT THEY | | | CAN PROVIDE SERVICE WITH THE CONFIGURATION SHOWN ON THE | | | PLANS. | | | | | | 8. ?CONCEPTUAL PAVING, DRAINAGE, WATER AND WASTEWATER | | | PLAN? SHEET 1 OF 1 SHOWS A PROPOSED 8-INCH WATER LINE | | | CONNECTION TO AN EXISTING 8-INCH LINE WHICH IS A | | | PRIVATE WATER LINE. PROPOSED WATER CONNECTION SHALL BE | | | MADE TO THE EXISTING 12-INCH WATER MAIN ON 45TH STREET. | | | | | | 9. ?CONCEPTUAL PAVING, DRAINAGE, WATER AND WASTEWATER | | | PLAN? SHEET 1 OF 1 SHOWS AN EXISTING 6-INCH SANITARY | | | SEWER WITHIN THE 12-FEET UTILITY EASEMENT. THIS LINE | | | NEED TO BE UPSIZED TO 8-INCH MINIMUM DIAMETER PRIOR TO | | | CONNECTING THE PROPOSED SANITARY SEWER TO THIS. | | | | | | 10. PLEASE NOTE THAT: AS OF DECEMBER 20, 2015 THE CITY | | | OF WEST PALM BEACH CROSS-CONNECTION CONTROL MANUAL HAS | | | BEEN REVISED, MAKING KNOWN THAT "ALL BACKFLOW DEVICES | | | MUST BE LEAD FREE." FOR MORE INFORMATION REFER TO THE | | | LINK BELOW: HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES | | | /FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-M | | | ANUAL | | | | | | 11. THE PROPOSED FIRE DEPARTMENT CONNECTION SHALL BE | | | WITHIN 150 FEET OF A FIRE HYDRANT. LANDSCAPE PLAN SHALL | | | SHOW LOCATIONS OF ALL WATER METERS, VALVES, CLEAN-OUTS, | | | LIGHT POLES, ETC. ROOT BARRIERS MAY BE REQUIRED WHERE | | | PLANTINGS ARE NEAR UNDERGROUND STORMWATER, SANITARY, OR | | | POTABLE WATER LINES. | | | | | | | | | MOSTAQUE KHAN, P.E. | | | LAND DEVELOPMENT ENGINEER | | | [email protected] | | | 561-494-1024 (OFFICE) | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
11-07-2016 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
11-07-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
11-07-2016 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2016-11-07 16:45:27 | 2ND REVIEW RESPONSE | | | | | | AFTER A REVIEW OF THE PPRC RESPONSE MEMO FROM HEATHER | | | TRIBOU, PLANNER, AND ATTACHMENT DATED OCTOBER 28, 2016, | | | FROM JON E. SCHMIDT AND ASSOCIATES, THE PREVIOUSLY | | | SUBMITTED FIRE PREVENTION BUREAU COMMENTS APPEAR TO | | | HAVE BEEN ADDRESSED. | | | | | | HOWEVER, THE BUREAU'S APPROVAL OF THIS SUBMITTED | | | PROJECT DOES NOT CONSTITUTE ITS FINAL REVIEW OR | | | APPROVAL. | | | | | | THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING PLANS AT | | | THE APPROPRIATE TIME AND IN ACCORDANCE WITH THE | | | REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | 561-804-4709 | | | [email protected] | | | 69A-60.0081 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
10-05-2016 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
10-05-2016 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
10-05-2016 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2016-10-05 13:54:39 | THE FOLLOWING COMMENTS WERE SUBMITTED BY PETER LEDUC, | | | FIRE MARSHAL, BUREAU OF FIRE PREVENTION, WEST PALM | | | BEACH FIRE RESCUE. | | | | | | THIS REVIEW CAN ONLY BE CONSIDERED PRELIMINARY AS THE | | | DRAWINGS THAT WERE REVIEWED WERE NOT COMPLETE. | | | ADDITIONAL COMMENTS CAN BE EXPECTED WHEN FULL DRAWINGS | | | ARE SUBMITTED FOR PERMIT. | | | | | | THE FIRE PREVENTION BUREAU HAS NO OBJECTIONS TO THE | | | PROPOSED PROJECT. | | | | | | 1. CONSTRUCTION, DEMOLITION, AND RENOVATION TO COMPLY | | | WITH NFPA 241. EXTRA ATTENTION SHALL BE GIVEN TO THE | | | PERMITTING AND LOCATION OF CONSTRUCTION TRAILERS. A | | | PERMIT IS REQUIRED FOR ANY CONSTRUCTION TRAILER RELATED | | | TO THIS PROJECT. SEPARATION DISTANCES FROM MAIN | | | STRUCTURES AS WELL AS OTHER TRAILERS SHALL BE CLOSELY | | | MONITORED FOR THE REQUIREMENTS OF FIRE SPRINKLER | | | PROTECTION. | | | | | | 2. SITE ACCESS AND EXIT POINTS ARE TO BE CLEARLY | | | IDENTIFIED AND MAINTAINED FOR EMERGENCY VEHICLES DURING | | | ALL CONSTRUCTION ACTIVITIES. | | | | | | 3. THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM | | | ALL ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. | | | ADDRESS NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND | | | AND SHALL NOT BE LESS THAN SIX (6) INCHES IN HEIGHT | | | WITH A ONE (1) INCH STROKE FOR ALL BUILDINGS. | | | | | | 4. DURING CONSTRUCTION, TRASH AND DEBRIS IS TO BE | | | REMOVED FROM THE SITE DAILY OR MORE OFTEN TO REDUCE THE | | | ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS. | | | | | | 5. THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH | | | THE 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE, | | | INCLUDING NFPA 1 & 101, SPECIFICALLY CHAPTER 28, NEW | | | HOTELS AND DORMITORIES AND ALL ASSOCIATED FIRE CODES. | | | | | | 6. A NFPA 13 COMPLIANT FIRE SPRINKLER SYSTEM AND A NFPA | | | 14 COMPLIANT STANDPIPE SYSTEM ARE REQUIRED FOR THIS | | | STRUCTURE. | | | | | | SEPARATE SHOP DRAWINGS, ARE REQUIRED TO BE SUBMITTED, | | | REVIEWED AND APPROVED BY THE FIRE PREVENTION BUREAU | | | PRIOR TO ANY INSTALLATION. | | | | | | PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004, | | | FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE | | | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF | | | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, | | | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR | | | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER | | | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) | | | AND ANY PERFORMANCE BASED INFORMATION SUCH AS | | | PRE-ENGINEERED SYSTEMS. | | | | | | FOR THE PROPOSED FIRE PUMP(S) , WHAT IS(ARE) THE | | | PRIMARY AND SECONDARY POWER SOURCES? | | | | | | 7. A NFPA 72 COMPLIANT MONITORED FIRE ALARM SYSTEM IS | | | REQUIRED FOR THIS STRUCTURE. SEPARATE SHOP DRAWINGS, | | | ARE REQUIRED TO BE SUBMITTED, REVIEWED AND APPROVED BY | | | THE FIRE PREVENTION BUREAU PRIOR TO ANY INSTALLATION. | | | | | | 8. ALL ELEVATORS SHALL BE EQUIPPED WITH A REGION 7 | | | KEYWAY SYSTEM. | | | | | | ALL NEW ELEVATORS SHALL CONFORM TO THE FIRE FIGHTER?S | | | EMERGENCY OPERATIONS REQUIREMENTS OF ASME A17.1/CSA | | | B44, SAFETY CODE FOR ELEVATORS. | | | | | | ANY BUILDING THAT IS MORE THAN THREE STORIES HIGH OR IN | | | WHICH THE VERTICAL DISTANCE BETWEEN THE BOTTOM TERMINAL | | | LANDING AND THE TOP TERMINAL LANDING EXCEEDS 25 FEET | | | MUST BE CONSTRUCTED TO CONTAIN AT LEAST ONE PASSENGER | | | ELEVATOR THAT IS OPERATIONAL AND WILL ACCOMMODATE AN | | | AMBULANCE STRETCHER 76 INCHES LONG AND 24 INCHES WIDE | | | IN THE HORIZONTAL POSITION. | | | | | | 9. COMPLETE LIFE SAFETY PLANS FOR EACH OCCUPANCY SHALL | | | BE PROVIDED THAT ILLUSTRATE OCCUPANT LOADS, TRAVEL | | | DISTANCES, COMMON PATHS OF TRAVEL, DEAD-END CORRIDORS, | | | EXIT SIGNS, EMERGENCY LIGHTING, EXITS LEADING TO A | | | PUBLIC WAY, FIRE EXTINGUISHER LOCATIONS, AND ALL FIRE | | | SAFETY FEATURES AND EQUIPMENT. | | | | | | 10. ALL EXISTING AND NEW FIRE HYDRANTS PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLEARLY INDICATED AND IDENTIFIED | | | ON THE PLAN AND CLOSELY COORDINATED WITH THE BUREAU OF | | | FIRE PREVENTION. | | | | | | ALL NEW FIRE HYDRANTS AND FDC?S PLANNED FOR THIS | | | DEVELOPMENT SHALL BE CLOSELY COORDINATED WITH THE | | | BUREAU OF FIRE PREVENTION. PROPOSED FIRE HYDRANTS AND | | | FDC?S SHOULD BE LOCATED ON THE SAME SIDE OF THE STREET | | | OR ACCESS ROADWAY TO ALLOW FREE ACCESS FOR OTHER | | | ARRIVING EMERGENCY VEHICLES. | | | | | | 11. KNOX-BOX KEY SYSTEM SHALL BE REQUIRED FOR THIS | | | BUILDING. | | | | | | ANY GATES SHALL BE PROVIDED WITH KNOX KEY ACCESS LOCKS, | | | PADLOCKS AND/OR SWITCHES FOR 24 HOUR EMERGENCY ACCESS. | | | | | | 12. THE BUREAU'S APPROVAL OF THIS SUBMITTED PROJECT | | | DOES NOT CONSTITUTE IT'S FINAL REVIEW OR APPROVAL. | | | | | | 13. THE BUREAU SHALL REVIEW ALL SUBMITTED BUILDING | | | PLANS AT THE APPROPRIATE TIME AND IN ACCORDANCE WITH | | | THE REQUIREMENTS OF ALL APPLICABLE CODES AND STANDARDS. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
P |
Date |
11-10-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
11-10-2016 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
11-10-2016 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2016-11-10 10:41:37 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 45TH STREET HOTEL Z16090010 | | | NOVEMBER 9, 2016 | | | STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS FOR THE ABOVE REFERENCED PETITION AND | | | PROVIDES THE FOLLOWING COMMENTS: | | | | | | | | | 1. SATISFIED. PLEASE PROVIDE THE DROUGHT TOLERANCE | | | LEVEL FOR EACH PLANT SPECIES ON THE PLANT LIST CHARTS | | | TO VERIFY PERCENTAGES CLAIMED WITH THE FLORIDA FRIENDLY | | | LANDSCAPE REQUIREMENTS OF SECTION 94-442 (G). | | | | | | 2. SATISFIED. PLEASE CORRECT CALCULATIONS TO SHOW | | | COMPLIANCE WITH SECTION 94-443 (C)(3) AND (4) FOR THE | | | LANDSCAPE AREAS REQUIREMENTS WITHIN THE PARKING AND | | | PAVED AREAS, INCLUDING REQUIRED NUMBER OF SHADE TREES, | | | THEN CALCULATE THE MAXIMUM NUMBER OF PALMS SUBSTITUTED | | | FOR THE REQUIRED PARKING LOT TREES. | | | | | | 3. SATISFIED. PLEASE CORRECT THE REQUIRED LANDSCAPE | | | AREA TO 20% PER SECTION 94-244 TABLE VIII-4. | | | | | | 4. SATISFIED. PLEASE CORRECT THE REQUIRED LINEAR FEET | | | OF LANDSCAPED AREA AROUND THE STRUCTURE TO 20% PER | | | SECTION 94-443 (E)(2). | | | | | | 5. SATISFIED. PLEASE CORRECT THE CANOPY TREE COUNT FOR | | | THE PARKING LOT PROVIDED TREES TO REFLECT THE COUNT OF | | | TREES WITHIN THE PARKING FIELD ONLY. | | | | | | 6. SATISFIED. PLEASE CORRECT THE REQUIRED TREES, | | | FLOWERING TREE AND SHRUB REQUIRED COUNTS IN THE CHART | | | TO REFLECT THE CALCULATION FROM 46,871 SQ. FT. OF | | | REQUIRED OPEN SPACE. | | | | | | 7. SATISFIED. PLEASE SHOW LOCATIONS OF MECHANICAL | | | EQUIPMENT SUCH AS A/C COMPRESSORS, ETC., AND PROVIDE | | | SCREENING FOR ALL GROUND MOUNTED EQUIPMENT AND | | | UTILITIES. | | | | | | 8. SATISFIED. PLEASE SHOW LOCATIONS OF WATER AND SEWER | | | LINES THAT SERVICE THE BUILDING, AND LOCATIONS OF ABOVE | | | GROUND VALVES, AND REVISE TO AVOID CONFLICTS WITH | | | LANDSCAPING. | | | | | | 9. SATISFIED. STAFF RECOMMENDS CHANGING THE ILEX | | | CASSINE TO A DIFFERENT SPECIES OR ILEX VARIETY TO AVOID | | | THE FATAL FUNGAL INFECTION SPHAEROPSIS. | | | | | | 10. SATISFIED. PLEASE ADD 2 ADDITIONAL PALMS NEAR SIGN | | | B TO MEET THE SUBSTITUTION REQUIREMENT FOR THE REQUIRED | | | SHADE TREES IN THE TERMINAL ISLAND. | | | | | | 11. SATISFIED. PLEASE CHANGE THE ILEX TO THE EAST OF | | | THE DUMPSTER ENCLOSURE TO 2 PALMS TO AVOID CONFLICT | | | WITH EMPTYING OF THE DUMPSTER. | | | | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | | | | 2. PRIOR TO THE ISSUANCE OF A LANDSCAPE PERMIT FOR THE | | | PROJECT, THE APPLICANT SHALL REVISE THE LANDSCAPE PLANS | | | TO SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH AS A/C | | | COMPRESSORS, ETC., AND PROVIDE SCREENING FOR ALL GROUND | | | MOUNTED EQUIPMENT AND UTILITIES. | | | | | | 3. PRIOR TO SCHEDULING FOR CITY COMMISSION, THE | | | APPLICANT SHALL REVISE THE LANDSCAPE PLAN TO SHOW | | | LOCATIONS OF LIGHTING PER THE PHOTOMETRIC PLAN AND | | | ADJUST TO AVOID CONFLICTS WITH TREES AND LANDSCAPING. | | | | | | 4. PRIOR TO SCHEDULING FOR CITY COMMISSION, THE | | | APPLICANT SHALL REVISE THE LANDSCAPE PLAN TO SHOW THE | | | LOCATION OF THE SIGN AND LANDSCAPING ALONG 45TH STREET | | | SO IT IS NOT IN CONFLICT WITH THE WATER SERVICE AND | | | ALSO PROVIDE ANY REQUIRED LANDSCAPE SCREENING. | | | |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
09-30-2016 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
09-30-2016 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
09-30-2016 |
Time |
14:01 |
Sent To |
|
|
| Notes |
| 2016-09-30 14:08:30 | FROM: RAY CARANCI, LANDSCAPE PLANNER 561-822-1462 | | | PROJECT: 45TH STREET HOTEL Z16090010 | | | SEPTEMBER 30, 2016 | | | STAFF HAS REVIEWED THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS FOR THE ABOVE REFERENCED PETITION AND | | | PROVIDES THE FOLLOWING COMMENTS: | | | | | | | | | 1. PLEASE PROVIDE THE DROUGHT TOLERANCE LEVEL FOR EACH | | | PLANT SPECIES ON THE PLANT LIST CHARTS TO VERIFY | | | PERCENTAGES CLAIMED WITH THE FLORIDA FRIENDLY LANDSCAPE | | | REQUIREMENTS OF SECTION 94-442 (G). | | | | | | 2. PLEASE CORRECT CALCULATIONS TO SHOW COMPLIANCE WITH | | | SECTION 94-443 (C)(3) AND (4) FOR THE LANDSCAPE AREAS | | | REQUIREMENTS WITHIN THE PARKING AND PAVED AREAS, | | | INCLUDING REQUIRED NUMBER OF SHADE TREES, THEN | | | CALCULATE THE MAXIMUM NUMBER OF PALMS SUBSTITUTED FOR | | | THE REQUIRED PARKING LOT TREES. | | | | | | 3. PLEASE CORRECT THE REQUIRED LANDSCAPE AREA TO 20% | | | PER SECTION 94-244 TABLE VIII-4. | | | | | | 4. PLEASE CORRECT THE REQUIRED LINEAR FEET OF | | | LANDSCAPED AREA AROUND THE STRUCTURE TO 20% PER SECTION | | | 94-443 (E)(2). | | | | | | 5. PLEASE CORRECT THE CANOPY TREE COUNT FOR THE PARKING | | | LOT PROVIDED TREES TO REFLECT THE COUNT OF TREES WITHIN | | | THE PARKING FIELD ONLY. | | | | | | 6. PLEASE CORRECT THE REQUIRED TREES, FLOWERING TREE | | | AND SHRUB REQUIRED COUNTS IN THE CHART TO REFLECT THE | | | CALCULATION FROM 46,871 SQ. FT. OF REQUIRED OPEN SPACE. | | | | | | 7. PLEASE SHOW LOCATIONS OF MECHANICAL EQUIPMENT SUCH | | | AS A/C COMPRESSORS, ETC., AND PROVIDE SCREENING FOR ALL | | | GROUND MOUNTED EQUIPMENT AND UTILITIES. | | | | | | 8. PLEASE SHOW LOCATIONS OF WATER AND SEWER LINES THAT | | | SERVICE THE BUILDING, AND LOCATIONS OF ABOVE GROUND | | | VALVES, AND REVISE TO AVOID CONFLICTS WITH LANDSCAPING. | | | | | | 9. STAFF RECOMMENDS CHANGING THE ILEX CASSINE TO A | | | DIFFERENT SPECIES OR ILEX VARIETY TO AVOID THE FATAL | | | FUNGAL INFECTION SPHAEROPSIS. | | | | | | 10. PLEASE ADD 2 ADDITIONAL PALMS NEAR SIGN B TO MEET | | | THE SUBSTITUTION REQUIREMENT FOR THE REQUIRED SHADE | | | TREES IN THE TERMINAL ISLAND. | | | | | | 11. PLEASE CHANGE THE ILEX TO THE EAST OF THE DUMPSTER | | | ENCLOSURE TO 2 PALMS TO AVOID CONFLICT WITH EMPTYING OF | | | THE DUMPSTER. | | | | | | PLEASE UNDERSTAND THAT ADDITIONAL INFORMATION MAY BE | | | REQUESTED, AND STAFF MAY HAVE ADDITIONAL COMMENTS AS | | | THE REVIEW PROCESS CONTINUES. | | | | | | CONDITIONS OF APPROVAL | | | 1. PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON | | | THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE | | | SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT | | | SERVICES DEPARTMENT, PLANNING DIVISION. | | | |
|
|
| Review Stop |
PARK |
PARKING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PW |
PUBLIC WORKS |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
2 |
Status |
P |
Date |
11-18-2016 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
11-18-2016 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
tward |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-11-18 11:10:16 | 1. ON THE LANDSCAPE PLANS SHOW THE STORM PIPE ENTERING | | | THE SITE FROM THE HARLEY DAVIDSON PROPERTY (NW CORNER | | | OF HOTEL SITE). | | | | | | 2. INDICATE MINIMUM CLEARANCES FROM OBSTRUCTIONS (E.G. | | | TREES) AROUND THE FIRE HYDRANTS AND FIRE DEPARTMENT | | | CONNECTION ON THE ENGINEERING PLANS.. | | | | | | 3. DRAINAGE EASEMENT TO BE REVISED TO INCLUDE NEW | | | LOCATION OF STORM PIPELINE CONVEYING FLOW FROM THE | | | HARLEY DAVIDSON SITE. | | | | | | 4. COPY OF APPROVED MODIFIED SFWMD ERP PERMIT TO BE | | | PROVIDED PRIOR TO RECEIVING CERTIFICATE OF OCCUPANCY. | | | | | | TRACY L. WARD, P.E. | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | [email protected] | | | 561-494-1120 |
|
|
| Review Stop |
STORM |
STORMWATER |
| Rev No |
1 |
Status |
F |
Date |
10-12-2016 |
|
|
Cont ID |
|
| Sent By |
tward |
Date |
10-12-2016 |
Time |
12:49 |
Rev Time |
|
| Received By |
tward |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-10-12 12:49:08 | THIS IS A CONCEPTUAL LEVEL REVIEW. CONSTRUCTION LEVEL | | | DETAILS, DESIGN CALCULATIONS AND THE POLLUTION | | | PREVENTION PLAN WILL BE REVIEWED AS PART OF THE | | | ENGINEERING DEVELOPMENT APPROVAL AND BUILDING PERMIT | | | APPLICATION PROCESSES. THE ENGINEERING DEVELOPMENT | | | APPROVAL APPLICATION FORMS CAN BE DOWNLOADED AT HTTP:// | | | WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FORMS,-PER | | | MITS-APPLICATIONS | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO SITE | | | PLAN APPROVAL: | | | 1. PRELIMINARY, UPDATED FEMA FLOOD INSURANCE MAPS ARE | | | AVAILABLE AT | | | HTTP://MAPS.CO.PALM-BEACH.FL.US/GIS/FLOODZONES.ASPX?. | | | PLEASE REVIEW THE MAPS AND VERIFY THAT THE NEW MAPS | | | WILL NOT IMPACT THE PROPOSED PROJECT. | | | | | | 2. THE CITY COMMISSION RECENTLY PASSED A RESOLUTION | | | INCREASING THE FREEBOARD REQUIREMENT TO ONE FOOT ABOVE | | | BASE FLOOD ELEVATION FOR STRUCTURES IN A SPECIAL FLOOD | | | HAZARD AREA. | | | | | | 3. SFWMD ERP PERMIT FOR THIS SITE AND HARLEY DAVIDSON | | | SITETO BE REVISED/MODIFIED FOR THIS PROJECT. EXISTING | | | PERMIT CONTAINS CONDITIONS PERTAINING TO THIS SITE AND | | | THE HARLEY DAVIDSON SITE. | | | | | | 4. STORMWATER DISCHARGE INTO THE CANAL MAY REQUIRE | | | PERMIT FROM FDOT. | | | | | | THE FOLLOWING COMMENTS MUST BE ADDRESSED PRIOR TO | | | ISSUANCE OF CONSTRUCTION AUTHORIZATION INCLUDING | | | BUILDING PERMITS AND ENGINEERING DEVELOPMENT APPROVAL. | | | | | | 1. AN ENGINEERING DEVELOPMENT APPROVAL APPLICATION WILL | | | BE REQUIRED FROM THE ENGINEERING SERVICES DEPARTMENT. | | | THE ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS | | | CAN BE DOWNLOADED AT: HTTP://WPB.ORG/DEPARTMENTS/ENGINE | | | ERING-PUBLIC-WORKS/FORMS,-PERMITS-APPLICATIONS | | | | | | TRACY WARD, PE | | | SENIOR STORMWATER ENGINEER | | | ENGINEERING SERVICES DEPARTMENT | | | 561-494-1120 | | | [email protected] | | | |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
2 |
Status |
P |
Date |
11-17-2016 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-17-2016 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SURVEY |
SURVEYING |
| Rev No |
1 |
Status |
F |
Date |
10-11-2016 |
|
|
Cont ID |
|
| Sent By |
vnoel |
Date |
10-11-2016 |
Time |
08:14 |
Rev Time |
|
| Received By |
vnoel |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-10-11 08:23:19 | 1. SITE/CIVIL PERMIT WILL BE REQUIRED THROUGH | | | ENGINEERING. | | | 2. MAY NEED TO CONNECT TO WATER MAIN IN 45TH STREET. | | | UTILITY DEPT. TO REVIEW. | | | |
|
|
| Review Stop |
TRAFFIC |
TRAFFIC ENGINEERING |
| Rev No |
1 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
|
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
11-22-2016 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
11-22-2016 |
Time |
|
Sent To |
|
|
| Notes |
| 2016-11-22 10:55:33 | CASE NUMBER: PB 1719 | | | PROJECT NAME: 45TH STREET HOTEL | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | COMMENTS | | | | | | --EASEMENTS: PROVIDE REVISED RECORDED EASEMENT PRIOR TO | | | CO. | | | | | | --PERMIT PLANS SHALL INCLUDE AND BE CONSISTENT WITH THE | | | FOLLOWING: | | | | | | --THE SITE PLAN (SP-1): PROTECT LIGHT POLES IN PARKING | | | AREA WITH CURB WITH GROUND COVER. | | | | | | --THE SITE PLAN (SP-1): SIGN ?B? DETAIL-THE 30? POLE | | | SIGN IS NOT PERMITTED IN THE INDUSTRIAL ZONING | | | DISTRICT. STAFF DOES NOT SUPPORT WAIVER. | | | | | | --THE LANDSCAPE PLAN (LP-2): LOCATE ONE OAK TREE | | | OUTSIDE OF UTILITY EASEMENT ON SOUTH SIDE OF PARKING | | | LOT. | | | | | | --THE LIGHTING PLAN: PROVIDE PEDESTRIAN SCALE BOLLARDS | | | FOR THE PEDESTRIAN PATH LEADING TO THE PUBLIC | | | RIGHT-OF-WAY. | | | | | | -- THE LIGHTING PLAN: CORRECT BIKE RACK LOCATION. | | | | | | --ENGINEERING PLANS: INDICATE MINIMUM CLEARANCE FROM | | | OBSTRUCTIONS, SPECIFICALLY TREES, AROUND FIRE HYDRANTS | | | AND FIRE DEPARTMENTS CONNECTIONS AND REFERENCE THE ROOT | | | BARRIERS ON THE LANDSCAPE PLANS. | | | | | | --ARCHITECTURAL PLANS: BUILDING SIGNAGE- ALL PROPOSED | | | BUILDINGS SIGNAGE SHALL MEET SECTION 94-408 (A)(1) OF | | | THE ZONING CODE | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
11-10-2016 |
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2016-11-10 13:58:45 | CASE NUMBER: PB 1719 | | | PROJECT NAME: 45TH STREET HOTEL | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | GENERAL COMMENTS | | | | | | - PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF NINE | | | (9) AND AN ELECTRONIC COPIES IN PDF FORMAT OF ALL | | | PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND | | | SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY, | | | OCTOBER 28, 2016, TO BE SCHEDULED FOR THE DECEMBER 20, | | | 2016 PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY | | | MONDAY DECEMBER 12, 2016), THE CASE SHALL BE CONSIDERED | | | WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW | | | DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WERE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. THE RESUBMITTAL FEE | | | IS 20% OF THE ORIGINAL APPLICATION FEE. $769.00 | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | SPECIFIC COMMENTS | | | | | | --THE LIGHTING PLAN SHALL MEET REQUIREMENT OF | | | 94-207(D)(8) AS NOT TO EXCEED ONE FOOT CANDLE AT OR | | | BEYOND THE BOUNDARIES OF DEVELOPMENT. SUBMITTED PLANS | | | EXCEED THIS REQUIREMENT ON BOTH THE NORTH AND WEST SIDE | | | OF PROPERTY. | | | | | | --THE LIGHTING PLAN AND SITE PLAN SHALL BE COORDINATED | | | TO MEET BOTH LIGHTING REQUIREMENTS AND MINIMUM PARKING | | | STALL DIMENSIONS. THE SIX LIGHT POLES PLACES IN PARKING | | | SPOTS REDUCE THE ALREADY MINIMUM SIZED PARKING SPACES. | | | PLUS, IT WOULD BE ADVISABLE TO HAVE CURB PROTECTING THE | | | POLES. | | | | | | --THE LIGHTING PLAN LUMENS STATED ON THE LIGHTING PLAN | | | USED FOR CALCULATIONS ARE LESS THAN THOSE FOUND IN THE | | | MANUFACTURES SPECIFICATIONS FOR R4, R3 AND R5. IF THE | | | MANUFACTURE SPECIFICATIONS LUMENS ARE USED THEN FOOT | | | CANDLES EXCEEDED WILL INCREASE. | | | | | | --THE LIGHTING PLAN AND THE ARCHITECTURE PLANS SHALL BE | | | COORDINATED SO THAT LIGHTS ARE NOT PLACED WHERE THE | | | OVERHANG OF THE PORTE COHERE ARE LOCATED. PEDESTRIAN | | | SCALE LIGHTING IS RECOMMENDED. | | | | | | --THE LIGHTING PLAN PROVIDES NO COVERAGE FOR THE | | | PEDESTRIAN PATH LEADING TO THE PUBLIC RIGHT-OF-WAY. | | | PEDESTRIAN SCALE BOLLARDS ARE RECOMMENDED. | | | | | | --THE SITE PLAN (SP-1): PLAN -IT APPEARS AS THE | | | DRAINAGE EASEMENT FROM THE SURVEY HAS BEEN MODIFIED FOR | | | ENTRY DRIVE. PLEASE CONFIRM. | | | | | | --THE SITE PLAN (SP-1): PLAN ?CONNECT NORTH DRIVE AISLE | | | TO CROSS ACCESS EASEMENT. LAW IS REVIEWING | | | REQUIREMENTS. | | | | | | --THE SITE PLAN (SP-1): SIGN ?B? DETAIL-THE 30? POLE | | | SIGN IS NOT PERMITTED IN THE INDUSTRIAL ZONING | | | DISTRICT. STAFF DOES NOT SUPPORT WAIVER. | | | | | | --THE SITE PLAN (SP-1): PLAN PAVING, DRAINAGE AND | | | WASTEWATER PLAN ?COORDINATE THE BIKE RACK LOCATION WITH | | | THE SITE PLAN. | | | | | | --THE SITE PLAN (SP-1)- DIMENSION OVERALL SIZE OF | | | BICYCLE RACK. | | | | | | --THE CIVIL PLAN- CORRECT BICYCLE RACK LOCATION | | | | | | --LANDSCAPE PLAN (LP-2): COORDINATE SIGN A WITH | | | LANDSCAPE. | | | | | | --ARCHITECTURAL PLANS AND/ OR SITE PLAN- BUILDING | | | SIGNAGE-DIMENSION ALL SIGNAGE AND SHOW COMPLIANCE WITH | | | SECTION 94-408 (A)(1) OF THE ZONING CODE, IF NOT ASK | | | FOR WAIVER. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
10-11-2016 |
|
|
Cont ID |
|
| Sent By |
Heather |
Date |
10-11-2016 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
10-11-2016 |
Time |
|
Sent To |
Z |
|
| Notes |
| 2016-10-11 15:37:12 | CASE NUMBER: PB 1719 | | | PROJECT NAME: 45TH STREET HOTEL | | | | | | ZONING CONTACT: HEATHER M. TRIBOU | | | (561) 822-1562 | | | [email protected] | | | | | | GENERAL COMMENTS | | | | | | - PLEASE PROVIDE RESPONSES TO ALL REVIEW COMMENTS IN | | | WRITTEN FORMAT. | | | | | | - WHEN RESUBMITTING, PLEASE PROVIDE A MINIMUM OF ELEVEN | | | (11) AND AN ELECTRONIC COPIES IN PDF FORMAT OF ALL | | | PLANS. PLEASE NOTE THAT CHANGES ON THE RESUBMITTED | | | PLANS OR THE SUBMITTAL OF INFORMATION/PLANS TO ADDRESS | | | THE COMMENTS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | - THE PPRC COMMENTS SHALL BE SUFFICIENTLY ADDRESSED AND | | | SUBMITTED TO THE PLANNING DIVISION BY 5 PM ON FRIDAY, | | | OCTOBER 28, 2016, TO BE SCHEDULED FOR THE DECEMBER 20, | | | 2016 PLANNING BOARD MEETING. | | | | | | - PLEASE NOTE THAT IF THE PLANNING DIVISION HAS NOT | | | RECEIVED A RESPONSE TO THE PPRC COMMENTS WITHIN 60 DAYS | | | FROM THE DATE OF THESE COMMENTS/THE PPRC MEETING (BY | | | MONDAY DECEMBER 12, 2016), THE CASE SHALL BE CONSIDERED | | | WITHDRAWN. ANY FURTHER ACTION SHALL REQUIRE A NEW | | | DEVELOPMENT APPLICATION. | | | | | | - PLEASE NOTE THAT YOU WILL BE PERMITTED ONE (1) | | | RESUBMITTAL AT NO ADDITIONAL COST. IF PREVIOUSLY-ISSUED | | | COMMENTS CONTINUE TO NOT BE SUFFICIENTLY ADDRESSED, THE | | | APPLICANT WILL BE ACCESSED A RESUBMITTAL FEE. SUCH FEE | | | WILL BE 20% OF THE ORIGINAL APPLICATION FEE. | | | | | | - PUBLIC HEARING NOTIFICATION SIGNAGE SHALL BE POSTED | | | IN ACCORDANCE WITH THE REQUIREMENTS OF SECTION | | | 94-39(I)(5) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. | | | | | | SPECIFIC COMMENTS | | | | | | --UPDATE ALL SHEETS TO REFLECT ANY CHANGES. | | | | | | --THE LETTER SUBMITTED BY THE PALM BEACH COUNTY TRAFFIC | | | DIVISION DOES NOT MEET COUNTY TRAFFIC PERFORMANCE | | | STANDARDS. IN ADDITION THE LETTER INDICATED A 196 ROOM | | | HOTEL. PLEASE PROVIDE PALM BEACH COUNTY TRAFFIC | | | DIVISION APPROVAL LETTER AND UPDATE SITE PLAN (SP-1) | | | SITE DATA IF NEEDED. | | | | | | --THE INTENT OF A PLANNED DEVELOPMENT DISTRICT (94-207 | | | (1)) IS TO ENCOURAGE INNOVATIVE LAND PLANNING AND | | | DEVELOPMENT TECHNIQUES TO CREATE MORE DESIRABLE AND | | | ATTRACTIVE DEVELOPMENT IN THE CITY. PLEASE INDICATE HOW | | | THE PROPOSED DEVELOPMENT MEETS THIS INTENT IN THE | | | JUSTIFICATION STATEMENT. | | | | | | --ARCHITECTURAL ELEVATIONS- THE ELEVATIONS ARE LACKING | | | PROPORTIONS TO CREATE A CLEAR BASE, MIDDLE AND TOP. | | | | | | --ARCHITECTURAL ELEVATIONS- PROVIDE CLEAR ENTRY. THE | | | WINDOWS LOCATED UNDER THE PORTE COCHERE ARE THE SAME AS | | | THE ROOM WINDOWS. | | | | | | --ARCHITECTURAL ELEVATIONS-RESOLVE RELATIONSHIP OF | | | WINDOWS AND PORTE COCHERE AT TRUSS BEAMS. | | | | | | --ARCHITECTURAL ELEVATIONS- PROVIDE DETAIL ON | | | STAIRWELLS AND IF POSSIBLE ROOF DIRECTION TO MATCH | | | ENTRY. | | | | | | --THE JUSTIFICATION LETTER (PAGE 2, SECOND PARAGRAPH) | | | INDICATES A BUFFER DETAIL IN THE LANDSCAPE PLAN THAT | | | STAFF DID NOT SEE ON THE LANDSCAPE PLANS. THE DETAIL IS | | | EXPRESSED TO ADDRESS THE RELATIONSHIP OF THE RETAINING | | | WALL THE LANDSCAPING. | | | | | | --AS REQUIRED IN SEC 94-207(D) (8) A LIGHTING PLAN | | | SHALL BE SUBMITTED MEETING THE REQUIREMENTS. | | | | | | --THE SITE PLAN (SP-1): SITE DATA- PROPOSED USE SHOULD | | | BE HOTEL (LIMITED SERVICE) | | | | | | --THE SITE PLAN (SP-1): SITE DATA- ARCHITECTURAL PLANS | | | SHOW 5 STORIES. PLEASE CONFIRM AND CORRECT APPROPRIATE | | | PLANS. | | | | | | --THE SITE PLAN (SP-1): SITE DATA- ADD PROPOSED NUMBER | | | OF ROOMS AND NUMBER OF ROOMS BY CODE AND JUSTIFY | | | WAIVER. | | | | | | --THE SITE PLAN (SP-1): BICYCLE RACK AND PARKING-SITE | | | DATA, PLAN AND DETAILS TO NOT MATCH, NOTE THAT 9 SPACES | | | ARE REQUIRED. PLEASE MEASURE BICYCLE RACK ON SITE PLAN | | | TO CONFIRM CORRECT SIZE TO MATCH DETAIL. | | | | | | -- THE SITE PLAN (SP-1): DEVELOPMENT REGULATIONS: | | | PLEASE REFERENCE CODE SECTION 94-7244- TABLE VIII-4 AND | | | UPDATE CODE REFERENCES. FOR DISCREPANCIES IN MINIMUM | | | ACREAGE OF SECTION 94-207(D) PLEASE MAKE A NOTE WITH A | | | REFERENCE TO THE WAIVER. | | | | | | -- THE SITE PLAN (SP-1): DEVELOPMENT REGULATIONS: | | | PROVIDE MAXIMUM IMPERMEABLE SURFACE CALCULATIONS. | | | | | | --THE SITE PLAN (SP-1): WAIVER CHART: COMMERCIAL | | | PLANNED DEVELOPMENT SHOULD BE INDUSTRIAL PLANNED UNIT | | | DEVELOPMENT. | | | | | | --THE SITE PLAN (SP-1): WAIVER CHART: CORRECT PROVIDED | | | ACREAGE. | | | | | | --THE SITE PLAN (SP-1): PLAN -IT APPEARS AS THE | | | DRAINAGE EASEMENT FROM THE SURVEY HAS BEEN MODIFIED FOR | | | ENTRY DRIVE. PLEASE PROVIDE REQUIRED DOCUMENTATION FOR | | | ANY CHANGES. | | | | | | --THE SITE PLAN (SP-1): PLAN -CONNECT NORTH DRIVE AISLE | | | TO CROSS ACCESS EASEMENT. | | | | | | --THE SITE PLAN (SP-1): PLAN- PROVIDE PEDESTRIAN | | | CONNECTION TO DEVELOPED PROPERTY TO THE WEST. | | | | | | --THE SITE PLAN (SP-1): PLAN -HANDICAP PARKING SPACE | | | DETAIL AND SITE PLAN DIMENSIONS DO NOT MATCH. | | | | | | --THE SITE PLAN (SP-1): PLAN -PROVIDE ONE SET OF | | | DIMENSIONS FOR ALL PARKING BAYS AND DIMENSION EACH | | | PARKING ISLAND TO MEET CODE. | | | | | | --THE SITE PLAN (SP-1): PLAN -DIMENSIONS LOCATION OF | | | ALL SIGNAGE TO MEET CODE. | | | | | | --THE SITE PLAN (SP-1): PLAN -THE LOADING SPACE IS | | | LOCATED UNDER THE PORTE COCHERE AND PROPOSED HEIGHT IS | | | ONLY 10?6? ON THE ARCHITECTURAL ELEVATIONS. PLEASE MOVE | | | LOADING SPACE OR RAISE PORTE COCHERE FOR TRUCK | | | CLEARANCES. | | | | | | --THE SITE PLAN (SP-1): SIGN "A" DETAIL-LOW | | | FREESTANDING SIGN- DIMENSION WIDTH AND SHOW COMPLIANCE | | | WITH SECTION 94-408 9A) (2). | | | | | | --THE SITE PLAN (SP-1): SIGN "B" DETAIL-THE 30' POLE | | | SIGN IS NOT PERMITTED IN THE INDUSTRIAL ZONING | | | DISTRICT. STAFF DOES NOT SUPPORT A VARIANCE OR WAIVER. | | | | | | --THE SITE PLAN (SP-1): PLAN AND PAVING, DRAINAGE AND | | | WASTEWATER PLAN -THE NORTH DRIVE AISLE MAY BE REDUCED | | | TO 20' SINCE ONLY ONE LINE OF PARKING IS LOCATED ON THE | | | DRIVE AISLE. | | | | | | --THE SITE PLAN (SP-1): PLAN PAVING, DRAINAGE AND | | | WASTEWATER PLAN -COORDINATE THE HANDICAP PARKING | | | SIGNAGE WITH THE BIKE RACK LOCATION. | | | | | | --PAVING, DRAINAGE AND WASTEWATER PLAN- IF POSSIBLE | | | SHIFT WATER LINE ON WEST OF BUILDING TO NORTH TO AVOID | | | LANDSCAPE. | | | | | | --PAVING, DRAINAGE AND WASTEWATER PLAN- SHOW DETAIL OF | | | RETAINING WALL IN RELATION TO DRAINAGE. | | | | | | --LANDSCAPE PLANS- ADD EXISTING AND PROPOSED UTILITIES | | | AND PROPOSED LIGHT POLE LOCATIONS TO ALL PLANS TO | | | CORRECT ANY DISCREPANCIES. | | | | | | --LANDSCAPE PLANS-SHOW SIGHT TRIANGLES. | | | | | | --ARCHITECTURAL PLANS- DIMENSION ALL SIGNAGE AND SHOW | | | COMPLIANCE WITH SECTION 94-408 (A)(1) OF THE ZONING | | | CODE. | | | | | | |
|
|
| |